Rain Bird WS-PRO Installation, Maintenance And Troubleshooting Manual

Page 1
WS-PRO Weather Station
INSTALLATION,
MAINTENANCE
AND
TROUBLESHOOTING
MANUAL
November 2004 GT27145D
Page 2
Page 3
WS-PRO Weather Station
Table of Contents
Description Page
1.0 General........1
2.0 Tools & Supplies.......2
Tools Required......2
Supplies Required......2
3.0 Weather Station Site Selection.....3
Temperature/Relative Humidity....4
Solar Radiation......4
Precipitation.......5
Determining True North for Wind Vane Operation. 5
Prompts from Geomag.....7
4.0 Weather Station Concrete Base.....9
Supplied Components .....9
Installer Supplied......9
Tools Required......9
Installation.......9
5.0 External Wiring to Weather Station....12
Wiring Valve Access Box.....12
Weather Station Power Wiring....12
Weather Station Communication Wiring (PRO-SH) . 13
Grounding Communication Cable....13
Weather Station Communication Wiring (PRO-PH) . 15
6.0 Tower Assembly and Installation ....15
Supplied Components .....15
Installation.......15
7.0 ET Instrumentation Enclosure Installation...18
General.......18
Mounting ET Enclosure to the Tower...18
Page 4
Table of Contents - Cont’d.
Description Page
Installation of Lightning Rod....19
Power Supply Rechargeable Battery....19
AC External Power Wiring.....21
Power Supply Option Solar Panel....22
8.0 Installation of Instrumentation.....24
General.......24
Supplied Components .....24
Installation of Cross-Arm to ET Enclosure...24
Installation of 034A Wind Sensor ....26
Installation of Relative Humidity/Temperature
Sensor and Radiation Shield....28
Installation of Solar Radiation Pyranometer . . 29
Sensor Cable Connections.....30
Configure Sensor Switch Settings ....31
Sensor Verification and Clock Set....31
Short Haul Modem Installation....31
Telephone Modem Installation....33
9.0 Sealing & Desiccating the Enclosure....34
10.0 Installation at Central Computer....35
Supplied Components .....35
Installation.......35
Model PRO-PH ~ Phone Connected....38
Supplied Components ....38
Installation - General.....38
Standard Installation Method . . 38
11.0 Maintenance & Troubleshooting....40
General Maintenance .....40
Instrumentation Maintenance....40
Batteries.......40
Rechargeable Battery.....40
Desiccant.......40
Sensor Maintenance......40
Page ii
Page 5
Table of Contents - Cont’d.
Description Page
1 Week ......40
1 Month......41
6 Months......41
1 Year.......41
2 Years ......41
3 Years ......41
4-5 Years......41
General Maintenance .....41
Sensor Maintenance......42
Rain Gage......42
Calibrating a Rain Bucket...42
Suggestions.....42
Solar Sensor......43
Wind Sensor......43
Relative Humidity Sensor....43
Temperature Sensor.....44
Other Maintenance......44
Seal of ET Enclosure.....44
Battery Check......45
Sensor Testing ......45
Wind Speed Sensor.....46
Wind Direction Sensor....46
Solar Radiation Sensor (Pyranometer) . . 46
Tipping Bucket Rain Gage....46
Temperature/Relative Humidity Sensor . . 47
Troubleshooting......48
Isolating the Problem.... 48
Checking the Weather Station...48
Using the ML 10-KD Keyboard Display . 48
Datalogger Location Table ...49
Troubleshooting Problems....49
No display on the ML 10-KD keyboard . 49
No response using the keyboard and/or
erroneous letters in the display . 50
Page iii
Page 6
Table of Contents - Cont’d.
Description Page
No Response from Datalogger through SC32A
or Modem Peripheral.....50
At the datalogger ...50 At the computer...50
-99999 Displayed in an Input Location . . 51 Unreasonable Results Displayed
in an Input Location.....51
6999 or 99999 Stored in Final Storage . . 51
Using a Laptop Computer....51
Checking the Communications Wire Path...53
Loop Resistance .....53
Ground Resistance.....53
WS-PRO-SH Direct Connect Weather Station . 53
Weather Station will not answer . . 53
Checking the RAD modem...53
Checking the Communication Wire Path . 54 WS-PRO-PH Phone Connect Weather Station . 55
Weather Station will not answer . . 55
Computer Modem & Communication Troubleshooting . 57
Weather Software will not communicate
with the weather station....57
Testing the Short Haul Modem . . 57
Testing the Phone Modem...58
Page iv
Page 7
Appendix
Description Page
Upgrading the Model JR Weather Station
to a Model PRO Weather Station....59
Typical 3-Rod Grounding Grid.....59
Ground Resistance......59
Bentonite Contact......60
Rocky Conditions ......60
Rock Layer.......60
Improving Earth Grounds.....61
MSP-1 Pipe Surge Arrestors.....61
Page v
Page 8
Table of Figures
Figure # Description Page
#1 Effect of Structure on Wind Flow...4
#2 Magnetic Declination for the Contiguous
United States......6
#3 Declination Angles.....8
#4 Concrete Base Detail.....11
#5 Anchor Bolt/Template Detail. . . 11
#6 External Wiring Detail at the PRO-SH Station . 14
#7 External Wiring Detail at the PRO-PH Station . 17
#8 Mounting ET Enclosure on Tower...18
#9 16VAC Connection & Rechargeable
Battery Installation....20
#10 Solar Pane Installation Detail...23
#11 Cross-Arm Mounting Detail....25
#12 Wind Sensor Installation Detail...27
#13 Temperature/RH Sensor Installation Detail. . 28
#14 Solar Radiation Sensor Installation Detail . . 29
#15 Sensor Cable Connections....30
#16 Sensor Switch Settings ....31
#18 Short Haul Modem Installation in ET Enclosure . 32
#19 Telephone Modem Installation in ET Enclosure . 34
Page vi
Page 9
Table of Figures Cont’d.
Figure # Description Page
#20 Desiccant Pack Installation....34
#21 Installation at Central Computer for Direct
Connected Weather Station....37
#22 Installation at Central Computer for
Telephone Connected Weather Station . . 39
#23 Using the ML 10-KD Keyboard Display . . 48
#24 Configuration of Serial Cable...52
#25 Test of Short Haul Modem....54
#26 Test of Communication Wires...55
#28 Typical 3-Rod Grounding Grid Detail . . 62
#29 Testing of Wind Sensor....63
#30 Testing of Solar Radiation Sensor...64
#31 Testing of Rain Gage.....65
#32 Testing of Temperature/RH Sensor...66
#33 Testing of Air Temperature Probe...67
Page vii
Page 10
Page viii
Page 11
WS-PRO Weather Station
1.0 GENERAL:
The Rain Bird “Model PRO” Weather Station, when used in conjunction with the Rain Bird MAXI 5, MAXI “Nimbus” or MAXI “Cirrus” Central Control system, provides the irrigation manager with a powerful tool to aid in the growing of lush, healthy, green turfgrass, while conserving important resources, such as water, power, etc.
The MAXI 5, MAXI Nimbus or MAXI Cirrus software interrogates the Weather Station to gather information that has been gathered on a daily basis, on 5 second intervals for short haul modem only, of the climatic conditions that affect the irrigation application for the area.
The MAXI 5, MAXI Nimbus or MAXI Cirrus software subjects the climatic information that it gathers to a version of the modified Penman Equation. The Penman Equation has been proven through over 35 years of university research, to be one of the most reliable predictors of turfgrass water use requirements.
The Weather Station monitors the following climatic conditions:
Rainfall Wind Speed & Direction
Air Temperature Relative Humidity Solar Radiation
The basic PRO Weather Station configuration includes sensors to monitor these conditions, a micrologger to capture this data, a modem to communicate the information to the MAXI Central Computer and a power supply.
The Rain Bird Model “PRO” Weather Station is available in two (2) basic configurations;
Model PRO-SH, which is a direct wire system intended for use when the weather station is within 20,000 feet of the MAXI Central Computer and communication is via a wire path, between the weather station and the computer.
Model PRO-PH, which is a phone modem system for use when the weather station is further than 20,000 feet from the MAXI Central Computer or when they cannot be connected by a communication wire path. The system communicates utilizing a standard, dedicated phone service.
Page 1
Page 12
2.0 TOOLS & SUPPLIES: (Installer Supplied)
The installer needs access to the following tools and supplies for installation of the Weather Station.
TOOLS REQ’D.
Shovel
SUPPLIES REQ’D. Rake Wire Strippers Screw driver, regular blade Flat Metal File Screw driver, thin regular blade Wheelbarrow Screw driver, Phillips head Hand Saw Open End Wrench 7/16” (2) - Open End Wrench 9/16” Open End Wrench ½” Open End Wrench 3/8” Claw Hammer Magnetic Compass Tape Measure 12’ - 20’ Matr’l. for Concrete Base Form:
(4) 12” Wood Stakes
(1) 2”x 4”x 10’ piece of wood
(8) 8p double-head nails (8)16p double-head nails 20 ft. of form wire
½ yard of concrete 6 Ft. Step Ladder Concrete trowel & edger Saw Horse Wire Fish Tape or small dia. rope
(2) Standard Size (12” x 18”)
Rectangular Valve Boxes
(3) MGP-1 Maxi Grounding Plate
Assembly
(5) MSP-1 Maxi Surge Arrestor (Pipe
Type) (for “PRO-SH” model ONLY).
(6) 5/8” Dia. X 8’-0” copper clad
grounding rods #10 Gauge or larger bare copper grounding wire - length as required. Brass Grounding Clamps - as required (20) 3-M model DBY or DBR Direct
Burial splice kits or 3-M Scotch-lok
3500 series Connector Packs. Belden #9883 or PE-39 direct burial,
communication cable - length as
required. (2) Lengths of type UF power wire
(white and black) - size and length as
required. (1) 4” x 4” electrical junction box with
cover plus connectors as required for
transformer mounting. (2) Open Spade, crimp-on type
connectors - for connecting power
wiring to transformer.
3.0
Page 2
Page 13
WEATHER STATION SITE SELECTION:
Site selection for the Weather Station is one of the most crucial steps in a successful installation and an efficiently operating irrigation system. The site selection will greatly impact the accuracy of the meteorological data collected by the station. The site selection process has many constraints placed on it, and although the “perfect” site is often non-existent, the following generalities should be kept in mind.
In general, the site should be representative of the general area of interest and reflect the general conditions of the project’s turf. The more “typical” the site, in this regard, the more useful will be the information gathered. The site should also be away from the influence of obstructions such as buildings, trees, etc.
The weather station should not be located where sprinkler irrigation water will strike sensors or instrument enclosure. The turf around the weather station needs to be irrigated however - so it is recommended that half-circle sprinklers be placed around the base of the weather station and ”throwing OUT’ away from the weather station. In this way the turf can be irrigated and at the same time water can be kept off the sensors and instrument enclosure of the weather station.
The sensors of the weather station should be eight (8) to ten (10) feet above the turfgrass. Remember that the roof of a building IS NOT a good site for the weather station.
The weather station does NOT need to be “hidden”. The Rain Bird weather station has been engineered to be aesthetically pleasing. The urge to “hide” the station needs to be balanced with the selection of the most “typical” turfgrass area. The station should NOT negatively impact the turfgrass environment or utility. In fact, many installations prominently display the Weather Station to demonstrate their commitment to water conservation.
If the site may be prone to vandalism, an open, chain-link, 6 foot high security fence with a lockable access gate should be placed around the weather station. The fence shall be a minimum of eight (8) feet out from the weather station on all sides and should be a type that will not interfere with the accuracy of the sensors.
In your selection of a site - try to avoid sites on or near open dirt fields and asphalt parking areas. These sites are prone to high invective heats that can distort the information. Any areas that are within 90 to 100 feet “up wind” of the weather station can adversely affect the weather station reading accuracies.
The requirements of each weather station sensor must be considered when selecting the proper location for a weather station site. In addition to these generalities, each sensor has its own specialized constraints. While complete information is available, upon special request, for each individual sensor, the following are the highlights of each.
Page 3
Page 14
(a) TEMPERATURE AND
RELATIVE HUMIDITY:
Sensors should be located over an open level turf area at least 30 feet in diameter. The surface should be the typical turfgrass of the area in interest. Sensors should be located a distance away of at least four (4) times the height of any nearby obstruction and at least 90 feet from large paved areas. Sensors should be protected from thermal radiation, and adequately ventilated.
Situations to avoid include:
large industrial heat sources
rooftops
steep slopes
sheltered hollows
high vegetation
shaded areas
top of a hill
bottom of a swale
swamps
areas where snow drifts occur
low places holding standing
water
(b) SOLAR RADIATION:
Pyranometers should be located to avoid shadows on the sensor at any time. Mounting it on the southern most portion (northern hemisphere) of the weather station will minimize the chance of shading from other weather station structures. Reflective surfaces and sources of artificial radiation should be avoided. The height at which the sensor is mounted is not critical.
Page 4
Page 15
(c ) PRECIPITATION
A rain gage should be located over level ground that is covered with short grass or gravel. In open areas, the distance to obstructions should be two to four times the height of the obstruction.
The height of the opening should be as low as possible, but should be high enough to avoid splashing from the ground.
The gage must be mounted above the average level of snow accumulation in areas that experience significant snowfall.
Standard measurement heights:
1.0 meter +/- 1.0 cm (AASC)
30.0 centimeter minimum (WMO, EPA)
(d) DETERMINING TRUE NORTH FOR WIND VANE OREINTATION
Magnetic declination, or other methods to find True North, should be determined prior to installing the weather station. True North is usually found by reading a magnetic compass and applying the correction for magnetic declination. (Other methods employ observations using the North Star or the sun, and are discussed in the Quality Assurance Handbook for Air Pollution Measurement Systems, Volume IV ­Meteorological Measurements.) The magnetic declination is the number of degrees between True North and Magnetic North. Magnetic declination for a specific site can be obtained from a USFA map, local airport, or through a computer service offered by the USFS called GEOMAG (see page 7). A general map showing magnetic declination for the contiguous United States is shown below in FIGURE 2.
Declination angles east of True North are considered negative and are subtracted from 0 degrees to get True North. Declination angles west of True North are considered positive and are added to 0 degrees to get True North. For example, the declination for Logan, Utah is 16 degrees East. True North is 360 degrees minus 16 degrees, or 344 degrees as read on a compass.
REFER TO NEXT PAGE FOR FIGURE 2
Page 5
Page 16
FIGURE 2 - MAGNETIC DECLINATION FOR THE
CONTIGUOUS UNITED STATE
Page 6
Page 17
PROMPTS FROM GEOMAG
GEOMAG is accessed by phone with a PC and telephone modem and a communications program such as Pro Comm or Windows 95 Hyperterminal. GEOMAG prompts the caller for site latitude, longitude and elevation, which it uses to determine the magnetic declination and annual change. The following information, menu and prompts are from GEOMAG.
Username: QED [RETURN}
Main Menu:
Type Q for Quick Epicenter
Determinations (QED) L for Earthquake Lists (EQLIST) M for Geomagnetic Field
values (GEOMAG) X to log out
GEOMAG is a user-friendly program that provides estimates of the geomagnetic field elements, including declination and total field intensity, based upon Magnetic Models. The program is accessible by modem or through the Internet.
Modem Access:
Modem settings: No parity, 8 data bits and 1 stop bit (i.e., N81).
Telephone numbers:
Phone Number Baud Rates
303-273-8672 2400 303-273-8673 1200 303-273-8678 1200
Upon carrier-signal detection, press Return once or twice.
ENTER program option: “M”
Would you like information on how to run GEOMAG (Y/N)? Enter N
OPTIONS:
1 = Field Values (D,I,H,X,Z,F) 2 = Magnetic Pole Positions 3 = Dipole Axis and Magnitude 4 = Magnetic Center [1] : 1
Display values twice [N]: press return Name of field model [USCON90]: press return Date [current date]: press return Latitude :42/2 N Longitude : 111/51/2W Elevation : 4454 ft
If you are using one of the commercial numbers, the following prompts will appear. Type the responses shown (followed by pressing RETURN):
GLDSV1> c neis [RETURN]
Page 7
Page 18
Example of report generated by GEOMAG:
Model: USCON90 Latitude: 42/2 N Date: 7/27/93 Longitude: 111/51/2W
Elevation: 4454.0 ft
Declination is: deg min 15 59.6
Annual change: deg min 0 -6.1
EXITING:
press “Cntrl-Z” to exit GEOMAG
When the main menu reappears either select another option or Type “X” to log out.
If you used one of the commercial numbers, the GLDSV1> prompt will reappear.
Type “LO” to disconnect.
Use of GEOMAG is free (except for telephone charges). If possible, please avoid using GEOMAG between 9 a.m. and 4 p.m., mountain time, Monday through Friday.
The declination in the example above is listed as 15 degrees and 59.6 minutes. Expressed in degrees, this would be
15.99 degrees. As shown in FIGURE 2, the declination for Utah is east, so True North for this site is 360 - 15.99, or 344 degrees. The annual change is -6.1 minutes.
Refer to FIGURE 3 below:
FIGURE 3 - DECLINATION ANGLES
Page 8
Page 19
4.0 WEATHER STATION CONCRETE BASE:
SUPPLIED COMPONENTS
(1) 2” x 4” x 10’-0” piece of
forming lumber
(3) ½” x 12” long “L” Anchor Bolts (9) ½” Nuts (3) Flat Steel Washers
(4) 16p Double Headed nails
10’-0 “ length of form wire
½ yard of concrete
Duct Tape
(1) Stainless Steel Template (1) 1 ½” Dia. Long Sweep
TOOLS REQUIRED
Elbow
Claw Hammer
INSTALLER SUPPLIED
Hand Saw
Saw Horse
Shovel
Pliers & Wire Cutters
INSTALLATION:
For the following procedures - Refer to FIGURE 4 below.
1.0 The Tower for the “PRO”
4.0 Construct the concrete form
Weather Station - attaches to a user supplied poured concrete foundation - constructed as shown in FIGURE 4 below.
2.0 Dig the required foundation hole - with a 24” square top and slanting outward sides, to the bottom of 32” square. The “Sloping” sides of the foundation are very IMPORTANT in providing the necessary support to the weather station tower, in preventing it from
5.0 Place a piece of duct tape “leaning” or falling over, due to wind load on the station.
3.0 Determine the proper location of the long sweep elbow and dig a small cavity to accept the end of the elbow that will protrude beyond the concrete base.
with 2” x 4” lumber and 16p double-headed nails. Center the form over the dug hole. Adjacent to the long legs of the form that extend beyond the hole, drive four stakes into the soil. Level the form. Secure the form to the stakes with 8p nails ­making sure that the form remains “level”.
over one end of the 1 ½” diameter long sweep elbow. Insert the elbow into the hole, with the taped end into the small cavity that you have dug on one side of the hole.
Page 9
Page 20
6.0 Insert the other end of the long
sweep elbow into the center hole in the stainless steel template. Tape the end of the elbow with duct tape.
7.0 Take the three ½” x 12” long “L” anchor bolts and install two (2) hex huts on to each bolt. Insert one in each of the holes in the template and install one of the flat washers and a nut to secure the anchor bolt to the template.
Refer to FIGURE 5.
8.0 Take the form wire and cut it into two (2) equal lengths. Attach one end of one of the wires to one of the 16p nails on the form. String the wire up over the form and to the long sweep elbow - making a turn around it. Continue the wire over to the 16p nail at the other corner of the form (located on the same side of the form as the other nail) and centering the template and elbow attach the wire securely to the nail. Repeat this same process with the other piece of form wire - going to the opposite nails and further securing the template, elbow and anchor bolts in the form.
9.0 Steady the template assembly by putting a 2” spacer between the template and the top of the form. Pour the concrete into the hole and form - it will require approximately ½ yard - screed the concrete level with the top of the form. Check to make sure the template is correctly orientated and centered. The bottom of the anchor bolt threads should be about ½” above the top of the concrete. Check to be sure the template is “level” in two (2) dimensions. Use a trowel and edger to finish the concrete.
BE SURE THAT YOU HAVE THE TEMPLATE PROPERLY ORIENTATED IN RESPECT TO
“NORTH”. Refer to FIGURE 4.
The template should have the two (2) bolt holes, that are parallel with one side of the template, on the north side of the base.
10.0 Wait 24 hours before removing the concrete form. Wait 7 days before mounting the weather station to the base.
REFER TO NEXT PAGE FOR FIGURES 4 & 5
Page 10
Page 21
FIGURE 4 - CONCRETE BASE DETAIL
FIGURE 5 - ANCHOR BOLT/TEMPLATE DETAIL
Page 11
Page 22
5.0 EXTERNAL WIRING TO WEATHER STATION: ( Refer to FIGS. 6 & 7)
WIRING VALVE ACCESS BOX
At the base of the Weather Station and as near to the base as feasibly possible, dig a hole large enough to install a standard 18” x 24” rectangular valve box and cover. The valve box shall accommodate all wiring connections, one rod of a 3-rod grounding grid, MGP-1 grounding plate assemblies and MSP-1 surge arrestors.
WEATHER STATION POWER WIRING
Furnished as part of the Weather Station is a 120VAC to 16VAC power transformer. This transformer can be located in the pedestal of a field satellite controller that is in the near proximity of the weather station or some other convenient weather proof location. Install the transformer in a 4”x 4” metal electrical box with cover. Connect the 120VAC power wires of the transformer to a source of 120VAC power that is not easily turned off. To the output of the transformer, connect a pair of UF wires, of proper size, using “crimp-on” open spade connectors.
The power wires shall be direct buried and run over to the weather station. Connect the 16VAC power wires to the “LINE” side of an MSP-1 surge arrestor, which shall be mounted in an MGP-1 grounding plate assembly. The MGP-1 grounding plate assembly shall be securely mounted on a 5/8” dia. copper
clad, ground rod - one of a 3-rod grounding grid.
NOTE ! The minimum voltage to the transformer shall be not less than 112 volts.
Wire sizing shall be in accordance with the chart given below.
Wire shall be Type “UF” (underground feeder cable) with PVC insulation. The 16VAC power is used to provide constant charging of the battery within the weather station, through the battery charging circuit.
WIRE SIZING CHART
WIRE SIZE DISTANCE (feet)*
18 500
16 800
14 1275
12 2000
10 3250
8 5100
* Transformer to Weather Station
The “EQUIPMENT’ side of this MSP-1 surge arrestor shall be connected to “red” and “black” wires of the 20’power wire cable, which is furnished as part of
Page 12
Page 23
the weather station, and MARKED “P/N 9922”. This cable shall be routed through the 1 ½” dia. long sweep elbow to the base of the weather station. All wire connections and splices in the power wiring shall be made using 3-M DBY direct burial connectors. DO NOT apply power to transformer at this time.
WEATHER STATION COMMUNICATION WIRING
DIRECT CONNECTED - USING SHORT HAUL MODEMS:
(MODEL PRO-SH - Only)
cable furnished with the weather station and marked P/N 9720 “ET SHORT HAUL” “COMM”.
The RED (+RCV) & BLACK (-RCV) pair shall be connected to the RED & BLACK wires respectively, at the “LINE” end of the other MSP-1 surge arrestor. The RED (+RCV) and the BLACK (-RCV) wires from the “EQUIPMENT” end of this MSP-1 surge arrestor shall be connected to the RED (+RCV) and the BLACK (-RCV) wires of the communication cable furnished with the weather station and marked P/N 9720 “ET SHORT HAUL” “COMM”.
Coming from the Central location, furnish and install a Belden #9883, Direct Burial Type, communication cable over to the weather station location. The Belden cable shall consist of three (3) twisted pair of wires (20 Gauge), a bare copper drain wire and an aluminum shield. The three (3) twisted pair shall be color coded as follows; 1 pair “black” and “white”, 1 pair “black” and “green” and 1 pair “black” and “red”.
The BLACK (-XMT) & GREEN (+XMT) pair shall be connected to the BLACK & RED wires respectively, at the “LINE” end of one of the MSP-1 surge arrestors. The BLACK (-XMT) and the RED (+XMT) wires from the “EQUIPMENT” end of this MSP-1 surge arrestor shall be connected to the WHITE (-XMT) and the GREEN (+XMT) wires of the communication
This communication cable shall be routed through the 1 ½” diameter long sweep elbow to the base of the weather station. All wire connections and splices in the communication wiring shall be made using 3-M DBY direct burial connectors. DO NOT attempt to use any other type connectors as communication signal may be impaired and poor communication resulting.
GROUNDING
COMMUNICATION CABLE
The bare copper drain wire of the Belden cable shall be grounded to the grounding rod, using a brass ground wire clamp. IMPORTANT ! DO NOT ground the drain wire at the Central end of the cable
- just leave the drain wire un-used.
Page 13
Page 24
FIGURE 6 - EXTERNAL WIRING DETAIL AT THE
PRO - SH WEATHER STATION
Page 14
Page 25
WEATHER STATION
COMMUNICATION WIRING
TELEPHONE CONNECTED - USING TELEPHONE COMPANY LINES:
(MODEL PRO-PH - Only)
The Telephone Company needs to run a
of the telephone patch cable (P/N 9661). direct burial telephone cable to the weather station and terminate it near the base of the weather station. This needs to be a modem quality type telephone line with a separate call number.
Splices shall be made using 3-M DBY
Direct Burial connectors. The splices
for the phone line shall be made in the
valve box, where the power wiring
splices are made and where the MGP-1 The “TIP” line of the telephone cable shall be connected to the WHITE (“TIP”) wire of a 20’telephone patch cable, furnished as part of the weather
grounding plate assembly with an MSP-
1 surge arrestor mounted in it, is
attached to one rod of a 3-rod grounding
grid. Refer to FIGURE 7 below. station, marked P/N 9661 - 2 conductor cable with WHITE (“TIP”) and BLACK (“RING”) pair of wires. The “RING” line of the telephone cable shall be connected to the BLACK (“RING”) wire
This telephone patch cable (P/N 9661)
shall be routed through the 1 ½”
diameter long sweep elbow to the base
of the weather station.
6.0 TOWER ASSEMBLY AND INSTALLATION:
INSTALLATION
SUPPLIED COMPONENTS
(1) Upper Tower Section
(Tapered)
(2) Lower Tower Section w/Base
(6) ½” Washers
(1) 12 foot 10 AWG Ground
Cable
(1) Tower Plastic Cap
Take the 12 foot 10 AWG Ground
Cable, furnished as part of the weather
station and cut a 9” piece from on end of
it. (This 9” piece will be used later).
Attach one end of the ground wire to the
ground rod, of the 3-rod grounding grid,
that is located in the valve box using a
brass clamp. Refer to FIGURE 6 or 7.
Feed this ground wire through the 1 ½”
long sweep elbow up to the base of the
weather station.
Page 15
Page 26
Remove the three (3) “top” nuts and flat washers from the anchor bolts at the weather station template. Next remove the metal template - slipping it up over the cables that are extending from the 1 ½’ long sweep elbow. Be careful NOT to damage the cables or the connectors on the cables.
Take the lower section (with the base attached) of the weather station tower and feed, from the base end, the power cable (P/N 9922) up through this section. Also feed, from the base end, the short haul communication cable (P/N 9720 ­for the Model JR-SH weather station) or the telephone communication patch cable (P/N 9661 - for the Model JR-PH weather station, up through this section of the tower. Finally feed the ground wire up through the lower section of the tower.
Lay this Lower Section of the tower, on the ground, next to the concrete base, with the cables extending out the top of the tower section.
Take the Upper Section of the tower (the tapered section) and position it above the lower section on the ground. Feed the cables, coming from the lower section, up through the upper section of the tower. Secure the cables at the top of the upper section with tape, so that they cannot pull back down into the tower as you assemble the two tower sections.
Now assemble the upper tower section
to lower tower section, being careful
NOT to damage the cables as you do so.
IMPORTANT ! Be sure that you have
everything in proper order BEFORE
you assemble the two tower sections
together -because once assembled they
cannot be taken apart.
Place one of the flat washers on top of
the two (2) nuts on each of the anchor
bolts. Raise the tower and position the
base on the three (3) anchor bolts that
have been embedded in the poured
concrete base. Be careful NOT to
damage the cables in doing so. Next
install a flat washer and a nut on each of
the bolts and hand tighten the nuts just
enough to hold the tower in position.
Next check the level of the tower by
placing a level on the north and east
sides of the lower tower base. Adjust
the topmost nut of the two (2) lower nuts
(leveling nuts) on each bolt, as
necessary to level the base. When level
is established, lock the leveling nut in
place by tightening the lowest nut
against it. Tighten the three top nuts
with a wrench to secure the tower to the
base. The tower should now be ready
for the final assembly of the Enclosure,
Sensors and Lightning Rod, etc.
REFER TO NEXT PAGE FOR FIGURE 7
Page 16
Page 27
FIGURE 7 - EXTERNAL WIRING DETAIL AT THE
PRO - PH WEATHER STATION
Page 17
Page 28
7.0 INSTRUMENTATION ENCLOSURE INSTALLATION:
GENERAL:
The Model PRO weather station datalogger, power supply, sensor connection panel, communications devices and data retrieval peripherals are mounted in the ET Enclosure with the sensors themselves mounted on a cross­arm, which mounts to the top of the Enclosure.
MOUNTING
ET ENCLOSURE TO THE
TOWER
Mount the Enclosure to the top of the weather station tower, by sliding the
enclosure brackets down the tower,
from the top of the tower.
Position the Enclosure so that the top of
the enclosure is even with the top of the
tower and on the north side of the tower
(for northern hemisphere). Tighten the
bolts, on the clamps, to secure the
enclosure to the tower. DO NOT over-
tighten the bolts since doing so may
damage the tower or the enclosure.
Refer to FIGURE 8 below
FIGURE 8 - MOUNTING ENCLOSURE ON TOWER
Page 18
Page 29
INSTALLATION OF
LIGHTNING ROD
Refer to FIGURE 8 above:
Carefully mount the lightning rod bracket, furnished with the weather station, to the top of the weather station tower. Locate it above the Enclosure top bracket and near the top of the tower. Clearance between the clamp and the Enclosure is minimal. Care should be taken not to scratch the enclosure or sensor assembly. Insert the lightning rod into the bracket, with approximately ½” to 1” of the rod extending below the bracket, and tighten the set screw to secure the rod in the bracket.
Take the ground wire, that has been fed up the weather station tower, strip the insulation from the end and curl the end so as to be able to connect the wire under the head of one of the bolts on the lightning rod bracket. Be sure that you wrap this wire completely around the bolt and that you get a good contact with the bolt and bracket. Tighten the bolt securely so that you have a good tight connection. This connection is EXTREMELY important to give maximum protection to the weather station against damage from lightning surges. This connection should be INSPECTED on a regular basis to
assure it remains tight and making good
contact.
Take the 9” piece of ground wire, that
you previously cut off the ground wire,
and strip the insulation from each end of
it. Insert one end of this wire into the
brass grounding lug, located at the top
of the Enclosure on the back panel.
Tighten the set screw to secure the wire
in the clamp. Curl the other end so as to
be able to place it around the other bolt
of the lightning rod bracket. Be sure that
you wrap this wire completely around
the bolt and that you get a good contact
with the bolt and bracket. Tighten the
bolt securely so that you have a good
tight connection. This connection is
EXTREMELY important to give
maximum protection to the weather
station against damage from lightning
surges. This connection should be
INSPECTED on a regular basis to
assure it remains tight and making good
contact.
POWER SUPPLY
RECHARGEABLE BATTERY
The weather station is furnished as
standard with a Sealed Rechargeable
Battery and including the mounting
bracket. This battery is to be installed
on the back panel of the Enclosure.
Refer to FIGURE 9 below.
Page 19
Page 30
FIGURE 9 - 16VAC CONNECTION AND RECHARAGEABLE BATTERY
INSTALLATION
with the screws. Tighten all four screws Loosen the four (4) screws located on the back panel of the Enclosure. Slip the end of the battery bracket, that has the two (2) keyhole slots in it over the
to properly secure the battery to the back
panel of the ET Enclosure. upper two (2) screws. Line up the battery bracket slotted holes, in the other end of the bracket, with the two (2) lower screws. Now push “down” on the battery - seating the bracket in place
Plug the connector on the wire leads of
the battery to the “top” battery
connection - marked “LA” - which is
located on the Enclosure panel
assembly just above the battery location.
Page 20
Page 31
AC EXTERNAL
POWER WIRING
the cap on the Heyco fitting to seal
around the cable. The wires can be
Refer to FIGURE 8 & 9 above:
attached to these connectors by
“depressing” the lever on the connector
for each wire and while doing so, insert The 16VAC power wiring, that you have fed up through the weather station tower, shall be routed down the back side of the Enclosure and into the Enclosure through the Heyco fitting, marked “power”. Unscrew the cap of the Heyco fitting (on the back side of the enclosure) and push the plug out of the fitting. This plug can be discarded as it will not be used. Feed the power wires through the Heyco fitting and connect them to the the connectors of the
the stripped end of the wire. Upon
release of the lever, the wire will be
secured in the connector. CAUTION !
Be careful in depressing the lever so as
not to break the lever. The polarity of
the 16VAC power wiring does not
matter, therefore it makes no difference
which wire goes into which connector.
At this point you can now connect the
power to the transformer or wait until
you have connected the sensors, which
ever you prefer. Enclosure, marked “CHG”. Tighten
It will be noted that on the panel assembly there are connectors marked “ALK”. These connectors are NOT to be USED. The use of an Alkaline battery is NOT an option.
CONTINUE ON THE NEXT PAGE
POWER SUPPLY
Page 21
Page 32
OPTION
SOLAR PANEL
Refer to FIGURE 10 below:
Model Numbers shall be as; PRO-SH-SP or PRO-PH-SP. (SP designating the Solar Panel Option).
An option is for use of a Solar Panel, for the power supply, rather than the standard 120VAC/16VAC transformer. Mount the solar panel to the weather station tower using the mounting brackets furnished as part of the solar panel assembly. Mount the solar panel to the tower so it faces south (northern hemisphere). Position the solar panel as high off the ground as practical, ensuring it cannot interfere with air flow or sunlight around the sensors.
The solar panel should be oriented to receive maximum sun light exposure over the course of the year. It is also necessary that the solar panel have the proper “tilt”. Suggested “tilt” angles (reference to the horizontal plane) are listed below.
Site Latitude Tilt Angle
0 to 10 degrees 10 degrees
11 to 20 deg. Latitude +5
degrees
21 to 45 deg. Latitude +10
degrees
46 to 65 deg. Latitude +15
degrees
65 deg. 80 degrees
After determining the “tilt” angle,
loosen the two (2) bolts that attach the
solar panel to the mounting bracket.
Adjust the angle of the solar panel, then
tighten the bolts to secure it in the proper
position. Secure the lead wire, coming
from the solar panel, to the Tower mast
using wire ties.
The solar panel cable shall be routed up
and through the Heyco fitting on the
back panel of the Enclosure and marked
“power”. Unscrew the cap of the Heyco
fitting (on the back side of the enclosure)
and push the plug out of the fitting.
This plug can be discarded as it will not
be used. Now feed the solar panel
power cable through the Heyco fitting
and connect it to the connectors of the
Enclosure, marked “CHG”. The wires
can be attached to these connectors by
“depressing” the lever on the connector
for each wire and while doing so, insert
the stripped end of the wire. Upon
release of the lever,, the wire will be
secured in the connector. CAUTION !
Be careful in depressing the lever so as
not to break the lever. The polarity of
the wires does not matter, therefore it
makes no difference which wire goes
into which connector. The solar panel
installation should now be completed.
Page 22
Page 33
FIGURE 10 - SOLAR PANEL INSTALLATION DETAIL
Page 23
Page 34
8.0 INSTALLATION OF INSTRUMENTATION
GENERAL:
The Model PRO weather station comes with the some of the sensing instruments, and sensor wiring to datalogger completely assembled as a unit on a cross-arm. The Solar Radiation Pyranometer - along with the leveling device are mounted on a bracket, which in turn is mounted on the cross-arm of the Enclosure. On this end of the cross-arm the “Tipping Rain Bucket” is also mounted at the factory. On the opposite end of the cross-arm is attached the mounting bracket, which has been factory installed, for the Wind speed and Wind direction sensing instruments. The Temperature and Relative Humidity sensors are on the end of their cable and only need installing into the radiation shield. The cables for each of these sensors are mounted in the cross-arm and terminated at the proper location of each sensor. The cables only need to be routed and plugged into the proper connectors on the back of the back panel of the ET Enclosure.
SUPPLIED COMPONENTS
(1) Sensor Cross-Arm (1) Met One 034A Wind Sensor (1) 034A Mounting Shaft (1) Radiation Shield
INSTALLATION OF CROSS-ARM
TO ET ENCLOSURE:
Refer to FIGURE 11 below:
Remove the four (4) Phillips head
screws from the bottom center of the
cross-arm. With the Enclosure cover
removed, place the cross-arm on top of
the Enclosure. The cross-arm needs to
be oriented along a due east to due west
axis. If necessary adjust the Enclosure
on the tower to properly orient the cross-
arm. Also be sure that the opening in
the middle and one side of the cross-
arm, where the sensor cables exit, is to
the back of the Enclosure so that the
cables can enter the top of the cover that
fits over the cable connectors on the
back of the Enclosure. Line up the four
threaded holes on the under side of the
cross-arm (where you just removed the
screws) with the four holes in the top of
the Enclosure. Attach the cross-arm to
the Enclosure by inserting the four (4)
screws, from in side the enclosure up
through the top and into the threaded
holes of the cross-arm. Tighten the
screws securely.
REFER TO NEXT PAGE FOR FIGURE 11
Page 24
Page 35
FIGURE 11 - CROSS-ARM MOUNTING
INSTALLATION OF 034A WIND SENSOR:
Page 25
Page 36
Refer to FIGURE 12 below:
With the Sensor Cross-Arm securely installed to the Enclosure you are ready to install the 034A Wind Sensor instrument. The wind vane is oriented after the datalogger has been programmed and the location of True North has been determined. Orientation is most easily done with two people, one to aim and adjust the sensor, while the other observes the wind direction displayed by CR10KD Keyboard Display or a laptop PC computer.
Remove the aligning screw from the base of the 034A wind sensor unit. Place the 034A wind sensor into the mounting shaft, that is clamped to the end of the sensor cross-arm by means of a U-Bolt clamp.
(The short, black mounting shaft, included with the 034A wind sensor will NOT be used).
Secure the 034A wind sensor in the mounting shaft, by aligning the threaded hole in the wind sensor with the hole in the side of the mounting shaft, and re­installing the aligning screw.
Next loosen the set screw in the top of
the 034A wind sensor (the set screw
opposite the one securing the wind
direction point). Place the end of the
wind vane into the hole. Properly orient
the vane to be in a true vertical position
and secure it by tightening the set screw.
Attach the wind sensor cable connector
to the connector on the 034A wind
sensor.
Without allowing the mounting shaft for
the 034A wind sensor to “slip down” (it
may be a good idea to mark the position
of the U-Bolt on the shaft so that you
can correctly position it should is “slip”)
slightly loosen the nuts of the “U-Bolt”
clamp of the mounting shaft - just
enough so you can rotate the mounting
shaft but not allow the shaft to “slip
down”.
Establish a reference point on the
horizon for True North.
Sighting down the instrument center
line, aim the counter weight at True
North. Display input location #8 for
wind direction, using the *6 Mode of
the datalogger.
REFER TO NEXT PAGE FOR FIGURE 12
While holding the wind vane position,
slowly rotate the sensor base/mounting
shaft until the datalogger indicates 0
degrees. Securely tighten the clamp
nuts.
Page 26
Page 37
FIGURE 12 - WIND SENSOR INSTALLATION DETAIL
HUMIDITY / TEMPERATURE
SENSOR AND RADIATION
SHIELD:
INSTALLATION OF RELATIVE
Refer to FIGURE 13 below:
Page 27
Page 38
On the bottom of the Cross-Arm, on the end where the wind sensor has been installed, remove the two screws for the Relative Humidity/Temperature sensor Radiation Shield.
Un-tape the RH/Temperature sensor from the bottom of the Cross-Arm.
Remove the “yellow” protective plastic cap from the end of the sensor, by
slipping it off the end of the sensor.
This can be discarded as it will not be
used.
Insert the RH/Temperature sensor into
the end of the shaft of the Radiation
Shield. Insert it to a depth where it is
securely seated. Now secure the
Radiation Shield to the bottom of the
sensor Cross-Arm with the two (2)
screws you have previously removed.
FIGURE 13 - TEMPERATURE/RH SENSOR INSTALLATION DETAIL
INSTALLATION OF SOLAR RADIATION PYRANOMETER:
Refer to FIGURE 14 below:
Page 28
Page 39
The Solar Radiation Pyranometer, (with the leveling device) is mounted, at the factory, on a mounting bracket at the opposite end of the cross-arm near the Tipping Rain Bucket gage. By using the three (3) leveling screws - level the
Pyranometer. After leveling - remove
the “RED” protective cap from the
Pyranometer.
FIGURE 14 - SOLAR RADIATION SENSOR INSTALLATION DETAIL
Refer to FIGURES 12 & 15:
SENSOR CABLE CONNECTIONS:
The Sensor Cables exit from the center
back of the Cross-Arm. The cables
need to be routed down the back of the
Page 29
Page 40
Enclosure and plugged into the connectors on the back panel of the Enclosure as follows:
Temp/RH #10090 cable - connect to #1 connector [labeled “TEMP/RH”]
Solar Radiation #10105 cable -
connect to #3 connector [labeled “SOLAR RADIATION”]
Rain #10094 cable - connect to #5
connector [labeled “RAIN (PRECIP)”]
WD/WS (Wind Direction/Wind Speed) #10408 cable - connect to #2 connector [labeled “WS/WD”]
Making sure that all cables are properly
enclosed behind the cover - replace the
cable cover. Be sure that you do not
pinch any of the cables between the
cover and the back panel of the
Enclosure.
FIGURE 15 - SENSOR CABLE CONNECTIONS
Page 30
Page 41
CONFIGURE SENSOR SWITCH SETTINGS:
Refer to FIGURE 16 below:
The Sensor Switches are located on the ET Enclosure panel just below the
modem and to the right of the the “Heat
Sink” located to the right of the battery
connectors. These switches or pots
need to be set as indicated in FIGURE
16 below.
FIGURE 16 - SENSOR SWITCH SETTINGS
SHORT HAUL MODEM
INSTALLATION
Refer to FIGURE 18 below: (PRO-SH)
The Short Haul Modem, at the weather station, is normally installed at the factory in the ET Enclosure. The Short Haul Modems enable communication between the datalogger and the central computer over two (2) twisted pairs of wires. The maximum distance between modems is determined by the baud rate and the wire gauge. At 9600 baud, the approximate range is 4.0 miles. DCE/ DTE switches on the modems must be set to DCE.
INSTALLATION:
For installation of the Short Haul RAD
Modem inside the Enclosure, the
following components are provided in
the Short Haul modem kit:
SC932C Interface w/ribbon cable RAD Modem RAD/SC932C Mounting Bracket Velcro Mounting Strap w/Buckle Mounting Screws 12 inch 4-wire Patch Cable
Partially install three (3) of the furnished
screws in the holes on the left side of the
Enclosure housing for the datalogger.
Hold the Modem mounting bracket in
the position it will be in the Enclosure.
Page 31
Page 42
Thread the Velcro mounting strap through the two outer slots of the lower set of slots in the modem mounting bracket. Thread from the top down on the far left slot first. The side of the strap with Velcro should be facing “down” toward the datalogger housing. Then carry the strap across the back of the bracket and thread it to the front of the bracket through the far right slot of the lower set of slots.
Slide the bracket flange, with the three screw slots, under the heads of the three (3) mounting screws you have partially installed in the holes on the left side of the datalogger housing. With the bracket fully seated tighten the three (3) screws to secure the mounting bracket to the datalogger housing.
Connect the SC932C Interface to the RAD Modem. Position this assembly
on the mounting bracket with the
SC932C Interface pointing “down”.
Strap the SC932C Interface unit securely
to the mounting bracket, using the
Velcro strap.
Connect the SC932C 9-pin port to the
internal Enclosure 9-pin port (located
just below the Phone Modem port) using
the blue ribbon cable provided.
Wire the RAD modem to the Enclosure
with the 12 inch 4-wire patch cord
provided. Black (-XMT) wire to -XMT
connections at the RAD modem and at
the connector on the Enclosure. The
RED (+XMT) wire to the +XMT
connections, the White (-RCV) wire to
the -RCV connections and the Green
(+RCV) wire to the +RCV connections
at the RAD modem and at the terminal
blocks: RED to +RCV, Black to -RCV,
Green to +XMT, White to -XMT.
Page 32
Page 43
FIGURE 18 - SH MODEM INSTALLATION IN ET ENCLOSURE
TELEPHONE MODEM INSTALLATION
Refer to FIGURE 19 below: (PRO-PH)
The Telephone Modem, at the weather
station, is normally installed at the
factory in the Enclosure. The
telephone modems enable
communication between the datalogger
and a Hayes compatible modem at the
Page 33
Page 44
central computer over a dedicated telephone line. Phone line surge protection is built into the Enclosure.
INSTALLATION
For installation of the phone modem inside the Enclosure, the following components are provided in the modem kit:
COM200 or COM 300 Modem 12 inch RJ-11 Patch Cord Modem Mounting Bracket Mounting Screws 12 inch #14 AWG Ground Wire 4 Screws and Nuts
Partially install three (3) of the furnished screws in the holes on the left side of the Enclosure housing for the datalogger.
in the bracket over the top two (2)
screws that you have previously installed
in the datalogger housing. Be sure the
open slot in the bracket is in line with
the lower screw. Seat the modem
properly and tighten the screws to secure
the modem to the datalogger. Connect
the 9-pin connector of the Blue Ribbon
Cable to the phone modem 9-pin port.
Connect the other end of the ribbon
cable to the 9-pin port (marked “CS
I/O”) on the Enclosure. Secure it with
the two screws on the connector.
Connect the modem RJ-11 Patch Cord to
the RJ-11 jack on the phone modem
(located to the right of the 9-pin port).
Connect the other end of the RJ-11 Patch
Cord to the RJ-11 jack on the
Enclosure, marked “phone modem”.
Attach the phone modem to the mounting bracket, using the four screws and nuts.
Taking the phone modem and bracket assembly - install the two keyhole slots
REFER TO NEXT PAGE FOR FIGURE 19
Connect one end of the 12 inch #14
AWG ground wire to the terminal,
marked “GND” and located on the right
side of the phone modem. Connect the
other end of this ground wire to the
connector on the Enclosure that is
marked “GND”.
The installation of the phone modem is
now completed.
Page 34
Page 45
FIGURE 19 - TELEPHONE MODEM INSTALLATION IN ET ENCLOSURE
latch for extra security.
9.0 SEALING & DESICCATING
THE ENCLOSURE:
The Enclosure is supplied with a desiccant pack. The desiccant maintains a low humidity in the enclosure to minimize the chance of condensation on the instrumentation Desiccant should be changed when the internal Enclosure humidity sensor measures 30% or higher. Install the desiccant as shown in FIGURE 21 below. Keep unused desiccant tightly sealed inan airtight container.
Take the desiccant pack out of its sealed plastic bag. Place it under the dessicant strap just before leaving the station.
Be sure to close the enclosure hasp securely. A padlock may be used on the
FIGURE 20 - DESSICANT PACK
INSTALLATION
Page 35
Page 46
10.0 INSTALLATION AT CENTRAL COMPUTER
WHITE (XMT-) wire to the upper right
MODEL PRO - SH ~ Direct Connected:
connector, connect the RED (RCV+)
wire to the lower right connector and the
BLACK (RCV-) wire to the lower left
Refer to FIGURE 22 below:
connector of the surge arrestor box.
SUPPLIED COMPONENTS
(1) SMR-5A RAD Modem (1) 5 Foot 4-Wire Patch Cord (1) 25 Foot #10 AWG Ground Wire (1) Surge Protection Box
INSTALLATION
Attach the 5 foot 4-wire patch cord to the SRM-5A RAD modem unit, which is furnished as part of the weather station. Connect the GREEN (XMT+) wire to the “XMT+” terminal of the RAD modem. Connect the WHITE (XMT-) wire to the “XMT-“ terminal, the RED (RCV+) wire to the “RCV+” terminal and the BLACK (RCV-) wire to the “RCV-“ terminal.
Connect the SRM-5A RAD modem directly to the serial port of the computer or use a 9-pin to 25-pin adapter if required.
Mount the Surge Arrestor Box, which is furnished as part of the weather station, in a suitable location near the computer (within less than 5 feet, as the patch cord is only 5 feet long).
Take the other end of the Patch Cord, that you have previously connected to the modem, and connect the GREEN (XMT+) wire to the upper left connector in the Surge Arrestor Box. Connect the
Just outside the building of the central
computer location, install an 18” x 24”
rectangular valve box with cover over
one ground rod of a 3-rod grounding
grid. (You may use the 3-rod grounding
grid for the central Interface unit, etc. if
located nearby).
Furnish and install and MGP-1
grounding plate assembly on the ground
rod in the valve box. Furnish and install
in the MGP-1 grounding plate assembly
two (2) MSP-1 Pipe Surge Arrestors.
Be sure to have the end marked
“EQUIP” toward the central equipment
and the “LINE” end toward the weather
station. Ground both ends of each of
the MSP-1 Surge Arrestors to a screw on
the
MGP-1 grounding plate assembly.
Using a piece of Belden #9883 direct
burial cable (of sufficient length to reach
from the Surge Arrestor Box to the
Valve box) take the Green and Black
twisted pair of wires and connect the
GREEN (XMT+) wire to the upper left
terminal in the Surge Arrestor Box.
Connect the BLACK (XMT-) wire to the
upper right terminal in the Surge
Arrestor Box. Take the Red and Black
twisted pair of wires and connect the
RED (RCV+) wire to the lower right
terminal of the Surge Arrestor Box.
Connect the BLACK (RCV-) wire to the
lower left terminal of the Surge Arrestor
Box. Leave the third pair of twisted
wires, consisting of a Black and White
wire disconnected and for a spare pair.
Page 36
Page 47
The copper drain wire shall also be left disconnected.
Route the Belden cable, out of the building, under ground and out to the valve box. Taking the Green and Black twisted pair of wires, connect the GREEN (XMT+) wire to the RED wire, on the end marked “EQUIP”, to one of the MSP-1 Pipe Surge Arrestor that you have installed in the MGP-1 Grounding Plate Assembly. The BLACK (XMT-) wire shall be connected to the BLACK wire, on the end marked “EQUIP”, of this MSP-1 Surge Arrestor.
Next take the Red and Black twisted pair of wires of the Belden cable and connect the RED (RCV+) wire to the RED wire, on the end marked “EQUIP”, of the second MSP-1 pipe surge arrestor. Connect the BLACK (RCV-) wire to the BLACK wire, on the end marked “EQUIP”, of this second MSP-1 pipe surge arrestor.
The third twisted pair, consisting of a Black and White wire pair, shall be left as a spare and un-connected. The copper drain wire shall also be left disconnected.
A Belden #9883 Cable, consisting of three twisted pair of wires, a copper drain wire and an aluminum shield with an outer insulation for direct burial, shall be run underground form the central
location valve box out to the weather station location. At the valve box, at
the central location, take the Green and
Black pair of wires and connect the
GREEN (XMT+) wire to the RED wire,
coming from the end marked “LINE”,
of the first MSP-1 pipe surge arrestor.
Connect the BLACK (XMT-) wire from
this pair, to the BLACK wire, coming
from the end marked “LINE”, of the
first MSP-1 pipe surge arrestor.
Take the Red and Black twisted pair of
wires, of the Belden cable and connect
the RED (RCV+) wire from this pair, to
the RED wire coming from the end
marked “LINE”, of the second MSP-1
pipe surge arrestor. Connect the
BLACK (RCV-) wire from this pair, to
the BLACK wire coming from the end
marked “LINE”, of the second MSP-1
pipe surge arrestor.
The third twisted pair, consisting of a
Black and White wire pair, shall be left
as a spare and un-connected. The
copper drain wire shall also be left
disconnected.
To the center ground terminal in the
Surge Arrestor Box - connect one end of
the #10 gauge bare copper ground wire.
Route this wire out the bottom of the
box, underground out to the valve box
and connect it to the ground rod using a
brass clamp. Keep this ground wire as
short and as straight as possible with NO
sharp bends or “kinks”.
For connections and wiring at the
Weather Station, refer to Section 5.0 of
this manual.
REFER TO NEXT PAGE FOR FIGURE 21
Page 37
Page 48
FIGURE 21 - INSTALLATION AT CENTRAL COMPUTER FOR
DIRECT CONNECTED WEATHER STATION
Page 38
Page 49
MODEL PRO - PH Phone Connected:
Refer to FIGURE 22 below:
SUPPLIED COMPONENTS
(1) Telephone Patch Cable (2) 25 Foot #10 Gauge Ground Wire
(1) Surge Arrestor Box
INSTALLATION
Furnish and install a Hayes Compatible ­9600 baud modem. Using the ribbon cable that comes with the modem connect one end to the RS232C cable connector on the Modem. Connect the other end of this ribbon cable to the serial port of the computer. Use a 9-pin to 25-pin adapter if required.
Plug the “Plug-In” type transformer, that has been supplied with the modem, in to an 120 VAC electrical outlet.
Surge protection, for protection against surges coming in on the telephone lines, is built into the Weather Station. In addition the telephone company also furnishes surge protection on their lines. Therefore no additional surge protection is required upon installation of the Weather Station.
STANDARD INSTALLATION
METHOD
Taking the telephone patch cable,
connect the WHITE (“TIP”) wire, of
this cable, to the “Tip” line of a piece of
underground telephone cable. Connect
the BLACK (“Ring”) wire, of this patch
cable, to the “Ring” line of this piece of
underground telephone cable.
Route this piece of direct burial
telephone cable, out of the building,
under ground and out to the valve box,
located just outside the building. In the
valve box connect the “TIP” wire
(white) to the WHITE “TIP” wire of the
direct burial underground telephone
cable installed by the telephone
company. Connect the “RING” wire
(black) to the BLACK “RING” wire of
the direct burial underground telephone
cable installed by the telephone
company.
REFER TO NEXT PAGE FOR
FIGURE 22
Page 39
Page 50
FIGURE 22 - INSTALLATION AT CENTRAL COMPUTER FOR
TELEPHONE CONNECTED WEATHER STATION
Page 40
Page 51
11.0 MAINTENANCE & TROUBLESHOOTING
GENERAL MAINTENANCE:
Be aware of battery voltage that Proper maintenance of weather station components is essential to obtain accurate data. Equipment must be in
consistently decreases over time, which
indicates a failure in the charging
circuitry. good operating condition, which requires a program of regular inspection
DESICCANT:
and maintenance. Routine and simple maintenance can be accomplished by the person in charge of the weather station. More difficult maintenance such as sensor calibration, sensor performance testing (i.e., bearing torque), and sensor
Enclosure humidity is monitored in the
Enclosure. Change the desiccant packs
when the enclosure RH exceeds 35%.
The RH chip should be changed every 5
to 8 years. component replacement, generally requires a skilled technician, or that the
SENSOR MAINTENANCE:
instrument be sent to Campbell Scientific for repair or updating. Contact your local Rain Bird distributor for instructions.
Sen0sor maintenance should be
performed at regular intervals,
depending on the desired accuracy and
the conditions of use. A suggested A station log should be maintained for
maintenance schedule is outlined below. each weather station that includes serial numbers, dates that the site was visited
1 Week -
and maintenance that was performed.
Visually inspect the station and all
INSTRUMENTATION MAINTENANCE:
sensors. Look for any damage and debris that may disturb sensor
readings. The instrumentation requires a minimum of routine maintenance. A few preventative maintenance steps will optimize battery life and decrease the
Check the pyranometer for level and contamination. Gently clean with a soft bristle brush, if needed.
chances of datalogger failure.
Check and Clean the Tipping Bucket
BATTERIES:
Rain Gage, especially the bucket screen and the small funnel outlet.
RECHARGEABLE
To check accuracy of the rain gage -
Rechargeable power supplies should be connected to an AC transformer or unregulated solar panel at all times.
16 ounces of fluid is equal to 1” of rainfall. Fluid must be poured into the gage VERY SLOWLY to get an accurate bucket tipping count.
Page 41
Page 52
1 Month -
Check the temperature/relative humidity sensor for contamination.
An occasional cleaning of the glass on the solar panel will improve its efficiency.
6 Months -
Clean the temperature/relative humidity sensor.
Check battery by disconnecting the AC Power and allow it to stabilize for at least 2 hours. Then check the voltage. Reconnect battery to AC Power.
1 Year -
Replace the RH chip if necessary.
2 Years -
Calibrate the Pyranometer (some suggest yearly).
Check sensor leads and cables for cracking, deterioration, proper routing and strain relief.
Check the tower for structural damage, proper alignment and for level/plumb.
Replace RH chip in Air Temp/RH Sensor.
Calibrate the Tipping Bucket Rain Gage. To check accuracy of the rain gage - 16 ounces of fluid is equal to 1” of rainfall. Fluid must be poured into the gage VERY SLOWLY to get an accurate bucket tipping count.
4 - 5 Years -
Replace sensor cables as requires.
General Maintenance
Page 42
Page 53
SENSOR MAINTENANCE
RAIN GAUGE
Inspect and clean every two to three months - removing leaves, debris, etc. In extreme environmental conditions it may be necessary to do this on a MONTHLY basis.
Check that the tipping mechanism moves freely and that it registers
0.01 inches per tip.
the large center drain hole. Adjust both screws the same number of turns or partial turns. Rotation clockwise increases the number of tips per 16 ounces of water, counter clockwise rotation decreases the number of tips per 16 ounces of water. One half turn of both screws causes a 2% to 3% change.
Check and Re-Level the Rain Bucket lid.
Factory Calibration is available through your Rain Bird Distributor.
Check and Re-Level the Rain Bucket, if necessary.
Calibrate the Rain Gage every 2 years.
Calibrating the Rain Bucket:
Secure a metal can that will hold at least one quart of water.
Punch a VERY SMALL HOLE in the bottom of the can.
Place the can in the top of the funnel, of the Rain Bucket, and pour 16 fluid ounces (1 pint) of water into the can.
If it takes LESS than 45 minutes for this water to run out, the hole in the can is TOO LARGE.
One hundred (100) tips plus or minus three tips should occur and register from 0.97 inches to 1.03 inches. (0.01 inches per each tip).
Adjusting screws are located on the bottom of the Rain Bucket, adjacent to
Suggestions:
Devices for dripping water are available through a chemistry equipment supply house.
In order to see the 100 tips, configure a FAKE weather station within the weather software, to use for this testing. Drip the water and then do an upload using the new test configuration to see the number of tips (0.01 inches = 1 tip).
CAUTION ! Be sure to disable any Automatic Uploads, since the 100 tips
will contaminate the every day weather data.
After the calibration is complete, reset the datalogger by removing the power and the battery connections in the Enclosure. Contact Campbell Scientific for further instructions. You will have to reset the time of day and year in the datalogger by up loading one day of data (#6 from the Weather Main Menu). The 7 days of data that are stored in the datalogger will be lost when you disconnect the power, so be sure to have done an upload before you begin the calibration process.
Page 43
Page 54
SOLAR SENSOR
Inspect and clean the Solar Sensor (Pyranometer) every two (2) to three (3)months. It is best cleaned with a blast of clean, dry air or with a soft bristle, camel hair brush. Be careful
NOT to scratch the surface of the sensor. DO NOT use Windex, soap or any other cleaning agent as it may scratch or more likely leave a film on the surface, which will affect its accuracy.
The bearings can only be replaced by the factory and therefore need to be returned to the factory through your local Rain Bird Distributor.
Checking the bearings of the 034A Wind Sensor.
Remove the Wind Sensor from the Weather Station cross-arm, by removing the set screw that is securing the sensor in the mounting shaft and raising the sensor up and out of the mounting shaft.
In EXTREME environmental conditions it may be necessary to clean the Solar Radiation Sensor (Pyranometer) on a monthly basis.
Be sure the DRAIN hole in the side of the sensor housing near the top, is OPEN and free of debris.
Re-Calibration of the Solar Radiation Sensor (Pyranometer) should be done every two (2) years. Return the sensor, through your Rain Bird Distributor, for calibration.
WIND SENSOR
Inspect bearings and operation of the Wind Sensor (wind speed and wind direction) on a regular basis, at least once a year. They should move freely and react to a wind speed of 2 to 3 mph.
Hold the Wind Sensor in a horizontal position (with one of the wind speed cups “down” toward the ground).
On one of the cups hang an ordinary paper clip (0.5 gm weight) on the outer edge of one of the cups.
Position this cup in the “up” position and release. The cup should rotate downward. Failure to rotate indicates the bearings need replacement.
RELATIVE HUMIDITY SENSOR
The life of the RH chip is dependent upon air quality in your area. As a General Rule the RH chip should be replaced EVERY 2 YEARS, if necessary.
In extreme environmental conditions, the RH chip may need to be replaced every year.
The bearings have a life expectancy of 3 to 5 years, except in very high wind areas, where their life may only be 1 year.
The best time to change the chip is at the beginning of the most critical
Page 44
Page 55
time for watering (spring and fall in the desert areas).
Clean the screen, on the tip of the RH chip enclosure, every six (6) months more often, if required. If the screen gets dirty quickly, this will reflect how often the chip will need to be replaced.
The seal on the panel assembly of the Enclosure forms the seal between the Enclosure cover and the Enclosure back panel.
This seal should be inspected on a regular basis, looking for cracks, hardening of the foam rubber and/or loosening from the back panel assembly.
TEMPERATURE SENSOR
Inspect and clean, at least every 2 to 3 months and more often in extreme environmental conditions.
CAUTION
Be careful of the thermister, as it is very delicate.
Carefully clean insects and debris from the temperature probe.
The temperature probe can NOT be calibrated, so if the readings are poor the complete probe must be replaced.
After several years the temperature/RH sensor may become corroded and should be replaced.
NOTE ! Water will affect the temperature readings, so be sure no direct water is hitting the weather station from sprinklers in the area.
Any time the Enclosure is opened, upon closing it the desiccant pack should be replaced with a new desiccant pack.
At least once a year the desiccant pack should be replaced with a new pack.
The Enclosure internal moisture should be monitored. The desiccant pack maintains a low humidity in the enclosure an minimizes the chance of condensation on the datalogger and other electronic components.
The desiccant pack should be changed when the internal Enclosure humidity sensor measures 35% or higher.
If the moisture level gets too high the Enclosure should be opened and dried out. The desiccant pack needs to be replace with a new pack.
All parts should be dried with a clean, dry cloth and components inspected for corrosion.
SEAL OF ET ENCLOSURE
When replacing the cover on the Enclosure, place the cover top into
Page 45
Page 56
the top of the Enclosure and be sure the cover is properly engaging in the tabs at the top of the Enclosure. Gently close the cover and secure it with the latch at the bottom. Be sure the latch hasp is securely latched, as keeping out moisture, is dependent upon a tight seal between the Enclosure back panel and the cover, provided by the molded rubber seal on the Enclosure back panel.
At least once a year, or whenever sensor failure is suspected, the sensors listed below should be checked with a volt/ohm meter for ohm resistance.
Wind Sensor - Wind Speed (Anemometer) sensor
Wind Sensor - Wind Direction Vane Sensor.
Rain Gage Tipping Bucket
BATTERY CHECK
At least TWICE (2 times) a year the AC power wires to the charger should be disconnected to allow the station to operate off the batteries without the charger in operation.
Check the battery under these conditions to get an accurate actual battery voltage level.
Allow 2 hours, after the battery AC recharge power has been disconnected, for the battery to dissipate high voltage level before checking the voltage.
CAUTION ! Be sure to RE-CONNECT the battery charger and/or power wires to the weather station after checking the battery voltage.
Solar Radiation Sensor - Pyranometer.
All sensors that are to be checked, EXCEPT the Rain Gage, should have a measurable resistance. INFINITE resistance indicates an OPEN circuit. Any sensor with an open circuit needs to be repaired or replaced.
The 16 VAC power or the solar panel power should be connected to the weather station at all other times.
SENSOR TESTING
Page 46
Page 57
WIND SPEED SENSOR
Refer to schematic wiring diagram ­located in the Appendix - FIGURE 29
Measure the resistance from P1 to G (pins 3 to 5) of the Wind Speed Sensor. Slowly turn the wind speed cup. The resistance should vary from infinite to less than 1 OHM as the reed switch closes in the anemometer.
WIND DIRECTION
Refer to schematic wiring diagram ­located in the Appendix - FIGURE 29
The Wind Direction sensor varies in its resistance as the vane turns. With the OHM meter connected to E2 and 2H (pins #1 & #2) the resistance should vary from 11K OHMS to 21K OHMS.
If infinite resistance is measured, then the wiper in the potentiometer is most likely damaged and the sensor needs to be repaired.
With the OHM meter connected to 2H & AG (pins #2 & #4) the resistance should vary from 1K to 11K OHMS with change in wind direction. If infinite resistance is measured then the potentiometer is bad and should be replaced.
SOLAR RADIATION SENSOR
PYRANOMETER
Refer to schematic wiring diagram ­located in the Appendix - FIGURE 30
The Solar Radiation Sensor (Pyranometer) should measure between 40 OHMS and 90.2 OHMS, when checked with an Ohm meter between 3H & 3L (pins #1 & #2).
Set meter for lowest DC millivolts (a very sensitive meter is required) and measure from 3H to 3L (pins #1 & #2). The small voltage should vary with variation in light intensity. Place your hand over the sensor ­should read 0 VDC.
TIPPING BUCKET RAIN GAGE
Refer to schematic wiring diagram ­located in the Appendix - FIGURE 31
The Rain Gage has a reed switch that closes as the tipping bucket mechanism “tips”. Connect the OHM meter across P2 & G (pins #3 & #5) and should read infinite OHMS. When bucket mechanism is “tipped” - should then get less than 1 OHM.
If the bucket tipping mechanism is working correctly you should read
+5 Volts DC with the meter set at DC
volts and connected across the reed switch, while sensor is plugged into the Weather Station. When the bucket is “tipped” the reed switch closes and you should have 0VDC. There is
Page 47
Page 58
continuous low voltage going through
this reed switch, except as it “tips” at which time the +5 Volts DC is shorted, and thus there is a possibility of corrosion build up on the switch over time.
If just the RH readings are “bad” - then the RH chip most likely needs to be replaced. New RH chips, for replacement, are available from your local Rain Bird Distributor.
The reed switch is easily replaced and the parts are available from your local Rain Bird Distributor.
TEMPERATURE AND
RELATIVE HUMIDITY SENSOR
Refer to schematic wiring diagram ­located in the Appendix - FIGURE 32
Set the meter to DC volts and check across pins #4 & #6 for 12VDC.
DO NOT connect an OHM meter across the RH chip or damage may occur to the RH chip. If you are experiencing problems with the temperature and relative humidity probe - determine the following:
Are both the temperature and humidity readings “bad” ?
Is just the temperature reading “bad”?
Is the RH reading “bad” ?
AIR TEMPERATURE PROBE ( ON REDUCED SET STATION
ONLY )
Refer to schematic wiring diagram ­located in the Appendix - FIGURE 33
Set meter to OHMs and measure from E1 to 1H (pins #3 to #1) should read a minimum of 249K OHMS. Colder temperatures result in higher resistances.
With meter on OHMS measure from 1H to AG (pins #1 to #5). Should have a fixed reading of 1K OHMS resistance.
With meter on OHMS measure from E1 to 1L (pins #3 to #2) should read a minimum of 249K OHMS. Colder temperatures result in higher resistances.
With meter on OHMS measure from 1L to AG (pins #2 to #5). Should have a fixed reading of 1K OHMS resistance.
Page 48
Page 59
TROUBLESHOOTING:
The following information is for trouble­shooting the weather station only.
ISOLATING THE PROBLEM
The recommended approach to trouble­shooting the weather station is to divide the system into three (3) sections, the weather station itself, the commun­ication path or network and the device for communication (computer hookup). Isolate these sections and test each one to find the problem.
FIGURE 23 - USING THE ML-10-KD KEYBOARD DISPLAY
CHECKING THE WEATHER STATION:
Check the weather station by using the ML-10-KD keyboard display. If the ML-10-KD is not available, you may also use a laptop computer along with a serial cable, as shown in FIGURE 25 under “Using a Laptop Computer”.
USING the ML-10-KD KEYBOARD DISPLAY
Connect the keyboard display to the Serial I/O connector on the back of the ET Enclosure behind the cable cover. Refer to FIGURE 24 below.
With the Keyboard display plugged into the Serial I/O connector on the back of the ET Enclosure, there should be power to the I/O connector and now to the keyboard display with the display now being active.
Enter [*6] on the keyboard keypad. Then press [A] to advance to the first location (location #1) which is the Battery Voltage. You can ADVANCE to each of the next locations by pressing the letter [A] key. Pressing the letter [B] key will BACK-UP to the previous location. By entering [*0] you can leave the ML-10-KD in a “low energy mode”.
The location values are not important at this time, as long as values are present.
Remove the cable cover. Remove the cap from the Serial I/O connector and plug the keyboard display cable into the connector.
After looking at all the locations needed be sure to do a [*0] to place the micro
Page 49
Page 60
logger in a low energy mode to conserve battery charge.
DATALOGGER LOCATION TABLE
Location Reading Normal Range
1 = Battery Voltage ~ 12.9 to 14.2 Volts
2 = Air Temp. C ~ close to air temp
3 = Relative Humidity ~ 0 to 100%
4 = Wind Run ~ Total Wind
5 = Solar Radation ~ 0 to 1.2 kW m-2
6 = Rain Fall ~ 0 to 2 Inches
7 = Wind Direction ~ 0 to 359 degrees
8 = Air Temperature ~ F degrees
9 = RH2 ~ 0 to 100%
10 = Wind Speed ~ MPH
13 = Enclosure RH ~ -40 degree to + 50
degree C or 10% to 30% when sealed for several hours.
Page 50
Page 61
TROUBLESHOOTING PROBLEMS
No display on the ML-10-KD keyboard.
(If there is display but NO response to input on the keyboard - continue with the next diagnostic problem below.)
If you see NO display on the keyboard then there is NO power output from the datalogger of the weather station.
Make sure the battery has been installed.
Use a voltmeter to measure the voltage on the 12V and G terminals; the voltage must be between 9.6 and 16 VDC.
Disconnect any communications or storage peripherals from the datalogger.
Pins 1 and 2 of the Serial I/O connector should give +5 Volts DC.
If NO voltage is found - then check for incoming power to the weather station ­starting at the transformer check for 110 volts AC power to the transformer.
Check for +16 Volts AC coming from the secondary side of the transformer.
Check for +16 Volts AC at the two (2) terminals marked “CHG” on the panel of the ET Enclosure. (Refer to FIGURE 9 for location of +16VAC terminals).
If you have power all the way to the datalogger PC board - then you must replace the datalogger PC board and have the original datalogger PC board repaired.
Enter [*] and wait a short time, at least two (2) minutes for the datalogger to see the keyboard - you should get 00:00 or some other characters on the display. Enter a [*0] and you should get LOG 1.
Continue with [*6] followed by
entering [A] to advance to the next location. Continue to press [A] to check ALL locations of the datalogger.
If still no response to keypad input - then continue with the next diagnostic problem below.
No response from datalogger through SC32A or modem peripheral.
At the datalogger:
No response using the keypad and/or erroneous letters in the display.
(If still NO response to keypad input ­then continue with the next diagnostic problem below.)
Check keypad response after each of the following steps:
Make sure the battery has been installed.
Use a voltmeter to measure the voltage on the 12V and G terminals; the voltage must be between 9.6 and 16 VDC.
Make sure the datalogger is dis- connected from the modem.
Page 51
Page 62
At the computer:
Make sure the Station File is configured correctly.
25-pin serial port:
computer endmodem end
Check the cable(s) between the serial port and the modem. If cables are not those furnished with the weather station, then check for the following configuration using an ohm meter:
9-pin serial port
computer end modem end
23 33 420 57
Make sure the modem is properly configured and cabled.
If still no response, contact your local Rain Bird distributor.
2 2 3 3 7 7 20 20
Make sure the sensor is properly wired to the datalogger.
Check the multiplier and offset parameters in the measurement instruction.
6999 or 99999 stored in final storage.
Final Storage format limitations are exceeded (no number larger than 6999 in low resolution, or 99999 in high resolution is stored). Change the datalogger program.
-99999 Displayed in an input location.
Make sure the battery voltage is between 9.6 and 16 VDC.
Make sure the Range parameter in the measurement instruction covers the full scale voltage output by the sensor.
Unreasonable results displayed in an input location.
Inspect the sensor for damage and/or contamination.
Page 52
Page 63
USING A LAPTOP COMPUTER
When a Laptop computer is being used to check the weather station it is necessary to use a Serial cable between the computer and the weather station, as configured in FIGURE 24 shown below.
CAUTION ! Before “plugging” the serial cable and computer into the Serial I/O connector on the back panel of the Enclosure - make certain that you have disconnected the 9-pin ribbon cable from
the Short Haul Modem or the Phone Modem. If you fail to do so, it is a high possibility that you will damage the modem.
FIGURE 24 - CONFIGURATION OF SERIAL CABLE
Connect the Laptop computer, using the serial cable as shown in FIGURE 25, to the Serial I/O connector on the back panel of the Enclosure - the same as shown for the Keyboard Display in FIGURE 24.
Start-Up the Weather Software and set the configuration up for the proper communication port.
Be sure a direct connect weather station has been configured.
Enter a capital [W] from the main menu.
Enter the security code [6275].
Choose a direct connect Weather
Station to monitor and the screen will go “BLANK”.
Enter [7240L].
Enter [7H].
Enter [*6].
[ENTER] [ENTER] - Continue to
[ENTER] and this will give you all the data locations and the current readings or each.
Enter [* ] to put the datalogger in a low energy mode.
Press the [ENTER] key until you see an (*).
Page 53
Page 64
CHECKING THE COMMUNICATIONS WIRE PATH:
Before initially connecting a direct connect or phone line weather station, or when troubleshooting the weather station and the communication wiring is suspect, check the communication wires for their integrity.
LOOP RESISTANCE
Connect the pair of wires, you will be checking, together at the far end. Using a volt/ohm meter, measure across the wire loop. A “GOOD” wire path has less than 600 OHMS resistance across the loop.
GROUND RESISTANCE
“Good” RAD SRM-5A Short Haul Modem.
First: Check that the RAD Short Haul
Modem, at the central computer location, is working correctly. This can be easily done by using the following method.
Jumper the output terminals of the RAD SRM-5A Short Haul Modem, located at the computer, as shown in FIGURE 26 below.
Using a working (“Good”) RAD SRM-5A Short Haul Modem connect the communication wires together at the weather station end as shown in FIGURE 26 below.
With the Rain Bird Weather Software, go to the Main Menu and set the “capital lock” on the keyboard of the computer.
Disconnect the communication wires at the MSP-1 pipe surge arrestor, located at the Weather Station. Using a volt/ohm meter, set the dial to R x 1K and measure from each wire to earth ground. A “GOOD” wire path has a high resistance to earth ground, of at least 750,000 OHMS or greater.
A “WS-PRO-SH” DIRECT CONNECT WEATHER STATION
Weather Station will not answer.
Test the wire path using a known
Be sure to configure a direct connect weather station.
Press a capital [W] from the Main Menu screen.
If a security number is asked for use [6275].
Choose a direct connect station and the screen will go “BLANK”.
Assuming you have connected the output terminals of the modem as shown in FIGURE 25 below, what you type will be echoed back to the computer screen. Testing the short haul modem in this way will verify that it is working properly. If you do not see the characters, that you
Page 54
Page 65
type, on the screen then the Short Haul Modem has a problem or the COM port and needs to be replaced.
FIGURE 25 - TEST OF SHORT HAUL MODEM
Second: After having determined, with
the test above that the RAD modem
at the computer is “Good” - you can then check to see if the communication path, between the computer and the weather station is “Good”.
Be sure to configure a direct connect weather station.
Press a capital [W] from the Main Menu screen.
If a security number is asked for use [6275].
Re-connect the field communication wires to the RAD modem output terminals, of the RAD modem at the central computer location.
At the Weather Station, disconnect
the communication wires from the MSP-1 pipe surge arrestors and tie the wires together as shown in FIGURE 26 below.
With the Rain Bird Weather
Software, go to the Main Menu and set the “capital lock” on the keyboard of the computer.
Choose a direct connect station and the screen will go “BLANK”.
Assuming you have connected the communication wires correctly at the weather station end, as shown in FIGURE 26 below, what you type at the computer will be echoed back to the computer screen. Testing in this way will verify that the communication wiring is “Good”. If you so not see the characters on the screen, that you have typed, then you know that there is a problem with the communication wiring.
Page 55
Page 66
NOTE ! Remember that you have a “spare” pair of communication wires in the Belden #9883 cable. Using this spare pair substitute it for one of the other pairs and test again. If it is not
FIGURE 26 - TEST OF COMMUNICATION WIRE
A “WS-PRO-PH” PHONE CONNECT WEATHER STATION
Weather Station will not answer.
Check the weather station for operation on it’s own to be sure it is functioning properly. This will verify the proper voltage coming into the weather station and also if the datalogger checks out O.K.
Connect a telephone to the phone line at the weather station and call out, or have someone call in. Listen for any noise on the line.
Refer to NOTE below.
NOTE ! A phone line going to the
computer or to the weather station itself MUST BE DATA QUALITY. You can talk over a phone line that will NOT allow data communication.. Listen for any fuzzy noises and any disturbance at all. You must be sure the phone line is
this pair that are “bad” then substitute the “spare” pair for the other pair and test again. In this way you should be able to determine which pair are “bad” and use the “spare” pair in their place.
“Good”. Time and time again we have set up stations and the phone line is NOT good enough for communication. Make sure the phone company knows this will be for data communication. Have Phone Company check line ALL the way back to the weather station.
If the station is still not answering, get your volt/ohm meter and measure across the phone line. It should read approximately 48 Volts DC, with the Ring as the positive side and the Tip the negative side.
Have someone call in and then measure the voltage across the phone line. It should read 90 to 110 Volts AC. The answer modem switch circuit requires 40 Volts to activate and allow the signal to pass to the datalogger.
The Datalogger detects the ring and raises the modem enable line high (pin 5), to +5 Volts DC. (Measure pin 5 to ground).
Page 56
Page 67
CAUTION ! Connect a volt/ohm meter to the phone line only in extreme cases. It is recommended to use FCC approved equipment only - while measuring current on a telephone line.
USE NO MSP-1, pipe surge arrestor on the telephone communication wires. If an MSP-1 pipe surge arrestor is used in the line, the Weather Station will usually answer and then hang up right away. The MSP-1 is for low voltage applications and the telephone line is excited to well over the 50 volt limit of the MSP-1 surge arrestor so will shunt the line to earth ground.
Test the phone modem, at the weather station by dialing out to the weather station. It is working and is O.K. if you can hear a dial tone and the dialing. This also verifies the communication path and most modem settings.
If telephone line appears to be O.K. - then change the phone modem at the weather station, to a known “Good” phone modem and try again.
If the station still does not answer, then have the telephone company check the phone line again, even if it is the fourth time they have been out.
COMPUTER MODEM AND COMMUNICATION TROUBLESHOOTING:
Weather Software will not commun­icate with the weather station.
Verify all the wiring, etc., at the computer, to the modem, and to the field.
Be sure the software is configured to the correct communication port according to the type of MAXI software being used for the system; i.e., MAXI 5, NIMBUS or CIRRUS. If you arrive at weather through MAXI then the serial port is configured through the MAXI software.
A data line monitor may be necessary to test the output from the computer and to verify that the serial port is working O.K. Most times output can be verified, however, with RAD Short Haul Modem or a phone modem. A data line monitor RS-232 Mini-Tester (available at Radio Shack) is a device that connects into the line with the serial port and by using lights will show the status of all the data lines.
It is important here to check the communication serial port of the computer and verify that it is functioning correctly, just as is required when troubleshooting MAXI or MAXICOM.
TESTING THE SHORT HAUL MODEM
For the older weather stations, which used the RAD SH-6A Short Haul Modems and the current “PRO” weather stations, which use the RAD SRM-5A Short Haul Modems - both of these modems can be tested in the same manner.
Page 57
Page 68
With the modem connected to the computer, jumper the output terminals of the RAD modem as shown in FIGURE 25.
With the Rain Bird Weather Software, go to the Main Menu and set the “capital lock” on the keyboard of the computer.
Be sure to configure a direct connect weather station.
Press a capital [W] from the Main Menu screen.
If a security number is asked for use [6275].
Choose a direct connect station and the screen will go “BLANK”.
Weather then the reading will jump to +15 Volts DC.
On the old SH-95C modem there is a ring button, and the voltage level will go up to +15 volts DC when you push this button, and return to +7 Volts DC upon release & when the communication cable is disconnected form the SC95A.
If these voltages do not exist, then you must replace the modem or have the modem repaired.
Assuming you have connected the output terminals of the modem as shown in FIGURE 26, what you type will be echoed back to the computer screen. Testing the Short Haul Modem in this way will verify that it is working properly. If you do not see the characters, that you type, on the screen then the Short Haul Modem has a problem and needs to be replaced.
If you have the very old type Short Haul modem - it should be replaced with the newer type RAD SRM-5A modem, if at all possible.
If the old SH-95C modem is working properly you can measure +7 Volts DC across the (SRC) and the (RET), during a rest period. This is only when the computer is out of the MAXI program and the Weather program. If the computer is running
Page 58
Page 69
TESTING THE PHONE
MODEM
If a Hayes Model 1200 or 2400 Smart Modem is being used to communicate with the Weather Station - be sure the switch settings are as follows:
7 UP Single Line RJ11 phone jack
8 DOWN Enables Commands
9 UP Compatible with Bell 103/212A modems
SW # Setting Function
1 DOWN Ignores DTR
2 UP English word result codes
SW # Setting Function
3 DOWN Result codes sent to computer
4 DOWN Characters not
echoed
5 DOWN Auto-Answer disabled
6 DOWN Carrier detect always on
10 UP Modem Reset when turned on
Test the phone modem by dialing out to the weather station. It works if you can hear a dial tone and the dialing. This verifies the communication path and most modem settings.
A phone line going to the computer or the weather station itself must be of DATA QUALITY . You can talk over a phone line that will not allow data communication. Listen for any fuzzy noises and any disturbance at all. If the modem keeps “HANGING UP”, this is an indication of either an incorrect setting or a bad phone line.
Page 59
Page 70
Appendix
TYPICAL 3-ROD GROUNDING GRID:
Grounding grids are required at the Central equipment location, for the weather station (grounding grid for the central equipment may also be used for the weather station if accessible) and at the weather station itself.
A typical 3-rod grounding grid shall consist of three (3) 5/8” diameter x 8’-0” long copper clad grounding rods. The rods shall be in a triangular arrangement, if at all possible, with each rod at least 8’-0” away from any other rod.(refer to FIGURE 28 below). If it is impossible to arrange the rods in a triangular pattern then they may be arranged in a straight line (although NOT as effective) with each rod at least 8’-0” from any other rod.
NOTE! If longer than 8’-0” rods are used, then the rods shall be spaced no closer than the length of the rod from each other.
The 3 rods shall be driven into the ground with top of rod at least six inches (6”) below the finish grade. The rods shall be tied together below grade with #10 gauge or larger bare copper wire. The wire shall be attached to the rod using a brass clamp. A separate brass clamp shall be used for each attachment.
NOTE ! No more than one wire shall be used in any individual clamp. Multiple wires shall NOT be allowed.
Any rod that has a ground wire con­nected to it, coming from the surge
arrestor at the equipment or grounding the equipment, shall have a standard 18” x 24” rectangular valve box installed around the top of the rod. This shall provide future access to inspect and/or maintain the MGP-1 grounding plate assembly, MSP-1 pipe surge arrestors, brass clamp and ground wire should this be necessary. Any of the other rods in the grid shall have a standard 6” diameter round valve box installed around the top of the rod for future access.
Where MSP-1 pipe surge arrestors are required on the communication path wiring, the MSP-1 pipe surge arrestor shall be mounted on an MGP-1 grounding plate assembly. The MGP-1 grounding plate assembly in turn shall be securely attached to one of the grounding rods of the 3-rod grounding grid. Attach the MGP-1 to the ground rod that is nearest to the equipment, so as to have a minimum of exposed wire between the equipment and the surge arrestor itself.
Use 3M - DBY or DBR Direct Burial splice kits for ALL wire splices.
GROUND RESISTANCE - With the 3­rod grounding grid we are attempting to get a ground resistance of 5 OHMS or less, if at all possible. Any thing above 15 OHMS is of little value for protection. In order for the surge arrestors to be effective they must be able to discharge to ground rather than allow the surge to go to the electronic components. Therefore the “HIGHER” the resistance to ground (higher OHM reading) the chance of the surge being shunted to
Page 60
Page 71
ground rather than go to the electronic components. From this you can see that it is also important to maintain a “Good Ground” at ALL times.
BENTONITE CONTACT: In using grounding rods we are depending upon the “contact” of the surface of the rod to the soil. The greater the contact the better chance we have of obtaining a “good” ground. If you are in a soil type that you know will not give good surface contact with the rod, you may want to consider drilling a 4” to 6” diameter hole in which to place the ground rod. You can then back fill around the rod with Bentonite or other similar material that is very dense and in this way increase the contact of the rod with the soil.
ROCKY CONDITIONS: In areas where you are unable to drive a rod or to bore a hole for a rod, you may need to consider laying the rods horizontal 12 inches or so below the surface on a good 6” deep bed of soil or Bentonite. Again rods should be 8’-0” apart and tied together with #10 gauge or larger bare copper wire at both top and bottom of the rods to form a grid.
ROCK LAYER: Where a rock layer is found under a shallow layer of soil, a 4’-0” x 4’-0” square piece of sheet steel, 3/8” to ½” thick, should be considered ot be laid horizontally on a 4” thick layer of soil or Bentonite over the rock layer. A bolt or short piece of steel rod welded to the plate will provide a means of connection to the steel plate. The plate should be covered to finish grade with good top soil.
IMPROVING EARTH GROUNDS:
When a grounding grid is first installed you are unable to get a true OHMs reading, since the rod surface will not be in good contact with the soil. The grid must be installed for 5 or 6 weeks before a meaningful reading can be obtained. It is also recommended that the grounds be checked at least once a year and in severe lightning areas perhaps as often as two or three times a year.
NOTE ! A good reading CANNOT be obtained with a volt/ohm meter. A Meggar or Vigra-Ground type instrument must be used to check the ground resistance.
If unsatisfactory readings are obtained, the ground may be improved in one of the following ways:
(1) Extend a #6 or larger bare copper
braided wire from one of the rods out across a fairway and buried a minimum of 12” below the surface. Be sure the wire is between rows of sprinklers and away from other wires, pipes, etc. as far as possible. This will place the wire in an area that will be frequently watered and will increase the surface contact of the grounding network.
(2) In the center of the triangle, of the
3-rod grid, install an 8’-0” long piece of 6” diameter perforated plastic pipe. Top shall be at least 6” below the finish grade. Fill this pipe with rock salt, Epson salts, or other suitable similar material and water it down. The salt will leach out into the soil and corrode the surface of the rods giving improved and greater surface contact. Place a 6” diameter
Page 61
Page 72
valve box cover over the end of the pipe and cover it with soil to finish grade.
MSP-1 PIPE SURGE ARRESTORS:
Each of the pairs of wires in the communication path, between the central computer and the weather station, shall be wired through an MSP­1 pipe surge arrestor, at both the computer end and at the weather station end. The MSP-1 pipe surge arrestors shall be located as close to the equipment it is to protect as is practical. The MSP-1 pipe surge arrestors shall be mounted in MGP-1 grounding plate assemblies.
The MSP-1 pipe surge arrestor is marked, “EQUIP” on one end and “LINE” on the other end. When installing the MSP-1 be sure that the end marked “EQUIP” is located “toward the equipment” it is to protect, i.e., computer or weather station. The “LINE” end goes toward the field.
The Green wire on each end of the MSP­1 pipe surge arrestor shall be attached to one of the grounding screws on the MGP-1 grounding plate assembly.
REFER TO FIGURE 28 ON THE NEXT PAGE
Page 62
Page 73
FIGURE 28 - TYPICAL 3-ROD GROUNDING GRID DETAIL
Page 63
Page 74
2H to AG - pins 1 to 2
2H to E2
pins 1 to 3
4
FIGURE 29 - TESTING OF WIND SENSOR
Page 64
Page 75
FIGURE 30 - TESTING OF SOLAR RADIATION SENSOR
Page 65
Page 76
FIGURE 31 - TESTING OF RAIN GAGE
Page 66
Page 77
FIGURE 32 - TESTING OF TEMPERATURE/RELATIVE HUMIDITY
SENSOR
Page 67
Page 78
FIGURE 33 - TESTING OF AIR TEMPERATURE PROBE
Page 68
Loading...