Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier’s
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to combustibles away from
equipment.
Some objects will catch fire or explode
when placed close to equipment.
Failure to follow these instructions can
result in death, injury or property
damage.
Rapid® 4000-Series
Direct-Fired Air Handler
Installation, Operation &
Service Manual
4024
4036
4040
4044
4049
4054
4060
4066
4073
4080
4089
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your service technician with necessary information.
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Rapid Engineering LLC.
SECTION 1: Air Handler Safety..............................................1
1.1 Description of Operation...............................................1
1.2 Inspection and Setup ................................................... 1
Table 34: Deflection Force B and BX Belts (in lbs) .............. 123
Table 35: Motor Sheave Drive Torque Specifications .......... 124
Table 36: Motor and Blower Bushing Torque Specifications 124
Table 37: Burner Mode by Amplifier Type............................ 125
Table 38: Maximum Temperature Rise ................................ 126
Table 39: Motor Lubrication Intervals ................................... 133
le on TH8110 Thermostat .. 96
There are references in this manual to various trademarks. All trademarks mentioned herein, whether registered or not, are the
property of their respective owners. Rapid Engineering LLC is not sponsored by or affiliated with any of the trademark or registered
trademark owners, and makes no representations about them, their owners, their products or services.
Yo ur Safety is Important to Us!
This symbol is used throughout
the manual to notify you of
possible fire, electrical or burn
hazards. Please pay special
attention when reading and
following the warnings in these
sections.
Installation, service and, at a minimum, annual
inspection of air handlers must be done by a
contractor qualified in the installation and service of
gas-fired heating equipment.
Read this manual carefully before installation,
operation or service of this equipment.
This air handler is designed for heating nonresidential indoor spaces. Do not install in residential
spaces. These instructions, the layout drawing, local
codes and ordinances and applicable standards that
apply to gas piping, electrical wiring, ventilation, etc.
must be thoroughly understood before proceeding
with the installation.
Protective gear is to be worn during installation,
operation and service. Thin sheet metal parts have
sharp edges. To prevent injury, the use of w
ork
gloves is recommended.
Before installation, check that the local distribution
conditions, nature of gas and pressure and
adjustment of the appliance are compatible.
The equipment must be applied and operated under
the general concepts of reasonable use and installed
using the best building practices.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory or
mental capabilities, or lack of experience and
knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a
person responsible for their safety.
Children should be supervised to ensure that they do
not play with the appliance.
For additional copies of the Installation, Operation
and Service Manual, please contact Rapid
Engineering LLC.
Gas-fired appliances are not designed for use in
atmospheres containing flammable vapors or dust or
atmospheres containing chlorinated or halogenated
hydrocarbons. Recirculated room air may be
hazardous if containing flammable solids, liquids,
and gases; explosive materials; and/or substances
which may become toxic
when exposed to heat (i.e.
refrigerants, aerosols, etc.).
SECTION 1: AIR H ANDLER S AFETY
1.1 Description of Operation
This air handler is a direct-fired, electric, steam, hot
water and/or energy recovery heated fresh air
appliance. It is designed for indoor or outdoor
installation with fresh outdoor air delivered to the
burner. Air handlers are designed to operate in
temperatures as low as -30 °F (-34 °C) variable
frequency drive is only approved for applications
15 °F (-9 °C) and above, unless a control enclosure
heater is installed. The air handler is factory-tested
and may be designed to operate using natural gas or
LPG (check the air handler's rating plate for
information on the appropriate gas). The heat will
modulate to maintain the selected supply air
temperature or room air temperature, depending on
the selected controls. See Page 92, Section .
The air handler may be provided with several
different controls and options to meet various
application requirements. Be sure to read this entire
manual before installation and start-up.
1.2 Inspection and Setup
The air handler may ship in multiple sections based
upon the configuration selected. The air handler was
inspected and operated prior to shipment.
Immediately u
pon receipt of the air handler, check
the fuel and electrical requirements of the air handler
and verify that they match the fuel and electrical
supply available. Verify that the specifications on the
air handler rating plate match the order. Check the air
handler for any damage that may have occurred
during shipment. If any damage is found, file a claim
with the transporting agency. Do not refuse
shipment. Check the installation location to ensure
proper clearances to combustibles. See Page 8, Section 3.1.
Any small options which do not come attached to the
air handler will be found inside the air handler.
Larger accessories (i.e. legs, stand, filter section,
inlet hood) may either ship with the air handler or
separately on another truck. Check the bill of lading
for information.
1 of 154
Page 10
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
1.3 Temporary Storage
If the air handler must be temporarily stored (ie. job
site is not ready for installation of the air handler), the
following procedure should be performed. After
unloading unit from truck, place on a flat clean
surface in a protected area. The air handler should
be set on 4" x 4" (10 cm x 10 cm) pieces of timber to
elevate unit off the ground. Cover air handler with a
tarp or weatherproof material to ensure protection
from the environment. Manually rotate the fan wheel
every 15 days to eliminate grease from settling in the
fan bearings and creating flat spots on the shaft.
Air handlers built for indoor installation are not weatherized.
Rapid Engineering LLC will not be held responsible
for any damage that may occur from outdoor storage.
1.4 Safety Labels and Their Placement
Product safety signs or labels should be replaced by
product user if they are no longer legible. Please
contact Rapid Engineering LLC or your RAPID
®
independent distributor to obtain replacement signs
or labels. See Page 3, Figure 1 through Page 5, Figure 3.
1.5 California Proposition 65
In accordance with California Proposition 65 require-
ments, a warning label must be placed in a highly
visible location on the outside of the equipment (i.e.,
near equipment's serial plate). See label placement
drawing on Page 3, Figure 1 through Page 5, Figure
3 for label location. Avoid placing labels on areas
with extreme heat, cold, corrosive chemicals or other
elements. To order additional labels, please contact
®
Rapid Engineering LLC or your RAPID
independent
distributor.
2 of 154
Page 11
1.6 Label Placement
BDBD
OAOA
7
11
7
VERTICAL CONTROL SIDE
VERTICAL OPP. CONTROL SIDE
HORIZONTAL OPP. CONTROL SIDEHORIZONTAL CONTROL SIDE
3
ON SHRINK WRAP
1
1
2
4
4
4
4
5
6
6
2
5
IF USED.
2
5
2
5
Item Part NumberDescription
119305Label Shock Hazard
219304Label Severe Injury Hazard
319307Label Crush Hazard
419308Label Fire Hazard
519309Label Falling Hazard
619306Label Burn Hazard
791040039 Rapid Logo Label
891070015 Proposition 65 Label
FIGURE 1: 4024 - 4049
SECTION 1: AIR H ANDLER S AFETY
3 of 154
Page 12
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
BD
BD
OA
LIFTING RINGS
OA
LIFTING RINGS
VERTICAL CONTROL SIDE
VERTICAL OPP. CONTROL SIDE
HORIZONTAL OPP. CONTROL SIDE
HORIZONTAL CONTROL SIDE
ACCESS DOOR
GAS CONNECTION
6 x 2 x 12GA
CHANNEL BASE FRAME
DISCONNECT
RC
Curb Channel
2 x 6
6 x 2 x 12GA
CHANNEL BASE FRAME
ON SHRINK WRAP
IF USED.
Curb Channel
2 x 6
Access Door
(18 x 30)
LA
Elec Conn.
Gas Conn.
RC
Disconnect
Disconnect
INLET
BR
BR
BD
EXH
BD
EXH
3
6
5
4
2
1
1
2
5
4
2
5
4
4
6
2
5
7
7
7
7
BURNERFAN
FAN
BURNER
BURNER
FAN
BURNER
FAN
Item Part NumberDescription
119305Label Shock Hazard
219304Label Severe Injury Hazard
319307Label Crush Hazard
419308Label Fire Hazard
519309Label Falling Hazard
619306Label Burn Hazard
791040039 Rapid Logo Label
891040015 Proposition 65 Label
FIGURE 2: 4054 and 4089
4 of 154
Page 13
FIGURE 3: 4000-Series Interior
1
CONE PLATE
12
13
2
12
MOTOR & MOTOR COOLING DUCT
INSIDE
CONTROL ENCLOSURE
8
9
7
7
9
2
CONTROL ENCLOSURE DOOR
PROP 65 LABEL
RATING TAG
ELECTRICAL PRINT
RH INSIDE WALL
CONTROL ENCLOSURE
LH INSIDE WALL
CONTROL ENCLOSURE
11
10
3
4
5
6
2
Item Part NumberDescriptionQty.
1Label - Rotation2
2Label - High Voltage2
3Label - Caution Don’t Overtighten Belt1
4Label - Alignment Guide1
5Label - Rapid Factory Direct Parts Information1
6Label - Bearing Lube Chart1
7Label - Gas Type3
8Label - Outdoor Temp Sensor1
9Label - Min/Max Gas Pressures Required1
10Label - Regulator Model Number1
11Label - Regulator/Internal Relief Required1
12Label - Notice To Installer1
13Label - Caution Yellow Wire Not Diffused1
1491070015 Proposition 65 Label1
SECTION 1: AIR H ANDLER S AFETY
5 of 154
Page 14
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Explosion Hazard
Equipment must have access to
uncontaminated air at all times.
Failure to follow these instructions can result
in death, injury or property damage.
CAUTION
Product Damage Hazard
Do not use equipment in area containing
corrosive chemicals.
Refer to appropriate Material Safety Data
Sheets (MSDS).
Failure to follow these instructions can result
in product damage.
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install and commission the air handler, as well
as the gas and electrical supplies, in accordance
with applicable specifications and codes. Rapid
Engineering LLC recommends the installer
contact a local building inspector or Fire Marshal
for guidance.
•To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the air handler in accordance with
clearances to combustibles.
•To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports.
• To provide access to
air handler
for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
•To never use air handler as support for a ladder or
other access equipment and never hang or
suspend anything from heater.
•To ensure there is adequate air circulation around
the air handler and to supply air for combustion, ventilation and distribution in accordance with
local codes.
• To assemble or install any accessories or
associated duct work using best building
practices.
• To properly size supports and hanging materials.
• To ensure air handler is placed in an approved
application.
6 of 154
• To provide building pressure relief/dampers fans
to prevent over pressurization of a building, if
needed.
2.1 Corrosive Chemicals
Rapid Engineering LLC cannot be responsible for
ensuring that all appropriate safety measures are
undertaken prior to installation; this is entirely the
responsibility of the installer. It is essential that the
contractor, the sub-contractor, or the owner identifies
the presence of combustible materials, corrosive
chemicals or halogenated hydrocarbons* anywhere
in the premises.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen elements
(fluorine, chlorine, bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents, solvents, etc. If
these compounds enter the air supply of the burner, the life span
of the air handler components will be greatly reduced. The location of the outside air supply must be carefully chosen to supply
outside air, free of these compounds, to the burners whenever
the presence of these compounds is suspect. Warranty will be
invalid if the air handler is exposed to halogenated hydrocarbons.
2.2 National Standards and Applicable Codes
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.
2.3 Required Equipment
When lifting of the equipment is required, the
installing contractor is responsible for supplying or
arranging for the appropriate lifting equipment so that
Page 15
the air handler and accessories may be placed in a
safe manner.
The qualified installer or service technician is
responsible for having the appropriate equipment for
the safe installation and start-up of an industrial air
handler. Tools required to commission the equipment
include, but are not limited to, the following:
• Various screwdriver types and sizes
• Various adjustable wrenches
• Torque wrenches
• Pipe wrenches sized appropriately for the gas
train components
• Drill motor and various drill bits and runners
• U-tube manometer or gas pressure gauge
• Volt meter
• Clamp style ammeter
• Belt tension gauge
• Thermometer
SECTION 2: INSTALLER R ESPONSIBILITY
7 of 154
Page 16
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to
combustibles away from equipment.
Some objects will catch fire or explode when
placed close to equipment.
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 3: CRITICAL CONSIDERATIONS
WARNING
• Locate the air handler so that the air intakes are
not too close to any exhaust fan outlets, gasoline
storage or other contaminants that could
potentially cause dangerous situations.
• Keep gasoline or other combustible materials
including flammable objects, liquids, dust or
vapors away from this air handler or any other
appliance.
• Maintain clearances from heat sensitive material,
equipment and workstations.
Clearances to combustibles do not denote
clearances for accessibility. Minimum clearance for
access is 48" (122 cm). Minimum clearance for
accessibility applies to the control enclosure, fan
access panel and filter access panel (when
equipped).
The stated clearances to combustibles represent a
surface temperature of 90 °F (50 °C) above room
temperature (90 °F [50 °C] plus ambient
temperature). Building materials with a low heat
tolerance (i.e. plastics, vinyl siding, canvas, tri-ply,
etc.) may be subject to degradation at lower
temperatures. It is the installer’s responsibility to
assure that adjacent materials are protected from
degradation.
Explosion Hazard
Fresh air supply duct and burner housing
must be purged with fresh air four times
before every ignition.
Explosive vapors will ignite if not evacuated
before ignition attempt.
Failure to follow these instructions can result
in death, injury or property damage.
3.1 Required Clearances to Combustibles
Clearances are the required distances that
combustible objects must be away from the air
handler to prevent fire hazards. Combustibles are
materials that may catch on fire and include common
items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times
for safety.
Check the clearances on each air handler being
installed to make sure the product is suitable for your
application and the clearances are maintained.
Clearances to combustibles for all models are 6"(15.2
cm) on all surfaces. Read and follow the safety
guidelines below:
• Maintain clearances from vehicles parked below the
air handler. See Page 9, Section 4.4.
3.2 Hardware
Unless otherwise specified, all hardware must be
torqued to settings on Page 8, Table 1.
Table 1: Recommended Torque Settings
Bolt Head
Grade Marking
Nut Grade
Marking
Bolt SizeGrade 2Grade 5
10-2427 in•lb42 in•lb
1/4-2065 in•lb101 in•lb
5/16-1811 ft•lb17 ft•lb
3/8-1619 ft•lb30 ft•lb
8 of 154
Page 17
SECTION 4: NATIONAL STANDARDS AND
APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the nameplate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1- latest revision,
Natural Gas and Propane Installation Code.
SECTION 4: NATIONAL S TANDARDSAND A PPLICABLE C ODES
4.5 Electrical
Electrical connection to air handler must be in
accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances, and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
4.2 Installation Codes
Installations must be made in accordance with
the Standard for the Installation of AirConditioning and Ventilating Systems, NFPA
90A - latest revision for the installation of air
conditioning and ventilating systems.
4.3 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard on Aircraft
Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code, Standard CSA B149.1 - latest
revision.
4.4 Parking Structures and Repair Garages
Installation in garages must be in accordance
with the following codes:
United States: Refer to standard for Parking
Structures, NFPA 88A - latest revision or Code
for Motor Fuel Dispensing Facilities and Repair
Garages, NFPA 30A - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code, standard CSA B149.1 - latest
revision.
4.6 Venting
The venting must be installed in accordance
with the requirements within this manual and
the following codes:
United States: Refer to NFPA 54/ANSI Z223.1latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision,
Natural Gas and Propane Installation Code.
4.7 High Altitude
These air handlers are approved for
installations up to 2000' (609.6 m) (in the US)
and 4500' (1371.6 m) (in Canada) without
modification. Consult factory if US installation is
above 2000
is above 4500
'
(609.6 m) or Canadian installation
'
(1371.6 m).
9 of 154
Page 18
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 5: SPECIFICATIONS
Dimension and estimated weight tables apply to both vertical and horizontal units of the same style.
All dimensions are in inches and all weights are in pounds, but are subject to change without notice.
Dimensions apply to both horizontal and vertical units. Filters and legs are shipped loose. Control enclosure
for 3" or smaller manifolds is 57"H x 57"W x 25"D. (B dimension of model 4024 cabinet is approximately 20"
smaller than the control enclosure. Model 4049 control enclosure is 57"H x 57"W x 20"D.) To minimize water
entrainment, an inlet hood with drift eliminator or inlet plenum is recommended. Outdoor duct sizes vary.
Control enclosure can be located on left or right side of unit. (Shown on right side in drawings.) Consult Rapid
Engineering LLC for additional information.
All industrial air handlers are built based on customer specific static pressure.
All ductwork and connections must be sized per SMACNA (Sheet Metal and Air Conditioning Contractors’
National Association).
The legend below details abbreviations used in this section and applies to Page 11, Figure 4 through Page 18, Figure 11.
Legend
OA = Outside Air
CE = Control Enclosure
BD = Bottom Discharge
LD = Left Discharge
RD = Right Discharge
UD = Up Discharge
BR = Bottom Return
RR = Right Return
LR = Left Return
ER = End Return
FJ = Field Joint *
AD1 = Access Door **
AD2 = Access Door ***
NOTE: Table to be used when calculating total tonnage of cooling adjusted for elevation.
10,000/
20.58
20 of 154
Page 29
FIGURE 13: Mechanical Cooling
OA
BD
UD
LD/RD
ELECTRICAL
CONNECTION
GAS CONNECTION
BR
CE
OA
RD
BD/UD
CE
FJ
LD
FJ
AD1AD2
AD1AD2
PLAN VIEW
RIGHT SIDE VIEW
FAN SECTIONBURNER SECTION
COIL SECTION
(OPTIONAL)
EVAPORATIVE
COOLER
(OPTIONAL)
ENERGY
RECOVERY
SECTION
(OPTIONAL)
FILTER
SECTION
(OPTIONAL)
INLET PLENUM
(OPTIONAL)
INLET HOOD
(OPTIONAL)
OR
DD
CC
EE
SECTION 5: SPECIFICATIONS
Table 13: Dimensions
Compatible
Cabinet
Sizes
100% RA
Available Tons
0% OA/
Airflow - Cubic
Feet per Minute
(CFM)
3,000-7,000248-35113.833 x 60218509684072
7,001-10,0002418-50118.036 x 72389556804472
10,001-20,00036-4025-100238.3 27 x 1022615231106572
20,001-27,50036-4450-138252.535 x 1083815241168078
27,501-30,00040-4969-150261.239 x 1134494901219078
30,001-35,00049-6075-175270.041 x 1234285001319684
35,001-50,00060-7388-250293.845 x 15037353315410584
50,001-60,00066-80125-3003106.536 x 142469563150126102
60,001-65,00073-89150-3253117.036 x 156513556164126102
* MUA configuration only.
** AM requires high velocity return air damper.
¤ Class II wheels
CF= Consult Factory
IMPORTANT NOTES:
Sound levels are in dBA at 5' from the supply air opening. This figure does not account for attenuation,
additional noise or directivity factors. More horsepower required includes both the running horsepower and
the starting torque requirements. Horsepower can be greater than the standard fan curve charts. Brake
horsepower does not include drive losses. For external static pressure greater than 2", contact your local
representative or Rapid Engineering LLC. For operation in altitudes exceeding 2000' above sea level, contact
the factory. The recommended motor horsepowers shown for the Fan Selection Chart in the 0 in. wc external
static pressure column include fan and burner static pressures only (internal equipment static pressure).
Other cabinet options could add static pressure and should be included in the external static pressure used
to select motor horsepower. See the Static Pressure Drops in Table 20, Page 41 for the external static
pressu
res that should be added for selected options.
(in wc)
Brake Horse Power (HP)
@ Noted External Static Pressure
(in wc)
101.5107.1112 .8118 .5124.
SECTION 5: SPECIFICATIONS
dBA Decibel @
Noted External
Static Pressure
(in wc)
91.2
96.590
5
4
91
25 of 154
Page 34
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Table 19: Static Pressure Drops for Options
Descriptionin wc
Cooling Coil Section0.10
Cooling CoilCF
Damper - Inlet0.05
Damper - Low Leak0.05
Damper - Discharge0.10
Damper - Discharge, Low Leak0.10
Supply Air EndCF
Discharge Plate0.05
Discharge Head - One Way0.10
Discharge Head - Three Way0.10
Discharge Head - Four Way0.05
Horizontal Inlet Hood0.00
Horizontal Inlet Plenum0.10
Vertical Inlet Plenum Base0.05
Moisture Limiter For Horizontal Inlet Hood0.10
Aluminum Mesh Filters For Horizontal Inlet Hood0.15
Vertical Stand with Polyester Filters (FR)0.25
Outside Air Filter Section, No Filters0
Filtered Mixing Box, No Filters0
Filters - Polyester0.25
Filters - Aluminum Mesh0.15
Filters - 30% Pleated0.25
Custom Filter Options (Bag, Cartridge, HEPA)CF
Evaporative Cooling Section (ECM)0.25
Evaporative Cooling Section (ECM-D)0.50
Note:
Calculate the static pressure for selected cabinet options plus any ductwork. Use external static pressure
column found in Page 24, Table 17 through Page 25, Table 18 Fan Selection Charts to determine motor
horsepower.
26 of 154
Page 35
SECTION 6: LIFTINGAN AIR H ANDLER (RIGGING)
SECTION 6: LIFTING AN AIR HANDLER
(RIGGING)
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Failure to follow these instructions can result
in death, injury or property damage.
The air handler must be installed in compliance with
all applicable codes. The qualified installer or service
technician must use best building practices when
installing the air handler and any optional equipment.
This appliance requires at least 4 CFM (6.8
outside air per 1,000 Btu/h (.293 kW). Any air
handler that recirculates air from the heated space
must use the return air opening to prevent any return
air from passing over the burner.
IMPORTANT: Four eye bolts are provided with each
upright air handler. These eye bolts are to be used
when lifting the air handler for placement on the
provided support legs. DO NOT Install the support
legs prior to lifting the air handler, damage to the legs
and /or air handler may occur.
3
m
/h) of
6.1 Preparing to Lift the Air Handler
Prior to lifting the air handler, the following steps must
be performed:
1. R e m o ve all packaging or banding that attached
the air handler to the skid and ensure that the
air handler is no longer bound to a skid or truck
bed.
2.Remove all packaging or blockers.
3.Remove all of the accessories or packages that were shipped on the same skid, inside the air
handler, or inside the control enclosure.
4.Inspect the air handler to:
•Verify that there is no damage as a result of
shipping.
•Ensure that it is appropriately rated for the utilities available at the installation site.
•Verify that the eye bolts (lifting lugs) are
intact, undamaged and secured to the air
handler.
•Ensure factory-installed hardware is
torqued to appropriate setting.
5.Prepare the installation location to be ready to
accept the air handler (i.e. roof curb or legs).
6.Verify that the lifting equipment can handle the
air handler’s weight and the required reach.
See Page 12, Table 3, Page 14, Table 5, Page
16, Table 7, Page 18, Table 9 and Page 14,
Ta b l e 5 for air handlers weight.
27 of 154
Page 36
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
LIFTING SLINGS
END VIEW
CLCR
CRANE OR HELICOPTER CABLE
FAN
SECTION
BURNER
SECTION
FILTER
SECTION
FILTER MIX BOX
OR
TRANS, EVAP &
FILTER SECTION
INLET
PLENUM
SPREADER BAR
END VIEW
CLCR
FILTER MIX BOX
OR
TRANS, EVAP &
FILTER SECTION
INLET
PLENUM
NOTE: FOR MODELS 4080-4089, ACCESS DOOR IS ON BURNER SECTION.
LIFTING SLINGS
FAN
SECTION
BURNER
SECTION
FILTER
SECTION
6.2 Lifting a Horizontal Air Handler
FIGURE 15: Lifting a Horizontal Air Handler Filter Section and Options (Model 4024 - 4049)
FIGURE 16: Lifting a Horizontal Air Handler with Options (Model 4054 - 4089)
28 of 154
Page 37
6.3 Lifting an Vertical Air Handler
BA
C
BA
C
BA
C
WOODEN BLOCKS
BASE FRAME
BASE FRAME
NOTE: SHEET METAL CHANNEL
OR ANGLE IRON FRAME MUST BE
ALIGNED ON ALL SECTIONS
INLET
Shipping Position:
1. Attach crane sling hooks to eye bolts A &
B (4 places.)
2. Lift off truck.
3. Place on a clean flat dry surface free from
water, mud, etc.
Turning Position:
4. Remove eye bolts B. (2 places)
5. Attached eye bolts from B to corner C (2
places.)
6. Attach crane sling hook to A eye bolts A
(2 places.)
7. S lo wly raise and rotate 90 degrees.
Vertical Position:
8. Place air handler section on 4" (10.2 cm)
wooden blocks.
9. Attach crane sling hooks to eye bolts A &
C (4 places).
10. Air handler/section is now ready to be
lifted into place.
NOTE: On fan sections lifting lugs are welded on supply air end.
FIGURE 17: Lifting an Vertical Air Handler (All Models)
SECTION 6: LIFTINGAN AIR H ANDLER (RIGGING)
29 of 154
Page 38
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
LIFTING LUGS
B
U
RNER
REMOVE LIFTING
EYE BOLTS AFTER
SETTING SECTION
F
IL
T
ER SE
CT.
SE
CT
IO
N
MIX BOX
S
EC
TION
F
A
N
&
FILTE
R
S
ECT.
S
ECTIO
N
MIX B
O
X
SECTIO
N
B
U
RNE
R
SEC
TION
F
A
N
LEGS (4 required)
REMOVE LIFTING
EYE BOLTS AFTER
SETTING SECTION
SHEETMETAL CHANNEL
OR ANGLE IRON FRAME
MUST BE ALIGNED ON
ALL SECTIONS
Model 4024 - 4049Model 4054- 4089
LIFTING LUGS
SHEETMETAL CHANNEL
OR ANGLE IRON FRAME
MUST BE ALIGNED ON
ALL SECTIONS
REMOVE LIFTING
EYE BOLTS AFTER
SETTING SECTION
LEGS (4 required)
NOTE: Sections may
vary as shown
SEE FIGURE 19,
PAGE 30
SEE FIGURE 19,
PAGE 30
SEE FIGURE 19,
PAGE 30
FIGURE 18: Lifting an Vertical Air Handler with Filter Section and Mixing Box
30 of 154
Page 39
6.4 Upright Assembly Alignment
ROPE
WALL
EXTERNAL
CAULKING
FIELD JOINT
SECTION VIEW-A
BURNER INLET/FAN DISCH. SECTION
FILTER MIXBOX DISCH./BURNER INLET
ALIGNMENT DETAIL.
(FOR UPRIGHTS MODELS 49-89 ONLY)
5/8 X 2 3/4
THREADED ROD
ALIGNMENT PIN
FAN SECTION INLET FRAME
OR BURNER INLET FRAME
WITH 7/8" CLEARANCE HOLE.
FMB DISCH./BURNER DISCH.
SECTION FRAME
5/8-11 FLANGE NUT TACK
WELDED (2) TO BURNER/FMB
DISCH. FRAME IN OPPOSITE
CORNER FROM ONE ANOTHER.
APPLY ROPE
CAULKING AROUND
PERIMETER OF FRAME.
DETAIL:
PLAN VIEW:
NOTE: THREADED ROD SHIPPED LOOSE. MOUNT IN OPPOSITE CORNERS WITH PROPER WELDED NUT.
FIGURE 19: Inlet Alignment
SECTION 6: LIFTINGAN AIR H ANDLER (RIGGING)
31 of 154
Page 40
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 7: AIR HANDLER ASSEMBLY
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Failure to follow these instructions can result in death, injury or property damage.
For models 4024 - 4049, the burner and fan sections of the air handler are shipped as one piece. Filter
section and/or filter mix box can be mounted to air handler when requested.
For models 4054 - 4089, the burner and fan sections of the air handler are shipped as two pieces that
require field-assembly. To assemble, use the supplied hardware and bolt the fan section to the burner section
through pre-drilled holes. Supplied hardware must be torqued to recommended specifications on Table 1, Page 8.
Caulk (provided by others) the sides, roof and bottom seams between the fan section and burner section. See Page 33, Figure 7.1through Page 35, Figure 22.
NOTE: After the equipment sections are set together (if shipped separately), connection of the electrical
conductors between the sections is required. The conductors are numbered on both ends. Join the
conductors like numbers. The quantity of conductors supplied varies with the selected options. In addition,
motor-supply conductors must be connected to the fan motor of model sizes 4054-4073. See Page 37, Section 7.4.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Equipment and
accessories are
heavy.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
32 of 154
Page 41
7.1 Caulking the Air Handler
3" (78.7 cm) ROOF TAPE PROVIDED BY MANUFACTURER
(NOT REQUIRED ON VERTICAL AIR
HANDLER OR INDOOR UNITS)
HOUSING SKIN
HOUSING SKIN
CAULK AFTER ASSEMBLY
HOUSING SKIN
3/8" x 3/4" STRIP
CLEAN HOUSING SKIN
3" (78.7 cm) ROOF TAPE
TYPICAL VERTICAL JOINT
PRIOR TO ASSEMBLY.
CAULK EACH VERTICAL JOINT
TYPICAL ROOF JOINT
CAULK EACH HORIZONTAL JOINT
AFTER ASSEMBLY APPLY
TYPICAL ROOF JOINT
PRIOR TO ASSEMBLY.
OF CAULKING
THE 3" (78.7 cm) ROOF TAPE
"A" Type Joint
"B" Type Joint
(CAULK PROVIDED BY OTHERS)
3/8" x 3/4" STRIP OF CAULKING
(PROVIDED BY MANUFACTURER)
TYPICAL VERTICAL JOINT
AFTER ASSEMBLY.
CAULK EACH VERTICAL EXTERIOR JOINT
NOTE: FAILURE TO PROPERLY CAULK THE AIR HANDLER JOINTS WILL ALLOW WATER TO ENTER THE AIR HANDLER.
Instructions for Roof Tape Installation:
1. Wipe surface clean and dry.
2. Peel backing off 3" (78.7cm) roof tape.
3. Apply roof tape over field joint.
4. Press tape firmly to form a tight seal (roll out if possible).
5. 3" (78.7 cm) roof tape NOT required on vertical air handlers.
6. Do not apply roof tape when outside temperature is below 40° F.
7. Roof tape is not required for indoor air handlers.
FIGURE 20: Caulking Air Handler Joints
SECTION 7: AIR H ANDLER A SSEMBLY
33 of 154
Page 42
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
A
P
L
E
N
U
M
INL
ET
A
IN
LET
B
B
U
R
N
E
R
FA
N
S
E
C
T
IO
N
S
EC
T
IO
N
B
HORIZONTAL AIR HANDLER
WITH INLET PLENUM
HORIZONTAL AIR HANDLER
WITH INLET PLENUM AND
OUTSIDE AIR FILTER
HORIZONTAL AIR HANDLER
WITH INLET PLENUM AND
FILTER MIX BOX
APPLY 3" (78.7 cm) ROOF TAPE TO ALL
ROOF JOINTS. COMPONENTS MAY
VARY AS SHOWN BELOW.
A
SEC
T
I
O
N
SE
C
TION
FAN
B
URNE
R
SECTIO
N
F
ILTE
R
B
P
L
E
N
U
M
IN
L
E
T
M
IX
B
OX
SECTIO
N
B
A
B
B
A
IN
L
ET
P
LE
N
U
M
A
IN
LE
T
F
ILT
E
R
S
ECT
ION
BUR
N
E
R
F
A
N
SE
C
T
IO
N
S
E
C
TIO
N
B
B
B
“A” Type Joint (typical both sides):
Seal with a HEAVY bead of calking.
(provided by others)
“B” Type Joint:
Cover with 3" (78.7 cm) Roof Tape.
(provided by manufacturer)
NOTE:
Failure to properly caulk the air
handler joints will allow water to
enter the air handler.
Caulk supply air/return sleeves
as appropriate.
“A” Type Joint : Vertical joint on
multiple-piece air handlers and inlet
hoods. Run a HEAVY bead of caulking (provided by others).
“B” Type Joint : Roof joints on multiple-piece
air handlers and inlet hoods. Cover with
3" (78.7 cm) roof tape (provided by manufacturer).
IN
LE
T
7.2 Caulking a Horizontal Air Handler
FIGURE 21: Caulking a Standard Horizontal Air Handler
Note: Sections may vary as shown.
34 of 154
Page 43
7.3 Caulking an Vertical Air Handler
SHEETMETAL CHANNEL OR ANGLE IRON FRAME
MUST BE ALIGNED ON ALL SECTIONS.
RAIN SKIRT ON
OUTDOOR AIR HANDLER
"A
Ó
"AÓ
"AÓ
"AÓ
LEGS
"A"
LIFTING LUGS
"A"
"A"
FIELD ATTACHMENT
"A"
"A"
RAIN SKIRT ON
OUTDOOR AIR HANDLER
FIELD ATTACHMENT
SHEETMETAL CHANNEL OR
ANGLE IRON FRAME MUST BE
ALIGNED ON ALL SECTIONS.
LIFTING LUGS
LEGS
"A" TYPE JOINT:
SEAL WITH HEAVY
BEAD OF CALUKING
(PROVIDED BY OTHERS)
FIGURE 22: Caulking a Standard Vertical Air Handler
SECTION 7: AIR H ANDLER A SSEMBLY
NOTE: Sections may vary as shown.
35 of 154
Page 44
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
--
TYPICAL ASSEMBLY
3'-4"
3'-4"
TYPICAL ASSEMBLY
NOTE:DISCHARGE AND RETURN AIR SLEEVE'S ARE A OPTION AND CAN BE PURCHASED
THRU RAPID, SEE CHART FOR ACTUAL OD OF DUCTS IF BEING BUILT AND INSTALLED BY
SERVICE CONTRACTOR.
A OD
X
B OD
SELF TAPPING SCREWS
EVERY 6-8" C.D.
AIR HANDLER
HOUSING
RETURN AIR
SLEEVE
CAULKING
FLANGE
NOTE: TEK SCREW RETURN SLEEVE
TO INSIDE OF AIR HANDLER
RETURN AIR FLANGE.
RETURN AIR
DAMPER
SELF TAPPING SCREWS
EVERY 6-8" C.D.
AIR HANDLER
HOUSING
FLOOR DISCH. FLANGE
LENGTH (MODELS 24-66) = 3.75"
(73-89) = 2"
DISCHARGE SLEEVE
CAULKING
AIR HANDLER
RETURN AIR FLANGE
DISCHARGE
AIR
RETURN
AIR
SEE CHART BELOW
FOR OD DIMENSION OF
DISCHARGE DUCT BEFORE
MAKING WALL PENETRATION.
2" FLANGE ON BOTH ENDS OF
DISCHARGE DUCT
RETURN
AIR
DISCHARGE
AIR
DISCHARGE DUCT
RETURN DUCT
FIGURE 23: Assembling Optional Discharge / Supply and Return Sleeves.
36 of 154
Page 45
7.4 Accessory Connections
Legend
OAOutside Air
BRBottom Return
BDBottom Discharge
LCLeft Controls
DUAL PERFORATED
ADJUSTABLE PANEL
ACCESS PANELS:
REMOVE TO BOLT
SECTIONS TOGETHER
COOLING COIL
MANIFOLD
CONNECTIONS
COIL HOUSING ACCESS
¥ MODELS 4024-4049 = 4" FORMED 10 GA GALV CHANNELS
¥ MODELS 4054-4066 = 6" FORMED 10 GA GALV CHANNELS
¥ MODELS 4073 = 3
x 3 x
3/16" ANGLE IRON
¥ MODELS 4080-4089 = 4
x 3 x
1/4" ANGLE IRON
FIGURE 24: Electrically Connecting Joined Sections
SECTION 7: AIR H ANDLER A SSEMBLY
Inlet Hood
OA
LEFT SIDE VIEW
TYPICALLY 6 THHN CONDUCTORS
AND 1 SHIELDED CABLE
1/2" CONDUIT TYP.
CONTROL
CABINET WALL
NOTE:
DETAIL A
Filter
Mixbox
BR
Burner
SectionFan Section
LC
BD
NOTE: TYPICALLY 2
THHN CONDUCTORS
AND 1 SHIELDED
CABLE
DETAIL B
FIGURE 25: Installing Cooling Coil Section
37 of 154
Page 46
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
MODUS
LOHI
PROTECT TUBING
OPENING FROM
THE WIND.
(Installed by others.)
OUTSIDE AIR DUCT
BUILDING WALL
OR ROOF
AIR HANDLER
SUPPLY AIR
NOTE: BUILDING PRESSURE
TRANSDUCER (INSIDE
CONTROL PANEL - TYPICAL)
FIELD INSTALLED
(Supplied by others)
MODUS
LO HI
RETURN AIR DUCT
AIR HANDLER
5/16" (Minimum)
PLASTIC TUBING
(Installed by others)
RETURN AIR
DAMPER BLADE
NOTE: ENSURE OPEN END OF TUBING
IS AWAY FROM ANY AIR FLOW. DO NOT
MOUNT TUBING NEAR SUPPLY AIR
AND RETURN AIR OPENINGS.
INDOOR INSTALLATION
OUTDOOR INSTALLATION
Factory furnished piping & devices.
Field furnished piping & devices.
HEADER
UNION
BLEED-OFF VALVE
WATER LEVEL
Notes
Legend
1)
2)
3)
4)
EVAPORATIVE COOLING MODULE
FLOAT VALVE & MAKE-UP CONN.
MANUAL SHUT-OFF VALVE
OVERFLOWR CONN.
DRAIN CONN.
VACUUM BREAKER
MANUAL DRAIN VALVE
PER CODE
FILL VALVE SOLENOID 1” NORMALLY CLOSED.
SUPPLY LINE DRAIN COLENOID 1” NORMALLY OPEN.
ROOF DRAIN
ROOF
ROOF CURB
RECIRCULATION PUMP
SUMP DRAIN 1 1/2”
BALL VALVE POWERED OPEN & CLOSED.
AIR GAP
All solenoids must be installed
in a line no smaller than the
solenoid orifice.
Pitch drain line minimum 1/8”
per foot towards outlet
Supply & supply line drain solenoids
must be installed in a non-freeze
location.
Makeup line must be installed
with no traps or sages above
the roof line.
WATER FLOW ADJUSTMENT VALVE
FIGURE 26: Installing Pressure Transmitter Tubing for AM and VAV
SUMP DRAIN 1 1/2”
BALL VALVE POWERED OPEN & CLOSED
CONDUCTIVITY CONTROL
Factory furnished piping & devices.
Field furnished piping & devices.
Notes
Legend
1)
2)
3)
4)
All solenoids must be installed
in a line no smaller than the
solenoid orifice.
Pitch drain line minimum 1/8”
per foot towards outlet
Supply & supply line drain solenoids
must be installed in a non-freeze
location.
Makeup line must be installed
with no traps or sages above
the roof line.
WATER FLOW ADJUSTMENT VALVE
Factory furnished piping & devices.
Field furnished piping & devices.
Notes
HEADER
EVAPORATIVE COOLING MODULE
FLUSH SOLENOID NORMALLY CLOSED
MANUAL SHUTOFF VALVE
FLOAT VALVE & MAKE-UP CONN.
MANUAL SHUTOFF VALVE
OVERFLOW CONN.
DRAIN CONN.
VACUUM BREAKER
MANUAL DRAIN VALVE
AIR GAP
PER CODE
UNION
CHECK VALVE
BLEED-OFF VALVE
WATER LEVEL
RECIRCULATION PUMP
ROOF CURB
ROOF
ROOF DRAIN
SUPPLY LINE DRAIN SOLENOID 1” NORMALLY OPEN.
FILL VALVE SOLENOID 1” NORMALLY CLOSED.
SUMP DRAIN 1 1/2”
BALL VALVE POWERED OPEN & CLOSED.
Legend
1)
2)
3)
4)
All solenoids must be installed
in a line no smaller than the
solenoid orifice.
Pitch drain line minimum 1/8”
per foot towards outlet
Supply & supply line drain solenoids
must be installed in a non-freeze
location.
5)
Header orifices serve as vacuum
break for flush solenoid connection
to header.
Makeup line must be installed
with no traps or sages above
the roof line.
WATER FLOW ADJUSTMENT VALVE
FIGURE 28: Conductivity Control and Freeze Protection (Evaporative Cooling Package #2)
FIGURE 29: Protection and Auto-Flush (Evaporative Cooling Package #3)
39 of 154
Page 48
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
FIGURE 30: Evaporative Cooling Trap Detail
40 of 154
Page 49
SECTION 8: ROOF CURB
SECTION 8: ROOF C URB
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Failure to follow these instructions can result in death, injury or property damage.
The roof curbs that support the air handler and
accessory sections are available for all horizontal air
handlers. See Page 41, Table 20 for roof curb. Roof
curbs are shipped unassembled and require field
assembly. Double check dimensions after assembly
before roof material is installed and compare to the
drawing on Page 40, Figure 30. NOTE: Before installation, verify that you have the
correct roof curb and all required assembly brackets.
If any components are missing, contact Rapid
®
Engineering LLC or your RAPID
independent
representative.
8.1 Roof Curb Assembly and Installation
Assemble roof curb according to the assembly
drawings in Page 43, Section 32. Supplied hardware
must be torqued to recommended specifications on Page 8, Table 1.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
Table 20: Roof Curbs (availability based on style)
Extended Curb (ADD for each section)
Fan
Style
MUA******
FR****
AM*******
VAV*****
and
Burner
Inlet
Coil
Mix
BoxOAFilter*
Inlet
Plenum
Evap.
Cooling
Section
and
Transition
External
Fan
Motor
with
Belt
Guard
*Curb add required only when an inlet plenum is
ordered with an outside air filter section.
For pitched curbs, insulated curbs, w
ood nailers or
cub mounted vibration isolation, consult the factory.
NOTE: Check the installation location to ensure
proper clearances to combustibles and clearance for
access. Page 8, Section 3.
Place the curb on the roof in the position in which it
will be installed. Check that the diagonal
measurements are within 1/8"(3 mm) of each other.
To ensure a weatherproof seal between the air
handler and the curb, the curb must be level with no
twist from end to end. Shim level as required and
secure curb to roof deck using best building
practices. The curb is self-flashing. Install roofing
material as required.
41 of 154
Page 50
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
NOTE: Adapter shown for models 4024 through 4089
horizontal AM, FMB and MUA.
FIGURE 31: Roof Curb
42 of 154
Page 51
FIGURE 32: Roof Curb Installation
COUNTER FLASHING
(BY OTHERS)
ROOFING (BY OTHERS)
CANT STRIP (BY OTHERS)
UNIT CURB ANGLE
¥ MODELS 4024-4049: 4 x 2 Sheetmetal Formed Channel
¥ MODELS 4054-4066: 6 x 2 Sheetmetal Formed Channel
CANT STRIP (BY OTHERS)
ROOFING (BY OTHERS)
COUNTER FLASHING (BY OTHERS)
ROOF INSULATION
BY CONTRACTOR
SILICONE CAULK
(BY OTHERS)
TYPICAL CURB INSTALLATION
ROOF CURB
CHANNEL
UNIT CURB ANGLE
¥ MODEL 4073: 3 x 3 x 3/16 Angle Iron
¥ MODELS 4080-4089: 4 x 3 x 1/4 Angle Iron
LAG BOLT
OPTIONAL
TYPICAL CURB INSTALLATION
1"
2"
4024-4049: 4"
4054-4066: 6"
ROOF INSULATION
BY CONTRACTOR
1"x4" NAILER
(BY OTHERS)
SILICONE CAULK
(BY OTHERS)
ROOF CURB
CHANNEL
1"x4" NAILER
(BY OTHERS)
DO NOT TWIST OR BEND FRAME
SECTION 8: ROOF C URB
43 of 154
Page 52
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
DETAIL 2
DETAIL 1
DETAIL 3
DETAIL 3
DETAIL 3
OVERHEAD PLANVIEW
SUPPLY AIR OR
INLET END
SIDE
SPLICE &
CROSSBRACE
12 BOLTS,
FLAT WASHERS,
LOCK WASHERS,
FLANGE NUTS
INTERMEDIATE
CROSSBRACE
8 BOLTS,
FLAT WASHERS,
LOCK WASHERS,
FLANGE NUTS
CORNER
CONNECTION
7 BOLTS,
FLAT WASHERS,
LOCK WASHERS,
FLANGE NUTS
1. Refer to the assembly drawings shipped with the curb.
2. Curb length can vary by options selected.
3. Verify overall assembly dimensions before roofing.
4. Curb material is 16 GA for models 4024 through
4049 and 14 GA for models 4054 through 4089.
5. All top corners to be flush and perpendicular.
6. All joints must be caulked.
NOTE: All top corners to be flush and perpendicular. All joints must be caulked.
FIGURE 33: Roof Curb Assembly with Brackets
44 of 154
Page 53
FIGURE 34: Duct Support Adapter
ASM SIZE A
NOTE:
GASKET SPONGE REQUIRED ON TOP SIDE OF FLANGE PERIMETER.
MATERIAL TO BE ALUMINIZED 20ga. STEEL
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Crush Hazard
Check blower assembly per
maintenance section.
Lack of blower assembly
maintenance can cause
excessive vibration.
Excessive vibration can
cause support failure.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Crush Hazard
Hanging hardware must
support equipment weight.
Do not hang by lifting lugs.
Crush Hazard
Use proper lifting equipment and practices.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Falling Hazard
Use proper safety
equipment and practices to
avoid falling.
Severe Injury Hazard
Use proper lifting practices
and equipment.
Equipment and accessories
are heavy.
Cut/Pinch Hazard
Wear protective gear during
installation, operation and
service.
Edges are sharp.
SECTION 9: INDOOR SUSPENSION MOUNTING - HORIZONTAL AIR HANDLER
9.1 Suspension Mounting Assembly and Instructions
Indoor suspension mounting is available for all models in horizontal orientation. Suspension mounts are
shipped assembled. The exterior frame perimeter includes additional L channel. Holes in the L channel allow
for threaded rod to be used for suspension. Threaded rod is provided by others. Minimum threaded rod size
is ¾".
NOTE: Check to be sure all required components are present. If there are any missing, contact Rapid
Engineering LLC or your RAPID
Once the suspension frame is secure, the air handler may be mounted. See Page 27, Section 6.1 for safe
lifting practices.
46 of 154
®
independent distributor.
Page 55
FIGURE 35: Indoor Suspension
VIBRATION ISOLATORS
WHEN SPECIFIED
SUPPORT
RODS
AIR HANDLER
CONTROLS RIGHT
INLET END VIEW
APPROXIMATE
GAS PIPE LOCATION
CENTER SUPPORTS
ROD SIZE4036 – 4089 3/4" Ø
4024 5/8" Ø
INLET
G
G
CONTROLS RIGHT
BURNER
SECTION
FAN
SECTION
Field Joint
Field Joint
(4054-4073 ONLY)
(4080-4089 ONLY)
PLAN VIEW
CONTROLS RIGHT SHOWN
CENTER SUPPORTS
ON 4040 TO 4089 ONLY
NOTES:
1. CONSULT FACTORY FOR DIMENSIONS WHEN USING
A 3V4 OR 4" MANIFOLD.
2. ALL DIMENSIONS & WEIGHTS ARE SUBJECT TO CHANGE
WITHOUT NOTICE & SHOULD NOT BE USED FOR
CONSTRUCTION UNLESS CERTIFIED.
3. ACCESSORIES MAY VARY BY INDIVIDUAL ORDER. CONSULT FACTORY
FOR ADDITIONAL INFORMATION.
SECTION 9: INDOOR S USPENSION MOUNTING - HORIZONTAL AIR HANDLER
47 of 154
Page 56
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 10: LEG MOUNTING
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Failure to follow these instructions can result in death, injury or property damage.
Vertical MUA, FR, AM and 4024-4049 VAV units require a quantity of four legs. Vertical 4054-4089 VAV units
without an OA filter section require a quantity of six legs (all of the same height). Vertical 4054-4089 VAV
units with an OA filter section require a quantity of six legs (four legs of the same height and two legs at a
height of 30" taller than the first four). Consult Factory if height of additional two legs exceed the standard leg
offerings. Horizontal 4024-4049 require a minimum quantity of four legs. Horizontal 4054-4089 require a
minimum quantity of eight legs. For every additional section (ie. mix box, coil, etc.) beyond the basic
horizontal unit except for inlet hoods and outside air filter sections, an additional four legs must be added.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Equipment and
accessories are
heavy.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
48 of 154
Page 57
FIGURE 36: Assembling Legs for Horizontal Air Handlers
CURB ANGLE
A
AIR HANDLER
INTERMEDIATE BOTTOM PLATE
(BOLTS TO 2 CORNER LEGS)
ACCESS
DOOR
1/2"x 1-5/8"
SLOTTED HOLES
CORNER SUPPORT LEGS
4 - REQUIRED
CONTROLS
RIGHT
INTERMEDIATE SUPPORT LEGS
REQUIRED ON ALL CURB ANGLE FIELD JOINTS
(2 CORNER LEGS BOLTED TOGETHER)
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Drawing #50010144
LEG
OPTIONAL
SECTION (s)
RAIN SKIRT
(3 PCS.)
NOTE: Rain Skirt With Outdoor Air Handlers Only
TOP AND BOTTOM PLATES
BOLT ON OUTSIDE OF LEG
NOTE -
(12) - 3/8 X 1" BOLTS
(8) - 3/8 FLANGE NUTS
FOR EACH LEG
(12) - 3/8 WASHERS
DIMENSION A
84"
DIM. A
STANDARD LEG SIZES
60"
72"
48"
36"
24"
96"
RAPID PROVIDES
SHEETMETAL CHANNEL OR ANGLE
IRON FRAME TOWARD BUILDING
NOTE: RAIN SKIRT WITH OUTDOOR AIR
HANDLERS ONLY
CAUTION, SHORTENING THE LEGS MAY
RESULT IN HIGH INLET AIR
VELOCITIES, CONSULT THE FACTORY
APPLY CAULKING ON INSIDE FEATHER EDGE
OF RAIN SKIRT BEFORE INSTALLING, USING #10 X
RUBBER CAP TEK SCREWS, SCREW TO THE SIDES OF
AIR HANDLER, REMOVE SCREW IN ROOF BEFORE INSTALLING
RAIN SKIRT TO ROOF PANEL OF AIR HANDLER, RAIN GUTTER
SHOULD BE FLUSH WITH INLET OF UNIT AS ILLUSTRATED.
RAIN SKIRT
UPRIGHT LEG
AIR HANDLER
20540 SCR,TEK #10 X 3/4 W/WASH
FIGURE 37: Assembly Legs and Rainskirt for Upright Air Handlers
50 of 154
Page 59
SECTION 11: FILTER SECTION
NOTE: 1) CONTRACTOR/INSTALLER MUST MAKE
APPROPRIATE ALLOWANCES FOR DUCT
CONNECTIONS.
2) SUPPORT LEG IS REQUIRED WHEN A FILTER
SECTION AND INLET HOOD ARE ORDERED.
3) SUPPORT LEG IS PROVIDED FOR USE WITH
STANDARD 19" (50 cm) ROOF CURB. SUPPORT
LEG FOR USE WITH STANDARD 46" (116.8 cm)
LEGS PROVIDED BY OTHERS.
SECTION 11: FILTER S ECTION
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
Failure to follow these instructions can result in death, injury or property damage.
All filter sections are shipped assembled. Models 4024-4049 ship attached to the base unit. Models 40544089 shipped loose and required field assembly to base unit.
NOTE: Check to be sure that all required components are present. If any are missing, contact Rapid
®
Engineering LLC or your RAPID
independent distributor.
FIGURE 38: Filter Section Support Assembly
51 of 154
Page 60
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Roof
Tape
Field Joint
Properly
Caulk
Notes:
(1) Failure to properly caulk the
field joints will allow water
to enter the air handler
(2) All parts mounted to inlet end
to be attached with 3/8" bolt
and flat washers.
(3) All other parts bolted together
with 5/16" bolts, flat washer,
and lock nut.
(4) All dimensions & weights are
subject to change without
notice & should not be used
for construction unless certified.
Typ. Assembly
Nut Inserts
Rapid recommends assembling
inlet hood parts to the air
handler in the following
sequence by item #:
5, 6, 11, 4, 2, 1, 10
SECTION 12: INLET HOODS
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
Failure to follow these instructions can result in death, injury or property damage.
Inlet hoods are shipped unassembled and must be assembled prior to installation.
NOTE: Check to be sure that all required components are present. If any are missing, contact Rapid
Engineering LLC or your RAPID
(1) Failure to properly caulk the
field joints will allow water
to enter the air handler
(2) All parts mounted to inlet end
to be attached with 3/8" bolt
and flat washers.
(3) All other parts bolted together
with 5/16" bolts, flat washer,
and lock nut.
(4) All dimensions & weights are
subject to change without
notice & should not be used
for construction unless certified.
Typ. Assembly
Nut Inserts
Rapid recommends assembling
inlet hood parts to the air
handler in the following
sequence by item #:
8, 9, 16, 7, 5, 6, 4, 2, 1, 10, 11, 12
10
10
11
FILTER RAILS
TOP FILTER RAIL
DescriptionDetail
12
BOTTOM PAN & RAIL
13
L INLET HOOD GUTTER
14
15
FILTER CLIPS
16
TEK SCREWS
17
RAIL HARDWARE
18
19
FILTER SPACERS
20
R INLET HOOD GUTTER
ISOMETRIC VIEW
FILTER SPACER
REQUIRED ON SOME
MODELS
11
12
13
14
15
16
FILTERS
40600672
4060067381
QtyASM/Part #
40600674 1
40600674 1
40600675 1
20900 4
20541 30
20699 14
20538 14
--
20596 8
MODEL 36
40620618
4062061981
QtyASM/Part #
40620620 1
40620621 1
40620621 1
20900 8
20541 30
20699 14
20538 14
--
20596 4
MODEL 40
40600641
4060064281
QtyASM/Part #
40600643 1
40600644 1
40600644 1
20900 8
20541 30
20699 12
20538 12
--
09701 12
MODEL 44
40504206-7
40504206-8101
QtyASM/Part #
40504206-9 1
40504206-12 1
40504206-12 1
20900 10
20541 50
20699 16
20538 16
40504206 5
20596 20
MODEL 49
40620418-19
40620418-20121
QtyASM/Part #
40620418-21 1
40620418-22 1
40620418-22 1
20900 12
20541 50
20699 22
20538 22
40620418-23 1
20596 24
MODEL 54
40630445
40630446121
QtyASM/Part #
40630447 1
40630448 1
40630449 1
20900 12
20541 50
20699 24
20538 24
--
20596 30
MODEL 60
437345
437346121
QtyASM/Part #
437347 1
437348 1
437349 1
20900 12
20541 50
20699 20
20538 20
--
20596 12
MODEL 66
40501125-7
40501125-851
QtyASM/Part #
40501125-9 1
40501125-12 1
40501125-12 1
20900 12
20541 50
20699 20
20538 20
-1
20596 36
MODEL 73
40600529-12
40600529-13141
QtyASM/Part #
40600529-14 1
40600529-15 1
40600529-16 1
20900 14
20541 50
20699 30
20538 30
-1
77500 49
MODEL 80/89
EXPLODED VIEW
ASSEMBLY INSTRUCTIONS
· ASSEMBLE INLET HOOD PARTS LISTED IN EXPLODED VIEW #7,8,9,14 TO AIR HANDLER WITH
3
8
" FLAT
WASHERS AND
3
8
X 1 BOLTS.
· BUTYL ROPE CAULKING IS SUPPLIED AND SHOULD BE APPLIED BET WEEN EACH SIDE AND ROOF PANELS TO INSURE A WATER TIGHT SEAL, 3" WIDE ZIP
TAPE IS SUPPLIED AND SHOULD BE USED ACROSS EACH ROOF JOINT AS SHOWN.
· BOLT ITEMS #4,5,6 WITH
5
16
" HARDWARE TO ITEM #7,8,9 PREVIOUS MOUNTED.
· ITEMS #1,2 & 3 ARE THEN BOLTED TO ITEMS #4,5 & 6.
· INTERIOR GUSSET ITEMS ARE MOUNTED ON THE INSIDE OF HOOD TO SIDE WALL PANELS #5 & 6 AND #4 ROOF PANEL.
· HORIZONTAL BRACE IS MOUNTED TO #5 & 6 ON INTERIOR OF HOOD FOR CENTER SUPPORT.
· ITEM #13 & 14 RAIN GUT TERS MOUNT TO TAPERED EDGE OF HOOD, MOUNTING FLANGE TO THE INSIDE OF HOOD AND 2" FLANGE WITH BE TO THE
OUTSIDE AS SHOWN.
· ITEM #11 TOP FILTER RAIL MOUNTS TO ROOF OF INLET HOOD ITEM #1 WITH ITEM #16 TEK SCREWS.
· ITEMS #10 DUAL FILTER RAILS MOUNT TO ITEMS #13 & 14 WITH #10-24 HARDWARE.
· ITEMS #15 FILTER CLIP RETAINER ARE FASTENED TO ITEMS #13 & #14 WITH TEK SCREWS.
· SOME MODELS REQUIRE FILTER SPACER ITEM #19 TO COMPLETE ROW OF FILTERS.
7
8
9
5
6
4
1
2
3
14
10
14
13
13
ITEM #11 TEK SCREWS
TO THE OUTSIDE FLANGE
OF ITEM #1
FILTER RAILS ITEMS #10
MOUNT TO ITEMS #13 & 14 WITH
#10-24 HARDWARE
SOME MODELS REQUIRE FILTER
SPACER #19 (SEE CUTTING LIST)
17
FILTER CLIPS ARE
TEK SCREWED TO THE
OUTSIDE FLANGE OF ITEM #13
& #14 ON BOTH SIDE OF HOOD.
3" WIDE ZIP TAPE, SUPPLIED
FOR EACH ROOF JOINT.
EACH VERTICAL AND HORIZONTAL ROOF JOINT SHOULD
BE CAULKED WITH BUTYL TAPE THAT IS SUPPLIED
WITH INLET HOOD, TO INSURE A WATER TIGHT SEAL.
17 18
ASSEMBLY INSTRUCTIONS
· STANDARD INLET HOOD INSTRUCTION #40004504 (PG.17) FOR INSTRUCTIONS ON CAULKING
PRIOR TO ASSEMBLY.
· REFER TO ASSEMBLY DRAWING PACKAGED WITH INLET HOOD.
· INLET HOODS (4024-4049) ARE 6-PIECES & (4054-4089) 12-PIECES
· INLET HOODS 4054-4089 HAVE INTERNAL CORNER BRACES AND HORIZONTAL CROSS MEMBERS.
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Equipment and
accessories are
heavy.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
SERVICE PLATFORM FRAME
SUPPORT CHANNEL
BURNER SECTION
3/8" BOLTS
3/8" BOLTS
3/4" NUTS
¥ MODEL 4073/4089 ANGLE IRON
¥ MODEL 4024/4066 SHTMTL CHANNEL
RAILING
CONTROLS
Side Railing
Field Assembly
ACCESS SIDE RAILING (SIZES 4049 - 4089)
TEK SCREW IN FIELD.
FRONT
GRATING
Two Front Rails on
4080/4089 Models
2
4
8
9
1
3
5
6
10
ACCESS
CHAINS
SIDE RAILING
4 PCS ASSEMBLY
7
OPTIONAL LADDER
(Available from manufacturer)
Assemble in the following order:
1. Bolt support channels to air handler with four ¾” nuts.
2. Bolt service platform frame between support channels with eight 3/8” x 1” bolts and fig nuts.
3. Lay grating inside service platform frame.
4. Bolt from railing to service platform with four 3/8” x 1” bolts and fig nuts.
5. Screw access railing to support channels with three #14 self-tapping screws.
6. Tek screw access railing to air handler roof.
7. Pre-assemble side railing (4 pieces) with four 3/8” x 1” bolts and fig nuts.
8. Bolt side railing to front railing with two 3/8” x 1” bolts and fig nuts.
9. Screw side railing to angle iron frame with three #14 self-tapping screws.
10. Attach safety chains between access side railing and front railing.
SECTION 13: SERVICE PLATFORM
13.1 Service Platform
Ladders are available as an additional accessory for service platforms. Ladders are available with or without
cages at various heights. Service Platforms are available for use with horizontal or vertical units.
FIGURE 43: Service Platform for an Vertical Air Handler
55 of 154
Page 64
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
CONTROLS
RIGHT
3/8" BOLT
FIELD JOINT
WHEN REQUIRED
SERVICE PLATFORM
SUPPORT CHANNEL
3/8" BOLTS
SAFETY CHAIN
FRONT RAILING
SWAY TAB
SUPPORT RODS
DOUBLE NUTTED
LIFTING EYE
AIR HANDLER
SUPPORT CHANNEL
ACCESS SIDE RAILING
SIDE RAILING
FIELD ASSEMBLY
HOLES FOR 3/8" BOLTS
SUPPORT ROD HOLES
(by others)
TEK SCREW IN FIELD.
SPLICE LOCATED ON
4044-4089 MODELS ONLY
SIDE RAILING 4 PCS ASSEMBLY
FRONT
RAILING
INLET VIEW
RIGHT CONTROLS
Detail A: Models 4073 - 4089
Detail A: Models 4024 - 4066
A
FIGURE 44: Service Platform for a Horizontal Air Handler
56 of 154
Page 65
SECTION 14: DISCHARGE ACCESSORIES
SECTION 14: DISCHARGEACCESSORIES
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Failure to follow these instructions can result in death, injury or property damage.
14.1 One-Way, Three-Way and Four-Way Discharge Head Installation
All discharge heads are shipped assembled. The discharge head is designed for mounting to the face of the
air handler (covering the supply air opening) or to an interior wall. All discharge heads must be field
supported (by others). The discharge head has four outward-turned flanges. If the discharge head is to be
installed to the face of the air handler, install hardware (provided by others) on all four sides of the discharge
head.
Discharge heads can be installed on horizontal or vertical air handlers. To install the discharge head on an
interior wall, drill holes in the flanges on all four sides of the discharge heads to accommodate lag bolts
(supplied by others). Sheet metal (supplied by others) may be required.
Consult factory for detailed installation instructions based on unit orientation and discharge location.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Equipment and
accessories are
heavy.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
57 of 154
Page 66
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
(SUPPLY AIR AND
RETURN AIR DUCT
SLEEVES AVAILABLE
FROM MANUFACTURER)
DETAIL A
DETAIL C
AIR HANDLER
DETAIL B
TYPICAL ASSEMBLY
2"
SELF TAPPING
SCREWS
ALTERNATE
SUPPORT BY
OTHERS
SUPPORT
BY OTHERS
INLET
DETAIL A
DETAIL B
DETAIL C
MODELS 4024-4089
AIR HANDLER
HOUSING
RETURN AIR SLEEVE
CAULK JOINT
AFTER ASSEMBLY
AIR HANDLER
HOUSING
SUPPLY AIR SLEEVE
3-3/4" DISCHARGE
COLLAR
SELF-TAPPING
SCREWS
CAULK JOINT PRIOR
TO ASSEMBLY
CAULK JOINT PRIOR
TO ASSEMBLY
SUPPLY AIR
SLEEVE
DISCHARGE
HEAD
1/4-20 x 1" BOLTS
(12" O.C.)
FIGURE 45: Vertical Air Handler with Duct Sleeves and Discharge Head
The splash plate is designed to hang, supported by
suspension rods (rods provided by others) directly
below the bottom discharge opening of a horizontal
air handler. The center point of the splash plate must
be located at the center point of the discharge
opening and be positioned below the air handler
within the range of dimensions show below as E
(min) & E (max.). For model sizes 60-89, center
support rods will be required (see illustration below).
FIGURE 50: Discharge Plate
RIGHT SIDE VIEW
FAN SECTION
NOTE: Be sure to inclu de provisions in the structure
suspending the discharge plate that will prevent
sway/movement of the plate when the supply fan is in
operation.
To attach all of the hanger rods to the splash plate,
start by threading a flanged nut onto each hanger
rod. Then, slip each hanger rod down through a hole
located in each corner of the splash plate. Next, feed
a flanged nut onto the rod below the splash plate.
Adjusting the nuts will level the splash plate. Torque
hardware after leveling.
SUPPORT RODS
(BY OTHERS)
DISCHARGE PLATE
A
C
CENTER HOLES
ON 60 THRU 89
13
/16” HOLES
D
E
B
2”
TYPICAL
D
2”
1¾” TYPICAL
4 CORNERS
63 of 154
Page 72
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
“D” HOLE DIA
SUPPORT ROD
TO STEEL-WORK
BY OTHERS
ISOLATOR
SUPPORT ROD
TO UNIT
BY OTHERS
L
A
H
NOTE:
ALL DIMENSIONS AND WEIGHTS
ARE SUBJECT TO CHANGE
WITHOUT NOTICE AND SHOULD
NOT BE USED FOR CONSTRUCTION
UNLESS CERTIFIED.
than the entering wet bulb, but is normally considered equal.)
3Wet Bulb Depression = ODB – OWB
4Evaporation Rate (GPH) = CFM x WBD x SE/8050
5 Bleed-off Rate = approximately 20% of evaporation rate*
6Recirculation Rate = approximately 3 times evaporation rate*
* Bleed-off and recirculation rates will vary with
locale, water quality and chemical treatment
program. These values are only for approximation.
Gallons per Hour (GPH) Per 1,000 Cubic Feet per Minute (CFM) at Stated Saturation Efficiency
Table 22: Abbreviations
Abbreviations
CFMCubic Feet Per Minute
GPHGallons Per Hour
IDBIndoor (Design) Dry Bulb Temperature
LDBLeaving Dry Bulb Temperature
LWBLeaving Wet Bulb Temperature
ODBOutdoor (Design) Dry Bulb Temperature
OWBOutdoor (Design) Wet Bulb Temperature
SESaturation Efficiency of the Evaporative Media
WBDWet Bulb Depression
• Heat of vaporization = 1043 BTU/lb
• Weight of water = 8.34 lb./Gallon
• GPH = CFM x WBD x SE x 1.08/1043/8.34 = CFM x WBD x SE/8050
Table 24: Suggested Air Changes Per Hour (Air
Change Method)
* For existing buildings: Average amount indoor
temperature exceeds ambient outdoor temperature when evaporative cooling is not in use.
** Experience has shown that significant benefit can
be achieved with 10-15 Air Changes per Hour (AC/
Hr) through the lowest 12' of the facility. For a 24'
Table 25: Saturation Efficiency at Stated Media
Depth
high building, this would mean 5-6 Air Changes per
Hour (AC/Hr) for the entire volume. This will v
application.
ary by
NOTE: Moisture limiter pressure drop is added for
face velocities greater than 600 Feet per Minute
(FPM). Rapid Engineering LLC's standard media
thickness equals 12".
6"8"12"18"24"
6"8"12"18"24"
68 of 154
Page 77
SECTION 17: DUCT CONSIDERATIONS
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
WARNING
Failure to follow these instructions can result
in death, injury or property damage.
The air handler has been designed to operate at the
specific air volume and external static pressure that
was originally specified. Static pressure is increased
by any additional components that are added to the
air handler (i.e. inlet hood, filter section, dampers,
ductwork, discharge heads, etc) Additional static
pressure beyond original intention (or time of order)
will affect the performance of the air handler and
reduce the air volume that can be delivered.
Proper engineering methods need to be employed
when calculating duct and component static pressure
(i.e. 2009 ASHRAE Handbook - Fundamentals,
Chapter 21).
The system ductwork must comply with Sheet Metal
and Air Conditioning Contractors Nationals
Association (SMACNA) or any other recognized
standards.
As a general rule, all ducting should have a straight
run of at least 3 duct diameters immediately before
and after the air handlers mechanical accessories.
No duct fittings, elbows or transitions with restrictions
can be placed within 3 duct diameters.
SECTION 17: DUCT C ONSIDERATIONS
The air handler is not designed to support the weight
of ductwork. Ductwork must be constructed in a
fashion that is self-supporting. Ductwork should be
straight, elbows should be minimal and any
transitions should be gradual.
Depending on the options ordered with the air
handler, flanges (either external or internal) may be
provided to facilitate connection of ductwork. In
cases where flanges are not provided, flat surfaces
on the exterior skin of the air handler are provided to
facilitate connection of ductwork.
Neither the flanges nor exterior skin of the air handler
are capable of supporting the load of the ductwork.
Ductwork support must come from the structure itself
that the air handler is serv
is recommended that ductwork be supported every 6
ft (1.8 m) for ductwork that has a cross section of 10 ft
(3 m) or less and every 4 ft (1.2 m) for ductwork which has a cross section of greater than 10 ft (3 m).
On vertical runs, it is recommended that ductwork be
supported every 10 ft (3.0 m). On both cases,
supporting members should be sized to carry the
weight load.
17.1 Inlet Air Duct
Inlet duct work height and width must be no smaller
than the air handler inlet height and width and supply
only uncontaminated air to the air handler. (See Page 10, Section 5 for return air dimensions).
17.2 Return Air Duct
Return air duct work height and width must be no
smaller than the air handler return air opening height
and width. (See Page 10, Section 5 for return air
dimensions).
17.3 Supply Air Duct Work
Supply air duct work sizes sho
the application requirements of the system. Supply
air ductwork must be smaller than supply air
opening. See Page 10, Section 5 for dimensions.
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Explosion Hazard
Leak test all components of gas piping
before operation.
Gas can leak if piping is not installed
properly.
Do not high pressure test gas piping with air
handler connected.
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 18: GAS PIPING
Minimum gas pressure as indicated on data plate
must be measured with the burner operating in high
fire.
Minimum inlet gas pressure is determined by gas
train size and BTU/h rating.
18.1 Gas Manifolds
All gas piping to the air handler must comply with:
United States: Refer to NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision,
Natural Gas and Propane Installation Code.
The air handlers are available with three gas manifold
options.
• American National Standards Institute (ANSI)
compliant manifold: (
•Factory Mutual (FM)-compliant manifold:
(
See Page 72, Figure 56
•XL Insurance (former IRI)-compliant manifold:
(
See Page 73, Figure 57
18.2 Gas Piping and Pressures
The air handler is equipped with a gas manifold
suitable for connection to supply pressure of up to 5
p.s.i. maximum for all manifold types.
When gas supply exceeds the above-listed maximum
gas pressures, an additional high pressure gas
regulator will be required to assure that the correct
gas pressure is supplied to the air handler.
Outlet pressure from the regulator / inlet pressure to
air handler should be measured at the inlet of the air
handler gas manifold.
NOTE: Items vary by manifold type. All items may not apply.
FIGURE 55: Standard Gas Manifold
SECTION 18: GAS P IPING
71 of 154
Page 80
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
VENT OUTSIDE
A
ALTERNATE
INLET
INLET
BY OTHERS
D
M
B
C
K
E
G
H
J
N
P
R
S
L
BY OTHERS
* INTEGRAL VENT LIMITER
* INTEGRAL VENT LIMITER
VENT LIMITER
VENT LIMITER
ALL VENT PIPING TO
OUTSIDE BY OTHERS
FIGURE 56: FM Gas Manifold
72 of 154
Page 81
FIGURE 57: XL Insurance Gas Manifold
ALL VENT PIPING TO
OUTSIDE BY OTHERS
VENT OUTSIDE
F
VENT OUTSIDE
A
ALTERNATE
INLET
INLET
BY OTHERS
D
B
C
K
E
G
H
J
N
P
R
S
ML
BY OTHERS
* INTEGRAL VENT LIMITER
* INTEGRAL VENT LIMITER
VENT LIMITER
VENT LIMITER
SECTION 18: GAS P IPING
73 of 154
Page 82
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
18.3 Gas Piping
The gas manifold connection extends through the
side of the control enclosure for vertical equipment
and through the bottom for horizontal equipment. The
factory piping terminates with a male pipe connection
in the primary gas valve. Be sure that the fuel supply
pipe connected at this point is large enough to
ensure the proper volume and line pressure at the
inlet of the air handler. The piping must comply with:
United States: Refer to NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision,
Natural Gas and Propane Installation Code.
Gas supply piping must conform to best building
practices and local codes. During installation of the
gas piping, be sure that piping does not restrict
accessibility to the air handler or its removable
access doors.
Lockable manual shut-off valve must be added by the
installer in compliance with Occupational Safety and
Health Administration (OSHA) regulations.
.4 Pressure Test Ports
18
There are 1/8"(3.2 mm) and 1/4"(6.4 mm) pressure
test ports located on the manifold. The test ports are
available to measure the manifold inlet gas pressure
and the burner gas pressure during burner setup.
18.4.1 Manifold Inlet Gas Pressure
The pressure test port for measuring manifold inlet
pressure is located on the inlet side of the first safety
shutoff valve. Refer to the unit rating plate for the
acceptable inlet gas pressure.
18.4.2 Burner Gas Pressure
A pressure tap is used to measure negative pressure
at the burner (fan only, gas valves closed) and to set
high fire gas pressure regulating (gas valves open).
Air handlers are equipped with a modulating/
regulating valve (MRV). The pressure tap is located
on the downstream side of the MRV.
74 o f 154
Page 83
SECTION 19: ELECTRICAL
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be
required to disconnect electric from
equipment.
Equipment must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
Each air handler is equipped with a wiring diagram
which will vary depending on the type of remote panel and/or options supplied.
SECTION 19: ELECTRICAL
Air handlers can also be supplied as building
management system (BMS)-ready. In this case, a
remote panel is not supplied.
Note: Spark testing or shorting of the control wires
by any means will render the transformers
inoperative.
Each unit is equipped with a fused rotary disconnect.
The rotary disconnects are for copper wire only.
75 of 154
Page 84
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
19.1 Disconnect Fuse Sizing
The fuse classification must be determined by the service disconnect rating plate and all applicable codes.
Fuse sizing is determined by the motor size, control current and supply voltage. Fuses that are being
replaced must be replaced with the same type, size and class of fuse that was supplied with the air handler.
For additional information or to confirm original fuse specifications, consult the factory.
Table 28: Minimum and Maximum Fuse Size by Motor Size and Supply Voltage
Electrical Characteristics
Motor Size HP(kW)208/3/60230/3/60460/3/60575/3/60230/1/60
All electrical wiring and connections, including
electrical grounding, must comply with:
United States: Refer to National Electrical Code
®
,
NFPA 70 - latest revision. Wiring must conform to the
most current National Electrical Code
®
, local
ordinances, and any special diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA
C22.1 Part 1 - latest revision.
Check rating plate on air handler for supply voltage
and current requirements.
If any of the original control wire supplied with the air
handler must be replaced, replace it with type MTW
105°C, 600 V, 16 gauge wire or equivalent, except for
temperature control wiring, which must be a minimum
of 20 AWG Type Beldon 5401FE CMR 75C shielded
or equivalent.
For all other wires, replace with the equivalent size
and type of wire that was originally provided with the
air handler.
NOTE: The controls referenced in this manual are
applicable to non-DDC equipped air handlers. If your
air handler is equipped with one of our DDC control
options, please consult the separate DDC Control
Operator's manual that accompanies this document.
19.3 Remote Panel
The remote panel mu
st be wired as shown on the
electrical schematic. For wire gauge sizes, see Page 76, Table 29. All power supply and motor wiring must
be minimum type THWN with a 167° F (75° C)
temperature rise.
19.3.1 Remote Panel Mounting Distance
If the interconnection wiring between the remote
panel and the air handler control enclosure is ru n in a
single conduit, the wire run can be as long as 100'
(30 m). For longer wire runs, consult the factory. If the
interconnection wiring between the remote panel and
the air handler control enclosure is run in two
conduits (separating the shielded cable and the 120
V power supply for the remote panel), the wire run
can be as long as 200' (60 m). For longer wire runs,
consult the factory. Care should be used to avoid
running the interconnect wiring near large industrial
loads or high voltage wire runs as that may further
limit the length of the interconnect wire run.
Table 29: Control Voltage Wiring For All Control
Systems
VoltsWire GaugeMax Wire
12018150' (45 m)
12016250' (75 m)
12014350' (106 m)
NOTE: Wiring for temperature controls must be run in
shielded cable as indicated on the wiring diagram.
19.3.2 Low Voltage Control Wiring
Low voltage (24 V - AC/DC) control wiring in excess
of 100' (30.5 m) in length should be in its own
separate conduit run to prevent interference.
19.4 Motor Current Draw
For specific current requirements, see rating plate
76 of 154
Page 85
SECTION 19: ELECTRICAL
located on the blower motor. Current draw may be
adjusted downward by reducing blower rotations per
minute (RPM) or by increasing external static
pressure.
19.5 Control Current Draw
The maximum current draw for an air handler’s
controls and accessories is 3A.
19.6 Safety Systems
Safety systems are required for proper performance
of the air handler. The air handler shall not be
permitted to operate with any safety system disabled.
If a fault is found in any of the safety systems, then
the system shall be repaired only by a contractor
qualified in the installation and service of gas fired
heating equipment, using only components that are
sold and supplied by Rapid Engineering LLC. Refer
to Page 81, Table 31 for a brief description of each
safety device, its location and its switching voltage.
Table 30: Safety Systems
Safety ControlsLocationVoltage
Manual Reset HighTemp Limit (All Models)
Pres sure Switches
(All Models)
Flame Control
(2010/2010B/2020/2030)
Flame Control (2005)
Discharge Temperature
Monitor (All Models)
AM Resistor
(A M /VAV S t yle)
Blower Discharge120
Air Handler Control
Enclosure
Air Handler Control
Enclosure
Air Handler Control
Enclosure
Blower Discharge24
Air Handler Control
Enclosure
120
120
24
24
19.6.1 Manual Reset High Temperature Limit
Switch
If for any reason, the temperature of the air at the
discharge of the blower reaches the limit set point of
160° F (71.1° C), the high temperature limit switch will
open the circuit to the burner system and discontinue
all burner functions. E
vents that could result in
excessive discharge air temperatures include if the
burner modulation amplifier is defective (i.e.
temperature sensor goes open circuit) or if a surge in
gas pressure reaches the burner. Restarting of the
burner can only be accomplished after the limit has
cooled down and the reset button on the switch has
been depressed. This switch is located on the blower
housing inside the air handler.
closes. When the switch closes, it permits the flame
safeguard relay to begin ignition. This switch is
factory set at 0.32 in wc (0.8 mbar). The high velocity
pressure s
witch will open if the airflow across the
burner reaches its maximum allowable limit. This
switch is factory set at 1.40 in wc (3.5 mbar). The
pressure switch is a safety device, which cannot be
field-adjusted or tampered with.
19.6.3 Gas Pressure Switches
Gas pressure switches are standard on certain
models (FM compliant gas trains above 2,500 MBH
and XL compliant gas trains) and are also available
as an option on the others.
The function of the gas pressure switches is to
protect against insufficient, lack of gas pressure and
excessive pressure in the system.
On the low gas pressure switch side, this switch
opens its internal switch which shuts the burner down
and prevents its operation due to insufficient gas
pressure.
On the high gas pressure switch side, its internal
switch w
ill open, shutting down the burner due to
excessive gas pressure passing through the gas
train.
The settings of the gas pressure switches are field
adjustable. The one monitoring the incoming gas
pressure is the low gas pressure switch. The low gas
pressure switch must be set to the minimum required
gas pressure as indicated on the data plate.
The high gas pressure switch must be set to 1 in w.c.
(2.5 mbar) above high fire setting established during
commissioning.
The switch will have to be reset manually, once the
condition has been corrected.
19.6.2 Pressure Switches
The low airflow velocity pressure switch monitors the
airflow (differential pressure) across the burner.
When the airflow across the burner reaches the
proper velocity (volume) for combustion, the switch
77 of 154
Page 86
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
19.6.4 Flame Control
This device will check for both pilot flame and main
flame within the burner. When a flame signal from the
pilot flame is available, it will allow the main gas valve
to open.
Yo ur air handler may equipped with either a flame rod
or UV scanner type of flame detection. Consult your
parts list / electrical diagram to confirm and for flame
rod sensors See Page 115 and Page 116. For UV
scanners See Page 119 and Page 120
If a pilot flame is not present, the electrical signal
cannot be sent and the pilot burner gas valve will
close. The relay is equipped with a 10-second trial for
ignition. If ignition does not occur, the flame
safeguard relay will lockout, it will reset upon power
restoration. (See the Trouble-Shooting Guide - Page 136, Section 24)
19.6.5 Discharge Temperature Sensor
This device senses the discharge temperature of the
air at the blower. The discharge temperature sensor
reports the discharge temperature to the temperature
control amplifier
which modulates the burner to the
temperature set on the remote panel selector. Should
this system fail, the manual high temperature limit
switch will turn the burner off. BMS-ready air
handlers do not come equipped with this sensor and
must be field-supplied.
Yo ur Rapid
®
direct fired air handler was built custom
to meet your needs. For details on interconnect
wiring or any other wiring questions, please consult
the specific wiring diagrams provided with your air
handler.
NOTE: A laminated wiring diagram can be found
permanently affixed inside the unit control enclosure.
78 of 154
Page 87
SECTION 19: ELECTRICAL
19.7 Interlocks
19.7.1 Carbon Dioxide Interlocks
All air handlers that recirculate air from the heated
space require either a control to limit the temperature
rise in proportion to the amount of outdoor air or the
use of a room carbon dioxide sensor. The carbon
dioxide sensor is field provided and set to maintain a
CO2 concentration below 5,000 ppm.
19.7.2 Carbon Monoxide Interlocks
Carbon Monoxide Detector is a ship loose sensor
that monitors the CO levels in the space. It can either
sound an alarm and/ or force the air handler into
100% outside air if its threshold set point is
exceeded.
19.8 Control Options
19.8.1 Mild Weather Outside Air Stat
This option is designed to turn the burner off when
the incoming outside air is at or above the
temperature setpoint. The blower is allowed to run for
continued ventilation. The mild weather outside air
stat is located in the control enclosure. It has an
adjustable setting between -20° F (-29° C) and
100° F (38° C).
19.8.2 Low Temperature Limit with Override Timer
This option is designed to turn the unit off when air is
discharged below the temperature setpoint for a
period in excess of timer setpoint. The low
temperatu
re limit switch is located in the air handler’s
control enclosure. The low temperature limit switch
has an adjustable setting between -20° F (-29° C)
and 100° F (38° C). The timer by-passes the low
temperature limit switch for the first 5 minutes to allow
the burner to establish a flame when the air handler
is turned on. If the air handler’s discharge
temperature falls to the predetermined low
temperature limit setpoint, after the 5 minute
establishing period, the air handler’s blower will be
turned off. To reset the low temperature limit switch,
set the fan switch to off and then on again. The air
handler will return to the normal sequence of
operations.
19.8.3 MUA / Exhaust Failsafe Interlock
This option incorporates the low temperature limit
with override timer and an exhaust fan airflow switch
monitor. The exhaust fan airflow switch is field
provided and field w
ired as per the option sheet
supplied with the unit. When the air handler is turned
on there is a 5 minute establishing period for the low
temperature limit switch and the exhaust fan
interlock. If the air handler’s discharge temperature
falls to the predetermined low temperature limit
setpoint, after the 5 minute establishing period, the
air handler fan will be turned off. If there is a failure of
the exhaust fan to activate the field supplied airflow
switch, after the 5 minute establishing period, the air
handler fan will be turned off. To reset the
MUA/exhaust failsafe interlock, set the fan switch to
off and then on again. The air handler will return to
the normal sequence of operations.
19.8.4 Motorized Inlet Damper
The motorized inlet damper covers the outside air
inlet of the air handler. When the air handler blower is
turned on, the damper motor is energized and opens
the damper. The damper motor has an auxiliary
switch that prevents the blower from starting until that
damper has opened sufficiently to allo
w the required
air volume to pass through the air handler.
19.8.5 Motorized Discharge Damper
The motorized discharge damper is mounted in the
duct downstream from the discharge opening of the
air handler. When the air handler fan is turned on the
damper motor is energized and opens the damper.
The damper motor has an auxiliary switch that
prevents the blower from starting until that damper
has opened sufficiently to allow the required air volume to pass through the air handler.
19.8.6 Control Enclosure Heater
The control enclosure heater is an electric heater that
keeps the temperature in the control enclosure within
the range for the control components. This option is
intended for extremely cold climates, but
recommended for installations below 15° F (-9° C).
The air handler controls are rated to perform at
temperatures as low as -30° F (-34° C). In
environments where the air handler may be exposed
to lower temperatures, a control enclosure heater
may be required.
19.8.7 Auxiliary Relay
An auxiliary relay may be added to an air handler for
either an interlock or a customer defined pu
rpose.
Refer to the option sheet supplied with the air handler
to indicate whether the relay is wired for an intended
purpose or left unwired for a future interface. Each
relay will be double pole double throw (DPDT) type.
Maximum switching capacity on the normally open
contact is 8A, and for the booth light relay, 15A.
19.8.8 Smoke Detector
A smoke detector interlock allows for the air handler
to operate (either off or on) based on signal input
from the fire alarm.
79 of 154
Page 88
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
19.8.9 Service Receptacle Powered by Others
(Wired)
This option provides a service receptacle. It includes
ground-fault interrupter (GFI) receptacle mounted on
the interior or exterior of the control enclosure. Power
to the receptacle is supplied by the installer.
19.8.10 Room Override Stat
For use with Standard Discharge Control remote.
This option provides additional thermostat capability
based on room temperature. The thermostat senses
room temperature, and resets the discharge air to a
higher temperature whenever the temperature falls
below settings indicated on the temperature selection
dial (located on remote panel). Override temperature
can be set 0° F to 40° F above the temperature
selection dial on the remote panel.
80 of 154
Page 89
SECTION 19: ELECTRICAL
19.9 Safety Systems
Safety systems are required for proper performance of the air handler. The air handler shall not be permitted
to operate with any safety system disabled. If a fault is found in any of the safety systems, then the system
shall be repaired only by a contractor qualified in the installation and service of gas fired heating equipment, using only components that are sold and supplied by Rapid Engineering LLC. Refer to Page 81, Table 31 for
a brief description of each safety device, its location and its switching voltage.
Table 31: Safety Systems
Safety ControlsLocationVoltage
Manual Reset High-Temp Limit (All Models)Blower Discharge120
Pres sure Switches (All Models)Air Handler Control Enclosure120
Flame Control (All Models)Air Handler Control Enclosure120
Supply Air Temperature Monitor (All Models)Blower Discharge24
81 of 154
Page 90
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
1
5 MIN.
LLS
RW
C
NC
TR
1
LOW TEMP
BY-PASS TIMER
HLS
LO
T-1 CONTROL TRANS.
H1H2
AFS1
PS-1
HIGH
GAS PRS.
SWITCH
FEEDER PROTECTION
REF: N.E.C. TABLE 430-152
SIZING BY OTHERS.
G
LPJ-50SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
35.1
3
F1
F1
DISC SW
F1
34.0
1800
25
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
AA
FAN ON
LIGHT
LT
MOTOR FLA TAKEN FROM N.E.C
REFER TO NAMEPLATE FOR ACTUAL FLA
H3H4
460VAC
HI
AFS2
RESET
MANUAL
LIMIT
HIGH TEMP
AIRFLOW
AIRFLOW
2
11
30
31
33
35
18
16
10
54
54
34
15
32
54
3A
CB-2
5A
CB-3
X4
120V
X1
X2X3
24VAC
T-4
DAMPER(s)
DAMPER L.S.
DM
1
INLET / SUPPLY
19
21
FAN
OFF
ON
ON
OFF
BURNER
SW-2
SW-1
M1
M1
MOL-1
START
MOTOR
M1
OL
350VA.
FAN RUNNING
86
CR39CR
PS-2
GAS PRS.
LOW
SWITCH
TH-3
OA STAT
BUR
19.10 Remote Panels
19.10.1 Basic Remote
FIGURE 58: Basic Remote
82 of 154
Page 91
FIGURE 59: Basic Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALVE
BURNER ON
FLAME RELAY
PILOT VALVE
SOLENOID
PRIMARY SHUT-OFF
20
AA
LT
VALVES OPEN
52
52
2
41
43
45
44
49
46
35
36
18
24VAC
40VA
80
81
6
5
TM
1
1
2
3
8
7
W
B
3
4
1
2
321
SEL
SERIES 14A
TCA
BASIC REMOTE
84
85
VENT VALVE
SOL.-2
V1
V2
L
1
1
21
SECTION 19: ELECTRICAL
83 of 154
Page 92
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
19.10.2 Standard Discharge Control Remote
FIGURE 60: Standard Discharge Remote
FEEDER PROTECTION
SIZING BY OTHERS.
REF: N.E.C. TABLE 430-250
L1
L2
L3
G
POWER SUPPLY
460
____V___PH___HZ
DISC SW
F1
F1
F1
LPJ-25SP
1
3
15.1
____FLA
60
M1
OL
CB-2
3A
T-1 CONTROL TRANS.
X4
CB-3
460VAC
H3H4
H1H2
5A
X1
X2X3
120V
MOTOR FLA TAKEN FROM N.E.C
REFER TO NAMEPLATE FOR ACTUAL FLA
T1
SUPPLY FAN
MTR
MOTOR
1
____HP
10
____RPM
1800
____FLA
14.0
T2
T3
2
JUMPER
5 MIN.
ON
OFF
AUTO
SW-1
6
5
RB
TH-1
CYCLE STAT
SUMMER
8
WINTER
SW-2
18
HIGH TEMP
LIMIT
RESET
MANUAL
HLS
30
C
10
RW
16
TR
1
NC
LLS
M1
JUMPER
T-4
19
DM
1
24VAC
21
11
15
MOL-1
HIGH GAS
PRS. SWITCH
31
35
PS-1
JUMPER
MANUAL
RESET
32
34
AIRFLOW
AFS1-LO
AIRFLOW
AFS2-HI
M1
LT-1
AA
33
LOW TEMP
BY-PASS TIMER
INLET/DISCHARGE
DAMPER(s)
DAMPER L.S.
MOTOR
START
FAN ON
LIGHT
54
84 of 154
54
54
Page 93
FIGURE 61: Standard Discharge Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALVE
BURNER ON
FLAME RELAY
PILOT VALVE
SOLENOID
PRIMARY SHUT-OFF
20
AA
LT-2
VALVES OPEN
52
52
2
41
43
45
44
49
46
35
52
18
24VAC
51
52
V1
V2
L
1
52
1
6
5
TM
1
1
2
3
8
7
W
B
3
4
1
2
321
SEL
53
54
SECTION 19: ELECTRICAL
85 of 154
Page 94
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
1
HLS
T-1 CONTROL TRANS.
H1H2
AFS1-LO
PS-1
HIGH GAS
PRS. SWITCH
RESET
MANUAL
FEEDER PROTECTION
REF: N.E.C. TABLE 430-250
SIZING BY OTHERS.
G
LPJ-30SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
22.1
3
F1
F1
DISC SW
F1
21.0
1800
15
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
AA
FAN ON
LIGHT
LT-1
MOTOR FLA TAKEN FROM N.E.C
REFER TO NAMEPLATE FOR ACTUAL FLA
H3H4
460VAC
AFS2-HI
RESET
MANUAL
LIMIT
HIGH TEMP
AIRFLOW
AIRFLOW
2
11
30
31
33
35
18
16
54
54
34
15
32
54
5A
CB-3
X4
120V
X1
X2X3
JUMPER
JUMPER
JUMPER
M1
M1
MOL-1
M1
OL
START
MOTOR
350VA
3A
CB-2
TH-1
SW-2
SUMMER
ON
SW-1
OFF
RB
CYCLE STAT
TC26
TC26
AUTO
6
7
8
WINTER
TC
TIME CLOCK
26
5 MIN.
LLS
RW
C
NC
TR
1
LOW TEMP
BY-PASS TIMER
10
19.10.3 Deluxe Room Control Remote
FIGURE 62: Deluxe Room Control Remote
86 of 154
Page 95
FIGURE 63: Deluxe Room Control Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALVE
BURNER ON
FLAME RELAY
PILOT VALVE
SOLENOID
PRIMARY SHUT-OFF
20
AA
LT-2
VALVES OPEN
52
52
41
43
45
44
49
46
52
24VAC
51
52
1
18
35
2
V1
V2
L
52
52
B
W
R
8
9
3
4
5
1
2
321
1
TM
TCA
S
E
E
S
L
N
6
7
55
56
57
SECTION 19: ELECTRICAL
87 of 154
Page 96
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
1
HLS
T-1 CONTROL TRANS.
H1H2
AFS1-LO
PS-1
HIGH GAS
PRS. SWITCH
RESET
MANUAL
FEEDER PROTECTION
REF: N.E.C. TABLE 430-250
SIZING BY OTHERS.
G
LPJ-125SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
79.7
3
F1
F1
DISC SW
F1
77.0
1800
60
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
AA
FAN ON
LIGHT
LT-1
MOTOR FLA TAKEN FROM N.E.C
REFER TO NAMEPLATE FOR ACTUAL FLA
H3H4
460VAC
AFS2-HI
RESET
MANUAL
LIMIT
HIGH TEMP
AIRFLOW
AIRFLOW
2
11
30
31
33
35
18
16
54
54
5
34
15
32
54
5A
CB-3
X4
120V
X1
X2X3
12
JUMPERJUMPER
SD
SMOKE DETECTOR
DISCHARGE
SD22
23
CR
22
23
CR
5
60
M1
M1
MOL-1
M1
OL
START
MOTOR
AFS3
AA
CLOGGED FILTER
LIGHT
70
500VA.
3A
CB-2
PS-2
LOW GAS
PRS. SWITCH
RESET
MANUAL
TH-3
OA STAT
BUR
TH-1
SW-2
SUMMER
ON
SW-1
OFF
RB
CYCLE STAT
AUTO
6
8
WINTER
5 MIN.
LLS
RW
C
NC
TR
1
LOW TEMP
BY-PASS TIMER
10
19.10.4 Standard Room Control Remote
FIGURE 64: Standard Room Control Remote
88 of 154
Page 97
FIGURE 65: Standard Room Control Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALV E
BURNER ON
FLAME RELAY
PILOT VALVE
SOLENOID
PRIMARY SHUT-OFF
20
AA
LT-2
VALVES OPEN
52
52
2
41
43
45
44
49
46
35
52
18
24VAC
51
52
SOV1
SOV2
1
52
47
B
W
R
8
9
3
4
5
1
2
321
1
TM
TCA
S
E
E
S
L
N
6
7
86
87
88
SECTION 19: ELECTRICAL
89 of 154
Page 98
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
T-1 CONTROL TRANS.
X4
120VAC
X1
H1
500VA
H4
FEEDER PROTECTION
REF: N.E.C. TABLE 430-152
SIZING BY OTHERS.
G
LPJ-40SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
29.7
3
F1
F1
DISC SW
F1
27.0
1800
20
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
MOTOR FLA TAKEN FROM N.E.C
REFER TO NAMEPLATE FOR ACTUAL FLA
4000-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Yo ur RAPID
®
Air Handler may be equipped with one
of the following DDC control offerings. If so, a
separate manual providing wiring, operation and
trouble shooting information, specific to that control
offering, will also accompany this document.
19.12 Intelligent Control Systems
19.12.1 ICS II
19.12.2 ICS IV
19.12.3 InfinityPro™
92 of 154
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.