Raychem AMC1B Installation Manual

Page 1
WARNING:
8.0 in
(202 mm)
AMC-1B
Line-Sensing Thermostat for Nonhazardous Locations Installation Instructions
DESCRIPTION
The nVent RAYCHEM AMC-1B thermostat is designed for controlling heat-tracing systems in nonhazardous locations. The AMC-1B can be used to control heat- tracing circuits in a pipe-sensing mode (see Figure 1 on back), to indicate low-temperature (Figure 2) or high temperature (Figure 3) alarm conditions, or to control the coil on a contactor (Figure 4).
APPROVALS
SPECIFICATIONS
Enclosure Type 4X, polyurethane-coated cast-
Entries One 3/4 in. NPT conduit hub Set point range 25°F to 325°F (–4°C to 163°C) Sensor exposure
limits Housing exposure
limits Switch SPDT Electrical rating 22 A at 125/250/480 Vac Accuracy ±6°F (±3.3°C) Deadband 2°F to 12°F (1.1°C to 6.7°C) above actuation
Set point repeatability
Sensor type Fluid-filled (silicone) bulb and 9 ft (2.7 m)
Sensor material 300 series stainless steel Connection
terminals
aluminum housing, stainless-steel hardware
–40°F to 420°F (–40°C to 215°C)
–40°F to 160°F (–40°C to 71°C)
temperature ±3°F (±1.7°C)
capillary
Screw terminals, 10–14 AWG (2–5 mm2)
4.5 in (114 mm)
4.0 in (102 mm)
Removable knob cover
Terminal
block
3⁄4 in
NPT conduit entry
Adjusting knob
3.0 in (76 mm)
0.3 in
(9 mm)
R
4.0 in
(102 mm)
4.5 in
(114 mm)
Ø.28 in (7 mm) mounting holes (2X)
1.2 in
(30 mm)
0.8 in
(20 mm)
5.6 in
(142 mm)
This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.
Component approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape to make connections.
Page 2
THERMOSTAT INSTALLATION INSTRUCTIONS
Conduit drain
90
Heating cable
Control thermostat bulb AT-180 tape
AT-180 tape
Heating cable
Control thermostat bulb
Double Traced
Single Traced
1. Verify that the thermostat is suitable for the area where it is to be installed.
2. Check the line voltage and the heat-tracing load to ensure that the thermostat ratings are not exceeded.
3. Mount the unit using unistrut or the nVent RAYCHEM Universal Mounting Bracket (UMB-263757) in a position that prevents condensation from draining into the enclosure from the connecting conduit (see diagram above).
POSITIONING THE SENSOR BULB
4. Position the bulb in the lower quadrant of the pipe as shown in the diagrams to the left. Place the bulb at least three feet from pipe supports, valves, or other heat sinks; protect the capillary from kinks or bends
less than 1⁄2 inch in radius.
WIRING
5. Tape the bulb firmly to the pipe with AT-180 aluminum tape, making sure there is no air space between the bulb and pipe. Do not overlap the bulb and heating cable with the same piece of AT-180 tape.
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp (purchased separately) and install the clamp per the instructions provided. Make sure there is no air space between the tank wall and the bulb.
For installation on plastic tanks, contact nVent at
(800) 545-6258.
SETTING THE THERMOSTAT
7. Set the thermostat dial to the desired temperature, then finish wiring.
8. Complete insulating. Do not turn the system on until the bulb is covered with thermal insulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle, check the fluid temperature with an immersed thermostat (best for plastic systems) or an accurate temperature indicator. Adjust the dial setting, if necessary.
Power Supply
GFEPD
ØØ
208-V or 240-V supply – 240-V cable
or
G
120-V supply – 120-V cable
N
Ø
277-V supply – 240-V cable
C NO NC
Power
G
connection
Thermostat bulb
Braid
(see "Positioning"
instructions above
for mounting details)
Heating Cable
North America
Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nvent.com
Power Supply
GFEPD
208-V or 240-V supply
ØØ
or
ØGN
120-V or 277-V supply
Control thermostat
Alarm
for mounting details)
Figure 2. Low-temperatu re alarm
Europe, Middle East, Africa
Tel +32.16.213.511 Fax +32.16.213.603 thermal.info@nvent.com
C
NO NC
Thermostat bulb
(see "Positioning"
instructions above
Control thermostat
Power Supply
GFEPD
208-V or 240-V supply
ØØ
or
ØGN
120-V or 277-V supply
C NO NC
Alarm
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Figure 3. High-temper ature alarm
Asia Pacific
Tel +86.21.2412.1688 Fax +86.21.5426.3167 cn.thermal.info@nvent.com
Control thermostat
Power Supply
GFEPD
GCNANBN
C
Braid
Heating
cable A
Heating cable B
Figure 4. Contract contolFigure 1. Pipe-sensing
For switching heat-tr acing loads greater than 22 A or switching multiple heat-t racing circuits.
120-V supply – 120-V heating cable or
Ø
ØBØ
C
A
277-V supply – 240-V heating cable
120-V or 277-V coil
Heating cable C
NONC
C
NONC C
Thermostat bulb (see "Positioning" instructions above for mounting details)