Radiant RBC 24 Installation, Use And Maintenance Manual

RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
Installation, Use and Maintenance Manual for model
0476
RBC 24
Open chamber boiler with built-in DHW
2
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
RBC 24_EN
TABLE OF CONTENTS
TABLE OF CONTENTS
INTRODUCTION 4
1. INSTALLER SECTION 7
1.1. INSTALLATION 8
1.1.1. GENERAL INSTALLATION WARNINGS 8
1.1.2. BOILER LOCATION ENVIRONMENTAL REQUIREMENTS 8
1.1.3. REFERENCE LEGISLATION 9
1.1.4. UNPACKING 10
1.1.5. OVERALL DIMENSIONS 11
1.1.6. JIG 11
1.1.7. POSITIONING AND MINIMAL TECHNICAL SPACES 12
1.1.8. CIRCULATOR PREVALENCE/FLOW DIAGRAM 13
1.1.9. HYDRAULIC CONNECTION 14
1.1.10. SYSTEM FILLING 15
1.1.11. ANTI-FREEZE PROTECTION 16
1.1.12. GAS CONNECTION 17
1.1.13. ELECTRICAL CONNECTION 17
1.1.14. OPTIONAL ELECTRICAL CONNECTIONS 18
1.1.15. FUME EXHAUST FITTINGS 19
1.1.16. TYPES OF INSTALLATION 20
2. SUPPORT CENTER SECTION 23
2.1. FIRST START-UP 24
2.1.1. PRELIMINARY OPERATIONS FOR FIRST START-UP 24
2.1.2. BOILER COMMISSIONING 25
2.1.3. GAS PRESSURE CHECK AND CALIBRATION 26
2.1.4. ACCESSING AND PROGRAMMING THE PARAMETERS 28
2.1.5. PARAMETER TABLE MIAB2013 31
2.1.6. HEAT CAPACITY / GAS PRESSURE DIAGRAM 35
2.2. MAINTENANCE 36
2.2.7. GENERAL MAINTENANCE WARNINGS 36
2.2.8. TECHNICAL DATA 37
2.2.9. TECHNICAL ASSEMBLY 41
2.2.10. HYDRAULIC BOARD 42
2.2.11. WIRING DIAGRAM 43
2.2.12. ACCESSING THE BOILER 44
2.2.2. ACCESSING THE ELECTRONIC BOARD 45
2.2.14. SYSTEM EMPTYING 46
2.2.15. FAULT SIGNALLING CODES 47
3
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
RBC 24_EN
TABLE OF CONTENTS
2.2.3. CHIMNEY SAFETY 50
2.2.16. ACTIVE FUNCTIONS SIGNALLING CODES 51
2.2.17. GAS TYPE TRANSFORMATION 52
3. USER SECTION 53
3.1. USE 54
3.1.1. GENERAL USE WARNINGS 54
3.1.2. CONTROL PANEL 55
3.1.2. DISPLAY ICONS 56
3.1.3. INFO MENU DISPLAY DATA 57
3.1.4. START-UP 58
3.1.5. OPERATING MODE 58
3.1.6. INFORMATIONAL NOTE ON ANTI-FREEZE FUNCTION 59
3.1.7. SYSTEM FILLING 60
3.1.8. FAULT SIGNALLING CODES 61
3.1.9. ACTIVE FUNCTIONS SIGNALLING CODES 63
3.1.7. MAINTENANCE 64
3.1.8. COVER CLEANING 64
3.1.9. DISPOSAL 64
4
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
_Prefazione_EN
1.
INTRODUCTION
WARNING
Before starting any operation it is mandatory to read this instruction manual, in relation to the activities to be carried out as described in each relevant section. Proper operation and optimal performance of the boiler are ensured by strict compliance with all the instructions given in this manual.
The installation, use and maintenance manual is an integral and essential part of the product and must be delivered to the user.
MANUAL USERS
The manual users are all those who install, use and maintain the boiler.
The boiler must be used and accessed only by qualified operators that fully read and understood the use and maintenance manual, paying particular attention to the warnings.
READING AND SYMBOLS OF THE MANUAL
To ease the understanding of this manual, recurrent symbols where used, in particular:
› On the outer margin of the page is placed a
thumb index indicating the type of user to which the instructions in that section address.
› The titles are differentiated by thickness and size
in accordance with their hierarchy.
› The images contain important parts described in
the text, marked with numbers or letters.
› (See chap “chapter name”): this entry indicates
another section in the Manual that you should refer to.
› Device: this term is used referring to the boiler.
DANGER
It identifies an information related to a general danger that if not complied with, may cause serious personal damage or even death.
ATTENTION
It identifies an information that if not complied with may cause small or medium level lesions to the person or serious deterioration to the boiler.
WARNING
It identifies a precaution information that must be observed in order to avoid damaging the machine or parts of it.
MANUAL STORAGE
The manual must be carefully stored and replaced in case of deterioration and/or low legibility.
If you misplace the use and maintenance manual, you can request it from the Technical Support Centre giving the serial number and model of the boiler indicated on the plate placed on the right side of its casing.
As an alternative, the use and maintenance manual can be downloaded free from the on-line site www. radiant.it, accessing the “download” section and entering the boiler model.
INTRODUCTION
5
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
_Prefazione_EN
1.
MANUFACTURER WARRANTY AND RESPONSIBILITY
The warranty of the Manufacturer is provided only through its own authorized Technical Support Centres, listed for each Region and Provence on the site www.radiant.it, and covers all conformity defects at the moment of sale.
The technical and functional features of the device are ensured by its use in compliance:
1. with the use and maintenance instructions contained in the manuals accompanying the product, the content of which the customer certifies that he is aware;
2. with the conditions and purposes to which assets of the same type are intended.
For more information on the warranty validity, its duration, the obligations and the exemptions, please consult the First start-up certificate attached to this manual.
The manufacturer reserves:
› the right to modify the tools and relative
technical documentation without any obligation to third parties; neither will the company be held responsible for any inaccuracies in this handbook deriving from printing or translation errors;
› the material and intellectual ownership of
this manual and forbids its distribution and duplication, even partial, without prior written authorization.
PRODUCT CONFORMITY
RADIANT BRUCIATORI spa declares that its gas boilers comply with the European Directives and with the requirements provided in the European standards below:
› Eco-design Directive 2009/125 CE,
› Energy labeling Directive 2010/30/CE,
› EU regulation 811/2013,
› EU regulation 813/2013,
› Gas Directive 2009/142/CE,
› Electromagnetic compatibility Directive 2014/30/
CE,
› Performance Directive 92/42/CE,
› Low voltage Directive 2014/35/CE.
The materials used such as copper, brass, stainless steel create a homogeneous, compact and functional assembly, easy to install and manage. In its simplicity, the boiler is equipped with all accessories necessary to render it a veritable independent heating unit. All boilers are tested and delivered with a quality certificate signed by the tester.
INTRODUCTION
The installation operations described in this section should
be performed only by qualified personnel, having the
appropriate technical training in the field for the installation
and maintenance of components of civil and industrial
domestic hot water production and heating plants.
1. INSTALLER SECTION1. INSTALLER SECTION
8
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Avvertenze generali per l'installazione_Locale caldaia_trad_EN
1. INSTALLATION
INSTALLER
1.1. INSTALLATION
1.1.1. GENERAL INSTALLATION WARNINGS
ATTENTION
This machine may be used only for the purpose for which it has been designed: heat water to a temperature below boiling point at atmospheric pressure. Any other use is considered wrong and dangerous. The manufacturer is excluded from any contractual or out of contract responsibility for damage caused to people, animals or property due to errors during installation.
ATTENTION
This boiler should be installed only by qualified personnel, having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water production and heating plants.
ATTENTION
After having removed the packing, make sure the equipment is intact. In case of doubt, do not use the equipment and contact the supplier.
BEFORE INSTALLING THE BOILER, THE INSTALLER MUST MAKE SURE THAT THE FOLLOWING CONDITIONS ARE MET:
› The device is connected to a heating plant and a
water supply network appropriate for its power and performance.
› The location must be properly vented through an
air vent.
› The air vent must be placed at floor level to
prevent it from being obstructed, protected by a grid that does not hamper the useful section of passage.
› The device is suitable for use with the type of
gas available by checking the boiler data plate (placed on the inner side of the front casing.
› Make sure that the tubes and couplings are
perfectly sealed, without any gas leaks.
› Make sure that the grounding system works
properly.
› Make sure that the electrical systems is suitable
for the maximum power absorbed by the equipment, value indicated on the data plate.
WARNING
Use only original RADIANT optional or kit
accessories (including electrical).
1.1.2. BOILER LOCATION ENVIRONMENTAL REQUIREMENTS
The device's installation location should be vented due to the presence of threaded joints on the gas adduction line. The location should be therefore provided with vents as to ensure air exchange, with output grid in the natural accumulation area of eventual gas losses.
WARNING
If the temperature in the boiler installation location goes below -10° centigrades, please fill the plant with anti-freeze liquid and insert and electrical resistances kit (see chapter ‘ANTI-FREEZE PROTECTION’).
WARNING
The manufacturer will not be held responsible for damages caused by incorrect installation not in conformity with the over mentioned
9
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Avvertenze generali per l'installazione_Locale caldaia_trad_EN
1. INSTALLATION
INSTALLER
instructions and not protected adequately from the freeze.
1.1.3. REFERENCE LEGISLATION
The installation must be realized according to the requirements of current legislation and in compliance with local technical regulations, according to the indications of the good technique.
10
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Disimballo_murale_EN
1. INSTALLATION
INSTALLER
1.1.4. UNPACKING
WARNING
Please unpack the boiler just before installing it. The Company is not responsible for the damages caused to the device due to incorrect storage.
WARNING
The packing elements (cardboard box, wooden crate, nails, fasteners, plastic bags, expanded polystyrene, etc.) must be kept out of the reach of children as they may be dangerous. Therefore they should be dismantled suitably differentiating them in accordance with the standards in force.
To unpack the boiler, proceed as follows:
› Place the packed boiler on the floor (fig. 1-A) and
remove the fasteners opening the four flaps of the box outwards.
› Turn the boiler at 90° holding it with your hand
(fig. 1-B).
› Lift the box (fig. 1-C) and remove the guards (fig.
1-D).
C
B
D
A
fig. 1
11
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Dimensioni_RBC 24_NC_R7_EN
1. INSTALLATION
INSTALLER
1.1.5. OVERALL DIMENSIONS
1.1.6. JIG
205
180
730
410
320
805
49 78 70 80 102 31
120
RCG F A
R- RETURN Ø 3/4” C - HOT Ø 1/2” G- GAS Ø 3/4” F- COLD Ø 1/2” A- INFEED Ø 3/4”
12
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Spazi tecnici minimi e posizionamento_murale_EN
1. INSTALLATION
INSTALLER
1.1.7. POSITIONING AND MINIMAL
TECHNICAL SPACES
The boiler must be installed only on a vertical solid wall, able to sustain its weight.
In order to allow the access inside the boiler for maintenance operations, you have to respect the minimum technical spaces indicated in figure 1.
To facilitate the installation, the boiler is provided with a jig that allows setting in advance the connections to the tubes offering you the possibility of connecting the boiler to completed masonry works.
For machine positioning, proceed as follows (see fig. 2):
1. Trace a line using a spirit level (min. length 25 cm) on the installation wall.
2. place the top of the jig along the traced line respecting the distances of the water connections; then
mark the two points to insert the two knobs or the fasteners, then trace the points for the fume exhaust fittings;
3. remove the jig and drill the wall;
4. hang the device using the knobs or the bracket and perform the connections.
3
1
42
70 80 10249 3178
Ø80
Ø125
Ø100
35826 26
54 54
821
681
699
302
785
H
B
A
Y
X
A - 200 mm B - 300 mm
X - 60 mm
Y - 60 mm
H - 1000 mm
fig.1
fig.2
13
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Diagramma portata-prevalenza circolatore_RBS 24_HE_EN
1. INSTALLATION
INSTALLER
1.1.8. CIRCULATOR PREVALENCE/FLOW DIAGRAM
Circulator priority maximum speed
- - - - Boiler load loss
Wilo-Yonos PARA MSL 12/6B
0 0,4 0,8 1,2 1,6 2,0 2,4
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7
02468
0
1
2
3
4
5
6
7
8
0
10
20
30
40
50
70
60
80
p/kPa
H/m
Q/m³/ h
Q/l/s
Q/Igpm
PREVALENCE
FLOW RATE
14
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Allacciamento idraulico_combinata_EN
1. INSTALLATION
INSTALLER
1.1.9. HYDRAULIC CONNECTION
DANGER
Make sure that the tubes of the water and heating plant are not used as grounding system for the electrical plant. There are not suitable for such use.
WARNING
To prevent voiding the warranty and to ensure the proper operation of the boiler, please wash the plant (if possible when hot) with suitable pickling or descaling solutions in order to remove the impurities coming from tubes and radiators.
WARNING
If the boiler is installed in a hydrostatic position lower than those of the user devices (radiators, fan coils, etc.), mount the shut-off valves on the domestic water heating circuit to ease the performance of the maintenance operations if it is necessary only to empty the boiler.
WARNING
When connecting the equipment to water supply, avoid excessive bending and recovery operations from any off axis positioning that may damage the tubes causing leaks, malfunction or early wear.
WARNING
In order to avoid any vibrations and noises, do not use tubes with small diameters or elbows with small radius and significant cut-off of the passage sections.
WARNING
Connect the boiler safety drains to a discharge funnel. The manufacturer is not responsible for any floods due to safety valve opening in case of plant overpressure.
DOMESTIC CIRCUIT
In order to prevent limestone build-up and damages to the domestic water heat exchanger, the hardness of the domestic supply water should not exceed 15 °f. However, please check the characteristics of the water used and install suitable treating devices.
The heat exchanger coil cleaning frequency depends on the hardness of the supply water and on the presence of solid residues or impurities inside the water that are often present in case of recently installed plants. Based on the characteristics of the infeed water, you should install suitable water treating devices, for residues presence please install a line filter.
The pressure of the cold infeed water should be between 0.5 and 6 bar. In case of greater pressure values, please install a pressure reducer upstream from the boiler.
HEATING CIRCUIT
In order to avoid any scale or deposits on the primary exchanger, the hardness of the heating circuit infeed water should not exceed 25 °f. However, please check the characteristics of the water used and install suitable treating devices.
This treatment is mandatory if frequent episodes of return water or partial or total emptying of the plant occur.
WARNING
In case the boiler is installed as part of a low temperature circuit, please install a safety thermostat on the heating flow, which can stop the boiler activity in case of high heating flow temperature. The company assumes no liability for damage caused to persons or for failure to comply with these instructions.
15
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Riempimento dell'impianto_RBS_HE_R7_EN
1. INSTALLATION
INSTALLER
1.1.10. SYSTEM FILLING
WARNING
For system filling use only clean tap water.
WARNING
If the system is filled by adding ethylene glycol-type chemical agents you have to install on the loading system a hydraulic trip unit in order to separate the heating circuit from the domestic circuit.
Before powering up the boiler, fill the system as follows:
1. slightly loosen the cap of the circulator jolly
valve (1-fig. 1) to release the air from the system;
2. open the feeding tap “R” (fig. 2);
3. use pressure gauge “M” (fig. 2) to make sure
that the system pressure reaches 1.2 bar (fig.
3);
4. After performing this operation, make sure that
the loading tap “R” (fig. 2) is properly closed.
5. open the air relief valves of the radiators and
check the air removal process. When the water starts to leak close the radiators air relief valves.
6. if after performing these operations you
observe a decrease of the water pressure inside the system, open once again the loading tap “R” until the pressure gauge indicates the value of 1.2 bar (fig. 3)
1
M
R
fig. 1
fig. 2
fig. 3
16
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Protezione antigelo_firm.L181D_EN
1. INSTALLATION
INSTALLER
1.1.11. ANTI-FREEZE PROTECTION
The boiler is protected against freezing thanks to the electronic board preparation with functions that start the burner and heat the concerned parts when their temperature goes below the minimum pre-set values, protecting the boiler up to an external temperature of -10 °C.
The device starts when the hot water temperature goes below 5 °C, automatically starting the burner until the water reaches the temperature of 30 °C.
The system starts even if on the display appears “OFF”, as long as the boiler is connected to the power (230 V) and gas supply.
For long periods of standby, please empty the boiler and the plant.
If the temperature goes below -10° centigrades, please fill the plant with anti-freeze liquid (CLEANPASS FLUIDO AG cod. 98716LA) and insert and electrical resistances kit (cod. 82259LP).
DILUTION PERCENTAGE OF CLEANPASS FLUIDO AG
ANTIFREEZE ­ETHYLENE GLYCOL
TEMPERATURE FREEZING POINT
(%) VOLUME (°C)
20 -7.5 30 -13 35 -18 40 - 22.5 45 -28 50 -33.5 55 -42
60 -50 RECOMMENDED MINIMUM PERCENTAGE OF GLYCOL : 20 %
17
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Allacciamento gas_elettrico_MIAB_EN
1. INSTALLATION
INSTALLER
1.1.12. GAS CONNECTION
DANGER
In order to connect the gas connector of the boiler to the supply pipe use a stop seal of an appropriate size and material. The use of hemp, teflon tape or similar materials is strictly forbidden.
BEFORE PERFORMING THE GAS CONNECTION, MAKE SURE THAT:
› the gas adduction line complies with the
standards and regulations in force;
› the tubing's section suits the requested capacity
and its length;
› the tubing is equipped with all safety and control
devices required by the standards in force;
› the internal and external seals of the gas infeed
plant are checked;
› the device is suitable for use with the type of
gas available by checking the boiler data plate (placed on the inner side of the front casing. If they do not match you must take the necessary measures to adapt the boiler to another type of gas (see chapter GAS TRANSFORMATION);
› the gas supply pressure falls within the values
indicated on the data plate.
1.1.13. ELECTRICAL CONNECTION
DANGER
The equipment is electrically safe only if it is properly connected to an efficient grounding system, performed in compliance with the safety standards in force. You should check this essential safety requirement. If in doubt, request an accurate check of the electrical system performed by qualified staff, as the manufacturer is not responsible for any damages caused by lack of grounding system.
› Make sure that the electrical systems is suitable
for the maximum power absorbed by the equipment, value indicated on the data plate.
› make sure that the cables section is appropriate
for the maximum power absorbed by the equipment and that it is however not lower than 1 mm
2
.
› The equipment works with alternating current of
230 V and 50 Hz.
WARNING
Make sure that the phase and neutral cables connection is performed in compliance with the wiring diagram (see chapter WIRING DIAGRAM).
WARNING
It is strictly forbidden the use of adaptors, multiple plugs and/or extensions for the general power supply of the equipment from the electrical network.
18
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Collegamenti elettrici opzionali_MIAB2013_EN
1. INSTALLATION
INSTALLER
1.1.14. OPTIONAL ELECTRICAL CONNECTIONS
To wire the optionals below:
• (EP) EXTERNAL TEMPERATURE PROBE CODE
73518LA
• (ET) ENVIRONMENT THERMOSTAT
• (CR) REMOTE CONTROL OPEN THERM CODE 40-
00017
use the terminal placed inside the control panel as follows:
DANGER
Cut off the voltage from the main switch.
› remove the boiler's front casing (refer to chapter
ACCESSING THE BOILER).
› remove the crankcase of the control panel (see
chapter ACCESSING THE ELECTRONIC BOARD).
· For the external temperature Probe connect the two non-polarised conductors to the M0904 contacts (see 'SE' fig. 1).
· For the ambient thermostat or Remote Control, first remove the bridge on the M0904 terminal board and then connect the two non-polarised conductors of the ambient thermostat or remote control (see 'TA' or 'CR' fig. 1).
After performing these operations, remount the crankcase of the control panel and then re-fit the front casing.
SE
TA
CR
BUZ1000
M0902
M0904
M0900
A
2
3
4
1
fig. 1
19
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Raccordi fumari_camera aperta_EN
1. INSTALLATION
INSTALLER
1.1.15. FUME EXHAUST FITTINGS
WARNING
In order to ensure proper operation and efficiency of the device you have to connect the boiler fume exhaust fitting to the fume exhaust duct using appropriate flue fittings for traditional boilers. We recommend installing approved discharge systems approved by approved by RADIANT.
WARNING
You cannot use traditional flue fittings for the discharge ducts of the condensing boilers, nor vice versa.
› In order to discharge the fumes through a fumes
exhaust duct carefully follow the technical standards in force.
› Suction and discharge systems, tailored to
individual installations, must be protected with accessories that prevent the ingress of foreign objects and atmospheric agents.
› Make sure that the discharge tube doe not
protrude inside the fumes exhaust duct, stop before it reaches the inner surface of the latter.
› The discharge duct must be perpendicular with
the opposite internal wall of the chimney or of the fumes exhaust duct (fig. 1).
fig. 1
20
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Tipologie di installazione_B11BS_EN
1. INSTALLATION
INSTALLER
1.1.16. TYPES OF INSTALLATION
For this type of boiler are available the following fumes discharge configurations: B11BS (see Fig. 1).
› B11BS:
· Type B, open chamber boiler, equipped with a control device for the evacuation of combustion products (flue safety thermostat).
· Air intake in the environment and flues exhaust to the outside.
· For the minimum chimney height allowed, refer to the ‘TECHNICAL DATA’ paragraph.
DISCHARGE OF COMBUSTION PRODUCTS FOR B-TYPE DEVICES.
The gas devices, provided with connection for fumes exhaust tube, must be directly connected to efficient chimneys or fume exhaust ducts: only if these are missing you can discharge the combustion products directly through the gas devices.
The connection to the chimney or to the fume exhaust ducts must respect the following requirements:
· Be sealed and realised in materials suitable to resist normal mechanical stress, heat, the action of combustion products and any condensate forming;
· have no more than three changes in direction, including the chimney and/or fume exhaust duct inlet connection, made with internal angles greater than 90°. The changes in direction must be made only by using curved curved elements;
· have the axis of the inlet end perpendicular to the internal wall opposite to the chimney or fume exhaust duct;
· have, along its entire length, a section equal to or greater then that of the connection of the device discharge tube;
· have no shut-off devices (shutters).
· for direct external discharge there must be no more than two changes in direction.
LOCATIONS VENTING FOR B-TYPE DEVICES
The locations in which are installed gas devices must be vented so as to ensure the amount of air necessary for a regular combustion and for location ventilation. The natural air intake must take place directly through:
B11BS
fig. 1
21
RBS 24 - RAD - ING - Manual - 1709.1_MIAB2013_R7
1 Tipologie di installazione_B11BS_EN
1. INSTALLATION
INSTALLER
· permanent openings on the external walls of the location (windows);
· single or collective, ramified ventilation ducts.
The openings on the external walls of the location must respect the following requirements:
· have a net overall free passage section of at least 6 cm
2
for every kW of heat capacity
installed with a minimum of 100 cm
2
;
· they must be realized so as to make sure that the opening inlets are not obstructed (neither indoors nor outdoors);
· they must be protected with grids, metal meshes, etc. so as to keep the useful section mentioned above.
· they must be placed at a height next to the floor level such as to allow proper operation of the combustion products discharge systems; if such position can not be obtained, please increase by at least 50% the section of the vents.
Loading...
+ 47 hidden pages