6. Immediately call your local gas
supplier after leaving the building.
Follow the gas suppliers
instructions.
7. If you cannot reach your gas
supplier, call the Fire Department.
WARNING
™
The Economical Unitary
Infrared Heater
Installation, Operation &
Service Manual
BH-40
Fire Hazard
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or property
damage. Read the Installation, Operation and Service
Manual thoroughly before installing or servicing
this equipment.
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
BH-60
BH-80
BH-100
BH-115
BH-125
BH-140
BH-150
BH-175
BH-200
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon.
Figure 21: Gas Connection with Flexible Gas Hose................ 39
Page 6
Page 7
SECTION 1: HEATER SAFETY
Your Safety is Important to Us!
This symbol is used throughout
the manual to notify you of
possible fire, electrical or burn
hazards. Please pay special
attention when reading and
following the warnings in these
sections.
Installation, Service and Annual Inspection of heater
must be done by a contractor qualified in the
installation and service of gas-fired heating
equipment.
Read this manual carefully before installation,
operation or service of this equipment.
This heater is designed for heating nonresidential
indoor spaces. Do not install in residential spaces.
These instructions, the layout drawing, local codes
and ordinances, and applicable standards that apply
to gas piping, electrical wiring, venting, etc. must be
thoroughly understood before proceeding with the
installation.
Thin sheet metal parts, the aluminum reflector
portion of the heater and the various venting
components have sharp edges. To prevent injury, the
use of work gloves is recommended. The use of
gloves will also prevent the transfer of body oils from
the hands to the surface of the reflector.
Before installation, check that the local distribution
conditions, nature of gas and pressure, and
adjustment of the appliance are compatible.
1.1 Manpower Requirements
To prevent personal injury and damage to the heater,
two persons will be required for installation.
SECTION 1: HEATER SAFETY
1
Page 8
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable
specifications and codes. Rapid Engineering
recommends the installer contact a local building
inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
Clearances to Combustibles.
• To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports.
• To provide access on all sides for burner servicing
and removal.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as a support for a ladder or
other access equipment and never hang or
suspend anything from heater.
• To ensure there is adequate air circulation around
the heater and to supply air for combustion,
ventilation and distribution in accordance with
local codes.
• To safely and adequately install heater using
materials with a minimal working load of 75 lbs
(33 kg).
2.1 Wall Tag
A laminated wall tag is available for the heater as
a permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Please contact Rapid Engineering or
™
your RAPID
independent distributor to obtain the
wall tag. Affix the tag by peeling
off the backing of the adhesive strips on the rear
surface and position the tag on a wall near the
heater (e.g. thermostat).
A copy of the wall tag (P/N 91037920) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found on
the burner and in the Installation, Operation and
Service Manual. See Page 4, Figure 1 through Page 7, Figure 10. Write the proper clearance dimensions in
permanent ink according to your model number and
configuration in the open spaces on the tag.
2.2 Corrosive Chemicals
CAUTION
Do not use heater in an area containing corrosive
chemicals.
Avoid the use of corrosive chemicals to ensure a
longer life of the burner, tubing and other parts.
Failure to follow these instructions can result in
property damage.
Rapid Engineering cannot be responsible for
ensuring that all appropriate safety measures are
undertaken prior to installation; this is entirely the
responsibility of the installer. It is essential that the
contractor, the sub-contractor, or the owner identifies
the presence of combustible materials, corrosive
chemicals or halogenated hydrocarbons* anywhere
in the premises.
* Halogenated Hydrocarbons are a family of
chemical compounds characterized by the
presence of halogen elements (fluorine, chlorine,
bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents,
solvents, etc. If these compounds enter the air
supply of the burner, the life span of the heater
components will be greatly reduced. An outside air
supply must be provided to the burners whenever
the presence of these compounds is suspected.
Warranty will be invalid if the heater is exposed to
halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.
2
Page 9
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Required Clearances to Combustibles
Clearances are the required distances that
combustible objects must be away from the heater to
prevent serious fire hazards. Combustibles are
materials, that may catch on fire and include common
items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times
for safety.
Clearances for all heater models are located on the
burner of the heater and on Page 4, Figure 1 through Page 7, Figure 10 in this manual. Check the
clearances on each burner for the model heater
being installed to make sure the product is suitable
for your application and the clearances are
maintained. Read and follow the safety guidelines
below:
• Keep gasoline or other combustible materials
including flammable objects, liquids, dust or
vapors away from this heater or any other
appliance.
• Maintain clearances from heat sensitive material,
equipment and workstations.
• Maintain clearances from vehicles parked below
the heater.
• Maintain clearances from swinging and overhead
doors, overhead cranes, vehicle lifts, partitions,
storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible
materials, signs must be posted to specify the
maximum permissible stacking height to maintain
SECTION 3: CRITICAL CONSIDERATIONS
WARNING
Fire Hazard
Some objects will catch fire or explode when placed
close to heater.
Keep all flammable objects, liquids and vapours the
required distance away from the heater.
Failure to follow these instructions can result in death,
injury or property damage.
required clearances from the heater to the
combustibles. Signs must be posted adjacent to
the heater thermostat. In the absence of a
thermostat, signs must be posted in a
conspicuous location.
• Consult local Fire Marshal, Fire Insurance Carrier
or other authorities for approval of proposed
installation when there is a possibility of exposure
to combustible airborne materials or vapors.
• Hang heater in accordance to the minimum
suspension requirements on Page 12, Figure 12.
• If the radiant tubes must pass through the building
structure, be sure that adequate sleeving and fire
stop is installed to prevent scorching and/or fire
hazard.
3
Page 10
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 1: Standard Reflector
Model ABCDABCD
A
BD
C
BH-406275227166913369
BH-606356235168915889
BH-806386538169716697
BH-1006 40704016102178102
BH-115/125646764616117194117
BH-140/150650795016127201127
BH-175/200852825221133209133
FIGURE 2: One Side Reflector
Model ABCDABCD
A
BD
C
BH-406952441623133112
BH-606 9 62471623158120
BH-806969541623176138
BH-1006976591623194150
BH-115/1256982651623209166
BH-140/1506985691623216176
BH-175/2008988732123224186
(inches)(centimeters)
(inches)(centimeters)
FIGURE 3: Two Side Reflectors
Model ABCDABCD
A
BD
C
BH-1006 277727166919669
BH-115/1256328332168221182
BH-140/150 6 358735168922189
BH-175/200840914021102232102
4
(inches)(centimeters)
BH-406155215163913339
BH-606236523165916659
BH-806257125166418164
Page 11
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 4: 45° Tilt Reflector
Model ABCDABCD
A
BD
C
BH-408850462121127117
BH-608 8 59542121150138
BH-808865602121166153
BH-10010873642621186163
BH-115/12510877692621196176
BH-140/15012883743121211188
BH-175/20012885793121216201
FIGURE 5: U-Tube, Standard Reflector
Model ABCDABCD
A
B
C
D
BH-40
BH-606356230168915877
BH-806386837169717394
BH-1006 40753916102191100
BH-115/125646784316117199110
BH-140/150650834716127211120
BH-175/200854875121138221130
SECTION 3: CRITICAL CONSIDERATIONS
(inches)(centimeters)
(inches)(centimeters)
- UNAPPROVED -- UNAPPROVED -
FIGURE 6: U-Tube, 45°
A
B
C
D
(inches)(centimeters)
Model ABCDABCD
BH-40
BH-608 8 59422121150107
BH-808865462121166117
BH-1008873522121186133
BH-115/1258877612121196155
BH-140/1508883662121211168
BH-175/2008885702121216178
- UNAPPROVED -- UNAPPROVED -
5
Page 12
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 10: Venting
(inches)(centimeters)
ModelAEFAEF
A
Unvented
Radiant Tubes
Vented
E
Vent
Pipes
F
BH-40141818364646
BH-60141818364646
BH-80202418516146
BH-100202418516146
BH-115/125202418516146
BH-140/150203018517746
BH-175/200203018517746
7
Page 14
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 4: NATIONAL STANDARDS AND
APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the nameplate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to National Fuel Gas Code,
ANSI Z223.1 - latest revision (same as NFPA 54).
Canada: Refer to CAN/CGA B149.1 and B149.2:
Installation Codes for Gas Burning Appliances.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, ANSI/NFPA 409 - latest revision.
Canada: Refer to Standard CAN/CGA B149.1
and B149.2.
• In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the
upper surface of wings or of engine enclosures
of the highest aircraft which may be housed in
the hangar. The measurement shall be made
from the wing or engine enclosure (whichever is
higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they
shall not be subject to injury by aircraft, cranes,
movable scaffolding or other objects. Provisions
shall be made to assure accessibility to
suspended heaters for recurrent maintenance
purposes.
4.3 Public Garages
Installation in garages must be in accordance
with the following codes:
United States: Standard for Parking Structures
NFPA 88A - latest revision or the Code for Motor
Fuel Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision. Canada: Refer to
CAN/CGA B149.1 and B149.2: Installation
Codes for Gas Burning Appliances.
• Heaters must not be installed less than 8'
(2.4 m) above the floor. Minimum clearances to
combustibles must be maintained from vehicles
parked below the heater.
• When installed over hoists, minimum
clearances to combustibles must be maintained
from the upper most point of objects on the hoist.
4.4 Electrical
The heater must be electrically grounded in
accordance with the following codes:
United States: Refer to National Electrical
®
Code
, ANSI/NFPA 70 - latest revision. Wiring
must conform to the most current National
®
Electrical Code
, local ordinances and any
special diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance with
the requirements within this manual and the
following codes:
United States: Refer to NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code.
Canada: Refer to CAN/CGA B149.1 and B149.2:
Installation Codes for Gas Burning Appliances.
8
4.6 High Altitude
These heaters are approved for installations up
to 2000 ft (US), 4500 ft (Canada) without
modification. Consult factory if US installation is
above 2000 ft (610 m) or Canadian installation
is above 4500 ft (1370 m).
Page 15
SECTION 5: MAJOR COMPONENTS
FIGURE 11: Major Component Descriptions
SECTION 5: MAJOR COMPONENTS
Burner with Tube Gasket
Must be installed with the
flame observation window
facing down.
Burner Tube
Supplied in 10
' (3 m) lengths.
Burner tube is always the first
tube after the burner.
Reflector (Aluminum or
Stainless Steel)
Alternate overlap as shown on
overview and on Page 14, Figure 14. Minimum overlap is
6” (16 cm).
Tube
Hot Rolled or Heat Treated
Aluminized Tube supplied in
10' (3 m) lengths.
Tube and Reflector Hanger
with Clamp Package
Position this hanger no more
than 4” (10 cm) away from the
burner.
Tube and Reflector Hanger
Suspend system from these
hangers.
Reflector Support Strap &
Wire Form
Flex Gas Line with
Shut Off Cock
Coupling Assembly with Lock
Reflector End Cap
Punch out center section to
accommodate heat exchanger
tube.
Vent Adapter
Turb ul ato r
Turbulator must be installed in the
last standard section of tube.
Turbulator is not required on the
BH-125/150/175/200. For
installation, see Page 18, Step 6.4
9
Page 16
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Additional tubing length may be added to heater. Tubing must be heat-treated, aluminized or porcelain
coated. Any additional tubing lengths are considered as vent length for length determination. Maximum
venting length for minimum heater length is 45' (13.7 m).
11
Page 18
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 6: HEATER INSTALLATION
WARNING
Suspension Hazard
Burner is secured to burner tube
by bolts and lockwashers.
Hang heater with materials
with a minimum working
load of 75 lbs (33 kg).
Failure of the supports
can result in death, injury
or property damage.
To ensure your safety, and comply with the terms of
the warranty, all units must be installed in
accordance with these instructions.
FIGURE 12: Critical Hanger Placement
Typical Suspension Details
Beam Clamp
Rod (3/8")
24" min.*
(61 cm)
(9.5 mm)
X*
The gas or the electrical supply lines must not be
used to support the heater.
Do not locate the gas or electric supply lines directly
over the path of the flue products from the heater.
The heater must be installed in a location that it is
readily accessible for servicing.
The heaters must be installed with clearances to
combustibles as indicated on the rating plate and in
this instruction manual.
The minimum and maximum gas inlet pressures
must be maintained as indicated on the rating plate.
Typical installation configurations are shown in
Figure 12.
Drive Slide Bar until tight.
End of Slide Bar should be
within tolerance listed below.
± 2" (5 cm)
Correct Slide Bar
dimensions
SECTION 6: HEATER INSTALLATION
Incorrect Slide Bar
position
• Repeat Step 6.3 A - D until all tubes are assembled. See Page 17, Step 6.3.2.
Step 6.3.2 Coupling and Tube Assembly (Continued)
7' 6" ± 1'
(229 cm ± 25 cm)
10' ± 1'
(305 cm ± 25 cm)
Tube Length
Model
BH-4010' (3 m)
BH-6020' (6 m)
BH-8020' (6 m)
BH-10030' (9 m)
BH-11530' (9 m)
BH-12540' (12 m)
BH-14040' (12 m)
BH-15050' (15 m)
BH-17550' (15 m)
BH-20060' (18 m)
Mi nimum
Total Overall
Tube Length
17
Page 24
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Step 6.4 Turbulator Installation
Turbulator
' Section
2.5
Turbulator
Adapter
Turbulator section 2.5'
(stainless) used in BH-40
heaters must be in the section of
turbulator nearest to the burner.
Ta b
Turbulator must be installed in the last
standard section of tube. Turbulator is
not required on the BH-125/150/175/200.
T
w
i
s
t
Pull String
Fold tab around outside
of tube nearest to the vent to hold turbulator
in place. Where a vent sleeve
is used, do not fold tab.
Step 6.5.1 Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in
Section 6 are schematic only and provide a general
guideline of where hangers, reflector supports and
U-clips are to be installed.
and reflector supports are used. The positioning of
reflector supports and U-clips depend on the
individual installation. The following rules must be
observed.
To ensure proper expansion and contraction
movement of the reflectors, a combination of U-clips
1. The first reflector after the burner must be affixed in
the middle of the reflector with a reflector support and
tight screws.
Reflector
End Cap
Wire Form
SECTION 6: HEATER INSTALLATION
Tight
Sheet Metal
Screw
First Reflector
U-Clips
Overlap must be a
minimum of 6" (16 cm).
2. The overlap at the first and second reflector is a slip overlap.
Thereafter, every third reflector joint is a slip overlap. A slip
overlap is achieved by either:
a.) both reflectors lay inside a hanger.
(No reflector support needed.)
b.) using a reflector support with
loose screws at the reflector
overlap.
3. The remaining reflector overlaps require a non-slipoverlap connection. To affix the reflectors together in
a non-slip overlap either:
a.) use reflector support and tight screws.
b.) if both reflectors lay inside a hanger, u-clips or
sheet metal screws may be used.
6"
(16 cm)
2 A
Slip Overlap
Reflector Support
Strap
2 B
Slip Overlap
3 A
Non-Slip Overlap
Reflector
Reflector
Support
Loose screws
loosened 1/16"
(2 mm) to allow
slippage.
Reflector
This section of three reflectors joined together must
be affixed to the tube with at least one reflector support
with tight screws.
DescriptionPart Number
Reflector Support Package03050010
Wire Form91908004
Reflector Support Strap03050000
Screw #8 x 3/494320812
U-Clip Package91107720
Reflector End Cap027508XX
Tight
screws
3 B
Non-Slip Overlap
U-Clip
(2 clips per
non-slip overlap
inside a hanger)
19
Page 26
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Heaters (except BH-40) are approved for optional
U-Tube configurations.
The U-Tube may be installed in either a standard
horizontal position, a 45° position or in an opposite
45° position as shown on Page 5, Figure 5 through Page 6, Figure 7. When using a U-Tube
configuration, the following additional rules must be
adhered to:
FIGURE 16: U-Tube Heater Assembly Overview
U-Tube
Support Bracket
Reflector
Support
Burner
Vent Adapter
• A minimum of 10' (3 m) on BH-60/80 and a
'
minimum of 15
(4.5 m) on BH-100/115/125/140/
150/175/200 is required between the burner and
the U-Tube.
• The correct turbulator (See Page 18, Step 6.4)
must be installed in the last standard section of
the tube.
• The burner must never be operated in a tilted
position.
• The heater must be properly supported at all
locations. See Page 22, Figure 17.
Tube Clamp
Package
U-Tube, Standard
12
U-Tube,
45°
2
1
U-Tube,
Opposite 45°
12
Turbulator
(With Select
Models)
Burner
Tube
Tight U-Bolt
12
4" (10 cm) U-Bolt,
secured to Burner Tube
with 1/4" (6 mm)
Lockwashers and
1/4-20 Hex Nuts
Tube
Couplings
Loose U-Bolt
4" (10 cm) U-Bolt,
secured to Bracket with
1/4" (6 mm) Lockwashers
and 1/4-20 Hex Nuts on
top and bottom to
allow for tube expansion
and contraction
U-Bolt
Nut
Lock Washer
Lock Washer
Nut
Reflector
U-Clips
Reflector
End Caps
U-Tube
18" (457 mm)
Center to Center
21
Page 28
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
FIGURE 17: U-Tube Heater Layout Overviews
LEGEND
Burner
b
c
g
e
Reflector
Tube 10
Tube 5' **
Tube/Reflector
Hanger
Coupling
Assembly
U-Tube
a = 14" (36 cm)
reflector width (not shown)
b = 2" (5 cm)
end cap to burner
c = 2" (5 cm)
end cap to hanger
'
6" (229 cm)
d= 7
distance first hanger
'
(305 cm)
e = 10
distance between hangers
f = 5
'
(153 cm)
distance between last full tube
hanger and half tube hanger
'
Vent Adapter
(not shown)
h
'
Tube Length*
20
b
c
g
d
f
h
30' Tube Length**
b
c
g
de
h
40' Tube Length
g = 12.5" (32 cm) burner length
h = 11" (28 cm) burner height
* Requires the last reflector
before the U-Tube to be cut in
half for use on both sides.
** Requires the last tube before
the U-Tube to be cut in half for
use on both sides.
90° Elbow01335801
Coupling01312700
Reflector End Cap02750800
Reflector Joint Piece02750900
U-Clip Package91107720
Coupling
90° Elbow
ee
Minimum Distance Required
Between Burner and Elbow
Model
BH-4010' (3 m)
BH-6010' (3 m)
BH-8010' (3 m)
BH-10015' (4.5 m)
BH-11515' (4.5 m)
BH-12515' (4.5 m)
BH-14015' (4.5 m)
BH-15015' (4.5 m)
BH-17515' (4.5 m)
BH-20015' (4.5 m)
Minimum
Distance
23
Page 30
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Step 7.2.2 Elbow Installation
Step 7.2.3 Reflector Joint Installation
Reflector
Tube
Coupling
Scribe
Contour
Step 7.2.4 Reflector Joint Installation
Reflector
Joint
Flatten Edge
1" (2.5 cm)
Maximum
Cut away contour
with tin snips.
24
Punch/drill six 3/32" (2 mm) holes.
Page 31
Step 7.2.5 Reflector Joint Detail
Install reflector
end cap.
FIGURE 19: Reflector Joint Detail
SECTION 7: OPTIONAL HEATER ACCESSORIES
Attach reflector joint
with six #8 sheet
metal screws.
Reflector
Joint
Reflector
25
Page 32
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
7.3 Reflector Side Extension
Step 7.3.1 Bracket Installation
Tube
DescriptionPart Number
Reflector Side Extension Package02712700
Reflector Side Extension01368000
Retainer Clips02751200
Sheet Metal Screws94118106
DescriptionPart Number
Lower Clearance Shield Package01397501
Shield Support Strap01397500
Lower Clearance Shield 8'02793000
Locknut #892311400
Flat Washer #895310800
Screw #8 x 3/893511406
Tube and Reflector
Hanger
Suspended Ceiling Frame
' x 4' (61 x 122 cm) Aluminum Grille
2
DescriptionPart Number
Aluminum Grille 2 ft x 4 ft91407000
27
Page 34
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Step 7.5.2 Frame Shield Installation
Shield
DescriptionPart Number
Deco Grille Shield01365900
Step 7.5.3 Reflector Side Extension Installation for Decorative Grilles
NOTE: If the Decorative Grille system is to
be installed in an area with considerable
air movement, it is recommended that one
#8 x 3/8 (3.9 x 9.5 mm) sheet metal screw
be installed per reflector extension to
prevent it from blowing over.
A
Cut Relief Notches for Tube
and Reflector Hangers
Insert Screw
here
Reflector Side
Extension
Distance "A"Extension
MinimumMaximumPart No.Width
2” (4 cm)6” (15 cm)013704088” (20 cm)
6” (15 cm)10” (26 cm)0137041212” (30 cm)
10” (26 cm)14” (37 cm)0137041616” (40 cm)
28
DescriptionPart Number
Reflector Side Extension01370412
Page 35
7.6 One-Foot Decorative Grille Installation
Spread apart brackets
and install
Decorative Grille.
#8 Sheet Metal Screws
Joint Piece
Reinforcement
Slip joint piece into
support bracket
and fasten to
bracket on one side
of the joint only.
Joint Piece
Step 7.6.1 One-Foot Decorative Grille Bracket
#8 Sheet Metal Screws
SECTION 7: OPTIONAL HEATER ACCESSORIES
In order to maintain reflector shape, do
not fasten brackets together. Do not
fasten bracket to adjoining reflectors.
Maintain same slipjoint position as
reflectors.
Decorative Grille Bracket
DescriptionPart Number
Bracket01363003
Step 7.6.2 Decorative Grille
DescriptionPart Number
Decorative Grille 8' x 1'91406700
Cut relief notches for
supports and hangers.
2" (51 mm)
Minimum
Bracket
Overlap
Step 7.6.3 Joint Piece and Reinforcement
DescriptionPart Number
Joint Piece01365903
Reinforcement01365902
29
Page 36
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Fasten end piece
to brackets using two
#8 sheet metal screws
and replace reflector end cap.
Insert end piece
between grille and
brackets.
End Piece
Reflector
End Cap
Step 7.6.4 End Piece and Reflector End Cap
Step 7.6.5 90° Elbow
Inside
Corner
Grille Brackets
Joint Piece
Decorative Grille
Brackets
Cut grille bracket at
reflector joint piece.
DescriptionPart Number
End Piece01365901
Insert
End Piece
between
grille and
brackets.
Joint Piece
30
Page 37
7.7 Protective Grille Installation
Step 7.7.1 Silicone Cap Installation
Silicone Cap
SECTION 7: OPTIONAL HEATER ACCESSORIES
Grille
Finger
Step 7.7.2 Grille End Cap Installation
A
Grille
C
Pull outward
Step 7.7.3 Grille Installation
DescriptionPart Number
Grille Section08050001
Grille End Cap08050002
Silicone Cap91915951-6P
B
Grille End Cap
D
Bend up 90°
40"
(101 cm)
Reflector
Final Grille
Section
Grille
Grille
End Cap
31
Page 38
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 8: VENTING
WARNING
Carbon Monoxide Hazard
Heaters installed unvented must
be interlocked with sufficient
building exhaust.
Heaters must be installed
according to the installation
manual.
Failure to follow these
instructions can result in death
or injury.
8.1 Venting
This heater must be vented in accordance with the
rules contained in this manual and with the following
national codes and any state, provincial or local
codes which may apply: United States: Refer to
ANSI Z223.1 (NFPA 54) - latest revision; Canada:
Refer to CAN/CGA-B149.1 and B149.2 - latest
revision.
Exhaust end of heater will accept a 4” (10 cm) vent
pipe using the vent adapter (P/N 90502700). To
prevent leakage of condensation, install the vent
adapter with the seam on top and seal the joint using
a high temperature silicone sealant.
Any portion of vent pipe passing through a
combustible wall must have an approved thimble
(P/N 90505600) to conform with the above listed
codes.
Vent pipe must be sloped downward away from the
burner 1/2” (1 cm) for every 20' (6 m).
The heater may be individually vented or common
vented. When venting horizontally, a maximum of two
heaters can be commonly vented. See Page 35, Section 8.9. When venting vertically, a maximum of
four heaters can be commonly vented. See Page 36, Section 8.10.
The heater may also be installed unvented in certain
circumstances according to building ventilation
codes. Refer to the above codes and Page 32, Section 8.2 for further information. Unvented
operation also requires compliance with the
clearances to combustibles given on Page 7, Figure
10.
The bottom of the vent or air intake terminal shall not
be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to public
walkways.
Vent terminal must be installed at a height sufficient
to prevent blockage by snow, and building materials
protected from degradation by flue gasses.
Secure all joints with #8 x 3/8 sheet metal screws.
Seal all joints with high temperature silicone sealant.
Vent terminal must be beyond any combustible
overhang.
8.1.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any
forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below, 4'
(1.2 m) horizontally from, or 1' (.3 m) above any door,
operable window, or gravity air inlet into any building.
8.1.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a
window or door that can be opened in any building,
any non-mechanical air supply inlet to any building,
or of the combustion air inlet of any other appliance.
8.2 Unvented Operation
Sufficient ventilation must be provided in the amount
of 4 cfm per 1000 Btu/h firing rate (United States); 3
cfm per 1000 Btu/h firing rate (Canada).
Use of optional outside combustion air is not
recommended with unvented heaters.
If exhaust fans are used to supply ventilation air, an
interlock switch must be used to prevent the heater
from coming on when the fans are off. This may be
done using a pressure switch.
8.3 Horizontal Venting
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4” (10 cm) vents in either combustible or
noncombustible walls, use P/N 90502100 (Tjernlund
VH1-4) or equivalent, insulated vent terminal. Follow
the manufacturer's instructions for proper installation.
For 6” (15 cm) common vents in either combustible or
noncombustible walls, use P/N 90502101 (Tjernlund
VH1-6) or equivalent, insulated vent terminal. Follow
the manufacturer's instructions for proper installation.
32
Page 39
8.4 Vertical Venting
For 4” (10 cm) common vent, an approved vent cap
(P/N 90502300) must be used.
For 6” (15 cm) common vent, an approved vent cap
(P/N 90502302) must be used.
For common vertical venting of more than two
heaters, See Page 36, Section 8.10.
A vent shall not extend less than 2' (.6m) above the
highest point where it passes through a flat roof of a
building.
8.5 Unvented Operation Tube Termination
Turndown type vent terminal with a screen must be
installed at the exhaust end of the tube. Vent terminal
design shall not incorporate backdraft flap.
FIGURE 20: Tube Termination
SECTION 8: VENTING
8.6 Length Requirements
The maximum vent length allowed is 45' (13.7 m).
The maximum outside air supply duct length allowed
is 45' (13.7 m).
The total vent length, plus outside air duct length,
plus any extensions to minimum heat exchanger
lengths, cannot exceed 65' (19.8 m).
Vent length should be limited to less than 20' (6 m). If
using vent lengths greater than 20' (6 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required. Optional heat
exchanger beyond minimum lengths is considered as
vent length for length determination.
Subtract 15' (4.6 m) of maximum allowed vent or duct
length per vent elbow if more than two are used.
33
Page 40
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
The last section of vent pipe
passing through the roof or
wall may be Type "B" vent pipe.
All other vent materials in the
building must be single wall
vent pipe.
34
Page 41
8.9 Common Side Wall Venting
TOP VIEW
Vent Terminal
Tjernlund VH1-6 or Equivalent
Outside Wall
Outside Wall
SECTION 8: VENTING
Vent Adapter
6" Single Wall Pipe
4" Single Wall Pipe
6" Single Wall Pipe
Sweeping 'Y'
Connection
DescriptionPart Number
Vent Terminal 6” (15 cm)90502101
Vent Adapter
Requirements:
• Maximum of 2 heaters can be commonly vented
through a side wall.
• Heaters must be of the same BTU output.
• Heaters must be controlled by a common
thermostat.
Sweeping 'T'
Connection
Vent Adapter
Vent Terminal
Tjernlund VH1-6 or Equivalent
Outside Wall
Vent Adapter
4 in Single Wall Pipe
4" Single Wall Pipe
35
Page 42
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
8.10 Common Vertical Venting
SIDE VIEW
Type "B" vent cap
(7" or 8") may be used.
(These are not available
from Rapid Engineering.)
Type "B" Vent Pipe
Vent Adapter
4" (10 cm)
Single Wall Pipe
TOP VIEW
18" (46 cm)
Min.
The last section of vent pipe
passing through the roof or
wall may be Type "B" vent pipe.
All other vent materials in the
building must be single wall
vent pipe.
D
Roof
Flashing
Roof
Approved
Thimble
(If Applicable)
Single Wall Pipe
D Area must equal sum
of open area of
individual vents.
Vent Adapter
4" (10 cm)
Single Wall Pipe
Requirements:
• Heaters must be controlled by a common
thermostat.
• Connections to a commom stack must be
positioned to avoid direct opposition between
streams of combustion gases.
36
Page 43
SECTION 8: VENTING
8.11 Outside Combustion Air Supply
IMPORTANT: If the building has a slight negative
8.11.1 Length Requirements
Follow the constraints listed on Page 33, Section 8.6.
pressure or corrosive contaminants, such as
halogenated hydrocarbons, are present in the air, an
outside combustion air supply to the heater is
required. Seal all combustion air pipe joints.
Use of optional outside combustion air is not
recommended with unvented heaters.
The air supply duct may have to be insulated to
prevent condensation on the outer surface. The
outside air terminal must not be more than 1' (31 cm)
above the vent terminal.
8.11.2 Vertical Outside Air Supply for Single Heater Installation
Vent Cap
18" (46 cm)
Min.
Roof
4" (10 cm)
Single Wall Pipe
(Recommended)
DescriptionPart Number
Vent Cap 4” (10 cm)90502300
Flex Hose
(Recommended)
Band Clamp
8.11.3 Horizontal Outside Air Supply for Single Heater Installation
4" (10 cm)
Single Wall Pipe
Vent Cap
Wall
Flex Hose
(Recommended)
Band Clamp
(Recommended)
Burner
Burner
DescriptionPart Number
Vent Cap 4” (10 cm)90502300
37
Page 44
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
8.11.4 Vertical Outside Air Supply for Double Heater Installation
Roof
Vent Cap
6" (15 cm) Single Wall Pipe
Flex Hose
Sweeping 'T'
Connection
(Recommended)
Band Clamp
(Recommended)
DescriptionPart Number
Vent Cap 6” (15 cm)90502302
4" (10 cm)
Single Wall Pipe
Requirements:
• Heaters must be controlled by a common thermostat.
8.11.5 Horizontal Outside Air Supply for Double Heater Installation
6" (15 cm) Single Wall Pipe
BurnerBurner
Flex Hose
(Recommended)
Vent Cap
DescriptionPart Number
Vent Cap 6” (15 cm)90502302
Requirements:
• Heaters must be controlled by a common thermostat.
38
Outside Wall
Flex Hose
(Recommended)
Burner
Sweeping 'Y'
Connection
4" (10 cm) Single Wall Pipe
(Seal All Joints)
Burner
Band Clamp
(Recommended)
Page 45
SECTION 9: GAS PIPING
WARNING
Fire Hazard
Tighten gas hose fittings to connect gas supply
according to Figure 20.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Failure to follow these instructions can result in death,
injury or property damage.
Install the gas hose as shown in Figure 21. The gas
hose accommodates expansion of the heating system
and allows for easy installation and service of the
burner. Before connecting the burners to the supply
FIGURE 21: Gas Connection with Flexible Gas Hose
SECTION 9: GAS PIPING
system, verify that all high pressure testing of the gas
piping has been completed.
There is an expansion of the tube with each firing
cycle, this will cause the burner to move with respect
to the gas hose. This can cause a gas leak resulting
in an unsafe condition if the gas connection is not
made strictly in accordance with Figure 21.
Meter and service must be large enough to handle all
the burners being installed plus any other connected
load. The gas hose which feeds the system must be
large enough to supply the required gas with a
maximum pressure drop of 1/2" w.c. When gas piping
is not included in the layout drawing, the local gas
supplier will usually help in planning the gas piping.
• Do not high pressure test the gas piping with
the burner connected. Failure to follow these
instructions can result in property damage.
• Check the pipe and tubing ends for leaks
before placing heating equipment into
service. When checking for gas leaks, use a
soap and water solution; never use an open
flame.
Shut-Off Valve
(Included With Gas Hose)
2" (5 cm)
12"
(30 cm)
Flexible
Gas Hose
DescriptionPart Number
1/2” Flexible Stainless Steel Gas Hose (US Models)91412200
3/4” Flexible Stainless Steel Gas Hose (US Models)91412203
1/2” Rubber (Type 1) Gas Hose (Canadian Models)91412206
3/4” Rubber (Type 1) Gas Hose (Canadian Models)91412207
Shut-Off Valve must be parallel to
burner gas inlet. The 2" (5 cm)
displacement shown is for the cold
condition. This displacement may
reduce when the system is fired.
Side View
90° Pipe Elbow
(Not Included)
Burner Assembly
(Shown Without Blower Assembly)
Rear View
45°
Hold gas nipple securely
with pipe wrench when
attaching the gas hose.
Failure to follow these
instructions can result in
product damage.
0°
45°
Pipe Nipple
39
Page 46
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 10: WIRING
WARNING
Electrical Shock Hazard
Disconnect electrical power and gas supply before
servicing.
This appliance must be connected to a properly
grounded electrical source.
Failure to follow these instructions can result in
death or electrical shock.
10.1 Line Voltage Thermostat Wiring
Line Voltage Thermostat
120 V-60 Hz
Supply Circuit
Heaters can be controlled using several methods.
Normally thermostats are used to control the heaters
but they can also be controlled by an Energy
Management System. Section 10.1 illustrates the
connection for heaters controlled by a line voltage
thermostat.
For heaters on a low voltage thermostat, See Page 41, Section 10.2. Heaters must be grounded in
accordance with applicable codes: United States:
®
refer to National Electrical Code
ANSI/NFPA 70 latest revision; Canada: refer to Canadian Electrical
Code CSA C22.1 Part I - latest revision.
If any of the original internal wiring must be replaced,
it must be replaced with wiring materials having a
temperature rating of at least 105°C and 600 volts.
L1
L2
Gnd.
NH
Gnd.
Burner 1Burner 2
Additional
Burners
NH
Gnd.
Maximum 5 Burners
Per Thermostat
40
Page 47
10.2 Low Voltage Thermostat Wiring
SECTION 10: WIRING
SPDT Transformer Relay
P/N 90417600
Black
Black
120 V-60 Hz
Supply Circuit
L1
L2
Gnd.
Burner 1
DescriptionPart Number
SPDT Transformer Relay90417600
Low Voltage Thermostat90425100
FRONT VIEWBACK VIEW
R
1
4
COIL
White
3
2
6
COIL
5
Red
C
G
W
Y
NH
Gnd.
Burner 2
Low Voltage Thermostat
Additional
Burners
NH
Gnd.
Maximum 8 Burners
Per Relay
10.3 Internal Wiring
DSIIgnitionModule
PressureSwitch
BLUE
WHITE
GREEN
WHITE
BLACK
N
BLACK
NO
C
Transformer
G
L
BLUE 24 V A/C
BLACKFlame Sense
YELLOW Ground
BROWN Main Valve
BLUE
BROWN
YELLOW
YELLOW
YELLOW
GREEN
BlowerConnection
Electrode
BLACK
GREEN
GasValve
BurnerGround
ElectricalConnection
L2
120 V-60 Hz
L1
Motor/Blower
41
Page 48
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
10.4 Ladder Diagram
Transformer
Pressure
Switch
Gap
Power Supply
120 V - 60 Hz
Blower
120 V
24 V
Ground
Power
Sense
Spark
Valve
Electrode
Ignition Module
Gas Valve
42
Page 49
10.5 Electrical Connection to the Burner
Connect Wires together with
suitable approved wire connections.
L1
L2
Green to Gnd.
White to L2
Gnd.
Black to L1
Conduit Hole
Green
White
SECTION 10: WIRING
Black
Internal Wire Bundle
Burner Box
Electrical Cord or
Flexible Conduit
BX or Romex Connector
43
Page 50
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 11: OPERATION AND MAINTENANCE
This heater is equipped with a direct spark ignition
system.
11.1 Sequence of Operation
1. Turn the thermostat up. When the thermostat
calls for heat, the blower motor will energize.
2. When the motor approaches nominal running
RPM, the pressure switch closes and activates
the ignition module.
3. After a 45 second prepurge, the ignition module
then opens the gas valve and energizes the
spark igniter.
4. When the flame is established, the sparking
sequence ceases.
5. If the flame is not established during the ignition
sequence, the ignition module closes the gas
valve and purge begins. Module will try 2
additional times for ignition (with purges in
between trials). If ignition is not established, the
module will lockout.
6. If the flame extinguishes during operation, the
ignition module will attempt the multiple trial
sequence described in step 5. If ignition is not
re-established, the module will lockout for one
hour or until reset.
11.4 Pre-Season Maintenance and Annual
Inspection
WARNING
Turn off gas and electrical supplies before performing
service or maintenance.
Failure to follow these instructions can result in
death, injury or property damage.
To ensure your safety and years of trouble-free
operation of the heating system, service and annual
inspections must be done by a contractor qualified in
the installation and service of gas-fired heating
equipment.
Turn off gas and electric supplies before performing
service or maintenance. Allow heater to cool before
servicing.
Before every heating season, a contractor qualified in
the installation and service of gas-fired heating
equipment must perform a thorough safety
inspection of the heater.
For best performance, the gas, electrical, thermostat
connections, tubing, venting, suspensions and
overall heater condition should be inspected
thoroughly.
NOTE: Gas flow and burner ignition are among the
first things that should be inspected.
Please see Page 45, Section 11.5 for suggested
items to inspect.
7. After lockout, the control can be reset by turning
down thermostat for five seconds, and then
raising it again to desired temperature, or by
disconnecting power and then reconnecting.
8. When thermostat is satisfied, all power to the
unit is shut off.
11.2 To Shut Off Heater
Set thermostat to lowest setting.
Turn OFF electric power to heater.
Turn OFF manual gas valve in the heater supply line.
11.3 To Start Heater
Turn gas valve and electric power OFF and wait five
minutes for unburned gases to vent from heater.
Turn ON main gas valve.
Turn ON electric power.
Set thermostat to desired temperature.
Burner should light automatically.
44
Page 51
SECTION 11: OPERATIONAND MAINTENANCE
11.5 Maintenance Checklist
All
™
replacement
WARNING
Turn off gas and electrical supplies before performing
service or maintenance.
Failure to follow these instructions can result in
death, injury or property damage.
Installation Code and Annual Inspections:
installations and service of RAPID
performed by a contractor qualified in the installation and
service of gas-fired heating equipment and conform to all
requirements set forth in the RAPID
applicable governmental authorities pertaining to the
installation, service and operation of the equipment.
To help facilitate optimum performance and safety, Rapid
Engineering recommends that a qualified contractor
annually inspect your RAPID
service where necessary, using only RAPID
parts.
™
products must be
™
manuals and all
™
products and perform
The Vicinity of the HeaterDo not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 3, Section 3.
Vehicles and Other
Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 3, Section 3.
ReflectorMake sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 19, Section 6.5.1.
Clean outside surface with a damp cloth.
Vent PipeVenting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
See Page 32, Section 8.
Outside Air InletInlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
45
Page 52
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
TubesMake sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 12, Section 6.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
Gas LineCheck for gas leaks. See Page 39, Section 9.
Burner Observation
Window
Blower Scroll, Wheel and
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Motor
Burner Cup and OrificeClear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
ElectrodeReplace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8” (3.2 mm).
ThermostatThere should be no exposed wire or damage to the thermostat.
See Page 40, Section 10.
Suspension PointsMake sure the heater is hanging securely. Look for signs of wear on the chain
or ceiling.
See Page 12, Figure 12.
Decorative and Protective
Grille (optional)
The grille must be securely attached.
Check that the side reflector extensions are installed correctly and secured in
place if necessary. (Decorative grille only.)
See Page 27, Section 7.5and Page 31, Section 7.7
Make sure shield is installed correctly and secured in place if necessary.
(Decorative grille only.) See Page 28, Section 7.5.2.
Lower Clearance Shield
(optional)
The lower shield must be securely attached. Inspect shield support straps
and lower clearance shield anchor points.
See Page 27, Section 7.4.
Make sure shield is installed correctly and secured in place if necessary.
See Page 27, Section 7.4.
46
Page 53
SECTION 12: TROUBLESHOOTING
12.1 Troubleshooting Flow Chart
SECTION 12: TROUBLESHOOTING
Remove obstruction.
YES
NO
blower turn freely?
Unplug burner. Does the
YES
the burner?
Is there power 120 V at
NO
YESNO
Check relay wiring
failed. Replace blower.
Blower bearings may have
Replace blower.
to the burner.
(if applicable) and wiring
Remove obstruction.YES
NO
the burner obstructed?
Is the vent pipe or the inlet of
YES
NO
set at 1/8"?
Is the igniter gap
Repair, replace, or tighten
NO
Are the air hoses to the
pressure switch secure and
Carefully reset spark gap
hoses as necessary.
leak free?
to 1/8"
YES
wires from the transformer.
Remove the blue and yellow
NO
With the blue and yellow
wires still removed, is the
Is there 24 V at the
transformer secondary?
voltage at the transformer
black and white leads 120 V?
YES
YES
Reconnect transformer
Replace pressure switchYES
wires. Place a jumper wire
Replace transformer.
across the pressure switch.
NO
Is there a spark?
Replace ignition module.
NO
YES
thermostat terminals.
Does the blower turn on?
Place a jumper across the
NOIs the blower obstructed?
Turn up thermostat.
Does the blower turn on?
Check thermostat wiring
and replace thermostat if
NO
YES
necessary.
YES
Unplug burner and check
igniter and ignition wire. Are
NO
Is there spark at the igniter?
they damaged?
Replace igniter and
ignition wire as needed.
NO
and transformer.
Check wiring between the
power cord, blower motor
47
Page 54
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Check for the proper
the burner.
orifice and air plate inside
YESYES
Is the gas outlet pressure
Adjust the valve pressure.
NO
(10.5" for LP)?
3.5" for Natural Gas
YES
Is there gas outlet
the ignition period?
pressure available during
YES
during ignition time?
terminals. Is there 24 V
Measure voltage on valve
NO
NO
Replace gas valve.
YES
NO
Turn valve ON.
Is the knob on the gas
valve in the ON position?
YES
the ignition module OK?
Are the wires connecting
proper polarity.
Electrode leads are
and reconnect leads for
reversed. Disconnect power
Ye s
electrode terminal and
sensing lead wire from
Perform the flame current
check. Remove low voltage
insert a 0-50 DC microamp
Ye s
No
in good condition?
Inspect the ignition/flame
sense electrodes. Are they
No
below 0?
sensor wire and sensor
meter in series with the
probe. Does the meter read
Clean or replace electrode.
is less than 5 microamps,
reposition the electrode in
If the flame current reading
reading.
If repositioning and/or
the flame to get a higher
cleaning electrode does not
result in a suitable current
reading, replace electrode.
NO
YES
YES
purged of air?
Were the gas lines
min., LP should be 11")
ignition correct? (Natural 4.6"
Is the inlet gas pressure during
NO
Does the burner light?Purge lines.
48
NO
YES
NO
YES
at
800-536-3461
Contact Rapid Engineering
NO
TROUBLESHOOT ENDS.
If problems persist, contact your
local RAPID distributor.
NO
Are the wires
Replace/correct wires.Replace ignition module.
Contact gas company.
Check gas line stop cock.
and electrode OK?
connecting the module
NO
YES
Replace/correct wires.
YES
Does the burner stay on?
Check the thermostat and
check the continuity of the
NO
when the call for heat
Does the burner turn off
ground wire.
ends?
Page 55
12.2 Manifold Gas Pressure Setting
Top View of Heater
SECTION 12: TROUBLESHOOTING
Manometer
6
5
4
3
2
1
0
1
2
3
4
5
6
Natural
3.5"
6
5
4
3
2
1
0
1
2
3
4
5
6
Propane
10.5"
49
Page 56
BH-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 13: REPLACEMENT PARTS
Use only genuine RAPID
™
replacement parts.
Use of parts not specified by Rapid Engineering voids warranty.
Failure to follow these instructions can result in property damage.
Blower Assemby
DSIIgnition Module
Blower Outlet Gasket
Tube Gasket
Electrode
Mica Window Assembly
Burner Cup Assembly
REAR VIEW
TOP VIEW
Pressure Switch
Transformer
50
Gas Valve
Page 57
SECTION 13: REPLACEMENT PARTS
DescriptionPart Number
Mica Window Assembly02553203
Electrode Gasket02558501
Tube Gasket02568200
Burner Cup Assembly03020100
Gas Valve (Natural)90032500
Gas Valve (LP)90032502
Electrode90427400
DSI Ignition Module90439500
Transformer90436900K
Pressure Switch
Vent Connection Size: 4” (10 cm)
Outside Air Connection Size: 4” (10 cm)
Refer to figure above for dimensional information.
52
GAS INLET PRESSURE:
Natural Gas:
for BH-40, 60, 80, 100,
115, 125, 140, 1504.6" wc Minimum
for BH-175, 2005.0" wc Minimum
14.0" wc Maximum
LP Gas:11.0" wc Minimum
14.0" wc Maximum
ELECTRICAL RATING (ALL MODELS):
120 V - 60 Hz, 1 A
Page 59
SECTION 15: THE RAPID™ BH WARRANTY
SECTION 15: THE RAPID
™
BH WARRANTY
RAPID ENGINEERING WILL PAY FOR:
Within 42 months from date of shipment from Rapid
Engineering, replacement parts will be provided free of
charge for any part of the product which fails due to a
manufacturing or material defect.
Rapid Engineering will require the part in question to be
returned to the factory. Rapid Engineering will, at its
sole discretion, repair or replace after determining the
nature of the defect and disposition of part in question.
RAPID
of 18 months from date of shipment from Rapid
Engineering or the remaining RAPID
™
Replacement Parts are warranted for a period
™
BH warranty.
RAPID ENGINEERING WILL NOT PAY FOR:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the
™
RAPID
• Use of the RAPID
BH in any way.
™
BH for other than its intended
purpose.
• Incorrect gas or electrical supply, accident, fire,
floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or
accessories not specified by Rapid Engineering.
™
• Failure to install or maintain the RAPID
BH as
directed in the Installation, Operation and Service
manual.
™
• Relocation of the RAPID
™
• Use of the RAPID
BH in a corrosive atmosphere
BH after initial installation
containing contaminants.
™
• Use of the RAPID
BH in the vicinity of a
combustible or explosive material.
™
• Any defect in the RAPID
BH arising from a drawing,
design, or specification supplied by or on behalf of
the consumer.
• Damage incurred during shipment. Claim must be
filed with carrier.
WARRANTY IS VOID IF:
TheRAPID™ BH is not installed by an electrician qualified
in the installation and service of control systems for
heating equipment.
You cannot prove original purchase date and required
annual maintenance history.
The data plate and/or serial number are removed,
defaced, modified or altered in any way.
The ownership of the
RAPID
This warranty is nontransferable.
Rapid Engineering is not permitted to inspect the
damaged controller and/or component parts.
™
BH is moved or transferred.
READ YOUR INSTALLATION, OPERATION AND
SERVICE MANUAL.
If you have questions about your controller, contact your
installing professional. Should you need Replacement
Parts or have additional questions, call or write
Rapid Engineering:
Rapid Engineering
1100 Seven Mile Road, NW
Comstock Park, MI 49321
616.784.0500
On the web at: www.rapidengineering.com
Rapid Engineering's liability, and your exclusive
remedy, under this warranty or any implied warranty
(including the implied warranties of merchantability
and fitness for a particular purpose) is limited to
providing replacement parts during the term of this
warranty. Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may
not apply to you. There are no rights, warranties or
conditions, expressed or implied, statutory or otherwise,
other than those contained in this warranty.
Rapid Engineering shall in no event be responsible for
incidental or consequential damages or incur liability
for damages in excess of the amount paid by you for
the RAPID
™ BH. Some jurisdictions do not allow the
exclusion or limitation of incidental or consequential
damages, so this limitation or exclusion may not apply to
you. This warranty gives you specific legal rights, and you
may also have other rights which vary from jurisdiction to
jurisdiction.
Rapid Engineering shall not be responsible for failure to
perform under the terms of this warranty if caused by
circumstances out of its control, including but not limited to
war, fire, flood, strike, government or court orders, acts of
God, terrorism, unavailability of supplies, parts or power.
No person is authorized to assume for Rapid Engineering
any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF
REPRESENTATIVES:
No representative of Rapid Engineering, other than an
Executive Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by
authorized Executive Officer.
Rapid Engineering's duly
53
Page 60
Page 61
Page 62
Attach this information to a wall near the RAPID
Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service.
Know your model number and installed configuration.
Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual.
Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces below.
heater.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting.
TO TURN OFF THE HEATER
1. Set the thermostat to off or the lowest setting.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation
and service of gas-fired heating equipment.
Some objects can catch fire or explode when placed close
to heater.
Keep all flammable objects, liquids and vapors the required
clearances to combustibles away from heater.
Failure to follow these instructions can result in death,
injury or property damage.
WARNING
Fire Hazard
Maintain ???? cm clearance
to the side and
???? cm clearance below
the heater from vehicles
and combustible materials.
Rapid Engineering
1100 Seven Mile Road, NW
Comstock Park, MI 49321
Telephone: 616.784.0500
Fax: 616.784.1910
Toll Free: 800.536.3461
Installation Code and Annual Inspections: All installations and service of RAPID products must be performed by a contractor qualified in the installation and service of gas-fired heating equipment and
conform to all requirements set forth in the RAPID manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment.
To help facilitate optimum performance and safety, Rapid Engineering recommends that a qualified contractor annually inspect your RAPID products and perform service where necessary, using only
RAPID replacement parts.