Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier’s
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to combustibles away from
equipment.
Some objects will catch fire or explode
when placed close to equipment.
Failure to follow these instructions can
result in death, injury or property
damage.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your service technician with necessary information.
Rapid Engineering LLC
1100 Seven Mile Road NW
Comstock Park, MI 49321
Telephone: +1.616.784.0500
Fax: +1.616.784.1910
Toll Free: 800.536.3461
www.rapidengineering.com
P/N RP121100NA Rev C 08/15
Page 2
Page 3
Conçus pour les applications non-résidentielles
Canada: seulement avec
100% d’air externe
ATTENTION
Linstallation doit être effectuée par un installateur
éprouvé/contractant qualifié dans linstallation et la
maintenance du système de chauffage par infrarouge
activé au gaz.
Linstallation, lajustement, laltération, le démarrage
ou lentretien inadéquat peuvent causer la mort, des
blessures ou des dégâts matériels. Lire entièrement
le manuel dinstallation, dopération et dentretien
avant linstallation ou l'entretien de cet équipement.
Installateur
Prenez le temps de lire et comprendre ces instructions
avant toute installation.
Linstallateur doit remettre au propriétaire
un exemplaire de ce manuel.
Propriétaire
Gardez ce manuel dans un endroit sûr pour
fournir des informations au réparateur
en cas de besoin.
Rapid Engineering LLC
1100 Seven Mile Road NW
Comstock Park, MI 49321
Téléphone: +1.616.784.0500
Fax: +1.616.784.1910
Numéro sans fraís: 800.536.3461
www.rapidengineering.com
AVERTISSEMENT
POUR VOTRE SECURITE
Si vous sentez une odeur de gaz:
1. Ouvrir les fenêtres.
2. N’essayer pas d’allumer un appareil.
3. N’utiliser pas d’interrupteurs
électriques.
4. N’utiliser pas de téléphone dans votre
bâtiment.
5. Eteindre flamme nue.
6. Quitter le bâtiment.
7. Après avoir quitté le bâtiment, appelez
immédiatement votre fournisseur local
de gaz.
Suivre les instructions du fournisseur
de gaz.
8. Si vous ne pouvez pas joindre votre
fournisseur de gaz, appeler le service
d’incendie.
Risque d’incendie
Garder tous les objets, liquides ou vapeurs
inflammables à la distance minimale de
l’unité de chauffage requise avec les
matériaux combustibles.
Certains objets prendront feu ou exploseront
s’ils sont placés à proximité de l’unité de
chauffage.
Le non respect de ces instructions peut
entraîner la mort, des blessures corporelles
ou des dommages matériels.
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Rapid Engineering LLC.
There are references in this manual to various trademarks. All trademarks mentioned herein, whether registered or not, are the
property of their respective owners. Rapid Engineering LLC is not sponsored by or affiliated with any of the trademark or registered
trademark owners, and makes no representations about them, their owners, their products or services.
Page 10
Page 11
SECTION 1: AIR HANDLER SAFETY
Yo ur Safety is Important to Us!
This symbol is used throughout
the manual to notify you of
possible fire, electrical or burn
hazards. Please pay special
attention when reading and
following the warnings in these
sections.
Installation, service and, at a minimum, annual
inspection of air handlers must be done by a
contractor qualified in the installation and service of
gas-fired heating equipment.
Read this manual carefully before installation,
operation or service of this equipment.
This air handler is designed for heating nonresidential indoor spaces. Do not install in residential
spaces. These instructions, the layout drawing, local
codes and ordinances and applicable standards that
apply to gas piping, electrical wiring, ventilation, etc.
must be thoroughly understood before proceeding
with the installation.
Protective gear is to be worn during installation,
operation and service in accordance to the
Occupational Safety and Health Administration
(OSHA). Gear must be in accordance to NFPA 70E,
latest revision w
hen working with electrical
components. Thin sheet metal parts have sharp
edges. To prevent injury, the use of work gloves is
recommended.
Before installation, check that the local distribution
conditions, nature of gas and pressure and
adjustment of the appliance are compatible.
The equipment must be applied and operated under
the general concepts of reasonable use and installed
using the best building practices.
This piece of equipment is not intended for use by
persons (including children) with reduced physical,
sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given
supervision or instruction concerning use of the
equipment by a person responsible for their safety.
Children should be supervised to ensure that they do
not play with the equipment.
For additional copies of the Installation, Operation
and Service Manual, please contact Rapid
Engineering LLC.
Gas-fired eq
uipment is not designed for use in
atmospheres containing flammable vapors or dust or
atmospheres containing chlorinated or halogenated
hydrocarbons. Recirculated room air may be
SECTION 1: AIR HANDLER S AFETY
hazardous if containing flammable solids, liquids,
and gases; explosive materials; and/or substances which may become toxic when exposed to heat (i.e.
refrigerants, aerosols, etc.).
1.1 Description of Operation
This air handler is a direct, gas-fired, fresh-air piece
of equipment. It is designed for indoor or outdoor
installation with fresh outdoor air delivered to the
burner. Air handlers are designed to operate in
temperatures as low as -30° F (-34° C). The air
handler is factory-tested to fire with natural gas or
LPG (check the air handler's rating plate for
information on the appropriate gas). The burner
flame will modulate to maintain the selected
discharge air temperature or room air temperature,
depending on the selected controls. See Page 110,
Section 18.2. For maximum temperature rise, See
Page 121, Table 24.
The air handler may be provided with several
different controls and options to meet various
application requirements. Be sure to read this entire
manual before installation and start-up.
1.2 Inspection and Setup
The air handler is shipped fully assembled. The air
handler was inspected and operated prior to
shipment. Immediately upon receipt of the air
handler, check the fuel and electrical characteristics
of the air handler and verify that they match the fuel
and electrical supply available. Verify that the
specifications on the air handler rating plate match
the order. Check the air handler for any damage that
may have occurred during shipment. If any damage
is found, file a claim with the transporting agency. Do
not refuse shipment. Check the installation location
to ensure proper clearances to combustibles. See Page 8, Section 3.1.
Any small options which do not come attached to the
air handler (i.e. remote panel) will be found inside the
air handler.
Larger accessories (i.e. legs, stand, filter section,
inlet hood) may either ship with the air handler or
separately. Check the bill of lading for information.
If the air handler must be temporarily stored (i.e. job
site is not ready for installation of the air handler), the
air handler should be set on 4" x 4" (10 cm x 10 cm)
pieces of timber on the ground in a protected area.
Cover the air handler to protect it from the
environment. Rapid Engineering LLC will not be held
responsible for any damages that may occur from
1 of 147
Page 12
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
outdoor storage.
1.3 Safety Labels and Their Placement
Product safety signs or labels should be replaced by
product user if they are no longer legible. Please
contact Rapid Engineering LLC or your RAPID
®
independent distributor to obtain replacement signs
or labels. See Page 3, Figure 1 through Page 4, Figure 3.
1.4 California Proposition 65
In accordance with California Proposition 65 require-
ments, a warning label must be placed in a highly
visible location on the outside of the equipment (i.e.,
near equipment's serial plate). See label placement
drawing on Page 3, Figure 1 through Page 4, Figure
3 for label location. Avoid placing labels on areas
with extreme heat, cold, corrosive chemicals or other
elements. To order additional labels, please contact
Rapid Engineering LLC or your RAPID
SO THAT IT CAN BE READ FROM TOP-LEFT
TO BOTTOM-RIGHT WHEN THE AIR HANDLER
IS INSTALLED AT THE JOB SITE.
-LABEL 15 IS USED ANY TIME THERE IS A
GFI OUTLET THAT
IS POWERED BY OTHERS. TO BE POSITIONED
NEXT TO LABEL 8 AND/OR 14.
8 or 14
2005 MOUNT
ON ENCL FLOOR
UNDER VFD/AUX
MOTOR STARTER
15
8 AND/OR 14
2010-2030 SPLASH PLATE MOUNTED
ON CONTROL ENCLOSURE BOTTOM PANEL
2005 CONTROL ENCLOSURE FLOOR UNDER
VFD/AUX MOTOR STARTER
15
16
1 OR 2
SAFETY
SHUTOFF
VALVE
IGNITION
TRANSFORMER
TRANSFORMER
40VA
AMPLIFIER
AIRFLOW
SWITCH
0.32IN W.C.
R6
AIRFLOW
SWITCH
1.40IN W.C.
10
7
9
SPLASH PLATE MOUNTED
ON CONTROL ENCLOSURE
DOOR
CONTROL ENCLOSURE DOOR
11 or 12
13 PLACE INSIDE ITEM #9
2010-2030
7
9
2005 CONTROL ENCLOSURE DOOR
13 PLACE INSIDE ITEM #9
11 or 12
NAMEPLATE
3MOTOR
4
3
BLOWER
HIGH TEMP LIMIT SWITCH
DISCHARGE SENSOR
6
REMOTE BOX
RIGHT SIDE
TERMINAL RAIL
REMOTE BOX 10X10 INTERNAL
10
11
REMOTE BOX
LEFT SIDE
16
10
TERMINAL RAIL
REMOTE BOX 12x16 INTERNAL
6
REMOTE BOX
RIGHT SIDE
11 or 12
REMOTE BOX
LEFT SIDE
16
ItemPart NumberDescriptionQty.
119024Label - Propane Gas1
219025Label - Natural Gas1
319162Label - Rotation1
419161Label - High Temperature Limit1
519100Label - Ground1
691070009Label - Electric Shock Hazard (Mini)1
791010444Label - 2000-Series Rating Plate1
891010443Label - 2000-Series Exhaust Fan Motor Control1
9909113009½" x 13" Clear Pouch1
1091010445
Label - 2000-Series Wire Connection Control Panel/
Remote Panel
2
1191010446Label - ETL Certification Without Recirculation Z83.42
1291010447Label - ETL Certification With Recirculation Z83.182
1380XXXWiring Diagram - Varies by Order2
1491040128Label - Auxiliary Motor Starter1
1591010448Label - Shock Hazard GFI1
SECTION 1: AIR HANDLER S AFETY
5 of 147
Page 16
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Explosion Hazard
Equipment must have access to
uncontaminated air at all times.
Failure to follow these instructions can result
in death, injury or property damage.
CAUTION
Product Damage Hazard
Do not use equipment in area containing
corrosive chemicals.
Refer to appropriate Material Safety Data
Sheets (MSDS).
Failure to follow these instructions can result
in product damage.
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install and commission the air handler, as well
as the gas and electrical supplies, in accordance
with applicable specifications and codes. Rapid
Engineering LLC recommends the installer
contact a local building inspector or Fire Marshal
for guidance.
•To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
•To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports.
• To provide access to
air handler
for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or
suspend anything from heater.
•To ensure there is adequate air circulation around
the air handler and to supply air for combustion, ventilation and distribution in accordance with
local codes.
• To assemble or install any accessories or
associated duct work using best building
practices.
• To properly size supports and hanging materials.
• To ensure heater is placed in an approved
application.
6 of 147
2.1 Wall Tag
A laminated wall tag is available for the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Please contact Rapid Engineering LLC
®
or your RAPID
independent distributor to obtain the
wall tag. Affix the tag on a wall near the heater (e.g.
thermostat or control system).
A copy of the wall tag (P/N 91040118) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found
on the rating plate and in the Installation, Operation
and Service Manual. See Page 3, Figure 1 through Page 4, Figure 3.
2.2 Corrosive Chemicals
Rapid Engineering LLC cannot be responsible for
ensuring that all appropriate safety measures are
undertaken prior to installation; this is entirely the
responsibility of the installer. It is essential that the
contractor, the sub-contractor, or the owner identifies
the presence of combustible materials, corrosive
chemicals or halogenated hydrocarbons* anywhere
in the premises.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen elements
(fluorine, chlorine, bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents, solvents, etc. If
these compounds enter the air supply of the burner, the life span
of the air handler components will be greatly reduced. The location of the outside air supply must be carefully chosen to supply
outside air, free of these compounds, to the burners whenever
the presence of these compounds is suspect. Warranty will be
invalid if the air handler is exposed to halogenated hydrocarbons.
Page 17
2.3 National Standards and Applicable Codes
All equipment must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installation in public garages, aircraft hangars, etc.
may be applicable.
2.4 Required Equipment
When lifting of the equipment is required, the
installing contractor is responsible for supplying or
arranging for the appropriate lifting equipment so that
the air handler and accessories may be placed in a
safe manner.
The qualified installer or service technician is
responsible for having the appropriate equipment for
the safe installation and start-up of a direct-fired air
handler. Tools required to commission the equipment
include, but are not limited to, the following:
• Various screwdriver types and sizes
• Various adjustable wrenches
• Torque wrenches
• Pipe wrenches sized appropriately for the gas
train components
• Drill motor and various drills
• U-tube manometer or gas pressure gauge
• Volt meter
• Clamp style ammeter
• Belt tension gau
ge
• Caulk (non-silicone)
SECTION 2: INSTALLER R ESPONSIBILITY
7 of 147
Page 18
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to
combustibles away from equipment.
Some objects will catch fire or explode when
placed close to equipment.
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 3: CRITICAL CONSIDERATIONS3.1 Required Clearances to Combustibles
Clearances are the required distances that
combustible objects must be away from the air
handler to prevent fire hazards. Combustibles are
materials that may catch on fire and include common
items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times
for safety.
Check the clearances on each air handler being
installed to make sure the product is suitable for your
application and the clearances are maintained.
Clearances to combustibles for models 2005-
2030 are 12" (30.5 cm) on the control enclosure side
and 6" (15.2 cm) on all other surfaces. Read and
follow the safety guidelines below:
• Locate the air handler so that the air intakes are
not too close to any exhaust fan outlets, gasoline
storage, propane tanks or other contaminants that
could potentially cause dangerous situations.
WARNING
• Keep gasoline or other combustible materials
including flammable objects, liquids, dust or
vapors away from this air handler or any other
piece of
• Maintain clearances from heat sensitive material,
equipment and workstations.
equipment
.
Explosion Hazard
Fresh air supply duct and burner housing
must be purged with fresh air four times
before every ignition.
Explosive vapors will ignite if not evacuated
before ignition attempt.
Failure to follow these instructions can result
in death, injury or property damage.
Clearances to combustibles do not denote
clearances for accessibility. Minimum clearance for
access is 48" (122 cm). Minimum clearance for
accessibility applies to the control enclosure, blower
access panel and filter access panel (when
equipped).
The stated clearances to combustibles represent a
surface temperature of 90° F (50° C) above room
temperature (90° F [50° C] plus ambient
temperature). Building materials with a low heat
tolerance (i.e. plastics, vinyl siding, canvas, tri-ply,
etc.) may be subject to degradation at lower
temperatures. It is the installer’s/owner’s
responsibility to assure that adjacent materials are
protected from degradation.
• Maintain clearances from vehicles parked below the
air handler. See Page 10, Section 4.4.
8 of 147
Page 19
SECTION 3: CRITICAL CONSIDERATIONS
8.8
10.9
3.2 Purge of Supply Duct
If this heating unit is to be installed indoors, and its
outdoor air supply ducted from outdoors, ANSI
Standards Z83.18 and Z83.4 require that all supply
duct shall be purged a minimum of four times prior to
any ignition attempt. If the volume of the outdoor air
supply duct exceeds the heating unit’s ability to
complete the required four air changes prior to
ignition, you must contact the factory to purchase an
extended purge card of the appropriate duration to
meet this requirement.
3.3 Hardware
Unless otherwise specified, all hardware must be
torqued to settings on Page 9, Table 1.
Note: Inlet hood opening shall not be installed with
inlet opening facing into the prevailing wind direction
in order to help prevent the possibility of moisture
entrainment.
Table 1: Recommended Torque Settings
Bolt Head
Grade Marking
Nut Grade
Marking
Bolt SizeGrade 2Grade 5
10-2427 in•lb42 in•lb
1/4-2065 in•lb101 in•lb
5/16-1811 ft•lb17 ft•lb
3/8-1619 ft•lb30 ft•lb
Bolt Head
Grade Marking
8.810.9
Nut Grade
Marking
Bolt SizeGrade 8.8Grade 10.9
M56Nm9Nm
M610Nm15Nm
M825Nm35Nm
M1050Nm75Nm
M1285Nm130Nm
M16215Nm315Nm
9 of 147
Page 20
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 4: NATIONAL STANDARDS AND
APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the nameplate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1- latest revision,
Natural Gas and Propane Installation Code.
4.4 Parking Structures and Repair Garages
Installation in garages must be in accordance
with the following codes:
United States: Refer to Standard for Parking
Structures, NFPA 88A - latest revision or the
Code for Motor Fuel Dispensing Facilities and
Repair Garages, NFPA 30A - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code, Standard CSA B149.1 - latest
revision.
4.2 Installation Codes
Installations must be made in accordance with
the Standard for the Installation of AirConditioning and Ventilating Systems, NFPA
90A - latest revision for the installation of air
conditioning and ventilating systems.
4.3 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard on Aircraft
Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane
Installation Code, Standard CSA B149.1 - latest
revision.
4.5 Electrical
Electrical connection to air handler must be in
accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances, and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
4.6 Venting
The venting must be installed in accordance
with the requirements within this manual and
the following codes:
United States: Refer to NFPA 54/ANSI Z223.1latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision,
Natural Gas and Propane Installation Code.
10 of 147
4.7 High Altitude
These air handlers are approved for
installations up to 2000' (609.6 m) (in the US)
and 4500' (1371.6 m) (in Canada) without
modification. Consult factory if US installation is
above 2000
is above 4500
'
(609.6 m) or Canadian installation
'
(1371.6 m).
Page 21
SECTION 5: SPECIFICATIONS
SECTION 5: SPECIFICATIONS
Dimension and estimated weight tables apply to both
upright and horizontal units of the same model.
Unless otherwise requested, all direct-fired air
handlers are set-up to accept an external static
pressure (ESP) of 1 in wc (2.5 mbar). The external
static pressure is the sum of all accessories and any
attached ductwork. See Page 16, Table 9 for static
pressure accessories. If more external static
pressure is required, this needs to be requested with
the order as required motor horsepower (HP) may
increase from the specifications given on Page 15,
FIGURE 5: 2005 Upright Model Dimensions
A
ED
F
E
D
Y
Z
LD or RD
FN
BBAABB
(One Each Corner)
Customer Supplied
Duct Location
(See Page 73, Table 11)
Ta b l e 8 .
The legend below details abbreviations used in this
section and applies to Page 11, Figure 5 through Page 14, Figure 8. Return Air (RA) is only for FR
(Fixed Recirculation) and AM (Air Management)
styles.
Legend
BD = Bottom DischargeOA = Outside Air
CE = Control EnclosureRA = Return Air (optional)
GC = Gas ConnectionRD = Right Discharge
ED = End DischargeTD = Top Discharge
LD = Left DischargeOH = Opposite Hand
C
Lifting Lug
LD
ED
QD
RD
B
G
U
GC-OH
M
CECE-OH
S
GC
Filter
Access
K
GC
(OPTIONAL)
FILTER SECTION
OAOA
STAND
(OPTIONAL)
END VIEW
CE
SIDE VIEW
Filter
Access
Table 2: 2005 Dimensions
ModelCFMABCDEFGKLMNPQSUWXYZAABB
(in)
1,000-
32.3
60.3
28.3
10.4
6.8
11.5
27.0
117.3
1.5
8.0
9.3
1.8
3.1
35.2
30.0
25.0
38.4
2005
(cm)
(in)
(cm)
3,000
4,000
82.0
32.3
82.0
153.2
60.3
153.2
71.9
28.3
71.9
26.4
13.8
35.1
17.3
7.6
19.3
29.2
8.2
20.8
68.6
27.0
68.6
297.9
117.3
297.9
3.8
1.5
3.8
20.3
8.0
20.3
23.6
15.8
40.1
4.6
1.8
4.6
7.9
3.1
7.9
89.4
35.2
89.4
76.2
30.0
76.2
63.5
25.0
63.5
97.5
38.4
97.5
5.3
13.51435.6
7.5
19.01435.6
17.5
44.5
17.5
44.5
7.4
18.7
7.4
18.7
11 o f 14 7
Page 22
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
ED
A
N
F
TD or BD
E
D
F
G
OA
B
OA
ED
P
L
W
C
D
Q
CE
CE-OH
CE
TD
BD
M
X
GC
GC
SIDE
VIEW
PLAN
VIEW
FILTER SECTION
(OPTIONAL)
INLET HOOD
(OPTIONAL)
Customer Supplied
Duct Location
(See page 73, Table 11)
Filter Access
Filter Access
S
AA
BB
BB
Y
Z
GC-OH
FIGURE 6: 2005 Horizontal Model Dimensions
Table 3: 2005 Weights
ModelAir Handler Stand
2005
(lb)450756020100755040132650
(kg)204.134.027.29.145.43422.718.15.911.822.7
Table 4: Motor Weights
Size
ODP
TEFC
HP
kW
lb
kg
lb
kg
2
1. 5
58
26.3
90
40.8
Inlet
Hood
3
2.2
69
31.3
135
61.2
Splash
Plate
Filter
Section
Roof
Curb
Discharge
Head
Dampers
Suspension
Kit
Legs
(each)
Skid
12 of 147
Page 23
FIGURE 7: 2010, 2010B, 2020 and 2030 Upright Model Dimensions
G
B
A
P
M
U
H
H
F
C
J
CE
CE-OH
LD or RD
Lifting Lug
(One Each Corner)
Filter
Access
CC
GC
GC
FILTER SECTION
(OPTIONAL)
STAN D
(OPTIONAL)
ED
ED
LD
RD
OA
OA
RA
RA
Filter
Access
F
V
DT
DD
KK
EE
Y
NS
SIDE VIEWEND VIEW
CE
NN
E
D
LL
MM
2”
2”
Customer Supplied
Duct Location
(See Page 73, Table 11)
SECTION 5: SPECIFICATIONS
Table 5: 2010, 2010B, 2020 and 2030 Dimensions
ModelABCDEFGHJMNPQR
2010/
(in)
(cm)
(in)
(cm)
(in)
(cm)
(in)
(cm)
(in)
(cm)
(in)
(cm)
44.2
112.3
56.0
142.2
68.0
172.7
1.6
4.1
1.5
3.8
1.5
3.8
234.4
116.2
295.1
116.2
295.1
2010B
2020
2030
ModelSTUVWYZAABBCCDDEEFFGGHHKKLLMMNN
2010/
2010B
2020
2030
92.3
3.0
7.6
3.9
9.9
3.9
9.9
22.0
55.9
31.5
80.0
36.8
93.5
10.0
25.4
26.5
67.3
30.5
77.5
CC
145.3
369.1
164.3
417.3
(Stand
Height
)
53.0
134.6
72.0
182.9
Model*M
(in)
(cm)
2010/
2010B
(in)
(cm)
19.0
10.5
26.7
13.8
35.0
17.0
43.2
56.4
143.2
89.3
226.8
86.9
220.7
11.1
28.2
12.3
31.2
15.6
39.6
37.2
94.5
44.0
111.8
44.0
111.8
48.3
31.5
80.0
36.8
93.5
3.4
8.6
6.0
15.2
6.0
15.2
37.9
96.3
44.3
112.5
56.3
143.0
34.0
86.3
31.0
78.7
31.0
78.7
3.2
8.1
6.0
15.2
6.0
15.2
38.8
98.6
49.7
126.2
64.1
162.8
14.0
35.6**
17.0
43.2
17.0
43.2
28.8
73.2**
52.8
134.1
56.8
144.3
188.2
477.8
188.2
477.8
72.0
182.9
72.0
182.9
29.6
32.7
48.1
75.2
52.6
133.6
56.6
143.8
28.6
72.6
33.0
83.8
33.0
83.8
83.1
56.1
142.5
60.1
152.7
1.5
3.8
2.0
5.1
2.0
5.1
122.2
69.6
176.8
69.6
176.8
1.1
2.8
1.1
2.8
1.1
2.8
35.1
89.2
23.3
59.2
23.3
59.2
41.0
104.1
52.0
132.1
66.4
168.7
0.5
1.3
0.4
1.0
0.4
1.0
6.5
16.5
N/A
N/A
25.3
64.3
35.3
89.5
40.8
103.5
9.5
24.1
10.4
26.4
13.6
34.5
25.3
64.3
35.3
89.5
40.8
103.5
13 of 147
Page 24
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
AA
OA
ED
ED
BD
CE
OA
TD
CE
CE-OH
TD or BD
RA
B
WZ
VU
H
J
D
E
C
F
F
A
Y
R
Q
D
T
GC
SIDE
VIEW
PLAN
VIEW
FILTER SECTION
(OPTIONAL)
INLET HOOD
(OPTIONAL)
GC
GC-OH
RA
DD
N
P
BB
GG
G
Lifting Lug
(One Each Corner)
Support Brace
Filter Access
Filter Access
H
FF
FF
HH
S
EE
2”
Customer Supplied
Duct Location
(See Page 73, Table 11)
LL
MM
MM
NN
FIGURE 8: 2010, 2010B, 2020 and 2030 Horizontal Model Dimensions
Inlet variation of screen mesh without filters has equal weight as inlet hood with filters.
Inlet dampers for MUA style use both the upper and lower dampers for 2020 and 2030.
Inlet dampers for FR, AM and VAV styles only use the upper damper for 2020 and 2030.
Model 2010/2010B damper weights apply to both discharge and inlet.
*Temperature rise at this CFM is less than the maximum temperature rise. Heat output is based on heater operation in 100% outside
air mode.
**dBA is measured at 10' (3 m) from unducted discharge.
***Maximum Inlet Gas Pressure:ANSI - Compliant Manifold = 14 in wc (34.9 mbar)
FM and XL Compliant Manifold = 5 psi (344.7 mbar)
Heat Output @ Max.
Temperature Rise
(Btu/h) x 1000
Minimum Inlet
Gas Pressure
in wc (mbar)***
Manifold Size
in NPT (mm)
15 of 147
Page 26
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Table 9: Estimated Pressure Drop of Accessory Components
Failure to follow these instructions can result
in death, injury or property damage.
Spreader Bar
SECTION 6: LIFTING AN AIR HANDLER
The air handler must be installed in compliance with
all applicable codes. The qualified installer or service
technician must use best building practices when
installing the air handler and any optional equipment.
This piece of equipment requires at least 4 CFM (6.8
3
m
/h) of outside air per 1,000 Btu/h (0.293 kW). Any
air handler that recirculates air from the heated
space must use the return air opening to prevent any
return air from passing over the burner.
Before installation, check that the local distribution
condition, nature of gas and gas pressure, and the
current state of adjustment of the equipment are
compatible. If filters are not installed (via inlet hood or
filter section), an air strainer (provided by others)
must be installed on the inlet of the air handler with
openings less than or equal to 5/8" (16 mm) in
diameter. Air inlets must be installed in such a
manner that their lowest edge is 19" (500 mm) above
any surface. This applies to roof curbs, upright
stands and suspended air handlers.
6.1 Lifting an Air Handler
6.1.1 Preparing to Lift the Air Handler
Prior to lifting the air handler, the following steps must
be performed:
1. R e m o ve all packaging or banding that attached
the air handler to the skid and ensure that the
air handler is no longer bound to the skid.
2.Remove all of the accessories or packages that
were shipped on the same skid, inside the air
handler or inside the control enclosu
3.Inspect the air handler to:
•Verify that there is no damage as a result of
shipping.
•Ensure that it is appropriately rated for the utilities available at the installation site.
•Verify that the lifting lugs are intact
undamaged and secured to the air handler.
•Ensure factory-installed hardware is
torqued as specified.
4.Prepare the installation location to be ready to
accept the air handler (i.e. roof curb, mounting
stand or legs).
5.Verify the lifting equipment can handle the air
handlers weight and the required reach. See
Page 17, Figure 9. For air handlers weight, see
Page 12, Table 3 and Page 12, Table 4 for
model 2005. See Page 14, Table 6 and Page
14, Table 7 for models 2010 - 2030.
6.1.2 Lifting a Horizontal Air Handler (All Models)
Lift the air handler into place installing appropriate
hardware (supplied by others) into all lifting lug holes
on the unit base. For model 2005, lifting lug holes are
1.5" (3.81 cm) diameter. For models 2010 - 2030,
lifting lug holes are 2.0" (5.1 cm) diameter. Use
spreader bars to ensure that the lifting cables clear
the sides of the air handler. The air handler must be
kept level during the lift to prevent tipping, twisting or
falling. If lifted improperly, product damage may
occur.
Next, refer to the applicable portions of Page 19, Section 7 through Page 26, Section 10 for specific
mounting instructions. For mounting of accessories,
refer to the applicable portions of Page 29, Section 11 through Page 69, Section 14.
FIGURE 9: Lifting a Horizontal Air Handler
re.
17 of 147
Page 28
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Step 1
Remove These
Lifting Lugs
Step 2
Step 3
Step 4
Spreader Bar
INLET
INLET
INLET
INLET
6.1.3 Lifting an Upright Air Handler (2005 - 2030)
All air handlers are shipped in the horizontal position.
Prior to lifting an upright air handler, the following
steps must be performed (See Page 18, Figure 10):
Step 2: Remove the lifting lugs on the inlet end of the
air handler and re-install hardware.
Step 3: Use all four lifting lugs on the discharge end
of the air handler to enable the air handler to be lifted
into the upright position.
Step 1: The air handler must be lifted using the two
lifting lugs on the top of the discharge end and the
two lifting lugs on the inlet end, using a spreader bar
across the long axis. Lift the air handler off the skid
Step 4: Lift the air handler into upright position.
Step 5: Next, refer to the applicable portions of Page 22, Section 8 for specific mounting instructions.
and place it on a flat, clean, dry surface.
FIGURE 10: Lifting an Upright Air Handler (2005 - 2030)
18 of 147
Page 29
SECTION 7: ROOF CURB
SECTION 7: ROOF CURB
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Failure to follow these instructions can result in death, injury or property damage.
The roof curbs only support the burner and blower sections of the air handler. Roof curbs are shipped
unassembled and require field assembly.
NOTE: Before installation, verify that you have the correct roof curb and that all required components are
present. If any are missing, contact your RAPID
7.1 Roof Curb Assembly and Installation
Assemble roof curb according to the assembly drawing, on Page 20, Figure 11. Supplied hardware must be
torqued to recommended specifications on Page 9, Table 1.
Place the curb on the roof in the position in which it will be installed. Check that the diagonal measurements
are within 1/8" (3 mm) of each other. To ensure a weatherproof seal between the air handler and the curb,
the curb must be level with no twist from end to end. Shim level as required and secure curb to roof deck using best building practices. The curb is self-flashing. Install roofing material as required.NOTE: Check the installation location to ensure proper clearances to combustibles and clearance for
access. See Page 8, Section 3.1.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
®
independent distributor.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Equipment and
accessories are
heavy.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
19 of 147
Page 30
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
ModelPart NumberABCDWeight (lbs)Weight (kg)
2005
(in)
(cm)
77351.201
27.0
68.6
57.5
146.1
23.8
60.5
-7534
2010 and
2010B
(in)
(cm)
77050.301
42.0
106.7
88.0
223.5
38.8
98.6
-110 49.9
2020
(in)
(cm)
77250.301
53.0
134.6
113 . 0
287.0
49.8
126.5
56.5
143.5
15068. 0
2030
(in)
(cm)
77532
65.0
165.1
113 . 0
287.0
61.8
157.0
56.5
143.5
16072. 6
FIGURE 11: Roof Curb Assembly
7.2 Air Handler Mounting to Roof Curb
After the curb has been installed, the air handler may be placed on the curb. See Page 21, Figure 12. After
the air handler is in place, the installer must fasten the air handler to the curb. This is accomplished by drilling
holes down through the floor of the air handler and into the curb. At least three #12 sheet metal screws
(supplied by others) equally spaced on each side must be used to attach the air handler to the curb. After the
curb has been installed, the air handler may be placed on the curb. There must be a 1/8" (.3 cm) x 2" (5.1
cm) neoprene closed cell, adhesive-back gasket (supplied by others) between the top of the curb and the
base surface of the air handler to prevent moisture from leaking into the building from either driving rains or
melting snow.
The installer is responsible for tying the air handler to the curb per all applicable codes.
20 of 147
Page 31
FIGURE 12: Curb Mounting
Air Handler
Roof Curb
Fastening Detail
SECTION 7: ROOF CURB
21 of 147
Page 32
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Foam Tape
Upright Stand
Attaching Locations
Foam Tape
Upright Stand
Attaching Location
SECTION 8: UPRIGHT STAND
WARNING
A stand can be used when an upright air handler is to
be installed on a concrete slab or on the floor. The
stand for model 2005 is 30" (76.2 cm) tall; stands for
models 2010 and 2010B are available at 53" (134.6
cm) or 72" (182.9 cm) tall; stands for models 2020
and 2030 are 72"(182.9 cm) tall. The stand must first
be fastened to the concrete slab or floor before the air
handler is mounted.
8.1 Upright Stand Installation
To attach the stand to a concrete slab, it must be
secured with the use of studs, embedded in the
concrete. Four 5/8" studs (minimum) must be
installed in the slab, one for each corner of the stand.
The stand has four 11/16" (17.4 mm) holes drilled
through the stand pads. See Page 23, Figure 16.
Fasten the stand to the slab with four 5/8" hex nuts
and lock washers (provided by others).
8.2 Attaching Air Handler to Stand
Once the stand is secured to a concrete slab, the air
handler may be placed on the stand. Prior to lifting
the air handler, apply the foam tape and remove the
attaching hardware as described below. The ½"
(12.7 mm) thick double-sided urethane foam tape
(provided by others) must be applied to the top edge
of the stand. The bolts on the air handler that
correspond to the attaching location of the mounting
stand must be removed and saved for re-installation
to sec
handler on to the mounting stand. See Page 17, Section 6.1 for safe lifting practices. Once the air
handler is placed on the stand, secure it with the
attaching hardware that was removed prior to lifting it
in to place per recommended torque settings. See
Page 9, Table 1. See Page 22, Figure 13 (2005) and
Page 22, Figure 14 (2010 - 2030). After placing the
air handler on the mounting stand, seems between
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
Failure to follow these instructions can result in death, injury or property damage.
the mounting stand and the air handler must be
properly caulked (caulk provided by others).
NOTE: If using a filter section with an upright air
handler and stand, the filter section must be set into
the stand before the air handler is mounted on the
stand. The 1/2" (12.7 cm) thick double-sided
urethane foam tape should be applied between the
stand and the filter section. See Page 43, Section
11. 6.
FIGURE 13: Upright Stand Detail (2005)
FIGURE 14: Upright Stand Detail (2010 - 2030)
ure the air handler to the stand. Lift the air
22 of 147
Page 33
FIGURE 15: Stand Shim (2010B - 2030)
NOTE: Quantity 8 required
per stand.
ModelPart NumberHeightABWeight (lbs) Weight (kg)
2005
(in)
(cm)
94000.3
30.0
76.2
27.1
68.9
22.8
57.8
75.034.0
2010 and
2010B
(in)
(cm)
91000.2
53.0
134.6
27.8
70.5
39.3
99.7
160.072.6
(in)
(cm)
94000.7
72.0
182.9
27.8
70.5
39.3
99.7
190.086.2
2020
(in)
(cm)
92000.3
72.0
182.9
51.1
129.8
51.5
130.8
230.0104.3
2030
(in)
(cm)
93000.3
72.0
182.9
63.5
161.3
55.8
141.6
300.0136.1
SECTION 8: UPRIGHT STAND
FIGURE 16: Upright Stand Mounting Detail
A
Non-Control Enclosure Side
Air Handler
Control Enclosure Side
B
Air Handler
23 of 147
Page 34
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
SECTION 9: LEGS
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Failure to follow these instructions can result in death, injury or property damage.
Part numbers that end with a “[W]” indicate that the
part can be ordered with either an unpainted
galvanized finish or an acrylic modified alkyd enamel
finish. To order with a galvanized finish, do not
include the "W" at the end of the part number; to
order with a painted finish, include the "W" at the end
of the part number.
9.1 Leg Mounting
Legs can be used when mounting an air handler on a
concrete slab or directly on the floor. Legs are
available for all models in the horizontal
configuration.
9.2 Leg Mounting - Horizontal Air Handler
(2005 - 2030)
The 46" (116.8 cm) legs must first be mounted to the
air handler before being mounted to the concrete
slab or floor. To attach the legs with the air handler
must first be lifted with the provided lifting lugs. See Page 17, Section 6.1 for safe lifting practices. In each
corner of the bottom of the air handler, four legmounting holes will be found. See Page 24, Figure
17.
The legs can now be mounted one at a time to the
inside of the corner by removing the hard
ware that
occupies each of the bolt locations. Place the leg on
the inside of the corner and attach with the previously
removed hardware. Missing hardware needs to be
added at each bolt location. The required hardware is
a 5/16"-18 x 1" grade 5 bolt, a 5/16" flat washer, and
a 5/16"-18 grade 5 flange nut.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
On models 2020 and 2030, there is a bracket on the
inside of each corner that is held in place by the two
bolts closest to the corner. This bracket must be
removed when the leg is attached to the air handler.
Bracket can be discarded once legs are attached.
FIGURE 17: Leg Mounting Holes (2005 - 2030)
10"
(25.4 cm)
1.5"
(3.8 cm)
1.5"
(3.8 cm)
To attach the legs to a concrete slab, the base of
each leg is equipped with two 1" holes. Studs
capable of accepting 5/8" nuts must be installed in
the concrete slab. For stud positioning, See Page 25, Figure 18.
The air handler may now be placed down over the
slab studs. The legs should then be bolted down with
5/8" nuts. See Page 25, Figure 19.
10"
(25.4 cm)
24 of 147
Page 35
FIGURE 18: Stud Positioning
ModelPart NumberABCWeight* (lbs) Weight* (kg)
2005
(in)
(cm)
77040.301[W]
38.8
98.5
10.8
27.4
9.5
24.1
26.011.8
2010 and
2010B
(in)
(cm)
77040.301[W]
71.0
180.3
23.5
59.7
9.5
24.1
26.011.8
2020
(in)
(cm)
77040.301[W]
95.0
241.3
35.0
88.9
9.5
24.1
26.011.8
2030
(in)
(cm)
77040.301[W]
95.0
241.3
47.0
119 . 4
9.5
24.1
26.011.8
B
C
C
C
AC
*NOTE: Weight
shown reflects
per each leg.
46"
(116.8cm)
14.6"
(37.1 cm)
1.0"
(2.5 cm)
10.5"
(26.7 cm)
SECTION 9: LEGS
FIGURE 19: Leg Bolt Detail
25 of 147
Page 36
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Crush Hazard
Check blower assembly per
maintenance section.
Lack of blower assembly
maintenance can cause
excessive vibration.
Excessive vibration can
cause support failure.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Crush Hazard
Hanging hardware must
support equipment weight.
Do not hang by lifting lugs.
Crush Hazard
Use proper lifting equipment and practices.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Falling Hazard
Use proper safety
equipment and practices to
avoid falling.
Severe Injury Hazard
Use proper lifting practices
and equipment.
Equipment and accessories
are heavy.
Cut/Pinch Hazard
Wear protective gear during
installation, operation and
service.
Edges are sharp.
SECTION 10: INDOOR SUSPENSION MOUNTING - HORIZONTAL AIR HANDLER
Suspension Kits are available for models 2005 2010B. Kits are shipped unassembled and must be
assembled prior to installation. Suspension Kits for
models 2020 - 2030 are not available.
NOTE: Before installation, verify all required
components are present. If any are missing, contact
your RAPID
10.1 Suspension Kit Assembly and Installation
After the air handler is in place, the installer must
fasten the air handler to the suspension frame. Once
the suspension frame is secure, the air handler may
be mounted. See Page 17, Section 6 for safe lifting
practices.
26 of 147
®
independent distributor.
On model 2005, remove the 1/4" bolts from four
corners of base on length of air handler. Slide
suspension angle assembly onto both ends of the air
handler aligning holes in angle tab with bottom holes.
Once completed, reinstall hardware. See Page 27, Figure 20.
On model 2010 and 2010B, drilling holes down
through the floor of the air handler and into the
suspension frame. At least three #12 sheet metal
screws (supplied by others) equally spaced on each
angle/side must be used to attach the air handler to
the suspension frame. See Page 28, Figure 21.
SECTION 10: INDOOR SUSPENSION MOUNTING - HORIZONTAL A IR HANDLER
27 of 147
Page 38
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
A
B
E
C
D
Suspension Sides
Suspension End
Suspension End
B
D
A
Gasket Tape*
Single Nut*
Double Nuts*
E
E
E
B
1/2" x 13 Threaded Rod and Nuts
Not Supplied by manufacturer.
Nuts and bolts provided
*Provided by others
DescriptionPart NumberQty.
2010 and 2010B Suspension Kit77046.301
Suspension Sides77047.1032
Suspension Ends77047.1062
1/2"-13 x 1 Bolt HHCS205244
Nut Flange 1/2-13204934
3/4" x 1/8" Gasket Tape9270001715' (5 m)
ModelABCDEWeight (lbs)Weight (kg)
2010 and
2010B
(in)
(cm)48121.946116 . 890228.642106.712.5
14063.5
FIGURE 21: Indoor Suspension (2010 and 2010B)
28 of 147
Page 39
SECTION 11: FILTER SECTION
SECTION 11: FILTER SECTION
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
Failure to follow these instructions can result in death, injury or property damage.
The 2005 filter section is shipped assembled. The 2010 - 2030 filter sections are shipped unassembled and
must be assembled prior to installation.
Part numbers that end with a “[W]” indicate that the part can be ordered with either an unpainted galvanized
finish or an acrylic modified alkyd enamel finish. To order with a galvanized finish, do not include the "W" at
the end of the part number; to order with a painted finish, include the "W" at the end of the part number. If the
filter section support is necessary, it may be installed prior to attaching the filter section to the air handler.
See Page 41, Section 11.4.
NOTE: Check to be sure that all required components are present. If any are missing, contact your RAPID
independent distributor.
11.1 Filter Section (2005)
Part Number DescriptionABC
B
C
77082.301[W]
77083.301[W]
Filter section with
permanent alumi-
num mesh filters
Filter section with
disposable polyester filters
in 28.3 27.0 32.3
cm 71.9 68.6 82.1
Weights
lbskg
10045.4
®
A
Filter access through
side access door.
Inlet
Filter
Filter SizeQuantityPart Number
in20 x 25 x 2
cm50.8 x 63.5 x 5.1
in20 x 50 x 1
cm50.8 x 127 x 2.5
222628
123628
29 of 147
Page 40
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
11.2 Filter Section Assembly (2010 and 2010B)
Filter Section with
DescriptionPart Number
Disposable Polyester Filters 20" x 40" x 1"236294N/A
Permanent Aluminum Mesh Filters 20" x 20" x 1"20628N/A8
Insulated Access Cover77401.002[W]11
Header Panel77402.002[W]11
Right Panel77403.001[W]11
Left Panel77403.002[W]11
Channel77404.00233
Support77405.00222
End Panel77406.002[W]11
Stiffener77407.002[W]11
Screw TEK3 #12 x 3/4" Washer HD134043838
Nut ¼"-20 Speed Grip2049944
Bolt ¼"-20 x ¾" HHCS2050444
¼" Flat Washer2050344
Fastener Rivnut 3/8"-16911201061010
3/8" Flatwasher205151010
3/8"-16 x 1" Bolt Hex Grade 5205171010
Disposable Polyester Filters
77080.301[W]77081.301[W]
QuantityQuantity
Permanent Aluminum Mesh Filters
Filter Section with
30 of 147
Page 41
Step 11.2.1
Flange
End Panel
Side Panel
Side Panel
Insert Screws
Attach left panel and right panel to
the end panel outside mounting
flanges. Fasten together with 6 TEK
screws on each side as shown.
DescriptionPart Number
Left Panel77403.002[W]
Right Panel77403.001[W]
End Panel77406.002[W]
TEK Screw13404
Supports
Insert Screws
Insert Screws
Make sure that the bottom
flanges are facing out.
Attach supports to top inside of
the left and right panels, making
sure that the channel portion is
facing down into the filter
section.
DescriptionPart Number
Supports77405.002
TEK Screw13404
Step 11.2.2
SECTION 11: FILTER SECTION
31 of 147
Page 42
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Attach channels to end plate. Make
sure top channel is facing down and
bottom channels are facing up.
NOTE: Channels "open" to the
inside of the filter box.
DescriptionPart Number
Channels77404.002
TEK screw13404
Stiffener
Header Panel
Attach header in between the lower
portion of the left and right side
panels.
Attach stiffener in between top
portion of left and right side panels.
Attach loose end of upper filter
channel to stiffener; attach loose
end of lower filter channels to
header piece.
On the inlet of the filter section,
rivnuts (P/N 91120106) are factory
installed. With additional 3/8"
hardware (P/N 20515 and
P/N 20517) the filter section can be
installed on the inlet of the unit. See Page 43, Section 11.5 for additional
information on filter section
installation.
NOTE: For easier installation, the
filter section may be mounted to the
air handler at this point, prior to the
addition of filters and access door.
Refer to Page 43, Figure 11.5 for
installation instructions.
DescriptionPart Number
Header Panel77402.002[W]
Stiffner77407.002[W]
TEK screw13404
Step 11.2.3
Step 11.2.4
32 of 147
Page 43
Step 11.2.5
Slide filters into channels. Verify
proper filter orientation.
For permanent aluminum mesh
filters: Verify the arrow on the side
of the filter points in the direction of
the airflow.
For disposable polyester filters:
Verify the white side is facing the
inlet and the blue side is facing the
discharge end.
Install cage nuts into each of the
four corresponding square holes
(two in stiffener, two in header
panel) with the cages on the inside
of the filter section.
Install insulated access cover and
secure with four ¼-20 screws, ¼-20
bolts and ¼" washers.
Access Door1330502511
Right Panel1330502611
Left Panel1330502811
Top/Bottom Panel1330502922
Filter Rail1330503077
Side Filter Rail1330503122
Screw TEK3 #12 x ¾" Washer HD134048686
Nut ¼"-20 Speed Grip2049933
Hinge Butt 3 x 3 Zinc2050022
¼" Flat Washer2050333
Bolt ¼"-20 x ¾" HHCS2050433
Bolt Retainer Pushnut 1/42050533
3/8" Flatwasher205151414
3/8"-16 x 1" Bolt Hex Grade 5205171414
10-24 KEPS Nut206981212
Permanent Aluminum Mesh Filter 20" x 20" x 1" 2062816N/A
Permanent Aluminum Mesh Filter 20" x 25" x 1" 206298N/A
Disposable Polyester Filter 20" x 60" x 1"23631N/A8
Bolt 10-24 x ¾" HHCS2169966
10-24 x ½" HMS Bolt2700066
Fastener Rivnut 3/8"-16911201061414
Spacer Hinge Filter1320503288
Gasket Door Filter132050351212
Part
Number
13305022 (Galvanized)
13305023 (Painted)
QuantityQuantity
13305020 (Galvanized)
13305021 (Painted)
34 of 147
Page 45
SECTION 11: FILTER SECTION
Top Panel
Side (Left) Panel
Top Panel
Side
Panel
For Model 2020: On a flat, clean and dry surface, attach the
top panel and side panel of the filter section using five TEK
self-tapping screws.
For Model 2030: On a flat, clean and dry surface, attach the
top panel and side panel of the filter section using seven TEK
self-tapping screws.
DescriptionPart Number
Top Panel13X05029
Side (Left) Panel13X05028
TEK Screw13404
Note: In the instructions, an "X" in a part number indicates a digit that changes based on model. Replace
the "X" with a "2" for model 2020; replace the "X" with a "3" for model 2030. For further clarification,
reference the individual table of components for each assembly at the begining of the instructions.
Step 11.3.1
35 of 147
Page 46
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
To p
Panel
Side (Left) Panel
Bottom Panel
Side (Right) Panel
Top Panel
Side (Right) Panel
For Model 2020: Attach the bottom panel with five TEK self-tapping
screws. Attach the right panel with five TEK self-tapping screws on
each side.
For Model 2030: Attach the bottom panel with seven TEK self-
tapping screws. Attach the right panel with seven TEK self-tapping
screws on each side.
DescriptionPart Number
Bottom Panel13X05029
Side (Right) Panel13X05026
TEK Screw13404
Step 11.3.2
36 of 147
Page 47
Step 11.3.3
Side Filter Rail
Top Panel
Top Panel
Top Panel
2030
2020
OutsideInside
Discharge End
To Unit
Inlet End
For Model 2020: Attach the side filter rail to the top panel
with five TEK self-tapping screws. Line up filter rail holes
with provided holes near the discharge end of the filter
section panel.
For Model 2030: Attach the side filter rail to the top panel
with six TEK self-tapping screws. Line up with provided
holes near the inlet end of the filter section.
DescriptionPart Number
Side Filter Rail13X05031
TEK Screw13404
SECTION 11: FILTER SECTION
37 of 147
Page 48
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Discharge End
To Unit
Side Filter Rail
Bottom Panel
Bottom Panel
2030
2020
OutsideInside
Inlet End
Bottom Panel
For Model 2020: Attach the side filter rail to the bottom panel
with five TEK self-tapping screws. Line up filter rail holes with
provided holes near the discharge end of the filter section
panel.
For Model 2030: Attach the side filter rail to the bottom panel
with seven TEK self-tapping screws. Line up with provided
holes near the inlet end of the filter section.
DescriptionPart Number
Side Filter Rail13X05031
TEK Screw13404
Step 11.3.4
38 of 147
Page 49
Step 11.3.5
Attach the remaining filter rails with four TEK
self-tapping screws, two on each side. Ensure
that the rails face into the filter section.
NOTE: For easier installation, the filter section
may be mounted to the air handler at this point,
prior to the addition of filters and access door.
Refer to Page 43, Section 11.5 for installation
instructions.
DescriptionPart Number
Filter Rail13X05030
TEK Screw13404
Load filters into the filter section.
Check that each filter in in the proper
orientation.
For permanent aluminum mesh
filters: Verify the arrow on the side of
the filter points in the direction of the
airflow.
For disposable polyester filters:
Verify the white side is facing the inlet
and the blue side is facing the
discharge end.
The end rows of filters need to be
installed first.
NOTE: When the filter section is
installed on the air handler, the top of
one row of filters will support the
bottom of the above row.
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Door Panel
Gasket
Bolt
Filter Box
Panel
Grip Nut
Door Panel
Filter Section
Panel
Hinge
Gasket
Spacers
Duct
Liner
Push Nut
Washer
Hinges
Right Panel
Bolt Holes
On right panel, apply provided gasket material to the filter access
opening.
Attach filter access door with two hinges.
Attach the hinges to the door using three 10-24 x 1/2" bolts and
10-24 nuts. Attach the hinge to the filter section right panel using
three 10-24 x 3/4" bolts and 10-24 nuts. Use four hinge spacers
between the hinge and the right panel to keep the hinge aligned.
Press the ¼-20 grip-nuts into each of the three square cut outs in
the filter section right panel on the opposite side of the filter access
opening from the hinges.
Place a ¼" washer on a ¼-20 bolt and insert it into one of the three
bolt holes on the door panel. Place a push-nut on to the bolt from
the inside of the door panel to keep the bolt from being separated
from the door panel when it is open. Repeat for the other two bolt
holes. Secure the door in the closed position by threading the
three bolts in the door panel to the grip-nuts on the filter section
right panel.
On the inlet of the filter section, rivnuts (P/N 91120106) are factory
installed. With additional 3/8" hardware (P/N 20515 and
P/N 20517) the filter section can be installed on the inlet of the
unit. See Page 43, Section 11.5 for additional information on filter
section installation.
DescriptionPart Number
Gasket Material13205035
Filter Access Door13X05025
Hinge20500
10-24 x ½" Bolt27000
10-24 Nut20698
Hinge Spacers13205032
10-24 X ¾" Bolt21699
¼-20 Grip-Nut20499
¼" Washer20503
¼-20 Bolt20504
Push-Nut20505
Step 11.3.7
40 of 147
Page 51
SECTION 11: FILTER SECTION
11.4 Filter Section Support Assembly
The filter section support assembly is used to add additional support to the air handler accessories that are
not supported by the roof curb in a horizontal configuration (support leg for use with standard 46" [116.8 cm]
legs provided by others). For Models 2010 - 2030, when the air handler has both a filter section and an inlet
hood, a filter section support assembly or its equivalent must be used.
Description
Filter Box Suppor t Base 2010 and 2010B774080011N/AN/A
Filter Box Suppor t Base 202077408002N/A1N/A
Filter Box Suppor t Base 203077408003N/AN/A1
Filter Box Suppor t Leg LS 2010 - 203077408011111
Filter Box Suppor t Leg RS 2010 - 203077408012111
Filter Box Suppor t Ext LS,RS 2010 - 203077408021222
Filter Box Suppor t Brace 2010 And 2010B774080311N/AN/A
Filter Box Suppor t Brace 202077408032N/A1N/A
Filter Box Suppor t Brace 203077408033N/AN/A1
Screw Tek3 #12x3/4 Washer13404111416
1/4-20 x 1/2 Bolt Hex Head Cap Screw20483888
1/4-20 Nut Flange20630888
1/4 Flat Washer20503888
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Support Leg
Left Side
Support Leg
Right Side
Support Base
Extension Arm
Left Side
Support Extension
Cross Brace
NOTE: 1) CONTRACTOR/INSTALLER MUST MAKE
APPROPRIATE ALLOWANCES FOR DUCT
CONNECTIONS.
2) SUPPORT LEG IS REQUIRED WHEN A FILTER
SECTION AND INLET HOOD ARE ORDERED.
A
CC
B
FILTER SECTION
3) SUPPORT LEG IS PROVIDED FOR USE WITH
STANDARD 19" (50 cm) ROOF CURB. SUPPORT
LEG FOR USE WITH STANDARD 46" (116.8 cm)
LEGS PROVIDED BY OTHERS.
ModelPart NumberA MinA MaxBCWeight lbs (kg)
2010 and
2010B
77412.001
in16.024.038.81.5
16 (7.3)
cm40.560.898.43.7
202077412.002
in16.024.049.61.5
18 (8.2)
cm40.560.8126.03.7
203077412.003
in16.024.064.11.5
20 (9.1)
cm40.560.8162.73.7
11.4.1 Filter Section Support Assembly Installation (2010 - 2030)
It is best to assemble the support base and support arms to the filter section prior to attaching the filter
section to the air handler but can also be assembled to a previously installed filter section. Refer to Page 42, Figure 22.
FIGURE 22: Filter Section Support Assembly
Step 1: Place the support base (P/N 7740800X) up to the bottom of the filter section towards the inlet end
and line up the pre-drilled holes. Use TEK self-tapping screws (P/N 13404) in the middle of the support base
(P/N 7740800X) to secure the support base in place.
Step 2: Line up the pre-drilled holes at the ends of the support base, the filter section and the support legs
(P/N 7740900X) and attach the legs to the bottom of the filter section through the support base with TEK selftapping screws (P/N 13404). Install TEK self-tapping screws (P/N 13404) at each of the remaining hole
locations in the support base.
Step 3: Mount the filter section to the air handler as described on Page 43, Section 11.5.
Step 4: Line up the support extension (P/N 77410001) with the left support leg (P/N 77409001) and select the
appropriate height alignment. Attach the support extension and left support legs and support brace
(P/N 774110X) at the lowest overlap position with one ¼-20 bolt (P/N 20483) and flange nut (P/N 220630) on
the front surface. Install a second ¼-20 bolt (P/N 20483) and flange nut (P/N 220630) directly above the first,
securing all three parts together.
Repeat step 4 on the right side of the su
42 of 147
pport assembly.
Page 53
SECTION 11: FILTER SECTION
Air Handler
Filter Section
11.5 Filter Section Installation - Horizontal Air
Handlers
11.5.1 Filter Section Installation (2005)
For installation directly onto the inlet of the air
handler, remove the hardware on the inlet surface of
the air handler that would prevent the filter section
from being mated to the inlet of the air handler. Use
the provided shims (one bottom and two sides) to
reduce the size of the gap between the air handler
and the filter section. Re-install the hardware (that was removed) through the filter section and the
shims to mate the air handler to the filter section.
Hardware must be torqued to recommended
specifications on Page 9, Table 1. Caulk (provided by
others) the sides, roof and bottom seams between
the filter section and air handler. Apply 3" zip tape
(provided by others) over the roof seam. Install the
filters in proper orientation (See Page 130, Section
20.6) and attach the filter access door. Secure filter
access door in the closed position.
11.5.2 Filter Section Installation (2010 - 2030)
For installation directly onto the inlet of the air
handler, foam tape (provided by others) must be
applied to the air handler sides and bottom. To place
the filter section, the top flange of the filter section will
slide up under the top panel (drip edge) of the air
handler. Refer to Page 43, Figure 23. All hardware in
this top panel drip edge will need to be removed prior
to placing the filter section on the air handler. Attach
the sides of the filter section to the factory installed
riv-nuts on the inlet of the air handler w
ith the
supplied hardware. Re-install the hardware from the
top panel of the air handler through the top panel and
top flange of the filter section. Additional TEK screws
may be used along the bottom flange of the filter
section to seal the bottom seam. Caulk (provided by
others) the side and bottom seams between the filter
section and air handler. If the filter section was
installed prior to completing the filter section
assembly, return to the filter section assembly
instructions to complete the assembly. See Page 33,
Figure 11.2.5 for Models 2010 and 2010B or Page 39,
Figure 11.3.6 for Models 2020 and 2030.
FIGURE 23: Filter Section Installation on Horizontal Air Handler (2010 - 2030)
11.6 Filter Section Installation - Upright Air
Handlers
11.6.1 Filter Section Installation (2005)
For installation directly onto the inlet of the air
handler, remove the hardware on the inlet surface of
the air handler that would prevent the filter section
from being mated to the inlet of the air handler. Use
the provided shims (one bottom and two sides) to
reduce the size of the gap between the air handler
and the filter section. Re-install the hardware (that was removed) through the filter section and the
shims to mate the air handler to the filter section.
Caulk (provided by others) the sides, roof and bottom
seams between the filter section and air handler.
Install the filters in proper orientation (See Page 130, Section 20.6) and attach the filter access door.
Secure filter access door in the closed position.
11.6.2 Filter Section Installation (2010 - 2030)
To install a filter section on an u
pright air handler that
is stand mounted, the filter section must be installed
in the stand prior to placing the air handler (See Page 22, Section 8 for proper stand mounting). Place the
filter section so that the outward flange is on the top
side. Set the filter section into the stand. Place ½"
foam tape (supplied by others) along the perimeter of
the top of the flange. Place the air handler in the
stand per the stand mounting instructions.
43 of 147
Page 54
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Filters load from topside,
remove the filter cap
to access the filters.
Note: Inlet hood is also available with screen mesh, no filters (P/N 13405059).
SECTION 12: INLET HOOD
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
Failure to follow these instructions can result in death, injury or property damage.
Inlet hoods are shipped unassembled and must be assembled prior to installation. The inlet hood may be
installed either onto the inlet of the air handler or to an outside wall. After installing an inlet hood, all hardware
must be torqued according to recommended specifications on Page 9, Table 1. In addition, all seams must
be caulked (provided by others).
Part numbers ending with a "[W]" indicate that the part can be ordered with either an unpainted galvanized
finish or an acrylic modified alkyd enamel finish. To order with a galvanized finish, do not include a "W" at the
end of the part number; to order with a painted finish, include a "W" at the end of the part number.NOTE: Check to be sure that all required components are present. If any are missing, contact your RAPID
Filter Rail Assembly1350506622N/A
Top Inner Rail13505068111
Bottom Rail Assembly1350507211N/A
Top Back Panel13505075111
Top Front Panel1350507611N/A
Left Panel13505080111
Right Panel13505081111
Upright Mount13505090222
Horizontal Mount13505091222
Drip Rail13505092222
TEK Screw134048210592
5/16-18 x 1 Bolt HHCS Grade 520507555
5/16 Flat Washer95211600555
5/16 Nut Flange20509555
Permanent Filter 20" x 20" x 1"206286N/AN/A
10-24 KEPS Nut2069888N/A
A1 Snap Fastener209006N/AN/A
10-24 x 1/2 HMS Bolt2700088N/A
Fastener Rivnut 3/8-1691120106101010
3/8 Flatwasher20515101010
3/8-16 x 1 Bolt Hex Grade 520517101010
Foam Tape9270001714ft14ft14ft
Horizontal Mount for Birdscreen13505087N/A2N/A
Screen 38.75" x 59"90740051N/A1N/A
Fender Washer 1/4 x 195211550N/A12N/A
Bottom Rail Assembly - ML13505095N/AN/A1
Top Front Panel - ML13505096N/AN/A1
Inner Support Rail - ML13505097N/AN/A1
Outer Suppor t Rail - ML13505098N/AN/A1
Side Cover - ML13505099N/AN/A2
Moisture Limiter Media 12" x 60" x 5.5"90740001N/AN/A3
Part
Number
Aluminum Mesh Filters
13505060 (Galvanized)
13505061 (Painted)
QuantityQuantityQuantity
Inlet Hood Without Filters,
With Birdscreen
13505058 (Galvanized)
13505059 (Painted)
Inlet Hood with
Moisture Limiter
13505062 (Galvanized)
13505063 (Painted)
45 of 147
Page 56
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Air Handler
Air Handler Top Panel
Horizontal Mount
Horizontal Mount
Without
Filter Section
Air Handler
With
Filter Section
Inlet Hood
Horizontal Mount
Horizontal Mount
Inlet Hood
Filter
Box
Air Handler
Without Filter Section
Without Filter Section
Air Handler
Filter Box
With Filter Section
With Filter Section
External Support
SIDE VIEWSIDE VIEW
TOP VIEWTOP VIEW
Upright Mount
Upright Mount
For an air handler without a filter section:On the inlet of the air handler, install horizontal and upright
mounts. The mounts will be installed via angles open towards the outside of the air handler.
For an air handler with a filter section: First, attach the filter section to the air handler. Then, bolt the
inlet hood horizontal and upright mounts to the inlet of the filter section with the angles opening towards
the inside of the filter section.
Upright mounts (P/N 13505090) are attached with five 3/8-16 bolts (P/N 20517) and flat washers
(P/N 20515) each; the receiving riv-nut (P/N 91120106) will be factory installed on the air handler or filter
section. Horizontal mounts (P/N 13505091) are attached using five TEK self-tapping screws (P/N 13404).
Prior to installing the mounts, seal the gap between the mating surfaces of the air handler/filter section
and the mounts with the provided foam tape (P/N 92700017).
When installing the top horizontal mount directly to the air handler without a filter section, foam tape
should NOT be used. In this case, the hardware on the lip of the air handler roof panel should be removed,
the mount slid under the lip and hardware re-installed. Foam tape to be used on remaining three sides.
To install inlet hood on an exterior wall, drill holes ev
ery 8" (20.3 cm) in the flanges of the inlet hood and
mount with lag bolts (provided by others).
Step 12.2.1
46 of 147
Page 57
Step 12.2.2
Right Panel
Left Panel
Attach left panel and right to each side flange of the air
handler/filter section using five TEK self-tapping screws.
Ensure that the flanges on the panels break inward.
DescriptionPart Number
Left Panel13505080
Right Panel13505081
TEK Screw13404
Screws
Bottom Rail
Attach the bottom panel to the bottom attaching flange with five TEK self-tapping screws and to
each side panel with two TEK self-tapping screws. Ensure that the side tabs of the bottom panel
are to the inside of the side panels.
DescriptionPart Number
Bottom Rail13505072/13505095
TEK Screw13404
SECTION 12: INLET HOOD
Step 12.2.3
47 of 147
Page 58
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Top Front
Panel
Attach top front panel to the sidewall panels using four
TEK self-tapping screws on each side. Ensure that the side
tabs of the top panel are to the outside of the side panels.
DescriptionPart Number
Top Front Panel13505076/13505096
TEK Screw13404
Top Front Panel
Top Inner Filter Rail
Top Front Panel
Bottom Rail
Right
Panel
Left
Panel
Top Inner Filter Rail
SIDE VIEWREVERSE INLET VIEW
Attach the top inner filter rail to the inside of the front top panel using four TEK self tapping screws.
Ensure that the rail is installed with the ends tight against the flanges of the sidewall panels and the
angle opening toward the inside of the inlet hood.
DescriptionPart Number
Top Inner Filter Rail13505068
TEK Screw13404
Step 12.2.4
Step 12.2.5
48 of 147
Page 59
Step 12.2.6
Top Back Panel
J-Bend
Attach top back panel with four TEK self-
tapping screws on each side, with five TEK self-tapping
screws to the top attaching flange and with five 5/16-18 x 1
hex head cap screws, 5/16 washers and 5/16 flange nuts at
the J-bend joint. Ensure that the side tabs of the roof panel
are to the outside of the side panels and that the J-bend
interlocks with the front roof panel.
DescriptionPart Number
Top Back Panel13505075
TEK Screw13404
5/16-18 x 1 Hex Head Cap Screw20507
5/16 Washer95211600
5/16 Flange Nut20509
SIDE VIEW
Birdscreen
Horizontal Mount
Install horizontal mounting brackets for birdscreen on to face of inlet hood. Mount birdscreen with brackets
and secure with self tapping screws and washers.
DescriptionPart Number
Horizontal mount for birdscreen13505087
Screen90740051
TEK Screw13404
SECTION 12: INLET HOOD
For inlet hoods with permanent aluminum mesh filters, continue to step 12.2.8.
For inlet hoods with birdscreen, no filters, continue to step 12.2.7.
For inlet hoods with moisture limiter, continue to step 12.2.9.
Step 12.2.7
49 of 147
Page 60
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Double Sided
Filter Rail
Filter Clip
Double Sided Filter Rail
Attach the double-sided filter rails horizontally to the face of the inlet hood using two #10-24 x ½" bolts and
#10-24 nuts on each side. When attaching the filter rails, insert the bolt from the inside of the filter rail to
allow for maximum clearance for the filters. Attach the snap fastener with one TEK self-tapping screw
each. (First remove the washer as the washer will restrict the snap fastener, making it difficult to open.)
NOTE: Inlet hood with birdscreen does not require filters or snap fasteners.
DescriptionPart Number
Double-Sided Filter Rails13505066
#10-24 x 1/2" Bolt27000
#10-24 Nut20698
Snap Fastener20900
TEK Screw13404
Caulk the seams between the inlet hood and the air handler/filter section and on the open sides of
the J-bend that lock the roof panels together.
Step 12.2.8
Step 12.2.9
Caulk
Caulk
50 of 147
Page 61
Step 12.2.10
Drip Rail
Attach drip rail to each side using five TEK self-tapping screws for each drip rail. Ensure that the drip
rails are positioned above the filter clips (where applicable), using the provided holes in the sidewall
panels. Apply caulk to the drip rails before attaching to the side panels.
NOTE: Double sided filter rails or snap fasteners are not required for inlet hood with moisture limiter.
DescriptionPart Number
Drip Rail13505092
TEK Screws13404
Filter
Load filters into the inlet hood, checking to see that each filter is in the proper orientation by
verifying that the arrow on the side of the filter points in the direction of air flow. All of the arrows
should be pointing towards the air handler when installed in the proper orientation. Once filters are
installed, close filter clips installed previously (See Page 50, Step 12.2.8) to hold filters in place.
Description SizePart Number
Permanent Aluminum Mesh Filter
in20 x 20 x 1
20628
cm 50.8 x 50.8 x 2.5
SECTION 12: INLET HOOD
For inlet hoods with permanent aluminum mesh filters, continue to step 12.2.11.
For inlet hoods with birdscreen, no filters, the instructions end here.
For inlet hoods with moisture limiter, continue to step 12.2.12.
Step 12.2.11
For inlet hoods with permanent alumimum mesh filters the instructions end here.
51 of 147
Page 62
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Moisture Limiter Side Cover
Attach side cover of moisture limiter frame to the left side
of the inlet hood rain gutter using eight TEK screws.
Attach to the bottom pan assembly with two #10-24 x ½"
bolts and #10-24 nuts.
DescriptionPart Number
Side Cover (ML)13505099
TEK Screw13404
#10-24 x ½" Bolt27000
#10-24 Nut26098
Inner Support
RailMoisture Limiter
Side Cover
Place the moisture limiter inner support rail under the top
flange of the moisture limiter frame side cover and to the top of
the inlet hood. Attach to the top of the inlet hood using nine
#10-24 x ½" bolts and nine #10-24 nuts. Attach to the left side
of the frame using two #10-24 x ½" bolts and two #10-24 nuts.
DescriptionPart Number
Inner Support Rail13505097
TEK Screw13404
#10-24 x ½" Bolt27000
#10-24 Nut26098
Step 12.2.12
Step 12.2.13
52 of 147
Page 63
Step 12.2.14
Moisture Limiter
Media
Insert the 3 pieces of 12" (30.5 cm) x 60" (152.4 cm)
moisture limiter media from the right side with the
long dimension running top to bottom.
DescriptionPart Number
Moisture Limiter Media90740001
Moisture Limiter
Side Cover
Outer Support Rail
Place the moisture limiter frame side cover in order to have the
flange at the top overlap the top of the frame. Attach to the inlet
hood rain gutter using eight TEK screws. Attach to the bottom
pan assembly and top with two #10-24 x ½" bolts and #10-24
nuts each. Attach front stiffeners to the left and right side of the
moisture limiter frame using four TEK screws for each support.
DescriptionPart Number
Side Cover (ML)13505099
Outer Suppor t Rail13505098
TEK Screw13404
#10-24 x 1/2" Bolt27000
#10-24 Nut26098
SECTION 12: INLET HOOD
Step 12.2.15
53 of 147
Page 64
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
12.3 Inlet Hood Assembly (2020 and 2030)
Model
2020
Description
2030
Part
Number
Double Sided Filter Rails13X0506644N/A
Top Inner Filter Rail13X05068111
Bottom Rail13X0507211N/A
Top Back Panel #113X05075111
Top Middle Panel #213X05076111
Top Front Panel #313X0507711N/A
Left Side Panel #113X05080111
Right Side Panel #113X05081111
Left Side Panel #213X05082111
Right Side Panel #213X05083111
Left Side Panel #313X05084111
Right Side Panel #313X05085111
Upright Mount13X05090222
Horizontal Mount13X0509122020=6 / 2030=22
Drip Rail Upper Right13305092111
Drip Rail Upper Left13305093111
Drip Rail Lower Right13305094111
Drip Rail Lower Left13305095111
TEK Screw134041502020=165 / 2030=1752020=152 / 2030=162
5/16"-18 x 1 Bolt HHCS Grade 520507262626
3/8" Flatwasher20515141414
3/8"-16 x 1 Bolt Hex Grade 520517141414
5/16" Flat Washer95211600262626
5/16" Nut Flange20509262626
Permanent Aluminum Mesh Filter
20" x 25" x 1"
Permanent Aluminum Mesh Filter
20" x 20" x 1"
10-24 KEPS Nut20698161616
A1 Snap Fastener2090010N/AN/A
10-24 x 1/2" HMS Bolt27000161616
Fastener Rivnut 3/8"-1691120106141414
Foam Tape9270001720' (6 m)20' (6 m)20' (6 m)
Birdscreen9074005XN/A1N/A
Birdscreen Mount*13305087*N/A4*N/A
Fender Washer 1/4" x 1"95211550N/A16N/A
Bottom Rail - ML**######**N/AN/A1
Left Side Cover - ML13X05078N/AN/A2
Right Side Cover - ML13X05079N/AN/A2
Top Front Panel #3 - ML13X05096N/AN/A1
Inner Rail - ML13X05097N/AN/A1
Outer Rail - ML13X05098N/AN/A1
Moisture Limiter 12" x 96" x 5.5"90740002N/AN/A2020=4 / 2030=5
206292020=10 / 2030=5N/AN/A
206282020=0 / 2030=10N/AN/A
Inlet Hood with Permanent
Aluminum Mesh Filters
13205060 (Galvanized)
13205061 (Painted)
13305060 (Galvanized)
13305061 (Painted)
QuantityQuantityQuantity
Inlet Hood without filters,
with Birdscreen
13205058 (Galvanized)
13205059 (Painted)
13305058 (Galvanized)
13305059 (Painted)
Inlet Hood with
Moisture Limiter
13205062 (Galvanized)
13205063 (Painted)
13305062 (Galvanized)
13305063 (Painted)
*For use on model 2030 Inlet Hoods only.
**For model 2020 P/N=13205095; for model 2030 P/N=13305100
Note: In the above chart, an "X" in a part number indicates a digit that changes based on model. Replace the
"X" with a "2" for model 2020; replace the "X" with a "3" for model 2030. For further clarification, reference
individual chart of components in each step.
54 of 147
Page 65
Step 12.3.1
Air Handler
Air Handler Top Panel
Horizontal Mount
Horizontal Mount
Without
Filter Section
Air Handler
With
Filter Section
Inlet Hood
Horizontal Mount
Horizontal Mount
Inlet Hood
Filter
Box
Air Handler
Without Filter Section
Without Filter Section
Air Handler
Filter Box
With Filter Section
With Filter Section
External Support
SIDE VIEWSIDE VIEW
TOP VIEWTOP VIEW
Upright Mount
Upright Mount
For an air handler without a filter section:On the inlet of the air handler, install horizontal and upright
mounts. The mounts will be installed via angles open towards the outside of the air handler.
For an air handler with a filter section: First, attach the filter section to the air handler. Then, bolt the inlet
hood horizontal and upright mounts to the inlet of the filter section with the angles opening towards the
inside of the filter section.
Upright mounts (P/N 13X05090) are attached with seven 3/8-16 bolts (P/N 20517) and flat washers (P/N
20515) each; the receiving riv-nut (P/N 91120106) will be factory installed on the air handler or filter section.
Horizontal mounts (P/N 13505091) are attached using nine TEK self-tapping screws (P/N 13404).
Prior to installing the mounts, seal the gap between the mating surfaces of the air handler/filter section and
the mounts with the provided foam tape (P/N 92700017).
When installing the top horizontal mount directly to the air handler without a filter section, foam tape should
NOT be used. In this case, the hardware on the lip of the air handler roof panel should be removed, the
mount slid under the lip and hardware re-installed. Foam tape to be used on remaining three sides.
To install inlet hood on an exterior wall, drill holes every 8" (20.3 cm) in the flanges of the inlet hood and
mo
unt with lag bolts (provided by others).
SECTION 12: INLET HOOD
55 of 147
Page 66
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Panel 1 Left
Panel 1 Right
Attach an innermost sidewall panel 1 to each side
attaching flange using seven TEK self-tapping screws.
NOTE: Flanges face inward.
DescriptionPart Number
Left Side Panel #113205080 / 13305080
Right Side Panel #113205081 / 13305081
TEK Screws13404
Bottom Rail
For Model 2020: Attach the bottom panel to the bottom
mounting flange with seven TEK self-tapping screws. Attach
to each side panel with two TEK self-tapping screws.
For Model 2030: Attach bottom panel to the bottom mounting
flange with nine TEK self-tapping screws. Attach to each side
panel with two TEK self-tapping screws.
NOTE: Ensure that the side tabs of the bottom panel are to
the inside of the side panels.
DescriptionPart Number
Bottom Rail
13205072 / 13305072 /
13205095 / 13305100
TEK Screws13404
Step 12.3.2
Step 12.3.3
56 of 147
Page 67
Step 12.3.4
Panel 2
Right
Panel 3
Right
Panel 2
Left
Panel 3
Left
Attach the middle sidewall panels (left panel, right panel) with
four 5/16"-18 x 1 bolt, 5/16 flat washer, 5/16" flange nut each.
Attach outermost sidewall panels (left panel, right panel) to
each side of the inlet hood using three 5/16"-18 x 1 bolt,
5/16" flat washer, 5/16" flange nut.
DescriptionPart Number
Left Side Panel #213205082 / 13305082
Right Side Panel #213205083 / 13305083
Left Side Panel #313205084 / 13305084
Right Side Panel #313205085 / 13305085
5/16"-18 x 1 Bolt20507
5/16" Flat Washer95211600
5/16" Nut Flange20509
Top Front Panel 3
Attach top front panel to the sidewall panels using four TEK
self-tapping screws on each side.
NOTE: Ensure that the side tabs of the top panel are to the
outside of the side panels.
DescriptionPart Number
Top Front Panel #3
13205077 / 13305077 /
13205096 / 13305096
TEK Screw13404
SECTION 12: INLET HOOD
Step 12.3.5
57 of 147
Page 68
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Top Front Panel (Roof)
Top Inner
Filter Rail
Top Front Panel
Bottom Rail
Right
Panel
Left
Panel
Top Inner Filter Rail
SIDE VIEW
REVERSE INLET
VIEW
For Model 2020: Attach top inner filter rail to the inside of
the top front panel using five TEK self tapping screws.
For Model 2030: Attach top inner filter rail to the inside of
the top front panel using six TEK self tapping screws.
NOTE: Ensure the rail is installed with the ends tight against
the flanges of the sidewall panels and the angle opening
toward the inside of the inlet hood.
DescriptionPart Number
Top Inner Filter Rail13205068 / 13305068
TEK Screw13404
Step 12.3.6
58 of 147
Page 69
Step 12.3.7
Attach top middle panel with five TEK self-tapping screws on
each side and with six 5/16-18 x 1 bolts, 5/16 washers and 5/16
flange nuts at the J-bend joint.
For Model 2020: Attach top back panel with five TEK self-
tapping screws on each side, seven TEK self-tapping screws to
the top mounting flange and with six 5/16-18 x 1 bolts, 5/16
washers and 5/16 flange nuts at the J-bend joint.
For Model 2030: Attach top back panel with five TEK self-
tapping screws on each side, nine TEK self-tapping screws to
the top mounting flange and with six 5/16-18 x 1 bolts, 5/16
washers and 5/16 flange nuts at the J-bend joint.
NOTE: Ensure that the side tabs of the roof panels are to the
outside of the side panels and that the J-bends interlock the
panel with the roof panel in front of it.
DescriptionPart Number
Top Middle Panel #213205076 / 13305076
Top Back Panel #113205075 / 13305075
TEK Screw13404
5/16"-18 x 1 Bolt20507
5/16" Flat Washer95211600
5/16" Nut Flange20509
Top Middle Panel 2
SECTION 12: INLET HOOD
Top Back Panel 1
For inlet hoods with permanent aluminum mesh filters, continue to Step 12.3.9.
For inlet hoods with birdscreen, no filters, continue to Step 12.3.8.
For inlet hoods with moisture limiter, continue to Step 12.3.10.
59 of 147
Page 70
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Birdscreen
Install birdscreen mounts into inlet hood opening.
Mount birdscreen into brackets and secure with self
tapping screws and washers.
Attach the double-sided filter rails horizontally to the
face of the inlet hood using two #10-24 x ½" bolts
and #10-24 nuts on each side. When attaching the
filter rails, insert the bolt from the inside of the filter
rail to allow for maximum clearance for the filters.
Attach the filter clips with TEK self-tapping screws.
(First remove the washer as the washer will restrict
the filter clip, making it difficult to open.)
NOTE: Inlet hoods with birdscreen does not require
filters or snap fasteners.
DescriptionPart Number
Double-Sided Filter Rails13205066 / 13305066
#10-24 x ½" Bolt27000
#10-24 Nut20698
TEK Screw13404
A1 Snap Fastener20900
Step 12.3.8
Step 12.3.9
60 of 147
Page 71
Step 12.3.10
CaulkCaulk
Caulk the seams between the inlet hood and the air handler/filter section and on the open sides of the
J-bends that lock the roof panels together.
NOTE: Double-sided filter rails or filter
clips are not required for inlet hood with
moisture limiter.
Lower
Rail
Upper
Rail
When attaching the drip rail, ensure that the drip rails are
positioned above the filter clips, using the provided holes in
the sidewall panels. Attach drip rail to right side of inlet hood
starting with the lower drip rail using five TEK self-tapping
screws. Attach the upper right side rail by sliding it inside the
lower drip rail where they overlap use five TEK self-tapping
screws. Attach drip rail to left side of inlet hood starting with
the lower drip rail using five TEK self-tapping screws. Attach
the upper right side drip rail by sliding it inside the lower drip
rail where they overlap use five TEK self-tapping screws.
Apply caulk to the drip rails before attaching to the side
panels.
For inlet hoods with permanent aluminum mesh filters, continue to Step 12.3.12.
For inlet hoods with birdscreen, no filters, the instructions end here.
For inlet hoods with moisture limiter, continue to Step 12.3.13.
61 of 147
Page 72
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Filter
Load filters into the inlet hood, checking
to see that each filter is in the proper orientation
by verifying that the arrow on the side of the filter points in
the direction of air flow. All of the arrows should be
pointing towards the air handler when installed in the
proper orientation. Once filters are installed, close snap
fasteners installed previously (See Page 60, Step 12.3.9)
to hold filters in place.
Description Size
Part
Number
Permanent Aluminum
Mesh Filter
in20 x 25 x 1
20629
cm50.8 x 63.5 x 2.5
in20 x 20 x 1
20628
cm50.8 x 50.8 x 2.5
Moisture Limiter Side Cover
Attach side cover of moisture limiter frame to the left side
of the inlet hood drip rail using eight TEK screws. Attach
to the bottom pan assembly with two #10-24 x ½" bolts
and #10-24 nuts.
DescriptionPart Number
Left Side Cover (ML)13205078 / 13305078
TEK Screw13404
Step 12.3.12
For inlet hoods with permanent aluminum mesh filters, the instructions end here.
Step 12.3.13
62 of 147
Page 73
Step 12.3.14
Inner Support
Rail
Moisture Limiter
Side Cover
Place the moisture limiter inner support rail under the top
flange of the moisture limiter frame side cover and to the top of
the inlet hood. Attach to the top of the inlet hood using nine
#10-24 x ½" bolts and #10-24 nuts. Attach to the side cover of
the frame using two #10-24 x ½" bolts and #10-24 nuts.
DescriptionPart Number
Inner Support Rail13205097 / 13305097
TEK Screw13404
#10-24 x 1/2" Bolt27000
#10-24 Nut26098
Moisture Limiter
Media
For Model 2020: Insert 4 pieces of 12" (30.5 cm) x
96" (243.8 cm) moisture limiter media from the right
side with the long dimension running top to bottom.
For Model 2030: Insert 5 pieces of 12" (30.5 cm) x
96" (243.8 cm) moisture limiter media from the right
side with the long dimension running top to bottom.
DescriptionPart Number
Moisture Limiter Media90740002
SECTION 12: INLET HOOD
Step 12.3.12
63 of 147
Page 74
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Moisture Limiter
Side Cover
Outer Support Rail
Place the moisture limiter frame side cover to the flange at the
top overlaps the top of the frame. Attach to the inlet hood drip rail using eight TEK screws. Attach to the bottom pan assembly and
top with two #10-24 x ½" bolts and #10-24 nuts each. Attach
front stiffeners to the left and right side of the moisture limiter
frame using four TEK screws for each support.
DescriptionPart Number
Right Side Cover13205079 / 13305079
Outer Suppor t Rail13205098 / 13305098
TEK Screw13404
Air Handler
Inlet Hood
Step 12.3.13
12.4 Inlet Hood Installation
The inlet hood may be installed either onto the inlet of the air handler or to an outside wall.
12.4.1 Inlet Hood Installation to Wall
Use lagbolts to install the inlet hood to an exterior wall. Once the inlet hood is in place, the edges must be
sealed to the wall with the proper sealant. For models 2010 - 2030, assemble the hood prior to mounting,
then mount as described below.
12.4.2 Inlet Hood Installation to Air Handler (2005)
First remove the hardware in the top drip edge of the air handler. Tuck the top flange of the hood behind the
top drip edge. See Page 64, Figure 25. Replace the hardware, screw together the top drip edge of the air
handler, top flange of the inlet hood and the air handler wall panel.
NOTE: After installing the inlet hood, all hardware must be tightened with a torque wrench. The roof, side and
bottom seams must be caulked (supplied by others).
12.4.3 Inlet Hood Installation to Air Handler (2010 - 2030)
Inlet hoods are assembled onto the air handler. For Models 2010 and 2010B See Page 46, Step 12.2.1. For
Models 2020 and 2030 See Page 55, Step 12.3.1.
FIGURE 25: Inlet Hood Positioning
64 of 147
Page 75
SECTION 13: DAMPERS
SECTION 13: DAMPERS
WARNING
Crush Hazard
Use proper lifting
equipment and
practices.
Failure to follow these instructions can result in death, injury or property damage.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Equipment and
accessories are
heavy.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
65 of 147
Page 76
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
C
E
C
D
A
B
C
C
F
NOTE:1) CONTRACTOR/INSTALLER MUST MAKE
APPROPRIATE ALLOWANCES FOR DUCT
CONNECTIONS.
2) NUMBER OF LOUVERS WILL VARY.
3) MOUNTED DOWNSTREAM OF AIR HANDLER IN
DUCT WORK. DOES NOT MOUNT DIRECTLY TO
AIR HANDLER. FIELD WIRED TO PROVIDED
TERMINALS ON CONTROL PANEL.
AIR FLOW
ModelPart NumberABCDEF
Weight lbs
(kg)
200577014.301
in21.019.01.019.017.09.0
40 (18.1)
cm53.348.32.548.343.222.9
2010/
2010B
77018.301
in27.025.01.023.521.58.0
60 (27.2)
cm68.663.52.559.754.620.3
202080922.2
in37.034.01.536.033.010.0
100 (45.4)
cm94.086.43.842.083.825.4
203077537.2
in42.039.01.542.039.010.0
150 (68)
cm106.799.13.8106.799.125.4
13.1 Discharge Damper
Discharge dampers are shipped loose. Discharge dampers are designed to be mounted downstream of the
air handler in ductwork. A qualified contractor/installer must make appropriate allowances for duct
connections.
To install the discharge damper on an interior wall, drill holes every 8" (20.5 cm) in the flanges on all four
sides of the discharge damper to accommodate lag bolts (provided by others).
Discharge dampers are not recommended to be mounted directly to the air handler.
3) MOUNTED UPSTREAM OF AIR HANDLER. MOUNTS
DIRECTLY TO AIR HANDLER, PRE-INSTALLED.
G
AIR FLOW
ModelPart NumberABCDEFG
Weight lbs
(kg)
200577019.301
in21.019.01.325.723.45.03.3
40 (18.1)
cm53.348.33.365.259.512.78.3
2010/2010B80900
in33.330.81.329.026.35.03.3
60 (27.2)
cm84.578.13.273.766.712.78.3
13.2 Inlet Damper
Inlet dampers are factory mounted to the inlet of the air handler (covering the inlet opening). The inlet
damper has four outward-turned flanges. Based on air handler style, damper may include upper and lower
damper.
FIGURE 27: Motorized Inlet Damper (2005 - 2010B)
67 of 147
Page 78
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
NOTE:1) CONTRACTOR/INSTALLER MUST MAKE
APPROPRIATE ALLOWANCES FOR DUCT
CONNECTIONS.
2) NUMBER OF LOUVERS WILL VARY.
3) MOUNTED UPSTREAM OF AIR HANDLER. MOUNTS
DIRECTLY TO AIR HANDLER, PRE-INSTALLED.
UPPER DAMPER
LOWER DAMPER
AC
B
D
CA
E
E
E
E
E
E
AIR FLOW
AIR FLOW
ModelABCDE
2020
in47.324.42.029.51.5
cm 120.063.05.174.93.8
2030
in59.324.42.033.51.5
cm 150.663.05.185.13.8
ModelPart NumberStyleDampers Used
Weight
lbs(kg)
202080920
MUAUpper and Lower
75(34)
203077530107(48.1)
202080920U
FR/AM/VAVUpper Only
34(15.4)
203077530U46(20.9)
FIGURE 28: Motorized Inlet Damper (2020 and 2030)
68 of 147
Page 79
SECTION 14: DISCHARGE HEADS AND SPLASH PLATES
ModelABCDE
Part
Number
Weight
lbskg
2005
(in)
(cm)
19.0
48.3
40.8
103.5
23.8
60.3
21.0
53.3
2.0
5.1
77349.301 50 22.7
2010
and
2010B
(in)
(cm)
22.4
56.9
40.8
103.5
24.0
61.0
19.4
49.3
2.0
5.1
77049.301 80 36.3
2020
(in)
(cm)
31.9
81.0
43.3
109.9
21.5
54.6
33.9
86.1
2.0
5.1
77249.201 120 54.4
2030
(in)
(cm)
36.9
93.7
48.3
122.6
22.5
57.2
36.9
93.7
2.0
5.1
77549.201 160 72.6
WARNING
SECTION 14: DISCHARGE HEADSAND SPLASH P LATES
Crush Hazard
Use proper lifting
equipment and
practices.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
Severe Injury Hazard
Use proper lifting
practices and equipment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Equipment and
accessories are
Edges are sharp.
heavy.
Failure to follow these instructions can result in death, injury or property damage.
Part numbers that end with a “[W]” indicate that the part can be ordered with either an unpainted galvanized
finish or an acrylic modified alkyd enamel finish. To order with a galvanized finish, do not include the "W" at
the end of the part number; to order with a painted finish, include the "W" at the end of the part number.
14.1 One-Way and Three-Way Discharge Head
Installation
All discharge heads are shipped assembled. The
discharge head is designed for mounting to the face
FIGURE 29: Three-Way Discharge Head
(2005 - 2030)
E
of the air handler (covering the discharge opening) or
to an interior wall. All discharge heads must be field
supported (by others). The discharge head has four
A
B
outward-turned flanges. If the discharge head is to
be installed to the face of the air handler, install
hardware (provided by others) on all four sides of the
discharge head.
To install the discharge head on an interior wall, drill
TOP VIEW
C
E
E
holes every 8" (20.5 cm) in the flanges on all four
sides of the discharge heads to accommodate lag
bolts (supplied by others). Sheet metal (supplied by
D
others) may be required. See Page 69, Figure 29 for
the three-way discharge head available for Models
2005 - 2030.
SIDE VIEW
E
69 of 147
Page 80
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Part NumberModelABCDE F
G
(min)G(max)
H
Weight
lbskg
77354.301[W] 2005
(in)
(cm)
22.0
55.9
19.5
49.5
0.9
2.2
25.0
63.5
1. 3
3.2
0.6
1. 6
15.0
38.1
20.0
50.8
N/A20.09.1
77053.301[W]
2010/
2010B
(in)
(cm)
44.0
118 . 8
41.5
105.4
0.9
2.2
44.0
111.8
1. 3
3.2
0.6
1. 6
18.0
47.5
27.0
68.6
N/A40.018.1
77253.301[W]
2020
(in)
(cm)
54.8
139.1
51.3
130.2
1. 8
4.4
54.8
139.1
1. 8
4.4
0.8
2.0
25.0
63.5
38.0
96.5
N/A
60.027.2
2030
(in)
(cm)
30.0
76.2
45.0
114 . 3
N/A
14.2 Splash Plate Installation
The splash plate is designed to hang directly from a horizontal air handler with a bottom discharge. Before
the splash plate can be installed on the air handler, first drill four holes (2005 - 2030) in the air handler floor.
These holes should be approximately 5/8" (15.9 mm) in diameter to accommodate 1/2" hanger rods
(supplied by others). These holes should be located as shown in the diagram on Page 71, Figure 31.
To attach all of the hanger rods to the splash plate, start by threading a flanged nut onto each hanger rod.
Then, slip each hanger rod down through a hole located in each corner of the splash plate. Next, feed a
flanged nut onto the rod below the splash plate See Page 70, Figure 30. The hanger rods should be attached
to the air handler in the same manner as the splash plate, with a flanged nut on both sides of the air handler
floor. Adjusting the nuts will level the splash plate. Torque hardware after leveling.
FIGURE 30: Splash Plate
70 of 147
Page 81
FIGURE 31: Hole Location (2005 - 2030)
Model20052010 and 2010B20202030
A
(in)
(cm)
19.5
49.5
41.5
105 .4
51.3
130.2
51.25
130.2
B
(in)
(cm)
22.5
57.2
41.5
105 .4
51.3
130.2
51.25
130.2
B
SECTION 14: DISCHARGE HEADSAND SPLASH P LATES
A
71 of 147
Page 82
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
Falling Hazard
Use proper safety
equipment and practices to avoid falling.
WARNING
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 15: DUCT CONSIDERATIONS
The air handler has been designed to operate at the
specific air volume and external static pressure that
was ordered (air handlers set-up to accept an
external static pressure (ESP) of 1 in wc (2.5 mbar).
This static pressure is generated by any additional
components that are added to the heater (i.e. inlet
hood, filter section, dampers, ductwork, discharge
heads, etc). Additional static pressure beyond that
ordered will affect the performance of the air handler
and lessen the air volume that can be delivered.
Proper engineering methods need to be employed
when calculating duct and component static pressure
(i.e. 2009 ASHRAE Handbook - Fundamentals,
Chapter 21). Accessory pressure drops are available
on Page 16, Table 9.
The system ductwork must comply with Sheet Metal
and Air Conditioning Contractors Nationals
Association (SMACNA) or any other recognized
standards.
As a general rule, all discharge ducts should have a
straight run of at least 3 hydraulic duct diameters
after the air handler before adding any fittings,
elbows, restrictions, etc. Return ducts should have
the same straight r
Hydraulic duct diameter for round ducts in inches:
Dh = d
Dh: hydraulic diameter
d: round duct inside diameter
Hydraulic duct diameter for rectangular ducts (in
The air handler is not designed to support the weight
of ductwork. Ductwork must be constructed in a
fashion that is self-supporting. Ductwork should be
straight, elbows should be minimal and any
transitions should be smooth.
Depending on the options ordered with the air
handler, flanges (either external or internal) may be
provided to facilitate connection of ductwork. In
cases where flanges are not provided, flat surfaces
on the exterior skin of the air handler are pro
facilitate connection of ductwork.
15.1 Inlet Duct Work
Inlet duct work height and width must be no smaller
than the air handler inlet height and width and supply
only fresh air to the air handler. (See Page 11, Section 5 for inlet dimensions).
15.2 Return Duct Work
Inlet duct work height and width must be no smaller
than the air handler inlet height and width and supply
only fresh air to the air handler. (See Page 11, Section 5 for inlet dimensions).
15.3 Discharge Duct Work
Refer to Page 73, Table 10 for minimum discharge
duct sizes by model. Refer to Page 73, Table 11 for
discharge duct size required for connecting to heater
(BD or RD), these dimensions provide clearance for
duct flange to blower mounting bolts.
vided to
72 of 147
Page 83
Table 10: Minimum Recommended Duct Size
ModelHeightWidth
2005
2010 and
2010B
2020
2030
(in)
(cm)
(in)
(cm)
(in)
(cm)
(in)
(cm)
14
35.6
24
61.0
32
81.3
38
96.5
15.6
39.7
24
61.0
32
81.3
38
96.5
Table 11: Discharge Duct Size Recommendations
to Connect to Heater (for BD/RD)
ModelHeightWidth
2005
2010 and
2010B
2020
2030
(in)
(cm)
(in)
(cm)
(in)
(cm)
(in)
(cm)
14
35.6
25.3
63.5
40
101.6
47
119 . 4
17.5
44.5
25.3
63.5
35.3
89.5
40.8
103.5
SECTION 15: DUCT CONSIDERATIONS
NOTE: Dimension clearance to clear blower
mounting bolts.
73 of 147
Page 84
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
WARNING
Explosion Hazard
Leak test all components of gas piping
before operation.
Gas can leak if piping is not installed
properly.
Do not high pressure test gas piping with air
handler connected.
Failure to follow these instructions can result
in death, injury or property damage.
SECTION 16: GAS PIPING
16.1 Gas Manifolds
All gas piping to the air handler must comply with:
United States: Refer to NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision,
Natural Gas and Propane Installation Code.
The air handlers are available with three gas manifold
options.
• American National Standards Institute (ANSI)
compliant manifold: (
See Page 75, Figure 33
2005.
See Page 75, Figure 32
for 2010 - 2030.
•Factory Mutual (FM)-compliant manifold:
See Page 75, Figure 32
(
Figure 34
for 2010 - 2030.
• XL compliant manifold: (
for 2005.
See Page 76, Figure 35
for 2005.
See Page 76,
See Page 75, Figure 32
for 2010 - 2030.
16.2 Gas Piping and Pressures
The air handler is equipped with a gas manifold
suitable for connection to supply pressure of up to:
•14 in wc maximum (34.9 mbar) (2005 - 2030 with
•5 p.s.i. maximum (2005 - 2030 with FM or XL
ANSI-compliant manifold.)
compliant manifold).
When gas supply exceeds the above-listed maximum
gas pressures, an additional high pressure gas
regulator will be required to assure that the correct
for
gas pressure is supplied to the regulator. Pressure
should be measured between the high pressure gas
regulator and safety shut off valve. Minimum gas
pressure as indicated on data plate must be
measured with the burner operating in high fire.
Table 12: Gas Manifold Size
Model
Gas NPT
Connection
200520102010B20202030
¾"1"1¼"1½"2"
16.3 Gas Manifold Venting
Vent valves fitted on XL compliant manifolds must be
piped to the atmosphere outside the structure and in
accordance with applicable codes. This is the
responsibility of the installer.
16.3.1 Main Gas Regulator Venting
The main regulator used on 1¼" and larger manifolds
must be piped to the atmosphere outside the
structu
re. This is the responsibility of the installer.
16.3.2 Vent Line Installation
The following may be used as a guideline for
installation, but all applicable codes and regulations
must be followed.
•Natural gas and LPG are toxic and flammable
substances. They must be released where they
will not cause personal injury or property damage.
The end of the vent line must be located where it
is safe to release gas.
• Pipe the vent line outside the structure.
• Use as short a vertical run of pipe as possible.
• Do not run pipe from a high point to a lower point
to avoid obstacles.
• Use a minimum number of bends.
• Do not downsize the pipe from the origination
point (must be same size or larger).
•Make sure vent line is free from obstructions.
• Do not group lines together into a common
header.
•The outside termination must have a weatherproof cap or be directed downward for
protection from the elements and must be
screened to prevent the entry of any objects.
74 o f 147
Page 85
FIGURE 32: ANSI/FM/XL-Compliant Manifolds (2005)
NOTE: Vent valves must be piped to the atmosphere outside the structure and in accordance with
applicable codes.
Alternate
Inlet
Inlet
By Others
Combination Valve
Manual Gas
High Gas Pressure Regulator (Optional)
Burner
Modulating Valve With Pressure Regulator
Manual Gas Valve (Burner)
Valve (Pilot)
Drip
Leg
Off Valve
Safety Shut Off Valve
Safety Shut
Manual Gas
Valve (Main)
Union
(By Others)
Alternate
Inlet
Inlet
Drip
Leg
By Others
High Gas Pressure Regulator (Optional For ANSI-Compliant Manifolds and supplied for FM and XL-Compliant Manifolds)
Regulator With Dual Safety Shut Off Valve
Manual Gas
Valve (Main)
Union
(By Others)
Manual Gas
Valve (Pilot)
SECTION 16: GAS PIPING
Vent to Atmosphere (FM and XL Manifold)
Modulating Valve
Manual Gas Valve (Burner)
Burner
Combination Valve
FIGURE 33: ANSI-Compliant Manifold (2010 - 2030)
75 of 147
Page 86
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
NOTE: Vent valves must be piped to the atmosphere outside the structure and in accordance with
applicable codes.
Alternate
Inlet
Inlet
By Others
Manual Gas
High Gas Pressure Regulator (Optional)
Valve (Pilot)
Drip
Leg
Ps
Modulating Valve With
Pressure Regulator
Manual Gas Valve (Burner)
High Gas Pressure Switch
Burner
LOW GAS
PRESSURE
SWITCH
Low Gas Pressure Switch
Pilot
Regulator
Pilot
Solenoid
Off Valve
With Actuator
Block Valve
With Actuator
Safety Shut
Vent
Valv e
Vent to Atmosphere
Vent to Atmosphere
Vent to Atmosphere
Vent to Atmosphere
Manual Gas
Valve (Main)
Union
(By Others)
NOTE: Vent valves must be piped to the atmosphere outside the structure and in accordance with
applicable codes.
FIGURE 34: FM-Compliant Manifold (2010 - 2030)
Alternate
Inlet
Inlet
Drip
Leg
High Gas Pressure Regulator (Optional)
Manual Gas
Valve (Main)
Union
(By Others)
Manual Gas
By Others
Valve (Pilot)
Safety Shut
Off Valve
Vent to Atmosphere
Pilot
Regulator
Visual Indicator
Pilot
Solenoid
Safety Shut
Off Valve
Vent to Atmosphere
Vent to Atmosphere
Modulating Valve With
Pressure Regulator
Manual Gas Valve (Burner)
Ps
High Gas Pressure Switch
Burner
FIGURE 35: XL-Compliant Manifold (2010 - 2030)
76 of 147
Page 87
SECTION 16: GAS PIPING
Burner
Modulating Valve
Manual Gas Valve (Burner)
Plugged Taping
To Measure Burner Pressure
Burner
Modulating Valve
Manual Gas Valve (Burner)
Plugged Taping
16.4 Gas Piping
The gas manifold extends through the side of the
control cabinet for models 2005 - 2030. The factory
piping terminates with a female pipe connection in
the manual gas valve. The manual main gas shutoff valve is shipped loose for field installation. A union
must also be installed (supplied by others) between
the supplied manual gas valve main and the first tee
pipe. Be sure that the fuel supply pipe connected at
this point is large enough to ensure the proper gas
flow and line pressure at the inlet of the air handler.
The piping must comply with:
United States: Refer to NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 - latest revision,
Natural Gas and Propane Installation Code.
Gas supply piping must conform to best building
practices and local codes. During installation of the
gas piping, be sure that no piping restricts
accessibility to the air handler or its removable
access doors.
Figure 79.
FIGURE 36: Plug Tapping (2005)
FIGURE 37: Plug Tapping (2010 - 2030)
Lockable manual shut-off val
installer in compliance with Occupational Safety and
Health Administration (OSHA) regulations.
16.5 Pressure Test Ports
There are 1/8" (3.2 mm) and 1/4" (6.4 mm) pressure
test ports located on the manifold. The test ports are
available to measure the manifold inlet gas pressure
and the burner gas pressure during burner setup.
16.5.1 Manifold Inlet Gas Pressure
The pressure port for measuring manifold inlet
pressure is located on the inlet side of the first safety
shutoff valve. Refer to the unit rating plate for the
acceptable inlet gas pressure.
16.5.2 Burner Gas Pressure
A pressure tap is used to measure negative airflow at
the burner and to set high fire gas pressure. On air
handlers equipped with a M611 modulating valve
(Model 2005), the pressure tap is located on a tee
between the M611 valve and the burner. See Page 77, Figure 36and Page 123, Figure 81. On air
handlers equipped with the MR212 modulating valve
(Models 2010 - 2030), the pressure tap could be
located on the downstream side of the MR212 valve,
on a T-fitting coming off the outlet pressure tap on the
MR212 valve or between the MR212 valve and the
burner. See Page 77, Figure 37 and Page 122,
ve must be added by the
16.6 Line Pressure Test - Leak Testing
The air handler and its individual shut-off valve must
be disconnected from the gas supply piping systems
during any pressure testing of that system at test
pressures in excess of 14 in wc (34.9 mbar). The air
handler must be isolated from the gas supply piping
system by closing its individual manual gas valv
e that
is located immediately upstream of the safety shut-off
gas valve.
77 of 147
Page 88
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be
required to disconnect electric from
equipment.
Equipment must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.
SECTION 17: ELECTRICAL
Each air handler is equipped with a wiring diagram
which will vary depending on the type of remote
panel supplied (See Page 80, Figure 38 through
Page 86, Figure 44). Depending on the air handler
configuration and optional equipment ordered, an
option sheet may also be included. This option sheet
overwrites the wiring diagram between the electrical
terminals indicated.
Air handlers can also be supplied as building
management system (BMS)-ready. In this case, a
remote panel is not supplied. See wiring diagrams on Page 87, Figure 45through Page 89, Figure 47.
Note: Spark testing or shorting of the control wires
by any means will render the transformers
inoperative.
Each unit is equipped with a fused rotary disconnect.
The rotary disconnects are for copper wire only.
17.1 Wiring and Electrical Connections
All electrical wiring and connections, including
electrical grounding, must comply with:
United States: Refer to National Electrical Code
NFPA 70 - latest revision. Wiring must conform to the
most current National Electrical Code
®
, local
ordinances, and any special diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA
C22.1 Part 1 - latest revision.
Check rating plate on air handler for supply voltage
and current requirements.
If any of the original control wire supplied with the air
handler must be replaced, replace it with type MTW
105°C, 600 V, 16 gauge wire or equivalent, except for
temperature control wiring, which must be a minimum
of 20 AWG Type Beldon 5401FE CMR 75C shielded
or equivalent.
For all other wires, replace with the equivalent size
and type of wire that was originally provided with the
air handler.
17.2 Remote Panel
The remote panel must be wired as shown on the
electrical schematic. For wire gauge sizes, see Page 78, Table 13. All power supply and motor wiring must
be minimu
m type THWN with a 167° F (75° C)
temperature rise.
17.2.1 Remote Panel Mounting Distance
If the interconnection wiring between the remote
panel and the air handler control enclosure is ru n in a
single conduit, the wire run can be as long as 100'
(30 m). For longer wire runs, consult the factory. If the
interconnection wiring between the remote panel and
the air handler control enclosure is run in two
conduits (separating the shielded cable and the 120
V power supply for the remote panel), the wire run
can be as long as 200' (60 m). For longer wire runs,
consult the factory. Care should be used to avoid
running the interconnect wiring near large industrial
loads or high voltage wire runs as that may further
limit the length of the interconnect wire run.
Table 13: Control Voltage Wiring For All Control
Systems
VoltsWire GaugeMax Wire
12018150' (45 m)
12016250' (75 m)
1201435 0' (106 m)
NOTE: Wiring for temperatu
re controls must be run in
shielded cable as indicated on the wiring diagram.
17.2.2 Low Voltage Control Wiring
Low voltage (24 V - AC/DC) control wiring in excess
of 100' (30.5 m) in length should be in its own
separate conduit run to prevent interference.
17.3 Motor Current Draw
®
,
For current requirements of the motor, refer to Page 79, Table 14. For specific current requirements, see
rating plate located on the blower motor. Current
draw may be adjusted downward by reducing blower
rotations per minute (RPM) or by increasing external
static pressure.
17.4 Control Current Draw
The maximum current draw for an air handler’s
controls and accessories is 3A.
17.5 Safety Systems
Safety systems are required for proper performance
78 of 147
Page 89
SECTION 17: ELECTRICAL
of the air handler. The air handler shall not be
permitted to operate with any safety system disabled.
If a fault is found in any of the safety systems, then
the system shall be repaired only by a contractor
heating equipment, using only components that are
sold and supplied by Rapid Engineering LLC. Refer
to Page 79, Table 15 for a brief description of each
safety device, its location and its switching voltage.
qualified in the installation and service of gas fired
Manual Reset High-Temp Limit (All Models)Blower Discharge120
Pres sure Switches (All Models)Air Handler Control Enclosure120
Flame Control (2010/2010B/2020/2030)Air Handler Control Enclosure120
Flame Control (2005)Air Handler Control Enclosure24
Discharge Temperature Monitor (All Models)Blower Discharge24
AM Resistor (AM/VAV Style)Air Handler Control Enclosure24
17.5.1 Manual Reset High Temperature Limit
Switch
If for any reason, the temperature of the air at the
discharge of the blower reaches the limit set point of
160° F (71.1° C), the high temperature limit switch will
open the circuit to the burner system and discontinue
all burner functions. Events that could result in
excessive discharge air temperatures include if the
burner modulation amplifier is defective (i.e.
temperature sensor goes open circuit) or if a surge in
gas pressure reaches the burner. Restarting of the
burner can only be accomplished after the limit has
cooled dow
n and the reset button on the switch has
been depressed. This switch is located on the blower
housing inside the air handler.
17.5.2 Pressure Switches
The low airflow velocity pressure switch monitors the
airflow (differential pressure) across the burner.
When the airflow across the burner reaches the
proper velocity (volume) for combustion, the switch
closes. When the switch closes, it permits the flame
safeguard relay to begin ignition. This switch is
factory set at 0.32 in wc (0.8 mbar). The high velocity
pressure switch will open if the airflow across the
burner reaches its maximum allowable limit. This
switch is factory set at 1.40 in wc (3.5 mbar). The
pressure switch is a safety device, which cannot be
field-adjusted or tampered with.
17.5.3 Gas Pressure Switches
Gas pressure switches are standard on certain
models (FM compliant gas trains above 2,500 MBH
and XL compliant gas trains) and are also available
The function of the gas pressure switches is to
protect against insufficient, lack of gas pressure and
excessive pressure in the system.
On the low gas pressure switch side, this switch
opens its internal switch which shuts the burner down
and prevents its operation due to insufficient gas
pressure.
On the high gas pressure switch side, its internal
switch will open, shutting down the burner due to
excessive gas pressure passing through the gas
train.
The settings of the gas pressure switches are field
adjustable. The one monitoring the incoming gas
pressure is the low gas pressure switch. The low gas
pressu
re switch must be set to the minimum required
gas pressure as indicated on the data plate.
The high gas pressure switch must be set to 1 in w.c.
(2.5 mbar) above high fire setting established during
commissioning.
If either switch senses a pressure which is lower (low
gas pressure switch) or higher (high gas pressure
switch) than its set point, then the switch will open
and lock out, shutting the burner down. The switch will have to be reset manually, once the condition has
been corrected.
17.5.4 Flame Control
This device will check for both pilot flame and main
flame within the burner. When a flame signal from the
pilot flame is available, it will allow the main gas valve
to open.
Models 2005 - 2010B operate with intermittent pilot
as an option on the others.
79 of 147
Page 90
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
Notes:
1. Wire Over 24vac To Be A Minimum Of
16 Awg Flexing Type Mtw, 105c, 600v Or Equivalent
Colors 115vac: Phase-red, Neutral-white,
Ground-green
Colors 24vac: Blue
2. Control Wire To Be A Minimum Of 20 Awg Type
Belden 5401fe Cmr 75c Shielded Or Equivalent
3. Power Supply And Motor Wires To Be Sized To Nfpa79,
Latest Edition
Colors All Voltages: Phase(s)-black, Ground-green
Terminals Located In Control Panel Only
Terminals Located In Control Panel And
Connected To The Remote Panel
Terminals Located In Remote Panel Only
Wire(s) Located In Control Panel
Wire(s) Located In Remote Panel
Shielded Wire(s), One End Grounded
M1
CR2
C
No
Nc
Relay / Motor Starter Coil (Associated With M1 Contacts)
Normally Open Contact (Associated With M1 Coil)
Normally Closed Contact (Associated With CR2 Coil)
Air Flow Switch
Indicator Light On Remote Panel
M1
L
(pilot stays lit during burner operation). Models 2020
- 2030 operate with interrupted pilot (pilot turns off
after flame is established). The flame sensor
observes main flame only.
Model 2005 uses a flame rod to detect the flame
(minimum flame current 1µA); Models 2010 - 2030
use an ultraviolet (UV) light scanner (5.0 Vdc flame
signal).
If a pilot flame is not present, the electrical signal
cannot be sent and the pilot burner gas valve will
close. The relay is equipped with a 10-second trial for
ignition. If ignition does not occur, the flame
safeguard relay will lockout, and must be manually
reset. 2005 will reset upon power restoration. (See
the Trouble-Shooting Guide - Page 136, Section 22)
17.5.5 Discharge Temperature Sensor
This device senses the discharge temperature of the
air at the blower. The discharge temperature sensor
FIGURE 38: Wiring Diagram Key
reports the discharge temperature to the temperature
control amplifier which modulates the burner to the
temperat
ure set on the remote panel selector. Should
this system fail, the manual high temperature limit
switch will turn the burner off. BMS-ready air
handlers do not come equipped with this sensor and
must be field-supplied.
17.5.6 Positive Low Fire Start
This feature forces the burner to start in low fire
rather than high fire during the air handler’s start-up
sequence of operations. The burner maintains its low
fire setting for 10 seconds (as per timer setpoint)
before it begins to modulate.
80 of 147
Page 91
FIGURE 39: Basic Remote Wiring Diagram (2005)
TEMPERATURE
1
1
40
MANUAL
RESET
FUSABLE DISCONNECT
HI TEMP
TAS-3
LIMIT
8
1
L1
7
3 AMP
BREAKER
L3
L2
TS114
TEMPERATURE
MONITOR
SELECTOR
TD114
12
44
TCA-A1014
2
32
43
45
VALVE MRV
REGULATING
MODULATING
7
15
56
4849
8
T3
24VAC
TEMP CONTROL
AMPLIFIER
X1
16
20VA
X2
MTR
250VA
M1
X2
X1
H2H1H3
H4
T1
4
MOTOR
2
FAN O N
L
M1
MOTOR STARTER
FAN ON
BLOWER
120vac
120VAC
2
M1OL
M1-OL
9C
MV MV/PV PV GND 24V(GND) 24V SPARK SENSE
CR2
S8600B
SSOV
MVMV
PV
40VA
120VAC
24VAC
X2
X1
2
SAFETY SHUTOFF
VALV E
PILOT VALVE
CONTROL
IGNITION
13
SP
FR
L
12
BURNER ON LIGHT
CR2
9C
9C
9
PRIMARY CONNECTION
T1 TRANSFORMER
H4 - COMMON
H2 - 230 USE 3.0 AMP BREAKER
H3 - 208 USE 4.0 AMP BREAKER
H1 - 460 USE 1.6 AMP BREAKER
WIRE CONNECTIONS
REMOTE TO MAIN PANEL
1, 2, 3A, 4, 7, 12
40, 41 (SHIELD)
10
41
TEMP. CONTROL
AMPLIFIER
BURNER
OFF
ON
FAN
OFF
ON
18
19
11
14
12A
FLAME
ROD
SPARK
PLUG
9B9A
3A3B3C3D
8A
LOW PRES.
SWITCH
HI PRES.
SWITCH
CNO
CNC
NC
3 PHASE ONLY
BURNER ON
RELAY 24VAC
GROUND SHIELDED CABLE AT CONTROL PANEL
BREAKER
SECTION 17: ELECTRICAL
81 of 147
Page 92
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
H2 - 230 USE 3.0 AMP BREAKER
H3 - 208 USE 4.0 AMP BREAKER
H1 - 460 USE 1.6 AMP BREAKER
WIRE CONNECTIONS
REMOTE TO MAIN PANEL
1, 2, 3A, 4, 7, 12, 24, 25
40, 41 (SHIELD)
TEMPERATURE
1
MANUAL
RESET
HI TEMP
TAS-3
LIMIT
8
1
L1
7
FAN
AUTO
ON
3 AMPBREAKER
L3
L2
TS114
TEMPERATURE
MONITOR
SELECTOR
TD114
12
44
TCA-A1014
2
43
45
VALVE MRV
REGULATING
MODULATING
7
15
56
48
49
8
T3
24VAC
TEMP CONTROL
AMPLIFIER
X1
16
20VA
X2
MTR
250VA
M1
X2
X1
H2H1
H3
3A
H4
T1
4
MOTOR
2
FAN ON
L
M1
MOTOR STARTER
FAN O N
BLOWER
120vac
120VAC
2
M1OL
M1-OL
9C
MV MV/PV PV GND 24V(GND) 24V SPARK SENSE
CR2
S8600B
SSOV
MVMV
PV
40VA
120VAC
24VAC
X2
X1
2
SAFETY SHUTOFF
VALV E
PILOT VALVE
CONTROL
IGNITION
13
SP
FR
L
12
BURNER ON LIGHT
CR2
9C
10
OFF
WINTER
SUMMER
CYCLE STAT
WINTER
3332
TEMP. CONTROL
AMPLIFIER
18
19
11
14
12A
FLAME
ROD
SPARK
PLUG
8A
LOW PRES.
SWITCH
HI PRES.
SWITCH
CNO
CNC
NC
99A 9B
3B3C3D
4041
3 PHASE ONLY
BURNER ON RELAY 24VAC
L
TD1
TD1
BURNER LOCKOUT
24
TIME DELAY (30S)
CR2
50
LIGHT
L
2
25
FILTERS
CHECK
PRIMARY CONNECTION
T1 TRANSFORMER
H4 - COMMON
BREAKER
132
FUSABLE DISCONNECT
GROUND SHIELDED CABLE AT CONTROL PANEL
FIGURE 40: Standard Discharge Control Remote (SDC) Wiring Diagram (2005)
82 of 147
Page 93
FIGURE 41: Deluxe Temperature Control Remote (DTC) Wiring Diagram (2005)
SECTION 17: ELECTRICAL
L3
L2
L1
FUSABLE DISCONNECT
1
8
CHECK
FILTERS
2
CR2
BREAKER
CR1
HI TEMP
LIMIT
TAS-3
MANUAL
RESET
LOW PRES.
SWITCH
CNO
NC
25
L
HI PRES.
SWITCH
CNC
3 PHASE ONLY
H2H1
3 AMP
X1
FAN
31
AUTO
ON
OFF
33
7
8A
9A
9
9B
H3
120vac
H4
X2
SUMMER
WINTER
9C
BREAKER
T1
250VA
3A
IGNITION
CONTROL
S8600B
MV MV/PV PV GND 24V(GND) 24V SPARK SENSE
M1OL
TH8110
3B3C3D
M1
4
9C
18
19
11
X1
24VAC
X2
14
12A
12
BLOWER
MTR
MOTOR
T4
24VAC
R
G
CR1
50
TD1
CR2
TIME DELAY (30S)
13
10
40VA
120VAC
SSOV
MV
20VA
C
M1
FAN O N
24
PV
CR2
L
L
SP
MV
M1-OL
L
TD1
FLAME
ROD
FR
SPARK
PLUG
2
2
THERMOSTAT
TH8110R 1008/U
THERMOSTAT CONTROL
RELAY 8
MOTOR STARTER
FAN O N
BURNER LOCKOUT
LIGHT
PILOT VALVE
SAFETY SHUTOFF
VALV E
BURNER ON RELAY 24VAC
BURNER ON LIGHT
TCA-A1044C
1
WIRE CONNECTIONS
REMOTE TO MAIN PANEL
1, 2, 3A, 4, 7, 12, 24, 25
40, 41 (SHIELD)
44
TEMPERATURE
1
MONITOR
46
2453
TS144C
GROUND SHIELDED CABLE AT CONTROL PANEL
32
40
41
45
TEMPERATURE
SELECTOR
T244A
54
9C
67
4849
MODULATING
REGULATING
VALVE MRV
120VAC
15
24VAC
X1
8
9
TEMP CONTROL
AMPLIFIER
T3
2
20VA
X2
16
T1 TRANSFORMER
PRIMARY CONNECTION
H1 - 460 USE 1.6 AMP BREAKER
H2 - 230 USE 3.0 AMP BREAKER
H3 - 208 USE 4.0 AMP BREAKER
H4 - COMMON
83 of 147
Page 94
H2 - 230 USE 3.0 AMP BREAKER
H3 - 208 USE 4.0 AMP BREAKER
H1 - 460 USE 1.6 AMP BREAKER
RM7890A
49
TD114
TEMPERATURE
SELECTOR
1
2
3
44
MONITOR
TEMPERATURE
TS114
1
45
40
2
4841
2
TCA-A1014
TEMP CONTROL
AMPLIFIER
13546
SCANNER
UV
14
13
87
16
VALVE MRV
REGULATING
MODULATING
BURNER ON
IGNITION
TRANSFORMER
PILOT VALVE
VALV E
SAFETY SHUTOFF
CONTROL
IGNITION
X1
15
20VA
24VAC
X2
T3
9
2
F
G
12
10
6
8
3
SP
11
SSOV
BURNER ON
A
T2
PV
FUSABLE DISCONNECT
M1
1
L1
BURNER
ON
OFF
4
H1
FAN
OFF
ON
H3
H2
X1
X2
H4
T1
250VA
L3
L2
M1
FAN ON
MOTOR STARTER
FAN O N
A
3A
M1
M1-OL
2
MOTOR
BLOWER
OL
MTR
120 VAC
FUSES BY OTHERS
WIRE CONNECTIONS
REMOTE TO MAIN PANEL
1, 2, 3A, 4, 7, 12,
40, 41 (SHIELD)
H4 - COMMON
PRIMARY CONNECTION
T1 TRANSFORMER
7
HI TEMP
LIMIT
HLS
MANUAL
RESET
88A9
LOW PRES.
SWITCH
0.3" W.C.
HI PRES.
SWITCH
1. 4 " W. C.
CNOCNC
NC
3B3C3D
7
9A 9B 9C
20
CLIP JR2
GROUND SHIELDED CABLE AT CONTROL PANEL
CONTROL
PRIMARY
IGNITION
SCANNER
UV
G
RM7897C
14
9
8
5
F
13
10
2
7
11
10
6
2
12
FOR 2020 AND 2030
CLIP JR2
7
9C
20
3 PHASE ONLY
10
BREAKER
BREAKER
3 AMP
B-SERIES INSTALLATION, OPERATIONAND SERVICE MANUAL
C1-01=20 ACCEL TIME (SEC)
C1-02=20 DECEL TIME (SEC)
d2-02=50% MINIMUM HZ (50%=30HZ)
H1-03=10, H1-04=11, H1-05=0F
H1-07=0F (V1000 ONLY)
L2-01=1, L5-01=5
ACCEL
DECEL
ACCEL/DECEL
CONTACTS
WIRED BY
OTHERS
1
2
4
(L1)
(L2)
HIGH
LOW
B
60
120V
61
W
R
62
2
MODULATING
DAMPER
MOTOR
NOTE: MOTOR STARTER,
L1
L2
T1
T2
20VA
MODULATING
REGULATING
VALVE
REDUCED FLOW SWITCH
49A
48
R4B
49
NC
C
29
2
R4B
1
Damper Switch
DM2
0
1.0
1.0
PHOTOHELIC
PROFILE PLATE
PRESSURE
PROFILE PLATE
BEFORE
AFTER
PHOTOHELIC PNEUMATIC DIAGRAM
+
-
BURNER
Part NumberDescriptionModels
VAVVAV Control Wiring2010 and 2010B
17.6 Additional Control Wiring
Depending on the style of the air handler (MUA, FR,
AM or VAV), there may be additional control wiring
that will be factory installed when the air handler is
ordered. Any additional control wiring that is added to
the air handler will be on the supplemental option
sheet. On the MUA style, there are no additional
controls unless an optional feature is added. The FR
style air handler uses a fixed damper and also does
not require additional control wiring unless an
optional feature is added.
The VAV style air handler controls a floating damper
and a variable frequency drive (VFD) and requires
additional control wiring. For additional VAV style
wiring for models 2010 and 2010B, See Page 90,
Figure 48 and Page 92, Figure 50. For additional
VAV style wiring for models 2020 and 2030, See
Page 91, Figure 49 and Page 93, Figure 51 through
Page 95, Figure 53.
The AM style air handler controls a floating damper
and requires additional control wiring. For additional
AM style wiring for models 2010 and 2010B, See Page 96, Figure 54. For additional AM style wiring for
models 2020 and 2030, See Page 96, Figure 55.
FIGURE 48: Additional Control Wiring for VAV Style (2010 and 2010B)
90 of 147
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.