Raychem EM2XR Installation Manual

Page 1
RaychemRaychem
ElectroMelt System
D E S I G N GUIDED E S I G N GUIDE
Page 2
ElectroMelt System Design Guide
2
Page 3
ElectroMelt System Guide Design
Table of Contents
Introduction
ElectroMelt Products
ElectroMelt System Design
Design Steps
Overview 5 How to Use This Guide 5 How to Use the Installation and Operation Manual 5 System Description 5 Codes 5 Warranty 6 Raychem Self-Regulating Heating Cable Technology 6 Self-Regulating Heating Cable 7 Components 7 Accessories 7 Basic ElectroMelt System Design 9 Design for Standard Applications 9 Design for Nonstandard Applications 9 Step 1. Determine Heating Cable Spacing 10 Step 2. Lay out Heating Cable 10 Step 3. Determine Electrical Parameters 11 Installation and Testing 14
Supplemental Design Information
Project Submittal Data Product Data Sheets
Factors Affecting Snow-Melting System Design 15 Performance Requirements 16 Anti-Icing Performance Requirements 16 Snow-Melting Performance Requirements 17 Electrical Performance Requirements 20 Submittal Data Form 23 Heating Cable 25 Power Connection and End Seal Kit, and Splice Kit 26 Expansion Joint Kit 27 Junction Box 28 Automatic Snow Controller 29 Ground-Fault Protection Device 30 Contactor 31 Ambient Sensing Thermostat 32 Accessories 33 Insulation Resistance Tester 34 Jacket Repair Kit 35
Condensed Specification Guide
Appendix A
3
37
Warranty; Suitability 39
Page 4
ElectroMelt System Design Guide
4
Page 5
ElectroMelt System Design Guide
Table of Contents
Overview
How to Use This Guide
How to Use the Installation and Operation Manual
This guide presents Raychem's recommendations for designing and ElectroMelt snow-melting and anti-icing system for use in concrete pavement. Do not use the ElectroMelt system buried in asphalt.
WARNING: ElectroMelt heating cable and associated system components are electrical devices that must be designed and installed properly. Follow all design, installation, assembly, and test instructions to ensure proper operation and to prevent shock or fire. Warnings are highlighted with in the manual.
Following these recommendations will result in a reliable, energy-efficient system. For information regarding other heat-tracing applications, contact your Raychem representative.
The ElectroMelt System Design Guide provides instructions to all engineering disciplines and trades involved in the design and installation of an Electro Melt System. It provides design and performance data, electrical sizing information, and heating-cable layout suggestions.
If, after reading this design guide, you still have questions concerning the design of an ElectroMelt system, contact your Raychem representative. For instructions on installing an ElectroMelt system be sure to read and follow the ElectroMelt Installation and Operations Manual (H53392).
In addition to this design guide, electrical and mechanic design engineers should also use the ElectroMelt Installation and Operations Manual as a general reference document during the design of an ElectroMelt system. They should use it during installation as well to coordinate the work of the trades involved. During and after startup, they should use the manual to record important design and test data.
System Description
Codes
Before design work begins, designers should review appropriate sections of the manual with the Raychem representative. Design engineers will obtain design details from the manual as well as trade coordination and testing requirements, all of which should be addressed in the project specification to ensure a suc­cessful snow-melting or anti-icing system.
The general contractor or construction manager should arrange a meeting with the other trades to discuss installation of the ElectroMelt system prior to the system installation. At this meeting, each trade should be given the appropriate section of the manual, and any questions regarding coordination and timing should be addressed.
The ElectroMelt system performs snow-melting and anti-icing in concrete pavement. The backbone of the system is the EM2-XR self-regulating heating cable. As the illustration on the next page indicates, the cable's output is reduced automatically as the pavement warms, so there is no possibility of failure due to overheating.
Elements of an ElectroMelt system include the EM2-XR heating cable, termination and splice components, and accessories, such as a junction box, automatic controls, ground-fault protection device, power contactor, and the tools necessary for a com­plete installation. This guide provides a data sheet for each element.
Installation of the ElectroMelt System is governed by Article 426 of the National Electrical Code, which requires the use of a ground-fault protection device (GFPD). Your installation must also comply with all applicable local codes and standards.
5
Page 6
ElectroMelt System Design Guide
Introduction
Warranty
The instructions in this guide and in the product packages must be followed. The Raychem warranty will not apply in the event of damage caused by acci­dent, misuse, neglect, alteration, or improper installation, repair, or testing. For the complete warranty statement refer to Appendix A.
Raychem Self-Regulating Heating-Cable Technology
At low temperature, there are many conducting paths, resulting in high output and rapid pavement heat-up. Heat is generated only when it is needed and precisely where it is needed.
At moderate temperature, there are fewer conducting paths because the heating cable efficiently adjusts to weather conditions by decreasing output-eliminating any possibility of concrete over­heating.
At high temperature, there are fewer conducting paths and output is correspondingly lower-conserving energy during operation.
6
Page 7
ElectroMelt System Design Guide
ElectroMelt Products
Self-Regulating Heating Cable
Components
The ElectroMelt EM2-XR heating cable is embedded in concrete pavement to melt snow and ice that might otherwise accumulate on the surface. The heating cable responds to the local concrete temperature, increasing output when concrete temperature drops and decreasing heat output when concrete temper­ature rises. The self-regulating heating cable cannot overheat and destroy itself, even if overlapped in the concrete, and therefore does not require the use of overlimit thermostats. For more detailed information on this cable, see page 25.
Description Catalog #
Self-regulating heating cable EM2-XR
Raychem provides all components necessary for system installation. They are available from Raychem in the kits listed below.
Note: ElectroMelt components must be used in order to satisfy code, approval agencies, and warranty requirements. Installation instructions included with the kits must be followed. For more detailed information on these components, see pages 26 and 27.
Description Catalog #
Power connection kit EMK-XP (includes one end seal) Splice kit EMK-XS Expansion joint kit EMK-XEJ
Accessories
Raychem also provides the following accessories for the ElectroMelt system:
Description Catalog #
Junction box EMK-XJB Automatic snow controller SD-CIT-1 Ground-fault protection device TraceGuard 277™ Contactor E104 Ambient sensing thermostat AMC-1A Cable ties EMK-CT Cable markers EMK-MARK Crimping tool EMK-XT Propane torch FH-2616A-1 Megohmeter EMK-MEG Jacket repair kit EMK-XJR
For more detailed information on these accessories, see pages 28 to 35.
7
Page 8
ElectroMelt System Design Guide
Introduction
Snow Sensor and Controller SD-CIT-1 (optional)
Power Connection and End Seal EMK-XP
Heating Cable Splice EMK-XS
Component Catalog # Usage Heating cable allowance
Power connection kit (includes end seal) EMK-XP One per circuit 3 feet Splice kit EMK-XS As required 1 foot Expansion joint kit EMK-XEJ One per expansion joint crossing 1½ feet
Cable ties EMK-CT One per foot of cable used
Snow controller (optional) SD-CIT-1 One per system
Expansion Joint Kit EMK-XEJ
8
Page 9
ElectroMelt System Design Guide
Supplemental Design Information
Basic ElectroMelt System Design
Design for Standard Applications
The power produced by ElectroMelt EM2-XR heating cable installed on 12-inch centers is adequate for the majority of concrete-pavement snow-melting and anti-icing systems. For this reason, the design steps in the next section and information in other ElectroMelt literature are based on this spacing.
In addition, information in this guide and in other ElectroMelt literature is based on the standard application of the EM2-XR heating cable in concrete pavement poured on grade only.
ElectroMelt system literature includes the following:
ElectroMelt System Brochure H53391
ElectroMelt System Design Guide H53393
ElectroMelt System Installation and Operation Manual H53392
The basic ElectroMelt system design for standard applications on grade is ade­quate for most snowfall and icing conditions, allowing no snow accumulation 97 percent of the time. The design keeps the pavement surface at or above freez­ing when the air above the pavement is a 5°F and the wind is steady at 10 miles per hour or less.
Because the design information in this guide applies only to standard concrete pavement poured on grade, it should not be used for other applications.
Design Requirements and Assumptions
The design for standard applications is based on the following assumptions with regard to the concrete and the heating cable:
Design for Nonstandard Applications
9
Concrete: Heating cable
4 to 6 inches thick 12-inch cable spacing
Placed on grade Secured to reinforcing steel or mesh
Standard density Located 1 ½ to 2 inches below
finished surface
WARNING: Concrete cracks that extend to the depth of the cable may damage the cable and create the risk of fire. Install the cable in pavement or slabs that have been designed for long-term structural integrity.
Increased Power and Performance Requirements
Some applications and some locations require more snow-melting power or more complete anti-icing protection than the standard 12-inch spacing provides. For these cases, refer to the Supplemental Design Information section of this guide for more detailed performance information and design data for nonstan­dard applications.
For nonstandard applications, contact your Raychem representative for assis­tance with your design. Using proprietary computer modeling based on a finite difference program for nonstandard applications. Raychem can design the appropriate system for a nonstandard application.
The following are some nonstandard applications:
concrete thinner than 4 inches
concrete thicker than 6 inches
lightweight concrete
concrete with pavers thicker than 1 ½ inches
ramps and walkways with air below
nonconcrete pavements
concrete without reinforcing
retrofitting of heating cable to existing pavement
Page 10
ElectroMelt System Design Guide
Design Steps
Step 1. Determine Heating-Cable Spacing
Step 2. Lay Out Heating Cable
For most standard applications, ElectroMelt EM2-XR heating cable may be installed on 12-inch centers. The design steps that follow are based on 12-inch spacing.
Snowfall and icing conditions vary widely with location. For this reason, heating cable installed on 12-inch centers may not provide adequate performance for every location.
To determine correct heating-cable spacing for a particular location, consult the Supplemental Design Information section of this guide.
For uniform heating, arrange the heating cable in a serpentine pattern that covers the area. Space the cable on 12-inch centers or use alternate spacing determined by consulting the Supplemental Design Information section of this guide.
Maintain the heating cable spacing in the design within 1 inch.
Use these symbols to indicate the heating cable and components:
Power Connection
End Seal
Splice
Do not route the heating cable closer than 4 inches to the edge of the pave­ment, drains, anchors, or other material in the concrete.
The water resulting from the melted snow or ice should run into a drain or off to a safe area.
Arrange the heating cable so that both ends of the cable terminate in an above­ground, UL Listed or CSA Certified weatherproof junction box. The following are guidelines for this procedure:
• Mount the heating-cable junction box above grade to prevent water entry Use an EMK-XJB or equivalent UL Listed or CSA Certified weatherproof junction box.
• Protect the heating cable from the pavement to the junction box by installing heating cable inside individual 1-inch rigid metal conduits. Minimize the length of the protective conduit. Do not penetrate building walls or floors with the protective conduit or insulate the conduit.
• Extend the conduit approximately 6 inches into the concrete for support.
• Provide bushings on both ends of each conduit.
• Do not install more than one run of heating cable per conduit.
• Minimize the length of the conduit.
• Do not insulate the conduit.
• Do not penetrate building floors or walls with the conduit.
If possible avoid crossing expansion, crack-control, or other pavement joints. Where crossing a joint is unavoidable, use the EMK-XEJ expansion joint kit to protect the heating cable.
Use these symbols to indicate the location of the joints:
Expansion Joint
Crack-control joint
Expansion joint kit
10
Page 11
ElectroMelt System Design Guide
Design Steps
Calculate the total length of heating cable required as: Total heating Heated area (ft²) x 12 end component cable length Heated cable spacing (in.) allowancesª allowances
ªEnd allowance is the length of heating cable installed between the heated area and the power connection junction box, measured in feet.
b
Component allowances measured in feet (see page 8).
=
Junction Box EMK-XJB
+
+
b
Step 3. Determine Electrical Parameters
6" (S/2)
6" (S/2)
This section will help you determine the electrical parameters for an ElectroMelt system. To determine the demands an ElectroMelt system will place on your electrical equipment, refer to "Electrical Performance Requirements" in the Supplemental Design Information section of this guide.
Electrical Protection
The installation and design of the ElectroMelt System is governed by Article 426 of the National Electrical Code. Your installation must also comply with all applicable local codes and standards. To comply with the National Electrical Code, use a 30-mA ground-fault protection device (GFPD).
12" (S)
S = Heating cable spacing
1" Conduit
6"
11
Warning: To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, use a ground-fault protection device with a 30-mA trip level. Electrical fault currents may be too small to trip conventional circuit breakers.
Voltage
Standard design information is provided for operation at 208 Vac. The allowable range of voltage for EM2-XR is 208 to 277Vac. Using a voltage higher than 208 volts results in slightly higher surface temperatures and allows longer maxi­mum circuit lengths as indicated in Tables 1 and 2.
Page 12
ElectroMelt System Design Guide
Design Steps
Circuit Breaker Rating
Use thermal-magnetic circuit breakers rated no greater than 50 amperes for overcurrent protection. Use the lowest rated circuit breaker compatible with the circuit lengths to be used. Use Tables 1 or 2 below to determine maximum cir­cuit length.
Table 1. Maximum Heating Cable Circuit Length for Startup at 0°F (in feet)
Circuit
breaker 208 V 220 V 240 V 277 V
50 amp 245* 250* 265* 300
40 amp 200* 200* 210* 240
30 amp 145 150 160 180
20 amp 100 100 110 120
15 amp 75 75 80 90
Heating cable operating voltage
Table 2. Maximum Heating Cable Circuit Length for Startup at 20°F (in feet)
Circuit
breaker 208 V 220 V 240 V 277 V
50 amp 265* 270* 285* 325
40 amp 210* 215* 230* 260
30 amp 160 165 170 195
20 amp 105 110 115 130
15 amp 80 80 85 100
*Contact RayChem for assistance, or change the voltage to 277 volts and use TraceGuard 277. (40 and 50 amp GFPD's are not standard for these voltages).
Ground -Fault Protection Devices (GFPDs)
Use a RayChem TraceGuard 277 GFPD for 277-volt applications, up to 50 amps. Equivalent 30mA ground-leakage protection is provided by Westing­house GFPDs or Square-D QO-EPD ground-leakage circuit breakers at 208 and 240 volts (30-amp maximum rating).
Heating cable operating voltage
12
Page 13
ElectroMelt System Design Guide
Design Steps
Controls
Three control methods are commonly used with snow-melting and anti-icing systems. All three methods require a contactor as shown in the diagram on the next page. The contactor must be sized to carry the load. Each method offers a tradeoff of initial cost against energy efficiency. Choose the one the best meets the project performance and requirements.
Automatic snow controller
An automatic snow controller offers the highest system reliability and the lowest operating cost. Raychem's SD-CIT-1 automatic snow controller detects both precipitation and low temperature and automatically energizes the ElectroMelt snow-melting system. When precipitation stops or the temperature rises above freezing, the controller de-energizes the snow-melting system. However, the pole-mounted sensor cannot detect runoff from adjacent areas, snow which is tracked into the heated area, or freezing dew.
Ambient thermostat
An ambient thermostat can be used to energize the system whenever the ambi­ent temperature is below freezing. Raychem's AMC-1A ambient thermostat should be used whenever the design objective is to prevent surface icing under all conditions (anti-icing). Since the number of hours of freezing temperatures is two to ten times the number of snowfall hours, the energy usage of a system under control of an ambient thermostat is two to ten times that of a system con­trolled by an automatic snow controller.
Manual control
Under manual control the system is operated by a manual switch controlling the system power contactor. In some small installations, the system may be con­trolled directly by operating the circuit breakers.
13
Page 14
ElectroMelt System Design Guide
Design Steps
Typical Control Diagram
Supplied Power 480 V/277 3 , 4 wire
100 A
3
MCB
50 A
GFPD TraceGuard 277
Contactor**
100 A
E 104 100 A/Pole, 120 V
Power Connection Kit EMK-XP
ElectroMelt Cable with Braid
End Seal Kit (part of EMK-XP)
N*
1
100 A
2
Control Power 120 Vac
Snow
Sensor
15 A
Up to 2000 Ft.
Off Delay Timer
0.5-5.0 Hr
20 A
20 A
Automatic Snow Controller SD-CIT-1 (120 V @ 50 W
Installation and Testing
14
* Neutral wire must pass through TraceGuard 277 (see Illustration Instructions). ** In 208-volt and 240-volt systems, means should be provided to disconnect both phases.
After the design is completed, the system should be installed and tested. Follow all design, installation, assembly, and test instructions to ensure proper opera­tion and to prevent shock or fire. Use only Raychem ElectroMelt connection components and follow the installation instructions included with them.
Install the ElectroMelt system in accordance with Raychem's ElectroMelt System installation and Operation Manual (H53392) and the installation instruc­tions (APP-910B) supplied with the heating cable and components.
Test the insulation resistance of the ElectroMelt heating cable with a 2500-Vdc Megger. Test after installation, during the concrete pour, and annually there­after. Refer to the ElectroMelt Installation and Operation Manual (H53392) for the proper testing procedure.
Page 15
ElectroMelt System Design Guide
Supplemental Design Information
Factors Affecting Snow Melting System Design
Snow-melting systems are installed for convenience and safety. They are often thought of only in terms of snowfall, but an important-and often the principal­function may be anti-icing.
Anti-icing is the ability of the system to prevent the formation of ice on the pave­ment surface; it is the ability to maintain all points on the surface above 32°F for given temperature and wind conditions. The anti-icing behavior of a system must be considered when the primary objective of the system is to reduce slip­ping hazards or when tracking or runoff of water from adjacent unheated pave­ment areas is a potential problem.
All surface points above 32°F.
Snowfall
Snowfall patterns vary widely with location. A system design that works well in one city may be inadequate in another. The energy required to melt snow varies with air temperature, wind speed, relative humidity, snow density, and the depth of the snow on the pavement.
The effective power of a snow-melting system (that is, the power delivered to the top surface on the pavement) is used to warm the fallen snow to melting temperature, to supply the heat to melt the snow, to make up for evaporation losses from the surface, and to make up for both convection- and radiation-heat losses from the pavement surface.
The power required in a given situation is strongly influenced by whether the surface is kept clear as snow falls. If snow is melted immediately as it falls, the system must make up for convection-, radiation-, and evaporation-heat losses as well as melt the fallen snow. However, if a light film of snow is allowed to cover the surface, the insulating blanket of snow reduces or eliminates the loss­es due to convection, radiation, and evaporation, and more of the effective sys­tem power is available for melting snow.
Heat loss varies with snow cover.
15
Page 16
ElectroMelt System Design Guide
Supplemental Design Information
Icing
Virtually any level of power will melt snow if there is a sufficiently deep snow cover to insulate the surface from convection-heat loss. However, icing prob­lems may arise once the insulating blanket has been melted and the pavement is subject to increased heat loss due to wind action on the exposed surface.
Icing problems also arise when water from adjacent unheated areas runs onto the heated area or when snow and slush are racked onto the heated area by pedestrians or vehicles. In many situations the expected anti-icing behavior of a system imposes more severe constraints than the ability to melt snow does.
Snow-melting and anti-icing systems require only enough power to meet the system performance requirements. Providing excess power increases system cost and leads to higher energy costs.
Performance Requirements
In designing an ElectroMelt system it is therefore critical to specify system per­formance requirements accurately. This means determining both anti-icing and snow-melting requirements, as shown below.
Sample Performance Specification
Anti-Icing requirements
Minimum ambient temperature 5°F
Average wind speed 10 MPH
Snow-melting requirements:
Surface clear 50% of snowfall hours
Snow accumulation 3% or less
As shown in the specification example above, a typical performance specifica­tion specifies the minimum ambient temperature and the average wind speed at which all surface points must be above freezing. These are the anti-icing requirements. It specifies the snow-melting requirements as well, in terms of the percentage of all snowfall hours for which the operating system must keep the surface essentially clear, and the allowable percentage of all snowfall hours for which some snow accumulation is tolerable.
The sections that follow should help you determine and specify an application's anti-icing and snow-melting requirements.
Anti-Icing Performance Requirements
16
Determining Ambient Temperature
Once you have determined the heating-cable spacing of an ElectroMelt System you can determine the ambient temperature by referring to Table 3. Simply locate the row corresponding to the design's heating-cable spacing. Move across that row to the column corresponding to the average wind speed during freezing periods and read the minimum ambient temperature at which all points on the pavement surface will be at or above 32ºF.
Note: This procedure is derived from finite model studies of 4-inch slabs and is applicable to standard concrete pavement from 4 inches to 6 inches thick placed directly on grade. If your application involves other materials or con­structions, contact your Raychem representative.
Page 17
ElectroMelt System Design Guide
Supplemental Design Information
Table 3. Ambient Temperatures (°F) for Ice-Free Surfaces
Heating-cable
spacing (in inches) 5 mph 10 mph 15 mph 20 mph
6 -40 -25 -10 0
8 -40 -10 0 10
10 -25 0 10 15
12 -15 5 15 20
Average wind speed during freezing periods
Snow Melting Performance Requirements
Table 4. Figure Selections for Snow-Melting Performance Curves
USA
City Fig. City Fig. City Fig.
Albuquerque, N. Mexioco 1 Detroit, Mich. 1 Oklahoma City, Okla. 5
Boston, Mass. 6 Duluth, Minn. 4 Philadelphia, Pa. 2
Buffalo-Niagra Falls, N.Y. 1 Falmouth, Mass. 6 Pittsburg, Pa. 1
Burlington, Vt. 1 Great Falls, Montana 4 Rapid City, S.D. 4
Caribou-Limestone, Maine 3 Hartford, Conn. 6 Salina, Kansas 3
Cheyenne, Wyo. 5 Lincoln, Nebr. 4 Sault Ste. Marie, Mich. 3
Chicago, Ill. 1 Memphis, Tenn. 6 Spokane, Wash. 1
Colorao Springs, Colo. 3 Minneapolis-St. Paul, Minn. 3 St. Louis, Mo. 6
Columbus, Ohio 1 New York, N.Y. 2 Washington, D.C. 2
Obtaining Snowfall Data
Snowfall data is not available for all cities. However, you may still specify snow­melting performance if you can obtain snowfall data for a city with comparable snowfall conditions for which published data are available.
Alternatively, you can use Table 4 below and Figures 1-6 on page 19 to deter­mine the snow-melting performance to specify. Each figure contains a snow­melting performance curve from which you can determine cumulative snowfall hours for your application.
Using Table 4
Which of the snow-melting curves you should use depends on the snowfall con­ditions for the city in which your application is located. Table 4 below lists typical U.S. and Canadian cities and shows the figure number for the curve applicable to snowfall conditions for each city. Using Table 4, locate the city with a snowfall pattern similar to the location for which you are designing the ElectroMelt system. Turn to the snow-melting curve in the figures listed for that city.
Canada
City Fig. City Fig. City. Fig.
Calgary, Alberta 4 Ottawa, Ont. 3 Sudbury, Ont. 4
Halifax, N.S. 6 Quebec City, P.Q. 3 Toronto, Ont. 1
Kamloops, B.C. 1 Regina, Sask. 4 Vancouver, B.C. 1
Montreal, P.Q. 3 Saint John, N.B. 1 Winnipeg, Man. 4
17
Page 18
ElectroMelt System Design Guide
Supplemental Design Information
Using Figures 1-6
Once you have determined the correct curve to use for your application, turn to the correct figure for that curve and take the following steps:
1. Draw a horizontal line across the figure at the heating-cable spacing you plan to use in the design.
2. Draw vertical lines from the points where the segmented snow melting per­ performance curves intersect your horizontal heating-cable-spacing line.
3. From the intersection of the left vertical line with the percentage axis read the percentage of all snowfall conditions for which the pavement will be com­ pletely clear.
The distance between the left and right vertical lines is the additional percent­age of all snowfall conditions for which the pavement may have a light snow cover. The distance, if any, from the right line to the end of the percentage axis is the percentage of snowfall conditions for which snow may actually accumu­late while the system is in operation. If increased snow-melting performance is required, reduce the heating cable spacing.
Example
To determine the snow-melting performance you should specify for ElectroMelt heating cable installed on 10-inch centers in Chicago, Illinois, find the figure number for Chicago in Table 4. The table refers you to Figure 1.
Using Figure 1, you see that the intersection of the 10-inch spacing line with the "Surface Completely Clear" curve occurs at approximately 88%, and the inter­section with the "Some Accumulation Possible" curve occurs at 0%
These percentages indicate that the system with 10-inch spacing will keep the surface completely clear for 88% of all snowfall conditions occurring in Chicago, and will allow no accumulation.
For the remaining 12% of conditions, the surface may have a light covering of snow, but the system will be able to melt snow at the same rate at which it falls (no accumulation).
18
Page 19
ElectroMelt System Design Guide
Supplemental Design Information
Figure 1.
6
) s e h
inc
8
ing ( c
pa S
10
ble
12
ing Ca
t a
He
Surface Completely Clear
25
25
0
0
Cumulative Snowfall Hours (%)
Snow Accumulates
50
50
Light
Cover Possible
75
75
100
100
Figure 3.
6
) s e h
inc
8
ing ( c
pa S
10
ble
12
ing Ca
t a
He
Light Cover Possible
10
12
10
12
6
8
6
8
Figure 2.
Surface Completely Clear
0
25
Cumulative Snowfall Hours (%)
Figure 4.
Light Cover Possible
Light Cover Possible
100
50
75
19
Snow AccumulatesSnow Accumulates
25
0
Cumulative Snowfall Hours (%)Cumulative Snowfall Hours (%)
50
75
Figure 5.
)
6
s e h
inc
ing (
8
c pa
S
10
ble
12
ing Ca
t a
He
25
0
Cumulative Snowfall Hours (%)
Snow Accumulates
50
Light
Cover Possible
75
100
100
10
12
6
8
0
25
Cumulative Snowfall Hours (%)
Figure 6.
0
25
Cumulative Snowfall Hours (%)
50
50
Snow Accumulates
75
Light
Cover Possible
Snow Accumulates
75
100
100
Page 20
ElectroMelt System Design Guide
Supplemental Design Information
Electrical Performance Requirements
Electrical Design
The ElectroMelt EM2-XR self-regulating heating cable varies its power output at every point along its length in response to the surface temperature or sheath temperature of the heating cable. When the concrete in contact with the surface of the heater is cool, the cable is cool and the resistance of the specially blend­ed polymer core is low, resulting in high power output. As the pavement warms, the heating cable core warms and the core resistance rises, resulting in lower power output. A graph of the relationship between sheath temperature and power output of the EM2-XR heating cable appears below.
) ot
o /f
ts at
w r (
we o
P
0 275
During normal operation, the heating-cable output varies between the points marked "Maximum Startup Power" and "Steady-State Operation." The heating­cable operating temperature varies with the concrete temperature and weather conditions, but is usually about 60ºF warmer than the concrete surface. On a hot summer day, the concrete in contact with the heating cable could reach 150ºF.
Heating Cable Sheath Temperature ( F)
Maximum Startup Power
Steady State Operation
Startup Temperature
The maximum length of heating cable allowed on a given size circuit breaker is determined primarily by the current drawn by the heating cable during low-tem­perature (high-power) startup conditions. The maximum circuit length data given in Table 1 on page 12 is based on starting the heating cable when the concrete pavement is at 0ºF. A maximum length circuit started at 0ºF will result in branch circuit loading of less than 80 percent of the circuit breaker rating within 10 minutes.
Transformer Sizing
Transformers should be sized to handle the startup load of the heating cable indefinitely. To determine the current load of each circuit, refer to the circuit breaker rating tables on page 12. The actual current per foot of heating cable and the transformer size are calculated as follows:
Current Circuit breaker rating per foot Maximum allowed length of heating cable at design voltage
Transformer Current Total Heating Heating Cable size per foot cable length operating voltage
Voltage Drop
Calculate the branch circuit voltage drop based on the current as computed above. Note that the maximum size branch circuit conductor that can be termi­nated in the EMK-XP power connection kit is 4 AWG.
=
0.8 x
=
x
x
20
Page 21
ElectroMelt System Design Guide
Supplemental Design Information
Example
An application at a parking garage requires four heating cable circuits 275 feet long. The heating cable is to be powered at 277 Vac.
Circuit Breaker Sizing
From Table 1 on page 12, up to 300 feet of heating cable may be connected to a single 50-amp branch circuit breaker.
Transformer Sizing
The branch circuit current after startup at 0ºF is calculated as follows:
Current = 80% x 50 amp/300 ft
= 0.13 amp/ft
Transformer size = 0.13 amp/ft x 275 ft/circuit x 277 Vac
= 39,600 watts = 39.6 kilowatts
21
Page 22
ElectroMelt System Design Guide
22
Page 23
ElectroMelt System Design Guide
Design Steps
Project Data
Project or area name
Submitted by
Reference
Date
Design Data
Site Location
Minimum ambient temperature
Average wind speed
Heating cable spacing
Description of performance requirements
Pavement Data
Pavement material
Pavement thickness
Heating cable depth
Type of reinforcement
Description of area to be to be heated
Is pavement placed on grade?
(if not, please describe)
Product Data
Heating cable model
Heating cable manufacturer
Product approvals
Power connection kit model
Splice Kit
Expansion joint kit model
23
Electrical Data
Heating cable operating voltage
Branch circuit overcurrent protection device and rating
Heating cable junction box description
Control System description
Total Electrical Load
Page 24
ElectroMelt System Design Guide
24
Page 25
ElectroMelt System Design Guide
EM2-XR
0.310"
Self-Regulating Heating Cable For Concrete Snow-Melting and Anti-Icing Applications
0.700"
Description
Specifications
Circuit Breaker Sizing
The ElectroMelt EM2-XR heating cable is a high-powered, self-regulating heat­ing cable for concrete snow-melting and anti-icing applications. The uniquely blended polymer core of the heating cable adjusts its power output at every point along its length to eliminate hot spots and burnouts that can be experi­enced with constant-wattage heating cables. A heavy-duty, modified polyolefin outer jacket resists abrasion, puncture, and damage caused by rough handlling.
Operating voltage 208 to 277 Vac Overcurrent protection 50 amps, maximum Maximum circuit length 300 feet at 277 Vac Minimum bend radius 2 inches Minimum installation temperature 30ºF Maximum self-generated temperature 275ºF Color: Orange
Maximum Heating Cable Circuit Length (in Feet) for Startup at Oº F
Heating Cable Operating Voltage
Circuit Breaker 208V 220V 240V 277V
50 amp 245 250 265 300 40 amp 200 200 210 240 30 amp 145 150 160 180 20 amp 100 100 110 120 15 amp 75 75 80 90
25
Ordering Information
Catalog number EM2-XR Part number 449561 Description Self-regulating heating cable Packaging Random-length reels Shipping weight 0.18 pound per foot
Page 26
ElectroMelt System Design Guide
EMK-XP EMK-XS
6"
6"
Power Connection and End Seal Kit, and Splice Kit For Use with EM2-XR Self-Regulating Heating Cable
Power Connection EMK-XP
End Seal EMK-XP
10"
Splice EMK-XS
Description
Specifications
Odering Instructions
The ElectroMelt termination and splicing components are used to terminate the end of the heating cable to power conductors or to splice one length of heating cable to another. These water-resistant electrical assemblies are sealed with a proprietary Raychem adhesive and protected by an outer heat-shrinkable tube manufactured by Raychem of crosslinked, modified polyolefin polymers.
Temperature rating 90ºF
Storage temperature -40ºF to 140ºF
Minimum installation temperature 30ºF
Power connection wire range 14 to 4 AWG
Voltage rating 600 Vac
Power connection and end seal
Catalog number EMK-XP
Part number 579519
Description Power connection and end seal kit
Packaging One power connection and one
end seal per box
26
Shipping weight 0.4 pound
Splice kit
Catalog number EMK-XS
Part number 356667
Description Splice kit
Packaging One splice kit per box
Shipping Weight 0.2 pound
Page 27
ElectroMelt System Design Guide
EMK-XEJ
Expansion Joint Kit For Use with EM2-XR Self-Regulating Heating Cable
Description
Specifications
Specifications
Ordering Information
The ElectroMelt EMK-XEJ expansion joint kit provides physical protection for the heating cable beneath slab joints. An expansion tube is used to form an expansion loop for the heating cable.
Temperature rating 195ºF
Storage temperature -40ºF to 140ºF
Min. installation temperature 30ºF
Catalog number EMX-XEJ
Part number 472207
Description Expansion joint kit
Packaging One expansion joint per kit
Shipping Weight 0.3 pound
27
Page 28
ElectroMelt System Design Guide
EMK-XJB
Junction Box For Use with EM2-XR Self-Regulating Heating Cable
Description
Specifications
Ordering Information
The EMK-XJB is a large, UL Listed weatherproof enclosure suitable for termi­nating both ends of one EM2-XR circuit. The enclosure is made of molded structural foam and provides high impact strength, excellent chemical resis­tance, high dielectric strength, and excellent weathering capabilities. It is suit­able for outdoor applications.
Manufacturer Carlon, model CJ12106 Inside dimensions 12" x 10" x 6 " Inside volume 825 cubic inches Outside dimensions 15 ½" x 11¾" x 7 " Temperature range -40ºF to 185ºF UL Standard UL508
Catalog number EMK-XJB Part Number 052577 Description Junction box
7/8
5/8
28
Packaging One junction box per kit
Shipping Weight 5.4 pounds
Page 29
ElectroMelt System Design Guide
SD-CIT-1
Automatic Snow Controller For Use with EM2-XR Self-Regulating Heating Cable
Description
Specifications
The ElectroMelt snow controller features a single snow sensor and a control panel to automatically control the operation of heating cables. The sensor detects snow as precipitation occurs at temperatures below 38°F. The panel provides an adjustable hold-on timer, which allows the heating cable to contin­ue to operate even after snow stops. This timer ensures complete melting of snow or ice. The sensor can be located up to 2000 feet from the panel. The panel has an internal contactor providing two contacts rated for 20 amps.
Snow Sensor Control temperature 38°F Operating temperature range -40°F to 140°F AC supply voltage requirement 22 to 30V (provided by control panel) Maximum power consumption 3 watts
Control Panel Heater hold-on timer
adjustment range 0.5 to 5 hours Control switch Automatic/Off/Manual Indicators Supply/Relay
Ordering Information
29
Number of sensors supported One to six (one provided) Supply voltage requirement 120Vac/240 Vac Current (heater load) 20 amps
Catalog number SD-CIT-1 Part number 208875 Description Pole-mounted snow detector and control panel Packaging One snow detector and panel per kit Shipping weight 13.7 pounds
Page 30
ElectroMelt System Design Guide
TraceGuard 277
Ground-Fault Protection Device (GFPD) For Use with EM2-XR Self-Regulating Heating Cable
Description
Specifications
Ordering Information
The TraceGuard 277 GFPD (Square D EHB-EPD) is a single-pole, thermal­magnetic circuit breaker with equipment ground-fault protection. The GFPD is rated for use with 480/277-Vac heat-tracing systems with a maximum load of 40 A. It is used to provide overcurrent and equipment ground-fault protection, but not to protect people from the hazard of electrical shock. The ground-fault trip level of the 277-volt GFPD is 30 mA. The GFPD is available in bolt-on con­struction for installation in Square D's EHB panelboards. It comes in two ver­sions, a base unit and a unit with bell alarm contacts.
Manufacturer Square D Breaker frame E4 Amp rating 15 A to 50 A (refer to tables below) UL interrupting rating: 120 Vac - 25 kA
277 Vac - 2 kA 125 Vdc - 5 kA
Description Ground-fault protection device Packaging One circuit breaker and relay per kit Shipping weight 15 pounds each
30
Catalog / Part No.: Amperes Base Unit Catalog No. Part No.
15 A GFPD EHB14015EPD 984563
20 A GFPD EHB14020EPD 833637 30 A GFPD EHB14030EPD 605703 40 A GFPD EHB14040EPD 021803 50 A GFPD EHB14050EPD 866711
Catalog / Part No.: Amperes Bell Alarm Unit Catalog No. Part No.
15 A GFPD EHB14015EPD2100 984563
20 A GFPD EHB14020EPD2100 833637 30 A GFPD EHB14030EPD2100 605703 40 A GFPD EHB14040EPD2100 021803 50 A GFPD EHB14050EPD2100 866711
Page 31
ElectroMelt System Design Guide
E104
Contactor For USe with EM2-XR Self-Regulating Heating Cable
Description
Specifications
Ordering Information
The E104 is a three-pole contactor housed in a thermoplastic enclosure that is lightweight, dusttight, watertight, and corrosion resistant.
Enclosure Carlon CJ1085, NEMA 4X, corrosion
resistant, dusttight, watertight
Contactor ITE 2250-HI930 ABA
UL Listed and CSA Certified
Power Connection I/O - 14 AWG box lugs
Power Contacts Silver, cadmium plated
Rating 100 amps per pole @ 600 Vac
Coil connection 32 #6 screw terminals
Coil rating 120 Vac
Catalog number E104, 120 Vac
Part number C77046
Description Contactor
Packaging One contactor per kit
Shipping weight 5 pounds
31
Page 32
ElectroMelt System Design Guide
AMC-1A
Ambient Sensing Thermostat For Use with EM2-XR Self-Regulating Heating Cable
Description
Specifications
The AMC-1A thermostat responds to air temperature changes detected by a stainless steel sensing probe. The AMC-1A can be used to control a contactor coil.
Manufacturer Barksdale Enclosure NEMA 4X; epoxy-coated aluminum
housing; exposed hardware is stainless steel
Approvals UL listed and CSA Certified Range 15°F to 140°F Sensor exposure limits -65°F to 160°F Housing exposure limits -65°F to 160°F Switch SP-DT UL Listed microswitch BM1R Electrical rating 22 amps @ 125, 250, or 277 Vac Connection Screw terminals on enclosed terminal block
through ½ NPT conduit hub
Differential 6°F maximum Setpoint repeatability ± 1°F Sensor type Fluid-filled probe Sensor material Stainless Steel
Ordering Information
32
Catalog number AMC-1A Part Number C77125 Description Ambient sensing thermostat Packaging One thermostat per kit Shipping weight 1.5 pounds
Page 33
ElectroMelt System Design Guide
FH-2616A-1, EMK-CT, EMK-XT, EMK-MARK
Accessories For Use with EM2-XR Self-Regulating Heating Cable
Description
Specifications
The ElectroMelt product line has the accessories necessary for a complete installation of EM2-XR cable. The propane torch (FH-2616A-1) is suitable for heat-shrinking the connection kits. The crimping tool (EMK-XT) is the correct size for the crimps in the connection kits. The cable ties (EMK-CT) are 7-inch nylon industrial cable ties. The cable markers (EMK-MARK) are Raychem TMS lables, which can be preprinted with the circuit numbers.
Torch (FH-2616A-1) Description Includes hose, handle assembly;
equipped with regulating valve
Crimp Tool (EMK-XT) Manufacturer Ideal Model number 30-425 Length 10”
Cable Ties (EMK-CT) Manufacturer Panduit Model number PLT25-C Length 7 3/8" ± 1/2" Width 3/16"
Labels (EMK-MARK) Description ShrinkMark-250-2.00-9 cable markers
Ordering Information
33
Torch Crimp Tool Cable Ties Labels
Catalog number FH-2616A-1 EMK-XT EMK-CT EMK-MARK Part number 102049 980631 906441 228347 Description Propane Crimp Nylon Cable ShrinkMark
torch tool ties labels
Packaging One per kit One per kit 100 per pack Contact factory Shipping Weight 5 pounds 1.2 pounds 0.5 pounds 1.2 pounds
per 100 markers
Page 34
ElectroMelt System Design Guide
EMK-MEG
Insulation Resistance For Use with EM2-XR Self-Regulating Heating Cable
Description
Description
Ordering Information
The EMK-MEG is a precision instrument that tests the insulation resistance of heating cables. Battery operated and portable for field use, it features a push­to-read and lock-on button to conserve the battery. The Megger can test insula­tion resistance at voltages up to 5000 Vdc and has neon scale-selection indica­tors. The kit includes batteries, two test leads, probes, an operation manual and leather carrying case.
Manufacturer Simpson
Model 405-2
Accuracy Megohm ranges ± 1.5% AC/DC voltage
ranges ± 5%; full scale to 1000 V
Supply Six 1.5-V batteries
Dimensions 9 3/5" x 5 1/2" x 4 1/8"
Catalog number EMK-MEG
Part number 130519
34
Description 5000-Vdc insulation tester/Megger
Packaging One instrument and case per kit
Shipping weight 5.0 pounds
Page 35
ElectroMelt System Design Guide
EMK-XJR
Jacket Repair Kit For Use with EM2-XR Self-Regulating Heating Cable
Description
Specifications
Ordering Information
The ElectroMelt jacket repair kit is a wraparound sleeve for covering a dam­aged outer jacket. The repair sleeve is adhesive-lined and comes with a metal closure channel.
Description Heat-shrinkable sleeve with adhesive lining;
removable metal closure
Approvals UL Listed for applications of 600 volts or less
Length 12 inches nominal
Catalog number EMK-XJR
Part number 693647
Description Jacket repair kit
Packaging One repair sleeve per kit
Shipping weight 0.8 pounds
35
Page 36
ElectroMelt System Design Guide
36
Page 37
ElectroMelt System Design Guide
Condensed Specification Guide
This is the product portion of a specification for the ElectroMelt System. For a complete specification that includes installation and testing recommendations, contact your Raychem representative.
PART 1 - GENERAL
Furnish and install a UL Listed and CSA Certified snow-melting system com­plete with heating cable, termination components, junction boxes, contactors, and controls.
PART 2 - PRODUCTS
2.1 The heating cable and termination components shall be UL Listed as De­icing and Snow-melting Equipment and CSA Certified as Designation 1B, 2B.
2.2 The heating cable shall consist of two 14-gauge nickel-coated-copper bus
wires embedded in parallel in a self-regulating polymer core. Power output shall vary in response to temperature all along its length, allowing the heat­ ing cable to be crossed over itself without overheating, to be cut to length in the field, and to have no heater-to-cold-lead connections buried in the pavement. The heating cable shall be covered by a crosslinked dielectric jacket and protected by a tinned-copper braid and a 70-mil-thick modified polyolefin outer jacket.
2.3 The heating cable shall be of parallel circuit construction to allow the cable to
be spliced if it is inadvertently cut during or after construction, and to be pow­ wered from both ends if it becomes advantageous to divide a circuit in two.
2.4 The heating cable shall operate on (select: 208, 220, 240, or 277) volts
without the use of transformers.
2.5 The heating cable shall be ElectroMelt EM2-XR as manufactured by
Raychem Corporation.
2.6 The system shall be controlled by (select: a switch, an ambient sensing ther-
mostat, or an automatic snow controller) through an appropriate contactor.
2.7 The heating cable power connection and end seal terminations shall be
made in an ElectroMelt EMK-XJB junction box.
2.8 Each circuit shall be protected by a 30-mA ground-fault protection device.
37
PART 3 - INSTALLATION
3.1 The heating cable shall be installed according to the manufacturer's recom-
mendations, the instructions supplied with the heating cable and compo­ nents, and the instructions in the ElectroMelt Installation and Operation Manual (H53392).
3.2 The heating cable shall be installed only in concrete pavement designed for
long-term structural integrity. The pavement shall be reinforced with rebar or wire mesh and the reinforcing supported such that the location of the reinforcing and the attached heating cable is not disturbed during the con­ crete placement. The rebar shall be placed at the heating-cable depth whenever possible.
3.3 The heating cable shall be protected from where it leaves the pavement to
the junction box by installing the cable in 1-inch rigid metal conduit. Use one conduit for each heating cable.
3.4 The power connection and end seal junction box shall be mounted above
grade. The junction box shall be installed so that water can not enter it.
3.5 Heating-cable repairs and splices shall be made using a splice kit provided
by the manufacturer and specifically approved for the purpose. They shall pass the Megger test after installation.
PART 4 - TESTING
The heating cable shall be tested for insulation resistance with a 2500-Vdc Megger after installation, during the concrete pour, and annually thereafter according to the manufacturer's recommendations and following the instruc­ tions provided in the ElectroMelt Installation and Operation Manual (H53392).
Page 38
ElectroMelt System Design Guide
38
Page 39
ElectroMelt System Design Guide
Appendix A
Warranty; Suitablity
(a) Raychem warrants products delivered hereunder against faulty workman­ship and use of defective materials for a period of eighteen (18) months from the date of installation or twenty-four (24) months from the date of shipment, whichever is sooner. When the contract calls for systems design, drawings, technical advice, services, or instructions (collectively "Services") by Raychem, in connection with the products, Raychem further warrants for the above stated warranty period solely that such Services will be undertaken in accordance with Raychem's reasonable technical judgment based on Raychem's understanding of the pertinent technical data as of the date of performance of such Services. The foregoing warranty with respect to products shall not be enlarged or affect­ed by, and (except as expressly provided herein) no obligation or liability shall arise or grow out of, Raychem's rendering Services in connection with the prod­ucts. Such warranty is the only warranty made by Raychem and it can be amended only by a written instrument signed by a duly authorized officer or Raychem. If the products furnished by Raychem hereunder are determined to contain a deficiency, Buyer's exclusive remedy shall be to have Raychem repair such products or supply replacement products or credit Buyer's account for such products and accept their return, whichever Raychem may elect in its sole discretion. Notwithstanding the foregoing sentence, in no circumstances shall Raychem have any liability or obligation with respect to expenses, liabilities, or losses associated with the installation or removal of any products or the installa­tion of replacement products or for any inspection, testing, or redesign occa­sioned by any deficiency or by the repair or replacement of products. Raychem's obligations are subject to the further condition that Raychem shall have no liability whatsoever for any deficiency unless (i) Raychem is notified in writing promptly (and in no event later than 30 days) after discovery by Buyer of the alleged deficiency, (ii) the products containing the alleged deficiency are promptly returned to Raychem, F.O.B. Raychem's plant, and (iii) Raychem's examination of such products discloses to Raychem's satisfaction that such alleged deficiency actually exists and occurred in the course of proper and nor­mal use and was not caused by accident, misuse, neglect, alteration or improp­er installation, repair, or testing. If any products so prove to contain a deficiency and Raychem elects to repair or replace them, Raychem shall have a reason­able time to make such repair or replacement.
39
THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PUR­POSE, OR NONINFRINGEMENT, AND OF ANY OTHER OBLICATION ON THE PART OF RAYCHEM.
(b) It shall be the responsibility of the Buyer to determine, on the basis of the most current written technical data, the suitability of the products and of any systems design or drawings for the intended use and their compliance with applicable laws, regulations, codes, and standards and the Buyer assumes all risks pertaining thereto.
Page 40
TraceGuard and ShrinkWrap are trademarks of Raychem Corporation. Megger is a trademark of Avo Biddle Instruments. ElectroMelt and RayChem are registered trademarks of Raychem Corporation.
R
O
Listed
877Z De-Icing and Snow­Melting Equipment
DESIG. 1B, 2B
Raychem Corporation Construction Products Group
40
®
should independently evaluate the suitability of each product for their application. Raychem makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Raychem's only obligations are those in the Standard Terms and Conditions of Sale for this product, and in no case will Raychem be liable for any inci­dental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Raychem reserves the right to make changes in materials or processing, which do not affect compli­ance with any applicable specification, without notification to the buyer.
Represented by: Industrial Heater
2941 Kate Bond Blvd. Suite 101 Bartlett, Tennessee 38033 Tel (888) 451-4328 Fax (901) 382-4766
All of the above information, including illustrations, is believed to be reliable. Users, however,
Loading...