Raychem H908 User Manual

WARNING:
CAUTION:
H908
WARNING:
CAUTION:
PLUG-IN POWER CONNECTION KIT WITH END SEAL INSTALLATION INSTRUCTIONS
DESCRIPTION
The Raychem H908 is a plug-in, ground-fault-protected power connection kit for use with WinterGard H311, WinterGard Plus H611, and WinterGard Wet H612 120 V heating cables.
This kit ensures compliance with Pentair Thermal Management, NEC and CEC requirements for ground-fault protection of equipment. It does not protect people against the hazards of shock. The kit includes materials for one power connection and end seal. All WinterGard, WinterGard Plus, and WinterGard Wet heating cables are designed for water-pipe freeze protection applications. Only the H612 heating cable can be used for both pipe freeze protection and roof and gutter de-icing applications.
For additional technical support call Pentair Thermal Management at (800) 542-8936.
TOOLS REQUIRED
• Needle nose pliers • Propane torch or heat gun
• Utility knife • Diagonal cutters
• Panduit crimp tools CT100 and CT570
APPROVALS
Pipe Heating Cable 718 K Also Listed as De-icing and Snow Melting Equipment
-ws
KIT CONTENTS
Item Qty Description
A 1 Plug-in ground-fault equipment protection device
B 2 Black cloth tapes (6 inch long x 1 inch wide)
C 1 Uninsulated braid crimp
D 2 Insulated bus wire crimps
E 2 Heat-shrinkable tubes (1 inch long x 1/8 inch dia.)
F 2 Clamp ties
G 1 Heat-shrinkable tube (8 inch long x 1 inch dia.)
H 2 Warning labels for pipe-trace applications
I 2 De-icing and snow melting equipment labels
J 2 Mastic strips
K 1 Gel-filled end seal
L 1 Heat-shrinkable tube (5 inch long x 3/4 inch dia.)
These components are electrical devices. They must be installed correctly to ensure proper operation and to prevent shock or fire. Carefully follow all of the installation instructions and read these important warnings.
• To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Pentair Thermal Management and the national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection.
• Component approvals and performance are based on the use of specified parts only. Do not substitute parts or use vinyl electrical tape.
• The black heating-cable core is conductive and can short. It must be
properly insulated and kept dry.
• Keep components and heating cable ends dry before and during installation.
• Damaged bus wires can overheat or short. Do not break braid or bus wire strands when scoring the jacket or core.
• Bus wires will short if they contact each other. Keep bus wires separated.
• Heat-damaged components can short. Use a heat gun or a torch with a soft, yellow, low-heat flame, not a blue focused flame. Keep the flame moving to avoid overheating, blistering, or charring the heat-shrinkable tubes. Avoid heating other components. Replace any damaged parts.
• Use only fire-resistant insulation materials such as fiberglass wrap.
• Leave these installation instructions with the user for future reference.
ADDITIONAL MATERIALS REQUIRED
• Grounded, UL Listed 15-amp, 120-volt receptacle (receptacle must be approved for wet locations if exposed to weather).
• Additional cable ties may be required for roof and gutter applications.
• Your application may require additional Raychem accessories; for example, H903 application tape for pipe applications; H913/H914 roof clips and/or H915 downspout hangers for roof and gutter de-icing applications.
Electric Deicing and
Electric Deicing and
on Premises
Snow Melting Equipment
on Premises
Snow Melting Equipment
WARNING
A
WARNING
Fire and Shock Hazard
Self-regulating electrical
Self-regulating electrical
Fire and Shock Hazard
heating cable attached to this pipe:
Disconnect before sevicing
heating cable attached to this pipe:
Disconnect before sevicing
B C D
E
F
G
Charring or burning the heat-shrinkable tubes in this kit will produce fumes that may cause eye, skin, nose, and throat irritation. Consult Material Safety Data Sheet RAY3122.
CHEMTREC 24-hour emergency telephone: (800) 424-9300
Non-emergency health and safety information: (800) 545-6258.
H
I
J
K
L
THERMAL BUILDING SOLUTIONS
1 / 14
H908 DESIGN AND INSTALLATION INFORMATION FOR HEATING CABLE ON PIPES ONLY
WINTERGARD H311, WINTERGARD PLUS H611, AND WINTERGARD WET H612 HEATING CABLES
Important: For the Pentair Thermal Management warranty to be
valid, you must comply with all the requirements outlined in these guidelines.
All thermal and design information provided here is based upon a “standard” installation with heating cable fastened to an insulated pipe. For any other application or method of installation, consult Pentair Thermal Management at (800) 545-6258.
HEATING CABLE SELECTION AND DESIGN
Make sure that the heating cable being used is suitable for your application. Refer to the Commercial and Residential Application and Design Guide (H53585) for heating cable application information.
1. Determine the heating cable type
Use Table 1 to select heating cables for insulated metal pipes. Use Table 2 to select heating cables for insulated plastic pipes. Read across the table to find your pipe size, then drop down to the line corresponding to the lowest air temperature for that application and the correct insulation thickness. The cell at that intersection has a particular shading and may have a number. The shading indicates which heating cable to use (key to the shading appears above the table headings). A number represents the spiraling ratio (feet of heating cable per foot of pipe).
If no number appears in the cell, straight trace the pipe. If a number does appear in the cell, spiral trace the pipe.
If your spiraling ratio is 2.0, multiple trace the pipe using two straight traces at the 4 o’clock and 8 o’clock positions.
If your spiraling ratio is 3.0, multiple trace the pipe using three straight traces at the 11 o’clock or 1 o’clock position, and at the 4 o’clock and 8 o’clock positions.
Table 1. For METAL pipes with fiberglass insulation or equivalent (based on 40°F maintain temperature)
Example 1:
Pipe size: 1 in Lowest air temp.: 0°F Insulation thickness: 1/2 in Metal pipe: Plastic pipe:
WinterGard Plus H611, H621
WinterGard Wet H612, H622
Example 2:
Pipe size: 2 1/2 in Lowest air temp.: –20°F Insulation thickness: 1/2 in Metal pipe:
1.3
WinterGard Plus H611 or
WinterGard Wet H612 (Use 1.3 feet of heating cable Plastic pipe:
per foot of pipe.)
2.0
WinterGard Plus H611 or
WinterGard Wet H612 (Use two straight traces at the 4 o’clock and 8 o’clock positions.)
WinterGard H311
Key to Table 1:
Lowest air
temp. (°F)
0
–20
–40
= H311 = H611, H612, H621, H622 = Use a thicker insulation
Insulation
thickness
1/2 in
1 in
1 1/2 in
1/2 in
1 in
1 1/2 in
2 in
1/2 in
1 in
1 1/2 in
2 in
1/2 in 6 in4 in3 in2 1/2 in2 in1 1/2 in1 1/4 in1 in3/4 in
Nominal pipe size
Table 2. For PLASTIC pipes with fiberglass insulation or equivalent (based on 40°F maintain temperature)
Key to Table 2:
Lowest air
temp. (°F)
0
–20
–40
= H311 = H611, H612 H621, H622 = Use a thicker insulation
Insulation
thickness
1/2 in
1 in
1 1/2 in
1/2 in
1 in
1 1/2 in
2 in
1/2 in
1 in
1 1/2 in
2 in
1/2 in 6 in4 in3 in2 1/2 in2 in1 1/2 in1 1/4 in1 in3/4 in
1.1
Nominal pipe size
1.41.2
2.0
1.21.1
3.03.02.01.81.51.1
1.1 1.9
1.61.41.2
3.01.81.51.31.1
1.4
3.02.01.71.41.21.1
1.31.1
3.0
1.71.41.21.1
1.31.1
1.81.3
3.01.81.51.31.1
1.51.1
1.1
1.91.41.1
1.4
1.1
3.02.01.7
1.61.2
1.2
3.01.8
1.7
1.4
3.0
1.8
THERMAL BUILDING SOLUTIONS
2 / 14
2. Calculate the total heating cable length required
Length = A + B + C + D + E + F + G + H
A Pipe length x spiraling ratio B 4 ft x # gate/globe valves x valve length (ft) x spiraling ratio C 2 ft x # ball/butterfly valves x valve length (ft) x spiraling ratio D 2 ft x # flanges x pipe diameter (ft) x spiraling ratio E 2 ft x # pipe supports v pipe diameter (ft) x spiraling ratio F 1 ft for each power connection G 2 ft for each splice connection H 3 ft for each tee connection
= Total heating cable length (ft)
3. Determine the maximum heating cable circuit length allowed.
See Table 3 on the next page. Ensure that your circuits do not exceed the maximum circuit length listed in Table 3. If necessary, use additional shorter circuits.
HEATING CABLE INSTALLATION
Example (taken from Example 2 [on metal pipe], page 3):
Pipe length: 50 ft Spiral ratio: 1.3 (from Table 1, page 3) Globe valves: 3 (each 0.5 ft long) Pipe supports: 10 supports for 1 in pipe Power connections: 1 Splice connections: 1
WinterGard heating cable required: A Pipe length x spiral ratio = 50 ft x 1.3 = 65.0 ft
B 3 globe valves (0.5 ft each) = 4 ft x 3 x 0.5 x 1.3 = 7.8 ft C 0 ball/butterfly valves = 0 = 0 D 0 flanges = 0 = 0 E 10 pipe supports = 2 ft x 10 x 0.085* x 1.3 = 2.2 ft F 1 power connection = 1 ft x 1 = 1.0 ft G 1 splice connection = 2 ft x 1 = 2.0 ft H 0 tee connection = 0 = 0
Total heating cable length required = 78.0 ft
*1 in pipe diameter / 12 in per foot = 0.085 foot
1. Prepare for installation
• Store the heating cable in a clean, dry place.
• Complete piping pressure test.
• Review the WinterGard heating cable design and compare to materials received to verify that the proper WinterGard heating cable and accessories are available. The WinterGard heating cable will have the heating cable type printed on the outer jacket.
• Walk the system and plan the routing of the WinterGard heating cable on the pipe.
2. Cut the heating cable to length
• Cut the heating cable to the length required. This can be done before or after the cable is attached to the pipe. Leave a minimum of 1 foot extra heating cable for connection to power. For splice and tee connections, leave a minimum of 1 foot for each section of heating cable. WinterGard heating cable can be cut to length without affecting its heat output per foot.
• Protect the heating cable ends from moisture or mechanical damage if they will be left exposed before connection.
3. Position and attach heating cable to pipe
• Be sure all piping to be traced is dry.
• Install heating cable, using straight tracing, spiraling, or multiple tracing according to the “Heating cable selection and design” section on page 2.
• For straight tracing, install the heating cable on a lower half of the pipe; for example, in the 4 o’clock or 8 o’clock position.
• Be sure to install the additional heating cable required for valves, flanges, etc. as indicated in Step 2 of the “Heating cable selection and design” section.
• When the design calls for spiraling, begin by suspending a loop every 10 feet as shown in Figure 1. To determine the loop length, obtain the spiral factor from Table 1 or 2 and multiply by 10. For example, if a spiral factor of 1.3 is called for, leave a 13-foot loop of heating cable at every 10-foot section of pipe. Grasp the loop in its center and wrap it around the pipe. Even out the distance between spirals by sliding the wraps along the pipe. Use glass tape to secure the center of the loop to the pipe. Secure the heating cable flat to the pipe to obtain good contact.
• Tape WinterGard heating cable to the pipe at 2-foot intervals using Raychem H903 fiberglass application tape or nylon cable ties. Do not use vinyl electrical tape, duct tape, metal bands, or wire.
4. Install heating cable end seals, splices, tees, and power connection
• Test each circuit before installing the H908 ground-fault device, according to the instructions in the “Heating cable testing and maintenance” section.
• Install all end seals, splices, tees, and power connection prior to plugging in.
• Follow the H908 kit installation instructions beginning on page 8.
• Use only weatherproof receptacles approved for wet locations when installing WinterGard Wet H612 heating cable with the H908 Power Connection Kit for Roof and Gutter De-Icing Applications.
5. Check the installation
• Prior to installing thermal insulation, make sure the heating cable is free of mechanical damage (from cuts, clamps, etc.) and thermal damage (from solder, overheating, etc.).
• Visually check all power connections, end seals, splices, and tees.
• Using a megohmmeter, test each circuit according to the instructions in the “Heating cable testing and maintenance” section (page 4) both before and after installing the thermal insulation.
10 feet
Glass tape (typical)
Heating cable
Apply glass tape before spiraling heating cable on pipe
Figure 1. Spiraled heat tracing
Pull heating cable loop length
Wrap loops in opposite direction
Tape after spiraling heating cable on pipe
3 / 14THERMAL BUILDING SOLUTIONS
6. Install thermal insulation
• A reliable heat-tracing system depends on properly installed and weather-proofed thermal insulation.
• Ensure that type and thickness of the insulation are in accordance with the information in the heating cable selection tables on page 2 and that all pipe work—including valves, joints, wall penetrations, and other elements—has been fully insulated.
• Minimize the potential for mechanical damage to the heating cable after instal lation by installing the insulation immediately.
7. Mark the installation
• Place “Warning” labels for pipe trace applications on the outer surface of the insulation at 10-foot intervals (on alternating sides of the pipe) to indicate the presence of WinterGard electric heating cable. Additional labels and application tape are contained in the H903 kit.
ELECTRICAL PROTECTION
For the maximum heating cable circuit length permitted for a given circuit breaker rating, refer to Table 3. Limit your circuit length based on your lowest anticipated start-up temperature.
The H908 kit contains a built-in 27-mA equipment-protection ground­fault device. This kit provides ground-fault protection of equipment only. It does not protect people against the hazards of electrical shock.
Do not use an extension cord. Plug the unit directly into the outlet. Note: Pentair Thermal Management, Article 427 of the NEC and
Part I, Section 62 of the CEC require ground-fault protection for pipe heating cable applications.
8. Check the installation
• Prior to powering, check to be sure the heating cable is free of mechanical damage (cuts, clamps, etc.).
• Visually check all power connections, end seals, splices, and tees for proper installation.
9. Test the ground-fault protection
• Verify the H908 ground-fault device is functioning correctly, according to the instructions in the “Heating cable testing and maintenance” section.
Table 3. Maximum heating cable circuit length on pipe
Maximum heater length
Circuit breaker
Heating cable type 0°F 40°F WinterGard 120 V
H311 on pipe
WinterGard Plus 120 V
H611 on pipe
WinterGard Wet 120 V
H612 on pipe
Note: Circuit breaker sizing is based on Section 427-4 of the National Electrical Code. Maximum circuit lengths are based on start-up load. Steady­state amps per foot is dependent upon heating cable temperature..
rating (A)
15 150 250
15 125 150
15 125 150
(ft) per circuit at start-up temperature
HEATING CABLE TESTING AND MAINTENANCE
Using a 2500-Vdc megohmmeter (Megger) test the heating cable circuit prior to installing the H908 ground-fault device but after installing any splices, tees and end seals. Measure the insulation resistance between the heating cable bus wires and the copper braid. If the readings are less than 1000 megohms, inspect heating cables for signs of damage and verify the components are correctly installed.
If physical damage is found, the entire damaged section must be removed and a new section of heating cable spliced in using only approved H910 splice kits.
If physical damage cannot be found, the complete circuit should be removed and replaced with new heating cable.
To verify the ground-fault circuit is functioning, test the H908 before each use. Push in the test button. The indicator light must turn off.
Table 4. Product data—WinterGard products on pipe only
Heating cable type WinterGard WinterGard Plus WinterGard Wet
H311 H611 H612 Service voltage (V) 120 120 120 Thermal output at 40°F (W/ft) 3 6 6 Weight per 100 ft (lb) 6 6 9 Minimum installation temp. (°F) 0 0 0 Maximum exposure temp. (°F) 150 150 150 Exposure to chemicals None None None Environment Use only in dry ordinary
(nonhazardous) areas.
Then press the reset button. If the light goes back on, the device is ready to use. Do not use the device if the indicator light does not go on when the device is reset or if the indicator light remains on when the test button is pushed.
Test the H908 functionality before each winter season or more often as required by local code.
WARNING: Shock and Fire Hazard. Damaged heating cable
or components can cause electrical shock, arcing, and fire. Do not attempt to energize damaged cable or components. Replace them immediately using a new length of heating cable and the appropriate WinterGard accessories.
Use only in dry ordinary (nonhazardous) areas.
Use only in wet or dry ordinary (nonhazardous) areas.
THERMAL BUILDING SOLUTIONS
4 / 14
H908 DESIGN AND INSTALLATION INFORMATION FOR ROOF AND GUTTER DEICING ONLY
(WinterGard Wet H612 Heating Cable)
Important:For the Pentair Thermal Management warranty to be
valid, you must comply with all the requirements outlined in these guidelines.
HEATING CABLE DESIGN
Only WinterGard Wet H612 120 V heating cable is suitable for use
with the H908 power connection kit for roof and gutter de-icing applications.
1. Calculate the heating cable length required.
Length = A + B + C + D + E + F + G
A Roof edge length (ft) x feet of heating cable per foot of roof edge
(From Table 5)
B Roof edge length (ft) x 0.5* C Total gutter length (ft) D Total downspout length (ft) + 1 (ft) E 1 ft for each power connection F 2 ft for each splice connection G 3 ft for each tee connection
= Total heating cable length (ft)
* Roof extension: This length allows the heating cable to extend into the gutter
to provide a continuous drain path, or where no gutters are present, extends beyond the roof edge to form a drip loop.
All design information provided here is based on a “standard” shake or shingle roof application. For any other application or method of installation, consult Pentair Thermal Management at (800) 545-6258.
Table 5. WinterGard Wet cable length for roof de-icing
Standing seam metal roof:
Eave overhang Shingle roof 18 inch seam
24 inch seam
0 2.0 ft 2.5 ft 2.0 ft 12 in 2.8 ft 2.8 ft 2.4 ft 24 in 3.8 ft 3.6 ft 2.9 ft 36 in 4.8 ft 4.3 ft 3.6 ft
Note: Pentair Thermal Management recommends a gutter and downspouts to provide a continuous path for melted water.
Example:
Roof edge: 20 ft Roof overhang: 1 ft Roof gutter: 20 ft Downspout: 15 ft Power connection: 1 ea Tee connection: 1 ea Voltage available: 120 V CB Size Available: 15 A Start-up temperature: 0 °F
WinterGard Wet heating cable required:
A Roof edge: 20 ft x 2.0
(from Table 5) = 40 ft
B Roof extension: 20 ft x 0.5 = 10 ft C Roof gutter: = 20 ft D Downspout: = 15 ft + 1 ft = 16 ft E Power connection: 1 ft x 1 ea = 1 ft F Splice connection: = 0 G Tee connection: 3 ft x 1 ea = 3 ft
Total WinterGard Wet heating cable required: 90 ft**
**This total is less than 100-ft maximum circuit length (see
Table 6), therefore a single circuit is required
HEATING CABLE INSTALLATION
1. Prepare for installation.
• Store the heating cable in a clean, dry place.
• Use only the following Raychem accessories to satisfy code and agency requirements:
- H908 Plug-in Power Connection Kit (with end seal)
- H910 Splice and Tee Kit (if splicing or teeing)
- H915 Downspout Hangers
- H913/H914 Roof Clips
• Carefully plan the routing of the heating cable for roof and gutter de-icing.
• Make certain gutters and downspouts are free of leaves and other debris.
2. Cut the heating cable to length.
• Cut the heating cable to the length required before or after it is installed. Leave a minimum of 1 foot extra heating cable for connection to power. For splice and tee connections leave a minimum of 1 foot for each section of heating cable. WinterGard heating cable can be cut to length without affecting its heat output per foot.
• Protect the heating cable ends from moisture and mechanical damage if they will be left exposed before connection.
3. Position and attach the heating cable.
On roofs
• Loop the heating cable on the overhang area of the roof. This is the part that extends past the building wall. Extend the bottom of each heating cable loop over the roof edge and, using a UV-resistant cable tie, connect the bottom of each loop to the cable running in the gutter to ensure a drainage channel off the roof and into the gutter and downspout. The cable running in the gutter should remain against the bottom of the gutter. Extend the top of each heating cable loop beyond where the wall joins the roof. Pentair Thermal Management
recommends 2-foot clip-spacing along the roof edge. See the “Heating cable design” section (Table 5) for spacing and layout information.
• Use WinterGard H913/H914 roof clips to attach heating cable to the roof surface. One kit contains ten double roof clips for approximately 7 linear feet of roof edge. One H914 kit contains 50 roof clips for approximately 35 linear feet of roof edge.
For flat roofs, the heating cable can be spaced as needed to create
runoff paths for melting ice and snow. Use single-ended clips located at 3-foot intervals to secure the cable to the roof.
Roof clips may be attached to a shake or shingle roof with nails or
screws. Roof clips may be attached to a metal roof using screw, nail or adhesive. (See H56723 installation instruction for more details.) Reseal the nail or screw holes if necessary before installing heating cable in the clips.
• A barrier (snow fence) can be placed on the roof above the heating cable. This prevents damage to the cable and keeps the installation from coming loose due to ice slides. The heating cable can be attached to the barrier with UV-resistant cable ties, instead of using roof clips, if desired. Do not use wire or other materials because they may damage the heating cable.
In gutters and downspouts
• Run heating cable along gutters and into downspouts, ending below the freezing level. Permanent attachment of the cable to the gutter bottom is not necessary. Loop the heating cable in downspouts if convenient, such as when the downspout is not at the end of the run, or use the H910 splice and tee kit to tee down the downspout.
• Use WinterGard H915 downspout hangers to protect the heating cable from fraying and from damage from sharp edges and to provide strain relief. Refer to the H915 kit instructions for installation details.
• Use WinterGard H913/H914 roof clips to route heating cable into and out of the gutter in such a way as to prevent abrasion to the cable. Protect all cable that protrudes past the lower opening of the downspout.
5 / 14THERMAL BUILDING SOLUTIONS
Loading...
+ 9 hidden pages