Rapid 4044, 4049, 4036, 4054, 4060 Installation, Operation & Service Manual

...
Page 1
NOT FOR RESIDENTIAL USE
WARNING
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
WARNING
FOR YOUR SAFETY If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas supplier after leaving the building. Follow the gas supplier’s instructions.
8. If you cannot reach your gas supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clear­ances to combustibles away from equipment.
Some objects will catch fire or explode when placed close to equipment.
Failure to follow these instructions can result in death, injury or property damage.
Rapid® 4000-Series
Direct-Fired Air Handler
Installation, Operation &
Service Manual
4024 4036 4040 4044 4049
4054 4060 4066 4073 4080 4089
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your service technician with necessary information.
CANADA: 100% OUTSIDE AIR ONLY
© 2018 Rapid Engineering LLC
Rapid Engineering LLC
1100 Seven Mile Road NW Comstock Park, MI 49321 Telephone: +1.616.784.0500 Fax: +1 616.784.0435
www.rapidengineering.com
P/N RP140000NA Rev A 03/18
Page 2
Page 3
TABLE OF CONTENTS
© 2018
Rapid Engineering LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Rapid Engineering LLC.
SECTION 1: Air Handler Safety..............................................1
1.1 Description of Operation...............................................1
1.2 Inspection and Setup ................................................... 1
1.3 Temporary Storage.......................................................2
1.4 Safety Labels and Their Placement .............................2
1.5 California Proposition 65 ..............................................2
1.6 Label Placement ..........................................................3
SECTION 2: Installer Responsibility .....................................6
2.1 Corrosive Chemicals....................................................6
2.2 National Standards and Applicable Codes ..................6
2.3 Required Equipment .................................................... 6
SECTION 3: Critical Considerations ..................................... 8
3.1 Required Clearances to Combustibles......................... 8
3.2 Hardware .....................................................................8
SECTION 4: National Standards and Applicable Codes .....9
4.1 Gas Codes...................................................................9
4.2 Installation Codes ........................................................9
4.3 Aircraft Hangars ...........................................................9
4.4 Parking Structures and Repair Garages...................... 9
4.5 Electrical ......................................................................9
4.6 Venting......................................................................... 9
4.7 High Altitude ................................................................9
SECTION 5: Specifications .................................................. 10
SECTION 6: Lifting an Air Handler (Rigging)......................27
6.1 Preparing to Lift the Air Handler.................................27
6.2 Lifting a Horizontal Air Handler ..................................28
6.3 Lifting an Vertical Air Handler ....................................29
6.4 Upright Assembly Alignment......................................31
SECTION 7: Air Handler Assembly...................................... 32
7. 1 Ca ulking the Air Handler............................................. 33
7. 2 Ca ulking a Horizontal Air Handler...............................34
7. 3 Ca ulking an Vertical Air Handler.................................35
7.4 Accessory Connections..............................................37
SECTION 8: Roof Curb .........................................................41
8.1 Roof Curb Assembly and Installation.........................41
SECTION 9: Indoor Suspension Mounting -
Horizontal Air Handler ....................................46
9.1 Suspension Mounting Assembly and Instructions ..... 46
SECTION 10: Leg Mounting .................................................48
SECTION 11: Filter Section ..................................................51
SECTION 12: Inlet Hoods .....................................................52
12.1 Inlet Hood Assembly ................................................ 52
SECTION 13: Service Platform.............................................55
13.1 Service Platform ......................................................55
SECTION 14: Discharge accessories..................................57
14.1 One-Way, Three-Way and Four-Way Discharge
Head Installation......................................................57
14.2 Splash Plate Installation........................................... 63
SECTION 15: Vibration Isolation..........................................64
SECTION 16: Cooling Specifications..................................68
16.1 Evaporative Cooling.................................................68
SECTION 17: Duct Considerations......................................69
17.1 Inlet Air Duct ............................................................. 69
17.2 Return Air Duct .........................................................69
17.3 Supply Air Duct Work ............................................... 69
SECTION 18: Gas Piping...................................................... 70
18.1 Gas Manifolds.......................................................... 70
18.2 Gas Piping and Pressures ....................................... 70
18.3 Gas Piping................................................................74
18.4 Pressure Test Ports...................................................74
SECTION 19: Electrical......................................................... 75
19.1 Disconnect Fuse Sizing .......................................... 76
19.2 Wiring and Electrical Connections........................... 76
19.3 Remote Panel .......................................................... 76
19.4 Motor Current Draw ................................................. 76
19.5 Control Cu rrent Draw ............................................... 77
19.6 Safety Systems........................................................ 77
19.7 Interlocks ................................................................. 79
19.8 Control Options........................................................ 79
19.9 Safety Systems........................................................ 81
19.10 Remote Panels ...................................................... 82
19.11 DDC-Ready Controls ............................................. 90
19.12 Intelligent Control Systems .................................... 92
19.13 HVAC Remote Panels and Panel Options ............. 94
19.14 Basic Air Handler Sequence of Operation............. 96
19.15 Honeywell
SECTION 20: Direct Fired Burner.......................................112
20.1 Direct Fired Burner Ignition.....................................115
20.2 Direct Fired Burner Flame Proving (Flame Rod) ....116
20.3 Honeywell UV Flame Detector ...............................119
20.4 Honeywell UV Flame Detector (Continued)........... 120
SECTION 21: Start-up Procedures .................................... 121
21.1 Installation of Recirculating Air Handler ................. 122
21.2 Mechanical ............................................................. 122
21.3 Electrical ................................................................ 123
21.4 Airflow .................................................................... 123
21.5 Gas Piping and Initial Pressure Settings................ 124
21.6 Safety Shut Off Valve Check .................................. 126
21.7 Temperature Control System Calibration................ 126
SECTION 22: Maintenance................................................. 129
22.1 General.................................................................. 130
22.2 Unit Exterior........................................................... 130
22.3 Blower Section...................................................... 130
22.4 Manifold and Controls............................................ 132
22.5 Burner................................................................... 132
22.6 Optional Equipment............................................... 134
SECTION 23: Replacement Parts ...................................... 135
SECTION 24: Troubleshooting .......................................... 136
24.1 Initial Checks ......................................................... 137
24.2 Motor and Blower ................................................. 137
24.3 Burner................................................................... 138
24.4 Temperature Controls ........................................... 139
24.5 A1014 Amplifier - Field Checklist .......................... 140
SECTION 25: RAPID SECTION 26: RAPID
Evaporative Cooler ............................................................. 148
SECTION 27: The RAPID® 4000-Series Warranty............. 151
®
RM7890 Flame Safeguard................ 100
®
4000-Series Start-Up Procedures. 143
®
4000-Series Start-Up Procedures
Printed in the U.S.A.
Page 4
Page 5
LIST OF TABLES
Table 1: Recommended Torque Settings................................. 8
Table 2: 4000 AM Dimensions ............................................... 11
Table 3: 4000 AM Approximate Shipping Weights ................. 12
Table 4: 4000 MUA Dimensions............................................. 13
Table 5: 4000 MUA Approximate Shipping Weights .............. 14
Table 6: 4000 FR Dimensions ................................................ 15
Table 7: 4000 FR Approximate Shipping Weights.................. 16
Table 8: 4000 VAV Dimensions.............................................. 17
Table 9: 4000 VAV Approximate Shipping Weights ............... 18
Table 10: Dimensions............................................................. 19
Table 11: Leaving Dry Bulb Temperature Drop (Average) ..... 19
Table 12: Air Density Ratio..................................................... 20
Table 13: Dimensions............................................................. 21
Table 14: Estimated Tons of Cooling ..................................... 21
Table 15: Dimensions............................................................. 22
Table 16: Energy Recovery.................................................... 23
Table 17: Fan Selection Chart................................................ 24
Table 18: Fan Selection Chart (continued)............................. 25
Table 19: Static Pressure Drops for Options.......................... 26
Table 20: Roof Curbs (availability based on style) ................. 41
Table 21: Formulas................................................................. 68
Table 22: Abbreviations.......................................................... 68
Table 23: Evaporation Rate.................................................... 68
Table 24: Suggested Air Changes Per Hour
(Air Change Method).............................................. 68
Table 25: Saturation Efficiency at Stated Media Depth.......... 68
Table 26: Static Pressure Drop (in wc) at Stated
Media Depth ........................................................... 68
Table 27: Manifold Component Identification ......................... 71
Table 28: Minimum and Maximum Fuse Size by Motor
Size and Supply Voltage ........................................ 76
Table 29: Control Voltage Wiring For All Control Systems..... 76
Table 30: Safety Systems....................................................... 77
Table 31: Safety Systems....................................................... 81
Table 32: Factory Preset Schedu
Table 33: Jumper Settings...................................................... 98
Table 34: Deflection Force B and BX Belts (in lbs) .............. 123
Table 35: Motor Sheave Drive Torque Specifications .......... 124
Table 36: Motor and Blower Bushing Torque Specifications 124
Table 37: Burner Mode by Amplifier Type............................ 125
Table 38: Maximum Temperature Rise ................................ 126
Table 39: Motor Lubrication Intervals ................................... 133
le on TH8110 Thermostat .. 96
There are references in this manual to various trademarks. All trademarks mentioned herein, whether registered or not, are the property of their respective owners. Rapid Engineering LLC is not sponsored by or affiliated with any of the trademark or registered trademark owners, and makes no representations about them, their owners, their products or services.
Page 6
Page 7
TABLE OF FIGURES
Figure 1: 4024 - 4049................................................................ 3
Figure 2: 4054 and 4089 ........................................................... 4
Figure 3: 4000-Series Interior ................................................... 5
Figure 4: 4000 AM Vertical Model Dimensions....................... 11
Figure 5: 4000 AM Horizontal Model Dimensions................... 12
Figure 6: 4000 MUA Vertical Model Dimensions..................... 13
Figure 7: 4000 MUA Horizontal Model Dimensions ................14
Figure 8: 4000 FR Vertical Model Dimensions........................ 15
Figure 9: 4000 FR Horizontal Model Dimensions ................... 16
Figure 10: 4000 VAV Vertical Model Dimensions.................... 17
Figure 11: 4000 VAV Horizontal Model Dimensions................ 18
Figure 12: Evaporative Cooling...............................................19
Figure 13: Mechanical Cooling................................................21
Figure 14: Energy Recovery ...................................................22
Figure 15: Lifting a Horizontal Air Handler Filter Section and
Options (Model 4024 - 4049) ................................. 28
Figure 16: Lifting a Horizontal Air Handler with Options (Model
4054 - 4089) ..........................................................28
Figure 17: Lifting an Vertical Air Handler (All Models)............. 29
Figure 18: Lifting an Vertical Air Handler with Filter Section and
Mixing Box .............................................................30
Figure 19: Inlet Alignment .......................................................31
Figure 20: Caulking Air Handler Joints.................................... 33
Figure 21: Caulking a Standard Horizontal Air Handler...........34
Figure 22: Caulking a Standard Vertical Air Handler............... 35
re 23: Assembling Optional Discharge / Supply and Return
Figu
Sleeves. .................................................................36
Figure 24: Electrically Connecting Joined Sections ................ 37
Figure 25: Installing Cooling Coil Section ...............................37
Figure 26: Installing Pressure Transmitter Tubing for AM and VAV
38 Figure 27: Typical Freeze Protection (Evaporative Cooling
Package #1)...........................................................38
Figure 28: Conductivity Control and Freeze Protection
(Evaporative Cooling Package #2).........................39
Figure 29: Protection and Auto-Flush (Evaporative Cooling
Package #3)...........................................................39
Figure 30: Evaporative Cooling Trap Detail ............................. 40
Figure 31: Roof Curb...............................................................42
Figure 32: Roof Curb Installation ............................................43
Figure 33: Roof Curb Assembly with Brackets........................44
Figure 34: Duct Support Adapter ............................................ 45
Figure 35: Indoor Suspension .................................................47
Figure 36: Assembling Legs for Horizontal Air Handlers......... 49
Figure 37: Assembly Legs and Rainskirt for Upright Air Handlers
50
ure 38: Filter Section Support Assembly............................51
Fig
Figure 39: Inlet Hood without Filters (4024-4049)................... 52
Figure 40: Inlet Hood without Filters (4054-4089)................... 53
Figure 41: Inlet Hood with Permanent Filters .......................... 53
Figure 42: Inlet Hood with Moisture Limiter.............................54
Figure 43: Service Platform for an Vertical Air Handler ..........55
Figure 44: Service Platform for a Horizontal Air Handler........ 56
Figure 45: Vertical Air Handler with Duct Sleeves and Discharge
Head .......................................................................................58
Figure 46: One-Way Discharge Head .................................... 59
Figure 47: Three-Way Discharge Head..................................60
Figure 48: Four-Way Discharge Head.................................... 61
Figure 49: 120° Discharge Head Horizontal Bottom Supply Air62
Figure 50: Discharge Plate ..................................................... 63
Figure 51: Suspended ............................................................ 64
Figure 52: Curb Mounted........................................................ 65
Figure 53: Platform Mounting on Vibration Isolators............... 66
Figure 54: Vibration Isolation Platform Locations ................... 67
Figure 55: Standard Gas Manifold .......................................... 71
Figure 56: FM Gas Manifold ................................................... 72
Figure 57: XL Insurance Gas Manifold ................................... 73
Figure 58: Basic Remote ........................................................ 82
Figure 59: Basic Remote (Continued)..................................... 83
Figure 60: Standard Discharge Remote.................................. 84
Figure 61: Standard Discharge Remote (Continued).............. 85
Figure 62: Deluxe Room Control Remote .............................. 86
Figure 63: Deluxe Room Control Remote (Continued)........... 87
Figure 64: Standard Room Control Remote ........................... 88
Figure 65: Standard Room Control Remote (Continued) ....... 89
Figure 66: DDC-Ready Controls............................................. 90
Figure 67: DDC-Ready Controls (Continued) ......................... 91
Figure 68: Air Handler Styles.................................................. 93
Figure 69: Fireye
®
M4RT1 ..................................................... 96
Figure 70: Jumper Locations .................................................. 98
Figure 71: Midco HMA-2A Burner..........................................113
Figure 72: Spark Rod Dimensions.........................................115
Figure 73: Maxon NPLE Burner.............................................116
Figure 74: Sheave Alignment ............................................... 122
Figure 75: Belt Tension ........................................................123
Figure 76: Fireye Flame Module........................................... 124
Figure 77: MR 212 Valve....................................................... 127
Figure 78: M611 Valve .......................................................... 128
Figure 79: Regulator (2005).................................................. 128
Figure 80: RM7897C Flame Control..................................... 142
Page 8
Page 9
SECTION 1: AIR HANDLER SAFETY
Yo ur Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these
sections. Installation, service and, at a minimum, annual inspection of air handlers must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation or service of this equipment.
This air handler is designed for heating non­residential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances and applicable standards that apply to gas piping, electrical wiring, ventilation, etc. must be thoroughly understood before proceeding with the installation.
Protective gear is to be worn during installation, operation and service. Thin sheet metal parts have sharp edges. To prevent injury, the use of w
ork
gloves is recommended.
Before installation, check that the local distribution conditions, nature of gas and pressure and adjustment of the appliance are compatible.
The equipment must be applied and operated under the general concepts of reasonable use and installed using the best building practices.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
For additional copies of the Installation, Operation and Service Manual, please contact Rapid Engineering LLC.
Gas-fired appliances are not designed for use in atmospheres containing flammable vapors or dust or atmospheres containing chlorinated or halogenated hydrocarbons. Recirculated room air may be hazardous if containing flammable solids, liquids, and gases; explosive materials; and/or substances
which may become toxic
when exposed to heat (i.e.
refrigerants, aerosols, etc.).
SECTION 1: AIR H ANDLER S AFETY
1.1 Description of Operation
This air handler is a direct-fired, electric, steam, hot water and/or energy recovery heated fresh air appliance. It is designed for indoor or outdoor installation with fresh outdoor air delivered to the burner. Air handlers are designed to operate in temperatures as low as -30 °F (-34 °C) variable frequency drive is only approved for applications 15 °F (-9 °C) and above, unless a control enclosure heater is installed. The air handler is factory-tested and may be designed to operate using natural gas or LPG (check the air handler's rating plate for information on the appropriate gas). The heat will modulate to maintain the selected supply air temperature or room air temperature, depending on the selected controls. See Page 92, Section .
The air handler may be provided with several different controls and options to meet various application requirements. Be sure to read this entire manual before installation and start-up.
1.2 Inspection and Setup
The air handler may ship in multiple sections based upon the configuration selected. The air handler was
inspected and operated prior to shipment. Immediately u
pon receipt of the air handler, check the fuel and electrical requirements of the air handler and verify that they match the fuel and electrical supply available. Verify that the specifications on the air handler rating plate match the order. Check the air handler for any damage that may have occurred during shipment. If any damage is found, file a claim with the transporting agency. Do not refuse shipment. Check the installation location to ensure proper clearances to combustibles. See Page 8, Section 3.1.
Any small options which do not come attached to the air handler will be found inside the air handler.
Larger accessories (i.e. legs, stand, filter section, inlet hood) may either ship with the air handler or separately on another truck. Check the bill of lading for information.
1 of 154
Page 10
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
1.3 Temporary Storage
If the air handler must be temporarily stored (ie. job site is not ready for installation of the air handler), the following procedure should be performed. After unloading unit from truck, place on a flat clean surface in a protected area. The air handler should be set on 4" x 4" (10 cm x 10 cm) pieces of timber to elevate unit off the ground. Cover air handler with a tarp or weatherproof material to ensure protection from the environment. Manually rotate the fan wheel every 15 days to eliminate grease from settling in the fan bearings and creating flat spots on the shaft.
Air handlers built for indoor installation are not weatherized.
Rapid Engineering LLC will not be held responsible for any damage that may occur from outdoor storage.
1.4 Safety Labels and Their Placement
Product safety signs or labels should be replaced by product user if they are no longer legible. Please contact Rapid Engineering LLC or your RAPID
®
independent distributor to obtain replacement signs or labels. See Page 3, Figure 1 through Page 5, Figure 3.
1.5 California Proposition 65
In accordance with California Proposition 65 require- ments, a warning label must be placed in a highly visible location on the outside of the equipment (i.e., near equipment's serial plate). See label placement drawing on Page 3, Figure 1 through Page 5, Figure
3 for label location. Avoid placing labels on areas with extreme heat, cold, corrosive chemicals or other
elements. To order additional labels, please contact
®
Rapid Engineering LLC or your RAPID
independent
distributor.
2 of 154
Page 11
1.6 Label Placement
BDBD
OAOA
7
11
7
VERTICAL CONTROL SIDE
VERTICAL OPP. CONTROL SIDE
HORIZONTAL OPP. CONTROL SIDE HORIZONTAL CONTROL SIDE
3
ON SHRINK WRAP
1
1
2
4
4
4
4
5
6
6
2
5
IF USED.
2
5
2
5
Item Part Number Description
1 19305 Label Shock Hazard 2 19304 Label Severe Injury Hazard 3 19307 Label Crush Hazard 4 19308 Label Fire Hazard 5 19309 Label Falling Hazard 6 19306 Label Burn Hazard 7 91040039 Rapid Logo Label 8 91070015 Proposition 65 Label
FIGURE 1: 4024 - 4049
SECTION 1: AIR H ANDLER S AFETY
3 of 154
Page 12
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
BD
BD
OA
LIFTING RINGS
OA
LIFTING RINGS
VERTICAL CONTROL SIDE
VERTICAL OPP. CONTROL SIDE
HORIZONTAL OPP. CONTROL SIDE
HORIZONTAL CONTROL SIDE
ACCESS DOOR
GAS CONNECTION
6 x 2 x 12GA
CHANNEL BASE FRAME
DISCONNECT
RC
Curb Channel
2 x 6
6 x 2 x 12GA
CHANNEL BASE FRAME
ON SHRINK WRAP
IF USED.
Curb Channel 2 x 6
Access Door (18 x 30)
LA
Elec Conn.
Gas Conn.
RC
Disconnect
Disconnect
INLET
BR
BR
BD
EXH
BD
EXH
3
6
5
4
2
1
1
2
5
4
2
5
4
4
6
2
5
7
7
7
7
BURNER FAN
FAN
BURNER
BURNER
FAN
BURNER
FAN
Item Part Number Description
1 19305 Label Shock Hazard 2 19304 Label Severe Injury Hazard 3 19307 Label Crush Hazard 4 19308 Label Fire Hazard 5 19309 Label Falling Hazard 6 19306 Label Burn Hazard 7 91040039 Rapid Logo Label 8 91040015 Proposition 65 Label
FIGURE 2: 4054 and 4089
4 of 154
Page 13
FIGURE 3: 4000-Series Interior
1
CONE PLATE
12
13
2
12
MOTOR & MOTOR COOLING DUCT
INSIDE
CONTROL ENCLOSURE
8
9
7
7
9
2
CONTROL ENCLOSURE DOOR
PROP 65 LABEL
RATING TAG
ELECTRICAL PRINT
RH INSIDE WALL CONTROL ENCLOSURE
LH INSIDE WALL CONTROL ENCLOSURE
11
10
3
4
5
6
2
Item Part Number Description Qty.
1 Label - Rotation 2 2 Label - High Voltage 2 3 Label - Caution Don’t Overtighten Belt 1 4 Label - Alignment Guide 1 5 Label - Rapid Factory Direct Parts Information 1 6 Label - Bearing Lube Chart 1 7 Label - Gas Type 3 8 Label - Outdoor Temp Sensor 1
9 Label - Min/Max Gas Pressures Required 1 10 Label - Regulator Model Number 1 11 Label - Regulator/Internal Relief Required 1 12 Label - Notice To Installer 1 13 Label - Caution Yellow Wire Not Diffused 1 14 91070015 Proposition 65 Label 1
SECTION 1: AIR H ANDLER S AFETY
5 of 154
Page 14
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
WARNING
Explosion Hazard
Equipment must have access to uncontaminated air at all times.
Failure to follow these instructions can result in death, injury or property damage.
CAUTION
Product Damage Hazard
Do not use equipment in area containing corrosive chemicals.
Refer to appropriate Material Safety Data Sheets (MSDS).
Failure to follow these instructions can result in product damage.
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install and commission the air handler, as well as the gas and electrical supplies, in accordance with applicable specifications and codes. Rapid Engineering LLC recommends the installer contact a local building inspector or Fire Marshal for guidance.
•To use the information given in a layout drawing and in the manual together with the cited codes and regulations to perform the installation.
• To install the air handler in accordance with clearances to combustibles.
•To furnish all needed materials not furnished as standard equipment.
• To plan location of supports.
• To provide access to
air handler
for servicing.
• To provide the owner with a copy of this Installation, Operation and Service Manual.
•To never use air handler as support for a ladder or other access equipment and never hang or suspend anything from heater.
•To ensure there is adequate air circulation around the air handler and to supply air for combustion, ventilation and distribution in accordance with local codes.
• To assemble or install any accessories or associated duct work using best building practices.
• To properly size supports and hanging materials.
• To ensure air handler is placed in an approved application.
6 of 154
• To provide building pressure relief/dampers fans to prevent over pressurization of a building, if needed.
2.1 Corrosive Chemicals
Rapid Engineering LLC cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the life span of the air handler components will be greatly reduced. The loca­tion of the outside air supply must be carefully chosen to supply outside air, free of these compounds, to the burners whenever the presence of these compounds is suspect. Warranty will be invalid if the air handler is exposed to halogenated hydrocar­bons.
2.2 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
2.3 Required Equipment
When lifting of the equipment is required, the installing contractor is responsible for supplying or arranging for the appropriate lifting equipment so that
Page 15
the air handler and accessories may be placed in a safe manner.
The qualified installer or service technician is responsible for having the appropriate equipment for the safe installation and start-up of an industrial air handler. Tools required to commission the equipment include, but are not limited to, the following:
• Various screwdriver types and sizes
• Various adjustable wrenches
• Torque wrenches
• Pipe wrenches sized appropriately for the gas train components
• Drill motor and various drill bits and runners
• U-tube manometer or gas pressure gauge
• Volt meter
• Clamp style ammeter
• Belt tension gauge
• Thermometer
SECTION 2: INSTALLER R ESPONSIBILITY
7 of 154
Page 16
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from equipment.
Some objects will catch fire or explode when placed close to equipment.
Failure to follow these instructions can result in death, injury or property damage.
SECTION 3: CRITICAL CONSIDERATIONS
WARNING
• Locate the air handler so that the air intakes are not too close to any exhaust fan outlets, gasoline storage or other contaminants that could potentially cause dangerous situations.
• Keep gasoline or other combustible materials including flammable objects, liquids, dust or vapors away from this air handler or any other appliance.
• Maintain clearances from heat sensitive material, equipment and workstations.
Clearances to combustibles do not denote clearances for accessibility. Minimum clearance for access is 48" (122 cm). Minimum clearance for accessibility applies to the control enclosure, fan access panel and filter access panel (when equipped).
The stated clearances to combustibles represent a surface temperature of 90 °F (50 °C) above room temperature (90 °F [50 °C] plus ambient temperature). Building materials with a low heat tolerance (i.e. plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
Explosion Hazard
Fresh air supply duct and burner housing must be purged with fresh air four times before every ignition.
Explosive vapors will ignite if not evacuated before ignition attempt.
Failure to follow these instructions can result in death, injury or property damage.
3.1 Required Clearances to Combustibles
Clearances are the required distances that combustible objects must be away from the air handler to prevent fire hazards. Combustibles are materials that may catch on fire and include common items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times for safety.
Check the clearances on each air handler being installed to make sure the product is suitable for your application and the clearances are maintained. Clearances to combustibles for all models are 6"(15.2 cm) on all surfaces. Read and follow the safety guidelines below:
Maintain clearances from vehicles parked below the
air handler. See Page 9, Section 4.4.
3.2 Hardware
Unless otherwise specified, all hardware must be torqued to settings on Page 8, Table 1.
Table 1: Recommended Torque Settings
Bolt Head
Grade Marking
Nut Grade
Marking
Bolt Size Grade 2 Grade 5
10-24 27 in•lb 42 in•lb
1/4-20 65 in•lb 101 in•lb
5/16-18 11 ft•lb 17 ft•lb
3/8-16 19 ft•lb 30 ft•lb
8 of 154
Page 17
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the nameplate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 ­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1- latest revision, Natural Gas and Propane Installation Code.
SECTION 4: NATIONAL S TANDARDS AND A PPLICABLE C ODES
4.5 Electrical
Electrical connection to air handler must be in accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances, and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
4.2 Installation Codes
Installations must be made in accordance with the Standard for the Installation of Air­Conditioning and Ventilating Systems, NFPA 90A - latest revision for the installation of air conditioning and ventilating systems.
4.3 Aircraft Hangars
Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard on Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code, Standard CSA B149.1 - latest revision.
4.4 Parking Structures and Repair Garages
Installation in garages must be in accordance with the following codes:
United States: Refer to standard for Parking Structures, NFPA 88A - latest revision or Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code, standard CSA B149.1 - latest revision.
4.6 Venting
The venting must be installed in accordance with the requirements within this manual and
the following codes:
United States: Refer to NFPA 54/ANSI Z223.1­latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision, Natural Gas and Propane Installation Code.
4.7 High Altitude
These air handlers are approved for installations up to 2000' (609.6 m) (in the US) and 4500' (1371.6 m) (in Canada) without modification. Consult factory if US installation is above 2000 is above 4500
'
(609.6 m) or Canadian installation
'
(1371.6 m).
9 of 154
Page 18
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 5: SPECIFICATIONS
Dimension and estimated weight tables apply to both vertical and horizontal units of the same style. All dimensions are in inches and all weights are in pounds, but are subject to change without notice. Dimensions apply to both horizontal and vertical units. Filters and legs are shipped loose. Control enclosure for 3" or smaller manifolds is 57"H x 57"W x 25"D. (B dimension of model 4024 cabinet is approximately 20" smaller than the control enclosure. Model 4049 control enclosure is 57"H x 57"W x 20"D.) To minimize water entrainment, an inlet hood with drift eliminator or inlet plenum is recommended. Outdoor duct sizes vary. Control enclosure can be located on left or right side of unit. (Shown on right side in drawings.) Consult Rapid Engineering LLC for additional information. All industrial air handlers are built based on customer specific static pressure. All ductwork and connections must be sized per SMACNA (Sheet Metal and Air Conditioning Contractors’ National Association). The legend below details abbreviations used in this section and applies to Page 11, Figure 4 through Page 18, Figure 11.
Legend OA = Outside Air CE = Control Enclosure BD = Bottom Discharge LD = Left Discharge RD = Right Discharge UD = Up Discharge BR = Bottom Return RR = Right Return LR = Left Return ER = End Return FJ = Field Joint * AD1 = Access Door ** AD2 = Access Door ***
* Models 4054 - 4089
** Models 4080 - 4089
*** Models 4024 - 4073
10 of 154
Page 19
FIGURE 4: 4000 AM Vertical Model Dimensions
F
B
Q
S
SECTION 5: SPECIFICATIONS
A
MK
K
J
BD RD/LD
ELECTRICAL CONNECTION
BR
GAS CONNECTION
BR
UD
FAN SECTIONBURNER SECTION
AD2
FJ
AD1
CE
RD
AD2
AD1
CE
BD/UD
FJ
BR
SERVICE
PLATFORM
(OPTIONAL)
FILTER
SECTION
R
(OPTIONAL)
P
L
LD
D
C
E
N
T
R
V
G
OR
V
H
R
(OPTIONAL)
FILTER MIX BOX
T
N
R
BR
P
RAIN SKIRT
OA
RIGHT SIDE VIEW
(STANDARD FOR
OUTDOOR EQUIPMENT)
LEGS
(OPTIONAL)
OA
AA
FRONT VIEW
Table 2: 4000 AM Dimensions
Air Handler
Width
Model
4024 40 40 109 - 4 - 62 62 62 4 5.5 20 29 18 27 32 22 34 4 2 3 10 30 40 60 48 36 40 4036 58 58 120 - 4 - 62 66 77 5 5.5 25 47 26 41 50 32 50 4 2 3 4 30 63 77 72 36 63 4040 63 63 130 - 4 - 81 68 77 6 6.5 33 50 30 41 55 40 53 4 2 3 4 30 63 77 84 36 63 4044 69 69 137 - 4 - 81 70 79 6 6.5 36 56 32 43 61 46 59 4 2 3 4 30 76 84 84 36 76 4049 76 76 140 - 4 - 81 72 80 6 6.5 39 63 34 44 68 53 66 4 2 3 4 30 76 84 84 36 76 4054 85 85 144 86 58 6 - 100 77 90 6 6.5 43 72 39 55 77 55 75 4 2 3 4 30 94 77 96 48 94 4060 94 94 154 90 64 6 - 100 77 85 6 6.5 48 81 38 50 86 65 84 4 2 3 4 30 94 77 96 48 94 4066 104 96 158 94 64 6 - 119 84 100 6 6.5 50 91 45 65 96 67 90 4 2 3 4 30 112 120 96 48 96 4073 112 96 163 94 69 - 3 119 84 107 6 6.5 50 99 44 72 104 64 90 4 2 3 4 30 112 120 96 48 96 4080 131 112 171 75 96 - 4 139 94 112 6 7.5 60 116 48 77 123 76 106 4 2 3 4 30 131 138 96 48 112 4089 131 112 177 81 96 - 4 139 94 112 6 7.5 60 116 48 77 123 76 106 4 2 3 4 30 131 138 96 48 112
Height
ABCDE F G HH1J K L M NN1PP1Q RR1STV X Y ZAABB
Length
Base Frame
Base Frame
Formed Channel
Filter Length
Plenum Width
Structural Angle
Filter Section Width
With Side Return
Filter Mixbox Length
Filter Mixbox Length
Discharge Width
Discharge Length
Return Air Length
Return Air Width
Return Air Height
Return Air Length
Discharge Height
Plenum Length
Inlet Hood Length
Minimum Leg Height
Plenum Height
11 o f 154
Page 20
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
OA
B
F
BD
UD
LD/RD
Q
S
ELECTRICAL
CONNECTION
GAS CONNECTION
BR
CE
V
LR
N
RR
T
H & (H1)
G
V
Y
X
Z
A
OA
RD
BD/UD BR BR
A
M
K
K
J
L
D
E
C
N
T
R
CE
R
FJ
N1
R1
S
P1
RR/LR
P
LD
BR
FJ
AD1
AD2
AD1
AD2
PLAN VIEW
RIGHT SIDE VIEW
FAN SECTION
BURNER SECTION
COIL SECTION
(OPTIONAL)
EVAPORATIVE
COOLER
(OPTIONAL)
ENERGY
RECOVERY
SECTION
(OPTIONAL)
FILTER
SECTION
(OPTIONAL)
FILTER MIX BOX
(OPTIONAL)
OR
INLET PLENUM
(OPTIONAL)
INLET HOOD (OPTIONAL)
OR
See Page 21, Figure 14 Energy recovery section for dimensions
See Page 19,Figure 12 Evaporative cooler section for dimensions
See Page 20, Figure 13 for coil section for dimensions
BB
R
R
P
FIGURE 5: 4000 AM Horizontal Model Dimensions
Table 3: 4000 AM Approximate Shipping Weights
Horizontal Service Platforms
Model
4024
4036
4040
4044
4049
4054
4060
4066
4073
4080
4089
Horizontal
Fan Section
Horizontal
Burner Section
Basic
Add
With
Outside Air
1,254 475 70 190 320 611 80 343 340 1,289 2,110 520 70 205 465 843 135 657 430 2,129 2,427 606 69 209 525 1,012 210 661 470 2,443 2,783 630 70 215 600 1,122 226 866 500 2,816
3,114 650 68 230 640 1,230 248 870 525 3,150 2,383 1,671 675 66 235 685 1,597 370 1,150 580 2,373 1,754 2,673 1,936 710 70 240 760 1,707 395 1,157 600 2,663 2,029 2,961 2,126 735 65 275 875 2,084 410 1,635 620 3,129 2,228 4,219 2,332 760 65 275 1,125 2,220 425 2,052 630 4,553 2,541 3,667 4,790 805 70 310 1,400 2,776 590 2,128 720 4,002 4,924 4,101 4,849 820 70 310 1,400 2,776 590 2,128 720 4,503 4,983
With
Filter Mix Box
Add
Filter Section
Filter Mixbox
Inlet Hood
Inlet Plenum
Vertical
Service Platform
Vertical
Fan Section
Vertical
Burner Section
12 of 154
Page 21
FIGURE 6: 4000 MUA Vertical Model Dimensions
F
B
N
H
GAS
CONNECTION
R
G
K
M
A
K
J
L
D
C
E
ELECTRICAL
CONNECTION
OA
BD/UD
CE
OA
CE
UD
BD
RD
RD/LD
LD
P
FJ
AD1
AD2
FRONT VIEW
RIGHT SIDE VIEW
FAN SECTIONBURNER SECTION
FILTER
SECTION
(OPTIONAL)
LEGS
(OPTIONAL)
RAIN SKIRT
(STANDARD FOR
OUTDOOR EQUIPMENT)
FJ
AD2
AD1
SECTION 5: SPECIFICATIONS
Table 4: 4000 MUA Dimensions
Air Handler
Width
Model
4024 40 40 109 - 4 - 62 3 4 5.5 20 29 34 36 30 52 60 48 40 4036 58 58 120 - 4 - 62 3 5 5.5 25 47 50 36 30 63 77 72 63 4040 63 63 130 - 4 - 81 3 6 6.5 33 50 53 36 30 76 84 84 63 4044 69 69 137 - 4 - 81 3 6 6.5 36 56 59 36 30 76 84 84 76 4049 76 76 140 - 4 - 81 3 6 6.5 39 63 66 36 30 94 77 84 76 4054 85 85 144 86 58 6 - 100 3 6 6.5 43 72 75 48 30 94 77 96 94 4060 94 94 154 90 64 6 - 100 3 6 6.5 48 81 84 48 30 112 120 96 94 4066 104 96 158 94 64 6 - 119 3 6 6.5 50 91 90 48 30 112 120 96 96 4073 112 96 163 94 69 - 3 119 3 6 6.5 50 99 90 48 30 131 138 96 96 4080 131 112 162 75 87 - 4 139 3 6 7.5 60 116 106 48 30 131 138 96 112 4089 131 112 168 81 87 - 4 139 3 6 7.5 60 116 106 48 30 131 138 96 112
Height
ABCDE F G HJKLMNPRXYZBB
Length
Base Frame
Formed Channel
Base Frame
Structural Angle
Filter Section Width
Plenum Width
Discharge Width
Discharge Length
Discharge Height
Filter Section Length
Minimum Leg Length
Plenum Length
Plenum Height
Inlet Hood Length
13 of 154
Page 22
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
C
D
E
A
M
K
K
J
L
FJ
G
R
Y
X
A
Z
GAS CONNECTION
F
B
N
H
ELECTRICAL CONNECTION
BD/UD
UD
BD
RD
LD/RD
LD
CE
CE
OA
OA
FJ
AD1AD2
AD1AD2
FAN SECTION BURNER SECTION
COIL SECTION
(OPTIONAL)
EVAPORATIVE
COOLER
(OPTIONAL)
FILTER
SECTION
(OPTIONAL)
INLET PLENUM
(OPTIONAL)
INLET HOOD
(OPTIONAL)
OR
RIGHT SIDE VIEW
PLAN VIEW
ENERGY
RECOVERY
SECTION
(OPTIONAL)
BB
See Page 21, Figure 14 Energy recovery section for dimensions
See Page 19,Figure 12 Evaporative cooler section for dimensions
See Page 20, Figure 13 for coil section for dimensions
FIGURE 7: 4000 MUA Horizontal Model Dimensions
Table 5: 4000 MUA Approximate Shipping Weights
Model
Horizontal
4024
4036
4040
4044
4049
4054
4060
4066
4073
4080
4089
Fan Section
1,325 320 80 452 1,360
2,110 465 135 657 2,129 2,530 525 210 862 2,546 2,783 600 226 866 2,816 3,305 640 248 1,126 3,341
2,518 1,695 685 370 1,150 2,508 1,760 2,808 1,973 760 395 1,627 2,798 2,076 3,036 2,159 875 410 1,635 3,204 2,234 4,525 2,361 1,125 425 2,052 4,859 2,441 3,667 4,790 1,400 590 2,128 4,002 4,624
4,101 5,210 1,400 590 2,128 4,503 5,044
Horizontal
Burner Section
Filter Section
Inlet Hood
Inlet Plenum
Vertical
Fan Section
Vertical
Burner Section
14 of 154
Page 23
FIGURE 8: 4000 FR Vertical Model Dimensions
B
F
Z
Q
ELECTRICAL
CONNECTION
GAS
CONNECTION
T
S x P
80%
BR
(Optional)
80%
ER
(Optional)
20%
OA
(Optional)
20%
OA
(Optional)
B
H
K
A
M
20%
OA
(Optional)
K
M
K
T
G
E
C
D
L
J
K
AD2
AD1
A
H
BD/UD
BD
LD
CE
UD
RD
RD/LD
CE
Y
FJ
FAN SECTION
BURNER SECTION
FILTER STAND
with BULK FILTER
MEDIA (OPTIONAL)
LEGS
(OPTIONAL)
FRONT VIEW
RIGHT SIDE VIEW
FJ
AD2
AD1
SECTION 5: SPECIFICATIONS
Discharge Length
Discharge Width
Return Ai r Width
Discharge Length
Discharge Height
Inlet Hoot /
Duct Height
Return Air Length
Louver Height
Inlet Hood Length
Minimum Leg Height
Table 6: 4000 FR Dimensions
Air Handler
Width
Model
4024 40 40 109 - 4 - 10 24 4 5.5 20 29 30 32 34 4 18 10 28 21 27 36 3 4036 58 58 120 - 4 - 12 36 5 5.5 25 47 30 50 50 4 26 4 34 30 35 36 3 4040 63 63 130 - 4 - 12 36 6 6.5 33 50 30 55 53 4 30 4 34 32.5 37 36 3 4044 69 69 137 - 4 - 16 36 6 6.5 36 56 30 61 59 4 32 4 45 35.5 39 36 3 4049 76 76 140 - 4 - 16 36 6 6.5 39 63 30 68 66 4 34 4 45 39 42 36 3 4054 85 85 144 86 58 6 - 16 36 6 6.5 43 72 30 77 75 4 39 4 45 43.5 46 48 3 4060 94 94 154 90 64 6 - 20 36 6 6.5 48 81 30 86 84 4 38 4 56 48 50 48 3 4066 104 96 158 94 64 6 - 20 48 6 6.5 50 91 30 96 90 4 45 4 56 49 51 48 3 4073 112 96 163 94 69 - 3 24 60 6 6.5 50 99 30 104 90 4 44 4 68 49 51 48 3 4080 131 112 171 75 96 - 4 24 60 6 7.5 60 116 30 123 106 4 48 4 68 57 57 48 3 4089 131 112 177 81 96 - 4 24 60 6 7.5 60 116 30 123 106 4 48 4 68 57 57 48 3
Height
ABCDE F G HJKLMNPQRSTUWXYZ
Length
Base Frame
Base Frame
Formed Channel
Structural Angle
Outside Air Length
Filter Stand Height
15 of 154
Page 24
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 9: 4000 FR Horizontal Model Dimensions
C
D
J
L
E
S
LD
K
A
M
K
BD/UD
FJ
AD1AD2
BR
CE
R
R
RD
FAN SECTION
BURNER SECTION
UD
Z
Q
B
LD/RD
FJ
CE
AD1AD2
F
BD
ELECTRICAL
CONNECTION
80% (Optional)
BR
Table 7: 4000 FR Approximate Shipping Weights
T
P
W
ER
80%
(Optional)
GAS CONNECTION
X
INLET HOOD (OPTIONAL)
RIGHT SIDE
VIEW
A
OA
OA
PLAN VIEW
A x U
Louver Duct Louver
A x W
Outdoor Air Duct Sleeve
N
A x U
N
A x W
Filtered Inlet Hood
X
FILTERS
Model
4024
4036
4040
4044
4049
4054
4060
4066
4073
4080
4089
Horizontal
Fan Section
1,245 320 80 1,230 95 2,055 465 135 2,054 140 2,354 525 210 2,360 150 2,716 600 226 2,704 160 3,034 640 248 3,017 175
2,383 1,470 685 370 2,373 1,553 320 2,673 1,712 760 395 2,663 1,805 350 2,961 1,847 875 410 3,129 1,949 400 4,219 1,994 1,125 425 4,553 2,203 450 3,667 4,359 1,400 590 4,002 4,493 500
4,101 4,418 1,400 590 4,503 4,552 500
Horizontal
Burner Section
16 of 154
Filter Section
Inlet Hood
Vertical
Fan Section
Vertical
Burner Section
Filter Stand
Page 25
FIGURE 10: 4000 VAV Vertical Model Dimensions
F
B
SECTION 5: SPECIFICATIONS
A
J
K
M
K
BD
20% to 100% Air
ELECTRICAL
CONNECTION
CONNECTION
GAS
L
FAN SECTIONBURNER SECTION
AD2
FJ
AD1
CE
FILTER
SECTION
(OPTIONAL)
RAIN SKIRT
(STANDARD FOR
OA
OUTDOOR EQUIPMENT)
LEGS
(OPTIONAL)
AD2
AD1
CE
BD
D
FJ
C
E
N
G
OA
H
RIGHT SIDE VIEW
FRONT VIEW
Table 8: 4000 VAV Dimensions
Air Handler
Width
Model
ABCDE F G HJKLMNXYZBB
4024 4059109 - 4 - 1036 4 5.524293040604840 4036 5884120 - 4 - 1236 5 5.532473063777263 4040 6392130 - 4 - 1236 6 6.535503063778463 4044 69102137 - 4 - 1636 6 6.535563076848476 4049 76109140 - 4 - 1636 6 6.540633076848476 4054 85 124 144 86 58 6 - 16 48 6 6.5 40 72 30 94 77 96 94 4060 94 138 154 90 64 6 - 20 48 6 6.5 43 81 30 94 77 96 94 4066 104 140 158 94 64 6 - 20 48 6 6.5 43 91 30 112 120 96 96 4073 112 137 163 94 69 - 3 24 48 6 6.5 43 99 30 112 120 96 96 4080 131 156 171 75 96 - 4 24 48 6 7.5 43 116 30 131 138 96 112 4089 131 156 177 81 96 - 4 24 48 6 7.5 43 116 30 131 138 96 112
Height
Length
Base Frame
Base Frame
Structural Angle
Formed Channel
Filter Section Width
Minimum Leg Height
Discharge Width
Discharge Length
Plenum Width
Filter Section Length
Plenum Length
Plenum Height
Inlet Hood Length
17 of 154
Page 26
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
C
K
A
M
K
J
L
FJ
G
N
X
Y
Z
GAS CONNECTION
F
B
20% to 100%AIR
ELECTRICAL CONNECTION
BD
CE
CE
BD
OA
OA
FJ
AD1AD2
AD1AD2
D
E
A
FAN SECTION
BURNER SECTION
COIL SECTION
(OPTIONAL)
EVAPORATIVE
COOLER
(OPTIONAL)
FILTER
SECTION
(OPTIONAL)
INLET PLENUM
(OPTIONAL)
INLET HOOD (OPTIONAL)
OR
RIGHT SIDE VIEW
PLAN VIEW
ENERGY
RECOVERY
SECTION
(OPTIONAL)
BB
See Page 21, Figure 14 Energy recovery section for dimensions
See Page 19,Figure 12 Evaporative cooler section for dimensions
See Page 20, Figure 13 for coil section for dimensions
FIGURE 11: 4000 VAV Horizontal Model Dimensions
Table 9: 4000 VAV Approximate Shipping Weights
Model
4024
4036
4040
4044
4049
4054
4060
4066
4073
4080
4089
Horizontal
Fan Section
1,564 320 80 343 1,589
Horizontal
Burner Section
2,585 465 135 657 2,627 2,982 525 210 661 3,033 3,413 600 226 866 3,470 3,804 640 248 870 3,870
2,953 2,061 685 370 1,150 2,943 2,144 3,333 2,396 760 395 1,157 3,323 2,489
3,711 2,626 875 410 1,635 3,879 2,278 4,959 2,842 1,125 425 2,052 5,293 3,051 4,537 5,640 1,400 590 2,128 4,872 5,774 4,971 5,699 1,400 590 2,128 5,373 5,833
Filter Section
Inlet Hood
Inlet Plenum
Vertical
Fan Section
Vertical
Burner Section
18 of 154
Page 27
FIGURE 12: Evaporative Cooling
LD
SECTION 5: SPECIFICATIONS
66”
BD/UD
AD2
FJ
AD1
CE
RD
FAN SECTION BURNER SECTION
UD
LD/RD
BD
AD2
ELECTRICAL
CONNECTION
FJ
CE
AD1
BR
COIL SECTION
(OPTIONAL)
GAS CONNECTION
A
EVAPORATIVE
COOLER
(OPTIONAL)
B
ENERGY
RECOVERY
SECTION
(OPTIONAL)
FILTER
SECTION
(OPTIONAL)
PLAN VIEW
INLET PLENUM
(OPTIONAL)
OR
INLET HOOD
RIGHT SIDE VIEW
(OPTIONAL)
Table 10: Dimensions
Applicable
Cabinet
Model
550 FPM
Max CFM
Applicable
Cabinet
Model
750 FPM
Max
CFM
4024 ECM24 4,000 4024 ECM24D 5,800 40 40
4024-4036 ECM36 10,000 4036 ECM36D 13,700 58 58
4036 ECM40 12,000 4036-4040 ECM40D 16,600 63 63
4036 ECM44 14,500 4036-4040 ECM44D 19,600 69 69 4036-4040 ECM49 17,700 4036-4049 ECM49D 24,300 76 76 4036-4049 ECM54 23,000 4044-4054 ECM54D 31,200 85 85 4040-4049 ECM60 28,000 4049-4060 ECM60D 38,500 49 49 4044-4054 ECM66 31,600 4049-4066 ECM66D 43,100 104 96 4044-4054 ECM73 34,100 4054-4066 ECM73D 46,600 112 96
4054-4066 ECM80/ECM89 48,000 4066-4080
ECM80D/
ECM89D
65,300 131 112
Dimensions
AB
NOTE: Evaporative Cooling Section is 42".
Transition section is 24". Total length is 66". Applicable for MUA/AM/VAV styles only.
OA
OA
Table 11: Le av i ng Dry Bulb Temperature Drop (Average)
Wet Bulb
Depression (°F)
4" 6" 8"12"18" 24"
10.0 5.3 6.8 7.9 8.9 9.8 9.9
12.5 6.6 8.5 9.8 11.1 12.2 12.3
15.0 7.9 10.2 11.8 13.3 14.6 14.8
17.5 9.2 11.9 13.8 15.6 17.1 17.3
20.0 10.5 13.6 15.8 17.8 19.5 19.7
22.5 11.8 15.3 17.7 20.0 21.9 22.2
25.0 13.2 17.0 19.7 22.2 24.4 24.7
27.5 14.5 18.7 21.7 24.4 26.8 27.2
30.0 15.8 20.4 23.6 26.7 29.3 29.6
32.5 17.1 22.1 25.6 28.9 31.7 32.1
35.0 18.4 23.8 27.6 31.1 34.1 34.6
37.5 19.7 25.5 29.5 33.3 36.6 37.0
40.0 21.1 27.2 31.5 35.6 39.0 39.5
NOTE: Rapid Engineering LLC's standard media thickness equals 12".
Temperature Drop (°F)
for Stated Media Depth (in)
19 of 154
Page 28
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Table 12: Air Density Ratio
Temperature
(°F)
68° 1.00 0.97 0.93 0.90 0.87 0.84 0.80 0.77 0.75 0.72 0.69 70° 1.00 0.96 0.93 0.90 0.86 0.83 0.80 0.77 0.74 0.71 0.69 72° 1.00 0.96 0.93 0.89 0.86 0.83 0.80 0.77 0.74 0.71 0.69 74° 0.99 0.96 0.92 0.89 0.86 0.83 0.80 0.77 0.74 0.71 0.68 76° 0.99 0.95 0.92 0.89 0.85 0.82 0.79 0.76 0.73 0.71 0.68 78° 0.99 0.95 0.92 0.88 0.85 0.82 0.79 0.76 0.73 0.70 0.68 80° 0.98 0.95 0.91 0.88 0.85 0.82 0.79 0.76 0.73 0.70 0.68
0/
29.92
1,000/
28.86
2,000/
26.82
Density Ratio for Stated Elevation (ft/in HG)
3,000/
26.82
4,000/
25.84
5,000/
24.90
6,000/
23.98
7, 0 0 0 /
23.09
8,000/
22.22
9,000/
21.39
NOTE: Table to be used when calculating total tonnage of cooling adjusted for elevation.
10,000/
20.58
20 of 154
Page 29
FIGURE 13: Mechanical Cooling
OA
BD
UD
LD/RD
ELECTRICAL
CONNECTION
GAS CONNECTION
BR
CE
OA
RD
BD/UD
CE
FJ
LD
FJ
AD1AD2
AD1AD2
PLAN VIEW
RIGHT SIDE VIEW
FAN SECTION BURNER SECTION
COIL SECTION
(OPTIONAL)
EVAPORATIVE
COOLER
(OPTIONAL)
ENERGY
RECOVERY
SECTION
(OPTIONAL)
FILTER
SECTION
(OPTIONAL)
INLET PLENUM
(OPTIONAL)
INLET HOOD
(OPTIONAL)
OR
DD
CC
EE
SECTION 5: SPECIFICATIONS
Table 13: Dimensions
Compatible
Cabinet
Sizes
100% RA
Available Tons
0% OA/
Airflow - Cubic
Feet per Minute
(CFM)
3,000-7,000 24 8-35 1 13.8 33 x 60 218 509 68 40 72
7,001-10,000 24 18-50 1 18.0 36 x 72 389 556 80 44 72 10,001-20,000 36-40 25-100 2 38.3 27 x 102 261 523 110 65 72 20,001-27,500 36-44 50-138 2 52.5 35 x 108 381 524 116 80 78 27,501-30,000 40-49 69-150 2 61.2 39 x 113 449 490 121 90 78 30,001-35,000 49-60 75-175 2 70.0 41 x 123 428 500 131 96 84 35,001-50,000 60-73 88-250 2 93.8 45 x 150 373 533 154 105 84 50,001-60,000 66-80 125-300 3 106.5 36 x 142 469 563 150 126 102 60,001-65,000 73-89 150-325 3 117.0 36 x 156 513 556 164 126 102
Table 14: Estimated Tons of Cooling
Airflow - Cubic
Feet per Minute
(CFM)
5,000 16 19 22 24 27
7, 5 0 0 2 4 2 8 3 3 3 5 4 1 10,000 32 38 44 47 54 12,500 39 47 55 59 68 15,000 47 56 66 71 81 20,000 63 75 88 95 108 25,000 79 94 110 118 135 30,000 95 113 132 142 162 35,000 110 131 154 165 189 40,000 126 150 176 189 216 45,000 142 169 197 213 243 50,000 158 188 219 236 270 55,000 173 206 241 260 297 60,000 189 225 263 284 324 65,000 205 244 285 308 351
Range of
of Cooling
Quantity
of Coils
25% OA/
75% RA
Square
Feet
Fin Area (L x H)
of Each Coil (in)*
50% OA/
50% RA
Coil Face Velocity Width Height Length
Low HighCCDD EE
75% OA/
25% RA
Estimated tons of cooling required to achieve 55/54 leaving air condition
(chart based on OA conditions 94/74 and RA conditions of 80/67)
100% OA/
0% RA
21 of 154
Page 30
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FJ
GAS CONNECTION
ELECTRICAL CONNECTION
BD/UD
UD
BD
RD
LD/RD
LD
CE
CE
OA
OA
FJ
AD1AD2
AD1AD2
FAN SECTION BURNER SECTION
COIL SECTION
(OPTIONAL)
EVAPORATIVE
COOLER
(OPTIONAL)
FILTER
SECTION
(OPTIONAL)
INLET PLENUM
(OPTIONAL)
INLET HOOD
(OPTIONAL)
OR
RIGHT SIDE VIEW
PLAN VIEW
ENERGY
RECOVERY
SECTION
(OPTIONAL)
B
A
C
FIGURE 14: Energy Recovery
Table 15: Dimensions
Applicable Model
MUA AM A B C
4024 4024 4,000-7,000 109 58 69 1,000 150 400 150 250 225
4036 4036
4040
4044 4049 30,001-35,000 150 131 123 4,800 300 1,280 275 750 600 4049 4054 35,001-40,000 160 146 123 5,000 350 1,490 300 750 675 4054 4060 40,001-50,000 164 178 123 5,800 350 1,673 300 1,050 800 4060 4066 50,001-60,000 164 212 123 6,400 400 1,924 325 1,300 925
4040 20,001-25,000 137 94 123 2,700 300 800 250 550 475 4044 25,001-30,000 140 108 123 2,900 300 800 250 600 550
Airflow
Cubic Feet per
Minute (CFM)
Dimensions Estimated Weights
Length Width Height
Module
Inlet
Hood
Exhaust
Fan
Exhaust
Hood
Downturn
Section
7,001-15,000 120 85 94 1,900 200 550 200 450 425
15,001-20,000 130 94 96 2,000 200 800 225 450 425
Filter
Housing
22 of 154
Page 31
Table 16: Energy Recovery
SECTION 5: SPECIFICATIONS
Compatible
Cabinet Size
MUA AM Supply Exhaust Supply Exhaust Supply Exhaust
4024 4024
4036 4036
4040 4040
4040 4044
4044 4049
4049 4054
4054 4060
4060 4066
Supply/Exhaust Air
Cubic Feet
per Minute (CFM)
4,000 0.42 0.45 59% 59% 329.19 / 851.18 367.34 / 889.82 5,000 0.63 0.67 60% 60% 411.49 / 1,064.04 459.17 / 1,112.20 6,000 0.88 0.94 59% 59% 493.79 / 1,276.74 551.01 / 1,334.75 7,000 1.17 1.25 59% 59% 576.09 / 1,489.31 642.84 / 1,557.43
7,001 0.29 0.30 63% 61% 240.04 / 632.20 267.85 / 658.93 8,000 0.37 0.39 63% 61% 274.33 / 722.60 306.12 / 752.99 9,000 0.45 0.48 63% 61% 308.62 / 812.94 344.38 / 847.09
10,000 0.55 0.59 63% 61% 342.91 / 903.25 382.64 / 941.23 11,000 0.66 0.70 63% 61% 377.20 / 993.53 420.91 / 1,035.40 12,000 0.77 0.82 63% 61% 411.49 / 1,083.78 459.17 / 1,129.59 13,000 0.89 0.95 63% 61% 445.78 / 1,174.00 497.44 / 1,223.81 14,000 1.03 1.09 63% 61% 480.08 / 1,264.21 535.70 / 1,318.05 15,000 1.17 1.24 63% 61% 514.37 / 1,354.39 573.97 / 1,412.31 15,001 0.70 0.74 62% 61% 403.43 / 1,021.84 450.17 / 1,065.94 16,000 0.79 0.84 62% 60% 430.32 / 1,089.88 480.18 / 1,137.09
17,000 0.88 0.94 62% 60% 457.22 / 1,157.91 510.19 / 1,208.25 18,000 0.98 1.05 62% 60% 484.11 / 1,225.92 540.20 / 1,279.42 19,000 1.08 1.16 62% 60% 511.01 / 1,293.92 570.22 / 1,350.60 20,000 1.19 1.27 61% 60% 537.90 / 1,361.91 600.23 / 1,421.78 20,001 0.72 0.77 62% 60% 457.22 / 1,130.29 510.19 / 1,179.84 21,000 0.79 0.85 61% 60% 480.08 / 1,186.72 535.70 / 1,238.92 22,000 0.87 0.92 61% 60% 502.94 / 1,243.14 561.21 / 1,297.99 23,000 0.94 1.00 61% 60% 525.80 / 1,299.55 586.72 / 1,356.99 24,000 1.02 1.09 61% 59% 548.66 / 1,355.95 612.23 / 1,415.99 25,000 1.10 1.17 61% 59% 571.52 / 1,412.35 637.74 / 1,474.99 25,001 0.83 0.89 61% 60% 489.87 / 1,218.80 546.64 / 1,272.52 26,000 0.90 0.96 61% 60% 509.47 / 1,267.47 568.50 / 1,323.44 27,000 0.96 1.03 61% 60% 529.06 / 1,316.14 590.37 / 1,374.35 28,000 1.03 1.10 61% 59% 548.66 / 1,364.80 612.23 / 1,425.25 29,000 1.10 1.17 61% 59% 568.25 / 1,413.45 634.10 / 1,476.15 30,000 1.17 1.25 61% 59% 587.85 / 1,462.10 655.96 / 1,527.05 30,000 0.87 0.92 61% 60% 493.79 / 1,243.14 551.01 / 1,297.99 31,001 0.92 0.98 61% 60% 510.25 / 1,284.50 569.38 / 1,341.26 32,000 0.98 1.04 61% 60% 526.71 / 1,325.87 587.74 / 1,384.53 33,000 1.03 1.10 61% 59% 543.17 / 1,367.23 606.11 / 1,427.79 34,000 1.09 1.17 61% 59% 559.63 / 1,408.59 624.48 / 1,471.06 35,000 1.15 1.23 61% 59% 576.09 / 1,449.94 642.84 / 1,514.32 35,001 0.93 0.99 61% 60% 514.37 / 1,289.10 573.97 / 1,346.07 36,000 0.98 1.04 61% 60% 529.06 / 1,325.87 590.37 / 1,384.53 37,000 1.03 1.10 61% 59% 543.76 / 1,362.63 606.77 / 1,422.98 38,000 1.08 1.15 61% 59% 558.46 / 1,399.40 623.16 / 1,461.44 39,000 1.13 1.21 61% 59% 573.15 / 1,436.16 639.56 / 1,499.90 40,000 1.19 1.27 61% 59% 587.85 / 1,472.92 655.96 / 1,538.36 40,001 0.79 0.84 61% 60% 477.09 / 1,184.03 532.38 / 1,236.11 42,000 0.87 0.92 61% 60% 500.95 / 1,243.14 558.99 / 1,297.99 44,000 0.94 1.01 61% 60% 524.80 / 1,302.23 585.61 / 1,359.80 46,000 1.02 1.09 61% 59% 548.66 / 1,361.32 612.23 / 1,421.61 48,000 1.11 1.18 61% 59% 572.51 / 1,420.40 638.85 / 1,483.42 50,000 1.20 1.28 61% 59% 596.37 / 1,479.48 665.47 / 1,545.23 50,001 0.83 0.89 61% 60% 489.87 / 1,218.80 546.64 / 1,272.52 52,000 0.90 0.96 61% 60% 509.47 / 1,267.47 568.50 / 1,323.44 54,000 0.96 1.03 61% 60% 529.06 / 1,316.14 590.37 / 1,374.35 56,000 1.03 1.10 61% 59% 548.66 / 1,364.80 612.23 / 1,425.25 58,000 1.10 1.17 61% 59% 568.25 / 1,413.45 634.10 / 1,476.15 60,000 1.17 1.25 61% 59% 587.85 / 1,462.10 655.96 / 1,527.05
Pressure Drop
(in wc)
Efficiency
Air Velocity Supply
(face/channel) (ft/min)
NOTE: Model sizes apply to MUA style cabinets. Consult factory when selecting energy recovery for AM
style cabinets. All weights are in pounds.
23 of 154
Page 32
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Table 17: Fan Selection Chart
Required Motor Horse Power (HP)
@ Noted External Static Pressure
(in wc)
Minute (CFM)
Model
Discharge Velocity
Feet per
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 0
Minute (FPM)
Feet per
Airflow Cubic
5,000 4024 1,241 2 2 2 3333CFCF1.11.41.61.92.22.52.8CFCF 65 6,000 4024 1,490 2 2 3 3355551.41.72.02.32.63.03.33.64.0 68 7,000 4024 1,738 2 3 3 3555551.82.12.52.83.13.53.94.24.6 71 8,000 4024 1,986 3 3 5 55557.57.52.22.63.03.33.74.14.54.95.3 74
9,000 4024 2,234 3 5 5 5 5 7.5 7.5 7.5 7.5 2.7 3.1 3.5 4.0 4.4 5.1 5.3 5.7 6.1 76 10,000 4024* 2,483 CF CF 5 5 7.5 7.5 7.5 7.5 10 3.2 3.7 4.2 4.6 5.1 5.6 6.1 6.6 7.0 78 10,000 4036 1,226 3 3 5 CF CF CF CF CF CF 2.1 2.6 3.2 CF CF CF CF CF CF 71 12,500 4036 1,532 5 5 5 5 7.5 7.5 7.5 CF CF 2.8 3.4 4.0 4.6 5.3 6.0 6.6 CF CF 73 15,000 4036 1,838 5 5 7.5 7.5 7.5 10 10 10 15 3.7 4.4 5.0 5.7 6.4 7.2 7.9 8.7 9.5 75 15,000 4040 1,309 5 5 7.5 7.5 7.5 10 10 CF CF 3.4 4.1 4.8 5.5 6.3 7.2 8.0 CF CF 74
17,500 4036 2,145 7.5 7.5 7.5 10 10 10 15 15 15 4.9 5.6 6.3 7.6 7.9 8.6 9.5 10.3 11.2 78
17,500 4040 1,527 5 7.5 7.5 7.5 10 10 10 15 15 4.2 5.0 5.8 6.6 7.5 8.3 9.2 10.2 11.1 76 20,000 4036 2,451 CF 10 10 10 15 15 15 15 15 6.3 7.1 7.9 8.7 10.1 10.4 11.3 12.2 13.1 80 20,000 4040 1,745 7.5 7.5 7.5 10 10 15 15 15 15 5.3 6.1 7.0 7.9 8.8 9.5 10.6 11.7 12.8 78 20,000 4044 1,429 5 7.5 7.5 10 10 15 15 15 15 4.7 5.6 6.5 7.5 8.5 9.5 10.6 11.7 12.8 77 22,500 4036* 2,757 CF CF 15 15 15 15 15 20 20 8.1 9.0 9.8 10.7 11.6 12.5 13.5 14.5 15.5 82 22,500 4040 1,964 7.5 10 10 15 15 15 15 15 20 6.6 7.5 8.4 9.4 10.3 11.4 12.4 13.4 14.5 80 22,500 4044 1,607 7.5 7.5 10 10 15 15 15 15 20 5.6 6.6 7.6 8.6 9.7 10.8 11.9 13.1 14.3 78 22,500 4049 1,319 7.5 7.5 10 10 15 15 15 20 20 5.1 6.1 7.2 8.3 9.5 10.7 12.0 14.7 16.2 71 25,000 4036** 25,000 4040 2,182 CF 10 15 15 15 15 20 20 20 10.3 11.2 12.1 13.1 14.0 15.0 16.0 17.7 18.1 86 25,000 4044 1,786 7.5 10 10 15 15 15 15 20 20 8.2 9.1 10.1 11.1 12.1 13.2 14.3 15.4 16.5 82 25,000 4049 1,465 7.5 10 10 15 15 15 15 20 20 6.7 7.8 8.8 9.9 11.0 12.2 13.4 14.7 15.9 80 27,500 4044 1,964 10 10 15 15 15 15 20 20 20 5.9 7.0 8.2 9.4 10.6 11.9 13.2 14.6 15.9 73 27,500 4049 1,612 7.5 10 10 15 15 15 20 20 20 10.0 11.0 12.1 13.1 14.2 15.4 16.5 17.7 18.9 83 30,000 4040* 2,618 15 15 20 20 20 20 25 25 25 8.1 9.1 10.3 11.4 12.6 13.9 15.1 16.4 17.7 81 30,000 4044 2,143 15 15 15 15 20 20 20 20 25 6.9 8.1 9.3 10.5 11.9 13.2 14.6 16.0 17.4 75 30,000 4049 1,758 10 10 15 15 15 20 20 20 25 12.6 13.7 14.8 15.5 16.6 17.8 19.1 20.3 21.6 86 30,000 4054 1,395 10 10 15 15 15 20 20 20 25 9.6 10.7 11.9 13.1 14.4 15.7 17.0 18.4 19.7 83 30,000 4060 1,111 7.5 10 15 15 15 20 20 25 25 8.0 9.2 10.5 11.9 13.2 14.6 16.1 17.6 19.1 77 32,500 4044 2,322 15 15 15 20 20 20 20 25 25 7.0 8.4 9.8 11.2 12.7 14.3 15.8 17.5 19.2 73 32,500 4049 1,905 10 15 15 15 20 20 20 25 25 11.4 12.6 13.8 15.1 16.4 17.8 19.2 20.6 22.1 84 32,500 4054 1,512 10 10 15 15 15 20 20 20 25 9.3 10.6 11.9 13.3 14.8 16.2 17.7 19.3 20.9 79 35,000 4044* 2,500 15 20 20 20 20 25 25 25 30 8.0 9.4 10.8 12.3 13.9 15.5 17.2 18.9 20.6 75 35,000 4049 2,051 15 15 15 20 20 20 25 25 25 13.4 14.6 16.0 17.3 18.7 20.1 21.6 23.1 24.6 86 35,000 4054 1,628 10 15 15 15 20 20 25 25 25 10.8 12.1 13.5 15.0 16.5 18.0 19.6 21.1 22.8 81 35,000 4060 1,296 10 15 15 20 20 20 25 25 30 9.0 10.5 12.0 13.6 15.2 16.9 18.6 20.4 22.2 77 37,500 4049* 2,198 15 15 20 20 20 25 25 25 30 8.0 9.6 12.9 14.8 16.7 18.7 20.7 22.9 25.0 73 37,500 4054 1,744 15 15 15 20 20 20 25 25 25 12.4 13.8 15.2 16.8 18.3 20.0 21.6 23.3 25.0 82 37,500 4060 1,388 10 15 15 15 20 20 25 25 25 10.2 11.7 13.3 15.0 16.6 18.4 20.2 22.0 23.9 78 40,000 4049* 2,344 20 20 20 25 25 25 30 30 30 8.9 10.6 12.3 14.1 15.9 17.8 19.8 21.8 23.9 75 40,000 4054 1,860 15 15 20 20 20 25 30 30 40 14.2 15.7 17.2 18.8 20.4 22.1 23.8 25.5 27.3 84 40,000 4060 1,481 15 15 15 20 20 25 25 25 30 11.4 13.1 14.7 16.4 18.2 20.0 25.4 27.5 29.5 80 40,000 4066 1,266 15 15 20 20 25 25 30 30 40 9.8 11.6 13.4 15.2 17.1 19.1 21.1 23.2 25.3 76 45,000 4049* 2,637 20 25 25 30 30 30 40 40 40 10.5 12.5 14.6 16.7 19.0 21.3 23.8 26.3 29.0 72 45,000 4054 2,093 20 20 20 25 25 30 30 30 40 18.5 20.1 21.8 23.5 25.2 27.0 28.8 30.7 32.6 87 45,000 4060 1,667 15 15 20 20 25 25 30 30 40 14.5 16.2 18.0 19.8 21.7 23.7 25.7 27.7 29.7 82 45,000 4066 1,424 15 15 20 20 25 25 30 30 30 12.0 13.9 15.8 17.8 19.8 21.9 24.1 26.4 28.6 79 50,000 4054* 2,326 20 25 25 30 30 30 40 40 40 10.6 12.6 14.7 16.9 19.1 21.4 23.8 26.2 26.7 74 50,000 4060 1,852 20 20 20 25 25 30 30 40 40 18.2 20.0 21.9 23.8 25.9 28.0 30.1 32.2 34.4 85 50,000 4066 1,582 15 20 20 25 25 30 30 40 40 14.6 16.6 18.7 20.8 23.0 25.2 27.4 29.8 32.3 81 50,000 4073 1,455 15 15 20 25 30 30 40 40 40 12.5 14.7 16.9 19.2 21.6 24.0 26.5 32.9 35.7 77
Brake Horse Power (HP)
@ Noted External Static Pressure
(in wc)
dBA Decibel @
Noted External
Static Pressure
(in wc)
24 of 154
Page 33
Table 18: Fan Selection Chart (continued)
Required Motor Horse Power (HP)
@ Noted External Static Pressure
Minute (CFM)
Model
Discharge Velocity
Feet per
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 0
Minute (FPM)
Feet per
Airflow Cubic
55,000 4060** 2,037 20 25 25 25 30 30 40 40 40 18.1 20.0 21.9 23.9 26.0 28.1 30.1 32.3 34.6 83 55,000 4066 1,741 20 20 20 25 25 30 30 40 40 15.0 17.1 19.2 21.2 23.5 25.7 28.1 30.4 32.8 80 55,000 4073 1,600 20 20 25 25 30 30 30 CF CF 16.1 18.4 20.8 23.2 25.6 28.2 30.8 CF CF 75 60,000 4060** 2,222 25 25 30 30 40 40 40 40 40 22.0 24.1 26.2 28.3 30.5 32.7 35.0 37.3 39.5 85 60,000 4066 1,899 20 25 25 25 30 30 40 40 40 18.1 20.2 22.4 24.7 27.0 29.4 31.8 34.3 36.9 81 60,000 4073 1,745 20 25 25 30 30 40 40 40 40 18.6 21.0 23.5 26.1 28.6 31.3 34.1 36.9 39.7 77 60,000 4080 1,241 20 20 25 25 30 CF CF CF CF 16.5 19.1 21.7 24.5 27.4 CF CF CF CF 72 65,000 4066 2,057 25 25 30 30 40 40 40 40 50 21.6 23.9 26.2 28.6 31.1 33.6 36.1 38.8 41.4 83 65,000 4073 1,891 25 25 30 30 40 40 40 50 50 21.3 23.8 26.5 29.2 31.9 34.7 37.6 40.5 43.5 79 65,000 4080 1,345 20 25 25 30 40 40 CF CF CF 18.5 21.3 24.0 27.0 30.2 33.0 CF CF CF 74 70,000 4066** 2,215 30 30 40 40 40 40 50 50 50 25.5 27.9 30.4 33.0 35.6 38.2 40.9 43.5 46.4 85 70,000 4073 2,036 25 30 30 40 40 40 50 50 50 24.5 27.1 29.8 32.7 35.6 38.5 41.5 44.5 47.6 81 70,000 4080 1,448 25 25 30 30 40 40 40 50 CF 20.7 23.6 26.6 29.5 32.7 35.9 39.1 42.4 CF 76 75,000 4066** 2,374 30 40 40 40 50 50 50 50 60 30.0 32.6 35.2 37.9 40.6 43.4 46.2 49.1 52.0 87 75,000 4073 2,182 30 40 40 40 40 50 50 50 60 27.9 30.7 33.6 36.4 39.5 42.6 45.7 48.9 52.1 83 75,000 4080 1,552 25 30 30 40 40 40 50 50 50 23.2 26.3 29.4 32.5 35.8 39.1 42.4 45.9 49.4 78 75,000 4089 1,552 25 25 30 40 40 CF CF CF CF 21.3 24.5 27.9 31.3 34.8 CF CF CF CF 73 80,000 4066** 2,532 40 40 50 50 50 50 60 60 60 35.1 37.8 40.6 43.4 46.3 49.2 52.1 55.1 58.2 88 80,000 4073 2,327 40 40 40 50 50 50 60 60 60 31.7 34.6 37.6 40.7 43.7 47.0 50.3 53.6 56.9 85 80,000 4080 1,655 30 30 40 40 40 50 50 50 60 26.0 29.0 33.9 35.5 38.9 42.3 45.8 49.4 52.9 79 80,000 4089 1,655 25 30 40 40 40 50 CF CF CF 23.5 26.9 30.3 33.9 37.6 41.3 CF CF CF 75 85,000 4073** 2,473 40 40 50 50 50 60 60 60 75 36.0 39.1 42.3 45.5 48.7 51.9 55.4 58.8 62.4 86 85,000 4080 1,759 30 40 40 40 50 50 50 60 60 29.0 32.2 35.5 38.9 42.4 46.0 49.6 53.2 57.1 81 85,000 4089 1,759 30 30 40 40 50 50 50 60 CF 25.8 29.4 33.0 36.6 40.4 44.3 48.3 52.3 CF 76 90,000 4073** 2,618 50 50 50 60 60 60 75 75 75 40.7 43.9 47.2 50.5 53.9 57.4 60.7 64.3 68.0 87 90,000 4080 1,862 40 40 40 50 50 50 60 60 75 32.4 35.7 39.2 42.6 46.3 50.0 53.8 57.6 61.5 82 90,000 4089 1,862 30 40 40 40 50 50 60 60 60 28.3 32.0 35.8 39.6 43.5 47.5 51.6 55.8 60.0 78 95,000 4073* 2,764 50 50 60 60 60 75 75 75 75 45.9 49.2 52.6 56.1 59.6 63.2 66.8 70.5 74.1 88 95,000 4080 1,966 40 40 50 50 60 60 60 75 75 35.9 39.4 43.0 46.6 50.3 54.2 58.1 62.1 66.1 84
95,000 4089 1,966 40 40 40 50 50 60 60 60 75 31.3 35.0 38.9 42.9 46.9 51.0 55.3 59.5 64.0 79 100,000 4073** 2,909 50 50 50 60 60 75 75 75 75 41.2 44.8 48.5 52.3 56.0 60.0 64.1 68.3 72.5 89 100,000 4080 2,069 40 50 50 60 60 60 75 75 75 39.8 43.5 47.2 51.0 54.9 58.7 62.8 66.9 71.1 85 100,000 4089 2,069 40 40 50 50 60 60 60 75 75 34.3 38.1 42.2 46.2 50.5 54.7 59.0 66.2 68.0 80
110,000 4080 2,279 50 60 60 60 75 75 75 100 100 46.2 50.4 54.4 59.4 64.0 68.7 73.6 78.5 83.5 88 110,000 4089 2,276 50 50 50 60 60 75 75 75 100 41.1 45.2 49.5 53.8 58.3 62.8 67.5 72.2 76.9 83
120,000 4080** 2,483 60 75 75 75 100 100 100 100 100 57.0 61.6 66.1 70.9 75.9 80.9 86.1
120,000 4089** 2,483 50 60 60 75 75 75 100 100 100 49.0 53.4 57.9 62.5 67.1 71.9 76.8 81.9 86.9 85 130,000 4089** 2,690 60 75 75 75 100 100 100 100 100 58.0 62.7 67.5 72.4 77.4 82.2 87.4 92.7 98.0 87
150,000 4089** 3,103 100 100 100 100 125 125 125 125 125 80.0 85.3 90.6 96.0
* MUA configuration only. ** AM requires high velocity return air damper. ¤ Class II wheels CF= Consult Factory
IMPORTANT NOTES:
Sound levels are in dBA at 5' from the supply air opening. This figure does not account for attenuation, additional noise or directivity factors. More horsepower required includes both the running horsepower and the starting torque requirements. Horsepower can be greater than the standard fan curve charts. Brake horsepower does not include drive losses. For external static pressure greater than 2", contact your local representative or Rapid Engineering LLC. For operation in altitudes exceeding 2000' above sea level, contact the factory. The recommended motor horsepowers shown for the Fan Selection Chart in the 0 in. wc external static pressure column include fan and burner static pressures only (internal equipment static pressure). Other cabinet options could add static pressure and should be included in the external static pressure used to select motor horsepower. See the Static Pressure Drops in Table 20, Page 41 for the external static pressu
res that should be added for selected options.
(in wc)
Brake Horse Power (HP)
@ Noted External Static Pressure
(in wc)
101.5107.1112 .8118 .5124.
SECTION 5: SPECIFICATIONS
dBA Decibel @ Noted External Static Pressure
(in wc)
91.2
96.5 90
5
4
91
25 of 154
Page 34
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Table 19: Static Pressure Drops for Options
Description in wc
Cooling Coil Section 0.10 Cooling Coil CF Damper - Inlet 0.05 Damper - Low Leak 0.05 Damper - Discharge 0.10 Damper - Discharge, Low Leak 0.10 Supply Air End CF Discharge Plate 0.05 Discharge Head - One Way 0.10 Discharge Head - Three Way 0.10 Discharge Head - Four Way 0.05 Horizontal Inlet Hood 0.00 Horizontal Inlet Plenum0.10 Vertical Inlet Plenum Base 0.05 Moisture Limiter For Horizontal Inlet Hood 0.10 Aluminum Mesh Filters For Horizontal Inlet Hood 0.15 Vertical Stand with Polyester Filters (FR) 0.25 Outside Air Filter Section, No Filters 0 Filtered Mixing Box, No Filters 0 Filters - Polyester 0.25 Filters - Aluminum Mesh 0.15 Filters - 30% Pleated 0.25 Custom Filter Options (Bag, Cartridge, HEPA) CF Evaporative Cooling Section (ECM) 0.25 Evaporative Cooling Section (ECM-D) 0.50
Note:
Calculate the static pressure for selected cabinet options plus any ductwork. Use external static pressure column found in Page 24, Table 17 through Page 25, Table 18 Fan Selection Charts to determine motor horsepower.
26 of 154
Page 35
SECTION 6: LIFTING AN AIR H ANDLER (RIGGING)
SECTION 6: LIFTING AN AIR HANDLER (RIGGING)
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Failure to follow these instructions can result in death, injury or property damage.
The air handler must be installed in compliance with all applicable codes. The qualified installer or service technician must use best building practices when installing the air handler and any optional equipment. This appliance requires at least 4 CFM (6.8 outside air per 1,000 Btu/h (.293 kW). Any air handler that recirculates air from the heated space must use the return air opening to prevent any return air from passing over the burner.
IMPORTANT: Four eye bolts are provided with each upright air handler. These eye bolts are to be used when lifting the air handler for placement on the
provided support legs. DO NOT Install the support legs prior to lifting the air handler, damage to the legs and /or air handler may occur.
3
m
/h) of
6.1 Preparing to Lift the Air Handler
Prior to lifting the air handler, the following steps must be performed:
1. R e m o ve all packaging or banding that attached the air handler to the skid and ensure that the air handler is no longer bound to a skid or truck bed.
2. Remove all packaging or blockers.
3. Remove all of the accessories or packages that were shipped on the same skid, inside the air handler, or inside the control enclosure.
4. Inspect the air handler to:
Verify that there is no damage as a result of shipping.
•Ensure that it is appropriately rated for the utilities available at the installation site.
Verify that the eye bolts (lifting lugs) are intact, undamaged and secured to the air handler.
•Ensure factory-installed hardware is torqued to appropriate setting.
5. Prepare the installation location to be ready to accept the air handler (i.e. roof curb or legs).
6. Verify that the lifting equipment can handle the air handler’s weight and the required reach.
See Page 12, Table 3, Page 14, Table 5, Page 16, Table 7, Page 18, Table 9 and Page 14, Ta b l e 5 for air handlers weight.
27 of 154
Page 36
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
LIFTING SLINGS
END VIEW
CL CR
CRANE OR HELICOPTER CABLE
FAN
SECTION
BURNER
SECTION
FILTER
SECTION
FILTER MIX BOX
OR
TRANS, EVAP &
FILTER SECTION
INLET
PLENUM
SPREADER BAR
END VIEW
CL CR
FILTER MIX BOX
OR
TRANS, EVAP &
FILTER SECTION
INLET
PLENUM
NOTE: FOR MODELS 4080-4089, ACCESS DOOR IS ON BURNER SECTION.
LIFTING SLINGS
FAN
SECTION
BURNER
SECTION
FILTER
SECTION
6.2 Lifting a Horizontal Air Handler FIGURE 15: Lifting a Horizontal Air Handler Filter Section and Options (Model 4024 - 4049)
FIGURE 16: Lifting a Horizontal Air Handler with Options (Model 4054 - 4089)
28 of 154
Page 37
6.3 Lifting an Vertical Air Handler
BA
C
BA
C
BA
C
WOODEN BLOCKS
BASE FRAME
BASE FRAME
NOTE: SHEET METAL CHANNEL OR ANGLE IRON FRAME MUST BE ALIGNED ON ALL SECTIONS
INLET
Shipping Position:
1. Attach crane sling hooks to eye bolts A & B (4 places.)
2. Lift off truck.
3. Place on a clean flat dry surface free from water, mud, etc.
Turning Position:
4. Remove eye bolts B. (2 places)
5. Attached eye bolts from B to corner C (2 places.)
6. Attach crane sling hook to A eye bolts A (2 places.)
7. S lo wly raise and rotate 90 degrees.
Vertical Position:
8. Place air handler section on 4" (10.2 cm) wooden blocks.
9. Attach crane sling hooks to eye bolts A & C (4 places).
10. Air handler/section is now ready to be lifted into place.
NOTE: On fan sections lifting lugs are welded on supply air end.
FIGURE 17: Lifting an Vertical Air Handler (All Models)
SECTION 6: LIFTING AN AIR H ANDLER (RIGGING)
29 of 154
Page 38
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
LIFTING LUGS
B
U
RNER
REMOVE LIFTING EYE BOLTS AFTER SETTING SECTION
F
IL
T
ER SE
CT.
SE
CT
IO
N
MIX BOX
S
EC
TION
F
A
N
&
FILTE
R
S
ECT.
S
ECTIO
N
MIX B
O
X
SECTIO
N
B
U
RNE
R
SEC
TION
F
A
N
LEGS (4 required)
REMOVE LIFTING EYE BOLTS AFTER SETTING SECTION
SHEETMETAL CHANNEL OR ANGLE IRON FRAME
MUST BE ALIGNED ON
ALL SECTIONS
Model 4024 - 4049 Model 4054- 4089
LIFTING LUGS
SHEETMETAL CHANNEL OR ANGLE IRON FRAME
MUST BE ALIGNED ON
ALL SECTIONS
REMOVE LIFTING EYE BOLTS AFTER SETTING SECTION
LEGS (4 required)
NOTE: Sections may vary as shown
SEE FIGURE 19, PAGE 30
SEE FIGURE 19, PAGE 30
SEE FIGURE 19, PAGE 30
FIGURE 18: Lifting an Vertical Air Handler with Filter Section and Mixing Box
30 of 154
Page 39
6.4 Upright Assembly Alignment
ROPE
WALL
EXTERNAL
CAULKING
FIELD JOINT
SECTION VIEW-A
BURNER INLET/FAN DISCH. SECTION
FILTER MIXBOX DISCH./BURNER INLET
ALIGNMENT DETAIL.
(FOR UPRIGHTS MODELS 49-89 ONLY)
5/8 X 2 3/4
THREADED ROD
ALIGNMENT PIN
FAN SECTION INLET FRAME
OR BURNER INLET FRAME
WITH 7/8" CLEARANCE HOLE.
FMB DISCH./BURNER DISCH.
SECTION FRAME
5/8-11 FLANGE NUT TACK
WELDED (2) TO BURNER/FMB
DISCH. FRAME IN OPPOSITE
CORNER FROM ONE ANOTHER.
APPLY ROPE
CAULKING AROUND
PERIMETER OF FRAME.
DETAIL:
PLAN VIEW:
NOTE: THREADED ROD SHIPPED LOOSE. MOUNT IN OPPOSITE CORNERS WITH PROPER WELDED NUT.
FIGURE 19: Inlet Alignment
SECTION 6: LIFTING AN AIR H ANDLER (RIGGING)
31 of 154
Page 40
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 7: AIR HANDLER ASSEMBLY
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Failure to follow these instructions can result in death, injury or property damage.
For models 4024 - 4049, the burner and fan sections of the air handler are shipped as one piece. Filter section and/or filter mix box can be mounted to air handler when requested.
For models 4054 - 4089, the burner and fan sections of the air handler are shipped as two pieces that require field-assembly. To assemble, use the supplied hardware and bolt the fan section to the burner section through pre-drilled holes. Supplied hardware must be torqued to recommended specifications on Table 1, Page 8.
Caulk (provided by others) the sides, roof and bottom seams between the fan section and burner section. See Page 33, Figure 7.1 through Page 35, Figure 22.
NOTE: After the equipment sections are set together (if shipped separately), connection of the electrical conductors between the sections is required. The conductors are numbered on both ends. Join the conductors like numbers. The quantity of conductors supplied varies with the selected options. In addition, motor-supply conductors must be connected to the fan motor of model sizes 4054-4073. See Page 37, Section 7.4.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Equipment and accessories are heavy.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
32 of 154
Page 41
7.1 Caulking the Air Handler
3" (78.7 cm) ROOF TAPE PROVIDED BY MANUFACTURER
(NOT REQUIRED ON VERTICAL AIR HANDLER OR INDOOR UNITS)
HOUSING SKIN
HOUSING SKIN
CAULK AFTER ASSEMBLY
HOUSING SKIN
3/8" x 3/4" STRIP
CLEAN HOUSING SKIN
3" (78.7 cm) ROOF TAPE
TYPICAL VERTICAL JOINT
PRIOR TO ASSEMBLY.
CAULK EACH VERTICAL JOINT
TYPICAL ROOF JOINT
CAULK EACH HORIZONTAL JOINT
AFTER ASSEMBLY APPLY
TYPICAL ROOF JOINT
PRIOR TO ASSEMBLY.
OF CAULKING
THE 3" (78.7 cm) ROOF TAPE
"A" Type Joint
"B" Type Joint
(CAULK PROVIDED BY OTHERS)
3/8" x 3/4" STRIP OF CAULKING (PROVIDED BY MANUFACTURER)
TYPICAL VERTICAL JOINT
AFTER ASSEMBLY.
CAULK EACH VERTICAL EXTERIOR JOINT
NOTE: FAILURE TO PROPERLY CAULK THE AIR HANDLER JOINTS WILL ALLOW WATER TO ENTER THE AIR HANDLER.
Instructions for Roof Tape Installation:
1. Wipe surface clean and dry.
2. Peel backing off 3" (78.7cm) roof tape.
3. Apply roof tape over field joint.
4. Press tape firmly to form a tight seal (roll out if possible).
5. 3" (78.7 cm) roof tape NOT required on vertical air handlers.
6. Do not apply roof tape when outside temperature is below 40° F.
7. Roof tape is not required for indoor air handlers.
FIGURE 20: Caulking Air Handler Joints
SECTION 7: AIR H ANDLER A SSEMBLY
33 of 154
Page 42
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
A
P
L
E
N
U
M
INL
ET
A
IN
LET
B
B
U
R
N
E
R
FA
N
S
E
C
T
IO
N
S
EC
T
IO
N
B
HORIZONTAL AIR HANDLER
WITH INLET PLENUM
HORIZONTAL AIR HANDLER WITH INLET PLENUM AND OUTSIDE AIR FILTER
HORIZONTAL AIR HANDLER WITH INLET PLENUM AND FILTER MIX BOX
APPLY 3" (78.7 cm) ROOF TAPE TO ALL ROOF JOINTS. COMPONENTS MAY VARY AS SHOWN BELOW.
A
SEC
T
I
O
N
SE
C
TION
FAN
B
URNE
R
SECTIO
N
F
ILTE
R
B
P
L
E
N
U
M
IN
L
E
T
M
IX
B
OX
SECTIO
N
B
A
B
B
A
IN
L
ET
P
LE
N
U
M
A
IN
LE
T
F
ILT
E
R
S
ECT
ION
BUR
N
E
R
F
A
N
SE
C
T
IO
N
S
E
C
TIO
N
B
B
B
“A” Type Joint (typical both sides):
Seal with a HEAVY bead of calking. (provided by others)
“B” Type Joint:
Cover with 3" (78.7 cm) Roof Tape. (provided by manufacturer)
NOTE:
Failure to properly caulk the air handler joints will allow water to enter the air handler.
Caulk supply air/return sleeves as appropriate.
“A” Type Joint : Vertical joint on multiple-piece air handlers and inlet hoods. Run a HEAVY bead of caulking (provided by others).
“B” Type Joint : Roof joints on multiple-piece air handlers and inlet hoods. Cover with 3" (78.7 cm) roof tape (provided by manufacturer).
IN
LE
T
7.2 Caulking a Horizontal Air Handler FIGURE 21: Caulking a Standard Horizontal Air Handler
Note: Sections may vary as shown.
34 of 154
Page 43
7.3 Caulking an Vertical Air Handler
SHEETMETAL CHANNEL OR ANGLE IRON FRAME MUST BE ALIGNED ON ALL SECTIONS.
RAIN SKIRT ON OUTDOOR AIR HANDLER
"A
Ó
"AÓ
"AÓ
"AÓ
LEGS
"A"
LIFTING LUGS
"A"
"A"
FIELD ATTACHMENT
"A"
"A"
RAIN SKIRT ON OUTDOOR AIR HANDLER
FIELD ATTACHMENT
SHEETMETAL CHANNEL OR
ANGLE IRON FRAME MUST BE
ALIGNED ON ALL SECTIONS.
LIFTING LUGS
LEGS
"A" TYPE JOINT: SEAL WITH HEAVY BEAD OF CALUKING (PROVIDED BY OTHERS)
FIGURE 22: Caulking a Standard Vertical Air Handler
SECTION 7: AIR H ANDLER A SSEMBLY
NOTE: Sections may vary as shown.
35 of 154
Page 44
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
--
TYPICAL ASSEMBLY
3'-4"
3'-4"
TYPICAL ASSEMBLY
NOTE:DISCHARGE AND RETURN AIR SLEEVE'S ARE A OPTION AND CAN BE PURCHASED THRU RAPID, SEE CHART FOR ACTUAL OD OF DUCTS IF BEING BUILT AND INSTALLED BY SERVICE CONTRACTOR.
A OD
X
B OD
SELF TAPPING SCREWS
EVERY 6-8" C.D.
AIR HANDLER
HOUSING
RETURN AIR
SLEEVE
CAULKING
FLANGE
NOTE: TEK SCREW RETURN SLEEVE
TO INSIDE OF AIR HANDLER
RETURN AIR FLANGE.
RETURN AIR DAMPER
SELF TAPPING SCREWS
EVERY 6-8" C.D.
AIR HANDLER
HOUSING
FLOOR DISCH. FLANGE
LENGTH (MODELS 24-66) = 3.75"
(73-89) = 2"
DISCHARGE SLEEVE
CAULKING
AIR HANDLER RETURN AIR FLANGE
DISCHARGE AIR
RETURN
AIR
SEE CHART BELOW
FOR OD DIMENSION OF
DISCHARGE DUCT BEFORE
MAKING WALL PENETRATION.
2" FLANGE ON BOTH ENDS OF DISCHARGE DUCT
RETURN AIR
DISCHARGE
AIR
DISCHARGE DUCT
RETURN DUCT
FIGURE 23: Assembling Optional Discharge / Supply and Return Sleeves.
36 of 154
Page 45
7.4 Accessory Connections
Legend
OA Outside Air BR Bottom Return BD Bottom Discharge
LC Left Controls
DUAL PERFORATED
ADJUSTABLE PANEL
ACCESS PANELS:
REMOVE TO BOLT
SECTIONS TOGETHER
COOLING COIL
MANIFOLD
CONNECTIONS
COIL HOUSING ACCESS
¥ MODELS 4024-4049 = 4" FORMED 10 GA GALV CHANNELS ¥ MODELS 4054-4066 = 6" FORMED 10 GA GALV CHANNELS ¥ MODELS 4073 = 3
x 3 x
3/16" ANGLE IRON
¥ MODELS 4080-4089 = 4
x 3 x
1/4" ANGLE IRON
FIGURE 24: Electrically Connecting Joined Sections
SECTION 7: AIR H ANDLER A SSEMBLY
Inlet Hood
OA
LEFT SIDE VIEW
TYPICALLY 6 THHN CONDUCTORS
AND 1 SHIELDED CABLE
1/2" CONDUIT TYP.
CONTROL
CABINET WALL
NOTE:
DETAIL A
Filter
Mixbox
BR
Burner
Section Fan Section
LC
BD
NOTE: TYPICALLY 2 THHN CONDUCTORS AND 1 SHIELDED CABLE
DETAIL B
FIGURE 25: Installing Cooling Coil Section
37 of 154
Page 46
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
MODUS
LOHI
PROTECT TUBING
OPENING FROM
THE WIND.
(Installed by others.)
OUTSIDE AIR DUCT
BUILDING WALL
OR ROOF
AIR HANDLER
SUPPLY AIR
NOTE: BUILDING PRESSURE
TRANSDUCER (INSIDE
CONTROL PANEL - TYPICAL)
FIELD INSTALLED (Supplied by others)
MODUS
LO HI
RETURN AIR DUCT
AIR HANDLER
5/16" (Minimum)
PLASTIC TUBING
(Installed by others)
RETURN AIR
DAMPER BLADE
NOTE: ENSURE OPEN END OF TUBING
IS AWAY FROM ANY AIR FLOW. DO NOT
MOUNT TUBING NEAR SUPPLY AIR
AND RETURN AIR OPENINGS.
INDOOR INSTALLATION
OUTDOOR INSTALLATION
Factory furnished piping & devices.
Field furnished piping & devices.
HEADER
UNION
BLEED-OFF VALVE
WATER LEVEL
Notes
Legend
1)
2)
3)
4)
EVAPORATIVE COOLING MODULE
FLOAT VALVE & MAKE-UP CONN.
MANUAL SHUT-OFF VALVE
OVERFLOWR CONN.
DRAIN CONN.
VACUUM BREAKER
MANUAL DRAIN VALVE
PER CODE
FILL VALVE SOLENOID 1” NORMALLY CLOSED.
SUPPLY LINE DRAIN COLENOID 1” NORMALLY OPEN.
ROOF DRAIN
ROOF
ROOF CURB
RECIRCULATION PUMP
SUMP DRAIN 1 1/2” BALL VALVE POWERED OPEN & CLOSED.
AIR GAP
All solenoids must be installed in a line no smaller than the solenoid orifice.
Pitch drain line minimum 1/8” per foot towards outlet
Supply & supply line drain solenoids must be installed in a non-freeze location.
Makeup line must be installed with no traps or sages above the roof line.
WATER FLOW ADJUSTMENT VALVE
FIGURE 26: Installing Pressure Transmitter Tubing for AM and VAV
FIGURE 27: Typical Freeze Protection (Evaporative Cooling Package #1)
38 of 154
Page 47
SECTION 7: AIR H ANDLER A SSEMBLY
HEADER
EVAPORATIVE COOLING MODULE
FLOAT VALVE & MAKE-UP CONN.
MANUAL SHUT-OFF VALVE
OVERFLOW CONN.
DRAIN CONN.
VACUUM BREAKER
MANUAL DRAIN VALVE
AIR GAP PER CODE
UNION
WATER LEVEL
RECIRCULATION PUMP
ROOF CURB
ROOF DRAIN
SUPPLY LINE DRAIN SOLENOID 1” NORMALLY OPEN.
FILL VALVE SOLENOID 1” NORMALLY CLOSED.
SUMP DRAIN 1 1/2” BALL VALVE POWERED OPEN & CLOSED
CONDUCTIVITY CONTROL
Factory furnished piping & devices. Field furnished piping & devices.
Notes
Legend
1)
2)
3)
4)
All solenoids must be installed in a line no smaller than the solenoid orifice.
Pitch drain line minimum 1/8” per foot towards outlet
Supply & supply line drain solenoids must be installed in a non-freeze location.
Makeup line must be installed with no traps or sages above the roof line.
WATER FLOW ADJUSTMENT VALVE
Factory furnished piping & devices. Field furnished piping & devices.
Notes
HEADER
EVAPORATIVE COOLING MODULE
FLUSH SOLENOID NORMALLY CLOSED
MANUAL SHUTOFF VALVE
FLOAT VALVE & MAKE-UP CONN.
MANUAL SHUTOFF VALVE
OVERFLOW CONN.
DRAIN CONN.
VACUUM BREAKER
MANUAL DRAIN VALVE
AIR GAP PER CODE
UNION
CHECK VALVE
BLEED-OFF VALVE
WATER LEVEL
RECIRCULATION PUMP
ROOF CURB
ROOF
ROOF DRAIN
SUPPLY LINE DRAIN SOLENOID 1” NORMALLY OPEN.
FILL VALVE SOLENOID 1” NORMALLY CLOSED.
SUMP DRAIN 1 1/2” BALL VALVE POWERED OPEN & CLOSED.
Legend
1)
2)
3)
4)
All solenoids must be installed in a line no smaller than the solenoid orifice.
Pitch drain line minimum 1/8” per foot towards outlet
Supply & supply line drain solenoids must be installed in a non-freeze location.
5)
Header orifices serve as vacuum break for flush solenoid connection to header.
Makeup line must be installed with no traps or sages above the roof line.
WATER FLOW ADJUSTMENT VALVE
FIGURE 28: Conductivity Control and Freeze Protection (Evaporative Cooling Package #2)
FIGURE 29: Protection and Auto-Flush (Evaporative Cooling Package #3)
39 of 154
Page 48
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 30: Evaporative Cooling Trap Detail
40 of 154
Page 49
SECTION 8: ROOF CURB
SECTION 8: ROOF C URB
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Failure to follow these instructions can result in death, injury or property damage.
The roof curbs that support the air handler and accessory sections are available for all horizontal air handlers. See Page 41, Table 20 for roof curb. Roof curbs are shipped unassembled and require field assembly. Double check dimensions after assembly before roof material is installed and compare to the drawing on Page 40, Figure 30. NOTE: Before installation, verify that you have the correct roof curb and all required assembly brackets. If any components are missing, contact Rapid
®
Engineering LLC or your RAPID
independent
representative.
8.1 Roof Curb Assembly and Installation
Assemble roof curb according to the assembly drawings in Page 43, Section 32. Supplied hardware must be torqued to recommended specifications on Page 8, Table 1.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Cut/Pinch Hazard
Wear protective gear during installation, operation and
service. Equipment and accessories are
Edges are sharp. heavy.
Table 20: Roof Curbs (availability based on style)
Extended Curb (ADD for each section)
Fan
Style
MUA * * * * * * FR * * * * AM * * * * * * * VAV * * * * *
and
Burner
Inlet
Coil
Mix
BoxOAFilter*
Inlet
Plenum
Evap. Cooling Section
and
Transition
External
Fan
Motor
with Belt
Guard
*Curb add required only when an inlet plenum is ordered with an outside air filter section.
For pitched curbs, insulated curbs, w
ood nailers or
cub mounted vibration isolation, consult the factory. NOTE: Check the installation location to ensure
proper clearances to combustibles and clearance for access. Page 8, Section 3.
Place the curb on the roof in the position in which it will be installed. Check that the diagonal measurements are within 1/8"(3 mm) of each other. To ensure a weatherproof seal between the air handler and the curb, the curb must be level with no twist from end to end. Shim level as required and secure curb to roof deck using best building practices. The curb is self-flashing. Install roofing material as required.
41 of 154
Page 50
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
NOTE: Adapter shown for models 4024 through 4089 horizontal AM, FMB and MUA.
FIGURE 31: Roof Curb
42 of 154
Page 51
FIGURE 32: Roof Curb Installation
COUNTER FLASHING (BY OTHERS)
ROOFING (BY OTHERS)
CANT STRIP (BY OTHERS)
UNIT CURB ANGLE
¥ MODELS 4024-4049: 4 x 2 Sheetmetal Formed Channel ¥ MODELS 4054-4066: 6 x 2 Sheetmetal Formed Channel
CANT STRIP (BY OTHERS)
ROOFING (BY OTHERS)
COUNTER FLASHING (BY OTHERS)
ROOF INSULATION
BY CONTRACTOR
SILICONE CAULK
(BY OTHERS)
TYPICAL CURB INSTALLATION
ROOF CURB
CHANNEL
UNIT CURB ANGLE
¥ MODEL 4073: 3 x 3 x 3/16 Angle Iron ¥ MODELS 4080-4089: 4 x 3 x 1/4 Angle Iron
LAG BOLT
OPTIONAL
TYPICAL CURB INSTALLATION
1"
2"
4024-4049: 4" 4054-4066: 6"
ROOF INSULATION
BY CONTRACTOR
1"x4" NAILER
(BY OTHERS)
SILICONE CAULK
(BY OTHERS)
ROOF CURB
CHANNEL
1"x4" NAILER
(BY OTHERS)
DO NOT TWIST OR BEND FRAME
SECTION 8: ROOF C URB
43 of 154
Page 52
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
DETAIL 2
DETAIL 1
DETAIL 3
DETAIL 3
DETAIL 3
OVERHEAD PLANVIEW
SUPPLY AIR OR
INLET END
SIDE
SPLICE &
CROSSBRACE
12 BOLTS,
FLAT WASHERS,
LOCK WASHERS,
FLANGE NUTS
INTERMEDIATE
CROSSBRACE
8 BOLTS, FLAT WASHERS, LOCK WASHERS,
FLANGE NUTS
CORNER
CONNECTION
7 BOLTS,
FLAT WASHERS,
LOCK WASHERS,
FLANGE NUTS
1. Refer to the assembly drawings shipped with the curb.
2. Curb length can vary by options selected.
3. Verify overall assembly dimensions before roofing.
4. Curb material is 16 GA for models 4024 through 4049 and 14 GA for models 4054 through 4089.
5. All top corners to be flush and perpendicular.
6. All joints must be caulked.
NOTE: All top corners to be flush and perpendicular. All joints must be caulked.
FIGURE 33: Roof Curb Assembly with Brackets
44 of 154
Page 53
FIGURE 34: Duct Support Adapter
ASM SIZE A
NOTE: GASKET SPONGE REQUIRED ON TOP SIDE OF FLANGE PERIMETER. MATERIAL TO BE ALUMINIZED 20ga. STEEL
BOTTOM RETURN DUCT ADAPTER ASM
24 38.00 36 56.00 40 61.00 44 67.00 49 74.00 54 83.00 60 92.00 66 102.00 73 109.00 80 128.00 89
436126 436184
BOTTOM RETURN DUCT ADAPTER
436196 436208 436220 436232 436247 436259 436268 436277 436277
B
24.69C17.81D31.88E3.44F3.44G3.06
31.13 25.81 49.88 1.81 3.50
35.13 29.81 54.88 1.81 3.50
37.13 31.81 60.88 1.81 3.50
39.13 33.81 67.88 1.81 3.50
44.13 38.81 76.88 1.81 3.50
43.13 37.81 85.88 1.81 3.50
50.13 44.81 95.88 1.81 3.50
48.62 43.25 101.88 1.81 3.56 3.56
52.62 47.25 122.88 1.81 3.56 2.56
INLET SIDE
ASM SIZE A
24 38.00 36 56.00 40 61.00 44 67.00 49 74.00 54 83.00 60 92.00 66 102.00 73 109.00 80 128.00 89
436126 436184
BOTTOM DISCHARGE DUCT ADAPTER
436196 436208 436220 436232 436247 436259 436268 436277 436277
B
25.31C20.00D29.00E3.50F1.81G4.50
31.31 25.00 47.00 4.50 1.81 4.50
40.31 33.00 50.00 5.50 1.81 5.50
43.31 36.00 56.00 5.50 1.81
46.31 39.00 63.00 5.50 1.81
50.31 43.00 72.00 5.50 1.81
55.31 48.00 81.00 5.50 1.81
57.31 50.00 91.00 5.50 1.81
57.13 50.63 99.63 4.69 1.81 4.69
67.13 60.63 116.63 4.69 1.81 5.69
BOTTOM DISCHARGE DUCT ADAPTER ASM
INLET SIDE
(AM AND FMB ASSEMBLIES ONLY)
3.06
3.06
3.06
3.06
3.06
3.06
3.06
5.50
5.50
5.50
5.50
5.50
128.00 52.62 47.25 122.88 1.81 3.56 2.56 128.00 67.13 60.63 116.63 4.69 1.81 5.69
A (OD)
B (OD)
C (ID)
D (ID)
E (ID)
F (ID)
G (ID)
G (ID)
A (OD)
B (OD)
DETERMINED
BY INSTALLER
DETERMINED
BY INSTALLER
E (ID)
F (ID)
G (ID)
G (ID)
C (ID)
D (ID)
SECTION 8: ROOF C URB
45 of 154
Page 54
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Crush Hazard
Check blower assembly per maintenance section.
Lack of blower assembly maintenance can cause excessive vibration.
Excessive vibration can cause support failure.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Crush Hazard
Hanging hardware must support equipment weight.
Do not hang by lifting lugs.
Crush Hazard
Use proper lifting equip­ment and practices.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Falling Hazard
Use proper safety equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equipment.
Equipment and accessories are heavy.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
SECTION 9: INDOOR SUSPENSION MOUNTING - HORIZONTAL AIR HANDLER
9.1 Suspension Mounting Assembly and Instructions
Indoor suspension mounting is available for all models in horizontal orientation. Suspension mounts are shipped assembled. The exterior frame perimeter includes additional L channel. Holes in the L channel allow for threaded rod to be used for suspension. Threaded rod is provided by others. Minimum threaded rod size is ¾".
NOTE: Check to be sure all required components are present. If there are any missing, contact Rapid Engineering LLC or your RAPID
Once the suspension frame is secure, the air handler may be mounted. See Page 27, Section 6.1 for safe lifting practices.
46 of 154
®
independent distributor.
Page 55
FIGURE 35: Indoor Suspension
VIBRATION ISOLATORS WHEN SPECIFIED
SUPPORT RODS
AIR HANDLER
CONTROLS RIGHT
INLET END VIEW
APPROXIMATE GAS PIPE LOCATION
CENTER SUPPORTS
ROD SIZE­4036 – 4089 3/4" Ø 4024 5/8" Ø
INLET
G
G
CONTROLS RIGHT
BURNER SECTION
FAN
SECTION
Field Joint
Field Joint
(4054-4073 ONLY)
(4080-4089 ONLY)
PLAN VIEW
CONTROLS RIGHT SHOWN
CENTER SUPPORTS
ON 4040 TO 4089 ONLY
NOTES:
1. CONSULT FACTORY FOR DIMENSIONS WHEN USING A 3V4 OR 4" MANIFOLD.
2. ALL DIMENSIONS & WEIGHTS ARE SUBJECT TO CHANGE WITHOUT NOTICE & SHOULD NOT BE USED FOR CONSTRUCTION UNLESS CERTIFIED.
3. ACCESSORIES MAY VARY BY INDIVIDUAL ORDER. CONSULT FACTORY FOR ADDITIONAL INFORMATION.
4. FOR NUMBER OF SUPPORT RODS CONSULT FACTORY.
Model A B C D E F G 4024 109 40 4 5 103 - - 3 4036 120 58 63 114 - - 3 4040 130 63 68 124 64 60 3 4044 137 69 74 131 67 64 3 4049 140 76 81 134 70 64 3 4054 144 85 90 138 80 58 3 4060 154 94 99 148 84 64 3 4066 158 104 109 152 88 64 3 4073 163 112 117 157 88 69 3 4080 162 131 136 165 75 90 3 4089 168 131 136 171 81 90 3
SECTION 9: INDOOR S USPENSION MOUNTING - HORIZONTAL AIR HANDLER
47 of 154
Page 56
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 10: LEG MOUNTING
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Failure to follow these instructions can result in death, injury or property damage.
Vertical MUA, FR, AM and 4024-4049 VAV units require a quantity of four legs. Vertical 4054-4089 VAV units without an OA filter section require a quantity of six legs (all of the same height). Vertical 4054-4089 VAV units with an OA filter section require a quantity of six legs (four legs of the same height and two legs at a
height of 30" taller than the first four). Consult Factory if height of additional two legs exceed the standard leg offerings. Horizontal 4024-4049 require a minimum quantity of four legs. Horizontal 4054-4089 require a minimum quantity of eight legs. For every additional section (ie. mix box, coil, etc.) beyond the basic horizontal unit except for inlet hoods and outside air filter sections, an additional four legs must be added.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Equipment and accessories are heavy.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
48 of 154
Page 57
FIGURE 36: Assembling Legs for Horizontal Air Handlers
CURB ANGLE
A
AIR HANDLER
INTERMEDIATE BOTTOM PLATE (BOLTS TO 2 CORNER LEGS)
ACCESS
DOOR
1/2"x 1-5/8" SLOTTED HOLES
CORNER SUPPORT LEGS 4 - REQUIRED
CONTROLS
RIGHT
INTERMEDIATE SUPPORT LEGS REQUIRED ON ALL CURB ANGLE FIELD JOINTS (2 CORNER LEGS BOLTED TOGETHER)
CORNER BOTTOM PLATE
(BOLTS TO CORNER LEG)
A
FOR MODEL 4073-4089
(8) - 3/8 X 1" BOLTS (8) - 3/8 FLANGE NUTS (8) - 3/8 FLAT WASHERS
MANUFACTURER PROVIDES
FOR EACH LEG:
(12) - 3/8 X 1" BOLTS
FOR MODEL 4024-4066
(12) - 3/8 FLANGE NUTS (12) - 3/8 FLAT WASHERS
CURB ANGLE
ON UNIT
SECTION VIEW A-A
Models 4024-4066
HORIZONTAL LEG
NOTE: Leg mounts to underneath side of channel curb.
LEG
HEIGHT
Formed 10Ga.
Galvanized Channels
Model 4024-4049: 4"
Models 4054-4066: 6"
LEG TOP PLATE
A-A
CURB ANGLE
ON UNIT
SECTION
VIEW A-A
HORIZONTAL LEG
NOTE: Leg mounts to inside of curb angle. Allow top of leg to rest against curb angle before tightening bolts.
LEG
HEIGHT
Structural Angle
Model 4073: 3"
Models 4080/4089: 4"
NOTE: To shorten legs, consult factory.
Leg
Heights
in cm 24 61 36 91.4 48 121.9 60 152.4 72 182.9 84 213.4 96 243.8
SECTION 10: LEG MOUN TING
49 of 154
Page 58
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Drawing #50010144
LEG
OPTIONAL SECTION (s)
RAIN SKIRT
(3 PCS.)
NOTE: Rain Skirt With Outdoor Air Handlers Only
TOP AND BOTTOM PLATES BOLT ON OUTSIDE OF LEG
NOTE -
(12) - 3/8 X 1" BOLTS
(8) - 3/8 FLANGE NUTS
FOR EACH LEG
(12) - 3/8 WASHERS
DIMENSION A
84"
DIM. A
STANDARD LEG SIZES
60"
72"
48"
36"
24"
96"
RAPID PROVIDES
SHEETMETAL CHANNEL OR ANGLE IRON FRAME TOWARD BUILDING
NOTE: RAIN SKIRT WITH OUTDOOR AIR
HANDLERS ONLY CAUTION, SHORTENING THE LEGS MAY RESULT IN HIGH INLET AIR VELOCITIES, CONSULT THE FACTORY
APPLY CAULKING ON INSIDE FEATHER EDGE OF RAIN SKIRT BEFORE INSTALLING, USING #10 X
RUBBER CAP TEK SCREWS, SCREW TO THE SIDES OF AIR HANDLER, REMOVE SCREW IN ROOF BEFORE INSTALLING RAIN SKIRT TO ROOF PANEL OF AIR HANDLER, RAIN GUTTER SHOULD BE FLUSH WITH INLET OF UNIT AS ILLUSTRATED.
RAIN SKIRT
UPRIGHT LEG
AIR HANDLER
20540 SCR,TEK #10 X 3/4 W/WASH
FIGURE 37: Assembly Legs and Rainskirt for Upright Air Handlers
50 of 154
Page 59
SECTION 11: FILTER SECTION
NOTE: 1) CONTRACTOR/INSTALLER MUST MAKE
APPROPRIATE ALLOWANCES FOR DUCT CONNECTIONS.
2) SUPPORT LEG IS REQUIRED WHEN A FILTER SECTION AND INLET HOOD ARE ORDERED.
3) SUPPORT LEG IS PROVIDED FOR USE WITH STANDARD 19" (50 cm) ROOF CURB. SUPPORT LEG FOR USE WITH STANDARD 46" (116.8 cm) LEGS PROVIDED BY OTHERS.
SECTION 11: FILTER S ECTION
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Cut/Pinch Hazard
Wear protective gear during installation, operation and
service. Equipment and accessories are
Edges are sharp. heavy.
Failure to follow these instructions can result in death, injury or property damage.
All filter sections are shipped assembled. Models 4024-4049 ship attached to the base unit. Models 4054­4089 shipped loose and required field assembly to base unit.
NOTE: Check to be sure that all required components are present. If any are missing, contact Rapid
®
Engineering LLC or your RAPID
independent distributor.
FIGURE 38: Filter Section Support Assembly
51 of 154
Page 60
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Roof Tape
Field Joint
Properly Caulk
Notes:
(1) Failure to properly caulk the field joints will allow water to enter the air handler (2) All parts mounted to inlet end to be attached with 3/8" bolt and flat washers. (3) All other parts bolted together with 5/16" bolts, flat washer, and lock nut. (4) All dimensions & weights are subject to change without notice & should not be used for construction unless certified.
Typ. Assembly
Nut Inserts
Rapid recommends assembling
inlet hood parts to the air
handler in the following
sequence by item #:
5, 6, 11, 4, 2, 1, 10
SECTION 12: INLET HOODS
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Cut/Pinch Hazard
Wear protective gear during installation, operation and
service. Equipment and accessories are
Edges are sharp. heavy.
Failure to follow these instructions can result in death, injury or property damage.
Inlet hoods are shipped unassembled and must be assembled prior to installation. NOTE: Check to be sure that all required components are present. If any are missing, contact Rapid Engineering LLC or your RAPID
®
independent distributor.
12.1 Inlet Hood Assembly FIGURE 39: Inlet Hood without Filters (4024-4049)
52 of 154
Page 61
FIGURE 40: Inlet Hood without Filters (4054-4089)
Roof Tape
Field Joint
Properly Caulk
Notes:
(1) Failure to properly caulk the field joints will allow water to enter the air handler (2) All parts mounted to inlet end to be attached with 3/8" bolt and flat washers. (3) All other parts bolted together with 5/16" bolts, flat washer, and lock nut. (4) All dimensions & weights are subject to change without notice & should not be used for construction unless certified.
Typ. Assembly
Nut Inserts
Rapid recommends assembling
inlet hood parts to the air
handler in the following
sequence by item #:
8, 9, 16, 7, 5, 6, 4, 2, 1, 10, 11, 12
10
10
11
FILTER RAILS
TOP FILTER RAIL
DescriptionDetail
12
BOTTOM PAN & RAIL
13
L INLET HOOD GUTTER
14
15
FILTER CLIPS
16
TEK SCREWS
17
RAIL HARDWARE
18
19
FILTER SPACERS
20
R INLET HOOD GUTTER
ISOMETRIC VIEW
FILTER SPACER REQUIRED ON SOME MODELS
11
12
13
14
15
16
FILTERS
40600672
4060067381
QtyASM/Part #
40600674 1
40600674 1
40600675 1
20900 4
20541 30
20699 14
20538 14
--
20596 8
MODEL 36
40620618
4062061981
QtyASM/Part #
40620620 1
40620621 1
40620621 1
20900 8
20541 30
20699 14
20538 14
--
20596 4
MODEL 40
40600641
4060064281
QtyASM/Part #
40600643 1
40600644 1
40600644 1
20900 8
20541 30
20699 12
20538 12
--
09701 12
MODEL 44
40504206-7
40504206-8101
QtyASM/Part #
40504206-9 1
40504206-12 1
40504206-12 1
20900 10
20541 50
20699 16
20538 16
40504206 5
20596 20
MODEL 49
40620418-19
40620418-20121
QtyASM/Part #
40620418-21 1
40620418-22 1
40620418-22 1
20900 12
20541 50
20699 22
20538 22
40620418-23 1
20596 24
MODEL 54
40630445
40630446121
QtyASM/Part #
40630447 1
40630448 1
40630449 1
20900 12
20541 50
20699 24
20538 24
--
20596 30
MODEL 60
437345
437346121
QtyASM/Part #
437347 1
437348 1
437349 1
20900 12
20541 50
20699 20
20538 20
--
20596 12
MODEL 66
40501125-7
40501125-851
QtyASM/Part #
40501125-9 1
40501125-12 1
40501125-12 1
20900 12
20541 50
20699 20
20538 20
-1
20596 36
MODEL 73
40600529-12
40600529-13141
QtyASM/Part #
40600529-14 1
40600529-15 1
40600529-16 1
20900 14
20541 50
20699 30
20538 30
-1
77500 49
MODEL 80/89
EXPLODED VIEW
ASSEMBLY INSTRUCTIONS
· ASSEMBLE INLET HOOD PARTS LISTED IN EXPLODED VIEW #7,8,9,14 TO AIR HANDLER WITH
3 8
" FLAT
WASHERS AND
3 8
X 1 BOLTS.
· BUTYL ROPE CAULKING IS SUPPLIED AND SHOULD BE APPLIED BET WEEN EACH SIDE AND ROOF PANELS TO INSURE A WATER TIGHT SEAL, 3" WIDE ZIP TAPE IS SUPPLIED AND SHOULD BE USED ACROSS EACH ROOF JOINT AS SHOWN.
· BOLT ITEMS #4,5,6 WITH
5
16
" HARDWARE TO ITEM #7,8,9 PREVIOUS MOUNTED.
· ITEMS #1,2 & 3 ARE THEN BOLTED TO ITEMS #4,5 & 6.
· INTERIOR GUSSET ITEMS ARE MOUNTED ON THE INSIDE OF HOOD TO SIDE WALL PANELS #5 & 6 AND #4 ROOF PANEL.
· HORIZONTAL BRACE IS MOUNTED TO #5 & 6 ON INTERIOR OF HOOD FOR CENTER SUPPORT.
· ITEM #13 & 14 RAIN GUT TERS MOUNT TO TAPERED EDGE OF HOOD, MOUNTING FLANGE TO THE INSIDE OF HOOD AND 2" FLANGE WITH BE TO THE OUTSIDE AS SHOWN.
· ITEM #11 TOP FILTER RAIL MOUNTS TO ROOF OF INLET HOOD ITEM #1 WITH ITEM #16 TEK SCREWS.
· ITEMS #10 DUAL FILTER RAILS MOUNT TO ITEMS #13 & 14 WITH #10-24 HARDWARE.
· ITEMS #15 FILTER CLIP RETAINER ARE FASTENED TO ITEMS #13 & #14 WITH TEK SCREWS.
· SOME MODELS REQUIRE FILTER SPACER ITEM #19 TO COMPLETE ROW OF FILTERS.
7
8
9
5
6
4
1
2
3
14
10
14
13
13
ITEM #11 TEK SCREWS TO THE OUTSIDE FLANGE OF ITEM #1
FILTER RAILS ITEMS #10 MOUNT TO ITEMS #13 & 14 WITH #10-24 HARDWARE
SOME MODELS REQUIRE FILTER SPACER #19 (SEE CUTTING LIST)
17
FILTER CLIPS ARE TEK SCREWED TO THE OUTSIDE FLANGE OF ITEM #13 & #14 ON BOTH SIDE OF HOOD.
3" WIDE ZIP TAPE, SUPPLIED FOR EACH ROOF JOINT.
EACH VERTICAL AND HORIZONTAL ROOF JOINT SHOULD BE CAULKED WITH BUTYL TAPE THAT IS SUPPLIED WITH INLET HOOD, TO INSURE A WATER TIGHT SEAL.
17 18
ASSEMBLY INSTRUCTIONS
· STANDARD INLET HOOD INSTRUCTION #40004504 (PG.17) FOR INSTRUCTIONS ON CAULKING PRIOR TO ASSEMBLY.
· REFER TO ASSEMBLY DRAWING PACKAGED WITH INLET HOOD.
· INLET HOODS (4024-4049) ARE 6-PIECES & (4054-4089) 12-PIECES
· INLET HOODS 4054-4089 HAVE INTERNAL CORNER BRACES AND HORIZONTAL CROSS MEMBERS.
21
66512 4 66512 8 - - - - - - - - 66512 18 - - - -
40630297
4063029841
QtyASM/Part #
40630299 1
40630301 1
40630300 1
20900 4
20541 10
20699 8
20538 8
40630302 4
20596 4
MODEL 24
--
20 21
FILTERS
RAIL HARDWARE
19
40600671 40620617 40600640 40504207 40620417 40630444 40437344 40501124 -40630296
Models
Assembly Reference
INLET HOOD FILTER HARDWARE, HARDWARE FOR INLET HOOD ASSEMBLY IS NOT LISTED HERE.
20 21
19
80/89 EXAMPLE
BOTTOM PAN VIEW
12
17
14
8
GUSSETS
SECTION 12: INLET H OODS
FIGURE 41: Inlet Hood with Permanent Filters
53 of 154
Page 62
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
C
B
DETAIL B: SCALE: 4x
A
(2) braces front & back on models 4060 thru 4089
(1) brace front & back on models 4024 thru 4054
1
3
6
8
5
4
2
2
1
3
4 5
6
8
Item 4 flush with Inlet Hood drip edge.
C
DETAIL A: SCALE: 4x
2
DETAIL C: SCALE: 2x
Models 4080-4089 only
Center Channel pieces
B
A
Seal perimeter of Inlet Hood and
Moisture Limiter 100% w/ caulking
Tek screw sides & top to Inlet Hood flanges
On models 4080 & 4089, moisture limited media is stacked two
rows high and separated with sheetmetal channels pop riveted together.
On all other models, moisture limited media is installed with full-lenth rows.
INLET HOOD
Assembly Instructions:
1. Pop rivet items #1 and #3 together and items #4 and #5 together and center channel piece (see detail C) for model 4080-4089 only.
2. If inlet hood is currently mounted, remove corner brackets. Bolt floor (items #1 and #3) to bottom of the inlet frame and sides of hood.
3. Tek screw one side to inlet hood rain gutter and to floor.
4. Pop rivet back supports (item #6) to inlet hood rain gutter using notches in side as a guide.
5. Tek screw top (items #4 and #5) to top lip of hood and to sides.
6. Install Moisture Limiters media.
7. Tek screw the other side to inlet hood rain gutter and to floor.
8. Tek screw #8 moisture limiter media to front of inlet hood.
9. Seal all joints of inlet hood and perimeter of mist eliminator to inlet hood 100% with caulking.
NOTE: 1. Inlet hood framing side (item #2) not shown.
2. All dimensions are in inches.
Model 4024 4036 4040 4044 4049 4054 4060 4066 4073 4080/4089
A 40 58 63 69 76 85 94 104 112 131 B 48 72 84 84 84 96 94 96 96 112
C
35
7
/8831/2955/8993/41045/81191/
2
126
123
1
/21231/21403/
4
Quantity of
Media Pieces
355667899 22
FIGURE 42: Inlet Hood with Moisture Limiter
54 of 154
Page 63
SECTION 13: SERVICE PLATFORM
Crush Hazard
Use proper lifting equipment and practices.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Equipment and accessories are heavy.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
SERVICE PLATFORM FRAME
SUPPORT CHANNEL
BURNER SECTION
3/8" BOLTS
3/8" BOLTS
3/4" NUTS
¥ MODEL 4073/4089 ANGLE IRON ¥ MODEL 4024/4066 SHTMTL CHANNEL
RAILING
CONTROLS
Side Railing Field Assembly
ACCESS SIDE RAILING (SIZES 4049 - 4089)
TEK SCREW IN FIELD.
FRONT
GRATING
Two Front Rails on 4080/4089 Models
2
4
8
9
1
3
5
6
10
ACCESS
CHAINS
SIDE RAILING 4 PCS ASSEMBLY
7
OPTIONAL LADDER
(Available from manufacturer)
Assemble in the following order:
1. Bolt support channels to air handler with four ¾” nuts.
2. Bolt service platform frame between support channels with eight 3/8” x 1” bolts and fig nuts.
3. Lay grating inside service platform frame.
4. Bolt from railing to service platform with four 3/8” x 1” bolts and fig nuts.
5. Screw access railing to support channels with three #14 self-tapping screws.
6. Tek screw access railing to air handler roof.
7. Pre-assemble side railing (4 pieces) with four 3/8” x 1” bolts and fig nuts.
8. Bolt side railing to front railing with two 3/8” x 1” bolts and fig nuts.
9. Screw side railing to angle iron frame with three #14 self-tapping screws.
10. Attach safety chains between access side railing and front railing.
SECTION 13: SERVICE PLATFORM
13.1 Service Platform
Ladders are available as an additional accessory for service platforms. Ladders are available with or without cages at various heights. Service Platforms are available for use with horizontal or vertical units.
FIGURE 43: Service Platform for an Vertical Air Handler
55 of 154
Page 64
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
CONTROLS
RIGHT
3/8" BOLT
FIELD JOINT WHEN REQUIRED
SERVICE PLATFORM
SUPPORT CHANNEL
3/8" BOLTS
SAFETY CHAIN
FRONT RAILING
SWAY TAB
SUPPORT RODS
DOUBLE NUTTED
LIFTING EYE
AIR HANDLER
SUPPORT CHANNEL
ACCESS SIDE RAILING
SIDE RAILING
FIELD ASSEMBLY
HOLES FOR 3/8" BOLTS
SUPPORT ROD HOLES
(by others)
TEK SCREW IN FIELD.
SPLICE LOCATED ON
4044-4089 MODELS ONLY
SIDE RAILING 4 PCS ASSEMBLY
FRONT
RAILING
INLET VIEW
RIGHT CONTROLS
Detail A: Models 4073 - 4089
Detail A: Models 4024 - 4066
A
FIGURE 44: Service Platform for a Horizontal Air Handler
56 of 154
Page 65
SECTION 14: DISCHARGE ACCESSORIES
SECTION 14: DISCHARGE ACCESSORIES
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Failure to follow these instructions can result in death, injury or property damage.
14.1 One-Way, Three-Way and Four-Way Discharge Head Installation
All discharge heads are shipped assembled. The discharge head is designed for mounting to the face of the air handler (covering the supply air opening) or to an interior wall. All discharge heads must be field supported (by others). The discharge head has four outward-turned flanges. If the discharge head is to be installed to the face of the air handler, install hardware (provided by others) on all four sides of the discharge head.
Discharge heads can be installed on horizontal or vertical air handlers. To install the discharge head on an interior wall, drill holes in the flanges on all four sides of the discharge heads to accommodate lag bolts (supplied by others). Sheet metal (supplied by others) may be required.
Consult factory for detailed installation instructions based on unit orientation and discharge location.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Equipment and accessories are heavy.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
57 of 154
Page 66
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
(SUPPLY AIR AND
RETURN AIR DUCT
SLEEVES AVAILABLE
FROM MANUFACTURER)
DETAIL A
DETAIL C
AIR HANDLER
DETAIL B
TYPICAL ASSEMBLY
2"
SELF TAPPING
SCREWS
ALTERNATE
SUPPORT BY
OTHERS
SUPPORT
BY OTHERS
INLET
DETAIL A
DETAIL B
DETAIL C
MODELS 4024-4089
AIR HANDLER HOUSING
RETURN AIR SLEEVE
CAULK JOINT
AFTER ASSEMBLY
AIR HANDLER HOUSING
SUPPLY AIR SLEEVE
3-3/4" DISCHARGE
COLLAR
SELF-TAPPING
SCREWS
CAULK JOINT PRIOR
TO ASSEMBLY
CAULK JOINT PRIOR
TO ASSEMBLY
SUPPLY AIR SLEEVE
DISCHARGE
HEAD
1/4-20 x 1" BOLTS (12" O.C.)
FIGURE 45: Vertical Air Handler with Duct Sleeves and Discharge Head
58 of 154
Page 67
FIGURE 46: One-Way Discharge Head
CONTROLS
RIGHT
CURB
ANGLE
ACCESS
DOOR
AIR HANDLER
DISCHARGE
HEAD
1-WAY
DISCHARGE
HEAD
1-WAY
INLET
AIR HANDLER
DISCHARGE
HEAD
1-WAY
INLET
A
G
D
G
C
F
30”
E
DETAIL A
TYPICAL ASSEMBLY
2”
SELF TAPPING
SCREWS
AIR HANDLER
HOUSING
DISCHARGE
HEAD
END VIEW
RIGHT SIDE VIEW
Model A C D E F G
4024 40 24.25 33.25 2 40 3.5 4036 58 29.25 51.25 3 58 3.5 4040 63 37.25 54.25 4 63 4.5 4044 69 40.25 60.25 4 69 4.5 4049 76 43.25 67.25 4 76 4.5 4054 85 47.25 76.25 4 85 4.5 4060 94 52.25 85.25 4 94 4.5 4066 104 54.25 95.25 4 96 4.5 4073 112 54.25 103.25 4 96 4.5 4080 131 64.25 120.25 4 112 5.5 4089 131 64.25 120.25 4 112 5.5
SECTION 14: DISCHARGE ACCESSORIES
59 of 154
Page 68
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
F
D
(TYPICAL)
B
A
C
E
G
G
PLAN VIEW
FRONT VIEW
SIDE VIEW
Model A B C D E F G
4024 44 25 24.4 14 20.3 29.3 2.1 4036 62 30 29.4 22 25.3 47.3 2.1 4040 65 31 37.4 23 33.3 50.3 2.1 4044 71 32 40.4 26 36.3 56.3 2.1 4049 78 34 43.4 28 39.3 63.3 2.1 4054 82 37 47.4 32 43.3 72.3 2.1 4060 96 40 52.4 36 48.3 81.3 2.1 4066 106 43 54.4 40 50.3 91.3 2.1 4073 114 45 54.4 40 50.3 99.3 2.1 4080 131 48 60.4 50 60.3 116.3 2.1 4089 131 48 60.4 50 60.3 116.3 2.1
FIGURE 47: Three-Way Discharge Head
60 of 154
Page 69
FIGURE 48: Four-Way Discharge Head
E
INLET
AIR HANDLER
C
ROOF CURB
A
ACCESS DOOR
CONTROLS
RIGHT
AIR HANDLER DUCT NOT SUPPLIED BY RAPID ENGINEERING LLC.
ROOF
B
D
F
F
F F
AIR HANDLER
12"
TYPICAL
12"
TYPICAL
RIGHT SIDE VIEW END VIEW
Model A B C D E F
4024 40 40 46 24.3 33.3 2 4036 58 58 46 29.3 51.3 2 4040 63 63 46 37.3 54.3 2 4044 69 69 46 40.3 60.3 2 4049 76 76 46 43.3 67.3 2 4054 85 85 58 47.3 76.3 2 4060 94 94 58 52.3 85.3 2 4066 96 104 58 54.3 95.3 2 4073 96 112 58 54.3 103.3 2 4080 112 131 58 64.3 120.3 2 4089 112 131 58 64.3 120.3 2
SECTION 14: DISCHARGE ACCESSORIES
61 of 154
Page 70
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Model A C D E F G H J K Disch ID Weight (lbs)
4024 40 20 1/4 24 1/4 3 7/8 40 5 3/8 19 47 30 24 x 29 75 4036 58 25 1/4 32 1/4 4 7/8 58 5 3/8 26 83 48 32 x 47 105 4040 63 33 1/4 35 1/4 5 7/8 63 6 3/8 31 73 39 35 x 50 140 4044 69 36 1/4 35 1/4 5 7/8 69 6 3/8 33 73 36 35 x 56 180 4049 76 39 1/4 40 1/4 5 7/8 76 6 3/8 33 78 36 40 x 63 190 4054 85 43 1/4 40 1/4 5 7/8 85 6 3/8 39 89 39 40 x 72 210 4060 94 48 1/4 43 1/4 5 7/8 94 6 3/8 44 92 39 43 x 81 250 4066 104 50 1/4 43 1/4 5 7/8 96 6 3/8 44 97 37 43 x 91 290 4073 112 50 1/4 43 1/4 5 7/8 96 6 3/8 41 136 64 43 x 99 380 4080 131 60 1/4 43 1/4 5 7/8 112 7 3/8 44 121 44 43 x 116 480 4089 131 60 1/4 43 1/4 5 7/8 112 7 3/8 44 145 63 43 x 116 480
FIGURE 49: 120° Discharge Head Horizontal Bottom Supply Air
62 of 154
Page 71
SECTION 14: DISCHARGE ACCESSORIES
Model A B C D
E
(min.)E(max.)
Weight
(lbs) 4024 42 54 3 - 25 38 80 4036 47 72 3 - 36 54 110 4040 55 75 3 - 42 64 130 4044 58 81 3 - 46 70 140 4049 61 88 3 - 50 75 160 4054 65 97 3 - 56 84 180 4060 70 106 3 53 64 96 230 4066 72 116 3 58 70 105 250 4073 72 124 3 62 75 112 260 4080 82 140 4 70 88 132 330 4089 82 140 4 70 88 132 330
14.2 Splash Plate Installation
The splash plate is designed to hang, supported by suspension rods (rods provided by others) directly below the bottom discharge opening of a horizontal air handler. The center point of the splash plate must be located at the center point of the discharge opening and be positioned below the air handler within the range of dimensions show below as E (min) & E (max.). For model sizes 60-89, center support rods will be required (see illustration below).
FIGURE 50: Discharge Plate
RIGHT SIDE VIEW
FAN SECTION
NOTE: Be sure to inclu de provisions in the structure suspending the discharge plate that will prevent sway/movement of the plate when the supply fan is in operation.
To attach all of the hanger rods to the splash plate, start by threading a flanged nut onto each hanger rod. Then, slip each hanger rod down through a hole located in each corner of the splash plate. Next, feed a flanged nut onto the rod below the splash plate. Adjusting the nuts will level the splash plate. Torque hardware after leveling.
SUPPORT RODS
(BY OTHERS)
DISCHARGE PLATE
A
C
CENTER HOLES ON 60 THRU 89
13
/16” HOLES
D
E
B
2” TYPICAL
D
2”
1¾” TYPICAL
4 CORNERS
63 of 154
Page 72
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
“D” HOLE DIA
SUPPORT ROD
TO STEEL-WORK
BY OTHERS
ISOLATOR
SUPPORT ROD
TO UNIT
BY OTHERS
L
A
H
NOTE: ALL DIMENSIONS AND WEIGHTS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND SHOULD NOT BE USED FOR CONSTRUCTION UNLESS CERTIFIED.
TYPE
L
WH
A
D
RH2 RH3
RH4
3 3 3/4 4 1/2
2 1/4 3 1/4
4
4 1/4 6 1/4
8 3/16
1 3/8 2 2
11/16 7/8
13/16
ISOLATORS REQ’D FOR
AIR HANDLER W/
SERVICE PLATFORM
AIR HANDLER (AM)
W/ FILTER MIX BOX
AIR HANDLER (AM) W/
FILTER MIX BOX &
SERVICE PLATFORM
AIR HANDLER
SIZE
VENDOR #
4024 4036 4040 4044 4049 4054 4060 4066 4073 4080 4089
RH – 2, GRAY RH – 3, GREEN RH – 3, GREEN RH – 3, GRAY RH – 3, GRAY RH – 4, GREEN
RH – 4, GREEN RH – 4, GREEN RH – 4, GREEN RH – 4, GREEN
RH – 4, GREEN
4 4 4 4 4 6 6 6 6 6 6
6 6 9 9 9 9 9 9 9 9 9
6 6 6 6 6 8 8 8 8 8 8
9 9 12 12 12 12 12 12 12 12 12
29875 20888 20888 20817 20817 46212 46212 46212 46212 46212 46212
SECTION 15: VIBRATION ISOLATION
WARNING
Crush Hazard
Use proper lifting equipment and practices.
Failure to follow these instructions can result in death, injury or property damage.
FIGURE 51: Suspended
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
Severe Injury Hazard
Use proper lifting practices and equip­ment.
Equipment and accessories are heavy.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
64 of 154
Page 73
FIGURE 52: Curb Mounted
Roof Curb
Roof Curb
SECTION 15: VIBRATION I SOLATION
65 of 154
Page 74
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
NOTE: ALL DIMENSIONS AND WEIGHTS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND SHOULD NOT BE USED FOR CONSTRUCTION UNLESS CERTIFIED.
TYPE
AB
CD
E
H R – 3 R – 4
3 3/8 4 1/4
5 1/2 6 1/2
4 1/8
5
9/16
9/16
1/2 5/8
1 3/4
1 3/4
H
B
C
D = DIA.
2 PL.
E = NC TAP
A
ISOLATORS
REQ’D FOR
MODEL
VENDOR #
AIR HANDLER
AIR HANDLER
(AM) W/ FILTER
4024 R – 3, RED
R – 3, GREEN R – 3, GREEN R – 3, GRAY R – 3, GRAY R – 4, BLACK R – 4, BLACK R – 4, BLACK R – 4, RED R – 4, RED R – 4, RED
4036 4040 4044 4049 4054 4060 4066
4073 4080 4089
4 4 4 4 4 6 6 6 6 6 6
6 6 6 6 6 8 8 8 8 8 8
FIGURE 53: Platform Mounting on Vibration Isolators
66 of 154
Page 75
FIGURE 54: Vibration Isolation Platform Locations
A2
NOTE: ALL DIMENSIONS AND WEIGHTS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND SHOULD NOT BE USED FOR CONSTRUCTION UNLESS CERTIFIED.
NOTE: FOR MUA, EXCLUDE MIX BOX
MODEL
A2
BC EFG
HD
A1
H
H
4024 4036 4040 4044 4049 4054 4060 4066 4073 4080 4089
171 186 198 207 212 221 231 242 247 265 271
40 58 63 69 76 85 94
104 112
131 131
A1
109 120 130 137 140 144 154 158 163 171 177
103 114 124 131 134 138 148 152 157 165 171
3 3 3 3 3 3 3 3 3 3 3
62 66 68 70 72 77 77 84 84 94 94
58
-
-
-
-
-
-
-
-
-
-
64 64
69 90 90
80 84 88
88 75 81
37 3/8 55 3/8 60 3/8 66 3/8 73 3/8 82 3/8 91 3/8 101 3/8 114 1/2 133 1/2 133 1/2
SEC A – A
END VIEW
VIBRATION ISOLATORS
AIR HANDLER
CONTROLS
RIGHT
APPROXIMATE GAS PIPE LOCATION
INLET
SECTION VIEW A – ASECTION VIEW A – A
MODELS 4024 – 4066
MODELS 4073 – 4089
PLAN VIEW
CONTROLS RIGHT SHOWN
CENTER ISOLATOR ON 4054 – 4089 ONLY
CONTROLS
RIGHT
MIX–BOX SECTION
BURNER
SECTION
(4054–4073 ONLY)
Field Joint
Field Joint
(4080 – 4089 ONLY)
FAN
SECTION
B
G
F
E
D
C
SECTION 15: VIBRATION I SOLATION
67 of 154
Page 76
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 16: COOLING SPECIFICATIONS
16.1 Evaporative Cooling Table 21: Formulas
Formulas
1 Leaving Dry Bulb = ODB – [SE* x (ODB - OWB)]
Leaving Wet Bulb = Entering Wet Bulb (actually, it’s slightly less
2
than the entering wet bulb, but is normally considered equal.) 3Wet Bulb Depression = ODB – OWB 4Evaporation Rate (GPH) = CFM x WBD x SE/8050 5 Bleed-off Rate = approximately 20% of evaporation rate* 6Recirculation Rate = approximately 3 times evaporation rate*
* Bleed-off and recirculation rates will vary with locale, water quality and chemical treatment program. These values are only for approximation.
NOTE: Refer to saturation efficiency table below.
Table 23: Evaporation Rate
Wet Bulb
Depression (°F)
5 0.50 0.51 0.52 0.53 0.55 0.56 0.57 0.58 0.60 0.61 10 0 . 9 9 1. 0 2 1.0 4 1. 0 7 1. 0 9 1. 1 2 1.1 4 1. 1 7 1. 1 9 1.2 2 15 1. 4 9 1.5 3 1.5 6 1.6 0 1.6 4 1.6 8 1. 7 1 1. 7 5 1. 7 9 1. 8 3 20 1.99 2.04 2.09 2.14 2.19 2.23 2.28 2.33 2.38 2.43 25 2.48 2.55 2.61 2.67 2.73 2.79 2.86 2.92 2.98 3.04 30 2.98 3.05 3.13 3.20 3.28 3.35 3.43 3.50 3.58 3.65 35 3.48 3.56 3.65 3.74 3.82 3.91 4.00 4.08 4.17 4.26 40 3.97 4.07 4.17 4.27 4.37 4.47 4.57 4.67 4.77 4.87 45 4.47 4.58 4.69 4.80 4.92 5.03 5.14 5.25 5.36 5.48
0.800.820.840.860.88 0.90 0.92 0.94 0.96 0.98
Gallons per Hour (GPH) Per 1,000 Cubic Feet per Minute (CFM) at Stated Saturation Efficiency
Table 22: Abbreviations
Abbreviations
CFM Cubic Feet Per Minute GPH Gallons Per Hour IDB Indoor (Design) Dry Bulb Temperature LDB Leaving Dry Bulb Temperature LWB Leaving Wet Bulb Temperature ODB Outdoor (Design) Dry Bulb Temperature OWB Outdoor (Design) Wet Bulb Temperature SE Saturation Efficiency of the Evaporative Media WBD Wet Bulb Depression
• Heat of vaporization = 1043 BTU/lb
• Weight of water = 8.34 lb./Gallon
• GPH = CFM x WBD x SE x 1.08/1043/8.34 = CFM x WBD x SE/8050
Table 24: Suggested Air Changes Per Hour (Air Change Method)
Leaving Air
Tem perature
(°F DB)
78° 20° 30 - 60 76° - 78° 15° - 20° 20 - 40 74° - 76° 10° - 15° 15 - 30 72° - 74° 5° - 15° 12 - 20
< 72° < 10° 10 - 15
Indoor Air
Temperature Above
Ambient (°F)*
Air Changes/Hour**
* For existing buildings: Average amount indoor temperature exceeds ambient outdoor temperature when evaporative cooling is not in use.
** Experience has shown that significant benefit can be achieved with 10-15 Air Changes per Hour (AC/ Hr) through the lowest 12' of the facility. For a 24'
Table 25: Saturation Efficiency at Stated Media Depth
Airflow
Feet per
Minute (FPM)
400 0.71 0.81 0.90 0.98 0.99 500 0.68 0.79 0.89 0.98 0.99 600 0.66 0.77 0.88 0.97 0.99 700 0.64 0.75 0.87 0.97 0.98
Table 26: Static Pressure Drop (in wc) at Stated Media Depth
Airflow
Feet per
Minute (FPM)
400 0.06 0.09 0.14 0.19 0.24 500 0.09 0.14 0.21 0.30 0.39 600 0.13 0.20 0.30 0.42 0.55 700 0.23 0.31 0.44 0.62 0.80
high building, this would mean 5-6 Air Changes per Hour (AC/Hr) for the entire volume. This will v application.
ary by
NOTE: Moisture limiter pressure drop is added for face velocities greater than 600 Feet per Minute (FPM). Rapid Engineering LLC's standard media thickness equals 12".
6" 8"12"18" 24"
6" 8"12"18" 24"
68 of 154
Page 77
SECTION 17: DUCT CONSIDERATIONS
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Falling Hazard
Use proper safety equipment and prac­tices to avoid falling.
WARNING
Failure to follow these instructions can result
in death, injury or property damage.
The air handler has been designed to operate at the specific air volume and external static pressure that was originally specified. Static pressure is increased by any additional components that are added to the air handler (i.e. inlet hood, filter section, dampers, ductwork, discharge heads, etc) Additional static pressure beyond original intention (or time of order) will affect the performance of the air handler and reduce the air volume that can be delivered. Proper engineering methods need to be employed when calculating duct and component static pressure (i.e. 2009 ASHRAE Handbook - Fundamentals, Chapter 21). The system ductwork must comply with Sheet Metal and Air Conditioning Contractors Nationals Association (SMACNA) or any other recognized standards. As a general rule, all ducting should have a straight run of at least 3 duct diameters immediately before and after the air handlers mechanical accessories. No duct fittings, elbows or transitions with restrictions can be placed within 3 duct diameters.
SECTION 17: DUCT C ONSIDERATIONS
The air handler is not designed to support the weight of ductwork. Ductwork must be constructed in a fashion that is self-supporting. Ductwork should be straight, elbows should be minimal and any transitions should be gradual. Depending on the options ordered with the air handler, flanges (either external or internal) may be provided to facilitate connection of ductwork. In cases where flanges are not provided, flat surfaces on the exterior skin of the air handler are provided to facilitate connection of ductwork. Neither the flanges nor exterior skin of the air handler are capable of supporting the load of the ductwork. Ductwork support must come from the structure itself that the air handler is serv is recommended that ductwork be supported every 6 ft (1.8 m) for ductwork that has a cross section of 10 ft (3 m) or less and every 4 ft (1.2 m) for ductwork which has a cross section of greater than 10 ft (3 m). On vertical runs, it is recommended that ductwork be supported every 10 ft (3.0 m). On both cases, supporting members should be sized to carry the weight load.
17.1 Inlet Air Duct
Inlet duct work height and width must be no smaller than the air handler inlet height and width and supply only uncontaminated air to the air handler. (See Page 10, Section 5 for return air dimensions).
17.2 Return Air Duct
Return air duct work height and width must be no smaller than the air handler return air opening height and width. (See Page 10, Section 5 for return air dimensions).
17.3 Supply Air Duct Work
Supply air duct work sizes sho the application requirements of the system. Supply air ductwork must be smaller than supply air opening. See Page 10, Section 5 for dimensions.
icing. On horizontal runs, it
uld be determined by
Duct diameter for round ducts (in inches):
Dh = d
Duct diameter for rectangular d
Dh:diameter d:round duct inside diameter
Dh = (2*H*W)/(H+W)
Dh:diameter H:rectangular duct inside height W:rectangular duct inside width
ucts (in inches):
69 of 154
Page 78
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
WARNING
Explosion Hazard
Leak test all components of gas piping before operation.
Gas can leak if piping is not installed properly.
Do not high pressure test gas piping with air handler connected.
Failure to follow these instructions can result in death, injury or property damage.
SECTION 18: GAS PIPING
Minimum gas pressure as indicated on data plate must be measured with the burner operating in high fire.
Minimum inlet gas pressure is determined by gas train size and BTU/h rating.
18.1 Gas Manifolds
All gas piping to the air handler must comply with:
United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision, Natural Gas and Propane Installation Code.
The air handlers are available with three gas manifold options.
• American National Standards Institute (ANSI) compliant manifold: (
•Factory Mutual (FM)-compliant manifold: (
See Page 72, Figure 56
•XL Insurance (former IRI)-compliant manifold: (
See Page 73, Figure 57
18.2 Gas Piping and Pressures
The air handler is equipped with a gas manifold suitable for connection to supply pressure of up to 5 p.s.i. maximum for all manifold types.
When gas supply exceeds the above-listed maximum gas pressures, an additional high pressure gas regulator will be required to assure that the correct gas pressure is supplied to the air handler.
Outlet pressure from the regulator / inlet pressure to air handler should be measured at the inlet of the air handler gas manifold.
See Page 71, Figure 55
).
).
).
70 of 154
Page 79
Table 27: Manifold Component Identification
ALTERNATE
INLET
INLET
B
OUTSIDE
C
VENT
E
H
P
J
BY OTHERS
D
A
M
L
BY OTHERS
VENT LIMITER
N
* INTEGRAL VENT LIMITER
G
VENT LIMITER
ALL VENT PIPING TO OUTSIDE BY OTHERS
Item Component Identification
A Leg Trap (by others) B Lockable Manual Shut-Off Valve (by others)
High Gas Pressure Regulator (by others)
C
if gas pressure is over 5 P.S.I.
D Pilot Gas Cock
EPrimary Safety Shut Off Valve and Actuator
F Vent Valve and Piping GBlock Valve and Actuator HPlug Cock
JModulator Valve / Gas Pressure Regulator
KLow Gas Pressure Switch
L Pilot Valve Solenoid (normally closed) M Pilot Regulator N High Gas Pressure Switch
PBurner Q­R Union (by others)
S ¼" FPT Pressure Tap with Plug (by others)
NOTE: Items vary by manifold type. All items may not apply.
FIGURE 55: Standard Gas Manifold
SECTION 18: GAS P IPING
71 of 154
Page 80
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
VENT OUTSIDE
A
ALTERNATE
INLET
INLET
BY OTHERS
D
M
B
C
K
E
G
H
J
N
P
R
S
L
BY OTHERS
* INTEGRAL VENT LIMITER
* INTEGRAL VENT LIMITER
VENT LIMITER
VENT LIMITER
ALL VENT PIPING TO
OUTSIDE BY OTHERS
FIGURE 56: FM Gas Manifold
72 of 154
Page 81
FIGURE 57: XL Insurance Gas Manifold
ALL VENT PIPING TO OUTSIDE BY OTHERS
VENT OUTSIDE
F
VENT OUTSIDE
A
ALTERNATE
INLET
INLET
BY OTHERS
D
B
C
K
E
G
H
J
N
P
R
S
M L
BY OTHERS
* INTEGRAL VENT LIMITER
* INTEGRAL VENT LIMITER
VENT LIMITER
VENT LIMITER
SECTION 18: GAS P IPING
73 of 154
Page 82
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
18.3 Gas Piping
The gas manifold connection extends through the side of the control enclosure for vertical equipment and through the bottom for horizontal equipment. The factory piping terminates with a male pipe connection in the primary gas valve. Be sure that the fuel supply pipe connected at this point is large enough to ensure the proper volume and line pressure at the inlet of the air handler. The piping must comply with:
United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision, Natural Gas and Propane Installation Code.
Gas supply piping must conform to best building practices and local codes. During installation of the gas piping, be sure that piping does not restrict accessibility to the air handler or its removable access doors.
Lockable manual shut-off valve must be added by the installer in compliance with Occupational Safety and Health Administration (OSHA) regulations.
.4 Pressure Test Ports
18
There are 1/8"(3.2 mm) and 1/4"(6.4 mm) pressure test ports located on the manifold. The test ports are available to measure the manifold inlet gas pressure and the burner gas pressure during burner setup.
18.4.1 Manifold Inlet Gas Pressure
The pressure test port for measuring manifold inlet pressure is located on the inlet side of the first safety shutoff valve. Refer to the unit rating plate for the acceptable inlet gas pressure.
18.4.2 Burner Gas Pressure
A pressure tap is used to measure negative pressure at the burner (fan only, gas valves closed) and to set high fire gas pressure regulating (gas valves open). Air handlers are equipped with a modulating/ regulating valve (MRV). The pressure tap is located on the downstream side of the MRV.
74 o f 154
Page 83
SECTION 19: ELECTRICAL
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be required to disconnect electric from equipment.
Equipment must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
Each air handler is equipped with a wiring diagram which will vary depending on the type of remote panel and/or options supplied.
SECTION 19: ELECTRICAL
Air handlers can also be supplied as building management system (BMS)-ready. In this case, a remote panel is not supplied.
Note: Spark testing or shorting of the control wires by any means will render the transformers inoperative.
Each unit is equipped with a fused rotary disconnect. The rotary disconnects are for copper wire only.
75 of 154
Page 84
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
19.1 Disconnect Fuse Sizing
The fuse classification must be determined by the service disconnect rating plate and all applicable codes. Fuse sizing is determined by the motor size, control current and supply voltage. Fuses that are being replaced must be replaced with the same type, size and class of fuse that was supplied with the air handler. For additional information or to confirm original fuse specifications, consult the factory.
Table 28: Minimum and Maximum Fuse Size by Motor Size and Supply Voltage
Electrical Characteristics
Motor Size HP(kW) 208/3/60 230/3/60 460/3/60 575/3/60 230/1/60
2(1.5) 7.3-10.2 6.9-9.6 3.4-4.8 2.6-3.6 13.3-18.6 3(2.2) 10.1-14.2 9.3-13.0 4.6-6.5 3.7-5.2 17.3-24.2 5(3.7) 15.4-21.6 15.1-21.1 7.5-10.6 6.1-8.5 24.3-34.0
7.5(5.6) 23.1-32.4 21.3-29.8 10.6-14.9 8.3-11.6 32.3-45.2 10(7.5) 30.4-42.6 28.1-39.3 14.0-19.7 10.6-14.8 40.3-56.4
15(11.2) 42.4-59.4 39.3-55.0 19.6-27.5 16.8-23.5 ­20(14.9) 51.4-72.0 49.3-69.0 24.6-34.5 19.8-27.7 ­25(18.6) 66.4-93.0 61.3-85.8 30.6-42.9 24.5-34.3 ­30(22.4) 78.4-109.8 73.3-102.6 36.6-51.3 29.6-41.4 ­40(29.8) - - 47.6-66.7 38.0-52.6 ­50(37.3) - - 59.5-83.3 48.1-66.7 -
19.2 Wiring and Electrical Connections
All electrical wiring and connections, including electrical grounding, must comply with:
United States: Refer to National Electrical Code
®
, NFPA 70 - latest revision. Wiring must conform to the most current National Electrical Code
®
, local
ordinances, and any special diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.
Check rating plate on air handler for supply voltage and current requirements.
If any of the original control wire supplied with the air handler must be replaced, replace it with type MTW 105°C, 600 V, 16 gauge wire or equivalent, except for temperature control wiring, which must be a minimum of 20 AWG Type Beldon 5401FE CMR 75C shielded or equivalent.
For all other wires, replace with the equivalent size and type of wire that was originally provided with the air handler.
NOTE: The controls referenced in this manual are applicable to non-DDC equipped air handlers. If your air handler is equipped with one of our DDC control options, please consult the separate DDC Control Operator's manual that accompanies this document.
19.3 Remote Panel
The remote panel mu
st be wired as shown on the electrical schematic. For wire gauge sizes, see Page 76, Table 29. All power supply and motor wiring must be minimum type THWN with a 167° F (75° C)
temperature rise.
19.3.1 Remote Panel Mounting Distance
If the interconnection wiring between the remote panel and the air handler control enclosure is ru n in a single conduit, the wire run can be as long as 100' (30 m). For longer wire runs, consult the factory. If the interconnection wiring between the remote panel and the air handler control enclosure is run in two conduits (separating the shielded cable and the 120 V power supply for the remote panel), the wire run can be as long as 200' (60 m). For longer wire runs, consult the factory. Care should be used to avoid running the interconnect wiring near large industrial loads or high voltage wire runs as that may further limit the length of the interconnect wire run.
Table 29: Control Voltage Wiring For All Control Systems
Volts Wire Gauge Max Wire
120 18 150' (45 m) 120 16 250' (75 m) 120 14 350' (106 m)
NOTE: Wiring for temperature controls must be run in shielded cable as indicated on the wiring diagram.
19.3.2 Low Voltage Control Wiring
Low voltage (24 V - AC/DC) control wiring in excess of 100' (30.5 m) in length should be in its own separate conduit run to prevent interference.
19.4 Motor Current Draw
For specific current requirements, see rating plate
76 of 154
Page 85
SECTION 19: ELECTRICAL
located on the blower motor. Current draw may be adjusted downward by reducing blower rotations per minute (RPM) or by increasing external static pressure.
19.5 Control Current Draw
The maximum current draw for an air handler’s controls and accessories is 3A.
19.6 Safety Systems
Safety systems are required for proper performance of the air handler. The air handler shall not be permitted to operate with any safety system disabled. If a fault is found in any of the safety systems, then the system shall be repaired only by a contractor qualified in the installation and service of gas fired heating equipment, using only components that are sold and supplied by Rapid Engineering LLC. Refer to Page 81, Table 31 for a brief description of each safety device, its location and its switching voltage.
Table 30: Safety Systems
Safety Controls Location Voltage
Manual Reset High­Temp Limit (All Models)
Pres sure Switches (All Models)
Flame Control (2010/2010B/2020/2030)
Flame Control (2005)
Discharge Temperature Monitor (All Models)
AM Resistor (A M /VAV S t yle)
Blower Discharge 120
Air Handler Control
Enclosure
Air Handler Control
Enclosure
Air Handler Control
Enclosure
Blower Discharge 24
Air Handler Control
Enclosure
120
120
24
24
19.6.1 Manual Reset High Temperature Limit Switch
If for any reason, the temperature of the air at the discharge of the blower reaches the limit set point of 160° F (71.1° C), the high temperature limit switch will open the circuit to the burner system and discontinue all burner functions. E
vents that could result in excessive discharge air temperatures include if the burner modulation amplifier is defective (i.e. temperature sensor goes open circuit) or if a surge in gas pressure reaches the burner. Restarting of the burner can only be accomplished after the limit has cooled down and the reset button on the switch has been depressed. This switch is located on the blower housing inside the air handler.
closes. When the switch closes, it permits the flame safeguard relay to begin ignition. This switch is factory set at 0.32 in wc (0.8 mbar). The high velocity pressure s
witch will open if the airflow across the burner reaches its maximum allowable limit. This switch is factory set at 1.40 in wc (3.5 mbar). The pressure switch is a safety device, which cannot be field-adjusted or tampered with.
19.6.3 Gas Pressure Switches
Gas pressure switches are standard on certain models (FM compliant gas trains above 2,500 MBH and XL compliant gas trains) and are also available as an option on the others.
The function of the gas pressure switches is to protect against insufficient, lack of gas pressure and excessive pressure in the system.
On the low gas pressure switch side, this switch opens its internal switch which shuts the burner down and prevents its operation due to insufficient gas pressure.
On the high gas pressure switch side, its internal switch w
ill open, shutting down the burner due to excessive gas pressure passing through the gas train.
The settings of the gas pressure switches are field adjustable. The one monitoring the incoming gas pressure is the low gas pressure switch. The low gas pressure switch must be set to the minimum required gas pressure as indicated on the data plate.
The high gas pressure switch must be set to 1 in w.c. (2.5 mbar) above high fire setting established during commissioning.
The switch will have to be reset manually, once the condition has been corrected.
19.6.2 Pressure Switches
The low airflow velocity pressure switch monitors the airflow (differential pressure) across the burner. When the airflow across the burner reaches the proper velocity (volume) for combustion, the switch
77 of 154
Page 86
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
19.6.4 Flame Control
This device will check for both pilot flame and main flame within the burner. When a flame signal from the pilot flame is available, it will allow the main gas valve to open.
Yo ur air handler may equipped with either a flame rod or UV scanner type of flame detection. Consult your parts list / electrical diagram to confirm and for flame rod sensors See Page 115 and Page 116. For UV scanners See Page 119 and Page 120
If a pilot flame is not present, the electrical signal cannot be sent and the pilot burner gas valve will close. The relay is equipped with a 10-second trial for ignition. If ignition does not occur, the flame safeguard relay will lockout, it will reset upon power restoration. (See the Trouble-Shooting Guide - Page 136, Section 24)
19.6.5 Discharge Temperature Sensor
This device senses the discharge temperature of the air at the blower. The discharge temperature sensor reports the discharge temperature to the temperature control amplifier
which modulates the burner to the temperature set on the remote panel selector. Should this system fail, the manual high temperature limit switch will turn the burner off. BMS-ready air handlers do not come equipped with this sensor and must be field-supplied.
Yo ur Rapid
®
direct fired air handler was built custom to meet your needs. For details on interconnect wiring or any other wiring questions, please consult the specific wiring diagrams provided with your air handler.
NOTE: A laminated wiring diagram can be found permanently affixed inside the unit control enclosure.
78 of 154
Page 87
SECTION 19: ELECTRICAL
19.7 Interlocks
19.7.1 Carbon Dioxide Interlocks
All air handlers that recirculate air from the heated space require either a control to limit the temperature rise in proportion to the amount of outdoor air or the use of a room carbon dioxide sensor. The carbon dioxide sensor is field provided and set to maintain a CO2 concentration below 5,000 ppm.
19.7.2 Carbon Monoxide Interlocks
Carbon Monoxide Detector is a ship loose sensor that monitors the CO levels in the space. It can either sound an alarm and/ or force the air handler into 100% outside air if its threshold set point is exceeded.
19.8 Control Options
19.8.1 Mild Weather Outside Air Stat
This option is designed to turn the burner off when the incoming outside air is at or above the temperature setpoint. The blower is allowed to run for continued ventilation. The mild weather outside air stat is located in the control enclosure. It has an adjustable setting between -20° F (-29° C) and 100° F (38° C).
19.8.2 Low Temperature Limit with Override Timer
This option is designed to turn the unit off when air is discharged below the temperature setpoint for a period in excess of timer setpoint. The low temperatu
re limit switch is located in the air handler’s control enclosure. The low temperature limit switch has an adjustable setting between -20° F (-29° C) and 100° F (38° C). The timer by-passes the low temperature limit switch for the first 5 minutes to allow the burner to establish a flame when the air handler is turned on. If the air handler’s discharge temperature falls to the predetermined low temperature limit setpoint, after the 5 minute establishing period, the air handler’s blower will be turned off. To reset the low temperature limit switch, set the fan switch to off and then on again. The air handler will return to the normal sequence of operations.
19.8.3 MUA / Exhaust Failsafe Interlock
This option incorporates the low temperature limit with override timer and an exhaust fan airflow switch
monitor. The exhaust fan airflow switch is field provided and field w
ired as per the option sheet supplied with the unit. When the air handler is turned on there is a 5 minute establishing period for the low temperature limit switch and the exhaust fan interlock. If the air handler’s discharge temperature falls to the predetermined low temperature limit
setpoint, after the 5 minute establishing period, the air handler fan will be turned off. If there is a failure of the exhaust fan to activate the field supplied airflow switch, after the 5 minute establishing period, the air handler fan will be turned off. To reset the MUA/exhaust failsafe interlock, set the fan switch to off and then on again. The air handler will return to the normal sequence of operations.
19.8.4 Motorized Inlet Damper
The motorized inlet damper covers the outside air inlet of the air handler. When the air handler blower is turned on, the damper motor is energized and opens the damper. The damper motor has an auxiliary switch that prevents the blower from starting until that damper has opened sufficiently to allo
w the required
air volume to pass through the air handler.
19.8.5 Motorized Discharge Damper
The motorized discharge damper is mounted in the duct downstream from the discharge opening of the air handler. When the air handler fan is turned on the damper motor is energized and opens the damper. The damper motor has an auxiliary switch that prevents the blower from starting until that damper has opened sufficiently to allow the required air volume to pass through the air handler.
19.8.6 Control Enclosure Heater
The control enclosure heater is an electric heater that keeps the temperature in the control enclosure within the range for the control components. This option is intended for extremely cold climates, but recommended for installations below 15° F (-9° C). The air handler controls are rated to perform at temperatures as low as -30° F (-34° C). In environments where the air handler may be exposed to lower temperatures, a control enclosure heater may be required.
19.8.7 Auxiliary Relay
An auxiliary relay may be added to an air handler for either an interlock or a customer defined pu
rpose. Refer to the option sheet supplied with the air handler to indicate whether the relay is wired for an intended purpose or left unwired for a future interface. Each relay will be double pole double throw (DPDT) type. Maximum switching capacity on the normally open contact is 8A, and for the booth light relay, 15A.
19.8.8 Smoke Detector
A smoke detector interlock allows for the air handler to operate (either off or on) based on signal input from the fire alarm.
79 of 154
Page 88
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
19.8.9 Service Receptacle Powered by Others (Wired)
This option provides a service receptacle. It includes ground-fault interrupter (GFI) receptacle mounted on the interior or exterior of the control enclosure. Power to the receptacle is supplied by the installer.
19.8.10 Room Override Stat
For use with Standard Discharge Control remote. This option provides additional thermostat capability based on room temperature. The thermostat senses room temperature, and resets the discharge air to a higher temperature whenever the temperature falls below settings indicated on the temperature selection dial (located on remote panel). Override temperature can be set 0° F to 40° F above the temperature selection dial on the remote panel.
80 of 154
Page 89
SECTION 19: ELECTRICAL
19.9 Safety Systems
Safety systems are required for proper performance of the air handler. The air handler shall not be permitted to operate with any safety system disabled. If a fault is found in any of the safety systems, then the system shall be repaired only by a contractor qualified in the installation and service of gas fired heating equipment, using only components that are sold and supplied by Rapid Engineering LLC. Refer to Page 81, Table 31 for a brief description of each safety device, its location and its switching voltage.
Table 31: Safety Systems
Safety Controls Location Voltage
Manual Reset High-Temp Limit (All Models) Blower Discharge 120 Pres sure Switches (All Models) Air Handler Control Enclosure 120 Flame Control (All Models) Air Handler Control Enclosure 120 Supply Air Temperature Monitor (All Models) Blower Discharge 24
81 of 154
Page 90
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
1
5 MIN.
LLS
R W
C
NC
TR
1
LOW TEMP BY-PASS TIMER
HLS
LO
T-1 CONTROL TRANS.
H1 H2
AFS1
PS-1
HIGH
GAS PRS.
SWITCH
FEEDER PROTECTION
REF: N.E.C. TABLE 430-152
SIZING BY OTHERS.
G
LPJ-50SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
35.1
3
F1
F1
DISC SW
F1
34.0
1800
25
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
AA
FAN ON LIGHT
LT
MOTOR FLA TAKEN FROM N.E.C REFER TO NAMEPLATE FOR ACTUAL FLA
H3 H4
460VAC
HI
AFS2
RESET
MANUAL
LIMIT
HIGH TEMP
AIRFLOW
AIRFLOW
2
11
30
31
33
35
18
16
10
54
54
34
15
32
54
3A
CB-2
5A
CB-3
X4
120V
X1
X2X3
24VAC
T-4
DAMPER(s)
DAMPER L.S.
DM
1
INLET / SUPPLY
19
21
FAN
OFF
ON
ON
OFF
BURNER
SW-2
SW-1
M1
M1
MOL-1
START
MOTOR
M1
OL
350VA.
FAN RUNNING 86
CR39CR
PS-2
GAS PRS.
LOW
SWITCH
TH-3
OA STAT
BU R
19.10 Remote Panels
19.10.1 Basic Remote FIGURE 58: Basic Remote
82 of 154
Page 91
FIGURE 59: Basic Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALVE
BURNER ON
FLAME RELAY
PILOT VALVE SOLENOID
PRIMARY SHUT-OFF
20
AA
LT
VALVES OPEN
52
52
2
41
43
45
44
49
46
35
36
18
24VAC
40VA
80
81
6
5
TM
1
1 2 3
8
7
W
B
3 4
1
2
321
SEL
SERIES 14A
TCA
BASIC REMOTE
84
85
VENT VALVE
SOL.-2
V1
V2
L
1
1
21
SECTION 19: ELECTRICAL
83 of 154
Page 92
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
19.10.2 Standard Discharge Control Remote FIGURE 60: Standard Discharge Remote
FEEDER PROTECTION SIZING BY OTHERS.
REF: N.E.C. TABLE 430-250
L1
L2
L3
G
POWER SUPPLY
460
____V___PH___HZ
DISC SW
F1
F1
F1
LPJ-25SP
1
3
15.1
____FLA
60
M1
OL
CB-2
3A
T-1 CONTROL TRANS.
X4
CB-3
460VAC
H3 H4
H1 H2
5A
X1
X2X3
120V
MOTOR FLA TAKEN FROM N.E.C REFER TO NAMEPLATE FOR ACTUAL FLA
T1
SUPPLY FAN
MTR
MOTOR
1
____HP
10
____RPM
1800
____FLA
14.0
T2
T3
2
JUMPER
5 MIN.
ON
OFF
AUTO
SW-1
6
5
R B
TH-1
CYCLE STAT
SUMMER
8
WINTER
SW-2
18
HIGH TEMP
LIMIT
RESET
MANUAL
HLS
30
C
10
R W
16
TR
1
NC
LLS
M1
JUMPER
T-4
19
DM
1
24VAC
21
11
15
MOL-1
HIGH GAS
PRS. SWITCH
31
35
PS-1
JUMPER
MANUAL
RESET
32
34
AIRFLOW
AFS1-LO
AIRFLOW
AFS2-HI
M1
LT-1
AA
33
LOW TEMP BY-PASS TIMER
INLET/DISCHARGE
DAMPER(s)
DAMPER L.S.
MOTOR START
FAN ON LIGHT
54
84 of 154
54
54
Page 93
FIGURE 61: Standard Discharge Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALVE
BURNER ON
FLAME RELAY
PILOT VALVE SOLENOID
PRIMARY SHUT-OFF
20
AA
LT-2
VALVES OPEN
52
52
2
41
43
45
44
49
46
35
52
18
24VAC
51
52
V1
V2
L
1
52
1
6
5
TM
1
1 2 3
8
7
W
B
3 4
1
2
321
SEL
53
54
SECTION 19: ELECTRICAL
85 of 154
Page 94
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
1
HLS
T-1 CONTROL TRANS.
H1 H2
AFS1-LO
PS-1
HIGH GAS
PRS. SWITCH
RESET
MANUAL
FEEDER PROTECTION
REF: N.E.C. TABLE 430-250
SIZING BY OTHERS.
G
LPJ-30SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
22.1
3
F1
F1
DISC SW
F1
21.0
1800
15
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
AA
FAN ON LIGHT
LT-1
MOTOR FLA TAKEN FROM N.E.C REFER TO NAMEPLATE FOR ACTUAL FLA
H3 H4
460VAC
AFS2-HI
RESET
MANUAL
LIMIT
HIGH TEMP
AIRFLOW
AIRFLOW
2
11
30
31
33
35
18
16
54
54
34
15
32
54
5A
CB-3
X4
120V
X1
X2X3
JUMPER
JUMPER
JUMPER
M1
M1
MOL-1
M1
OL
START
MOTOR
350VA
3A
CB-2
TH-1
SW-2
SUMMER
ON
SW-1
OFF
R B
CYCLE STAT
TC26
TC26
AUTO
6
7 8
WINTER
TC
TIME CLOCK
26
5 MIN.
LLS
R W
C
NC
TR
1
LOW TEMP BY-PASS TIMER
10
19.10.3 Deluxe Room Control Remote FIGURE 62: Deluxe Room Control Remote
86 of 154
Page 95
FIGURE 63: Deluxe Room Control Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALVE
BURNER ON
FLAME RELAY
PILOT VALVE SOLENOID
PRIMARY SHUT-OFF
20
AA
LT-2
VALVES OPEN
52
52
41
43
45
44
49
46
52
24VAC
51
52
1
18
35
2
V1
V2
L
52
52
B
W
R
8 9
3
4 5
1
2
321
1
TM
TCA
S E
E
S
L
N
6 7
55
56
57
SECTION 19: ELECTRICAL
87 of 154
Page 96
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
1
HLS
T-1 CONTROL TRANS.
H1 H2
AFS1-LO
PS-1
HIGH GAS
PRS. SWITCH
RESET
MANUAL
FEEDER PROTECTION
REF: N.E.C. TABLE 430-250
SIZING BY OTHERS.
G
LPJ-125SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
79.7
3
F1
F1
DISC SW
F1
77.0
1800
60
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
AA
FAN ON LIGHT
LT-1
MOTOR FLA TAKEN FROM N.E.C REFER TO NAMEPLATE FOR ACTUAL FLA
H3 H4
460VAC
AFS2-HI
RESET
MANUAL
LIMIT
HIGH TEMP
AIRFLOW
AIRFLOW
2
11
30
31
33
35
18
16
54
54
5
34
15
32
54
5A
CB-3
X4
120V
X1
X2X3
12
JUMPER JUMPER
SD
SMOKE DETECTOR DISCHARGE
SD22
23
CR
22
23
CR
5
60
M1
M1
MOL-1
M1
OL
START
MOTOR
AFS3
AA
CLOGGED FILTER LIGHT
70
500VA.
3A
CB-2
PS-2
LOW GAS
PRS. SWITCH
RESET
MANUAL
TH-3
OA STAT
BU R
TH-1
SW-2
SUMMER
ON
SW-1
OFF
R B
CYCLE STAT
AUTO
6
8
WINTER
5 MIN.
LLS
R W
C
NC
TR
1
LOW TEMP BY-PASS TIMER
10
19.10.4 Standard Room Control Remote FIGURE 64: Standard Room Control Remote
88 of 154
Page 97
FIGURE 65: Standard Room Control Remote (Continued)
MRV
1
W
2
B
UV
T3
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T2
TRANSFORMER
IGNITION
G
F
9
8
L2
76
FR-1
10
5
SOL.-1
VALV E
BURNER ON
FLAME RELAY
PILOT VALVE SOLENOID
PRIMARY SHUT-OFF
20
AA
LT-2
VALVES OPEN
52
52
2
41
43
45
44
49
46
35
52
18
24VAC
51
52
SOV1
SOV2
1
52
47
B W R
8 9
3
4 5
1
2
321
1
TM
TCA
S E
E
S
L
N
6 7
86
87
88
SECTION 19: ELECTRICAL
89 of 154
Page 98
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
T-1 CONTROL TRANS.
X4
120VAC
X1
H1
500VA
H4
FEEDER PROTECTION
REF: N.E.C. TABLE 430-152
SIZING BY OTHERS.
G
LPJ-40SP
POWER SUPPLY
____V___PH___HZ
____FLA
460
L2
L1
L3
60
29.7
3
F1
F1
DISC SW
F1
27.0
1800
20
SUPPLY FAN
MOTOR
____HP
____FLA
____RPM
MTR
T3
T2
1
T1
MOTOR FLA TAKEN FROM N.E.C REFER TO NAMEPLATE FOR ACTUAL FLA
H3 H2
FAN START/STOP
INTERLOCK
BURNER START/STOP
INTERLOCK
CR98
CR93
1
2
12
16
18
15
X3 X2
54
54
21
24
22
21
1
CR-23
5
JUMPER
460VAC
L2L3
M1
M1
MOL-1
M1
OL
MOTOR STARTER/
MOTOR
INLET
TRANS.
TRANS.
OVERLOAD RELAY
DM
1
INLET DAMPER
24VAC
T-4
INLET DAMPER
DAMPER L.S.
T-6
120VAC
120VAC
40VA
40VA
INLET DAMPER
OA/RA DAMPER
BLK
RED
3
DM2
BY OTHERS
CONTROL
24VAC
(-) COMMON
OA/RA
W
DAMPER
(+) 0 -10 VDC
3A
CB-2
5A
CB-3
8
9
2
18
19.11 DDC-Ready Controls FIGURE 66: DDC-Ready Controls
90 of 154
Page 99
FIGURE 67: DDC-Ready Controls (Continued)
W
B
V3/MRV
2 1
UV
50
51
LOW VOLTAGE
TRANSFORMER
AMPLIFIER
SP
T-2
TRANSFORMER
IGNITION
G
F
9
8
L2
67
FR-1
10
5
SOL.-1
VALV E
BLOCK VALVE
FLAME RELAY
PILOT VALVE SOLENOID
PRIMARY SHUT-OFF
20
HLS
LO
AFS1
PS-1
HIGH
GAS PRS.
SWITCH
HI
AFS2
LIMIT
HIGH TEMP
AIRFLOW
AIRFLOW
RM7897C
BU R
TH-2
OA STAT
CR93
24 VAC COIL
(YELLOW WIRE)
POWERED BY OTHERS
FAN START/STOP
INTERLOCK
CR98
24 VAC COIL
(YELLOW WIRE)
POWERED BY OTHERS
BURNER START/STOP
INTERLOCK
10 AMPS MAX
BURNER FAILURE
INTERLOCK
3
CR67
SAFETIES
BURNER FAILURE RELAY
30
31
33
32
34
40
41
42
43
44
45
46
64
65
JUMPER
49
110
111
112
113
114
115
53
53
MANUAL
RESET
MANUAL
RESET
MANUAL
RESET
CR67
(YELLOW WIRE)
POWERED BY OTHERS
24VAC
T-3
120VAC
40VA
PS-2
GAS PRS.
LOW
SWITCH
SOV1
SOV2
48
4-20mA/0-10VDC MODULATION
INPUT
CONDITIONER
SIGNAL
1
2
3
4
-
+
6
5
B
R
SC-1
18
2
SECTION 19: ELECTRICAL
91 of 154
Page 100
4000-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Yo ur RAPID
®
Air Handler may be equipped with one of the following DDC control offerings. If so, a separate manual providing wiring, operation and trouble shooting information, specific to that control offering, will also accompany this document.
19.12 Intelligent Control Systems
19.12.1 ICS II
19.12.2 ICS IV
19.12.3 InfinityPro™
92 of 154
Loading...