Ravenheat WH System 3-20/4-24 INSTRUCTIONS FOR USE INSTALLATION AND SERVICING

Page 1
THE WHITE BOILER COMPANY
Installation and Servicing
To be left with the user
SYSTEM BOILER
HIGH EFFICIENCY
CONDENSING
WH System 3-20
Natural Gas (G20) II
LPG (G31) II
G.C. No.
2H3P
G. C. No.
2H3P
WH System 4-24
Natural Gas (G20) II
LPG (G31) II
Technical and illustrative data are not binding and can be modifi ed without prior notice. The descriptions and illustrations in the present booklet are for guidance purposes only.
THE WHITE BOILER COMPANY A Ravenheat Group Company CHARTISTS WAY, MORLEY, LEEDS, U.K. LS27 9ET TEL.: 0113 252 7007 - FAX: 0113 238 0229
Website: www.ravenheat.co.uk - E-mail: sales@ravenheat.co.uk
2H3P
G.C. No.
G. C. No.
2H3P
1312
Page 2
2
Page 3
EFFICIENCY CONDENSING BOILER
EFFICIENCY CONDENSING BOILER
FOR CENTRAL HEATING AN
Gas valve.
- Variable head pump suitable for any type of central heating system.
- Burner with fl ame stabiliser designed to operate under all thermal conditions.
- Unique
condensing heat exchanger
for high thermal fl ue transfer from gases to water.
- Built in frost protection.
- Printed circuit board designed to connect to room stat and/or timer.
- Aesthetically pleasing panels and controls.
- On/Off ball valves for shutting off gas and central heating.
- Safety relief valve (for safety discharge).
effi ciency of thi
HAZARDOUS TO HEALTH
IMPORTANT
HIGH
FOR CENTRAL HEA TING AND DOMESTIC HOT WATER
This new highly effi cient turbo-modulating boiler is designed to meet central heating requirements at super high effi ciency .
POSITION
The appliance is extremely versatile as it can be fi tted in almost any room. The appliance is room sealed so there is no contact
between the combustion chamber and living accommodation. This guarantees maximum safety and effi ciency. Each boiler has been designed and manufactured in our modern plant to exacting ISO 9001 discipline, all boilers carry full CE marking of approval. Technical sales and commercial services are available throughout the UK Mainland. This product is guaranteed by The White Boiler Company , Chartists W ay, Morley, LEEDS, LS27 9ET. Telephone No (01 13) 252 7007.
Guarantee is a full 12 months from date of purchase providing the appliance has been fi tted in accordance with these instructions
and relevant codes of practice.
-
- Variable head pump suitable for any type of central heating system.
- Burner with fl ame stabiliser designed to operate under all thermal conditions.
- Unique
- Built in frost protection.
- Printed circuit board designed to connect to room stat and/or timer.
- Aesthetically pleasing panels and controls.
- On/Off ball valves for shutting off gas and central heating.
- Safety relief valve (for safety discharge).
NOTE: Due to the high
terminal during operation.
It is the Users/Installers responsibility to ensure that the necessary personal protective clothing is worn when handling this appliance, and where applicable the pertinent parts that contain any materials that could be interpreted as being injurious to health and safety.
Gas valve.
condensing heat exchanger
COSHH - CONTROL OF SUBST ANCES
effi ciency of this boiler a plume of water vapour will form at the fl ue
MAJOR COMPONENTS
for high thermal fl ue transfer from gases to water.
IMPORT ANT
HAZARDOUS TO HEAL TH
GENERAL INFORMATION: GLUES AND SEALANTS - exercise caution - if these are still in liquid form. THE WHITE BOILER COMPANY use only high quality material for production of this product, in an effort to protect the environment wherever possible components should be recycled.
WARNING: when installing the appliance, care should be taken to avoid any possibility of injury when handling sheet metal parts.
3
Page 4
Users instructions
Sections Page Sections Page
1 Users guide 6 5 Installation 23
1.1 Introduction 6 5.1 Warning 23
1.2 Clearances around the appliance 6 5.2 Delivery 23
1.3 Operating safety checks to protect 6 5.3 Unpacking of boiler 23 your appliance (checking the system 5.4 Positioning of the boiler 23 pressure) 5.5 Optional extras 24
1.4 Appliance status indicators 7 5.6 Plume management kit 25
1.5 Digital display 7 5.7 Installing the appliance for rear flue 26
1.6 Boiler value 7 outlet
1.7 Diagnostic 7 5.8 Installing the appliance for side flue 26 outlet
2 General layout 8 5.9 Completing horizontal flue installation 29
2.1 Operating scheme 9 5.10 Intake and exhaust terminal 29
2.2 Introduction 10 components
2.3 Description of control system and 10 5.11 In-line flue bend and flue extension 29
sequence of operation 5.12 Vertical flue instructions 30
2.4 Operating mode 10 5.13 Installation instructions for twin flue 32
2.5 Central heating mode 10 pipe
2.6 General function 10 5.14 Twin flue instructions 32
2.6 Safety device 10 5.15 Exhaust / suction system with 33
2.7 Overall dimension 11 concentric pipes for flat or sloping
2.8 Available pump head 11 roofs.
2.9 Pressure drop across appliance 11 Extensions with two separate pipes
5.16 Exhaust / suction system with two 33
3 Technical data WH System 3-20 12 separate rated 80 dia. pipes natural gas exhaust on flat or sloping roof, suction
3.1 Technical data WH System 3-20 LPG 13 from vertical wall
3.2 Technical data WH System 4-24 14 5.17 Exhaust / suction system with two 33
natural gas separate pipes through a single
3.3 Technical data WH System 4-24 LPG 15 vertical wall
5.18 Installation instructions for 80/125 34
4 General requirements 16 concentric flue system
4.1 Safety 16 5.19 Assemble boiler 35
Gas safety (Installation and use) 5.20 Fitting valve pack 35
4.2 General information 16 5.21 Gas connection 35
4.3 Location of boiler 17 5.22 Central heating connection 35
4.4 Clearances around the appliance 17 5.23 Position of water/gas connections 35
4.5 Important notice 17 5.24 Safety valve discharge 36
4.6 Gas supply 17 5.25 Condensate drain connection 36
4.7 Flue system 18 5.26 Converting the appliance to different 37
4.8 Air supply 18 gas types
4.9 Water circulation (central heating) 18 5.27 Electrical connections 37
4.10 Flue terminal position 19 5.28 Outdoor sensor 37
4.11 Pipework 20
4.12 Boiler interlock control 20 6 Commissioning 38
4.13 Draining tap 20 6.1 Gas supply installation 38
4.14 Air release points 21 6.2 Electrical installation 38
4.15 Mains water feed: central heating 21 6.3 Initial filling of the system 38
4.16 Permissible methods of filling 21 6.4 Setting the heating system 38
4.17 Sizing of additional expansion vessel 22 design pressure
4.18 Installation to an existing central 22 6.5 Lighting the boiler 39
heating system 6.6 Check the gas pressure 39
4.19 Water treatment 23 6.7 Combustion check 39
4.20 Hard water areas 23 6.8 Checking the flue system 40
4.21 Electrical supply 25 6.9 Checking the heating thermostat 40
4
Page 5
Sections Page
6.10 C.H. high/low temperature 40
6.11 Range rating central heating 40
6.12 Test mode 40
6.13 Instructing the user 41
7 Servicing instructions 41
7.1 Boiler frost protection 42
7.2 To inspect and clean the appliance 42
8 Replacements of parts 43
8.1 General 43
8.2 To remove front panel 43
8.3 To remove left and right panels 43
8.4 To remove/replace spark igniter box 43
8.5 To remove/replace fan 44
8.6 To remove/replace the electrodes 44
8.7 To remove/replace the burner 44
8.8 To remove/replace the heat 44 exchanger
8.9 To remove/replace expansion 45 vessel
8.10 To remove/replace gas valve 45
8.11 To remove/replace the water 45 pressure transducer
8.12 To remove/replace safety relief valve 45
8.13 To remove/replace pump 46
8.14 To remove/replace automatic air vent 46
8.15 To remove/replace C.H. flow and 46 return sensors
8.16 To remove/replace flue sensor 46
8.17 To clean and remove/replace 46 condensing trap
8.18 To remove panel control box 47
8.19 To remove the instrument panel 47
8.20 To remove/replace control board 47
8.21 To remove/replace digital display 47 board
8.22 External control connection 47
9 Fault finding 48
10 Electrical system diagram 49
11 Spare parts 50
12 Benchmark commissioning 55 checklist details
12.1 Analyser check list 60
5
Page 6
A minimum bottom clearance of 80mm is
required between the appliance
USER CONTROLS
This appliance is designed to operate with the minimum of ease for the user. All the controls are found on the control panel on the front of the boiler.
1.3 OPERATING SAFETY CHECKS TO PROTECT YOUR APPLIANCE (CHECKING THE SYSTEM PRESSURE)
Before lighting the appliance check that the system pressure is not less than 1 bar. If it is below this it will be necessary to re-pressurise the system, between 1 and 1.5 bar to allow the boiler to operate. To view the system pressure press the P button once, this will display the current pressure
(if the pressure is on nil or too low, then error code 08E is displayed).
A fi lling device (fi lling loop) will have been fi tted on the system. This is usually on the pipework near to the boiler. If you are unsure of its position, or you cannot identify it, consult the installer who fi tted the boiler. The fi lling loop usually consists of two taps and a separate silver coloured braided fl exible pipe with connection fi ttings. Only when re-pressurising should the braided fl exible pipe be connected between the two taps, ensure that the nuts or the pipe ends are tightened onto the taps. Fully open one of the taps fi rst and then while monitoring the water pressure on the digital display, carefully open the second tap. When the water pressure is to a maximum of 1.5 bar turn both taps off. Disconnect the fl exible pipe from the taps (a small amount of water may be present). Keep the pipe in a safe place for future use. Press the P button once to return to the main screen.
In the event of an error, the appliance will show a sequence code displayed on the digital display of the control panel (fi g. 1). By pressing the “RESET“ button it is possible to relight the boiler (see page 51 for list of error codes).
1 USERS GUIDE
It is the law that all gas appliances are installed by a competent person, in accordance with the gas safety installation and to the current Gas Safety (Installation and Use) Regulations B.S.5440:2-(2000).
All registered installers carry a Gas Safe Register ID card and have a registration number. Both should be recorded in your boiler Log book. You can check your installer’s registration at www.gassaferegister.co.uk.
ESCAPE OF GAS Should a gas leak be suspected, contact your gas supplier without delay .
GAS EMERGENCY NUMBER: 08001 11999
Do NOT search for gas leaks with a naked fl ame.
Top clearance:
The top clearance should be a minimum of 125mm.
Bottom clearance:
required between the appliance and any surface, though 150mm is preferred whenever possible.
Front clearance: A minimum of 450mm is required in front of the appliance for access during servicing, the front clearance can be reduced when installed in a cupboard to 25mm from the access door.
of ease for the user. All the controls are found on the control panel on the front of the boiler.
1.3 OPERA TING SAFETY CHECKS T O PROTECT YOUR APPLIANCE (CHECKING THE SYSTEM PRESSURE)
WARNING: This appliance must be earthed.
1.1 INTRODUCTION Please carefully read the information given in this
booklet to help you gain maximum control from your appliance with minimum trouble and cost.
Y our White Boiler Company Condensing Low Nox has been designed to supply your Central Heating and hot water with separate indirect hot water storage cylinder is also incorporated in the system. The system boilers which incorporates a circulation pump, expansion vessel, safety valve, pressure gauge and electronic ignition.
PLEASE NOTE:
Due to the high ef ciency of this appliance and resulting
low fl ue gas exhaust temperature a white plume of condensation vapour (cool steam) will be emitted from the fl ue outlet terminal, this is quite normal. It will be particularly evident during periods of low outdoor temperature or when the boiler is working at its optimum performance (Plume Management kits are available on request).
IMPORT ANT: In the unlikely event of the exhaust ue gases exceeding
the overheat temperature setting, the boiler operation will be stopped to prevent damage to the appliance.
1.2 CLEARANCES AROUND THE APPLIANCE
Side clearance:
The position of the appliance must provide a minimum clearance of only 5mm as the side panels.
system pressure is not less than 1 bar. If it is below this it will be necessary to re-pressurise the system, between 1 and 1.5 bar to allow the boiler to operate. To view the system pressure press the P button once, this will display the current pressure
pressure is on nil or too low, then error code 08E is displayed).
A fi lling device (fi lling loop) will have been fi tted on the system. This is usually on the pipework near to the boiler . If you are unsure of its position, or you cannot identify it, consult the installer who fi tted the boiler. The fi lling loop usually consists of two taps and a separate silver coloured braided fl exible pipe with connection fi ttings. Only when re-pressurising should the braided fl exible pipe be connected between the two taps, ensure that the nuts or the pipe ends are tightened onto the taps. Fully open one of the taps fi rst and then while monitoring the water pressure on the digital display , carefully open the second tap. When the water pressure is to a maximum of 1.5 bar turn both taps off. Disconnect the fl exible pipe from the taps (a small amount of water may be present). Keep the pipe in a safe place for future use. Press the P button once to return to the main screen.
sequence code displayed on the digital display of the control panel (fi g. 1). By pressing the “RESET“ button it is possible to relight the boiler (see page 51 for list of error codes).
A minimum bottom clearance of 80mm is
USER CONTROLS
This appliance is designed to operate with the minimum
Before lighting the appliance check that the
In the event of an error, the appliance will show a
(if the
6
Page 7
1.4 APPLIANCE STATUS INDICATORS
maintain time and update parameters. The screen will display CLOW, after a few minutes of power su
2 - Water pressure: Shows the current pressure in the system. 3 - Heating: When there is a demand for heating, icon 3 will be fl ashing.
Use the arrow up and the arrow down
buttons, (item 3 and
1.7 DIAGNOSTIC
The display shows eventual error or faulty message.
Stop boiler: The boiler stops the operating cycle and waits for the disappearance of the cause of the error in order to go back to be operating mode.
Block boiler: The boiler requires a manual reset to become operational again.
Your boiler is equipped with a large LCD display that indicates the appliance operating status (fi g. 1).
After a long period switched off (no power supply), the fi rst switch on the internal backup circuit will charge in order to and update parameters. The screen will display CLOW, after a few minutes of power supply the display will be charged enough to allow all the functions.
KEY :
maintain time
During the initial charge time, the display doesn’t allow the visualisation and/or modifi cation function parameters. Instead other functions are working. When the appliance operates in rest mode, the display shows the boiler temperature and, alternatively the system water pressure.
1 - ON/OFF button Press the button also to confi rm selections.
2 - Press to reset the appliance if ever an error code is displayed.
3/4 - Temperature and function mode selectors. Press the arrow up or the arrow down to increase or decrease the central heating outlet temperature. Press also to show the boiler values or to show the options program when the digital display is in menu setting.
5 - Press to set the Central Heating Temperature required. Press the arrow up or the arrow down buttons to increase or decrease the temperature.
1.5 DIGITAL DISPLAY
KEY
1 - ON/OFF: When the appliance is ON icon 7 is displayed. 2 - Water pressure: Shows the current pressure in the system. 3 - Heating: When there is a demand for heating, icon 3 will be fl ashing. 4 - Anomaly - Lock - out - Test function. 5 - Temperature. 6 - Modulation fl ame level: When the burner is lit, 3 different levels on icon 8 are displayed.
Fig. 1
6 - Press to show the boiler values. Use the arrow up and arrow down buttons to select the following information: PBAR: water pressure SFAN: speed fan (the display shows 3 digits (e.g. 500 = 5000 rpm) TFLOW: fl ow temperature TRET: return temperature PWR: % power of modulation.
- Press for 3 seconds to enter into menu. Use the arrow up or arrow down buttons to select the following option:
- BOIL: It is possible to set the boiler parameters: C.H. max fan speed C.H. High/Low temperature: “1” high/“2” low.
1.6 BOILER VALUE
It is possible to show the boiler value. Press P button to show the boiler value.
Use the arrow up and the arrow down buttons, (item 3 and 4 fi g. 1) to show the following info:
PBAR: water pressure SFAN: speed fan TFlow: fl ow temperature TRet: return temperature PWR: % power of modulation.
Fig. 2
1.7 DIAGNOSTIC
The display shows eventual error or faulty message.
Stop boiler: The boiler stops the operating cycle and waits for the disappearance of the cause of the error in order to go back to be operating mode.
Block boiler: The boiler requires a manual reset to become operational again.
7
Page 8
2.0 GENERAL LAYOUT (Fig. 3)
KEY
1 - Condensate trap 2 - Gas valve 3 - Gas inlet 4 - Drain point 5 - CH fl ow 6 - By-pass
7 - Control board 8 - Safety pressure relief valve 9 - CH return 10 - Circulation pump
1 1 - Automatic air vent 12 - Condensate drain 13 - Expansion vessel 14 - Heat exchanger 15 - Spark electrode 16 - Sensing electrode 17 - Flue temperature sensor 18 - Spark igniter 19 - Fan 20 - Burner
Fig. 3
21 - Manual air vent 22 - Overheat cut off thermostat 23 - CH flow sensor 24 - CH return sensor
8
Page 9
temperature
2.1 OPERATING SCHEME (Fig. 4)
KEY
1 - Flue exhaust manifold 2 - Condensate drain 3 - CH return 4 - CH return sensor 5 - Heat exchanger 6 - CH fl ow 7 - Overheat cut off thermostat 8 - CH fl ow sensor 9 - Manual air vent
10 - Burner 1 1 - Spark electrode 12 - Sensor electrode
13 - Fan 14 - Flue 15 - Expansion vessel 16 - Automatic air vent 17 - Circulation pump 18 - Water pressure transducer
temperature sensor
Fig. 4
19 - Safety pressure relief valve 20 - Gas valve 21 - Gas service cock 22 - CH compression ball valves
9
Page 10
2.2 INTRODUCTION
2.3
DESCRIPTION OF CONTROL SYSTEM
AND SEQUENCE OF OPERATION
2.4 Operating mode
If the appliance is in demand for heat to
supply radiators, etc. , with the heating circuit fully cha
external timer if required. The
An overheat cut off thermostat acts to turn
off the burner to resettable “lockout”.
Y our White Boiler Company Condensing Low Nox has been designed to supply your Central Heating and hot water where a separate indirect hot water storage cylinder is also incorporated in the system. The system boilers which incorporates a circulation pump, expansion vessel, safety valve and electronic ignition.
2.3 AND SEQUENCE OF OPERATION
2.4 Operating mode
DESCRIPTION OF CONTROL SYSTEM
2.6 SAFETY DEVICE In central heating, safe operation is ensured
by a control board which shuts off the main burner, if the fan stops or the fl ue or combustion air intake duct is obstructed.
An overheat cut off thermostat acts to turn off the burner to resettable “lockout”. A safety valve is fi tted on the central heating
circuit set at 3 bar. A low water pressure switch set at 0.4 bar is
tted on heating circuit, to prevent the boiler
operating below this boiler system pressure.
If the appliance is in demand for heat to
supply radiators, etc. , with the heating circuit fully charged above 1 bar, the boiler will begin the ignition sequence and ignite.
As the heating sensor reaches temperature
the fan speed modulates to maintain the temperature set on the display panel. When starting, the fan will always start at the set-point speed.
The boiler is fi tted with an anti-cycling device
on the control board. This delays the boiler
from re-fi ring within 10 minutes. If the heating temperature goes 20°C below the set point, the burner restarts immediately .
2.5 GENERAL FUNCTION The instrument panel permits regulation of the
boiler to partial heating requirements, between
maximum and minimum settings. Air and gas are drawn by the fan for
combustion. The fan also forces exhaust gas through the fl ue
to the outside, this creates a lesser pressure in
the sealed combustion chamber, thus sucking
in combustion air, through the inlet duct. The boiler water temperature is automatically
controlled by a built in thermostat. Interior space temperature is set by the room
thermostat to be installed in the heating
system. The boiler already carries connection
terminals for this thermostat, as well as for
a
external timer if required. The burner continues to operate until it is stopped by the digital clock or one of the thermostats.
When the internal C.H. temperature sensor or the room thermostat intervenes the burner
shuts down. The fan stops but the pump continues to operate for 3 minutes.
The boiler also incorporates an anti-block
system which powers the pump every 24 hours, allowing it to operate for 2 minutes if the boiler has not been in use. This operation may in some cases be heard for a short period when the pump has been activated.
10
Page 11
2.7 OVERALL DIMENSION (Fig. 5)
Fig. 5
2.8 AVAILABLE PUMP HEAD (Fig. 6)
2.9 PRESSURE DROP ACROSS APPLIANCE (Fig. 7)
Fig. 6
Fig. 7
11
Page 12
3 TECHNICAL DATA
WH SYSTEM 3-20
TABLE 3/A
NATURAL GAS (G 20) П2H3P
NOMINAL HEAT INPUT NET QMS 20.0 kW MINIMUM HEAT INPUT NET 3.7 kW
NOMINAL HEAT OUTPUT 19.5 kW NOMINAL HEAT OUTPUT CONDENSING 21.4 kW MINIMUM HEAT OUTPUT 3.6 kW MINIMUM HEAT OUTPUT CONDENSING 4.0 kW
GAS RATE max 2.1 m AFTER 10 MINUTES min 0.4 m3/h
INLET PRESSURE 20 mbar
3
/h
FAN SPEED Max 4200 rpm - 140 Hz Combustion % CO
: 9.0 (+ 0.5 / - 0.5) Case ON
2
min 1300 rpm - 43 Hz 9.0 (+ 0.5 / - 0.5) Case OFF ELECTRICAL SUPPLY 230 V ~ 50 HZ
POWER CONSUMPTION 110 W EXTERNAL FUSE RATING 3A INTERNAL FUSE F1 - 3.15 A (20 mm to BS 4265)
DRY WEIGHT 25 kg WATER CONTENT 0.8 litre
GAS SUPPLY CONNECTION 15 mm compression isolating valve FLOW CONNECTION C.H. 22 mm compression isolating valve RETURN CONNECTION C.H. 22 mm compression isolating valve SAFETY DISCHARGE C.H. 15 mm copper pipe CONDENSATION DRAIN 3/4” (21.5 mm) push fi t over fl ow
MAX COLD WATER CAPACITY WITHOUT ADDITIONAL EXPANSION VESSEL 110 LITRE SEALED WATER SYSTEM C.H.
MAX PRESSURE PHS 2.5 bar MINIMUM WORKING PRESSURE 0.5 bar 7 LITRES EXPANSION VESSEL PRE-CHARGE-PRESSURE 0.5 bar
CENTRAL HEATING OPERATING TEMPERATURE MAX 80 °C min 35 °C MINIMUM FLOW RATE C.H. 350 I/h FLUE OUTLET NOM. DIAMETER 100 mm specially supplied with boilers (If required) DESTINATION: GB, IE CATEGORY II FLUE TYPE - C13 - C33 - C53 NOX 5 SEDBUK
2H3P
A IP X4 D
12
Page 13
3.1 TECHNICAL DATA
Combustion
WH SYSTEM 3-20
TABLE 3/B
LPG (G 31) П2H3P
NOMINAL HEAT INPUT NET QMS 20.0 kW MINIMUM HEAT INPUT NET 3.7 kW
NOMINAL HEAT OUTPUT 19.5 kW NOMINAL HEAT OUTPUT CONDENSING 21.4 kW MINIMUM HEAT OUTPUT 3.6 kW MINIMUM HEAT OUTPUT CONDENSING 4.0 kW
GAS RATE max G31 0.8 m AFTER 10 MINUTES min 0.15 m3/h
INLET PRESSURE G31 37 mbar
3
/h
FAN SPEED Max 4200 rpm - 140 Hz
Combustion % CO2 : 10.5 (+ 0.5 / - 0.5) Case ON
min 1300 rpm - 43 Hz 10.5 (+ 0.5 / - 0.5) Case OFF ELECTRICAL SUPPLY 230 V ~ 50 HZ
POWER CONSUMPTION 110 W EXTERNAL FUSE RATING 3A INTERNAL FUSE F1 - 3.15 A (20 mm to BS 4265)
DRY WEIGHT 25 kg WATER CONTENT 0.8 litre
GAS SUPPLY CONNECTION 15 mm compression isolating valve FLOW CONNECTION C.H. 22 mm compression isolating valve RETURN CONNECTION C.H. 22 mm compression isolating valve SAFETY DISCHARGE C.H. 15 mm copper pipe CONDENSATION DRAIN 3/4” (21.5 mm) push fi t over fl ow
MAX COLD WATER CAPACITY WITHOUT ADDITIONAL EXPANSION VESSEL 110 LITRE SEALED WATER SYSTEM C.H.
MAX PRESSURE PHS 2.5 bar MINIMUM WORKING PRESSURE 0.5 bar 7 LITRES EXPANSION VESSEL PRE-CHARGE-PRESSURE 0.5 bar
CENTRAL HEATING OPERATING TEMPERATURE MAX 80 °C min 35 °C MINIMUM FLOW RATE C.H. 350 I/h FLUE OUTLET NOM. DIAMETER 100 mm specially supplied with boilers (If required) DESTINATION: GB, IE CATEGORY II FLUE TYPE - C13 - C33 - C53 NOX 5 SEDBUK
2H3P
A IP X4 D
13
Page 14
3.2 TECHNICAL DATA
TABLE 3/C WH SYSTEM 4-24
NATURAL GAS (G 20) П2H3P
NOMINAL HEAT INPUT NET QMS 24.5 kW MINIMUM HEAT INPUT NET 4.1 kW
NOMINAL HEAT OUTPUT 23.9 kW NOMINAL HEAT OUTPUT CONDENSING 26.4 kW MINIMUM HEAT OUTPUT 4.0 kW MINIMUM HEAT OUTPUT CONDENSING 4.4 kW
GAS RATE max 2.6 m AFTER 10 MINUTES min 0.4 m3/h
INLET PRESSURE 20 mbar
3
/h
FAN SPEED Max 4200 rpm - 140 Hz Combustion % CO
: 9.0 (+ 0.5 / - 0.5) Case ON
2
min 1300 rpm - 43 Hz 9.0 (+ 0.5 / - 0.5) Case OFF ELECTRICAL SUPPLY 230 V ~ 50 HZ
POWER CONSUMPTION 119 W EXTERNAL FUSE RATING 3A INTERNAL FUSE F1 - 3.15 A (20 mm to BS 4265)
DRY WEIGHT 26 kg WATER CONTENT 0.8 litre
GAS SUPPLY CONNECTION 15 mm compression isolating valve FLOW CONNECTION C.H. 22 mm compression isolating valve RETURN CONNECTION C.H. 22 mm compression isolating valve SAFETY DISCHARGE C.H. 15 mm copper pipe CONDENSATION DRAIN 3/4” (21.5 mm) push fi t over fl ow
MAX COLD WATER CAPACITY WITHOUT ADDITIONAL EXPANSION VESSEL 110 LITRE SEALED WATER SYSTEM C.H.
MAX PRESSURE PHS 2.5 bar MINIMUM WORKING PRESSURE 0.5 bar 7 LITRES EXPANSION VESSEL PRE-CHARGE-PRESSURE 0.5 bar
CENTRAL HEATING OPERATING TEMPERATURE MAX 80 °C min 35 °C MINIMUM FLOW RATE C.H. 350 I/h FLUE OUTLET NOM. DIAMETER 100 mm specially supplied with boilers (If required) DESTINATION: GB, IE CATEGORY II FLUE TYPE - C13 - C33 - C53 NOX 5 SEDBUK
2H3P
A IP X4 D
14
Page 15
3.3 TECHNICAL DATA
TABLE 3/D WH SYSTEM 4-24
LPG (G 31) П2H3P
NOMINAL HEAT INPUT NET QMS 24.5 kW MINIMUM HEAT INPUT NET 4.1 kW
NOMINAL HEAT OUTPUT 23.9 kW NOMINAL HEAT OUTPUT CONDENSING 26.4 kW MINIMUM HEAT OUTPUT 4.0 kW MINIMUM HEAT OUTPUT CONDENSING 4.4 kW
GAS RATE max G31 1.0 m AFTER 10 MINUTES min 0.16 m
INLET PRESSURE G31 37 mbar G30 28-30 mbar FAN SPEED Max 4200 rpm - 140 Hz Combustion % CO2 : 10.5 (+ 0.5 / - 0.5) Case ON
min 1300 rpm - 43 Hz 10.5 (+ 0.5 / - 0.5) Case OFF ELECTRICAL SUPPLY 230 V ~ 50 HZ
POWER CONSUMPTION 119 W EXTERNAL FUSE RATING 3A INTERNAL FUSE F1 - 3.15 A (20 mm to BS 4265)
3
/h
3
/h
DRY WEIGHT 26 kg WATER CONTENT 0.8 litre
GAS SUPPLY CONNECTION 15 mm compression isolating valve FLOW CONNECTION C.H. 22 mm compression isolating valve RETURN CONNECTION C.H. 22 mm compression isolating valve SAFETY DISCHARGE C.H. 15 mm copper pipe CONDENSATION DRAIN 3/4” (21.5 mm) push fi t over fl ow
MAX COLD WATER CAPACITY WITHOUT ADDITIONAL EXPANSION VESSEL 110 LITRE SEALED WATER SYSTEM C.H.
MAX PRESSURE PHS 2.5 bar MINIMUM WORKING PRESSURE 0.5 bar 7 LITRES EXPANSION VESSEL PRE-CHARGE-PRESSURE 0.5 bar
CENTRAL HEATING OPERATING TEMPERATURE MAX 80 °C min 35 °C MINIMUM FLOW RATE C.H. 350 I/h FLUE OUTLET NOM. DIAMETER 100 mm specially supplied with boilers (If required) DESTINATION: GB, IE CATEGORY II FLUE TYPE - C13 - C33 - C53 NOX 5 SEDBUK
2H3P
A IP X4 D
15
Page 16
valuable
additional information:
equipment
4 GENERAL REQUIREMENTS
The installation of the boiler MUST be in accordance with the latest I.E.E. (BS 7671) Wiring Regulations, local building regulations,
Both the user and the manufacturer rely
heavily on the installer, whose job it is to
install the combination boiler and connect it to a correctly designed heating system. Acquaint yourself with the relevant British Standards concerning installation requirements. If you need further advice on any points contact the Technical Services Office on 0113 2527007 who would be pleased to help. It is recommended that tools suitable for brass fittings are used, and have a capability to accommodate hexagon sizes up to 50 mm.
4.1 SAFETY
Gas Safety (Installation and Use).
Regulations.
It is law that all gas appliances are installed
and serviced by a Gas Safe registered installer in accordance with the above regulations and these installation instructions. All registered installers carry a Gas Safe I.D. card and have a registration number. Both should be recorded in your Benchmark commissioning checklist. You can check your installer on the Gas Safe register (www.gassaferegister.co.uk). Failure to install appliances correctly could lead to prosecution. It is in your own interest, and that of your safety, to ensure the law is complied with. Check the boiler and flue is the correct type for installation undertaken.
4.2 GENERAL INFORMATION
heavily on the installer, whose job it is to
APPLICABLE CODES OF PRACTICE Ref: Documents.
Detailed recommendations are contained in the
The installation of the boiler MUST be in accordance with the latest I.E.E. (BS 7671) Wiring Regulations, local building regulations, bye-laws of the local water authority, the building regulations and the Building Standards (Scotland) and any relevant requirements of the local authority.
Both the user and the manufacturer rely install the combination boiler and connect
it to a correctly designed heating system. Acquaint yourself with the relevant British Standards concerning installation requirements. If you need further advice on any points contact the Technical Services Office on 0113 2527007 who would be pleased to help. It is recommended that tools suitable for brass fittings are used, and have a capability to accommodate hexagon sizes up to 50 mm.
following British Standard Codes of Practice:
BS6891:2005: Low pressure installation
pipes. BS6798: Installation of gas fired hot water
boilers of rated input not exceeding 70 kW.
BS5546: Installation of gas hot water supplies domestic purposes
(2nd Family Gases).
BS5440: Flues (for gas appliances of rated
input not exceeding 70 kW).
BS5440: 2 Ventilation (for gas appliances of
rated input not exceeding 70 kW).
BSEN 677: 1998 Gas fired central heating boilers.
I.S. 813: Domestic gas Installations. The followings standards give
additional information: BS 7074: Expansion vessels and ancillary
equipment for sealed water system. BS 7593: Treatment of water in domestic hot water and central heating system.
Health & Safety Document No.635
The Electricity at Work Regulations, 1989.
IMPORTANT: These appliances are CE certificated for
safety and performance. It is therefore important that no external control devices e.g. flue dampers, economisers etc., are directly connected to this appliance unless covered by these Installation and Service Instructions or as otherwise recommended by The White Boiler Company in writing. If in doubt please enquire.
Any direct connection of a control device not
approved by The White Boiler Company could invalidate the certification and the normal appliance warranty.
It could also infringe the Gas Safety
regulations and the above regulations.
NOTE: The White Boiler Company WH System 3-20/4-24 system boiler has been tested and
examined by CERTIGAZ, and is certified to comply with PrEN 483.
Manufacturers instructions must NOT be taken
in any way as overriding statutory obligations.
If in doubt on any point please consult The
White Boiler Company.
valuable
16
BSEN12828: Design for water based heating systems.
BSEN12831: Heating systems in buildings, Method for calculation of the design heat load.
BSEN14336: Installation & commissioning of water based heating systems.
Page 17
4.3 LOCATION OF BOILER
The White Boiler Company
system boiler m
responsibility of the Gas Installer to size the gas installation pipework in accordance with BS 6891:2005. Whilst the principle of the 1:1 gas valve ensures t White Heat range
Siting of The White Boiler Company WH System 3-20/4-24 system boiler must be as follows. The position of installation should be within the
building, unless otherwise protected by a suitable enclosure.
Adequate space for installation, servicing and air circulation around the boiler must be allowed
for.
3-20/4-24 and vertical wall capable of adequately supporting the weight of the boiler and any ancillary equipment. The appliance may be fitted on a combustible
For electrical safety reasons there must be no access available from the back of the boiler.
The boiler must not be fitted outside. LPG versions of this appliance shall not be
4.4 CLEARANCES AROUND THE APPLIANCE
Side clearance:
The position of the appliance must provide a minimum clearance of 5mm as the side panels.
Top clearance: The top clearance should be a minimum of 125 mm.
Bottom clearance: A bottom clearance of 80mm is required
between the appliance and any surface. Though 150mm is preferred whenever possible.
Front clearance: A minimum of 450mm is required in front of the appliance for access during servicing, the front clearance can be reduced when installed in a cupboard, to 25mm from the access door.
4.5 IMPORTANT NOTICE For installation into timber framed buildings,
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland the electrical provisions of the Building Regulations
The White Boiler Company WH System
system boiler must be fitted on a flat
wall insulation between the wall and the boiler is not necessary, unless required by the local authority.
installed in cellars or basements.
please refer to the Institute of Gas Engineers Document IGE/UP/7.
applicable in Scotland, with respect to the installation of the combination boiler in a room or internal space containing a bath or shower.
Where a room sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control, utilising mains electricity should be situated so that it cannot be touched by a person using a bath or shower. A compartment when used to enclose the system boiler MUST be designed and constructed specifically for this purpose. An existing cupboard, or compartment, may be used provided it is modified accordingly. Samples of the WH System 3-20/4-24 system boiler have been examined by CERTIGAZ notification body, and are certified to comply with the essential requirements of the gas appliance.
Directive 90/396/EEC, the Low Voltage. Directive 72/23/EEC and shows compliance
with the Electro Magnetic Compatibility.
Directive 89/336/EEC and are therefore permitted to carry the CE Mark.
The appliance has been tested and approved
by the WRc as meeting the requirements of G3 and L of the Building regulations and water Bylaws Scheme - Approved Products.
4.6 GAS SUPPLY A gas meter is connected to the service pipe
by the Local Gas Region or the Local Gas Region contractor. An existing meter should be checked preferably by the Gas Region to ensure that the meter is adequate to deal with the rate of gas supply required for all appliances it serves. Installation pipes should be fitted in accordance with BS 6891:2005. Pipework from the meter to the boiler must be of adequate size (22mm) min to within at least one metre of the boiler, (15mm) min. can then be used for remaining pipe work to the appliance. A smaller size than the boiler inlet gas connection should not be used. The complete installation must be tested for soundness as described in the above code.
. N.B. It is the
to size the gas installation pipework in accordance with BS 6891:2005. Whilst the principle of the 1:1 gas valve ensures the White Heat range is able to deliver the full output at an inlet pressures as low as 14 mbar, other gas appliances in the property may not be as tolerant.
When operating pressures are found to be
below the minimum meter outlet of 19 mbar these should be checked to ensure this is adequate for correct and safe operation.
responsibility of the Gas Installer
17
Page 18
Allowing for the acceptable pressure loss of 1
d at its
ocated in a place where it is likely to cause a nuisance in cold and/or humid weather as water vapour may condense on leaving the flue terminal.
The effect of such pluming must be
considered.
The terminal must not be closer than 25 mm (1 inch) to any combustible material for
less than 2 metres high. The part number is
PRO110100.
Fit only recommended
FLUE TERMINAL
GUARD
times.
mbar across the installation pipework, it can be assumed that a minimum permitted operating pressure of 18mbar (nat gas) will be delivered to the inlet of the appliance. (reference BS 6400-1 Clause 6.2 Pressure Absorption).
The external gas cock could further reduce the
operating pressure when measure point. The pressure drop is relative to the heat input to the boiler (kW), refer to graph below.
d at its test
IMPORTANT NOTICE: If the fl ue terminates
below a balcony, above the ground, above a fl at roof to which people have access, then a suitable terminal guard must be fi tted if
less than 2 metres high. The part number is
PRO110100.
Fit only recommended
GUARD bby securing concentrically around
terminal with screws. Available on request from:
The White Boiler Company Chartists Way, Morley, Leeds, West Yorkshire ENGLAND LS27 9ET - UK
Tel. 0113 252 7007
IMPORTANT:
The following notes are intended for general guidance. The boiler MUST be installed so that the terminal is exposed to external air.
It is important that the position of the terminal allows the free passage of air across it at all times.
FLUE TERMINAL
4.7 FLUE SYSTEM The terminal should be located where
dispersal of combustion products is not impeded and with due regard for the damage
or discolouration that might occur to building products in the vicinity (section 4.10).
The terminal must not be l
where it is likely to cause a nuisance in cold and/or humid weather as water vapour may condense on leaving the flue terminal.
The effect of such pluming must be
considered.
The terminal must not be closer than 25 mm (1 inch) to any combustible material for protection of combustibles, refer to BS 5440.1. Where a flue terminal is installed less than
1000 mm. from a plastic, or painted gutter; or 500 mm from painted eaves, an aluminium shield 1000 mm. long, should be fitted to the underside of the gutter or painted surface.
Pluming will occur at the terminal so, where
possible, terminal positions which could cause a nuisance should be avoided.
The flue must be installed in accordance with
the recommendations of BS 5440: Part 1.
ocated in a place
Minimum acceptable spacing from the terminal to obstructions and ventilation openings are specifi ed in section 4.10.
Note positions: Due to the terminal design, installation is possible with clearances less than those specifi ed in BS 5440, Part 1
NOTE: The flue must be terminated in a place not likely to cause a nuisance.
A concentric vertical flue kit is available for
longer flueing applications (see table 5 page
26).
For further details see vertical flue installation
instructions.
4.8 AIR SUPPLY The following notes are intended for general
guidance.
The room sealed fan flued boiler does not
require a permanent air vent for combustion air supply.
Where installed in a cupboard or compartment
ventilation is not required.
4.9 WATER CIRCULATION (Central heating)
18
IMPORTANT NOTES: For greater fl ue lengths see alternative fl ue instructions. Flue must be positioned in a place not likely to cause a nuisance from pluming.
Detailed recommendations are given in BS6798
2009/5449:1990 - BSEN12828 - BSEN12831
- BSEN14336 (for smallbore and microbore central heating systems). The following notes are given for general guidance.
Page 19
4.10 FLUE TERMINAL POSITION
19
Page 20
and aluminium
4.11 PIPEWORK
to ensure air is carried naturally to air release
points and water flows naturally to drain taps. It should be ensured as far as possible that the appliance’ s heat exchanger is not a natural collecting point for air except where providing useful heat. Pipes should be insulated to prevent heat loss and to avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
IMPORTANT:
4.12 BOILER INTERLOCK CONTROL
Copper tubing to BSEN 1057:1 2006, BSEN 1172, BSEN 1652 and BSEN 1653, is recommended for water pipes. Jointing should be either with capillary soldered or with compression fittings. Where possible pipes should have a gradient
IMPORTANT: A minimum length of 1 metre of copper pipe
MUST be fitted to both flow and return connections from the boiler before connection to any plastic piping.
The water through the appliance heat exchanger
If the volume of circulating water is too low, the
This appliance is designed to work on a two
to ensure air is carried naturally to air release
points and water flows naturally to drain taps. It should be ensured as far as possible that the appliance’ s heat exchanger is not a natural collecting point for air except where providing useful heat. Pipes should be insulated to prevent heat loss and to avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
circuit must exceed the min. 2.38 gals/min. (650 I/h) when the burner is firing. It is important to ensure that this rate is achieved when sections of the system are shut off either manually or by automatic controls.
boiler water temperature will rise too rapidly. This could cause noise in the system or even cause the safety thermostat to trip.
pipe system as shown in fig.6.
Central heating system controls should be installed to ensure the boiler is switched off
when there is no demand for heating, in
compliance with Building Regulations. The boiler has its own built in bypass. If the system has thermostatic radiator valves on
all radiators, or two port valves, then a bypass
circuit must be fitted with an automatic bypass
valve to ensure a flow of water should all valves
be in the closed position (fig. 6). It is important that the system is flushed
thoroughly before the appliance is fitted or
left to operate (as recommended in BS 7593)
in order to maintain an efficiently operating
heating system. For replacement installations,
the system MUST be flushed with the old boiler
insitu, in order to prevent system debris. Once
the system has been flushed, an inhibitor (suitable for stainless steel exchanger) should be added (see section
4.18).
4.13 DRAINING TAP These must be located in accessible positions
to permit the draining of the whole system.
The taps must be at least 15 mm nominal size
and manufactured in accordance with BS 2870
1980.
and aluminium heat
20
Fig.6
Page 21
4.14 AIR RELEASE POINTS
7 L of expansion water
If the appliance is connected to a system with
an unusually high water content, calculate the total expansion (see table 4) and add additional sealed expansion capacity as appropriate (Fig. 7). In general, modern systems below 7 L should not present any problem.
4.15
MAINS WATER FEED. CENTRAL HEATING
There must be no direct connection to the
mains water supply, even through a
non-return valve, without the approval of the
Local Water Authority.
These must be fitted at all high points where
air will naturally collect, and must be sited to facilitate complete filling of the system.
The appliance has an integral sealed expansion
vessel to accommodate the increase of water volume when the system is heated.
It can accept up to If the appliance is connected to a system with
an unusually high water content, calculate the total expansion (see table 4) and add additional sealed expansion capacity as appropriate (Fig. 7). In general, modern systems below 7 L should not present any problem.
4.15
There must be no direct connection to the non-return valve, without the approval of the
MAINS WATER FEED. CENTRAL HEATING
mains water supply, even through a Local Water Authority.
7 L of expansion water
Fig.7
Fig.8
4.16 PERMISSIBLE METHODS OF FILLING Figure depicts the requirements of Diagram
R24.2a of the Water Supply (Water Fittings) regulations 1999.
21
Page 22
If the capacity of the central heating system should exceed 110 L, an additional vessel should be installed on the return to the combination boiler from the heating system (fig. 7). Guidance on vessel sizing is given (see table 4).
Reference should be made to British Gas
Publications.
Debris from the system can damage the
boiler and reduce the efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance guarantee and contravene the Building Regulations.
It is recommended that you fit a primary water cleanser to the system. We recommend fitting a filter that will help remove both magnetite and non-magnetic debris.
4.17 SIZING OF ADDITIONAL EXPANSION VESSEL TABLE 4
Deduct from the value given in the table the 7 litre vessel supplied.
Safety
valve setting (bar)
Vessel charge
pressure (bar)
Initial system
pressure (bar)
T otal water
content of system
Litres
25 50
75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500
3.0
0.5 1.0 1.5
0.5 1.0 1.5 2.0 1.0 1.5 2.0 1.5 2.0
EXPANSION VESSEL VOLUME (LITRES)
2.1
4.2
6.3
8.3
10.4
12.5
14.6
16.7
18.7
20.8
22.9
25.0
27.0
29.1 31 .2
33.3
35.4
37.5
39.6
41.6
3.5
7.0
10.5
14.0
17.5
21.0
24.5
28.0 31 .5
35.0
38.5
42.0
45.5
49.0
52.5
56.0
59.5
63.0
66.5
70.0
6.5
12.9
19.4
25.9
32.4
38.8
45.3 51 .8
58.3
64.7 71 .2
77.7
84.1
90.6 97 .1
103.6
110.1
116.5
123.0
125.9
13.7
27.5
41.3
55.1
68.9
82.6
96.4
110.2
124.0
137.7 151 .5
165.3 179 .1
192.8
206.6
220.4
239.2
247.9
261 .7
275.5
2.7
5.4
8.2
10.9
13.6
16.3
19.1
21.8
24.5
27.2
30.0
32.7
35.7 38 .1
40.9
43.6
46.3
49.0
51 .8
54.5
4.7
9.5
14.2
19.0
23.7
28.5
33.2
38.0
42.7
47.5
52..2
57.0 61 .7
66.5 71 .2
76.0
80.7
85.5
90.2
95.0
10.3
20.6
30.9
41.2
51.5
61.8
72.1
82.4
92.7
103.0
113.3
123.6
133.9
144.2
154.5
164.8
175.1
185.4
195.7
206.0
3.9
7.8
11.7
15.6
19.5
23.4 27 .3
31.2 35 .1
39.0
42.9
46.8
50.7
54.6
58.5
62.4
66.3
70.2
74.1
78.0
107.6
115.8
124.1
132.4
140.7
148.9
157.2
165.5
8.3
16.5
24.8
33.1
41.3
49.6
57.9
66.2
74.5
82.7
91.0
99.3
For system volumes other than those given above, multiply the system volume by the factor across
Note: This pressure can be increased up to 1.5 bar to suit high static head situations.
Reference should be made to British Gas
If the capacity of the central heating system should exceed 110 L, an additional vessel should be installed on the return to the combination boiler from the heating system (fig. 7). Guidance on vessel sizing is given (see table 4).
Publications. Draining taps should be at least
0.0833 0.140 0.259 0.551 0 .109 0.190 0.412 0.156 0.331
1/2” in BSP nominal size and be in accordance with BS 2879.
4.18 INSTALLATION TO AN EXISTING CENTRAL
HEATING SYSTEM
The system boiler is designed to operate on a
sealed system only. Therefore if the existing system is of the open water type it will have to
be modified to comply with BS 5376 Part 2. Before installing a new system boiler to an existing system, flush out the old system with a recommended descaling agent. If the boiler is installed in an existing system any unsuitable additives MUST be removed by thorough cleaning, and flushing out the old system with recommended descaling agent.
22
. BS 7593:2006 details the steps necessary to clean domestic central heating system. Also check pipework and renew any corroded pipework or fittings. Valve glands must be repacked or replaced wherever necessary and any defective controls exchanged.
boiler and reduce the efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance guarantee and contravene the Building Regulations.
water cleanser to the system. We recommend fitting a filter that will help remove both magnetite and non-magnetic debris.
Debris from the system can damage the
It is recommended that you fit a primary
Page 23
4.19 WATER TREATMENT
manufacturer’s instructions.
4.20 HARD WATER AREAS
If the area of installation is recognised as a hard water area, it is recommended that a suitable water treatment device is installed on the mains supply.
with a connection to a 230 V ~ 50 Hz single phase supply.
The supply must be fused at 3 A.
NOTE: The method of connection to the electricity supply MUST facilitate complete electrical isolation of the appliance, by the use of a fused, double pole isolator, having a contact separation of at least 3 mm in all poles. The point of connection to the electricity supply must be readily accessible and
The appliance carton contains:
a) Boiler fully assembled with fl ue adaptor b) Installation instructions, user instructions and Benchmark log book c) White paper template d) Guarantee card e) Polythene bag containing:
-
1-15mm gas service valve
- 2-22mm compression ball valves
complete with 3/4” washers
- 2 fi xing bolts and wall plugs
5 INSTALLATION
This boiler has an aluminium heat exchanger. The White Boiler Company recommend the use
of FERNOX or SENTINEL, or other treatment products recognised by The White Boiler Company which must be used in accordance with the
4.20 HARD WATER AREAS
a hard water area, it is recommended that a suitable water treatment device is installed on the mains supply. The water hardness can be
4.21 ELECTRICAL SUPPLY
Warning: this appliance must be earthed
External wiring to the appliance must be carried out by a competent person and be in accordance with the current I.E.E. Regulations and local regulations which apply. The White Boiler Company boiler is supplied connection to a 230 V ~ 50 Hz single phase supply.
If the area of installation is recognised as
determined by using the standard test paper or by referring to local water authority.
NOTE: The method of connection to the electricity supply MUST facilitate complete electrical isolation of the appliance, by the use of a fused, double pole isolator, having a contact separation of at least 3 mm in all poles. The point of connection to the electricity supply must be readily accessible and adjacent to the appliance except, where the appliance is installed in a bathroom.
The current electrical IEE Wiring regulations must be followed in GB.
manufacturer’s instructions.
with a
The supply must be fused at 3 A.
5.1 WARNING It is MOST IMPORTANT that this appliance is
installed in a HORIZONTAL POSITION, with the flue air duct passing through the wall.
Make sure the flue is at a 1.5° incline, rising
from the boiler with 50 mm. Flue terminal diagram states 1.5° - 25 mm, fall back on flue (fig. 9).
5.2 DELIVERY
b) Installation instructions, user instructions and Benchmark log book c) White paper template d) Guarantee card e) Polythene bag containing:
-
complete with 3/4” washers
- 2 fi xing bolts and wall plugs
IMPORTANT NOTES:
The appliance carton contains:
a) Boiler fully assembled with fl ue adaptor
1-15mm gas service valve
- 2-22mm compression ball valves
This appliance will produce a plume of
condensation in cool weather. This is due to the High Effi ciency and hence low fl ue gas temperature of the boiler. A plume management kit is available. (see section 5.6 fi g 12)
5.3 UNPACKING OF BOILER
IMPORTANT: With regard to the Manual Handling
Operations, 1992 Regulations, the following lift operation exceeds the recommended weight for a one man lift.
- Stand the boiler carton upright.
- Open the top of the carton.
- Rest the carton on the fl oor (keeping the fl aps open).
- Turn the carton over with the boiler inside and then pull the carton up away from the boiler.
- Rest the boiler on its back on the fl oor to prepare it for installation.
Fig.9
5.4 POSITIONING OF THE BOILER Unscrew the two lower screws that secure the
front panel and pull forward and lift up (fig. 39). Unscrew the 4 screws that fasten the lower
grating on the casing and remove it from the
bottom of the casing. Make sure the casing and screws are put to
one side in a safe place.
23
Page 24
(horizontal length) (horizontal length)
fl ue, the maximum
ue length is 8 metres
5.5 OPTIONAL EXTRAS
HORIZONTAL FLUE KIT BOX CONTAINING (Fig 10):
52 - Self-cutting joint securing screw 57 - Elbow header 59 - Rubber seal Ø 60
56 - Rubber seal Ø 100 60 - Fumes sample point 61 - Flue exhaust duct 62 - Air intake duct 69 - Air sample point 127 - Terminal Rubber wall seal
IMPORTANT: Please lubricate the internal part of the seals before fitting.
Generally speaking, oils and greases are not suitable for the “peroxide -EPDM”, therefore we suggest a correct lubrication using silicon-substances, for instance “Silikon Spray“ (Arexons).
Fig 10
FLUE EXTENSION BOX CONTAINING (Fig. 11): 1000 mm fl ue extension duct as an extra cost only when requested for side and vertical fl ue applications.
59 - Rubber seal Ø 60 63 - Air intake duct extension
64 - Flue exhaust duct extension
WARNING: With horizontal concentric ue length is 8 metres, duct extension can be used with the standard fl ue (see table 5).
fl ue, the maximum
Fig 11
TYPE OF FLUE SYSTEM (All types) - minimum and maximum distance TABLE 5
Flue type C
13
C33 C
53
Flue Diameter 60/100 80/125 60/100 80/125 80 mm
Minimum length (m) 0.3 0.3 1.0 1.0 0.5 Maximum length (m) 8.0 23.0 13.0 26.0 43.0
(concentric) (concentric) (concentric) (concentric) single pipe
(horizontal length) (horizontal length) (vertical length) (vertical length)
1
Equivalent length of 45° bend (m) 0.5 1.25 0.5 1.25 1.25 Equivalent length of 90° bend (m) 1.0 2.5 1.0 2.5 2.5
24
Page 25
5.6 PLUME MANAGEMENT KIT (Fig 12)
Max 6000 mm fl ue extension duct as an extra cost only when requested to reduce pluming nuisance of condensation from 60/100 horizontal concentric fl ue.
Plume Management Kit TABLE 6
Maximum Length (mm) 6000 minimum length (mm) 500
Equivalent length of 45° bend (mm) 500 Equivalent length of 90° bend (mm) 1000
The Maximum permitted fl ue length is measured from the centre line of the fl ue terminal to the top of the outlet terminal
IMPORTANT : Max fl ue length must not exceed 6 m with a horizontal concentric 60/100 fl ue of 3 m ( L )
Plume Management Kit Part No. Part. No. Description
TER110101 1 metre high plume kit containing: (Fig. 12) n. 1 terminal bend n. 1 90° elbow bend n. 2 45° bend n. 1 metre 60 M-F fl ue length n. 1 fl ue length bracket
FLUE EXHAUST DEFLECTION BEND (Fig 12a)
Flue exhaust defl ection bend are also available. These come in both 45° and 90° degree versions. These bends fi t directly onto the fl ue exhaust terminal to defl ect the fl ue gas plume in an upward or sideways direction. Although they are not substitute for a plume kit, they can be considered useful where condensate pluming is causing a nuisance or can be used to eliminate condensate collecting on the end of the horizontal ue terminal.
Fig. 12
CUR110050 45° fl ue exhaust defl ection bend (Fig. 12a)
CUR110100 90° fl ue exhaust defl ection bend (Fig. 12a)
IMPORTANT: Please lubricate the internal part of the seals before fitting.
L+L max 6000 mm minimum plume kit length 500 mm
Fig. 12a
25
Page 26
5.7 INSTALLING THE APPLIANCE FOR REAR
Mark the two holes for the top fixing bolts to fix the boiler on the wall as well as the centre of the flue duct.
- Detach the template from the wall.
- Use a 10 mm. dia drill to make the 2 holes. Insert the plastic expansion plugs.
- Cut or core drill a 105 mm dia hole for
inserting the flue duct. Fit the elbow header into the flue flange on
the top of the boiler, positioning it towards the required direction (fig 13).
Important: Make sure that the inner 60 mm diameter of the elbow header is inserted fully into the flue manifold, and the flue manifold rubber seal is correctly fitted. (Fig 17 item 65)
If using the horizontal flue duct and it is too long it can be shortened. Should it be necessary to cut the flue always cut on right angles and ensure the cut is de-burred.
Note
: Add 30 mm to overall flue length to
allow for terminal wall cover.( fig.10 item 127).
Insert the flue assembly locating it onto the
wall. Lift the boiler on the wall, locating onto the top
two fixing bolts. Tighten the two bolts using a spanner to secure to the wall.
Working above the boiler pull the flue exhaust
duct towards the boiler in order to engage tube
(fig. 18 item 61) into its header.
Position flue into elbow header and push so as
to locate inner and outer flue correctly ensuring a good seal is made with O-rings. Tighten the two screws on the flue flange to secure the elbow header in place and fix securing screw.
Fit the terminal rubber wall seal and if
necessary terminal guard.
Extension kits are available to order for flue extension of up to a total overall length of 8 metres (fig.18).
Each extension length extends the pipe by
approximately 1000 mm long up to a maximum of seven extensions.
Extensions must be installed with the widened
end of pipe and the tapered end of the flue pipe aimed towards the exhaust terminal.
g.14.
- Mark the two fixing bolt securing holes on the wall and extend the axis of the flue duct hole to the side wall ensuring it i
fixing bolts.
In
Important: Make sure that the inner 60 mm diameter of the elbow header is inserted fully into the flue manifold, and the flue manifold rubber seal is correctly fitted. (Fig 17 item 65)
FLUE OUTLET (Fig. 13, 16, 17, 18). FOR APPLIANCE CLEARANCES SEE SECT. 4.4 AND SECT. 4.10
Use adhesive tape to attach the template to
the wall, making sure that the centre line is vertical and that the clearance distance is no less than that shown in fig. 13.
- fix the boiler on the wall as well as the centre of the flue duct.
Important: Make sure that the inner 60 mm diameter of the elbow header is inserted fully into the flue manifold, and the flue manifold rubber seal is correctly fitted. (Fig 17 item 65)
If using the horizontal flue duct and it is too long it can be shortened. Should it be necessary to cut the flue always cut on right angles and ensure the cut is de-burred.
allow for terminal wall cover.( fig.10 item 127).
Mark the two holes for the top fixing bolts to
- Detach the template from the wall.
- Use a 10 mm. dia drill to make the 2 holes. Insert the plastic expansion plugs.
- Cut or core drill a 105 mm dia hole for
inserting the flue duct. Fit the elbow header into the flue flange on
the top of the boiler, positioning it towards the required direction (fig 13).
Note
: Add 30 mm to overall flue length to
Extensions must be installed with the widened
end of pipe and the tapered end of the flue pipe aimed towards the exhaust terminal.
IMPORTANT: Inline flue bend - 1000 mm must be deducted from overall length for each 90°bend. Obtuse flue bend - 500 mm must be deducted from overall length for each 135° bend (see table 5).
5.8 INSTALLING THE APPLIANCE FOR SIDE FLUE OUTLET (Fig. 14, 15, 16, 17, 18)
- Attach the template to the wall with adhesive tape, making sure that the centre line is
vertical and that the distance from the centre line to the nearest side wall is not less than measurement in fi
- Mark the two fixing bolt securing holes on the wall and extend the axis of the flue duct hole to the side wall ensuring it is horizontal.
- Make sure flue slopes 1.5° down towards
the boiler and that there is a 25 mm fall per metre of the flue length.
- Trace the centre of the flue duct hole and measure distance from the corner of the wall (fig.14), measure the distance (127 mm) between the centre of flue duct hole to the corner.
Detach the template from the wall.
-
Use a 10 mm. dia drill to make the 2 holes for
the
fixing bolts. plugs. Core drill a 105 mm side wall for inserting the flue duct.
g.14.
Insert the plastic expansion
dia. hole in the
wall. Lift the boiler on the wall, locating onto the top
two fixing bolts. Tighten the two bolts using a spanner to secure to the wall.
duct towards the boiler in order to engage tube Position flue into elbow header and push so as
necessary terminal guard.
extension of up to a total overall length of 8 metres (fig.18).
Each extension length extends the pipe by
Insert the flue assembly locating it onto the
Working above the boiler pull the flue exhaust
(fig. 18 item 61) into its header. to locate inner and outer flue correctly ensuring
a good seal is made with O-rings. Tighten the two screws on the flue flange to secure the elbow header in place and fix securing screw.
Fit the terminal rubber wall seal and if
Extension kits are available to order for flue
approximately 1000 mm long up to a maximum of seven extensions.
Fit the elbow header into the flue flange on the top of the boiler, positioning it towards the required direction.
diameter of the elbow header is inserted fully into the flue manifold, and the flue manifold rubber seal is correctly fitted. (Fig 17 item 65)
If using the horizontal flue duct and it is too long it can be shortened. Should it be necessary to cut the flue always cut on right angles and ensure the cut is de-burred.
Note: Add 30 mm to overall flue length to allow for terminal rubber wall seal ( fig.10 item 127).
Important: Make sure that the inner 60 mm
26
Page 27
REAR FLUE OUTLET
Lift the boiler on the wall, locating onto the two fixing bolts. Tighten the two bolts using a spanner to secure to the wall.
Working above the boiler pull the flue duct towards the elbow in order to engage the tube into its header (fig.10). Position the flue elbow in line with the flue and push so as to locate inner and outer flue correctly. Ensuring a good seal is made with O-rings. Tighten the two screws on the flue flange to secure the elbow header in place.
IMPORTANT:
Terminal rubber wall seal must be fitted (item 127 fig.10).
Each extension length extends the pipe
by approximately 1000 mm long up to a maximum of seven extensions.
Pipeline length can be established using the
instructions in section 5.5. Extensions must be installed with the widened end of the air intake pipe and the tapered end of the flue pipe aimed towards the exhaust terminal.
Extensions must be joined together with the standard terminal pipe, and inserted in each other as far as they can go.
If an extension must be shortened, this must
be done from the straight end, and not from the widened or tapered end. To measure the pipeline properly all components must be assembled and total length measured before cutting. The straight end of the extension connects to the boiler. The flue output and air intake pipes fits into the boiler header until it stops (fig.17 - 18).
When cutting both inner and outer ducts of
the extension, always ensure that the reduced end (male) of the inner and outer duct are square and to the same length.
NOTE: minimum side clearances of 5 mm as the side panels.
The position of the appliance must provide
Fig 13
Insert the flue assembly into the wall, making
sure it will not interfere when fixing the boiler on the wall.
towards the elbow in order to engage the tube into its header (fig.10). Position the flue elbow in line with the flue and push so as to locate inner and outer flue correctly. Ensuring a good seal is made with O-rings. Tighten the two screws on the flue flange to secure the elbow header in place.
Terminal rubber wall seal must be fitted (item 127 fig.10).
Pipeline length can be established using the
Lift the boiler on the wall, locating onto the two fixing bolts. Tighten the two bolts using a spanner to secure to the wall.
Working above the boiler pull the flue duct
IMPORTANT:
Each extension length extends the pipe
by approximately 1000 mm long up to a maximum of seven extensions.
instructions in section 5.5. Extensions must be installed with the widened end of the air intake pipe and the tapered end of the flue pipe aimed towards the exhaust terminal.
If an extension must be shortened, this must
When cutting both inner and outer ducts of
Extensions must be joined together with the standard terminal pipe, and inserted in each other as far as they can go.
be done from the straight end, and not from the widened or tapered end. To measure the pipeline properly all components must be assembled and total length measured before cutting. The straight end of the extension connects to the boiler. The flue output and air intake pipes fits into the boiler header until it stops (fig.17 - 18).
the extension, always ensure that the reduced end (male) of the inner and outer duct are square and to the same length.
27
Page 28
SIDE FLUE OUTLET
All joints must be sealed with the rubber seals
supplied.
It is important to put the centering spacer, supplied
with the unit, inside between the two pipes, from the side opposite the extension’s straight end.
NOTE: minimum side clearances of 5 mm as the side panels.
Fig. 14
The position of the appliance must provide
NOTE: A suitable support bracket (flue bracket)
is available from The White Boiler Company and should be used to support the flue length at least every one metre preferably at each joint this bracket should be secured to wall and flue duct.
Fig. 15
28
Page 29
50 - Flue fl ange
5.9 COMPLETING HORIZONTAL FLUE INSTALLATION.
Ensure the flue system has been checked for
soundness, is stable and secure. Where the horizontal flue terminal passes through the external wall, it is essential that the flue must be sealed on both in exterior and interior part of the wall and fix securing screw.
The terminal rubber must also be fitted (fig. 16-17 item 127).
5.10 INTAKE AND EXHAUST TERMINAL COMPONENTS
Fig 16
Fig.17
KEY
52 - Self-cutting joint securing screw
50 - Flue fl ange 56 - Rubber seal Ø 100 57 - Elbow header 58 - Header gasket
60 - Fumes sample point
61 - STD fl ue exhaust duct 62 - Terminal 63 - Flue extension 64 - Flue exhaust duct extension
59 - Rubber seal Ø 60
5.11 IN-LINE FLUE BEND AND FLUE EXTENSION
IN-LINE FLUE BEND Measure the distance between the flue bends or
the flue/terminal assembly. The measurements should be taken from the outer edge of the flue and bend (fig. 18).
IMPORTANT: Please lubricate the internal part of the seals before fitting.
65 - Flue manifold rubber seal 66 - Securing screw
67 - Flue temperature sensor 69 - Air sample point 127 - Terminal Rubber wall seal
52 - Self-cutting joint securing screw
49 - In-line Flue Bend 56 - Rubber seal Ø 100 59 - Rubber seal Ø 60 63 - Air intake duct extension 64 - Flue exhaust duct extension
Fig.18
29
Page 30
5.12 VERTICAL FLUE INSTRUCTION ONLY (Fig. 19-20-21)
permissible flue
length is not exceeded (fig. 20 and see table 5).
- Mark the two wall fixing bolt holes
- Detach the template from the wall.
- Use a 10mm dia. drill to make the 2 holes.
- Insert plastic expansion plug.
- Screw in the two coach bolts.
- Position the flue sample point starter (straight flue header which must be fitted) and fix the securing screw on the flue adaptor appliance
SEE SECT. 4.10 FOR PERMISSIBLE FLUE POSITION
IN-LINE FLUE BEND - 1000 mm MUST BE DEDUCTED FROM OVERALL LENGTH FOR EACH 90° BEND OBTUSE FLUE BEND - 500 mm MUST BE DEDUCTED FROM OVERALL LENGTH FOR EACH 135° BEND.
The vertical flue kit is intended for use where a horizontal flue outlet is not possible or desired. The vertical flue can be used either with a flat roof or a pitched roof (maximum pitch 60°). Where a straight vertical flue is not possible or desired, an offset vertical flue can be used in conjunction with a side horizontal flue extension piece and in-line 135°/90° flue bend (fig. 19).
IMPORTANT NOTES : For greater flue length see twin flue or concentric 80/125 flue instructions
Proceed with installation as detailed in section 5 ignoring all references to horizontal flue installations. Use adhesive tape to attach the template to the wall, making sure that the centre line is vertical and that the flue centre line is virtually below the point at which the flue will exit the roof.
L + L = 8m Max
Fig. 19
30
Fig. 20
Straight Flue Straight Flue Offset Flue Offset Flue L = 12 m Max L = 12 m Max L = 10 m Max L = 11 m Max plus Terminal plus Terminal plus 2 bend 90° plus 2 bend 45° and Terminal and Terminal
- Ensure that the maximum length is not exceeded (fig. 20 and see table 5).
- Mark the two wall fixing bolt holes
- Detach the template from the wall.
- Use a 10mm dia. drill to make the 2 holes.
- Insert plastic expansion plug.
- Screw in the two coach bolts.
- Position the flue sample point starter (straight
flue header which must be fitted) and fix the securing screw on the flue adaptor appliance
permissible flue
(fig. 22 item 66), and ensure that the gasket
is correctly fitted.
Important: Make sure that the inner 60
mm diameter of the straight flue header is inserted fully into the flue manifold, and the flue manifold rubber seal is correctly fitted. (fig 22 item 65)
Page 31
Cut a 105 mm diameter hole through the ceiling and/or
the
roof, at the point previously marked. Fit a roof flashing slate to the roof, available from The White Boiler Company. Insert the Vertical Flue terminal assembly through the flashing slate from the outside. Lift the boiler on the wall, locating onto the top two fixing bolts. Tighten the two bolts using a spanner to secure to the wall. Measure the vertical distance between the top of the flue and the bottom of the flue terminal assembly (fig.
21). The measurements should be taken from the outer diameter of the flue. NOTE: Where this length does not match any standard combination of the extensions, only be cut to the required length (fig. 23). When cutting both inner and outer ducts of the extension, always cut on spigot side, and they must be de-burred.
ACCESSORIES CONCENTRIC FLUE 60/100 EXTRAS: TABLE 7
the extension can
Part. No. Description PR5094110A Straight fl ue header / sample point
60/100 PRFE Flue Extension 60/100 L1000 PR45FBI 45° bend 60/100 PR90FBI 90° Elbow bend 60/100 PR5023016 Horizontal terminal 60/100 TER110200 Vertical fl ue Terminal
Starting at the appliance end, assemble the extension duct sections, making each inner and outer (flue) joint by inserting the spigot end into the socket end of the next tube, making sure the seal rings are correctly located (fig. 22). Make sure that the entire flue is adequately supported. Use at least one bracket for each extension used. Ensure that all inner flue connections have a good fit/seal, and that the space clips in each extension are correctly positioned.
Fig.22
Fig. 21
Straight Flue Offset Flue Offset Flue L = 12 m Max L = 12 m Max L = 11 m Max plus Combi ridge plus 2 bend 90° plus 2 bend 45° and Combi ridge and Combi ridge
Fig.23
KEY
52 - Self-cutting joint securing screw
56 - Flue adapter 58 - Header gasket 59 - Rubber seal Ø 60 60 - Fumes sample point 63 - Flue extension 64 - Flue exhaust duct extension 65 - Flue manifold rubber seal 66 - Securing screw 68 - Flue starter 69 - Air sample point
IMPORTANT: Please lubricate the internal part of the seals before fitting.
31
Page 32
Make sure that the fl ue manifold rubber seal is located into the fl ue manifold, and lubricate the internal part of the seal before assembly. Locate the header gasket on the twin fl ue header and push into the fl ue adaptor making sure that the inner plastic exhaust
5.13 INSTALLATION INSTRUCTIONS FOR TWIN FLUE PIPE (ECCENTRIC FLUE DUCT SYSTEM)
TABLE 8
Part. No Description SDO110050 Twin fl ue header F80/F80
PRO110200 Straight pipe L.1000 80 CUR110150 90° elbow bend 80 CUR110200 45° bend 80 GRI110050 Air inlet terminal 80 GRI110100 Exhaust terminal 80 TER060110 Vertical eccentric fl ue Terminal
5.14 TWIN FLUE INSTRUCTIONS This part of the installation manual covers the
installation and fi xing instructions of the twin fl ue eccentric fl ue duct systems only. When ordering twin fl ue it must be stated for WH System 3-20/4-24 range. Typical installation procedures are illustrated by drawings.
Remove the front panel of the case (sect.8.1). Unscrew the screw (item 66 fi g. 17) on the ue adapter .
Fig. 24
IMPORTANT: Please, lubricate the internal part of the seals before fitting.
IMPORTANT: These instructions must be read in
conjunction with the main installation and servicing instructions. As with all fl ues the kits must be installed taking due account of the current issue of BS 5440 parts 1 & 2 and timber frame housing DM2 is referenced to the Institute of Gas Engineers Document IGE/UP/7. Also note that the requirements will vary depending upon the kit being installed. Guidance is provided but unless otherwise stated, always comply with the recommendations of the relevant codes of practice.
Make sure that the fl ue manifold rubber seal is located into the fl ue manifold, and lubricate the internal part of the seal before assembly. Locate the header gasket on the twin fl ue header and push into the fl ue adaptor making sure that the inner plastic exhaust locates rmly in the outlet spigot of the fl ue manifold, and screw the securing screw that secure the
twin fl ue header on the boiler. Locate the 2 x 80 mm O-rings in the twin flue header and lubricate the internal part of the seal before assembly to ensure easy snug fi t.
Figures show the versatility of this flueing
system. Measurements and bends must be
calculated correctly to ensure the maximum
flue length is not exceeded.
All located O-rings must be lubricated with a
silicone grease to ensure a snug fit.
NOTE: Exhaust flue must slope 1.5° down
towards the boiler 25 mm/m fall per metre of
flue length.
Spacing Clips
Spacing Clips are available on request should
they be required.
NOTE: for eccentric vertical flue a 125mm
(5 in) diameter flashing plate will be required.
32
Page 33
IMPORTANT:
See fi g. 6 for terminal clearances.
Chartists way, Morley, Leeds, West Yorkshire
See fi g. 6 for terminal clearances.
-
IMPORTANT NOTICE:
- Inlet and exhaust terminals must never be installed on opposite walls of the building (PrEN 483).
- If the ue terminates less than 2 m above a balcony, above
the ground, or above a fl at roof to which people have access, then a suitable terminal guard must be fi tted.
- Fit only recommended fl ue terminal guard by securing concentrically around terminal with screws.
Fig. 25
5.15
Exhaust/suction system with concentric pipes for fl at or sloping roofs. Extensions with two separate pipes (fi g. 24).
Maximum distance: T = L = 21 + 21 = 42 metres + Terminal Minimum distance: L = 0.5 + 0.5 = 1 metre + Terminal
Exhaust terminal must not be cut.
NOTE:
- If bends are used in the exhaust fl ue then horizontal sections must be avoided and there must be a 1.5° slope
- Towards the boiler 25 mm fall per metre.
5.16
5.17
Exhaust/suction system with with two separate rated 80 dia. pipes exhaust on fl at or sloping roof, suction from vertical wall (fi g. 25).
Maximum distance D = L + L1 = 39.5 metres + Terminal Minimum total length = 2 metre NOTE: Exhaust fl ue must slope 1.5° down towards the boiler 25 mm fall per metre.
Exhaust/suction system with two separate pipes through a single vertical wall (fi g. 26).
Maximum distance: D = L + L1 = 37 metres Minimum distance: D = L + L1 = 1 metre Min distance between pipe 50 mm.
Fig. 26
IMPORTANT: Please lubricate the internal part of the seals before fitting.
Available on request from: THE WHITE BOILER COMPANY
Chartists way, Morley, Leeds, West Yorkshire ENGLAND LS27 9ET - U.K. Tel: 0113 252 7007
33
Page 34
installed on either a flat roof or a pitched roof (maximum pitch 60°). Where a straight vertical flue is not possible or desired, an offset vertical flue can be used in conjunction with a side horizontal flue extension piece and an inline 135°/90° flue bend (fig. 27).
See fi g. 6 for terminal clearances.
Available on request from: THE WHITE BOILER COMPANY Chartists way, Morley, Leeds, West Yorkshire ENGLAND LS27 9ET - U.K. Tel: 0113 252 7007
5.18 INSTALLATION INSTRUCTIONS FOR CONCENTRIC 80/125 FLUE SYSTEM
The vertical 80/125 flue kit is intended for use
where a horizontal 60/100 flue outlet is not possible or desired. The vertical flue can be roof or a pitched roof (maximum pitch 60°). Where a straight vertical flue is not possible or desired, an offset vertical flue can be used in conjunction with a side horizontal flue extension piece and an inline 135°/90° flue bend (fig. 27).
IMPORTANT:
See fi g. 6 for terminal clearances.
-
IMPORTANT NOTICE: When using our vertical fl ue kit the 125 mm x 100 reducer is supplied complete with the vertical terminal simply remove this and fi x it into the straight fl ue header (which must be fi tted) on the top of the boiler.
installed on either a flat
Fig. 27
L + L = 23.5m Max
Fig. 28
Straight Flue Straight Flue 90° Offset Flue 135° Offset Flue L = 25m Max L = 25m Max L = 20m Max L = 22.5m Max plus Terminal plus Terminal plus Terminal plus Terminal
NOTE : If using Flue arrangement in g. 27 then the 125x100 Flue reducer
TABLE 9
Part No Description PR5094110A Straight fl ue header / sample point 60/100
must be purchased separately.
IMPORTANT: Please lubricate the internal part of the seals before fitting.
PRO110300 Flue Extension 80/125 L1000 RID110050 125/80 to 100/60 Flue reducer CUR110250 45° fl ue bend 80/125 CUR110300 90° elbow fl ue bend 80/125 TER010050 Horizontal Flue Terminal 80/125 TER110200 Vertical Flue Terminal 80/125
Available on request from: THE WHITE BOILER COMPANY Chartists way, Morley, Leeds, West Yorkshire ENGLAND LS27 9ET - U.K. Tel: 0113 252 7007
TEG060050 Flashing sleeve/slate
34
Page 35
5.19 ASSEMBLE BOILER
Fit the gas service cock to the boiler via the union nut and connect gas pipe. Do not over tighten
5.20 Fitting valve pack Remove plastic caps from boiler connection and fit valves as per fig. 29 using the washers provided.
It is recommended fitting the valve pack before installing the boiler on the wall.
5.21 GAS CONNECTION (Fig. 29)
A minimum working gas pressure of 20 mbar (8
in w.g.) must be available at the boiler inlet at full flow rate (37 mbar for propane).
(Also see section 4.6)
Important consult (sect 4.6).
5.22 CENTRAL HEATING CONNECTION
(Fig. 29) Before any central heating connections are
made to the boiler all system valves should be opened and the system thoroughly flushed out with cold water.
Fit the gas service cock to the boiler via the union nut and connect gas pipe. Do not over tighten and use another spanner as a counter force to avoid straining internal connections.
- Connect the central heating return pipe to the isolating cock.
- Connect the central heating flow pipe to the isolating cock marked CHF.
- Pipe dimensions and positions are marked on template supplied (fig. 30).
Fig.29
5.23 POSITION OF WATER/GAS CONNECTIONS
Fig. 30
35
Page 36
5.24 SAFETY VALVE DISCHARGE The safety valve is located to the rear
(15 mm copper) to permit a discharge pipe to be connected. When connecting ensure the
discharge pipe does not restrict access. The discharge should terminate facing downward exterior to the building in a position where discharging (possibly boiling water & steam) will not create danger or nuisance, an easily visible position, and not to cause damage to electrical components or wiring. The discharge must not be over an entrance or a window or any other type of access.
5.25 CONDENSATE DRAIN CONNECTION The condensate drain connection is a flexible
3/4” pipe and is therefore adjustable Fig. 29.
Notes: ALL EXTERNAL PIPE RUNS MUST BE IN ACCORDANCE WITH BS 6798
1 - INTERNAL TO SINK WASTE UPSTREAM OF SINK WASTE TRAP
The drain pipe should have a fall of a least
2.5° away from the boiler. Condensate should, if possible be discharged into the household internal drainage system.
If this is not practicable, discharge can be
allowed into the external household drains or a purpose designed soak away.
It is recommended that any external condensate
drain pipe is insulated and also must be of 40 mm (1” 1/2) diameter, through the outside wall to prevent freezing in adverse weather conditions.
It is not necessary to provide air breaks or extra
traps in discharge pipe as there is already a 125mm high trap inside the boiler.
Fitting an extra trap may cause the boiler siphon
to work incorrectly.
Refer to BS5546 or BS6798 for advice on
disposal of boiler condensate.
2 - INTERNAL CONNECTION TO SOIL VENT STACK Make connection to SVP using a solvent welded saddle.
Fig. 31
Fig. 32
36
Page 37
3 - TERMINATION TO SOAK AWAY 4 - TERMINATION TO DRAIN / GULLY
authorised by th
as in section
6.9 and table 10, and adjust to correct data settings information.
8.2. You can slide towards the top the instrument panel box and push the retaining latches and remove the instrument panel (sect. 8.24).
- Heat resistant flexible cable is fitted between the isolator and the terminal block which is a 3 core cable
Fig. 33
5.26 CONVERTING THE APPLIANCE TO DIFFERENT GAS TYPES
Boilers are factory set to work for use
with Natural gas or LPG gas. This is
clearly marked on the packaging and
boiler data badge.
To convert a boiler from one gas to another this operation must be carried out by a qualified competent person, with all necessary equipment
authorised by the manufacturer.
It will also be necessary to obtain a data badge conversion kit directly from The White Boiler Company.
1 - Remove the case. 2 - Check gas mains pressure at the gas valve test nipple upstream (fig.35) with boiler operating (sect.6.8). 3 - Adjust fan speed as sect.3 (technical data). 4 - Measure the level of CO2
6.9 and table 10, and adjust to correct data settings information. 5 - Affix new data badge. 6 - Replace in reverse order.
5.27 ELECTRICAL CONNECTIONS IMPORTANT:
Electricity supply must be as specified in
clause (sect. 4.22).
- When controls external to the appliance are required, design of the external electrical circuits should be undertaken by a
competent person. In accordance with the
IEE wiring regulations.
as in section
Fig. 34
Factory fitted internal wiring must not be disturbed when wiring external controls.
- To gain access to the electrical box remove the front panel of the case as described in clauses sect. You can slide towards the top the instrument panel box and push the retaining latches and remove the instrument panel (sect. 8.24).
- Heat resistant flexible cable is fitted between the isolator and the terminal block which is a 3 core cable of 0.75 mm2 (24x0,2 mm) to BS 6500.
Make sure all wires to the appliance are routed away from sharp edges and hot surfaces.
The cable must be fastened with its cord anchorage and connected so that it should take the cable slip from the anchorage until the current carrying conductors become taut before the earthing conductor. Securely tighten all terminal screws and arrange the cable with slack between the cord anchorage and the terminal block.
WARNING: If the supply cord is damaged, it must be replaced by a service engineer (supply cord available from The White Boiler Company).
5.28 OUTDOOR SENSOR For use, consult Outdoor Sensor
instructions.
8.2.
37
Page 38
6 COMMISSIONING
Continue filling the system until 1.5 bar
register on digital display.
Press the P button once again to return to the main screen.
1.5
Each boiler has been through a rigorous operational testing procedure at our factory and should not require any further
adjustment, if you are not the installer but
just commissioning this boiler check that the boiler has been installed in accordance with these instructions, and the integrity of the flue system and the flue seals, as described in the flue installation section.
6.1 GAS SUPPLY INSTALLATION Inspect the entire installation including the
gas meter, test for soundness and purge, all as described in BS 6891.
In Ireland refer to IS 813:2002.
6.2 ELECTRICAL INSTALLATION
6.4 SETTING THE HEATING SYSTEM DESIGN PRESSURE
The design pressure must be min. 1bar and
max. 1.5 bar. These figures are read on the
digital display by pressing the P button.
The actual reading should ideally be 1 bar +
the height in metres to the highest point of the system above the base of the appliance (up to max of
N.B.: The safety valve is set to lift at 3 bar (30 mt/42.5 psi). To lower the system pressure to the
required value remove at the drain point (fig. 36) or drain on the heating circuit.
GAS VALVE
1.5 bar).
Preliminary electrical systems checks to
ensure electrical safety shall be carried out by a competent person.
ALWAYS carry out the preliminary electrical system checks: i.e. earth continuity, polarity, resistance to earth and short circuit, using a suitable test meter.
Connecting the external switch live. To create a demand the boiler requires a
230V switch live from the external controls. This switch live simply needs connecting to the connection on the bottom left side of the PCB housing. (see system diagram fig. 55 and fig. 38).
6.3 INITIAL FILLING OF THE SYSTEM
Open central heating flow and return valves
Unscrew the cap on automatic air release valve positioned on the top of the pump housing one full turn (leave open permanently).
- Close all air release taps on the central
heating system. Press the P button to display the current pressure (code E8 will display if the pressure is nil/too low).
- Gradually open stopcock at the filling point
connection to the central heating system until water is heard to flow.
- Starting with the lowest radiator open each
air release tap in turn. Close when the water is clear, free of bubbles and flows out. In the same way release air from any high points in the pipework.
-
Continue filling the system until 1.5 bar register on digital display. button once again to return to the main screen. Then turn off the filling points stopcock.
- Inspect the system for water soundness and remedy any leaks discovered.
Press the P
Fig. 35
Fig. 36
Fig. 38
38
Page 39
- To select the minimum heating temperature press the radiator button.
IMPORTANT:
Before lighting the boiler select the minimum
heating temperature (see section 1.4 key 5). This must be left at minimum for approx 5 mins to purge air safely from the boiler.
To select the minimum heating temperature press the radiator button.
- Press arrow up and arrow down buttons to adjust.
- The digital display shows the current set temperature in central heating.
- After a few seconds the digital display shows the central heating temperature in demand (C.H. icon flashing, item 3 fig. 2).
- The fan starts and after a few seconds or so the digital led display will show that the ignition has commenced.
- The ignition control will automatically make
three attempts to start, if it doesn’t start this
may be due to air in the gas supply line. If the burner fails to light, the digital led display and fan will stop, and the display will show the lockout code (E1 depicts flame failure).
- If necessary push the boiler Reset button
(item 2 fig.1) and the boiler will restart automatically.
- After the boiler has lit, allow to warm at
minimum temperature setting to purge any air from the system.
- Once the system has been purged of air, set the heating temperature to the desired setting.
6.6 CHECK THE GAS PRESSURE
Check the gas mains pressure at the gas valve inlet pressure test point (fig.35) with the boiler operating at full rate. Check with the Local Gas supplier if the pressure differs significantly from 20 mbar G20 (natural gas), 37 mbar G31 (propane). With leak detection fluid test for gas tightness
of all gas components and joints.
IMPORTANT: The Gas Valve Throttle adjuster is required to be sealed with tamper proof paint after adjustment (fig. 35).
carrying out a combustion
measurement should have been assessed
6.7
COMBUSTION CHECK
Check all gas carrying components along
with, the combustion of the appliance which
should be checked as follows. Remove the front panel of the appliance. Ensure the boiler and external controls
are calling for heat. Turn on the electrical
supply.
open the hot water tap at maximum flow
rate. Wait at least five minutes or until the
unit has reached its operating temperature. Unscrew the test sample screw on the boiler
elbow bend (item 60 fig. 10). Measure the
level of CO
2
. Check the reading against the
corresponding value in table 10 and with
reference to page 63.
It is essential that this test is repeated
with the casing on as this will check the
integrity of the flue.
6.5 LIGHTING THE BOILER
6.7
COMBUSTION CHECK
Before lighting the boiler make sure that the
heating circuit flow and return valves are open.
- Ensure all external controls are calling for heat.
- To select the minimum heating temperature
press the radiator button.
IMPORTANT:
Before lighting the boiler select the minimum
heating temperature (see section 1.4 key 5). This must be left at minimum for approx 5 mins to purge air safely from the boiler.
-
To select the minimum heating temperature press the radiator button.
- Press arrow up and arrow down buttons to adjust.
- The digital display shows the current set temperature in central heating.
- After a few seconds the digital display shows the central heating temperature in demand (C.H. icon flashing, item 3 fig. 2).
- The fan starts and after a few seconds or so the digital led display will show that the ignition has commenced.
- The ignition control will automatically make
three attempts to start, if it doesn’t start this
may be due to air in the gas supply line. If the burner fails to light, the digital led display and fan will stop, and the display will show the lockout code (E1 depicts flame failure).
- If necessary push the boiler Reset button
(item 2 fig.1) and the boiler will restart automatically.
- After the boiler has lit, allow to warm at
minimum temperature setting to purge any air from the system.
- Once the system has been purged of air, set the heating temperature to the desired setting.
6.6 CHECK THE GAS PRESSURE
Check the gas mains pressure at the gas valve inlet pressure test point (fig.35) with the boiler operating at full rate. Check with the Local Gas supplier if the pressure differs significantly from 20 mbar G20 (natural gas), 37 mbar G31 (propane). With leak detection fluid test for gas tightness
of all gas components and joints.
The Gas Valve Throttle adjuster is required to be sealed with tamper proof paint after adjustment (fig. 35).
IMPORTANT:
Remove the front panel of the appliance. Ensure the boiler and external controls
Unscrew the test sample screw on the boiler
corresponding value in table 10 and with
Check all gas carrying components along
with, the combustion of the appliance which should be checked as follows.
are calling for heat. Turn on the electrical supply.
open the hot water tap at maximum flow
rate. Wait at least five minutes or until the unit has reached its operating temperature.
elbow bend (item 60 fig. 10). Measure the level of CO
reference to page 63.
. Check the reading against the
2
It is essential that this test is repeated
with the casing on as this will check the integrity of the flue.
If adjustment proves necessary then
proceed as follows.
IMPORTANT: Any adjustment to the gas
valve should only be carried out by a qualified person. Referring to the table 10, adjust the maximum level of CO
with the Throttle
2
using a 4 mm hex on the gas valve (fig.35). Anti-clockwise to decrease CO Clockwise to increase CO
.
2
2
After any new regulation wait to stabilise for about one minute. Replace the front cover.
TABLE 10
CO2%
NATGAS 9.0(+0.5/Ͳ0.5) LPG 10.5(+0.5/Ͳ0.5)
IMPORTANT: Do not insert the analyser
probe into the sample point immediately or leave in long periods. This will prevent saturation of the analyser.
During the calibration function the
combustion ratio may increase for a short time while the boiler performance is optimised.
The person measurement should have been assessed as competent in the use of a flue gas
carrying out a combustion
analyser.
The flue gas analyser used should be one
meeting the requirements of BS7927 or BS­EN50379-3 and be calibrated in accordance with the analyser manufacturer’s requirements.
39
Page 40
Once the process of commissioning the boiler is complete, the
commissioning engineer MUST complete the relevant section in the Benchmark log book.
ATTENTION
sec 1.5 key 5 to set heating
temperatures).
6.10 C.H. HIGH/LOW TEMPERATURE
The boiler comes set, in Central heating, at the 80 °C flow temperature. It is possible to adjust the max set-point to max 50°.
- Press P button (item 8 fig. 1) for 3
seconds to enter in menu.
- Use arrow up and arrow down buttons (item 3 and 4 fig. 1), to select BOIL.
- Press enter and reset buttons (item 1 and 8 fig. 1) together and enter button again.
- Use arrow up and arrow down buttons (item 3 and 4 fig. 1) to select the following option:
- PM4 (“1” high temperature, “2” low temperature).
been adjusted by the manufacturer during production. If the adjustments need to be made again, observe the following procedures.
The adjustment to fan speed must be strictly in the sequence indicated, by qualified personnel only.
To check max fan speed, see tables 11:
- Press P button (item 8 fig. 1) for 3
seconds to enter in menu.
- Use arrow up and arrow down buttons (item 3 and 4 fig. 1), to select BOIL.
- Press enter and reset buttons (item 2 and 3 fig. 1) together and enter button again.
- Use arrow up and arrow down buttons (item 3 and 4 fig. 1) to select the followings options:
- PM1 C.H. max fan speed.
the arrow up and the arrow down buttons, (item 3 and 4 fi g. 1) for 5 seconds. Press the arrow up and the arrow down buttons to set the maximum or minimum fan speed. The function is enabled for maximum 15 minutes. Press reset to esc test mode.
IT IS A CONDITION OF THE MANUFACTURERS WARRANTY THAT THE BENCHMARK
COMMISSIONING CHECKLIST IS FULLY COMPLETED AND LEFT WITH THE APPLIANCE
Once the process of commissioning the boiler is complete, the
commissioning engineer MUST complete the relevant section in the Benchmark log book.
ELECTRODES POSITION
Fig. 38
6.8 CHECKING THE FLUE SYSTEM The flue system should be visually checked for
soundness. Check all connections and fixings are secure and tight.
6.9 CHECKING THE HEATING THERMOSTAT Allow the system to warm up and then select
the C.H thermostat to ensure the main burner modulates from “high” to “low” and “low” to “off” and vice versa (scale range covers approx.
35 °C - 80 °C,
temperatures).
6.10 C.H. HIGH/LOW TEMPERATURE
at the 80 °C flow temperature. It is possible to adjust the max set-point to max 50°.
seconds to enter in menu.
- Use arrow up and arrow down buttons (item 3 and 4 fig. 1), to select BOIL.
and 8 fig. 1) together and enter button again.
- Use arrow up and arrow down buttons (item 3 and 4 fig. 1) to select the following option:
- PM4 (“1” high temperature, “2” low temperature).
The boiler comes set, in Central heating,
- Press P button (item 8 fig. 1) for 3
- Press enter and reset buttons (item 1
sec 1.5 key 5 to set heating
6.11 RANGE RATING CENTRAL HEATING
The boiler comes set, in Central heating, at the MID RANGE of its output.
The boiler has already
manufacturer during production. If the adjustments need to be made again, observe the following procedures.
strictly in the sequence indicated, by qualified personnel only.
To check max fan speed, see tables 11:
seconds to enter in menu.
- Use arrow up and arrow down buttons (item 3 and 4 fig. 1), to select BOIL.
- Press enter and reset buttons (item 2 and 3 fig. 1) together and enter button again.
(item 3 and 4 fig. 1) to select the followings options:
- PM1 C.H. max fan speed.
The adjustment to fan speed must be
- Press P button (item 8 fig. 1) for 3
- Use arrow up and arrow down buttons
been adjusted by the
- Press enter (item 1 fig. 1) to select CH fan speed. Adjust if necessary.
6.12 TEST MODE
It is possible to activate the test mode function by pressing arrow down buttons, (item 3 and 4 fi g. 1) for 5 seconds. Press the arrow up and the arrow down buttons to set the maximum or minimum fan speed. The function is enabled for maximum 15 minutes. Press reset to esc test mode.
the arrow up and the
TABLE 11
Range rating regulation of Central Heating
C.H. regulations Heat input (kW) Fan speed (rpm)
Maximum setting 20 24,5 4200 4200
Minimum setting 3,7 4,1 1300 1300
WH System 3-20 WH System 4-24 WH System 3-20 WH System 4-24
40
Page 41
RATIO BETWEEN FAN SPEED AND HEAT INPUT
6.13 INSTRUCTING THE USER
After completion of the installation and commissioning of the system, the installer should hand over to the Householder by taking the following actions:
- To the Householder explain his/her
responsibilities under the “Gas Safety Regulations 2000”.
- Explain and demonstrate the lighting and shutting down procedures.
user how to isolate the appliance from the gas, water and electricity supplies an
(Refer to
table 10 and page 59).
- Check all joints and connections in the appliance and remake any that show signs of leakage.
NOTE: Service consumables are not covered by the warranty. To view warranty exclusions please visit www.ravenheat.co.uk or contact us on 01132 527007.
COMPETENCE TO CARRY OUT THE CHECK OF COMBUSTION PERFORMANCE.
Please note: BS6798:2009 Specification for installation and maintenance of gas-fired boilers of rated input not exceeding 70 kW net advises that:
- The person carrying out a combustion measurement should have been a
satisfactory completion of th
6.13 INSTRUCTING THE USER
commissioning of the system, the installer should hand over to the Householder by taking the following actions:
- To the Householder explain his/her
After completion of the installation and
responsibilities under the “Gas Safety Regulations 2000”.
- Explain and demonstrate the lighting and shutting down procedures.
- Show the user the location of the filling valve and how to top-up the system pressure correctly.
- Explain the operation of the boiler including the use and adjustment of ALL system controls which should be fully explained to the Householder. This will ensure the optimum fuel economy for the household requirements of both heating and hot water consumption.
Advise the User of the precautions necessary to prevent damage to the system, and to the building, in the event of the system remaining inoperative during frost conditions.
-
Explain the func tion and t he use of the
boiler, the summer/winter button, the
ON/OFF switch and th e reset of the
digital display.
- Explain and demonstrate the function of the temperature controls, radiator valves etc. for the economic use of the system.
- If an external time clock is fitted, then draw attention to the digital time.
- Stress the importance of regular servicing by a qualified Heating Engineer and that a comprehensive service should be carried out AT LEAST ONCE A YEAR.
- Fill in the Benchmark log book and leave completed with the customer.
- Explain to the appliance from the gas, water and electricity supplies and the locations of
user how to isolate the
all drain points.
SERVICING INSTRUCTIONS
7
The White Boiler Company is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark was instructed to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.
Combustion testing must be carried out by competent person
using a combustion analyser conforming to BS7927.
During routine servicing, and after any maintenance or change of part of the combustion circuit, the following must be checked:
- The integrity of the flue system and the flue seals.
- The integrity of the boiler combustion circuit and the relevant seals.
- The operational dynamic (working) gas inlet pressure at maximum rate.
- The gas rate.
- The combustion performance table 10 and page 59).
- Check all joints and connections in the appliance and remake any that show signs of leakage.
NOTE: Service consumables are not covered by the warranty. To view warranty exclusions please visit www.ravenheat.co.uk or contact us on 01132 527007.
COMPETENCE TO CARRY OUT THE CHECK OF COMBUSTION PERFORMANCE.
Please note: BS6798:2009 Specification for installation and maintenance of gas-fired boilers of rated input not exceeding 70 kW net advises that:
- The person carrying out a combustion measurement should have been assessed
(Refer to
as competent in the use of a flue gas analyser and the interpretation of the results.
- The flue gas analyser used should be one meeting the requirements of BS7927 or BS-EN 50379-3 and be calibrated in accordance with the analyser manufacturers requirements.
- Competence can be demonstrated by
satisfactory completion of the CPA1 ACS assessment which covers the use of electronic portable combustion gas analysers in accordance with BS 7967, Parts 1 to 4.
41
Page 42
Examine and remove loose debris from the combustion chamber using a soft brush and vacuum cleaner. Carefully flush,
by spraying water at any remaining debris
through the condensate trap. (Ensure the water is kept away from electrical components).
Inspect the siphonic condensate trap for a blockage. Remove the cap at the base
of the condensate trap. Remove an
7.1 BOILER FROST PROTECTION
The appliance has a built in frost protection device that protects the boiler from freezing. With the gas and electric supplies ON and irrespective of any room thermostat setting, the frost protection device will operate the pump when the temperature falls below 10 °C and will operate the burner when the temperature falls below 5 °C. The burner will switch off when the temperature reaches 27 °C. When the frost protection device operates “AF” is displayed on the digital display.
IMPORTANT NOTE: The system should be protected by incorporating a
system frost thermostat.
- IMPORTANT: After completing any servicing or replacement of gas carrying components it
is essential that a test for gas soundness is always carried out along with functional checks in operation.
7.2 TO INSPECT AND CLEAN THE
APPLIANCE Before carrying out the cleaning
operation, cover the electrical control panel with a piece of waterproof material to protect it from debris. Inspect the heat exchanger for any
blockage. Deposits of any material should
be brushed away using a soft brush.
To ensure continued efficient operation of the appliance it is necessary to carry out servicing and cleaning at regular intervals. The frequency of servicing and cleaning
will depend upon the particular installation conditions and usage but in general, once a year is advisable.
WARNING: Before the start of any servicing or replacement of components always isolate the electricity supply to the appliance and always turn off the appliance gas supply at the gas service cock.
The Data badge is positioned low on the inside left panel.
- The following notes apply to the appliance and its controls but it should be remembered that attention must also be paid to the heating and hot water circuits with special attention to radiator valves, thermostats, clocks, leaking hot water taps etc.
- Where it is necessary to replace a gasket that relies on adhesive for securing - this adhesive will be supplied with the gasket as a spare item.
- In all cases prior to servicing, remove the front panel of the case. Operate the appliance by turning the hot water services on to a high water flow. Measurement of the products of combustion can be achieved by connection of a probe to the combustion analyser test point.
NOTE: Do not use brushes with metallic
bristles.
Examine internal pipe-work connections and automatic air vent for any water leaks
and rectify if necessary.
the combustion chamber using a soft brush and vacuum cleaner. Carefully flush,
(Ensure the water is kept away from electrical components).
a blockage. Remove the cap at the base
Any deposits should be flushed out. Reassemble and refit the condensing
When refitting the cap ensure that a
It is essential that a good seal is made at
Examine and remove loose debris from
by spraying water at any remaining debris through the condensate trap.
Inspect the siphonic condensate trap for of the condensate trap. Remove any
debris found. Remove the float to clean it.
trap. watertight seal is achieved, but do not use
excessive force.
Examine the spark and sensing electrodes
for any mechanical damage. Clean away any debris and check the spark and sensing gap.
Examine flue duct and flue manifold and
ensure that there is no obstruction. Examine the gasket at the entry into the flue manifold.
the outlet to the flue manifold, renew this gasket if there is any sign of damage or deterioration.
42
Page 43
8 REPLACEMENT OF PARTS
After replacing any parts always test for gas soundness and if necessary carry out functional test of the controls.
For replacement of parts, the front, and bottom panels of the boiler will need to be removed (it is not necessary to remove the side panels as all parts are accessible from the front or beneath the boiler).
8.2 TO REMOVE THE FRONT PANEL (Fig. 39)
To remove the front panel unscrew the two
lower screws that secure the front panel to the boiler and lift off
Remove the front panel (fig. 39).
Unscrew the four screw to the bottom
panel. Unscrew the two screws to the side panel and pull.
8.1 GENERAL
Replacement of parts must be carried out by a competent person.
Before replacing any parts the boiler should
be isolated from the mains electric supply and the gas should be turned off at the service cock on the boiler.
After replacing any parts always test for gas soundness and if necessary carry out functional test of the controls.
Fig.39
8.2 TO REMOVE THE FRONT PANEL (Fig. 39)
To remove the front panel unscrew the two
8.3 TO REMOVE LEFT AND RIGHT PANELS (Fig. 39)
Unscrew the four screw to the bottom
8.4 TO REMOVE/REPLACE SPARK
IGNITER BOX (Fig. 41) Remove the front panel (fig. 39).
Detach all the connectors from the igniter Remove the 2 screws that secure the spark Replace in reverse order.
For replacement of parts, the front, and bottom panels of the boiler will need to be removed (it is not necessary to remove the side panels as all parts are accessible from the front or beneath the boiler).
lower screws that secure the front panel to the boiler and lift off..
Remove the front panel (fig. 39). panel.
Unscrew the two screws to the side panel and pull.
control box. igniter to the bracket.
Fig.40
Fig.41
43
Page 44
8.5 TO REMOVE/REPLACE FAN
the retaining clip. Detach the connectors from the fan. Unscrew the four screws that fix the fan
and remove only the right screws. Pull the fan to the right and pull forward. Replace in reverse order (always fitting a
new gasket).
Replace with a new
the fan.
U
Follow the instructions to remove the burner (sect. 8.7). Pull down to remove the condens
O-ring sea
(Fig. 42) Remove the front panel (fig. 39).
Unscrew the gas pipe nut and remove the retaining clip. Detach the connectors from the fan. Unscrew the four screws that fix the fan
and remove only the right screws. Pull the fan to the right and pull forward. Replace in reverse order (always fitting a
new gasket).
8.6 TO REMOVE/ REPLACE THE ELECTRODES (Fig.37)
Remove the front panel (fig. 39).
Remove the ignition and/or sensing lead plug. Unscrew the two securing screws and put
them into a suitable container so that they
don’t get lost. Withdraw the Spark electrode and/or Sensing electrode carefully from the burner
cover being careful not to damage the
seal.
8.7 TO REMOVE/REPLACE THE BURNER (FIG.43)
Remove the front panel (fig. 39).
Unscrew the gas pipe nut and remove the retaining clip. Detach the connectors from
Unscrew the screws to the burner cover To remove the burner, unscrew the screws
in the lower cover side. Replace in reverse order (always fitting a
Replace with a new electrode in reverse order. Ensure the gap is correct and there is a good seal when replaced (always fitting a new gasket).
the fan. and remove the cover with the fan.
new gasket).
Fig.42
8.8 TO REMOVE/REPLACE THE HEAT EXCHANGER
Remove the front and bottom panels (fig. 39-40).
Close the on/off valves for the heating
circuit and drain the water at the drain point (fig.36).
Loosen the four heat exchanger securing
screws and clamps then carefully ease the heat exchanger out.
Follow the instructions to remove the burner (sect. 8.7). Pull down to remove the condense pipe on the bottom of the heat exchanger. Disconnect the flow and return pipes at the heat exchanger.
CAUTION : There will be water in the heat
exchanger. Replace in reverse order, always use new
O-ring seals.
44
Fig.43
Page 45
8.9 TO REMOVE/REPLACE EXPANSION
Unscrew the nut and the four screws on
the bottom of the gas valve.
Replace in reverse order.
Close the on/off valves for C.H. circuit and
drain the water from at drain point fig.36.
Unscrew the safety relief valve screw and
pull up.
Replace in reverse order and using a new
gasket.
VESSEL (Fig.44)
Remove the front and bottom panels (fig. 39-40). Close the on/off valves for the heating circuit and drain the water at the drain point (fig.36). Unscrew the fixing bracket and the nut connecting the expansion vessel. Lift up the vessel and remove. Replace in reverse order. Use a new gasket, taking care to ensure they are replaced correctly.
8.10 TO REMOVE/REPLACE GAS VALVE (Fig. 45)
Remove the front and bottom panels (fig. 39-40). Unscrew the nut and the four screws on
the bottom of the gas valve.
Replace in reverse order. IMPORTANT:
when the gas valve is re-fitted, check
combustion CO2 and adjust if necessary (see section 6.9).
Fig.44
8.11 TO REMOVE/REPLACE THE WATER PRESSURE TRANSDUCER (Fig. 46)
Remove the front and bottom panels
(fig. 39-40). Close the on/off valves for the heating circuit and drain the water at drain point (fig.36). Detach the wire connector, remove the securing clip. Replace in reverse order.
8.12 TO REMOVE/REPLACE SAFETY RELIEF VALVE (Fig. 46)
Remove the front and bottom panels (fig. 39-40). Close the on/off valves for C.H. circuit and
drain the water from at drain point fig.36.
Unscrew the safety relief valve screw and
pull up.
Replace in reverse order and using a new
gasket.
Fig.45
Fig.46
45
Page 46
8.13 TO REMOVE/REPLACE PUMP (Fig.47)
Close the on/off valves for the heating
circuit and drain the water at drain point (fig.36).
Detach
the supply wire connector from the
pump.
Unscrew the nut that fastens the pump to
the CH pipe and remove the pump and
remove the securing clip at the pump
manifold. Replace in reverse order. NOTE:
Always use new O-ring.
Remove the panel control box (sect. 8.23). Close the on/off valves for C.H. circuit and
drain the water from at drain point Fig.36.
Remove the clip and pull the automatic air
vent from the pump. Replace in reverse order. NOTE: Always use new O-ring.
8.15 TO REMOVE/REPLACE C.H. FLOW AND
RETURN SENSORS (Fig. 48)
Detach the wire connector and remove
the retaining cli
the f
front panel (fig. 39), bottom
and left side panels (fig. 40). Remove the securing clip and pull out the plastic pipe that connects the condensing trap at the heat exchanger. Unscrew the nut that fastens the condensing trap to the depr
Remove the front and bottom panels (fig. 39-40). Close the on/off valves for the heating
circuit and drain the water at drain point
(fig.36). Detach
pump. Unscrew the nut that fastens the pump to
the CH pipe and remove the pump and
Replace in reverse order. NOTE:
8.14 TO REMOVE/REPLACE AUTOMATIC AIR VENT (Fig. 47)
Remove the front and bottom panels
(fig. 39-40).
Replace in reverse order. NOTE: Always use new O-ring.
remove the securing clip at the pump
manifold.
Remove the panel control box (sect. 8.23). Close the on/off valves for C.H. circuit and
drain the water from at drain point Fig.36.
Remove the clip and pull the automatic air
vent from the pump.
the supply wire connector from the
Always use new O-ring.
Fig.47
8.15 TO REMOVE/REPLACE C.H. FLOW AND
RETURN SENSORS (Fig. 48)
Remove the front panel (fig. 39). Detach the wire connector and remove
the retaining clip sensor from the pipe.
NOTE: When reconnecting ensure the
correct wires go to the relevant sensor (the polarity on each one is unimportant).
8.16 TO REMOVE/REPLACE FLUE SENSOR
(Fig. 3 item 22)
Remove
Detach the wire connector and rotate the
sensor. Replace in reverse order.
8.17 TO CLEAN AND REMOVE/REPLACE CONDENSING TRAP (Fig. 49)
Remove the
and left side panels (fig. 40). Remove the securing clip and pull out the plastic pipe that connects the condensing trap at the heat exchanger. Unscrew the nut that fastens the condensing trap to the depression chamber and remove it. If the side panel can not be removed then remove the gas valve (see sec
8.10) and continue with the above instructions. Replace in reverse order.
the front panel (fig. 39).
front panel (fig. 39), bottom
Fig.48
Fig.49
46
Page 47
818 TO REMOVE PANEL CONTROL BOX
front panel (fig. 39). Pull forward the control panel box with both hands until it is slightly out of the boiler. As doing so move the box
the
front panel (fig. 39). Push the four retaining latches and remove the front of the panel box (fig.
52).
8.20 TO REMOVE/REPLACE CONTROL BOARD (Fig.54).
Remove the front panel (fig. 39).
Remove the instrument panel (sect.
8.24). Detach all connectors from control board, unscrew the four screws and lift up. Replace in reverse order (fig. 54).
8.21 TO REMOVE/REPLACE DIGITAL DISPLAY BOARD.
Remove the front panel (fig. 39). Remove the instrument panel (8.24). Detach the connectors and unscrew the four screws. Replace in reverse order.
8.22 EXTERNAL CONTROL CONNECTION (Fig. 53)
Remove the front panel (fig. 39). Connect the external control connection to switching wire.
(Fig. 50,51,52). Remove the
Pull forward the control panel box with both hands until it is slightly out of the boiler. As doing so move the box over to the left while still pulling it forward until the control box becomes free. Lift and fix the box on the depression chamber with the service retaining clips (fig. 52). This will allow free access to lower part of the boiler.
front panel (fig. 39).
Fig.51
Fig.50
Fig.52
8.19 TO REMOVE THE INSTRUMENT PANEL (Fig. 53).
Remove
Push the four retaining latches and remove the front of the panel box (fig.
52).
8.20 TO REMOVE/REPLACE CONTROL BOARD (Fig.54).
Remove the instrument panel (sect.
8.24). Detach all connectors from control board, unscrew the four screws and lift up. Replace in reverse order (fig. 54).
8.21 TO REMOVE/REPLACE DIGITAL DISPLAY BOARD.
Remove the instrument panel (8.24). Detach the connectors and unscrew the four screws. Replace in reverse order.
Remove the front panel (fig. 39).
Remove the front panel (fig. 39).
the
front panel (fig. 39).
8.22 EXTERNAL CONTROL CONNECTION (Fig. 53)
Connect the external control connection to switching wire.
Remove the front panel (fig. 39).
Fig.53
Fig.54
47
Page 48
9 FAULT FINDING
Before trying to operate the boiler make sure that: all gas supply cocks are open and the gas supply has been
purged of air. The heating system pressure is at least 1 bar min to 1.5 bar max, set the central heating temperature to maximum. (sect. 1.5). Ensure external controls are calling for heat (room thermostat/ digital clock) and check the following appliance operations:
48
Page 49
10 ELECTRICAL SYSTEM DIAGRAM
Fig. 55
49
Page 50
11 SPARE PARTS
50
Fig. 56
Page 51
THE WHITE BOILER COMPANY WH SYSTEM 3-20/4-24
HIGH EFFICIENCY CONDENSING COMBINATION BOILER
SHORT LIST OF SPARE PARTS AND FLUE ACCESSORIES
Pos. Part. No. G.C.
Part. No.
1 CIR150100 Digital display WH System 3-20/4-24 2 PAN150200 Instrument panel WH System 3-20/4-24
3 CIR150070 Control board 4 SCA110051 Instrument panel box 5 FUS010150 Internal fuse 3.15 A 6 CIR130100 Switching wire board 7 TRA150100 Water pressure transducer 8 FOR150250 Water pressure transducer clip
9 GRU150150 System return manifold 10 TUB150550 System by-pass pipe 11 GRU150080 System fl ow manifold 12 VAL150250 Drain valve 13 VAL150100 Safety relief valve 14 5018025 1/2” gasket 15 TUB150480 Safety relief valve pipe 16 5018030 3/4”gasket 17 TUB150150 Gas valve inlet pipe 18 TUB150500 Flow pipe 19 SON110100 C.H. fl ow and return sensors 20 ORI150100 Heat exchanger O-ring 21 FOR150050 Heat exchanger clip 22 TER080050 Overheat thermostat (TER060150) 23 VAL150200 Manual air vent 24 TUB110150 Flexible condensing pipe (TUB110300) 25 RAC110050 Condensing trap 26 FAS150050 Condensing trap pipe hose clamp 12-22 27 TUB150050 Condensing pipe 28 FAS150150 Condensing trap hose clamp 30-45 29 GUA010260 3/4” gas valve gasket 30 VAL150150 Gas valve 31 TUB150200 Gas valve outlet pipe 32 RAC150050 Air/gas mixer junction 33 ORI150050 Air/gas mixer junction O-ring 34 FOR150100 Air/gas mixer junction clip 35 MIX150050 WH System 4-24 air/gas mixer 36 MIX150100 WH System 3-20 air/gas mixer 37 ORI110050 Air/gas mixer - fan O-ring 38 VEN130100 Fan 39 GUA110052 Fan - burner gasket 40 CAN150100 Sensing electrode 41 CAN150070 Spark electrode 42 GUA150050 Sensing/spark electrode gasket
Description
(GUA010200)
(GUA010250)
(SON110150)
51
Page 52
Pos. Part. No. G.C.
Description
Part. No.
43 GUA150100 WH System 4-24 burner gasket
43.1 GUA150120 WH System 3-20 burner gasket 44 BRU150050 WH System 3-20 burner
44.1 BRU150100 WH System 4-24 burner 45 FLA110050 Flue fl ange
(FLA110052)
46 GUA110350 Flue fl ange gasket 47 GUA110250 Flue manifold washer (GUA130050) 48 SON130050 Temperature fl ue sensor 49 GEN150100 Spark igniter 50 COL150050 Flue exhaust manifold 51 SCA150050 WH System 3-20 heat exchanger
51.1 SCA150100 WH System 4-24 heat exchanger 52 VAS150050 Expansion vessel 53 GUA050050 3/8” gasket
(GUA060111)
54 TUB150120 Expansion vessel pipe 55 GUA010050 1/4” gasket
56 TUB150110 Return pipe 57 GUA010310 1” gasket
(GUA010311)
58 CIR150100 Pump 59 ORI150150 Pump O-ring 60 FOR150200 Pump clip / IMP150100 WH System 3-20/4-24 wiring harness
52
Page 53
Plume Management Kit (see sect. 5.6)
Part. No. Description
TER110101 1 metre high plume kit CUR110050 45° fl ue exhaust defl ection bend CUR11010 90° fl ue exhaust defl ection bend
Accessories concentric flue 60/100 (see sect. 5.12 - Table 7)
Part. No. Description
PR5094110A Straight fl ue header / sample point 60/100 PRFE Flue Extension 60/100 L1000 PR45FBI 45° bend 60/100 PR90FBI 90° elbow bend 60/100 PR5023016 Horizontal terminal 60/100 TER110200 Vertical fl ue Terminal
Accessories concentric flue 80/125 (see sect. 5.18)
Part. No. Description
PR5094110A Straight fl ue header / sample point 60/10 PRO110300 Flue Extension 80/125 L1000 RID110050 125/80 to 100/60 Flue reducer CUR110250 45° bend 80/125 CUR110300 90° elbow bend 80/125 TER010050 Horizontal Flue Terminal 80/125 TER110200 Vertical Flue Terminal 80/125 TEG060050 Flashing sleeve/slate
Accessories eccentric flue 80/80 (see sect. 5.13 - 5.14 - 5.15 - 5.16 - 5.17)
Part. No. Description
SDO110100 Twin fl ue header F80/80 PRO110200 Straight pipe L1000 80 CUR110150 90° elbow bend 80 CUR110250 45° bend 80 GRI110050 Air inlet terminal 80 GRI110100 Exhaust terminal 80 TER060110 Vertical eccentric fl ue terminal
53
Page 54
THE WHITE BOILER COMPANY
A Ravenheat Group Company
Chartists Way, Morley, Leeds, U.K. LS27 9ET
Telephone: 0113 252 7007 Fax: 0113 238 0229 Website: www.ravenheat.co.uk E-mail: sales@ravenheat.co.uk
Ravenheat reserves the right to make changes and
improvements in our products which may affect the accuracy
of the information contained in this leafl et.
54
COD 0017LIB15010/0 07/2015
Page 55
BENCHMARK COMMISSIONING CHECKLIST DETAILS
12
Boiler Page Page
Make and model ………………………………………14/17 Burner operating pressure….....................................n/a
Appliance serial no. on data badge………..Left side panel Central heating fl ow temp…….. . measure and record Controls Central heating return temp…… .measure and record
Temperature control to heating…………...................…12 For combination boilers only
Temperature control to hot water…………...............….12 Scale reducer…………… …………………..................25
Heating zone valves……………………………………..n/a Hot water mode Auto by-pass………………………………………………22 Max. operating burner pressure….measure and record
Boiler interlock…………………………………….……....22 Max. operating water pressure…...measure and record
Cold water inlet temp…………….. measure and record
For all boilers Hot water temp……………………. measure and record Flushing to BS7593………………………………...…….24 Water fl ow rate at max. setting…...measure and record Inhibitor…………………………………………………….25 For condensing boiler only
Central heating mode Condensate drain………………………………......38/39
Heat input………………………………….to be calculated For all boilers: complete, sign & hand over to the customer.
NOTE TO THE INSTALLER:
COMPLETE
THE BENCHMARK COMMISSIONING
CHECKLIST AND LEAVE THESE
INSTRUCTIONS WITH APPLIANCE
For assistance please call The White Boiler Company technical helpline: telephone: 01 13 252 7007 fax: 01 13 238 0229 e-mail: sales@ravenheat.co.uk
55
Page 56
56
Page 57
57
Page 58
Benchmark Commissioning and Servicing Section
It is a requirement that the boiler is installed and commissioned to the manuIacturers instructions and the data ¿elds on the commissioning checNlist completed in full.
7o instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation.
7o maintain the boiler guarantee it is essential that the boiler is serYiced annually by a *as 6afe registered engineer who has been trained on the boiler installed.
7he serYice details should be recorded on the %enchmarN 6erYice InterYal 5ecord and left with the householder.
58
www.centralheating.co.uk
© Heating and Hotwater Industry Council (HHIC)
Page 59
FLOWCHART FOR CO LEVEL AND COMBUSTION RATIO
CHECK ON COMMISSIONING A CONDENSING BOILER
59
Page 60
12.1 ANALYSER CHECK LIST
60
Page 61
THE WHITE BOILER COMPANY
GAS BOILER SYSTEM COMMISSIONING CHECKLIST
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
)DLOXUHWRLQVWDOODQGFRPPLVVLRQDFFRUGLQJWRWKHPDQXIDFWXUHU¶VLQVWUXFWLRQVDQGFRPSOHWHWKLV%HQFKPDUN&RPPLVVLRQLQJ&KHFNOLVWZLOOLQYDOLGDWHWKH ZDUUDQW\7KLVGRHVQRWDIIHFWWKHFXVWRPHU ¶VVWDWXWRU\ULJKWV
&XVWRPHUQDPH 7HOHSKRQHQXPEHU
$GGUHVV
%RLOHUPDNHDQGPRGHO
%RLOHUVHULDOQXPEHU
&RPPLVVLRQHGE\35,171$0( *DV6DIHUHJLVWHUQXPEHU
&RPSDQ\QDPH 7HOHSKRQHQXPEHU
&RPSDQ\DGGUHVV
&RPPLVVLRQLQJGDWH
To be completed by the customer on receipt of a Building Regulations Compliance Certi¿cate
%XLOGLQJ5HJXODWLRQV1RWL¿FDWLRQ1XPEHULIDSSOLFDEOH CONTROLSWLFNWKHDSSURSULDWHER[HV
7LPHDQGWHPSHUDWXUHFRQWUROWRKHDWLQJ
7imH anG tHmpHraturH control to Kot ZatHr &\linGHr tKHrmostat anG proJrammHrtimHr &omEination %oilHr +HatinJ ]onH YalYHs Fitted 1ot reTuired +ot Zater ]one YalYes Fitted 1ot reTuired 7Kermostatic radiator YalYes Fitted 1ot re $utomatic E\pass to s\stem Fitted 1ot reTuired %oiler interlocN 3roYided
ALL SYSTEMS
7Ke s\stem Kas Eeen ÀusKed and cleaned in accordance ZitK %6 and Eoiler manuIacturer¶s instructions Yes :Kat s\stem cleaner Zas used" :Kat inKiEitor Zas used" 4uantit\ litres +as a primar\ Zater s\stem ¿lter Eeen installed" Yes 1o
CENTRAL HEATING MODE measure and record *as rate mñKr OR ItñKr %urner operatinJ pressure iI applicaEle &entral KeatinJ ÀoZ temperature & &entral KeatinJ return temperature &
COMBINATION BOILERS ONLY
,s tKe installation in a Kard Zater area aboYe ppm" Yes 1o ,I \es and iI reTuired b\ tKe manuIacturer Kas a Zater scale reducer been ¿tted" Yes 1o :Kat t\pe oI scale reducer Kas been ¿tted" DOMESTIC HOT WATER MODE 0easure and 5ecord *as rate mñKr OR ItñKr %urner operatin &old Zater inlet temperature & +ot Zater Kas been cKecNed at all outlets Yes Temperature & :ater ÀoZ rate ,min
CONDENSING BOILERS ONLY
TKe condensate drain Kas been installed in accordance ZitK tKe manuIacturers instructions andor %6%6 Yes
ALL INSTALLATIONS
5ecord tKe IolloZinJ
TKe KeatinJ and Kot Zater s\stem complies ZitK tKe appropriate %uildinJ ReJulations Yes TKe boiler and associated products KaYe been installed and commissioned in accordance ZitK tKe manuIacturers instructions Yes TKe operation oI tKe boiler and s\stem controls KaYe been demonstrated to and understood b\ tKe customer Yes TKe manuIacturers literature includinJ %encKmarN &KecNlist and 6erYice Record Kas been e[plained and leIt ZitK tKe customer Yes
ommissioninJ (nJineer¶s 6iJnature
& &ustomers 6iJnatureTo con¿rm satisIactor\ demonstration and receipt oI manuIacturer¶s literature
J pressure at ma[imum rate mbar OR *as inlet pressure at ma[imum rate mbar
mbar OR *as inlet pressure mbar
$t ma[ rate &O ppm AND &O&O $t min rate ZKere possible &O ppm AND &O&O
5RRPWKHUPRVWDWDQGSURJUDPPHUWLPHU 3URJUDPPDEOHURRPWKHUPRVWDW
/RDGZHDWKHUFRPSHQVDWLRQ Optimum start control
Tuired
² ²
Ratio Ratio
$OOLQVWDOODWLRQVLQ(QJODQGDQG:DOHVPXVWEHQRWL¿HGWR/RFDO$XWKRULW\%XLOGLQJ&RQWURO/$%&HLWKHUGLUHFWO\RUWKURXJKD
&RPSHWHQW3HUVRQV6FKHPH$%XLOGLQJ5HJXODWLRQV&RPSOLDQFH&HU WL¿FDWHZLOOWKHQEHLVVXHGWRWKHFXVWRPHU
+HDWLQJDQG+RWZDWHU,QGXVWU\&RXQFLO++,&
ZZZFHQWUDOKHDWLQJFRXN
ZZZcentralKeatinJcouN
61
Page 62
SERVICE RECORD
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed. Service Provider
%HIRUHFRPSOHWLQJWKHDSSURSULDWH6HUYLFH5HFRUGEHORZSOHDVHHQVXUH\RXKDYHFDUULHGRXWWKHVHUYLFHDVGHVFULEHGLQWKHPDQXIDFWXUHU¶VLQVWUXFWLRQV $OZD\VXVHWKHPDQXIDFWXUHU¶VVSHFL¿HGVSDUHSDUWZKHQUHSODFLQJFRQWUROV
SERVICE 01
(QJLQHHUQDPH
&RPSDQ\QDPH
7HOHSKRQH1R
*DVVDIHUHJLVWHU1R
5HFRUG
&RPPHQWV
6LJQDWXUH
$WPD[UDWH &2SSP AND &2² % $W PLQ UDWH
:KHUH 3RVVLEOH
SERVICE 03
(QJLQHHU QDPH
&RPSDQ\ QDPH
7HOHSKRQH 1R
*DV VDIH UHJLVWHU 1R
5HFRUG
&RPPHQWV
6LJQDWXUH
$W PD[ UDWH &2 SSP AND &2² % $W PLQ UDWH
:KHUH 3RVVLEOH
SERVICE 05
(QJLQHHU QDPH
&RPSDQ\ QDPH
7HOHSKRQH 1R
*DV VDIH UHJLVWHU 1R
5HFRUG
&RPPHQWV
$W PD[ UDWH &2 SSP AND &2² % $W PLQ UDWH
:KHUH 3RVVLEOH
'DWH
&2 SSP AND &2² %
'DWH
&2 SSP AND &2² %
'DWH
&2 SSP AND &2² %
SERVICE 02
(QJLQHHU QDPH &RPSDQ\ QDPH 7HOHSKRQH 1R *DV VDIH UHJLVWHU 1R
$W PD[ UDWH &2 SSP AND &2² %
5HFRUG
$W PLQ UDWH
&RPPHQWV
6LJQDWXUH
:KHUH 3RVVLEOH
&2 SSP AND &2² %
SERVICE 04
(QJLQHHU QDPH &RPSDQ\ QDPH 7HOHSKRQH 1R *DV VDIH UHJLVWHU 1R
$W PD[ UDWH &2 SSP AND &2² %
5HFRUG
$W PLQ UDWH
&RPPHQWV
6LJQDWXUH
:KHUH 3RVVLEOH
&2 SSP AND &2² %
SERVICE 06
(QJLQHHU QDPH &RPSDQ\ QDPH 7HOHSKRQH 1R *DV VDIH UHJLVWHU 1R
$W PD[ UDWH &2 SSP AND &2² %
5HFRUG
$W PLQ UDWH
&RPPHQWV
:KHUH 3RVVLEOH
&2 SSP AND &2² %
'DWH
'DWH
'DWH
6LJQDWXUH
SERVICE 07
(QJLQHHU QDPH
&RPSDQ\ QDPH
7HOHSKRQH 1R
*DV VDIH UHJLVWHU 1R
5HFRUG
&RPPHQWV
6LJQDWXUH
$W PD[ UDWH &2 SSP AND &2² % $W PLQ UDWH
:KHUH 3RVVLEOH
&2 SSP AND &2² %
SERVICE 09
(QJLQHHU QDPH
&RPSDQ\ QDPH
7HOHSKRQH 1R
*DV VDIH UHJLVWHU 1R
5HFRUG
&RPPHQWV
6LJQDWXUH
$OOLQVWDOODWLRQVLQ(QJODQGDQG:DOHVPXVWEHQRWL¿HGWR/RFDO$XWKRULW\%XLOGLQJ&RQWURO/$%&HLWKHUGLUHFWO\RUWKURXJKD
&RPSHWHQW3HUVRQV6FKHPH$%XLOGLQJ5HJXODWLRQV&RPSOLDQFH&HUWL¿FDWHZLOOWKHQEHLVVXHGWRWKHFXVWRPHU
$W PD[ UDWH &2 SSP AND &2² % $W PLQ UDWH
:KHUH 3RVVLEOH
&2 SSP AND &2² %
'DWH
'DWH
6LJQDWXUH
SERVICE 08
(QJLQHHU QDPH &RPSDQ\ QDPH 7HOHSKRQH 1R *DV VDIH UHJLVWHU 1R
$W PD[ UDWH &2 SSP AND &2² %
5HFRUG
$W PLQ UDWH
&RPPHQWV
6LJQDWXUH
:KHUH 3RVVLEOH
&2 SSP AND &2² %
SERVICE 10
(QJLQHHU QDPH &RPSDQ\ QDPH 7HOHSKRQH 1R *DV VDIH UHJLVWHU 1R
$W PD[ UDWH &2 SSP AND &2² %
5HFRUG
$W PLQ UDWH
&RPPHQWV
6LJQDWXUH
:KHUH 3RVVLEOH
&2 SSP AND &2² %
'DWH
'DWH
+HDWLQJDQG+RWZDWHU,QGXVWU\&RXQFLO++,& ZZZFHQWUDOKHDWLQJFRXN
62
Loading...