Rainbow Electronics DS18S20 User Manual

r
(
)
(
)
C
C
8
5
DS18S20
High Precision
1-Wire
®
Digital Thermomete
FEATURES
Unique 1-wire interface requires only one
port pin for communication
Each device has a unique 64-bit serial code
stored in an on-board ROM
Multi-drop capability simplifies distributed
Requires no external components
Can be powered from data line. Power supply
range is 3.0V to 5.5V
Measures temperatures from –55°C to
+125°C (–67°F to +257°F)
• ±0.5°C accuracy from –10°C to +85°C
9-bit thermometer resolution
Converts temperature in 750 ms (max.)
User-definable nonvolatile alarm settings
Alarm search command identifies and
addresses devices whose temperature is outside of programmed limits (temperature alarm condition)
Applications include thermostatic controls,
industrial systems, consumer products, thermometers, or any thermally sensitive system

PIN ASSIGNMENT

DALLAS DS1820
2 3
1
N N
V
DD
DQ
8-pin 150-mil SOIC
DQ
GND
DD
V
1
2 3
BOTTOM VIEW
TO-92
DS18S20

PIN DESCRIPTION

GND - Ground
1
DS1820
2
3
4
7
6
(DS18S20Z)
NC NC
NC GND
DQ - Data In/Out V
- Power Supply Voltage
DD
NC - No Connect

DESCRIPTION

The DS18S20 Digital Thermometer provides 9–bit centigrade temperature measurements and has an alarm function with nonvolatile user-programmable upper and lower trigger points. The DS18S20 communicates over a 1-wire bus that by definition requires only one data line (and ground) for communication with a central microprocessor. It has an op eratin g tempera ture ran ge of –55°C to +125°C and is accurate to ±0.5°C over the ran ge of –10°C to +85°C. In addition, the DS18S20 can derive power directly from the data line (“parasite power”), eliminating the need for an external power supply.
Each DS18S20 has a unique 64-bit serial code, which allows multiple DS18S20s to function on the same 1–wire bus; thus, it is simple to use one microprocessor to control many DS18S20s distributed over a large area. Applications that can benefit from this feature include HVAC environmental controls, temperature monitoring systems inside buildings, equipment or machinery, and process monitorin g and control systems.
1 of 21 043001
DETAILED PIN DESCRIPTIONS Table 1
V
8-PIN SOIC* TO-92 SYMBOL DESCRIPTION
DS18S20
5 1 GND
Ground.
4 2 DQ Data Input/Output pin. Open-drain 1-wire interface pin. Also
provides power to the device when used in parasite power mode (see “Parasite Power” section.)
3 3 VDD Optional VDD pin. VDD must be grounded for operation in
parasite power mode.
*All pins not specified in this table are “No Connect” pins.

OVERVIEW

Figure 1 shows a block diagram of the DS18S20, and pin descriptions are given in Table 1. The 64-bit ROM stores the device’s unique serial code. The scratchpad memory contains the 2-byte temperature register that stores the digital output from the temperature sensor. In addition, the scratchp ad provides access to the 1-byte upper and lower alarm trigger registers (TH and TL). The TH and TL registers are nonvolatile (EEPROM), so they will retain data when the device is powered down.
The DS18S20 uses Dallas’ exclusive 1-wire bus protocol that implements bus communication using one control signal. The control line requires a weak pullup resistor since all devices are linked to the bus via a 3-state or open-drain port (the DQ pin in the case of the DS18S20). In this bus system, the microprocessor (the master device) identifies and addresses devices on the bus using each device’s unique 64-bit code. Because each device has a unique code, the number of devices that can be addressed on one bus is virtually unlimited. The 1-wire bus protocol, including detailed explanations of the commands and “time slots,” is covered in the 1-WIRE BUS SYSTEM section of this datasheet.
Another feature of the DS18S20 is the ability to operate without an external power supply. Power is instead supplied through the 1-wire pullup resistor via the DQ pin when the bus is high. The high bus signal also charges an internal c apacitor (CPP), which then supplies power to the device when the bus is low. This method of deriving power from the 1-wire bus is referred to as “parasite power.” As an alternative, the DS18S20 may also be powered by an external supply on VDD.

DS18S20 BLOCK DIAGRAM Figure 1

V
PU
4.7K
DQ
GND
DD
PARASITE POWER
CPP
CIRCUIT
INTERNAL VDD
POWER
SUPPLY
SENSE
64-BIT ROM
AND
1-wire PORT
MEMORY CONTROL
LOGIC
SCRATCHPAD
DS18S20
TEMPERATURE SENSOR
ALARM HIGH TRIGGER (TH)
REGISTER (EEPROM)
ALARM LOW TRIGGER (TL)
REGISTER (EEPROM)
8-BIT CRC GENERATOR
2 of 21
DS18S20

OPERATION – MEASUR ING TEMPE RAT URE

The core functionality of the DS18S20 is its direct-to-digital temperature sensor. The temperature sensor output has 9-bit resolution, which corresponds to 0.5°C steps. The DS18S20 powers-up in a low-power idle state; to initiate a temperature measurement and A-to-D conversion, the master must issue a Convert T [44h] command. Following the conversion, the resulting thermal data is stored in the 2-byte temperature register in the scratchpad memory and the DS18S20 returns to its idle state. If the DS18S20 is powered by an external supply, the master can issue “read time slots” (see the 1-WIRE BUS SYSTEM section) after the Convert T command and the DS18S20 will respond by transmitting 0 while the temperature conversion is in progress and 1 when the conversion is done. If the DS18S20 is po wered with parasite power, this notification technique cannot be used sinc e the bus must be pulled high by a strong pullup during the entire temperature conversion. The bus requirements for parasite power are explained in detail in the POWERING THE DS18S20 section of this datasheet.
The DS18S20 output data is calibrated in degrees centigrade; for Fahrenheit applications, a lookup table or conversion routine must be used. The temperature data is stored as a 16-bit sign-extended two’s complement number in the temperature register (see Figure 2). The sign bits (S) indicate if the temperature is positive or negative: for positive numbers S = 0 and for negative numbers S = 1. Table 2 gives examples of digital output data and the corresponding temperature reading.
Resolutions greater than 9 bits can be calculated using the data from the temperature, COUNT REMAIN and COUNT PER °C registers in the scratchpad. Note that the COUNT PER °C register is hard-wired to 16 (10h). After reading the scratchpad, the TEMP_READ value is obtained by truncating the 0.5°C bit (bit 0) from the temperature data (see Figure 2). The extended resolution temperature can then be calculated using the following equation:
REMAINCOUNTCPERCOUNT
READTEMPETEMPERATUR
25.0_
+=
___
CPERCOUNT
__
Additional information about high-resolution temperature calculations can be found in Application Note 105: “High Resolution Temperature Measurement with Dallas Direct-to-Digital Temperature Sensors”.

TEMPERATURE REGISTER FORMAT Figure 2

bit 7
LS Byte
MS Byte
26 2
bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
S S S S S S S S
bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
5
2
4
2
3
2
2
2
1
2
0
2
-1

TEMPERATURE/DATA RELATIONSHIP Table 2

TEMPERATURE DIGITAL OUTPUT
(Binary)
+85.0°C* 0000 0000 1010 1010 00AAh
+25.0°C 0000 0000 0011 0010 0032h
+0.5°C 0000 0000 0000 0001 0001h
0°C 0000 0000 0000 0000 0000h
-0.5°C 1111 1111 1111 1111 FFFFh
-25.0°C 1111 1111 1100 1110 FFCEh
-55.0°C 1111 1111 1001 0010 FF92h
*The power-on reset value of the temperature register is +85°C
DIGITAL OUTPUT
(Hex)
3 of 21
DS18S20

OPERATION – ALARM SIG NALING

After the DS18S20 performs a temperature conversion, the temp erature value is compared to the user­defined two’s complement alarm trigger values stored in the 1-byte TH and TL registers (see Figure 3). The sign bit (S) indicates if the value is positive or negative: for positive numbers S = 0 and for negative numbers S = 1. The TH and TL registers are nonvolatile (EEPROM) so they will retain data when the device is powered down. T
and TL can be accessed through b ytes 2 and 3 of the scratchpad as ex plained
H
in the MEMORY section of this datasheet.

TH AND TL REGISTER FORMAT Figure 3

bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
S 26 2
5
2
5
2
5
2
2
2
1
2
0
Only bits 8 through 1 of the temperat ure register are used in t he TH and TL comparison since TH and T
L
are 8-bit registers. If the result of a temperature measurement is higher than TH or lower than TL, an alarm condition exists and an alarm flag is set inside the DS18S20. This flag is updated after every temperature measurement; therefore, if the alarm condition goes away, the flag will be turned off after the next temperature conversion.
The master device can check the alarm flag status of al l DS 18S20s on the bus b y issuing an Alarm S earch [ECh] command. Any DS18S20s with a set alarm flag will respond to t he command, so the master can determine exactly which DS18S20s have experienced an alarm condition. If an alarm condition exists and the TH or TL settings have changed, another temperature conv ersion should be done to validate the alarm condition.

POWERING THE DS18S20

The DS18S20 can be powered by an external supply on the VDD pin, or it can operate in “parasite power” mode, which allows the DS18S20 to function without a local external supply. Parasite power is very useful for applications that require remote temperature sensing or that are very space constrained. Figure 1 shows the DS18S20’s parasite-power control circuitry, which “steals” power from the 1-wire bus via the DQ pin when the bus is high. The stolen charge powers the DS18S20 while the bus is high, and some of the charge is stored on the parasite power capacitor (CPP) to provide power when the bus is low. When the DS18S20 is used in parasite power mode, the V
pin must be connected to ground.
DD
In parasite power mode, the 1-wire bus and CPP can provide sufficient current to the DS18S20 for most operations as long as the specified timing and voltage requirements are met (refer to the DC ELECTRICAL CHARACTERISTICS and the AC ELECTRICAL CHARACTERISTICS sections of this data sheet). However, when the DS18S20 is performing temperature conversions or copying data from the scratchpad memory to EEPROM, the operating current can be as high as 1.5 mA. This current can cause an unacceptable voltage drop across the weak 1-wire pullup resistor and is more current than can be supplied by C
. To assure that the DS18S20 has sufficient supply current, it is necessary to provide a
PP
strong pullup on the 1-wire bus whenever temperature conversions are taking place or data is being copied from the scratchpad to EEPROM. This can be accompl ished by using a MOSFET to pull the bus directly to the rail as shown in Figure 4. The 1-wire bus must be switched to the strong pullup within 10 µs (max) after a Convert T [44h] or Copy Scratchpad [48h] command is issued, and the bus must be held high by the pullup for the duration of the conversion (t
) or data transfer (t
conv
= 10 ms). No other
wr
activity can take place on the 1-wire bus while the pullup is enabled. The DS18S20 can also be powered by the conventional method of connecting an external power supply to
the V
pin, as shown in Figure 5. The advantage of this method is that the MOSFET pullup is not
DD
required, and the 1–wire bus is free to carry other traffic during the temperature conversion time. 4 of 21
DS18S20
The use of parasite power is not recommended for temperatures above 100°C since the DS18S20 may not be able to sustain communications due to the hi gher leakage current s that can ex ist at these t emperatures. For applications in which such temperatures are likely, it is strongly recommended that the DS18S20 be powered by an external power supply.
In some situations the bus master may not know whether the DS18S20s o n the bus are parasite powered or powered by external supplies. The master needs this information to determine if the strong bus pullup should be used during temperature conversions. To get this information, the master can issue a Skip ROM [CCh] command followed by a Read Power Supply [B4h] command followed by a “read time slot”. During the read time slot, parasite powered DS18S20s will pull the bus low, and externally powered DS18S20s will let the bus remain high. If the bus is pulled low, the master knows that it must supply the strong pullup on the 1-wire bus during temperature conversions.

SUPPLYING THE PARASITE-POWERED DS18S20 DURING TEMPERATURE CONVERSIONS Figure 4

Micro-
processor
VPU
4.7K
VPU
1-Wire Bus
DS18S20
GND
V
DQ
DD
To Other 1-Wire Devices

POWERING THE DS18S20 WITH AN EXTERNAL SUPPLY Figure 5

Micro-
processor
VPU
4.7K 1-Wire Bus
DS18S20
GND
V
VDD (External Supply)
DQ
DD
To Other 1-Wire Devices

64-BIT LASERED ROM CODE

Each DS18S20 contains a unique 64–bit code (see Figure 6) stored in ROM. The least significant 8 bits of the ROM code contain the DS18S20’s 1–wire family code: 10h. The next 48 bits contain a unique serial number. The most significant 8 bits contain a cyclic redundancy check (CRC) byte that is calculated from the first 56 bits of the ROM code. A detailed explanation of the CRC bits is provided in the CRC GENERATION section. The 64–bit ROM code and associated ROM function control logic allow the DS18S20 to operate as a 1–wire device using the protocol detailed in the 1-WIRE BUS SYSTEM section of this datasheet.

64-BIT LASERED ROM CODE Figure 6

8-BIT CRC 48-BIT SERIAL NUMBER 8-BIT FAMILY CODE (10h)
MSB MSB LSB LSB LSBMSB
5 of 21
DS18S20

MEMORY

The DS18S20’s memory is organized as shown in Figure 7. The memory consists of an SRAM scratchpad with nonvolatile EEPROM storage for the high and low alarm trigger registers (TH and TL). Note that if the DS18S20 alarm function is not used, the TH and TL registers can serve as general-purpose memory. All memory commands are described in detail in the DS18S20 FUNCTION COMMANDS section.
Byte 0 and byte 1 of the scratchpad contain the LSB and the MSB of the temperature register, respectively. These bytes are read-onl y. Bytes 2 and 3 provide access to TH and TL registers. Bytes 4 and 5 are reserved for internal use by the device and cannot be overwritten; these bytes will return all 1s when read. Bytes 6 and 7 contain the COUNT REMA IN and COUNT PER ºC registers, which can be used to calculate extended resolution results as explained in the OPERATION – MEASURING TEMPERATURE section.
Byte 8 of the scratchpad is read-only and contains the cyclic redundancy check (CRC) code for bytes 0 through 7 of the scratchpad. The DS18S20 generates this CRC using the method described in the CRC GENERATION section.
Data is written to bytes 2 and 3 of the scratchpad using the Write Scratchpad [4Eh] command; the data must be transmitted to the DS18S20 starting with the least significant bit of byte 2. To verify data integrity, the scratchpad can be read (using the Read Scratchpad [BEh] command) after the data is written. When reading the scratchpad, data is transferred over the 1-wire bus starting with the least significant bit of byte 0. To transfer the TH and TL data from the scratchpad to EEPROM, the master must issue the Copy Scratchpad [48h] command.
Data in the EEPROM registers is retained when the device is powered down; at power-up the EEPROM data is reloaded into the corresponding scratchpad locations. Data can also be reloaded from EEPROM
to the scratchpad at any time using the Recall E2 [B8h] command. The master can issue “read time slots” (see the 1-WIRE BUS SYSTEM section) following the Recall E2 command and the DS18S20 will indicate the status of the recall by transmitting 0 while the recall is in progress and 1 when the recall is done.
DS18S20 MEMORY MAP cбЦмкЙ=T
SCRATCHPAD (Power-up State)
byte 0 Temperature LSB (AAh)
(85°C)
byte 1 Temperature MSB (00h) byte 2 TH Register or User Byte 1* TH Register or User Byte 1 byte 3 TL Register or User Byte 2* TL Register or User Byte 2 byte 4 Reserved (FFh) byte 5 Reserved (FFh) byte 6 COUNT REMAIN (0Ch) byte 7 COUNT PER °C (10h)
EEPROM
byte 8 CRC*
*Power-up state depends on value(s) stored
in EEPROM
6 of 21
DS18S20

CRC GENERATION

CRC bytes are provided as part of the DS18S20’s 64-bit ROM code and in the 9th byte of the scratchpad memory. The ROM code CRC is calculated from the first 56 bits of the ROM code and is contained in the most significant byte of the ROM. The scratchpad CRC is calculated from the data stored in the scratchpad, and therefore it changes when the data in the scratchpad changes. The CRCs provide the bus master with a method of data validation when data is read from the DS18S20. To verif y that data has been read correctly, the bus master must re-calculate the CRC from the received data and then compare this value to either the ROM code CRC (for ROM reads) or to the scratchpad CRC (for scratchpad reads). If the calculated CRC matches the read CRC, the data has been received error free. The comparison of CRC values and the decision to continue with an operation are determined entirely by the bus master. There is no circuitry inside the DS18S20 that prevents a command sequence from proceeding if the DS18S20 CRC (ROM or scratchpad) does not match the value generated by the bus master.
The equivalent polynomial function of the CRC (ROM or scratchpad) is:
CRC = X8 + X5 + X4 + 1
The bus master can re-calculate the CRC and compare it to the CRC values from the DS18S20 using the polynomial generator shown in Figure 8. This circuit consists of a shift register and XOR gates, and the shift register bits are initialized to 0. Starting with the least significant bit of the ROM code or the least significant bit of byte 0 in the scratchpad, one bi t at a time should shifted into the shift register. After shifting in the 56th bit from the ROM or the most significant bit of byte 7 from the scratchpad, the polynomial generator will contain the re-calculated CRC. Next, the 8-bit ROM code or scratchpad CRC from the DS18S20 must be shifted into the circuit. At this point, if the re-calculated CRC was correct, the shift register will contain all 0s. Additional information about the Dallas 1-wire c yclic redundancy check is available in Application Note 27 entitled “Understanding and Using Cyclic Redundancy Checks with Dallas Semiconductor Touch Memory Products.”

CRC GENERATOR Figure 8

XOR XOR
INPUT
XOR
(MSB) (LSB)
7 of 21
Loading...
+ 14 hidden pages