Radiant R1K 50 Installation, Use And Maintenance Manual

Installation, Use and Maintenance Manual for model
R1K 50
Premix condensing system boiler
only heating
0476
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
SUMMARY
SUMMARY
INTRODUCTION 4
1. INSTALLER SECTION 7
1.1. INSTALLATION 8
1.1.1. GENER A L INS TALLATION WARNINGS 8
1.1.2. BOILER LOCATION ENVIRONMENTAL REQUIREMENTS 8
1.1.3. REFERENCE LEGISL ATION 9
1.1.4. BOILER OVERALL DIMENSIONS 10
1.1.5. JIG 10
1.1.6. OVERALL DIMENSIONS OF THE HEATING ONLY MODULE 10
1.1.7. OVERALL DIMENSIONS OF THE MODULE FOR REMOTE BOILER SUPPLY 11
1.1.8. MECHANICAL SYSTEM DIAGRAM 12
1.1.9. SYSTEM ACCES SORIES 14
1.1.10. CIRCULATOR PREVALENCE/FLOW DIAGRAM 16
1.1.11. GENERATOR INSTAL L ATION 17
1.1.12. HYDRAULIC CONNECTION 20
1.1.13. CHARACTERISTICS OF THE WATER OF THE SYSTEM 21
1.1.14. SYSTEM FILLING 23
1.1.15. FILLING THE CONDENSATE COLLECTION SIPHON 24
1.1.16. ANTI-FREEZE PROTECTION 25
1.1.17. GAS CONNECTION 26
1.1.18. ELECTRICA L CONNECTION 26
1.1.19. POWER SUPPLY 27
1.1.20. OPTIONAL ELECTRICAL CONNECTIONS 28
1.1.21. FUME EXHAUST FITTINGS 31
1.1.22. T YPES OF FUME EXHAUST SYSTEMS 32
R1K 50_EN
2. SUPPORT CENTER SECTION 37
2.1. FIRST START-UP 38
2.1.1. PRELIMINARY OPERATIONS FOR FIRST START-UP 38
2.1.2. BOILER COMMISSIONING 39
2.1.3. CO2 VALUE CHECK AND CALIBRATION 40
2.1.3. ACCESSING AND PROGRAMMING THE PARAMETERS 41
2.1.4. DIGITECH CS PARAMETERS TABLE 43
2.1.6. ELECTRIC FAN FREQUENCY/HEAT CAPACITY DIAGRAM 50
2.2. MAINTENANCE 51
2.2.5. GENERAL MAINTENANCE WARNINGS 51
2.2.8. TECHNICAL DATA 52
2.2.9. TECHNICAL ASSEMBLY 54
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
SUMMARY
2.2.6. HYDRAULIC BOARD 55
2.2.7. WIRING DIAGRAM 56
2.2.13. ACCESSING THE BOILER 57
2.2.8. ACCESSING THE ELECTRONIC BOARD 58
2.2.16. SYSTEM EMPTYING 59
2.2.9. FAULT SIGNALLING CODES 60
2.2.10. ACTIVE FUNCTIONS SIGNALLING CODES 63
2.2.11. GAS CONVERSION 64
3. USER SECTION 65
3.1. USE 66
3.1.1. GENERAL USE WARNINGS 66
3.1.2. CONTROL PANEL 67
3.1.3. DISPLAY ICONS 68
3.1.4. INFO MENU DISPLAY DATA 69
3.1.5. START-UP 70
3.1.6. OPERATING MODE 70
3.1.7. INFORMATIONAL NOTE ON ANTI-FREEZE FUNCTION 71
3.1.8. FAULT SIGNALLING CODES 72
3.1.9. ACTIVE FUNCTIONS SIGNALLING CODES 74
R1K 50_EN
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
INTRODUCTION
1.
INTRODUCTION
WARNING
Before starting any operation it is mandatory to read this instruction manual, in relation to the activities to be carried out as described in each relevant section. Proper operation and optimal performance of the boiler are ensured by strict compliance with all the instructions given in this manual.
The installation, use and maintenance manual is an integral and essential part of the product and must be delivered to the user.
MANUAL USERS
The manual users are all those who install, use and maintain the boiler.
The boiler must be used and accessed only by qualified operators that fully read and understood the use and maintenance manual, paying par ticular attention to the warnings.
READING AND SYMBOLS OF THE MANUAL
To ease the understanding of this manual, recurrent symbols where used, in particular:
› On the outer margin of the page is placed a
thumb index indicating the type of user to which the instructions in that section address.
DANGER
It identifies an information related to a general danger that if not complied with, may cause serious personal damage or even death.
ATTENTION
It identifies an information that if not complied with may cause small or medium level lesions to the person or serious deterioration to the boiler.
WARNING
It identifies a precaution information that must be observed in order to avoid damaging the machine or parts of it.
MANUAL STORAGE
The manual must be carefully stored and replaced in case of deterioration and/or low legibility.
If you misplace the use and maintenance manual, you can request it from the Technical Support Centre giving the serial number and model of the boiler indicated on the plate placed on the right side of its casing.
As an alternative, the use and maintenance manual can be downloaded free from the on-line site www. radiant.it, accessing the “download” section and entering the boiler model.
_Prefazione_EN
› The titles are differentiated by thickness and
size in accordance with their hierarchy.
› The images contain important parts described
in the text, marked with numbers or letters.
› (See chap “chapter name”): this entry indicates
another section in the Manual that you should refer to.
› Device: this term is used referring to the boiler.
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
INTRODUCTION
1 .
MANUFACTURER WARRANTY AND RESPONSIBILITY
The warranty of the Manufacturer is provided only through its own authorized Technical Support Centres, listed for each Region and Provence on the site www.radiant.it, and covers all conformity defects at the moment of sale.
The technical and functional features of the device are ensured by its use in compliance:
1. with the use and maintenance instructions contained in the manuals accompanying the product, the content of which the customer certifies that he is aware;
2. with the conditions and purposes to which assets of the same type are intended.
For more information on the warranty validity, its duration, the obligations and the exemptions, please consult the First start-up certificate attached to this manual.
› Energy labeling Directive 2010/30/CE,
› EU regulation 811/2013,
› EU regulation 813/2013,
› Gas Directive 2016/426/EU,
› Electromagnetic compatibility Directive
2014/30/CE,
› Performance Directive 92/42/CE,
› Low voltage Directive 2014/35/CE.
The materials used such as copper, brass, stainless steel create a homogeneous, compact and functional assembly, easy to install and manage. In its simplicity, the boiler is equipped with all accessories necessary to render it a veritable independent heating unit. All boilers are tested and delivered with a quality certificate signed by the tester.
_Prefazione_EN
The manufacturer reserves:
› the right to modify the tools and relative
technical documentation without any obligation to third parties; neither will the company be held responsible for any inaccuracies in this handbook deriving from printing or translation errors;
› the material and intellectual ownership of
this manual and forbids its distribution and duplication, even partial, without prior written authorization.
PRODUCT CONFORMITY
RADIANT BRUCIATORI spa declares that its gas boilers comply with the European Directives and with the requirements provided in the European standards below:
› Eco-design Directive 2009/125 CE,
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
1. INSTALLER SECTION1. INSTALLER SECTION
The installation operations described in this section should
be performed only by qualified personnel, having the
appropriate technical training in the field for the installation
and maintenance of components of civil and industrial
domestic hot water production and heating plants.
INSTALLER
1.1. INSTALLATION
2. INSTALLATION
1.1.1. GENERAL INSTALL ATION WARNINGS
ATTENTION
This machine may be used only for the purpose for which it has been designed: heat water to a temperature below boiling point at atmospheric pressure. Any other use is considered wrong and dangerous. The manufacturer is excluded from any contractual or out of contract responsibility for damage caused to people, animals or property due to errors during installation.
ATTENTION
This boiler should be installed only by qualified personnel, having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water production and heating plants.
ATTENTION
After having removed the packing, make sure the equipment is intact. In case of doubt, do not use the equipment and contact the supplier.
BEFORE INSTALLING THE BOILER, THE INSTALLER MUST MAKE SURE THAT THE FOLLOWING CONDITIONS ARE MET:
› The device is connected to a heating plant and a
water supply network appropriate for its power and performance.
› The location must be properly vented through
an air vent.
› The air vent must be placed at floor level to
prevent it from being obstructed, protected by a grid that does not hamper the useful section of passage.
› The device is suitable for use with the type of
gas available by checking the boiler data plate (placed on the inner side of the front casing.
› Make sure that the tubes and couplings are
perfectly sealed, without any gas leaks.
› Make sure that the grounding system works
properly.
› Make sure that the electrical systems is
suitable for the maximum power absorbed by the equipment, value indicated on the data plate.
WARNING
Use only original RADIANT optional or kit
accessories (including electrical).
1.1.2. BOILER LOCATION ENVIRONMENTAL REQUIREMENTS
The boiler has a thermal power over 35 kW and, therefore, it must be installed only into a heating unit.
The device's installation location should be vented due to the presence of threaded joints on the gas adduction line. The location should be therefore provided with vents as to ensure air exchange, with output grid in the natural accumulation area of eventual gas losses.
WARNING
DO NOT install the boiler in a technical compartment near a swimming pool or a laundry, to avoid that the combustion air is exposed to chlorine, ammonia or alkaline agents that may worsen the corrosion phenomenon of the heat exchanger. Failure to observe this caution will void the warranty of the heat exchanger.
1 Avvertenze gener ali per l'installazione_Locale c aldaia _cond _ alta potenza_EN
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
WARNING
If the temperature in the boiler installation location goes below -10 centigrades, please fill the plant with anti-freeze liquid and insert and electrical resistances kit (see chapter ‘ANTI-FREEZE PROTECTION’).
WARNING
The manufacturer will not be held responsible for damages caused by incorrect installation not in conformity with the over mentioned instructions and not protected adequately from the freeze.
1.1.3. REFERENCE LEGISLATION
The installation must be realized according to the requirements of current legislation and in compliance with local technical regulations, according to the indications of the good technique.
2. INSTALLATION
INSTALLER
1 Avvertenze gener ali per l'installazione_Locale c aldaia _cond _ alta potenza_EN
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
INSTALLER
3. INSTALLATION
1.1.4. BOILER OVERALL DIMENSIONS
302
157
480
640
306
150
136
410
1.1.6. OVERALL DIMENSIONS OF THE HEATING ONLY MODULE
160
145
209
1794
178
192
155
1.1.5. JIG
244
R- HEATING RETURN Ø 1” 1/4 G- GAS Ø 3/4 A- HEATING FLOW Ø 1” 1/4 SC- CONDENSATE DRAIN Ø 25 mm
107
42
70 94 47 129 70
RGsc A
157
530
157
157
504
524
524
RI RETURN SYSTEM Ø 1”1/2 AI DELIVERY SYSTEM Ø 1”1/2
157
200
514
1 Dimensioni_R1K 50_no INAIL_EN
10
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
1.1.7. OVERALL DIMENSIONS OF THE MODULE FOR REMOTE BOILER SUPPLY
3. INSTALLATION
INSTALLER
209
1794
145
227 99227 99282282
160
178
192
155
1 Dimensioni_R1K 50_no INAIL_EN
157
157
200
157
157
504
524524
RI RETURN SYSTEM Ø 1”1/2 AI DELIVERY SYSTEM Ø 1”1/2 RB HEATING FLOW TO DHW
STORAGE CYLINDER
AB HEATING FLOW TO DHW
STORAGE CYLINDER
514
Ø 1”
Ø 1”
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
11
INSTALLER
1.1.8. MECHANICAL SYSTEM DIAGRAM
HEATING ONLY INSTALLATION
The boiler can manage a heating system at a fixed point delivery temperature or in climatic compensation with an external probe, managing the modulation according to the actually requested thermal load.
1. INSTALLATION
1
2
fume exhaust system
3
GAS
DELIVERY SYSTEM
RETURN SYSTEM
condensate
LOAD SYSTEM
1 Schema meccanico impianto_R1K 50_no INAIL _EN
12
DESCRIPTION
1 EXTERNAL PROBE 2 REMOTE OPEN THERM 3CONTROL PANEL
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
1. INSTALL ATION
HEATING INSTALLATION + REMOTE BOILER SUPPLY SYSTEM
The boiler can manage a heating system at a fixed point delivery temperature or in climatic compensation with an external probe, managing the modulation according to the actually requested thermal load.
The boiler probe activates the system in order to pre-heat the boiler, the boiler will be put into domestic circuit mode and the deviating valve switches to the remote boiler.
1
2
INSTALLER
1 Schema meccanico impianto_R1K 50_no INAIL _EN
4
DESCRIPTION
1 EXTERNAL PROBE 2 REMOTE OPEN THERM 3CONTROL PANEL 4 REMOTE BOILER NTC PROBE
fume exhaust system
condensation
3
GAS
LOAD SYSTEM
DELIVERY SYSTEM
RETURN SYSTEM
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
13
INSTALLER
1.1.9. SYSTEM ACCESSORIES
DIVERTER VALVE KIT
The kit allows combining the thermal generator with a remote boiler for the production of domestic hot water (cod. 26097LP, fig. 1).
In this configuration, it is possible to manage the domestic circuit in an independent manner, by implementing a diverter valve which ensures the power supply of the serpentine upon the pre­heating request of the boiler.
The kit is completed with a probe for the external boiler and with a power supply cable of the diverter valve which is connected directly to the electronic board of the generator.
1. INSTALLATION
HYDRAULIC SEPARATOR
In order to always ensure to the heat generator an operation without problems related to two low heat capacities (due, for example, to closed radiators or to impurities of various type), it is strictly necessary to install a trip unit, as an alternative, a heat exchanger which separates the hydraulic circuit.
Choosing a separation system in the detriment of another is exclusively imposed by the type of the system.
In case of a new system o r in case of replacem ent of the generator with the possibility to wash the water pipes, it is recommended to install a hydraulic separator (code 26205LA, fig. 1).
The hydraulic separator creates an area with reduced load loss, which allows hydraulically rendering independent the primary and secondary circuits connected to it. With the hydraulic separator you can thus have a production circuit with constant heat capacity and a distribution circuit with variable heat capacity, operation conditions typically specific to modern air-conditioning systems.
1 Accessori impianto_R1K 50_no INAIL_EN
cod. 26097LPcod. 26205LA cod. 65-00440
fig. 1
14
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
Particular attention should be given, during the design phase, to possible temperature variations to which the circuits can be subject due to the generated mixing inside the hydraulic separator.
A secondary circuit with a heat capacity higher than the circulatory one of the primary circuit generates, in fact, by means of the hydraulic separator, a delivery temperature lower than the one of the primary circuit.
1. INSTALL ATION
INSTALLER
1 Accessori impianto_R1K 50_no INAIL_EN
15
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
INSTALLER
1.1.10. CIRCULATOR PREVALENCE/FLOW DIAGRAM
1. INSTALLATION
Wilo-Yonos PARA RS 15/7.5
H/m
8
PWM1
4770/ 5
7
PWM1
4270/ 15
6
PWM1
5
3780/ 25
4
PWM1
3280/ 35
3
PWM1
2780/ 45
PWM1
2
2280/ 55
PWM1
1780/ 65
1
PWM1
1290/ 75
PWM1
790/ 85
0
PREVALENCE (m)
0 0,5 1,0 1,5 2,0 2,5 3,0 3,5
0 0,2 0,4 0,6 0,8 1,0
20 4 6 8 10 12 14
/W
P
1
60
40
20
0
0 0,5 1,0 1,5 2,0 2,5 3,0 3,5
max.
4,0
4,0
Q/m³/ h
Q/l/s
Q/Igpm
max.
Q/m³/ h
p/kPa
80
70
60
50
40
30
20
10
0
Appliance Loss
FLOW RATE (m3/h)
1 Diagramma portata-prevalenza circol atore _R1K 50_YONOS PARA RS 15-7.5_EN
16
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
1.1.11. GENERATOR INSTALLATION
MINIMAL TECHNICAL SPACES
1. INSTALL ATION
INSTALLER
X Y
In order to allow the access inside the boiler for maintenance operations, you have to respect the minimum technical spaces indicated in figure 1.
WARNING
The incorrect slopes of the device can cause the incorrect discharge of condensate by means of the discharge duct with consequent condensate stagnation inside the condensate module.
WARNING
The boiler must be installed only on a vertical solid wall, able to sustain its weight.
WARNING
The boilers have the electrical protection degree IPX5D. The outdoor installation in partially protected environments (platform roof, balcony - see fig. 2) is allowed in compliance with the related standards. The Company is not held liable for installations in environments with a temperature under –10°C or non-compliant with the above indications.
A
H
B
A
A - 200 mm B - 300 mm X - 60 mm Y - 60 mm H - 1,000 mm
balcony/ platform roof
1,200 mm minimum
fig.1
A
SECTION A-A
1 Installazione generatore_R1K 50_EN
fig. 2
17
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
INSTALLER
WALL MOUNTING BY MEANS OF FIXING BRACKET
is slightly inclined towards the rear part (1-1.5°) in order to evacuate the condensate.
In order to fix the thermal generator on the wall, proceed as follows:
1. fix on the wall (fig. 1), using the fisher, the upper bracket;
2. hook the eyelets of the boiler into the adequate hooks (fig. 2);
3. unscrew the fixing screws of the lower bracket (fig. 3) ensuring the free sliding of the bracket (fig. 4)
4. adjust the inclination of the boiler (fig. 5) by sliding the lower bracket ensuring an inclination of the
1. INSTALLATION
WARNING
In order to avoid condensate stagnations inside the condensate module, check that the boiler
WARNING
The device must be installed only on a vertical solid wall, able to sustain its weight.
towards the boiler;
boiler, against the vertical, of about 1–1.5°.
LOWER BRACKET
fig. 3
fig. 2
fig.1
1 Installazione generatore_R1K 50_EN
fig. 5
18
fig. 4
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
LOWER BRACKET
1-1.5°
1. INSTALL ATION
INSTALLATION ON SELF-SUPPORTING FRAME
WARNING
During the installation of the heat generator, pay maximum attention to the installation of the self-supporting frame. The frame must rest on a perfectly flat surface and, when supported against the wall, the latter must be perfectly angled. The incorrect slopes of the device can cause the incorrect discharge of condensate by means of the discharge duct with consequent condensate stagnation inside the condensate module. The correct installation of the frame allows obtaining, acting on the lower bracket, a counterslope of the device against the perpendicular.
In order to mount the frame and therefore the generator, proceed as follows:
1. check the angle of the wall with the floor;
2. assemble the side profiles 3 and 4 on the pillars 1 and 2 (fig. 1);
3. assemble the side pillars 1 and 2 on the horizontal crossbeam 5;
4. assemble the central crossbeam 8 and the lower one 7;
5. complete the assembly, position the frame binding it to the wall 9 (if provided) and on the floor 10;
6. mount the upper bracket 6 and hook the eyelets of the boiler into the adequate hooks 11;
7. make sure that the frame is angled, adjust the inclination of the boiler by means of the lower bracket
(see "Wall mounting by means of fixing bracket") ensuring an inclination of the boiler, against the vertical, of about 1–1.5°;
8. complete the installation by assembling the hydraulic components.
INSTALLER
5
1
2
1 Installazione generatore_R1K 50_EN
8
4
7
3
6
9
9
10
10
10
10
11
11
fig.1
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
19
INSTALLER
1. INSTALLATION
1.1.12. HYDRAULIC CONNECTION
DANGER
Make sure that the tubes of the water and heating plant are not used as grounding system for the electrical plant. There are not suitable for such use.
WARNING
To prevent voiding the warranty and to ensure the proper operation of the boiler, please wash the plant (if possible when hot) with suitable pickling or descaling solutions in order to remove the impurities coming from tubes and radiators.
WARNING
If the boiler is installed in a hydrostatic position lower than those of the user devices (radiators, fan coils, etc.), mount the shut-off valves on the domestic water heating circuit to ease the performance of the maintenance operations if it is necessary only to empty the boiler.
DOMESTIC CIRCUIT
In order to prevent limestone build-up and damages to the domestic water heat exchanger, the hardness of the domestic supply water should not exceed 15 °f. However, please check the characteristics of the water used and install suitable treating devices.
The heat exchanger coil cleaning frequency depends on the hardness of the supply water and on the presence of solid residues or impurities inside the water that are often present in case of recently installed plants. Based on the characteristics of the infeed water, you should install suitable water treating devices, for residues presence please install a line filter.
The pressure of the cold infeed water should be between 0.5 and 6 bar. In case of greater pressure values, please install a pressure reducer upstream from the boiler.
WARNING
When connecting the equipment to water supply, avoid excessive bending and recovery operations from any off axis positioning that may damage the tubes causing leaks, malfunction or early wear.
WARNING
In order to avoid any vibrations and noises, do not use tubes with small diameters or elbows with small radius and significant cut-off of the passage sections.
WARNING
Connect the boiler safety drains to a discharge funnel. The manufacturer is not responsible for any floods due to safety valve opening in case of plant overpressure.
HEATING CIRCUIT
In order to avoid any scale or deposits on the primary exchanger, the hardness of the heating circuit infeed water should not exceed 25 °f. However, please check the characteristics of the water used and install suitable treating devices.
This treatment is mandatory if frequent episodes of return water or partial or total emptying of the plant occur.
WARNING
In case the boiler is installed as part of a low temperature circuit, please install a safety thermostat on the heating flow, which can stop the boiler activity in case of high heating flow temperature. The company assumes no liability for damage caused to persons or for failure to comply with these instructions.
1 Allacciamento idraulico_combinata_EN
20
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
1. INSTALL ATION
INSTALLER
1.1.13. CHARACTERISTICS OF THE
Water treatment
WATER OF THE SYSTEM
In order to preserve the integrity of the water-
For a correct operation of the system, it is necessary to make sure that:
1. The system does not present losses or that the most obvious are at least eliminated;
2. If an automatic filling system is present, a litre meter must be installed in order to precisely know the extent of any losses;
3. The filling in of the system and the top ups are performed with softened water in order to reduce the total hardness. The water must also be treated in order to maintain the pH within the provided threshold so as to avoid corrosion phenomena.
4. Either on new systems or on replacements, the system must be fitted with efficient systems which ensure the elimination of the air and impurities: Y filters, micro impurity separators and micro bubbles of air separators;
5. Avoid draining the water of the system during the routine maintenance even if it is about apparently insignificant quantities: for example, in order to clean the filters, provide the system with adequate shut-off valves;
1 Riempimento dell'impianto_MIAH4_R1K 10 0_v.1_ EN
6. Always perform an analysis of the water of the system before opening the communication between the new generator and the system, in order to establish if the parameters present in the water indicate the need to fully drain the system, to use the water already present in the system or to chemically wash the system using utility water adding a detergent when it is suspected that the system might be dirty or particularly clogged and at the next loading with new treated water.
fume exchanger and to guarantee optimal thermal exchanges, it is necessary that the water of the primary circuit, circulating inside the exchanger of the condensate boiler, has the characteristics defined and constant in time. To obtain this, it is fundamental to perform a series of system preparation and maintenance operations such as:
• washing the system;
• check the characteristics of the water of the system;
The type of treatment to be performed will be chosen based on the characteristics of the water to treat, of the type of system and on the requested purity limits
Oxygen
A certain amount of oxygen always enters the system, both during the filling phase and during the use in case of reintegration or presence of hydraulic components without oxygen barriers. The reaction between the oxygen and the stainless steel creates corrosion and forms sludge. While the water fume exchanger is made of stainless steel, and therefore it is not subject to corrosion, the sludge created in the carbon steel system is deposited in the warm points, including the exchanger. This has the effect to reduce the heat capacity and thermally insulate the active parts of the exchanger, which might cause damages.
The precautions to limit the phenomena are:
- Mechanical systems: a deaerator combined with a sludge remover, correctly installed, reduce the quantity of oxygen circulating inside the system.
- Chemical systems: the additives allow the oxygen to dissolve in water.
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
21
INSTALLER
Hardness
The filling and make-up water hardness brings a certain amount of limestone into the system. It attacks the warm parts of the exchanger, thus creating load losses and thermal insulation losses on the active parts. This phenomena can cause damages.
The filling and make-up water of the system, if it does not fall under the values indicated below, should be softened. Moreover, additives can be added in order to maintain the limestone into the solution. The hardness must be periodically checked and registered.
1. INSTALLATION
Acidity 7 < pH < 8.5 Conductivity < 400 μs/cm (at 25°C) Chlorides < 125 mg/l Iron < 0.5 mg/l Copper < 0.1 mg/l
If the above indicated limits are exceeded, a water must be chemically treated.
The type of treatment to be performed will be chosen based on the characteristics of the water to treat, of the type of system and on the requested purity limits.
1 Riempimento dell'impianto_MIAH4_R1K 10 0_v.1_ EN
22
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
1. INSTALL ATION
INSTALLER
1.1.14. SYSTEM FILLING
WARNING
For system filling use only clean tap water. In order to prevent limestone build-up and damages to the domestic water heat exchanger, the hardness of the domestic supply water should not exceed 15° Fr. However, please check the characteristics of the water used and install suitable treating devices.
WARNING
If the system is filled by adding ethylene glycol-type chemical agents you have to install on the loading system a hydraulic trip unit in order to separate the heating circuit from the domestic circuit.
Before powering up the boiler, fill the system as follows:
tap until the pressure gauge reaches the design pressure.
fig. 1
1. slightly loosen the cap of the jolly valve placed
on the top of the condensing block to release the air form the top of the system (fig.1);
2. check that the jolly valves vent the air present
in the system are not blocked
3. open the general domestic water input tap and
load the system by exhaling all the air;
4. use pressure gauge present in the system to
1 Riempimento dell'impianto_MIAH4_R1K 10 0_v.1_ EN
make sure that the system pressure reaches the design value;
5. after performing this operation, make sure
that the loading tap is properly closed.
6. Open the air relief valves of the radiators and
check the air removal process. When the water starts to leak close the radiators air relief valves.
7. If after performing these operations you
observe a decrease of the water pressure inside the system, open once again the loading
23
R1K 50 - RAD - ING - Manuale - 1801.1_SK.3
Loading...
+ 53 hidden pages