Radionics D2112, D2112E Installation Manual

D2112/D2112E Control/Communicator
Installation Manual
74-07111-000-D 1/96
D2112/D2112E Installation Manual
Page 1
© 1995 Radionics

Notice

If a discrepancy is found in this documentation, please mail a photocopy of the corrected material to:
Technical Communications c/o Radionics, Inc. 1800 Abbott Street P.O. Box 80012 Salinas, CA 93912-0012
© 1995 Radionics, Inc., Salinas, CA, U.S.A.
All rights reserved.

Revision Marking

In this version of the Installation Manual, we added information about the D2112E Control/Communicator. New information about the D2112E appears throughout the manual. We marked changes significant to the design and operation of the panel with a vertical line in the margin. An example of the line is shown in the margin to the left of this paragraph.

FCC Notices

Part 15
This equipment generates and uses radio frequency energy. If not installed and used in accordance with the manufacturer’s instructions, it may cause interference to radio and television reception. It has been tested and found to comply with the specifications in Part 15 of FCC rules for Class B Computing Devices.
If this equipment causes interference to radio or television reception, which can be determined by turning the equipment on and off, the installer is encouraged to correct the interference by one or more of the following measures: 1) Reorient the antenna of the radio/television. 2) Connect the AC transformer to a different outlet so the control panel and radio/television are on different branch circuits. 3) Relocate the control panel with respect to the radio/ television.
If necessary, the installer should consult an experienced radio/television technician for additional suggestions, or send for the “Interference Handbook” prepared by the Federal Communications Commission. This booklet is available from the U.S. Government Printing Office, Washington D.C. 20402, stock number 004-000-00450-7.
Part 68
This equipment complies with Part 68 of FCC rules. A
D2112/D2112E Installation Manual
74-07111-000-D 196 © 1995 Radionics
label contains, among other information, the FCC registration number and ringer equivalence number (REN).
Radionics registered the D2112 Control/ Communicator for connection to the public telephone network using an RJ38X or RJ31X jack.
Use the ringer equivalence number (REN) to determine the number of devices you can connect to the telephone line. Excessive RENs on the telephone line may result in devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5). Contact the telephone company to determine the maximum REN for the calling area.
If the D2112 Control/Communicator causes harm to the telephone network, the telephone company will notify you in advance. If advance notice isn’t practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the D2112. If this happens, the telephone company will provide advance notice in order for you to make the necessary modifications to maintain uninterrupted service.
If you experience trouble with the D2112 Control/ Communicator, please contact Radionics Customer Service for repair and/or warranty information. If the trouble is causing harm to the telephone network, the telephone company may request that you remove the D2112 from the network until the problem is resolved. User repairs must not be made. Doing so voids the user’s warranty.
Do not install the D2112 on public coin service provided by the telephone company. Connection to Party Line service is subject to state tariffs (Contact your state public utilities commission for information.). You must supply the local telephone company with the following information at their request.
The line you are going to connect the panel to
Make (Radionics), model (D2112), and serial
number of the panel
FCC registration number and ringer equivalence for the panel.
FCC Registration Number: AJ9USA-20644-AL-E Ringer Equivalence: 0.2B Service Center in USA: Radionics, Inc.
1800 Abbott Street P.O. Box 80012 Salinas, CA 93912-0012
(800) 538-5807
Page 2

Table of Contents

Notice ............................................................... 2
FCC Notices .....................................................2
Introduction ........................................................... 4
D2112/D2112E Control/Communicator ............ 4
Ordered Separately ..........................................4
Enclosure Options ............................................4
Listings and Approvals ..................................... 4
Getting Started ...................................................... 4
Before You Begin ............................................. 4
Mount the Enclosure......................................... 5
Run the Premises Wiring.................................. 5
Connect Earth Ground
Terminal 3......................................................... 6
Charge the Battery as You Work ......................... 6
Lock the Standby Switch .................................. 6
Transformer
Terminals 1 and 2.............................................6
Battery
Terminals 4 and 5.............................................6
Install Detection Devices, Keypads, and Bells... 7
No Connections to the Panel Yet ..................... 7
Number of Sensors........................................... 7
Continue Connections
to the Panel............................................................ 7
Power Down First .............................................7
Alarm Output
Terminals 6 and 7.............................................7
Keypads
Terminals 8, 9, and 10......................................8
Auxiliary Power
Terminal 9......................................................... 8
Testing and Replacing D2112E Fuses ............. 9
External Relays
Terminals 11 and 12......................................... 9
Connect the Points ............................................. 10
Point 1 on the D2112 Only
Terminals 13 and 14....................................... 10
Points 2 to 6 (1 to 6 on D2112E)
Terminals 15 to 22 (14 to 22 on D2112E) ...... 10
Points 7 and 8 on the D2112 Only
Terminals 23 to 25 ..........................................10
Program the Panel.......................................... 12
Make the Telephone Connections ..................... 12
Power Up........................................................12
Fill out the Point Chart .................................... 12
Unlock the Standby Switch ............................. 12
Test the System.............................................. 13
Detailed Panel Description................................. 13
Primary (AC) Power Circuit ............................ 13
Secondary (DC) Power................................... 13
Power Outputs................................................ 14
Telephone....................................................... 14
Points.............................................................. 15
Keyswitch ....................................................... 15
Installation Guide for UL Applications.............. 17
Introduction .....................................................17
Optional Compatible Equipment..................... 17
Current Rating Chart for Standby Battery Calcu-
lations................................................................... 18
Standby Battery Requirements....................... 18
System Chart ....................................................... 19
System Wiring Diagram, Issue A ....................... 20
Specifications...................................................... 21
D2112/D2112E Terminal Quick Reference ........ 22
74-07111-000-D 1/96
D2112/D2112E Installation Manual
Page 3
© 1995 Radionics

Introduction

D2112/D2112E Control/Communicator

The Radionics D2112 and D2112E Control/ Communicators are shipped pre-assembled from the factory. You should receive the following parts with your D2112 or D2112E panel.

Panel Assembly

• D2112 or D2112E Panel
• D2103 Enclosure
• D1625 Transformer
D2112 Only: Smoke Detectors Compatible with the D2112 Technogram

Hardware Pack

D2112 only:
Point 1 (30-01098-102)
• Five 1k end-of-line resistors for Points 2 to 6 (six with D2112E) (15-03130-008)
• Two #6 by 3/8" sheet metal screws to secure the D2103 Enclosure cover (60-03977-006)
One 2.0k end-of-line resistor for

Ordered Separately

Literature Pack

D2112/D2112E Installation Manual
(74-07111-000)
D2112/D2112E Program Entry Guide
(74-07112-000)
D2112/D2112E Program Record Sheet
(74-07114-000)

D202 Keypad

The D2112C package includes one D202 Keypad. Each D202 includes the following.
D202 Keypad
Installation Sheet
User's Cards
Key Labels
Security System User's Guide
(74-07117-000)
*
Three-wire cable assembly

Battery

Order a D1240 Battery (12 V 4.0Ah) to complete a basic D2112 or D2112E installation.
Order a D126 Battery (12 V 7.0Ah) for fire and combined fire/burglary systems.
(74-07090-000)
(74-07092-000)
(73-07115-000)
(74-07118-000)
(15-07032-000)

Enclosure Options

The D2112 and D2112E are shipped in the D2103 enclosure. If you want to mount the D2112 or D2112E in one of the optional enclosures listed below, order the D2112M or D2112EM, and the enclosure of your choice.
• D8103 Universal Enclosure
• D8108A Attack Resistant Enclosure
• D8109 Fire Rated Enclosure

Listings and Approvals

Fire
Underwriters Laboratories lists the D2112 and D2112E Control/Communicators as Signal System Control Units for NFPA 72 Household Fire Warning.
The D2112 and D2112E have been submitted for evaluation to:
CSFM 7167-0801:143 (Residential) UL 985 Household Fire Warning
ULC 540 Household Fire Warning and Burglar Alarm
Control Units and Accessories
Burglary
UL 1023 Household Burglar Alarm UL 365 Police Station Connect UL 609 Local Burglar Alarm UL 1076 Proprietary Burglary Alarm UL 1610 Central Station ULC 303 Burglar Alarm System Control Units, Local
Type
ULC 304 Burglar Alarm System Control Units,
Monitoring Station Type, Commercial Premises

Getting Started

Before You Begin

Radionics recommends you review this manual before you begin the installation to determine the hardware and wiring requirements for the features you want to use.
Have the following additional documents handy as you read through the manual:
D2112/D2112E Program Record Sheet
D2112/D2112E Program Entry Guide
Security System User's Guide
D2112/D2112E Installation Manual
74-07111-000-D 196 © 1995 Radionics
Page 4

Mount the Enclosure

Lift the bottom of the enclosure cover and remove it from the base. See Figure 1.
Mount the base in the desired location. Leave a 2" clearance at the top of enclosure so that you can easily install the cover.

Run the Premises Wiring

Run the necessary wiring throughout the premises and pull the wires into the enclosure. Do not make any connections yet.

Wire Length

The length of the wire run for points is limited only by the resistance on the loop and potential EMI (Electro-Magnetic Interference) problems.
On the D2112, wire resistance on the Point 1 sensor loop must be less than 50. Measure the wire resistance before installing smoke detectors. Short the end-of-line resistor before metering the wire.
Resistance on the sensor loops for Points 2 to 8 (1 to 6 on D2112E) must be less than 100 with the end of line resistor shorted and the detection devices connected.
Maximum wire length for the transformer is 50 feet (18 AWG, stranded).
Maximum wire length for all keypads combined is 500 feet (22 AWG).

EMI (Electro Magnetic Interference)

AC wiring can induce EMI (both noise and low level voltage) into adjacent wiring. Run phone and sensor loop wiring away from AC conductors, including the transformer wire. Run keypad wiring away from AC and phone wiring.
EMI may also occur if you install the panel or run system wires near the following:
• Computer network system
• Fluorescent fixtures
• Telephone cabling
• Ham radio transmitter site
• Heavy machinery and motors
• High voltage electrical equipment
• PBX telephone system
• Public service (police, fire departments, etc.) using radio communications
• Radio station transmitter site, or other broad­cast station equipment
• Welding shop
If you think that EMI may be a problem, use shielded cable. The drain wire for the shielded cable must have continuity from terminal 3 on the panel to the end of the wire run.
If continuity is not maintained, the shielded cable may aggravate potential noise problems rather than eliminate them. If you cut the drain wire to install devices be certain to splice it together. Solder and tape all splices.
Cover
Base
Swing cover out from base at bottom. Lift cover clear of base.
74-07111-000-D 1/96
Connecting the drain wire to ground at other than terminal 3 may also produce problems.
Mount base to wall. Leave at least 2 inches clearance at top to install and remover cover.
Mounting locations
for optional
D133 Relay Modules.

Figure 1: D2103 Enclosure

D2112/D2112E Installation Manual
Page 5
Base
Slide cover tab into slot on base for convenient view of Wiring Diagram during installation.
Label showing Wiring Diagram
Cover
© 1995 Radionics
Connect Earth Ground Terminal 3
To help prevent damage from electrostatic charges or other transient electrical surges, connect the panel to earth ground at terminal 3 before making any other connections.
A grounding rod or cold water pipe are recommended earth ground references.
Radionics does not recommend a telephone or electrical ground for the earth ground connection. Use 18 AWG wire maximum under the terminal. Use a lug or splice for larger wire.
Do not connect any other panel terminals to earth ground. The panels common terminals and terminal 3, earth ground, are electrically isolated.

Charge the Battery as You Work

Lock the Standby Switch

Locking the pin in the standby position allows you to charge the battery as you install the detection devices and keypads. Lock the pin down now. See Figure 2.
With the Standby Switch locked down, the panel deactivates the external relay outputs, suppresses reports, and disables all arming functions.
Lock the Standby Switch down to program the panel locally, from the keypad or the D5200.
Releasing the Standby Switch from the closed position resets the panel. The panel resets all its timers and counters, and clears all buffers.
Transformer Terminals 1 and 2
Connect the transformer to terminals 1 and 2 on the panel before plugging it into the power source.
Use 18 AWG wire to connect the transformer to the panel. Wire length should be kept as short as possible. Maximum length is 50 feet.
Never share the transformer with other equipment:
Foreign grounds on the AC input
damage the panel's power circuit.
Battery Terminals 4 and 5
Place the battery upright in the base of the enclosure. First connect the bare end of the black battery lead to terminal 5 on the panel. Then plug the other end to the negative (-) side of the battery.
Next connect the bare end of the red battery lead to terminal 4 on the panel. Then plug the other end to the positive (+) side of the battery.
D126 Battery required for fire and combined fire/ burglary systems:
requirements, use the Radionics D126, 12 V 7.0Ah battery for fire and combined fire/burglary systems.
In order to meet standby battery
Standby Switch
Locked (Closed)
1511 12 16 17
1413
10
9 8 7 6 5 4 3 2 1
Standby Switch
Normal (Open)
20
1918
21 22 23 24 25
27
28
26
29

Figure 2: Standby Switch

D2112/D2112E Installation Manual
74-07111-000-D 196 © 1995 Radionics
Page 6

Install Detection Devices,

Keypads, and Bells

No Connections to the Panel Yet

Install and wire detection devices, keypads, and indicating devices (bells, sirens, or strobes for example) at their locations throughout the premises. DO NOT make the connections at the panel end of the wiring yet.

Number of Sensors

When using the D2112's Point 1 as a fire point, the number of devices you can connect to it's sensor loop is limited. See Page 10.
The number of sensors you can connect to the sensor loops for points 2 to 8 (1 to 6 on D2112E) is limited only by the resistance on the loop. Resistance must be less than 100 with the detection devices connected.
Point 1 on the D2112 Only
on

Continue Connections

to the Panel

Power Down First

Unplug the transformer and disconnect the battery to make the remaining connections to the panel.
Available Power
The panel combines power produced by the power supply with power from the secondary power source (the battery) to produce a total of 1.5A of power at terminals 6 and 7.
D126 Battery required for fire and combined fire/ burglary systems:
requirements, use the Radionics D126, 12 V 7.0Ah battery for fire and combined fire/burglary systems.
Power restricted for fire and combined fire/ burglary systems:
Formula
available for fire and combined fire/burglary systems.
Fire System Power Formula
To calculate the current available at terminals 6 and 7 for fire and combined fire/burglary systems:
below to calculate the alarm current
1. Add together the current draws for all devices connected to terminal 9. This total is current required for the Normal Standby Condition (NSC). This total must be less than 140mA.
2. Subtract the NSC current required calculated in step 1 from the Primary Alarm Current, 860mA. The difference is the Alarm Current Available for terminals 6 and 7.
In order to meet standby battery
Use the
Fire System Power
alarm
Alarm Output Terminals 6 and 7
Terminals 6 and 7 provide a 10.2 VDC to 13.9 VDC output when activated.
steady positive output.
pulsed or steady negative output as programmed.
There is always power at Terminal 6:
sends a trouble report if terminal 6 is shorted to ground. The D2112 sends a trouble report if terminal 6 is shorted to terminal 7 while the alarm output is activated.
Use this power for bells, siren drivers, piezo fire sounders, electronic horns, or other devices.
74-07111-000-D 1/96
Terminal 6 provides a
Terminal 7 provides a
The D2112
D2112/D2112E Installation Manual
In formula format:
Primary Alarm Current – NSC current required = Alarm Current Available
Page 7
© 1995 Radionics
Keypads Terminals 8, 9, and 10
You can connect up to four keypads to the panel. The installation sheet packaged with each keypad
contains mounting instructions. Wire keypads to the panel in parallel as shown in Figure 3.
You must use a minimum of five feet of wire (22 AWG) when connecting the keypad to the panel.
A short on terminal 9 within five feet of the panel prevents the panel from operating correctly.
Maximum wire length for all keypads combined is 500 feet (22 AWG).
Auxiliary Power Terminal 9
The continuous current draw for powered devices connected to terminal 9, including keypads, must not exceed 350mA (140mA for fire and combined fire/burglary systems). Devices powered from this output must operate over a range of 10.2 VDC to
13.9 VDC.
You must use a minimum of five feet (22 AWG) of wire when connecting devices mounted outside the enclosure to terminal 9.
within five feet of the panel prevents the panel from operating correctly.
A short on terminal 9
Extra power needed for more keypads:
Keypad draws 45mA (125mA Alarm). Review
Outputs
output requirements for your system. Instructions for using stand alone power supplies are included.
on page 14 to determine the total power
The D202
Power
Keypad
Connect up to
four in parallel.
Checking Continuous Current Draw
The panel allows you to check current draw using the keypad. For more information about this and other keypad diagnostic features, see the
Keypad Diagnostics
manual (74-07113-000).
D2112
11 12
1413
Black
(Common)
10
Green (Data)
74-07111-000-D 196 © 1995 Radionics
Red
(+12VDC)

Figure 3: Keypad Wiring

D2112/D2112E Installation Manual
9 8
Page 8

Testing and Replacing D2112E Fuses

The D2112E's Aux Power and Bell outputs are protected by 2 Amp fast blow fuses. The fuses are 5 mm x 20 mm, 2 Amp Fast Blow (Radionics Part # 57-03570-008). To test the fuses, use a Volt/Ohm meter to follow these steps:
1. Remove the fuse from the socket.
4 3 2 1
2. Switch the meter to measure Ohms.
3. Attach the meter leads to each side of the fuse.
4. If the meter does not change when you connect the leads to the fuse, the fuse is open (blown). Replace the blown fuse with a 5 mm x 20 mm, 2 Amp Fast Blow fuse.
5. If the meter measures 0 Ohms, the fuse is closed (normal), and does not need to be replaced.
External Relays Terminals 11 and 12
You can program terminals 11 and 12 to provide outputs for two external relays. Review the
Group in the D2112/D2112E Program Entry Guide
for a description of the relay functions available. Connect a D133 Relay Module for each of the
external relay outputs you intend to use. Figure 5 shows the connections.
RELAYS
Aux Power Fuse
2 Amp Fast Blow

Figure 4: D2112E Fuse Locations

External Relay 1
D133
Relay Module
Alarm Output Fuse
2 Amp Fast Blow
N/O 1 (Closes to COMM1 when relay is activated.) COMM1 (Common) N/C 1 (Opens from COMM1 when relay is activated.) X1- (Connect to terminal 11 for External Relay 1) X1+ (Connect to terminal 9.)
Warning:
Install D133 modules connected to terminals 11 and 12 in the enclosure with the panel as shown in Figure 1. Do not connect wiring for external devices directly to terminals 11 or 12.
D2112/D2112E Installation Manual
74-07111-000-D 1/96
Page 9
External Relay 2
D133
Relay Module
N/O 1 COMM1 N/C 1 X1- ( Connect to terminal 12
for External Relay 2) X1+
15 16 17
11 12
10
9 8 7
1413

Figure 5: External Relay Wiring

© 1995 Radionics
20
1918

Connect the Points

Point 1 on the D2112 Only Terminals 13 and 14
Point 1 on the D2112 is a powered, supervised point.
The panel monitors the Point 1 sensor loop for normal, shorted, or open conditions. Programming determines how the panel responds to those conditions. See the
Guide
.
Terminal 13 provides positive (+) voltage to detection devices. Terminal 14, the loop return (-), is isolated from earth ground.
The keypad Reset function interrupts power to this sensor loop to reset smoke or glass break detectors.
Use a 2.0k end of line resistor for point 1 on the D2112. Figure 6 shows point wiring.
Connecting Two-Wire Smoke Detectors to Point 1 on D2112 Only:
Connect up to five Radionics D262 two-wire smoke detectors to point 1 on the D2112. Refer to the
Technogram, Smoke Detectors Compatible with the D2112
(73-07115-000), for a complete list of
detectors compatible with the D2112.
Four-Wire Smoke Detectors
Connect any number (limited by available power and the Authority Having Jurisdiction) of 12 VDC four­wire smoke detectors to any supervised point. Install a suitable power supervision device according the manufacturer's instructions. Route the power for the detectors through a D133 Relay Module. The relay module must be connected to one of the panel's external relay outputs programmed for the reset function. See
Program Entry Guide
Heat Detectors and Other Dry Contact Initiating Devices
Connect any number (limited by the Authority Having Jurisdiction).
Burglar Devices
Connect any number (limited by available power) of burglar devices to any point. Do not combine fire detection and burglar devices.
D2112/D2112E Program Entry
RELAYS
in the
D2112/D2112E
for programming instructions.

Points 2 to 6 (1 to 6 on D2112E) Terminals 15 to 22 (14 to 22 on D2112E)

Points 2 to 6 (1 to 6 on D2112E) are supervised, non-powered points.
The panel monitors sensor loops for normal, shorted, or open conditions. Programming for each point determines how the panel responds to those conditions. See the
Guide
.
Terminate each sensor loop with a 1.0k end of line resistor. Figure 6 shows point wiring.
Four-Wire Smoke Detectors
Connect any number (limited by available power and the Authority Having Jurisdiction) of 12 VDC four­wire smoke detectors to any supervised point. Install a suitable power supervision device according the manufacturer's instructions. Route the power for the detectors through a D133 Relay Module. The relay module must be connected to one of the panel's external relay outputs programmed for the reset function. See
Program Entry Guide
Heat Detectors and Other Dry Contact Initiating Devices
Connect any number (limited by the Authority Having Jurisdiction).
Burglar Devices
Connect any number (limited by available power) of burglar devices to any point. Do not combine fire detection and burglar devices.
D2112/D2112E Program Entry
RELAYS
in the
D2112/D2112E
for programming instructions.

Points 7 and 8 on the D2112 Only Terminals 23 to 25

Points 7 and 8 are non-powered points that are not supervised with an end of line resistor.
The D2112 monitors the sensor loops for Points 7 and 8 for normal (closed) and open conditions. Programming determines how the panel responds to those conditions. See the
Entry Guide
. Figure 6 shows point wiring.
D2112/D2112E Program
D2112/D2112E Installation Manual
74-07111-000-D 196 © 1995 Radionics
Page 10
D2112
Powered Sensor Loop
suitable for
Two Wire Smoke
Detectors
6.8 K Resistor
2.0
required at End of Line.
For compatible smoke
detectors see
RPN 73-07115-000.
11 12 1413
Point 1
s
s
Point
1
Points 2 to 6
Supervised Points
Open 8.9 - 13.9VDC
Normal 2.5 - 8.5VDC Short 0.0 - 2.0VDC
1.0 K Resistor
Required at End of Line
15 16 17
Point 2Point 3Point 4Point
20
Points 7 & 8
Unsupervised Points Open 2.4 - 13.9VDC
Normal (Closed)
0.0 - 1.4VDC
No End of Line Resistor
21 221918
Point
5
23 24 25
Point
6
7
Point
8
NOT
USED
11 12 14
13
Point
D2112E
Open 8.9 - 13.9VDC
Normal 2.5 - 8.5VDC Short 0.0 - 2.0VDC
15 16 17
Point
1

Figure 6: Points

Six Supervised Points
1.0 K Resistor
Required at End of Line
20
Point 3Point 4Point 5Point
2
NOT
USED
21 221918
6
2423 25
74-07111-000-D 1/96
D2112/D2112E Installation Manual
Page 11
© 1995 Radionics
11 12
9
10
1
25
26
27
28
29

Make the Telephone Connections

Phone Jack

To prevent jamming of reports, wire the RJ31X jack before the in-house phone system to support line seizure. See Figure 7. Line seizure provides for a temporary interruption of normal phone usage while the communicator transmits data.

Unlock the Standby Switch

When you're finished programming move the Standby Switch to the normal position. See Figure 9. The panel sends a RE-BOOT report to the receiver and the panel returns to the disarmed state. If you programmed for test reports and left the hours and minutes to next report prompts at 0 (zero), the panel sends a test report with the RE-BOOT report.
After installation, confirm that the panel seizes the line, acquires dial tone, reports correctly to the receiver, and releases the phone line to the in­house phone system.
PREMISES PHONE
FULL MODULAR PHONE JACK
R1
T1
1 2 3 4 5 6 7 8
RJ31X MODULE
R T
INCOMING TELCO LINE

Figure 7: RJ31X Phone Jack

Phone Cord

Connect the flying leads of the D164 Phone Cord to the panel as shown in Figure 8. Connect the modular end to the RJ31X jack.
To RJ31X Phone Jack
D164
Phone Cord
Black, Yellow,
Orange, and
Blue not used.
Brown
T1 R R1T
Green
Red
Gray
10
9 8 7 6 5 4 3 2 1
All Non-Fire “Points to Watch” become selected:
After the Standby Switch is unlocked, all non-fire points on the system become selected “Points to Watch.” See the D202 Keypad for more information.
RAM II ResetBye does not disarm the panel:
you unlock the standby switch, the panel returns to a disarmed state. Using RAM II does not affect the armed state of the panel.

Fill out the Point Chart

Radionics recommends you fill out the
Standby Switch
Locked (Closed)
1511 12 16 17
1413
20
21 22 23 24 25
1918
Standby Switch
Normal (Open)
26

Figure 9: Standby Switch

Watch-Test
User’s Card on the
ResetBye
27
28
29
After
, however,
Point Chart
on the Installation Label located inside the D2103
Figure 8: Phone Cord
enclosure cover.

Power Up

Connect the battery and then plug in the transformer.
Leave the Standby Switch locked down for now.

Program the Panel

Use the D202 Keypad, the Radionics D5200 Programmer, or a remote programmer to program the panel. See the
Guide
for programming options and keypad
programming instructions.
If you're programming from the keypad or using the D5200, make sure the Standby Switch is locked down. See Figure 9.
If you're using the D5200, Figure 10 shows the location of the programming jack. See the
Programmer Operation Manual
using the programmer.
74-07111-000-D 196 © 1995 Radionics
D2112/D2112E Program Entry
D5200
for instructions on
D2112/D2112E Installation Manual
You must fill out the point chart if you programmed Point 1 for Fire with Verification (Digit 1 = 2).
D2112E Program Entry Guide
See
POINT CODES
in the
for more information.
Use the program record sheet to gather the information you need to fill out the point chart.
Local Programmer Connect
Lock standby switch to program.

Figure 10: Programmer Jack

Page 12
D2112/

Test the System

After finishing installation and programming, make a complete functional test of the system. Test the panel and all devices for proper operation. Test after you first program the panel and after any subsequent programming session.
Clear after test:
report buffer, close the Standby Switch for two seconds and then release it. The panel returns to service in the disarmed state.
To clear the alarm memory and

Detailed Panel Description

Primary (AC) Power Circuit

A 16.5 VAC, 25VA transformer (Radionics model D1625) is the primary power source for the panel.
The AC power circuit provides 1.0 Amps of rectified DC power. The panel reserves 140mA of this power for internal operations and 350mA for continuously powered devices. Under alarm conditions 860mA of power is available for continuously powered and alarm indicating devices combined.
Battery Replacement
Radionics recommends battery replacement every three to five years under normal use. Exceeding the maximum output ratings, or installing the transformer in an outlet that is routinely switched off, causes heavy discharges. Routine heavy discharges can lead to premature battery failure.
D135A Prevents Deep Discharge:
Battery Cutoff Module protects the battery from deep discharge during extended power outages. Deep discharge can cause permanent battery damage.
Battery Supervision
When the battery drops to 12.1 VDC the OK light on the keypad winks, indicating a trouble condition. The panel transmits a BATTERY LOW report.
When battery voltage returns to 13.0 VDC and there is AC power at terminals 1 and 2, the OK LIGHT at the keypad stays on steady. The panel transmits a BATTERY RESTORAL report.
Investigate low battery reports right away
If primary (AC) power is off and the discharge continues, the panel becomes inoperative when the battery voltage drops below 10.2 VDC.
The D135A Low
:
Transient suppressors and spark gaps protect the circuit from power surges. This protection relies on the ground connection at terminal 3. Make sure you connect terminal 3 to a proper ground.
AC Power Failure
The panel indicates an AC power failure when power at terminals 1 and 2 is missing for 60 seconds. The
AC Fail Buzz/Rpt AC Fail Buzz/Rpt
response to detected AC failure. The panel indicates an AC power restoral 60 seconds after power restores to terminals 1 and 2.
program item sets the panels

Secondary (DC) Power

A 12V, 4.0 Ah sealed lead-acid rechargeable battery (Radionics D1240) supplies secondary power for auxiliary and alarm outputs. The battery also powers the system during interruptions in primary (AC) power.
Lead Acid Batteries Only: The panel charging circuit is only calibrated for lead-acid batteries. Do not use gel-cell or nicad batteries.
Larger Battery Increases Backup Time: To increase battery backup time, connect a larger capacity battery, up to 7 Ah (Radionics D126).
Battery Charging Circuit Float Charge
The float voltage for the battery charging circuit is
13.9 VDC. Deduct any continuous load for devices connected to the panel from 860mA to find the maximum current available for charging. At 13.9 VDC the battery is fully charged and is maintained with a trickle charge of approximately 5mA.
Battery Discharge/Recharge Schedule (No AC Power)
Discharge Cycle
AC OFF OK light on keypad begins winking
AC Fail reports if programmed
13.9 VDC Charging float level
12.1 VDC Low Battery reports if programmed
10.2 VDC Panel shuts down below 10.2 VDC
Recharge Cycle
AC ON Panel restarts, battery charging
begins, AC restoral report sent
13.0 VDC Battery restoral reports sent, OK light on steady
13.9 VDC Battery float charged
74-07111-000-D 1/96
D2112/D2112E Installation Manual
Page 13
© 1995 Radionics

Power Outputs

D2112 Circuit Protection
Two self-resetting protection devices protect the panel from short circuits on both the auxiliary and alarm power outputs.
D2112E Circuit Protection
Two fuses protect the panel from short circuits on both the auxiliary and alarm power outputs.
D2112 bell circuit protection:
power output while the bell is ringing disables the alarm power output until the output times out or you perform a panel reset.
Reports
The panel transmits a trouble Point 99 report when there is a short on the alarm output, terminals 6 and 7, or when the fuse is open. The panel transmits a trouble Point 98 report when Auxiliary Power, terminal 9, is shorted, or when the fuse is open.
Extra Power for Keypad or Other Powered Devices
The D202 Keypad draws 45mA (125mA in alarm). You may need to add one or more D8132 Battery
Charger/Power Supply Modules for the number of keypads you want to use. Figure 11 shows the D8132 powering keypads in a stand-alone configuration.
For UL certificated accounts use a UL listed power supply. The D8132 is not UL listed as a stand-alone power supply.
D2112 and D8132 (or other power supply) must share COMMON:
Note that Figure 11 shows the common from the D8132 module connected to both the keypads' common and the terminal 10 on the panel.
A short on alarm
A stand-alone power supply powering any device connected to the panel must also be connected to terminal 10 on the panel. Do not connect the stand­alone power supply to earth ground.

Telephone

Dialing Format
You can program the panel to use DTMF or pulse dialing. See
D2112E Program Entry Guide
Communication Failure
After 5 attempts to reach the receiver (10 attempts if two phone number are programmed) the panel goes into communication failure. The panel clears any reports in its phone buffer. The panel sounds a tone at the keypad and winks the OK light.
Pressing the Clear key silences the tone. When communication restores (a report is acknowledged by the receiver), the OK light restores.
Ground Start
Some telephone systems require a momentary ground input to initiate dial tone. To interface with a ground start system, connect a D133 relay as shown in Figure 12.
See
RELAYS Group
Entry Guide
external relay output for Ground Start. Terminal 3 on the panel must be connected to an
earth ground reference.
Warning:
systems for fire or combined fire burglary systems.
Phone Parameters
in the
D2112/
.
in the
D2112/D2112E Program
for instructions on programming the
You cannot use ground start phone
D8132
Battery Charger Module
(Stand-Alone Power Supply
Configuration)
+12VDC Common
Red
(+12VDC)

Figure 11: Power for Keypads

D2112/D2112E Installation Manual
74-07111-000-D 196 © 1995 Radionics
Keypad
Connect up to
four in parallel.
Page 14
Green (Data)
Keypad
Connect up to
four in parallel.
Black
(Common)
11 12
13
10
9 8 7 6
11 12
D133
Relay Module
15 16 17
1413
N/O 1 COMM1 N/C 1 X1- ( Connect to terminal 11
for External Relay 1) X1+
1918
Phone Cord
20
21 22 23 24 25
D164
To RJ31X Phone Jack
Brown
Green
Red
T1 R R1T
27
26
28
29
Gray
10
9 8 7

Figure 12: D133 for Ground Start

Points

Point Parameters D2112 Point 1
Point 1 is a powered sensor loop. Review the Radionics Technogram:
Compatible with the D2112
of compatible detectors. Point 1 is supervised with a 2.0K EOL resistor.
Points 2 to 6 (1 to 6 on D2112E)
Points 2 to 6 are supervised with a 1.0K EOL resistors
Open Loop = Greater than 8.9 VDC, but less
than 13.9 VDC.
Normal Loop = Greater than 2.5 VDC, but less
than 8.5 VDC.
Shorted Loop = Greater than 0.0 VDC, but less
than 2.0 VDC.
(D2112 Only) Points 7 and 8
Points 7 and 8 are not supervised with EOL resistors.
Open Loop = Greater than 2.4 VDC, but less
than 13.9 VDC.
Normal (Closed) Loop = Greater than 0.0 VDC,
but less than 1.4 VDC.
Point Response Time
The panel scans point sensor loops every 500 milliseconds. A point must be faulted for 2 scans before the panel initiates an alarm.
74-07111-000-D 1/96
Smoke Detectors
(73-07115-000) for a list
D2112/D2112E Installation Manual
See RELAYS in D2112/D2112E Program Entry Guide to program External Relay 1 for Ground Start.

Keyswitch

Description
You can connect a momentary contact arming station (keyswitch) to turn the D2112 on and off. The keyswitch is connected to a point sensor loop (points 2 to 6 only, do not use points 7 and 8).
You can use the external relay outputs and D133 Relay Modules to activate arming status lights for keyswitch arming stations. See the
D2112/D2112E Program Entry Guide
Programming
See the
POINT CODES Group
D2112E Program Entry Guide
programming for points used for keyswitches.
Installation
Connect the end-of-line resistor for the point at the keyswitch so that the switch shorts the resistor when it operates. An open on the circuit produces an alarm if the area is armed and a trouble if it is disarmed. See Figure 13.
COMMON
End of Line
Resistor
POINT INPUT

Figure 13: Keyswitch

Page 15
Relays
.
in the
D2112/
for the correct
Short and restoral on circuit toggles arming state.
© 1995 Radionics
section

Keyswitch Operation

4
Shorting and restoring the point sensor loop toggles the system On and Off. All faulted points are bypassed. See
D2112E Program Entry Guide
POINT CODES Group
.
in the
D2112/

Silencing the Bell

To silence the bell (stop Alarm output) if the system is On (or Part On), operate the keyswitch to turn the system Off. If the area is Off, operating the keyswitch only silences the bell. It does not turn the system On.
EasiKey Control
+
To 12VDC, Switched
parallel to door strike.
End of Line Resistor

Easikey

You can use a Radionics Easikey access system to turn the system Off. Program the to Easikey. See the
Guide
for instructions. You must use a 12VDC
D2112/D2112E Program Entry
option for the Easikey installation. See the
Installation and Operation Instructions
Keyswitch Keyswitch
Easikey
.
prompt
Connect the Easikey door controller to the panel using a D133 Relay Module as shown in Figure 14. Make certain to connect the common for the Easikey's 12VDC power supply to terminal 10 on the panel.
D133
Relay Module
N/O 1 COMM1 N/C 1 X1­X1+
Connect to any supervised point
programmed for Keyswitch
(Digit 1 =A, See D2112/D2112E
Program Entry Guide).
Shorting and restoring point turns
system Off.
20
1918
21 22 23 2
10
11 12
15 16 17
1413
Figure 14: Easikey

D2112/D2112E Installation Manual

74-07111-000-D 196 © 1995 Radionics
Page 16

Installation Guide for UL Applications

Introduction

The
System Chart
and listed by Underwriters’ Laboratories for compatibility with the panel. These components meet the basic system requirements for the applicable standard.
The
System Wiring Diagram, Issue A
relationship between the panel and the accessory components referred to in the installation and operation instructions for each component for detailed instructions.
references components evaluated
shows the
System Chart.
See the

Optional Compatible Equipment

You can use UL listed components that do not require evaluation for electrical compatibility in many applications when installed according to the manufacturer’s instructions.
Burglary Applications
You can use UL listed burglary alarm sensors that do not require evaluation for electrical compatibility in burglary applications. In some cases you must use a UL listed Radionics interface module in conjunction with the sensors. Consult the individual component specification and installation documents to determine suitability.
In burglary applications with one 7.0Ah, 12 VDC battery the panel supports an auxiliary output of 350mA and an alarm (bell) output of 1.5A configured as necessary. For additional loadings refer to the
Current Rating Chart for Standby Battery Calculations.
For commercial burglary installations use a maximum of 45 seconds of entry delay and a maximum of 60 seconds of exit delay.
Test weekly:
test. Configure the User System Test to test the battery. See
D2112E Program Entry Guide
Fire Applications
You can use UL listed fire initiating devices not requiring electrical compatibility evaluation in any application. For example: four-wire smoke detectors, heat detectors, waterflow switches, and manual pull stations are suitable fire initiating devices. Consult the individual component specification and installation documents to determine suitability.
UL Standard 1023 requires a weekly
User Configuration
in the
D2112/
for instructions.
When using four-wire smoke detectors, install a suitable power supervision unit according to the manufacturer’s instructions. Use the D133 Relay Module to provide reset capability.
In fire applications with one 7.0Ah, 12 VDC battery the panel supports an auxiliary output of 140mA and a bell output of 720mA configured as necessary. For additional loadings refer to the
Current Rating Chart
for Standby Battery Calculations.
D2112 only:
compatible, and must be UL listed for use with the D2112. See the Radionics Technogram
Detectors Compatible with the D2112
000), or you may contact the detector manufacturer.
Test weekly:
and combined fire/burglary systems weekly. Configure the User System Test to test the battery. See
User Configuration
Program Entry Guide
For all Burglary applications the panel must be programmed to send a supervisory signal to the central station a minimum of once every 24 hours.
Do not set or program an automatic telephone dialer or similar device to place a call to a police station number that is not specifically assigned by that station for such service.
Sounding Device
The sounding device shall operate for at least four minutes before an automatic cutoff for Household Burglary applications and at least 15 minutes for Commercial Burglary applications.
For all Commercial Burglary applications the system must be programmed to sound the audible device every time the system is armed.
Enclosures
The D2103 enclosure is suitable for Household Fire and Burglary applications only.
Enclosure tamper protection causing an immediate alarm signal is required for all burglary applications.
Radionics offers three optional enclosures. The D8103 enclosure is suitable for residential fire
and/or burglary installations and commercial applications that do not require attack resistance or approval by Factory Mutual. (See the System for acceptable applications.)
Two-wire detectors must be electrically
Smoke
(73-07115-
Radionics recommends testing fire
in the
D2112/D2112E
for instructions.
Chart
74-07111-000-D 1/96
D2112/D2112E Installation Manual
Page 17
© 1995 Radionics
The D8108A is attack resistant. It is intended primarily for UL commercial burglar alarm and mercantile safe and vault applications requiring a local bell. You can use the D8108A in any burglar application where the D8103 or D8109 enclosure is suitable. The D8108A is approved by Factory Mutual, California State Fire Marshal, and the New York City Materials and Equipment Acceptance System.
The D8109 is normally used for fire alarm applications. The D8109 is approved by Factory Mutual, California State Fire Marshal, and the New York City Materials and Equipment Acceptance System.

Standby Battery Requirements

Household Burglary and Commercial Burglary
Four hours of standby battery capacity required.
Standby Battery Calculation for Fire Alarm Applications
NFPA 72 Household Fire Warning Equipment
The NFPA 72 Household Fire Warning Equipment Standard requires 24 hours of standby plus four minutes (.067 hrs) of alarm operation at the end of the 24 hour period.
You must use battery ampere hour (Ah) calculations to verify compliance. The formula below includes a 10% contingency factor for depletion of battery capacity with age.
NFPA 72 Ampere-Hour Calculation Formula
(Total B ___ x 24 Hrs) + (Total C ___ x .067 Hrs) + (10% Contingency) = Total Ah required.
Total Ah requirements must not exceed Ah capacity of batteries.

Current Rating Chart for Standby Battery Calculations

All currents are in milliamperes (1 ampere=1000 milliamperes).
AC Power On AC Power Off In Alarm Normal Current Minimum Current Maximum Current
Model Number Each Each Each Number Used Unit Total Unit Total Unit Total
D202 ____ 45 _____ 45 _____ 125 _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____ ______ ____ ____ _____ ____ _____ ____ _____
Total A1 = _____ Total B = _____ Total C2= _____
1
If Total A exceeds 860 mA, a stand-alone power supply is required to provide additional current.
2
If Total C exceeds 860 mA for fire systems, a stand-alone power supply is required to provide additional current.
D2112/D2112E Installation Manual
74-07111-000-D 196 © 1995 Radionics
Page 18

System Chart

Police Connected
Central Station Burglary
Household Fire /
Household Fire
(Grade A)
74 74
72 72
24 +
24 +
4 mins
4 mins
alarm
alarm
Included with panel.
1
1
Opt.No Opt.
Required to connect panel to
RJ31X TelCo Block.
1+ 1+
1+1+
1•
1•
No No
Required for all applications.
Opt.
Opt.
derived channel service.
NFPA Standard Minimum Hours
of Standby Battery
D2103 Enclosure D8103 Enclosure
D8108A Enclosure D8109 Enclosure
D126 Battery D127 Reversing
Relay
D164 Telephone
Cord
D202 Command Center
D262 Smoke Detector Head D261A Base
D431, D435, D438, D440, D442, D448, Indicating Device
D1240 Battery D1625 Transformer D8004 Transformer
Enclosure
D8122 Derived
Channel S.T.U.
D8130 Release
Module
Household Burglary
4
Optional, order D2112M
(panel on D2102 mounting
skirt) and D1625 transformer.
Order D101 lock for D8103. Opt. Opt.
Opt.
1+ 1+ 1+
1
Optional, contact TelCo for availability of
The D2112 and D2112E control panels are suitable for Grade A Local Mercantile Premises Alarm systems and Grade A Mercantile Safe and Vault Alarm systems. For all local applications and Grades, the model D8108A Attack Resistant Enclosure and a UL listed sounding device are required.
The D2112 and D2112E control panels are suitable for Grade B when used with a UL listed local sounding device. Suitable for Grade AA Central Station Mercantile when used with model D8122 derived channel subscriber terminal unit.
74-07111-000-D 1/96
(Grade C)
Burglary Combined
4
No No No No
Req. Req.
No
Opt. Opt.
Opt.
1+
Opt.
Opt.
Opt.
Optional
D2112/D2112E Installation Manual
Burglary
4
No
Opt.
1+
11
Opt.Opt.
Page 19
Proprietary Burglary
Local Burglary
D2112 and D2112E not listed for these applications
4
4
No No
Req. = Required for this application
Req.
No
Opt.
Opt.
Local and Central Station
Local Fire / Burglary
72
Local Fire
Combined
72
Fire Combined
71, 72 7171, 72
Central Station Fire /
Local and Central Station
Fire / Burglary (Grade C)
Key
No = Not acceptable for this application
Opt. = Optional for this application
1+ = One or more required for this
application. Consult the appropriate standard.
Central Station Fire
Burglary (Grade C)
71
2+ = Two or more required for this
application. Consult the appropriate standard.
1+
1• = D2112 Only: At least one detector
required. You can substitute other 2-wire detectors listed for use with the D2112. You could use the
D262 with the D270 four-wire base or other manufacturers' four wire detectors. You must use a listed
1
1
power supervision relay with four wire detectors.
= Listed bell (siren) housing required
for burglary alarm bell or siren.
= (Empty Box) Not used for this
application.
The D2112 and D2112E control panels are suitable for Grade A Mercantile Premises and Mercantile Safe and Vault alarm systems. Suitable for Grade AA Police Station Mercantile Premises and Mercantile Safe and Vault systems when model D8122 derived channel subscriber terminal unit is used. For all Police Station Connect applications the model D8108A Attack Resistant Enclosure and a UL listed sounding device are required.
The D2112 and D2112E control panels are suitable for Grade B Proprietary Burglary applications when used with a UL listed local sounding device and Grade BB proprietary Burglar applications when installed with a model D8122 derived channel subscriber terminal unit.
© 1995 Radionics
Electrically Actuated
Transmitter
71
D2112
Listed Audible Signaling Device Rated At 10.2 TO 13.9 VDC (Do NOT Use Vibrating Type Horns)
Required for
Fire and
Combined
Fire/Burglary.
Optional for
other.
-++
D126
Battery
12V 7Ah

System Wiring Diagram, Issue A

Supervised with 6.8k
2.0k
EOL Resistor.
s
Supervised with 1k EOL Resistor. Typical Initiating Devices are Door Contacts NO/NC,
s
Floor Mats, Motion Sensors, Glass Break Detectors, etc.
P
P S
PSP
P
= POWER LIMITED
S
= SUPERVISED
P
S
S
-
D1240
Battery
12V 4Ah
Arming Station
D202 Up to
Four
P
P
P
P
S
D133
Relay
P
D133 Relay
P
P
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
10
9 8 7 6 5 4 3 2 1
P S
NOT Supervised, Normally Closed. Typical Initiating Devices are Door Contacts, Floor Mats, Motion Sensors, T amper Switches, etc. All devices open on alarm.
D164 Phone Cord to RJ31X for Phone Line
P
PSP
P P
S
D2112E
Listed Audible Signaling Device Rated At 10.2 TO 13.9 VDC (Do NOT Use Vibrating Type Horns)
Required for
Fire and
Combined
Fire/Burglary.
Optional for
other.
-++
D126
Battery
12V 7Ah
-
12V 4Ah
D1240
Battery
16 VAC
25 VA 60 HZ
Transformer
Arming Station
D202 Up to
Four
P
D1625
P
P
P
S
P S
D8004 Transformer Enclosure
Supervised with 1k EOL Resistor. Typical Initiating Devices are Door Contacts NO/NC, Floor Mats, Motion Sensors, Glass Break Detectors, etc.
D133
Relay
P
P
D133
Relay
P
10
9
8 7 6 5 4 3 2
1
NOT USED
P
11 12 14 15 16 17 18 19 20 21 22 26 27 28 29
P
P
S
S
P S
P
P
S
S
S
= POWER LIMITED = SUPERVISED
PSP
23 24 2513
NOT USED
D164 Phone Cord to RJ31X for Phone Line
P
16 VAC
25 VA 60 HZ
Transformer
D1625
D8004 Transformer Enclosure
Aux Power Fuse
2 Amp Fast Blow
Alarm Output Fuse
2 Amp Fast Blow
D2112/D2112E Installation Manual
74-07111-000-D 196 © 1995 Radionics
Page 20

Specifications

Primary Power Supply
• 16.5 VAC 25 VA class 2 plug-in transformer (D1625)
Secondary Power Supply
• 12 VDC 4.0 Ah sealed lead acid rechargeable battery. 7.0 Ah battery required for Fire and combined Fire/Burglary systems.
Auxiliary Power Output
• 350mA maximum at 10.2 VDC to 13.9 VDC for devices powered at terminal 9 (140mA for Fire and combined Fire/Burglary systems) .
Alarm Power Output
• 1.5 A maximum at 10.2 VDC to 13.9 VDC output. Output may be steady or pulsed depending on programming.
Fire and Fire/Burglary Systems To comply with UL 985 listing standards for household fire alarm systems (effective March 1,
1989), the total combined continuous and alarm current draw for the system during alarm conditions must be limited to 860 mA provided by the primary power supply (rectified AC).
Minimum Operating Voltage
• 10.2 VDC
Telephone Connection
• RJ31X or RJ38X jack interfaced with D164 phone cord.
Environmental
• Temperature: 32°-122°F (0°-50°C)
• Relative Humidity: 5-85% at 86°F (30°C) non­condensing
D2103 Enclosure Dimensions
Height: 10.75 inches Width: 9.18 inches Depth: 3.5 inches
D2112E Auxiliary Power and Bell Output Fuse Specifications
2 Amp Fast Blow (5 mm x 20 mm) Radionics Part # 57-03570-008
Arming Stations
• D202 Keypad
• Keyswitch
• Easikey
Compatible Enclosures
• D2103 Standard Enclosure
• D8103 Universal Enclosure
• D8109 Fire Enclosure
• D8108A Attack Resistant Enclosure
Compatible Accessories (D2112 and D2112E)
See the Radionics Product Catalog for complete list.
• D126 12V, 7 Ah Rechargeable Battery
• D127 Reversing Relay
• D133 Relay Module
• D135A Low Battery Cutoff Module
• D164 Phone Cord
• D202 Keypad
• D250 Heat Detector Base
• D254 135° Fixed Point Thermostat
• D255 190° Fixed Point Thermostat
• D440 (6"), D442 (10") Bells
• D448 12 VDC Horn
• D1240 12V, 4 Ah Rechargeable Battery
• D1625 16.5 VAC 25 VA Transformer
• D5200 Programmer
• D5300 Remote Account Manager II
• D8004 Transformer Enclosure
• D8121A/ D8122 Derived Channel S.T.U.
• Easikey
D2112 Point 1 Only
• D261A Smoke Detector Base
• D262 Smoke Detector Head
74-07111-000-D 1/96
D2112/D2112E Installation Manual
Page 21
© 1995 Radionics

D21 12/D2112E Terminal Quick Reference

Terminal Description
1,2 AC Input Connect 16.5 VAC, 25 VA transformer for primary power
source.
3 Earth Ground Connect to earth ground. A cold water pipe or grounding rod is
preferred. Do not connect to telephone or electrical ground.
4 Battery Positive Connect Positive terminal of 4.0 to 7.0 Ah battery to this
terminal.
5 Battery Negative Connect Negative terminal of 4.0 to 7.0 Ah battery to this
terminal.
6 Alarm Output Positive Supplies 1.5 Amps at 10.2 to 13.9 VDC for alarm output. This
terminal provides a constant output. Negative is switched.
7 Alarm Output Negative Negative terminal for alarm output. This terminal switches for
pulsed or steady alarm output. 8 Keypad Data Data for Keypads 9 Auxiliary Power Positive Supplies 350mA at 10.2 to 13.9 VDC for auxiliary power,
keypads, and relay outputs .
10 Common Common for Auxiliary Power and Relay Drivers 11 External Relay 1 Connect D133 Relay for Form C Dry Contact 12 External Relay 2 Connect D133 Relay for Form C Dry Contact 13 D2112 Positive Point 1
Not used on D2112E
14 D2112: Negative Point 1
D2112E: Input Point 1
D2112: Positive power for Point 1. Switched for sensor reset.
Use for approved two wire smoke or glass break detectors.
D2112: Negative power for Point 1
D2112E: Input for Point 1
15 Common Common for Points 1 and 2 16 Input Point 2 Input for Point 2 17 Input Point 3 Input for Point 3 18 Common Common for Points 3 and 4 19 Input Point 4 Input for Point 4 20 Input Point 5 Positve for Point 5 21 Common Common for Points 5 and 6 22 Input Point 6 Input for Point 6 23 D2112: Point 7
D2112E: Not Used
D2112: Input for Point 7. No EOL Resistor
D2112E: Not Used
24 Common Common for Points 7 and 8 25 D2112: Point 8
D2112E: Not Used
D2112: Input for Point 8. No EOL Resistor
D2112E: Not Used
26 T1 Tip of phone line to premises phone 27 T Tip of incoming phone line 28 R Ring of incoming phone line 29 R1 Ring of phone line to premises phone
The Radionics logo is a registered trademark of Radionics, Inc., Salinas, CA, U.S.A. ©1994 Radionics, Inc., Salinas, CA, U.S.A. All rights reserved
Radionics, Inc., 1800 Abbott Street Radionics, 1 Park Gate Close, Bredbury Salinas, California 93901 Stockport, Cheshire, SK6 2SZ, England Customer Service: (800) 538-5807 Technical Support: (061) 494 0851
O&I Menu
Documents by Type Menu
Documents by Product Menu
Main Menu
Loading...