WCM-D Instruction Sheet
CAT5 Data connections
to RAKO Wired system
Wiring Switches to the WCM-D
Switches must be Momentary Action types
Switch cables must be 200mm maximum length
Each switch must be connected to the 10 way terminal housing. One switch wire must go to either Common 1 or
Common 2.
The other switch wire must go to one of 1, 2, 3, 4 or 5
Programming the WCM-D
The WCM-D is programmed in Rasoft as a Wired Plate.
To put WCM-D into setup mode, either press buttons G & I together (as for a Wired Plate), or short Setup terminal to
Common 2 for several seconds.
Map switches as follows:
WCM-D allows Custom & Third Party Switch Plates to be used in place of standard Rako Push Button
panels to control a Rako Wired system. WCM-D will fit inside a single gang back box. The switch
plate must be formed of Momentary Action switches which have short wires to terminals on the
WCM-D.