Raychem E507S-LS Installation Manual

Page 1
Hazardous locations
WARNING:
E507S-LS
Line-Sensing Thermostat for Hazardous Locations Installation Instructions
DESCRIPTION
The nVent RAYCHEM E507S-LS thermostat is designed for controlling
heat-tracing systems in hazardous locations. TheE507S-LS can be used to control heat-tracing circuits in apipe-sensing mode (see Figure 1 on back page), to indicate low-temperature (see Figure 2) or
Pentair
high-temperature (see Figure 3) alarm conditions, or to control the coil on a contactor (see Figure 4).
Class I, Div. 1 and 2, Groups B, C, D Class II, Div. 1 and 2, Groups E, F, G Class III
8.0 in.
(202 mm)
Terminal
block
3⁄4 in. NPT conduit entry
4.5 in. (114 mm)
4.0 in. (102 mm)
Pentair
Adjusting knob
Removable knob cover
4.0 in. (102 mm)
4.0 in.
(102 mm)
2.0 in.
(50 mm)
Ø.28 in. (7 mm) mounting hole (4X)
4.5 in.
(114 mm)
6.6 in.
(168 mm)
1.2 in. (30 mm)
0.3 in. (9 mm)
SPECIFICATIONS
Enclosure NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware
Entries One 3/4 in. NPT conduit hub
Set point range 25°F to 325°F (–4°C to 163°C)
Sensor exposure
limits
Housing exposure
limits
Switch SPDT
Electrical rating 22 A at 125/250/480 Vac
Accuracy ±6°F (±3.3°C)
Deadband 2°F to 12°F (1.1°C to 6.7°C) above actuation
Set point repeatability
Sensor type Fluid-filled (silicone) bulb and 9 ft (2.7 m)
Sensor material 300 series stainless steel
Connection terminals
–40°F to 420°F (–40°C to 215°C)
–40°F to 140°F (–40°C to 60°C)
temperature
±3°F (±1.7°C)
capillary
Screw terminals, 10–14 AWG (2–5 mm2)
This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.
Component approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape to make connections.
Page 2
INSTALLING THE THERMOSTAT
1. Verify that the thermostat is
suitable for the area where it is to be
Pentair
installed.
2. Check the line voltage and the
heat-tracing load to ensure that the thermostat ratings are not exceeded.
3. Mount the unit using unistrut or the RAYCHEM universal mounting bracket (UMB-263757) in a position that prevents
condensation from draining into the enclosure from the
connecting conduit (see diagram above).
POSITIONING THE SENSOR BULB
4. Position the bulb in the lower quadrant of the pipe as shown in the diagrams to the left. Place the bulb
at least three feet from
pipe supports, valves, or other heat sinks; protect the capillary from kinks or bends less than 1⁄2 inch in radius.
90
Single traced
Heating cable Control thermostat bulb AT-180 tape
Double traced
Heating cable Control thermostat bulb AT-180 tape
Conduit drain
5. Tape the bulb firmly to the pipe with AT-180 aluminum tape, making sure there is no air space between the bulb and pipe. Donot overlap the bulb and heating cable with the same piece ofAT-180 tape.
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp (purchased separately) and install the clamp per the instructions provided. Make sure there is no air space between the tank wall and the bulb.
For installation on plastic tanks, contact nVent at (800) 545-6258.
SETTING THE THERMOSTAT
7. Set the thermostat dial to the desired temperature, then finish wiring.
8. Complete insulating. Do not turn the system on until the bulb is covered with thermal insulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle, check the fluid temperature with an immersed thermostat (best for plastic systems) or an accurate temperature indicator. Adjust
the dial setting if necessary.
WIRING
GFEPD
ØØ
208-V or 240-V supply – 240-V heater
or
G
120-V supply – 120-V heater
N
Ø
277-V supply – 240-V heater
C
NO NC
Power
G
connection
Thermostat bulb
Braid
(see "Positioning"
instructions above
for mounting details)
Heating Cable
Figure 1. Pipe-sensing
North America
Tel +1.800.545.6258 Fax +1.800.527.5703 [email protected]
GFEPD
208-V or 240-V supply
ØØ
or
ØGN
120-V supply – 120-V heater 277-V supply – 240-V heater
Control thermostat
Alarm
for mounting details)
Figure 2. Low-temperature alarm
Europe, Middle East, Africa
Tel +32.16.213.511 Fax +32.16.213.604 [email protected]
C
NO NC
Thermostat bulb
(see "Positioning"
instructions above
Control thermostat
GFEPD
208-V or 240-V supply
ØØ
or
ØGN
120-V supply – 120-V heater 277-V supply – 240-V heater
C
NO NC
Alarm
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Figure 3. High-temperature alarm
Asia Pacific
Tel +86.21.2412.1688 Fax +86.21.5426.3167 [email protected]
Control thermostat
GCNANBN
Braid
C
Heating cable A
GFEPD
Heating cable B
A
120- V supply – 120-V heater or
Ø
ØBØ
C
277-V supply – 240-V heater
120-V or 277-V coil
Heating cable C
NONC
C
NONC
C
Thermostat bulb (see "Positioning" instructions above for mounting details)
Figure 4. Contactor control
For switching heat-tracing loads greater than 22 A or switching multiple heat-tracing circuits.
Latin America
Tel +1.713.868.4800 Fax +1.713.868.2333 [email protected]
Control thermostat
nVent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.
Raychem-IM-H56913-E507SLS-EN-1805 PN 137863
Loading...