The MAX6754–MAX6764 low-power window detectors
monitor undervoltage/overvoltage conditions on system
power supplies. These devices assert when the monitored voltage is under the undervoltage and/or over the
overvoltage thresholds.
The MAX6754–MAX6759/MAX6763/MAX6764 monitor a
single voltage. The MAX6760/MAX6761/MAX6762
monitor dual-voltage systems. The MAX6754/MAX6755/
MAX6756 provide a single undervoltage/overvoltage
output and the MAX6757–MAX6764 provide independent undervoltage and overvoltage outputs. The outputs are available in push-pull or open-drain
configurations.
The MAX6754–MAX6762 offer factory-fixed voltage
thresholds for monitoring system voltages from 0.9V to
5V with a selectable ±5%, ±10%, or ±15% window voltage. The MAX6763/MAX6764 allow for externally
adjustable thresholds. The MAX6754–MAX6762 are
available in two delay timing options (20µs, typ or
100ms, min). The MAX6760/MAX6761/MAX6762 also
include a latched overvoltage output function and the
MAX6754–MAX6762 include a manual reset input.
The family of products is available in small SOT23 and
TDFN packages and is specified over the extended
temperature range of -40°C to +125°C.
Applications
Features
♦ Single- or Dual-Supply Voltage Monitors
♦ Factory-Trimmed Window Threshold Options for
5V, 3.3V, 3V, 2.5V, 1.8V, 1.5V, 1.2V, and 0.9V
Supplies
♦ Externally Adjustable Window Monitoring Options
for Supplies Down to 0.5V
♦ Selectable Window Threshold Options (±5%,
±10%, ±15%)
♦ Single (Combined UV/OV) or Dual (Separate UV
and OV) Outputs
♦ 20µs (typ) or 100ms (min) Timeout Period Options
For pricing, delivery, and ordering information, please contact Maxim/Dallas Direct! at
1-888-629-4642, or visit Maxim’s website at www.maxim-ic.com.
*Note: Insert the threshold level suffixes for VCCand V
CC2
(Tables 1 and 2) after UK, UT, or TA. For the
MAX6754–MAX6759, insert only the VCCthreshold suffix after
the UK or UT. Insert the reset timeout delay (Table 3) after D to
complete the part number. For example, the MAX6760TALTD3-T
provides a V
CC
threshold of 5V, a V
CC2
threshold of 3.3V, and a
100ms minimum reset timeout period. Sample stock is generally
held on standard versions only (see the Standard Versions
table). Standard versions have an order increment requirement
of 2500 pieces. Nonstandard versions have an order increment
requirement of 10,000 pieces. Contact factory for availability.
Ordering Information continued at end of data sheet.
= 0 to 6.0V (MAX6760–MAX6762), TA= -40°C to +125°C, unless otherwise noted. Typical values are at TA=
+25°C.) (Note 1)
Stresses beyond those listed under “Absolute Maximum Ratings” may cause permanent damage to the device. These are stress ratings only, and functional
operation of the device at these or any other conditions beyond those indicated in the operational sections of the specifications is not implied. Exposure to
absolute maximum rating conditions for extended periods may affect device reliability.
(Voltages with respect to GND)
V
CC
, V
CC2
, ............................................................-0.3V to +6.5V
SET, OVLATCH, MR, UVIN, OVIN ..............-0.3V to (V
CC
+ 0.3V)
UV, RESET, OV (open drain) .................................-0.3V to +6.5V
RESET, OV, UV, UV, RESET (push-pull).....-0.3V to (V
CC
+ 0.3V)
Input/Output Current (all pins) ............................................20mA
Continuous Power Dissipation (T
A
= +70°C)
5-Pin SOT23-5 (derate 7.1mW/°C above T
A
= +70°C)....571mW
6-Pin SOT23-6 (derate 8.7mW/°C above T
A
= +70°C)....696mW
8-Pin TDFN (derate 24.4mW/°C above T
A
= +70°C).....1951mW
Operating Temperature Range .........................-40°C to +125°C
= 0 to 6.0V (MAX6760–MAX6762), TA= -40°C to +125°C, unless otherwise noted. Typical values are at TA=
+25°C.) (Note 1)
Note 1:Devices are production tested at +25°C. Overtemperature limits are guaranteed by design.
Note 2:Voltage monitoring requires that V
CC
must be greater than or equal to 1.4V, but outputs remain asserted in the correct
state for V
CC
down to 1.0V.
Note 3:Guaranteed by design.
Note 4:For D0 window detector options and OV outputs, startup delay time is the time required for the internal reference/circuitry
to reach specified accuracy after the monitor is powered up from GND.
Note 5:The input bias voltage is based off of V
CC
. The minimum value is given by the equation (0.1 x V
Active-Low Manual Reset Input. Drive MR low to assert undervoltage
and reset outputs. The asserted output remains asserted for the
specified propagation delay period after MR goes high. MR is internally
pulled up to V
Reset Output. The Reset Output asserts when V
selected UV
output deasserts after the specified timeout period after V
above the UV
MAX6754: Active-low push-pull output (RESET).
MAX6755: Active-high push-pull output (RESET).
MAX6756: Active-low open-drain output (RESET).
Threshold Window Select Input. SET configures the undervoltage and
overvoltage window range for the internal detectors. Connect SET to
GND for ±5% window, or to V
for a ±15% window.
CC
through a 26kΩ resistor.
CC
threshold or above the selected OVTH threshold. Reset
TH
threshold or drops below the OVTH threshold.
TH
powers the device. VCC is the monitored
CC
powers the device.
CC
for ±10% window. Bias SET to VCC/2
CC
is below the
rises
CC
—46—
—— 3—V
555OV
UV/
UV
CC2
Undervoltage Output. UV/UV asserts when the monitored
supply/supplies are below the UV
deasserts after the specified timeout period when the monitored
supply/supplies rise above the UV
propagation delay after MR goes high.
MAX6757/MAX6760: Active-low push-pull output (UV).
MAX6758/MAX6761: Active-high push-pull output (UV).
MAX6759/MAX6762: Active-low open-drain output (UV).
V
Voltage Input. Input for the second window voltage monitor, and
CC2
device output power supply when V
Active-Low Overvoltage Output. OV asserts low when the monitored
supply/supplies are above their overvoltage threshold (OV
high impedance immediately when the monitored supply/supplies drop
below OV
There is no timeout delay period for the OV output.
For MAX6763/MAX6764, OV is low when OVIN is above the internal
0.5V threshold. OV is high when OVIN is below the internal 0.5V
threshold.
MAX6757–MAX6762: Active-low open-drain output.
MAX6763: Active-low push-pull output.
MAX6764: Active-low open-drain output.
Overvoltage Output Latch Control Input. Drive OVLATCH high to latch
the overvoltage output for any V
OVLATCH low to clear the latch after overvoltage conditions have been
removed. The latch is transparent when OVLATCH is connected to
GND. OVLATCH is a high-impedance input. Use external pullup or
pulldown.
Undervoltage Input. UV is low when UVIN is below the internal 0.5V
threshold. UV is high when UVIN is above the internal 0.5V threshold.
Undervoltage Output. UV is low when UVIN is below the internal 0.5V
threshold. UV is high when UVIN is above the internal 0.5V threshold.
There is no timeout delay period for the UV output.
Overvoltage Input. OV is low when OVIN is above the internal 0.5V
threshold. OV is high when OVIN is below the internal 0.5V threshold.
Exposed Pad. EP is internally connected to GND. Leave EP
unconnected or connect to GND.
The MAX6754–MAX6764 are low-power window voltage detectors capable of monitoring undervoltage and
overvoltage conditions on system power supplies.
Whenever a monitored voltage falls below its undervoltage threshold or exceeds its overvoltage threshold,
these devices assert their outputs to notify the system
(see Functional Diagrams).
The MAX6754/MAX6755/MAX6756 are single-voltage
window detectors with internally fixed nominal voltage,
externally adjustable set window, single reset
under/overvoltage output, and a manual reset input.
The MAX6757/MAX6758/MAX6759 are single-voltage
window detectors with internally set nominal voltage,
externally adjustable set window, separate under/overvoltage outputs, and manual reset input.
The MAX6760/MAX6761/MAX6762 are dual-voltage
window detectors with internally/externally set nominal
voltages, externally adjustable set window, separate
under/overvoltage outputs, manual reset input, and
overvoltage latch functions.
The MAX6763/MAX6764 are single adjustable window
detectors with separate under/overvoltage outputs.
The MAX6754–MAX6762 offer factory-fixed voltage
thresholds for monitoring system voltages from 0.9V to
5V. The MAX6754–MAX6762 include a SET function to
select the window voltage to ±5%, ±10%, or ±15%. The
MAX6763/MAX6764 allow for externally adjustable
upper and lower voltage thresholds to be set externally
(down to 0.5V). The MAX6754–MAX6762 are available
with two timing options (20µs propagation delay or
100ms minimum reset timeout).
Supply Voltages
VCCis the power-supply input and the monitored voltage
of the MAX6754–MAX6762. These devices feature a factory-trimmed VCCand V
CC2
divider that sets the nominal
input range (see Tables 1 and 2). VCCfor the MAX6763/
MAX6764 is the power supply of the device and not the
monitored voltage. For noisy systems, bypass VCCand
V
CC2
each with a 0.1µF capacitor to GND.
Setting the Adjustable Nominal Voltage
Threshold
The MAX6760/MAX6761/MAX6762 (versions with suffixes LA, TA, RA, ZA, WA, and AA) offer adjustable nominal
voltage threshold to monitor V
CC2
. Use an external volt-
age-divider to set the voltage at V
CC2
to 0.4255V.
Configure SET to select a monitor window of ±5%,
±10%, or ±15% (see Figure 5). The MAX6760/MAX6761/
MAX6762 suffix AA monitor only V
Choose R2 to have a resistance of up to 500kΩ.
Calculate R1 by:
R1 = ((V+- 0.4255V) x R2) / 0.4255V
The MAX6763/MAX6764 provide inputs to a window
detector allowing the programming of the threshold
voltage to within VCC(see Figure 6).
Choose R1, R2, and R3 such that:
(V+ / (R1 + R2 + R3)) ≥ 1µA
SET
The MAX6754–MAX6762 allow the setting of the window
voltage range of the voltage detector. Connect SET to
GND to set a ±5% window. Connect SET to V
CC
for a
±10% window. Bias SET to VCC/2 for a ±15% window.
Manual Reset (MR)
The MAX6754–MAX6762 include an active-low manual
reset input. Drive MR low to assert a reset output
(MAX6754/MAX6755/MAX6756) or an undervoltage
output (MAX6757/MAX6758/MAX6759). The output
remains asserted for the specified propagation delay
time (see Figure 7) after MR goes high. MR is internally
pulled to VCCwith a 26kΩ resistor.
Overvoltage Latch Control Input
(OVLATCH)
The MAX6760/MAX6761/MAX6762 provide an overvoltage latch control input (OVLATCH). Drive OVLATCH
high to latch the overvoltage output for any VCCor
V
CC2
overvoltage condition. Drive OVLATCH low to
clear the latch after overvoltage conditions have been
removed. The latch is transparent when OVLATCH is
connected to GND. OVLATCH is a high impedance
input. Use external pullup or pulldown.
Reset, Undervoltage, and Overvoltage
Outputs (RESET,
RESET, UV
, UV, OV)
RESET, RESET, UV, UV, and OV outputs assert when
the monitored supply is below the selected UV
TH
threshold or above the selected OVTHthreshold. The
reset output deasserts after the specified timeout period when the monitored supply rises above the UV
TH
threshold or drops below the OVTHthreshold. The
push-pull versions are referenced to VCC.
The MAX6760/MAX6761/MAX6762 monitor both V
CC
and V
CC2
. An under/overvoltage condition on either
voltage supply asserts the corresponding output.
RESET and UV are guaranteed to be in the correct
logic state when V
Figure 8 shows a microprocessor monitoring circuit. An
overvoltage condition on either the core or I/O supply
turns the SCR on, blowing the fuse to disconnect the
circuit from the power source. An optional capacitor
(C1) on the gate of the SCR provides additional transient immunity against nuisance trips.
*Note: Insert the threshold level suffixes for VCCand V
CC2
(Tables 1 and 2) after UK, UT, or TA. For the
MAX6754–MAX6759, insert only the V
CC
threshold suffix after
the UK or UT. Insert the reset timeout delay (Table 3) after D to
complete the part number. For example, the MAX6760TALTD3-T
provides a V
CC
threshold of 5V, a V
CC2
threshold of 3.3V, and a
100ms minimum reset timeout period. Sample stock is generally
held on standard versions only (see the Standard Versions
table). Standard versions have an order increment requirement
of 2500 pieces. Nonstandard versions have an order increment
requirement of 10,000 pieces. Contact factory for availability.
Table 1. Window Threshold Voltage
Suffix Guide Single Fixed V
CC
(MAX6754—MAX6759)
Table 2. Window Threshold Voltage
Suffix Guide Dual Fixed/Adjustable
(MAX6760/MAX6761/MAX6762)
*See Setting the Adjustable Nominal Voltage Threshold Section.
Table 3. Timeout Period Suffix Guide
**Future product—contact factory for availability.
(The package drawing(s) in this data sheet may not reflect the most current specifications. For the latest package outline information,
go to www.maxim-ic.com/packages.)
(The package drawing(s) in this data sheet may not reflect the most current specifications. For the latest package outline information,
go to www.maxim-ic.com/packages.)
SOT-23 5L .EPS
PACKAGE OUTLINE, SOT-23, 5L
1
21-0057
E
1
MAX6754–MAX6764
Low-Power, Single/Dual-Voltage Window
Detectors
Maxim cannot assume responsibility for use of any circuitry other than circuitry entirely embodied in a Maxim product. No circuit patent licenses are
implied. Maxim reserves the right to change the circuitry and specifications without notice at any time.
22 ____________________Maxim Integrated Products, 120 San Gabriel Drive, Sunnyvale, CA 94086 408-737-7600
(The package drawing(s) in this data sheet may not reflect the most current specifications. For the latest package outline information,
go to www.maxim-ic.com/packages.)
6LSOT.EPS
PACKAGE OUTLINE, SOT-23, 6L
1
21-0058
F
1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.