The material and instructions covered in this manual
have been carefully checked for accuracy and are
presumed to be reliable. However, Radionics, Inc.
assumes no responsibility for inaccuracies and
reserves the right to modify and revise this manual
without notice.
If a discrepancy is found in this documentation,
please mail a photocopy of the corrected material to:
Technical Communications
c/o Radionics, Inc.
1800 Abbott Street
P.O. Box 80012
Salinas, CA 93912-0012
In this version of the Installation Manual, we added
information about the D2112E Control/Communicator.
New information about the D2112E appears
throughout the manual. We marked changes
significant to the design and operation of the panel
with a vertical line in the margin. An example of the
line is shown in the margin to the left of this
paragraph.
FCC Notices
Part 15
This equipment generates and uses radio frequency
energy. If not installed and used in accordance with
the manufacturer’s instructions, it may cause
interference to radio and television reception. It has
been tested and found to comply with the
specifications in Part 15 of FCC rules for Class B
Computing Devices.
If this equipment causes interference to radio or
television reception, which can be determined by
turning the equipment on and off, the installer is
encouraged to correct the interference by one or
more of the following measures: 1) Reorient the
antenna of the radio/television. 2) Connect the AC
transformer to a different outlet so the control panel
and radio/television are on different branch circuits. 3)
Relocate the control panel with respect to the radio/
television.
If necessary, the installer should consult an
experienced radio/television technician for additional
suggestions, or send for the “Interference Handbook”
prepared by the Federal Communications
Commission. This booklet is available from the U.S.
Government Printing Office, Washington D.C. 20402,
stock number 004-000-00450-7.
Part 68
This equipment complies with Part 68 of FCC rules. A
label contains, among other information, the FCC
registration number and ringer equivalence number
(REN).
Radionics registered the D2112 Control/
Communicator for connection to the public telephone
network using an RJ38X or RJ31X jack.
Use the ringer equivalence number (REN) to
determine the number of devices you can connect to
the telephone line. Excessive RENs on the telephone
line may result in devices not ringing in response to
an incoming call. In most, but not all areas, the sum
of the RENs should not exceed five (5). Contact the
telephone company to determine the maximum REN
for the calling area.
If the D2112 Control/Communicator causes harm to
the telephone network, the telephone company will
notify you in advance. If advance notice isn’t
practical, the telephone company will notify the
customer as soon as possible. Also, you will be
advised of your right to file a complaint with the FCC
if you believe it is necessary.
The telephone company may make changes in its
facilities, equipment, operations, or procedures that
could affect the operation of the D2112. If this
happens, the telephone company will provide
advance notice in order for you to make the
necessary modifications to maintain uninterrupted
service.
If you experience trouble with the D2112 Control/
Communicator, please contact Radionics Customer
Service for repair and/or warranty information. If the
trouble is causing harm to the telephone network, the
telephone company may request that you remove the
D2112 from the network until the problem is resolved.
User repairs must not be made. Doing so voids the
user’s warranty.
Do not install the D2112 on public coin service
provided by the telephone company. Connection to
Party Line service is subject to state tariffs (Contact
your state public utilities commission for information.).
You must supply the local telephone company with
the following information at their request.
• The line you are going to connect the panel to
• Make (Radionics), model (D2112), and serial
number of the panel
• FCC registration number and ringer equivalence
for the panel.
FCC Registration Number: AJ9USA-20644-AL-E
Ringer Equivalence:0.2B
Service Center in USA: Radionics, Inc.
1800 Abbott Street
P.O. Box 80012
Salinas, CA 93912-0012
The Radionics D2112 and D2112E Control/
Communicators are shipped pre-assembled from the
factory. You should receive the following parts with
your D2112 or D2112E panel.
Panel Assembly
• D2112 or D2112E Panel
• D2103 Enclosure
• D1625 Transformer
•
D2112 Only: Smoke Detectors Compatible with
the D2112 Technogram
Hardware Pack
•
D2112 only:
Point 1 (30-01098-102)
• Five 1k Ω end-of-line resistors for Points 2 to 6
(six with D2112E) (15-03130-008)
• Two #6 by 3/8" sheet metal screws to secure
the D2103 Enclosure cover (60-03977-006)
One 2.0k Ω end-of-line resistor for
Ordered Separately
Literature Pack
•
D2112/D2112E Installation Manual
(74-07111-000)
•
D2112/D2112E Program Entry Guide
(74-07112-000)
•
D2112/D2112E Program Record Sheet
(74-07114-000)
D202 Keypad
The D2112C package includes one D202 Keypad.
Each D202 includes the following.
•
D202 Keypad
•
Installation Sheet
•
User's Cards
•
Key Labels
•
Security System User's Guide
(74-07117-000)
*
Three-wire cable assembly
Battery
Order a D1240 Battery (12 V 4.0Ah) to complete a
basic D2112 or D2112E installation.
Order a D126 Battery (12 V 7.0Ah) for fire and
combined fire/burglary systems.
(74-07090-000)
(74-07092-000)
(73-07115-000)
(74-07118-000)
(15-07032-000)
Enclosure Options
The D2112 and D2112E are shipped in the D2103
enclosure. If you want to mount the D2112 or
D2112E in one of the optional enclosures listed
below, order the D2112M or D2112EM, and the
enclosure of your choice.
• D8103 Universal Enclosure
• D8108A Attack Resistant Enclosure
• D8109 Fire Rated Enclosure
Listings and Approvals
Fire
Underwriters Laboratories lists the D2112 and
D2112E Control/Communicators as Signal System
Control Units for NFPA 72 Household Fire Warning.
The D2112 and D2112E have been submitted for
evaluation to:
CSFM7167-0801:143 (Residential)
UL 985 Household Fire Warning
ULC 540 Household Fire Warning and Burglar Alarm
Control Units and Accessories
Burglary
UL 1023 Household Burglar Alarm
UL 365 Police Station Connect
UL 609 Local Burglar Alarm
UL 1076 Proprietary Burglary Alarm
UL 1610 Central Station
ULC 303 Burglar Alarm System Control Units, Local
Type
ULC 304 Burglar Alarm System Control Units,
Monitoring Station Type, Commercial
Premises
Getting Started
Before You Begin
Radionics recommends you review this manual
before you begin the installation to determine the
hardware and wiring requirements for the features
you want to use.
Have the following additional documents handy as
you read through the manual:
Lift the bottom of the enclosure cover and remove it
from the base. See Figure 1.
Mount the base in the desired location. Leave a 2"
clearance at the top of enclosure so that you can
easily install the cover.
Run the Premises Wiring
Run the necessary wiring throughout the premises
and pull the wires into the enclosure. Do not make
any connections yet.
Wire Length
The length of the wire run for points is limited only by
the resistance on the loop and potential EMI
(Electro-Magnetic Interference) problems.
On the D2112, wire resistance on the Point 1 sensor
loop must be less than 50Ω. Measure the wire
resistance before installing smoke detectors. Short
the end-of-line resistor before metering the wire.
Resistance on the sensor loops for Points 2 to 8 (1
to 6 on D2112E) must be less than 100Ω with the
end of line resistor shorted and the detection devices
connected.
Maximum wire length for the transformer is 50 feet
(18 AWG, stranded).
Maximum wire length for all keypads combined is
500 feet (22 AWG).
EMI (Electro Magnetic Interference)
AC wiring can induce EMI (both noise and low level
voltage) into adjacent wiring. Run phone and sensor
loop wiring away from AC conductors, including the
transformer wire. Run keypad wiring away from AC
and phone wiring.
EMI may also occur if you install the panel or run
system wires near the following:
• Computer network system
• Fluorescent fixtures
• Telephone cabling
• Ham radio transmitter site
• Heavy machinery and motors
• High voltage electrical equipment
• PBX telephone system
• Public service (police, fire departments, etc.)
using radio communications
• Radio station transmitter site, or other broadcast station equipment
• Welding shop
If you think that EMI may be a problem, use shielded
cable. The drain wire for the shielded cable must
have continuity from terminal 3 on the panel to the
end of the wire run.
If continuity is not maintained, the shielded cable
may aggravate potential noise problems rather than
eliminate them. If you cut the drain wire to install
devices be certain to splice it together. Solder and
tape all splices.
Cover
Base
Swing cover out from
base at bottom. Lift
cover clear of base.
74-07111-000-D 1/96
Connecting the drain wire to ground at other than
terminal 3 may also produce problems.
Mount base to wall.
Leave at least 2 inches
clearance at top to install
and remover cover.
Mounting locations
for optional
D133 Relay Modules.
Figure 1: D2103 Enclosure
D2112/D2112E Installation Manual
Page 5
Base
Slide cover
tab into slot
on base for
convenient
view of Wiring
Diagram
during
installation.
To help prevent damage from electrostatic charges
or other transient electrical surges, connect the
panel to earth ground at terminal 3 before making
any other connections.
A grounding rod or cold water pipe are
recommended earth ground references.
Radionics does not recommend a telephone or
electrical ground for the earth ground connection.
Use 18 AWG wire maximum under the terminal. Use
a lug or splice for larger wire.
Do not connect any other panel terminals to earth
ground. The panels common terminals and terminal
3, earth ground, are electrically isolated.
Charge the Battery as You Work
Lock the Standby Switch
Locking the pin in the standby position allows you to
charge the battery as you install the detection
devices and keypads. Lock the pin down now. See
Figure 2.
With the Standby Switch locked down, the panel
deactivates the external relay outputs, suppresses
reports, and disables all arming functions.
Lock the Standby Switch down to program the
panel locally, from the keypad or the D5200.
Releasing the Standby Switch from the closed
position resets the panel. The panel resets all its
timers and counters, and clears all buffers.
Transformer
Terminals 1 and 2
Connect the transformer to terminals 1 and 2 on the
panel before plugging it into the power source.
Use 18 AWG wire to connect the transformer to the
panel. Wire length should be kept as short as
possible. Maximum length is 50 feet.
Never share the transformer with other
equipment:
Foreign grounds on the AC input
damage the panel's power circuit.
Battery
Terminals 4 and 5
Place the battery upright in the base of the
enclosure. First connect the bare end of the black
battery lead to terminal 5 on the panel. Then plug
the other end to the negative (-) side of the battery.
Next connect the bare end of the red battery lead to
terminal 4 on the panel. Then plug the other end to
the positive (+) side of the battery.
D126 Battery required for fire and combined fire/
burglary systems:
requirements, use the Radionics D126, 12 V 7.0Ah
battery for fire and combined fire/burglary systems.
Install and wire detection devices, keypads, and
indicating devices (bells, sirens, or strobes for
example) at their locations throughout the premises.
DO NOT make the connections at the panel end of
the wiring yet.
Number of Sensors
When using the D2112's Point 1 as a fire point, the
number of devices you can connect to it's sensor
loop is limited. See
Page 10.
The number of sensors you can connect to the
sensor loops for points 2 to 8 (1 to 6 on D2112E) is
limited only by the resistance on the loop.
Resistance must be less than 100Ω with the
detection devices connected.
Point 1 on the D2112 Only
on
Continue Connections
to the Panel
Power Down First
Unplug the transformer and disconnect the battery to
make the remaining connections to the panel.
Available Power
The panel combines power produced by the power
supply with power from the secondary power source
(the battery) to produce a total of 1.5A of
power at terminals 6 and 7.
D126 Battery required for fire and combined fire/
burglary systems:
requirements, use the Radionics D126, 12 V 7.0Ah
battery for fire and combined fire/burglary systems.
Power restricted for fire and combined fire/
burglary systems:
Formula
available for fire and combined fire/burglary systems.
Fire System Power Formula
To calculate the current available at terminals 6 and
7 for fire and combined fire/burglary systems:
below to calculate the alarm current
1. Add together the current draws for all devices
connected to terminal 9. This total is current
required for the Normal Standby Condition
(NSC). This total must be less than 140mA.
2. Subtract the NSC current required calculated in
step 1 from the Primary Alarm Current, 860mA.
The difference is the Alarm Current Available
for terminals 6 and 7.
In order to meet standby battery
Use the
Fire System Power
alarm
Alarm Output
Terminals 6 and 7
Terminals 6 and 7 provide a 10.2 VDC to 13.9 VDC
output when activated.
steady positive output.
pulsed or steady negative output as programmed.
There is always power at Terminal 6:
sends a trouble report if terminal 6 is shorted to
ground. The D2112 sends a trouble report if terminal
6 is shorted to terminal 7 while the alarm output is
activated.
Use this power for bells, siren drivers, piezo fire
sounders, electronic horns, or other devices.
74-07111-000-D 1/96
Terminal 6 provides a
Terminal 7 provides a
The D2112
D2112/D2112E Installation Manual
In formula format:
Primary Alarm Current – NSC current required =
Alarm Current Available
You can connect up to four keypads to the panel.
The installation sheet packaged with each keypad
contains mounting instructions. Wire keypads to the
panel in parallel as shown in Figure 3.
You must use a minimum of five feet of wire (22
AWG) when connecting the keypad to the panel.
A short on terminal 9 within five feet of the panel
prevents the panel from operating correctly.
Maximum wire length for all keypads combined is
500 feet (22 AWG).
Auxiliary Power
Terminal 9
The continuous current draw for powered devices
connected to terminal 9, including keypads, must
not exceed 350mA (140mA for fire and combined
fire/burglary systems). Devices powered from this
output must operate over a range of 10.2 VDC to
13.9 VDC.
You must use a minimum of five feet (22 AWG) of
wire when connecting devices mounted outside
the enclosure to terminal 9.
within five feet of the panel prevents the panel from
operating correctly.
A short on terminal 9
Extra power needed for more keypads:
Keypad draws 45mA (125mA Alarm). Review
Outputs
output requirements for your system. Instructions for
using stand alone power supplies are included.
on page 14 to determine the total power
The D202
Power
Keypad
Connect up to
four in parallel.
Checking Continuous Current Draw
The panel allows you to check current draw using
the keypad. For more information about this and
other keypad diagnostic features, see the
The D2112E's Aux Power and Bell outputs are
protected by 2 Amp fast blow fuses. The fuses are
5 mm x 20 mm, 2 Amp Fast Blow (Radionics Part #
57-03570-008). To test the fuses, use a Volt/Ohm
meter to follow these steps:
1. Remove the fuse from the socket.
4
3
2
1
2. Switch the meter to measure Ohms.
3. Attach the meter leads to each side of the fuse.
4. If the meter does not change when you
connect the leads to the fuse, the fuse is open
(blown). Replace the blown fuse with a 5 mm x
20 mm, 2 Amp Fast Blow fuse.
5. If the meter measures 0 Ohms, the fuse is
closed (normal), and does not need to be
replaced.
External Relays
Terminals 11 and 12
You can program terminals 11 and 12 to provide
outputs for two external relays. Review the
Group in the D2112/D2112E Program Entry Guide
for a description of the relay functions available.
Connect a D133 Relay Module for each of the
external relay outputs you intend to use. Figure 5
shows the connections.
RELAYS
Aux Power Fuse
2 Amp Fast Blow
Figure 4: D2112E Fuse Locations
External Relay 1
D133
Relay Module
Alarm Output Fuse
2 Amp Fast Blow
N/O 1 (Closes to COMM1 when relay is activated.)
COMM1 (Common)
N/C 1 (Opens from COMM1 when relay is activated.)
X1- (Connect to terminal 11 for External Relay 1)
X1+ (Connect to terminal 9.)
Warning:
Install D133 modules connected to
terminals 11 and 12 in the enclosure with the panel
as shown in Figure 1. Do not connect wiring for
external devices directly to terminals 11 or 12.
Point 1 on the D2112 is a powered, supervised
point.
The panel monitors the Point 1 sensor loop for
normal, shorted, or open conditions. Programming
determines how the panel responds to those
conditions. See the
Guide
.
Terminal 13 provides positive (+) voltage to
detection devices. Terminal 14, the loop return (-), is
isolated from earth ground.
The keypad Reset function interrupts power to this
sensor loop to reset smoke or glass break detectors.
Use a 2.0k Ω end of line resistor for point 1 on the
D2112. Figure 6 shows point wiring.
Connecting Two-Wire Smoke Detectors
to Point 1 on D2112 Only:
Connect up to five Radionics D262 two-wire smoke
detectors to point 1 on the D2112. Refer to the
Technogram, Smoke Detectors Compatible with the
D2112
(73-07115-000), for a complete list of
detectors compatible with the D2112.
Four-Wire Smoke Detectors
Connect any number (limited by available power and
the Authority Having Jurisdiction) of 12 VDC fourwire smoke detectors to any supervised point. Install
a suitable power supervision device according the
manufacturer's instructions. Route the power for the
detectors through a D133 Relay Module. The relay
module must be connected to one of the panel's
external relay outputs programmed for the reset
function. See
Program Entry Guide
Heat Detectors and
Other Dry Contact Initiating Devices
Connect any number (limited by the Authority Having
Jurisdiction).
Burglar Devices
Connect any number (limited by available power) of
burglar devices to any point. Do not combine fire
detection and burglar devices.
D2112/D2112E Program Entry
RELAYS
in the
D2112/D2112E
for programming instructions.
Points 2 to 6 (1 to 6 on D2112E)
Terminals 15 to 22 (14 to 22 on D2112E)
Points 2 to 6 (1 to 6 on D2112E) are supervised,
non-powered points.
The panel monitors sensor loops for normal,
shorted, or open conditions. Programming for each
point determines how the panel responds to those
conditions. See the
Guide
.
Terminate each sensor loop with a 1.0k Ω end of line
resistor. Figure 6 shows point wiring.
Four-Wire Smoke Detectors
Connect any number (limited by available power and
the Authority Having Jurisdiction) of 12 VDC fourwire smoke detectors to any supervised point. Install
a suitable power supervision device according the
manufacturer's instructions. Route the power for the
detectors through a D133 Relay Module. The relay
module must be connected to one of the panel's
external relay outputs programmed for the reset
function. See
Program Entry Guide
Heat Detectors and
Other Dry Contact Initiating Devices
Connect any number (limited by the Authority Having
Jurisdiction).
Burglar Devices
Connect any number (limited by available power) of
burglar devices to any point. Do not combine fire
detection and burglar devices.
D2112/D2112E Program Entry
RELAYS
in the
D2112/D2112E
for programming instructions.
Points 7 and 8 on the D2112 Only
Terminals 23 to 25
Points 7 and 8 are non-powered points that are not
supervised with an end of line resistor.
The D2112 monitors the sensor loops for Points 7
and 8 for normal (closed) and open conditions.
Programming determines how the panel responds to
those conditions. See the
To prevent jamming of reports, wire the RJ31X jack
before the in-house phone system to support line
seizure. See Figure 7. Line seizure provides for a
temporary interruption of normal phone usage while
the communicator transmits data.
Unlock the Standby Switch
When you're finished programming move the
Standby Switch to the normal position. See Figure 9.
The panel sends a RE-BOOT report to the receiver
and the panel returns to the disarmed state. If you
programmed for test reports and left the hours and
minutes to next report prompts at 0 (zero), the panel
sends a test report with the RE-BOOT report.
After installation, confirm that the panel seizes the
line, acquires dial tone, reports correctly to the
receiver, and releases the phone line to the inhouse phone system.
PREMISES
PHONE
FULL MODULAR PHONE JACK
R1
☎
T1
1
2
3
4
5
6
7
8
RJ31X MODULE
R
T
INCOMING
TELCO LINE
Figure 7: RJ31X Phone Jack
Phone Cord
Connect the flying leads of the D164 Phone Cord to
the panel as shown in Figure 8. Connect the modular
end to the RJ31X jack.
To RJ31X Phone Jack
D164
Phone Cord
Black, Yellow,
Orange, and
Blue not used.
Brown
T1R R1T
Green
Red
Gray
10
9
8
7
6
5
4
3
2
1
All Non-Fire “Points to Watch” become selected:
After the Standby Switch is unlocked, all non-fire
points on the system become selected “Points to
Watch.” See the
D202 Keypad for more information.
RAM II ResetBye does not disarm the panel:
you unlock the standby switch, the panel returns to a
disarmed state. Using RAM II
does not affect the armed state of the panel.
Fill out the Point Chart
Radionics recommends you fill out the
Standby Switch
Locked (Closed)
1511 121617
1413
20
21 22 23 24 25
1918
Standby Switch
Normal (Open)
26
Figure 9: Standby Switch
Watch-Test
User’s Card on the
ResetBye
27
28
29
After
, however,
Point Chart
on the Installation Label located inside the D2103
Figure 8: Phone Cord
enclosure cover.
Power Up
Connect the battery and then plug in the
transformer.
Leave the Standby Switch locked down for now.
Program the Panel
Use the D202 Keypad, the Radionics D5200
Programmer, or a remote programmer to program
the panel. See the
Guide
for programming options and keypad
programming instructions.
If you're programming from the keypad or using
the D5200, make sure the Standby Switch is
locked down. See Figure 9.
If you're using the D5200, Figure 10 shows the
location of the programming jack. See the
You must fill out the point chart if you
programmed Point 1 for Fire with Verification
(Digit 1 = 2).
D2112E Program Entry Guide
See
POINT CODES
in the
for more information.
Use the program record sheet to gather the
information you need to fill out the point chart.
Local Programmer Connect
Lock standby switch to program.
Figure 10: Programmer Jack
Page 12
D2112/
Test the System
After finishing installation and programming, make a
complete functional test of the system. Test the
panel and all devices for proper operation. Test after
you first program the panel and after any
subsequent programming session.
Clear after test:
report buffer, close the Standby Switch for two
seconds and then release it. The panel returns to
service in the disarmed state.
To clear the alarm memory and
Detailed Panel Description
Primary (AC) Power Circuit
A 16.5 VAC, 25VA transformer (Radionics model
D1625) is the primary power source for the panel.
The AC power circuit provides 1.0 Amps of rectified
DC power. The panel reserves 140mA of this power
for internal operations and 350mA for continuously
powered devices. Under alarm conditions 860mA of
power is available for continuously powered and
alarm indicating devices combined.
Battery Replacement
Radionics recommends battery replacement every
three to five years under normal use. Exceeding the
maximum output ratings, or installing the transformer
in an outlet that is routinely switched off, causes
heavy discharges. Routine heavy discharges can
lead to premature battery failure.
D135A Prevents Deep Discharge:
Battery Cutoff Module protects the battery from deep
discharge during extended power outages. Deep
discharge can cause permanent battery damage.
Battery Supervision
When the battery drops to 12.1 VDC the OK light on
the keypad winks, indicating a trouble condition. The
panel transmits a BATTERY LOW report.
When battery voltage returns to 13.0 VDC and there
is AC power at terminals 1 and 2, the OK LIGHT at
the keypad stays on steady. The panel transmits a
BATTERY RESTORAL report.
Investigate low battery reports right away
If primary (AC) power is off and the discharge
continues, the panel becomes inoperative when the
battery voltage drops below 10.2 VDC.
The D135A Low
:
Transient suppressors and spark gaps protect the
circuit from power surges. This protection relies on
the ground connection at terminal 3. Make sure you
connect terminal 3 to a proper ground.
AC Power Failure
The panel indicates an AC power failure when power
at terminals 1 and 2 is missing for 60 seconds. The
AC Fail Buzz/Rpt AC Fail Buzz/Rpt
response to detected AC failure. The panel indicates
an AC power restoral 60 seconds after power
restores to terminals 1 and 2.
program item sets the panels
Secondary (DC) Power
A 12V, 4.0 Ah sealed lead-acid rechargeable battery
(Radionics D1240) supplies secondary power for
auxiliary and alarm outputs. The battery also powers
the system during interruptions in primary (AC)
power.
Lead Acid Batteries Only: The panel charging
circuit is only calibrated for lead-acid batteries. Do
not use gel-cell or nicad batteries.
Larger Battery Increases Backup Time: To
increase battery backup time, connect a larger
capacity battery, up to 7 Ah (Radionics D126).
Battery Charging Circuit
Float Charge
The float voltage for the battery charging circuit is
13.9 VDC. Deduct any continuous load for devices
connected to the panel from 860mA to find the
maximum current available for charging. At 13.9
VDC the battery is fully charged and is maintained
with a trickle charge of approximately 5mA.
Battery Discharge/Recharge Schedule
(No AC Power)
Discharge Cycle
AC OFFOK light on keypad begins winking
AC Fail reports if programmed
13.9 VDCCharging float level
12.1 VDCLow Battery reports if programmed
10.2 VDCPanel shuts down below 10.2 VDC
Recharge Cycle
AC ONPanel restarts, battery charging
begins, AC restoral report sent
13.0 VDCBattery restoral reports sent, OK
light on steady
Two self-resetting protection devices protect the
panel from short circuits on both the auxiliary and
alarm power outputs.
D2112E Circuit Protection
Two fuses protect the panel from short circuits on
both the auxiliary and alarm power outputs.
D2112 bell circuit protection:
power output while the bell is ringing disables the
alarm power output until the output times out or you
perform a panel reset.
Reports
The panel transmits a trouble Point 99 report when
there is a short on the alarm output, terminals 6 and
7, or when the fuse is open. The panel transmits a
trouble Point 98 report when Auxiliary Power,
terminal 9, is shorted, or when the fuse is open.
Extra Power for Keypad or Other Powered
Devices
The D202 Keypad draws 45mA (125mA in alarm).
You may need to add one or more D8132 Battery
Charger/Power Supply Modules for the number of
keypads you want to use. Figure 11 shows the
D8132 powering keypads in a stand-alone
configuration.
For UL certificated accounts use a UL listed power
supply. The D8132 is not UL listed as a stand-alone
power supply.
D2112 and D8132 (or other power supply) must
share COMMON:
Note that Figure 11 shows the
common from the D8132 module connected to both
the keypads' common and the terminal 10 on the
panel.
A short on alarm
A stand-alone power supply powering any device
connected to the panel must also be connected to
terminal 10 on the panel. Do not connect the standalone power supply to earth ground.
Telephone
Dialing Format
You can program the panel to use DTMF or pulse
dialing. See
D2112E Program Entry Guide
Communication Failure
After 5 attempts to reach the receiver (10 attempts if
two phone number are programmed) the panel goes
into communication failure. The panel clears any
reports in its phone buffer. The panel sounds a tone
at the keypad and winks the OK light.
Pressing the Clear key silences the tone. When
communication restores (a report is acknowledged
by the receiver), the OK light restores.
Ground Start
Some telephone systems require a momentary
ground input to initiate dial tone. To interface with a
ground start system, connect a D133 relay as shown
in Figure 12.
See
RELAYS Group
Entry Guide
external relay output for Ground Start.
Terminal 3 on the panel must be connected to an
earth ground reference.
Warning:
systems for fire or combined fire burglary systems.
Point 1 is a powered sensor loop. Review the
Radionics Technogram:
Compatible with the D2112
of compatible detectors.
Point 1 is supervised with a 2.0K EOL resistor.
Points 2 to 6 (1 to 6 on D2112E)
Points 2 to 6 are supervised with a 1.0K EOL
resistors
Open Loop = Greater than 8.9 VDC, but less
than 13.9 VDC.
Normal Loop = Greater than 2.5 VDC, but less
than 8.5 VDC.
Shorted Loop = Greater than 0.0 VDC, but less
than 2.0 VDC.
(D2112 Only) Points 7 and 8
Points 7 and 8 are not supervised with EOL
resistors.
Open Loop = Greater than 2.4 VDC, but less
than 13.9 VDC.
Normal (Closed) Loop = Greater than 0.0 VDC,
but less than 1.4 VDC.
Point Response Time
The panel scans point sensor loops every 500
milliseconds. A point must be faulted for 2 scans
before the panel initiates an alarm.
74-07111-000-D 1/96
Smoke Detectors
(73-07115-000) for a list
D2112/D2112E Installation Manual
See RELAYS in D2112/D2112E
Program Entry Guide to program
External Relay 1 for Ground
Start.
Keyswitch
Description
You can connect a momentary contact arming
station (keyswitch) to turn the D2112 on and off. The
keyswitch is connected to a point sensor loop (points
2 to 6 only, do not use points 7 and 8).
You can use the external relay outputs and D133
Relay Modules to activate arming status lights for
keyswitch arming stations. See the
D2112/D2112E Program Entry Guide
Programming
See the
POINT CODES Group
D2112E Program Entry Guide
programming for points used for keyswitches.
Installation
Connect the end-of-line resistor for the point at the
keyswitch so that the switch shorts the resistor when
it operates. An open on the circuit produces an
alarm if the area is armed and a trouble if it is
disarmed. See Figure 13.
COMMON
End of Line
Resistor
POINT INPUT
Figure 13: Keyswitch
Page 15
Relays
.
in the
D2112/
for the correct
Short and restoral
on circuit toggles
arming state.
Shorting and restoring the point sensor loop toggles
the system On and Off. All faulted points are
bypassed. See
D2112E Program Entry Guide
POINT CODES Group
.
in the
D2112/
Silencing the Bell
To silence the bell (stop Alarm output) if the system
is On (or Part On), operate the keyswitch to turn the
system Off. If the area is Off, operating the
keyswitch only silences the bell. It does not turn the
system On.
EasiKey Control
+
–
To 12VDC, Switched
parallel to door strike.
End of Line Resistor
Easikey
You can use a Radionics Easikey access system to
turn the system Off. Program the
to Easikey. See the
Guide
for instructions. You must use a 12VDC
D2112/D2112E Program Entry
option for the Easikey installation. See the
Installation and Operation Instructions
Keyswitch Keyswitch
Easikey
.
prompt
Connect the Easikey door controller to the panel
using a D133 Relay Module as shown in Figure 14.
Make certain to connect the common for the
Easikey's 12VDC power supply to terminal 10 on the
panel.
and listed by Underwriters’ Laboratories for
compatibility with the panel. These components
meet the basic system requirements for the
applicable standard.
The
System Wiring Diagram, Issue A
relationship between the panel and the accessory
components referred to in the
installation and operation instructions for each
component for detailed instructions.
references components evaluated
shows the
System Chart.
See the
Optional Compatible Equipment
You can use UL listed components that do not
require evaluation for electrical compatibility in many
applications when installed according to the
manufacturer’s instructions.
Burglary Applications
You can use UL listed burglary alarm sensors that
do not require evaluation for electrical compatibility
in burglary applications. In some cases you must
use a UL listed Radionics interface module in
conjunction with the sensors. Consult the individual
component specification and installation documents
to determine suitability.
In burglary applications with one 7.0Ah, 12 VDC
battery the panel supports an auxiliary output of
350mA and an alarm (bell) output of 1.5A configured
as necessary. For additional loadings refer to the
Current Rating Chart for Standby Battery
Calculations.
For commercial burglary installations use a
maximum of 45 seconds of entry delay and a
maximum of 60 seconds of exit delay.
Test weekly:
test. Configure the User System Test to test the
battery. See
D2112E Program Entry Guide
Fire Applications
You can use UL listed fire initiating devices not
requiring electrical compatibility evaluation in any
application. For example: four-wire smoke detectors,
heat detectors, waterflow switches, and manual pull
stations are suitable fire initiating devices. Consult
the individual component specification and
installation documents to determine suitability.
UL Standard 1023 requires a weekly
User Configuration
in the
D2112/
for instructions.
When using four-wire smoke detectors, install a
suitable power supervision unit according to the
manufacturer’s instructions. Use the D133 Relay
Module to provide reset capability.
In fire applications with one 7.0Ah, 12 VDC battery
the panel supports an auxiliary output of 140mA and
a bell output of 720mA configured as necessary. For
additional loadings refer to the
Current Rating Chart
for Standby Battery Calculations.
D2112 only:
compatible, and must be UL listed for use with the
D2112. See the Radionics Technogram
Detectors Compatible with the D2112
000), or you may contact the detector manufacturer.
Test weekly:
and combined fire/burglary systems weekly.
Configure the User System Test to test the battery.
See
User Configuration
Program Entry Guide
For all Burglary applications the panel must be
programmed to send a supervisory signal to the
central station a minimum of once every 24 hours.
Do not set or program an automatic telephone dialer
or similar device to place a call to a police station
number that is not specifically assigned by that
station for such service.
Sounding Device
The sounding device shall operate for at least four
minutes before an automatic cutoff for Household
Burglary applications and at least 15 minutes for
Commercial Burglary applications.
For all Commercial Burglary applications the system
must be programmed to sound the audible device
every time the system is armed.
Enclosures
The D2103 enclosure is suitable for Household Fire
and Burglary applications only.
Enclosure tamper protection causing an immediate
alarm signal is required for all burglary applications.
Radionics offers three optional enclosures.
The D8103 enclosure is suitable for residential fire
and/or burglary installations and commercial
applications that do not require attack resistance or
approval by Factory Mutual. (See the System
for acceptable applications.)
The D8108A is attack resistant. It is intended
primarily for UL commercial burglar alarm and
mercantile safe and vault applications requiring a
local bell. You can use the D8108A in any burglar
application where the D8103 or D8109 enclosure is
suitable. The D8108A is approved by Factory
Mutual, California State Fire Marshal, and the New
York City Materials and Equipment Acceptance
System.
The D8109 is normally used for fire alarm
applications. The D8109 is approved by Factory
Mutual, California State Fire Marshal, and the New
York City Materials and Equipment Acceptance
System.
Standby Battery Requirements
Household Burglary and Commercial Burglary
Four hours of standby battery capacity required.
Standby Battery Calculation for
Fire Alarm Applications
NFPA 72 Household Fire Warning Equipment
The NFPA 72 Household Fire Warning Equipment
Standard requires 24 hours of standby plus four
minutes (.067 hrs) of alarm operation at the end of
the 24 hour period.
You must use battery ampere hour (Ah) calculations
to verify compliance. The formula below includes a
10% contingency factor for depletion of battery
capacity with age.
NFPA 72 Ampere-Hour Calculation Formula
(Total B ___ x 24 Hrs) + (Total C ___ x .067 Hrs) +
(10% Contingency) = Total Ah required.
Total Ah requirements must not exceed Ah capacity
of batteries.
Current Rating Chart for Standby Battery Calculations
All currents are in milliamperes (1 ampere=1000 milliamperes).
AC Power OnAC Power OffIn Alarm
Normal CurrentMinimum CurrentMaximum Current
The D2112 and D2112E control panels are suitable
for Grade A Local Mercantile Premises Alarm
systems and Grade A Mercantile Safe and Vault
Alarm systems. For all local applications and
Grades, the model D8108A Attack Resistant
Enclosure and a UL listed sounding device are
required.
The D2112 and D2112E control panels are suitable
for Grade B when used with a UL listed local
sounding device. Suitable for Grade AA Central
Station Mercantile when used with model D8122
derived channel subscriber terminal unit.
74-07111-000-D 1/96
(Grade C)
Burglary Combined
4
NoNo
NoNo
Req.Req.
No
Opt.Opt.
Opt.
1+
Opt.
Opt.
Opt.
Optional
D2112/D2112E Installation Manual
Burglary
4
No
Opt.
1+
11
Opt.Opt.
Page 19
Proprietary Burglary
Local Burglary
D2112 and D2112E not listed for these applications
4
4
No
No
Req. =Required for this application
Req.
No
Opt.
Opt.
Local and Central Station
Local Fire / Burglary
72
Local Fire
Combined
72
Fire Combined
71, 727171, 72
Central Station Fire /
Local and Central Station
Fire / Burglary (Grade C)
Key
No =Not acceptable for this application
Opt. =Optional for this application
1+ =One or more required for this
application. Consult the appropriate
standard.
Central Station Fire
Burglary (Grade C)
71
2+ =Two or more required for this
application. Consult the appropriate
standard.
1+
1• =D2112 Only: At least one detector
required. You can substitute other
2-wire detectors listed for use with
the D2112. You could use the
◆
◆◆
D262 with the D270 four-wire base
or other manufacturers' four wire
detectors. You must use a listed
1
1
power supervision relay with four
wire detectors.
◆
=Listed bell (siren) housing required
for burglary alarm bell or siren.
=(Empty Box) Not used for this
application.
The D2112 and D2112E control panels are suitable
for Grade A Mercantile Premises and Mercantile
Safe and Vault alarm systems. Suitable for Grade
AA Police Station Mercantile Premises and
Mercantile Safe and Vault systems when model
D8122 derived channel subscriber terminal unit is
used. For all Police Station Connect applications the
model D8108A Attack Resistant Enclosure and a UL
listed sounding device are required.
The D2112 and D2112E control panels are suitable
for Grade B Proprietary Burglary applications when
used with a UL listed local sounding device and
Grade BB proprietary Burglar applications when
installed with a model D8122 derived channel
subscriber terminal unit.
NOT Supervised,
Normally Closed.
Typical Initiating
Devices are Door
Contacts, Floor
Mats, Motion
Sensors, T amper
Switches, etc. All
devices open on
alarm.
D164 Phone
Cord to
RJ31X for
Phone Line
P
PSP
PP
S
D2112E
Listed Audible
Signaling Device
Rated At 10.2
TO 13.9 VDC
(Do NOT Use
Vibrating Type
Horns)
Required for
Fire and
Combined
Fire/Burglary.
Optional for
other.
-++
D126
Battery
12V 7Ah
-
12V 4Ah
D1240
Battery
16 VAC
25 VA
60 HZ
Transformer
Arming Station
D202
Up to
Four
P
D1625
P
P
P
S
P
S
D8004
Transformer
Enclosure
Supervised with 1k Ω
EOL Resistor.
Typical Initiating
Devices are Door
Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Detectors, etc.
• 16.5 VAC 25 VA class 2 plug-in transformer
(D1625)
Secondary Power Supply
• 12 VDC 4.0 Ah sealed lead acid rechargeable
battery. 7.0 Ah battery required for Fire and
combined Fire/Burglary systems.
Auxiliary Power Output
• 350mA maximum at 10.2 VDC to 13.9 VDC for
devices powered at terminal 9 (140mA for Fire
and combined Fire/Burglary systems) .
Alarm Power Output
• 1.5 A maximum at 10.2 VDC to 13.9 VDC output.
Output may be steady or pulsed depending on
programming.
• Fire and Fire/Burglary Systems
To comply with UL 985 listing standards for
household fire alarm systems (effective March 1,
1989), the total combined continuous and alarm
current draw for the system during alarmconditions must be limited to 860 mA provided
by the primary power supply (rectified AC).
Minimum Operating Voltage
• 10.2 VDC
Telephone Connection
• RJ31X or RJ38X jack interfaced with D164 phone
cord.
Environmental
• Temperature: 32°-122°F (0°-50°C)
• Relative Humidity:5-85% at 86°F (30°C) noncondensing
1,2AC InputConnect 16.5 VAC, 25 VA transformer for primary power
source.
3Earth GroundConnect to earth ground. A cold water pipe or grounding rod is
preferred. Do not connect to telephone or electrical ground.
4Battery PositiveConnect Positive terminal of 4.0 to 7.0 Ah battery to this
terminal.
5Battery NegativeConnect Negative terminal of 4.0 to 7.0 Ah battery to this
terminal.
6Alarm Output Positive Supplies 1.5 Amps at 10.2 to 13.9 VDC for alarm output. This
terminal provides a constant output. Negative is switched.
7Alarm Output NegativeNegative terminal for alarm output. This terminal switches for
pulsed or steady alarm output.
8Keypad DataData for Keypads
9Auxiliary Power PositiveSupplies 350mA at 10.2 to 13.9 VDC for auxiliary power,
keypads, and relay outputs .
10CommonCommon for Auxiliary Power and Relay Drivers
11External Relay 1Connect D133 Relay for Form C Dry Contact
12External Relay 2Connect D133 Relay for Form C Dry Contact
13D2112 Positive Point 1
Not used on D2112E
14D2112: Negative Point 1
D2112E: Input Point 1
D2112: Positive power for Point 1. Switched for sensor reset.
Use for approved two wire smoke or glass break detectors.
D2112: Negative power for Point 1
D2112E: Input for Point 1
15Common Common for Points 1 and 2
16Input Point 2Input for Point 2
17Input Point 3Input for Point 3
18CommonCommon for Points 3 and 4
19Input Point 4Input for Point 4
20Input Point 5 Positve for Point 5
21CommonCommon for Points 5 and 6
22Input Point 6 Input for Point 6
23D2112: Point 7
D2112E: Not Used
D2112: Input for Point 7. No EOL Resistor
D2112E: Not Used
24CommonCommon for Points 7 and 8
25D2112: Point 8
D2112E: Not Used
D2112: Input for Point 8. No EOL Resistor
D2112E: Not Used
26T1Tip of phone line to premises phone
27TTip of incoming phone line
28RRing of incoming phone line
29R1Ring of phone line to premises phone