Radiant R1K 34, R1K 34B Installation, Use And Maintenance Manual

R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
Installation, Use and Maintenance Manual for model
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may result,
-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
-WHAT TO DO IF YOU SMELL GAS >Do not try to light any appliance. >Do not touch any electrical switch; do not use any phone in your building. >Immediately call your gas suppl ier fr om an out side phone. F ollow the ga s supplier ’s instructio ns. >If you cannot reach your gas supplier, call the fire department.
-Installation and service must be performed by a qualified installer, service agency or the gas supplier.
R1K 34 /B
2
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
SUMMARY
SUMMARY
INTRODUCTION 4
1. INSTALLER SECTION 7
1.1. INSTALL ATION 8
1.1.1. GENERAL INSTALLATION WARNINGS 8
1.1.2. BOILER LOCATION ENVIRONMENTAL REQUIREMENTS 8
1.1.3. REFERENCE LEGISLATION 9
1.1.4. UNPACKING 10
1.1.5. OVERALL DIMENSIONS (inch) 11
1.1.6. PIPING LAYOUT/IDENTIFICATION 11
1.1.7. HYDRAULIC CONNECTION KIT 11
1.1.8. POSITIONING AND CLEARANCES TO COMBUSTIBLE MATERIAL AND SERVICE CLEARANCES 12
1.1.9. CIRCULATOR PERFORMANCE CURVES 13
1.1.10. WAT ER CONNECT ION S 14
1.1.11. PRESSURE RELIEF VALVE KIT 15
1.1.12. SYSTEM FILLING 16
1.1.13. FILLING THE CONDENSATE COLLECTION SIPHON 17
1.1.14. ANTI-FREEZE PROTECTION 19
1.1.15. GA S CONNEC TION 20
1.1.16. ELECTRICAL CONNECTION 20
1.1.17. POW ER SUP PLY 21
1.1.18. OPTIONAL ELECTRICAL CONNECTIONS 22
1.1.19. DHW SENSOR INSTALL ATION 24
1.1.20. VENTING 25
1.1.21. TYPES OF EXHAUST SYSTEMS 27
1.1.22. TABLE 1: ALLOWABLE VENT LENGTHS 32
2. SEZIONE CENTRO ASSISTENZA 33
2.1. FIRST START-UP 34
2.1.1. PRELIMINARY OPERATIONS FOR FIRST START-UP 34
2.1.2. BOILER COMMISSIONING 35
2.1.3. CO2 VALUE CHECK AND CALIBRATION 36
2.1.4. ACCESSING AND PROGRAMMING THE PARAMETERS 37
2.1.5. DIGITECH CS (MIAH402) PARAMETERS TABLE 39
2.1.6. COMBUSTION BLOWER FREQUENCY/HEAT CAPACITY DIAGRAM 45
2.2. MAINTENANCE 46
2.2.7. GENERAL MAINTENANCE WARNINGS 46
2.2.8. TECHNICAL DATA 47
2.2.9. TECHNICAL ASSEMBLYTECHNICAL ASSEMBLY 49
3
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
SUMMARY
2.2.10. INTERNAL PIPING SCHEMATIC 50
2.2.11. 3-WAY VALVE OPERATION 51
2.2.12. WIRING DIAGRAM 52
2.2.13. ACCESSING THE BOILER 53
2.2.14. ACCESSING THE ELECTRONIC BOARD 54
2.2.15. SYSTEM EMPTYING 55
2.2.16. FAULT SIGNALLING CODES 56
2.2.17. ACTIVE FUNCTIONS SIGNALLING CODES 59
2.2.18. CONVERSION TO A DIFFERENT GAS TYPE 60
2.2.19. POSITIONS OF THE ELECTRODES 61
3. USER SECTION 63
3.1. USE 64
3.1.1. GENERAL USE WARNINGS 64
3.1.2. CONTROL PANEL 69
3.1.3. DISPLAY ICONS 70
3.1.4. INFO MENU DISPLAY DATA 71
3.1.5. START-UP 72
3.1.6. OPERATING MODE 72
3.1.7. INFORMATIONAL NOTE ON ANTI-FREEZE FUNCTION 73
3.1.8. SYSTEM FILLING 74
3.1.9. FAULT SIGNALLING CODES 75
3.1.10. ACTIVE FUNCTIONS SIGNALLING CODES 77
3.1.11. MAINTENANCE 78
3.1.12. COV ER CLE ANING 78
3.1.13. DISPOS AL 78
4
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
2.
INTRODUCTION
WARNING
Before star ting any operation it is mandator y to read this instruction manual, in relation to the activities performed as described in each relevant section. Proper operation and optimal performance of the boiler are ensured by strict compliance with all the instructions given in this manual.
The installation, use and maintenance manual is an integral and essential part of the product and must be delivered to the user.
MANUAL USERS
The manual users are all those who install, use and maintain the boiler.
The boiler must be used and accessed only by qualified operators that fully read and understood the use and maintenance manual, paying particular attention to the warnings.
READING AND SYMBOLS OF THE MANUAL
To ease the understanding of this manual, recurrent symbols where used, in particular:
› On the outer margin of the page is placed a
thumb index indicating the type of user to which the instructions in that section address.
› The titles are differentiated by thickness and
size in accordance with their hierarchy.
› The images contain important parts described
in the text, marked with numbers or letters.
› (See chap “chapter# name”): this entry indicates
another section in the Manual that you should refer to.
› Device: this term is used referring to the boiler.
DANGER
It identifies information related to a general danger that if not complied with, may cause serious personal damage or even death.
ATTENTION
It identifies information that if not complied with may cause small or medium level burns to the person or serious damage to the boiler.
WARNING
It identifies a precaution information that must be observed in order to avoid damaging the machine or various parts.
MANUAL STORAGE
The manual must be stored carefully and replaced in case of deterioration and/or low legibility.
If you misplace the use and maintenance manual, you can request a copy from the Technical Support Center. It is important to provide the model number and serial number of the unit which is found on the inside surface of the right panel.
INTRODUCTION
5
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
2.
MANUFACTURER WARRANTY AND RESPONSIBILIT Y
The Manufacturer’s warranty is provided only through its own authorized Technical Support Centers, listed for each Region on the site www.radianthydronics.com, and covers all manufacturing defects at the time of sale.
The technical and functional features of the unit are ensured when proper installation and miantenance is carried out. Conditions of Manufacturer’s warranty includes the following:
1. The customer is aware of and follows instructions contained in the manuals that accompany the product.
2. Annual service check up is required to keep warranty valid.
3. The unit is installed and operated in the conditions in which it is designed to.
For more information on the warranty validity, its duration, the obligations and the exemptions, please consult the First start-up certificate attached to this manual.
The manufacturer reserves:
› the right to modify the tools and relative
technical documentation without any obligation to third parties;
› the material and intellectual ownership of
this manual and forbids its distribution and duplication, even partial, without prior written authorization.
PRODUCT CONFORMITY
RADIANT BRUCIATORI spa with reference to ANSI Z21.13-2014 • CSA 4.9-2014 GAS FIRED LOW PRESSURE STEAM AND HOT WATER BOILERS, declares that its gas boilers are professionally manufactured.
The materials used such as copper, brass, stainless steel create a homogeneous, compact and functional assembly, easy to install and maintain. The boiler is equipped with all accessories necessary to provide a dependable independent heating unit. All boilers are tested and delivered with a quality certificate signed by the testing department.
INTRODUCTION
The installation operations described in this section should
be performed only by qualified personnel, having the
appropriate technical training in the field for the installation
and maintenance of components of civil and industrial
domestic hot water production and heating plants.
1. INSTALLER SECTION
1. INSTALLER SECTION
8
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1. INSTALLATION
1.1.1. GENERAL INSTALLATION WARNINGS
This boiler must be installed in accordance with local codes, if any; if not, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CAN/CSA B149.1, as applicable.
WARNING
This unit may be used only for the purpose for which it has been designed: heat water to a temperature below boiling point at atmospheric pressure. Any other use is considered wrong and dangerous. The manufacturer is excluded from any contractual or out of contract responsibility for damage caused to people, animals or property due to errors during installation.
WARNING
This boiler should be installed only by qualified service technician, having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water production and heating plants.
WARNING
After having removed the packing, make sure the equipment is intact. In case of doubt, do not use the equipment and contact the supplier.
BEFORE INSTALLING THE BOILER, THE INSTALLER MUST MAKE SURE THAT THE FOLLOWING CONDITIONS ARE PRESENT:
› The unit is connected to a heating plant and a
water supply network appropriate for its power and performance.
› The location must be properly vented through
an air vent.
The air vent must be placed at floor level to prevent it from being obstructed, protected by a grid that does not hamper air flow.
› The unit is suitable for use with the type of
gas available by checking the boiler data plate placed on the inner side of the front casing.
› Make sure that the gas lines are properly sealed
without any gas leaks.
› Make sure that the grounding system works
properly.
› Make sure that the electrical system is suitable
for the maximum power required by the equipment, value indicated on the data plate.
WARNING
Use only original RADIANT optional or kit
accessories (including electrical).
1.1.2. BOILER LOCATION ENVIRONMENTAL REQUIREMENTS
The boiler shall be installed so the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacement, etc.).
The boiler installed using inside air supply must provide provisions for Combustion Air and Ventilation Air in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z 223,1/NFPA 54, or section 7,2, 7.3, or 7.4, of CAN/CSA B 149, Installation Codes, or local codes having jurisdiction.
Where an exhaust fan or any other air consumption appliance is installed in the same space as the
9
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
boiler, sufficient air openings must be available to provide fresh air when all appliances are operating simultaneously. It is essential that in rooms where the boiler is installed to provide as much air as required by normal combustion of the gas consumed by the varius appliances. Consequently, it maybe necessary to make openings in the walls to provide air inlet into the rooms.
Application where air from the structure is used to supply combustion air for the unit, the following openings are required:
1. Have a total free section of a least 25 mm2 every kW (1 in2 for every 1000 Btu/hr) of heat input, with a minimum of 100 cm2 (15.5 in2);
2. Where required by code or when required for additional opening must be provided at the highest practical elevation.
With a hermetically sealed combustion chamber and air supply circuit from outdoors, the boiler may be installed in any room in the home. Keep boiler area clear and free from combustible materials, gasoline and other flammable vapors and liquids.
WARNING
If the temperature in the boiler installation location goes below 14°F centigrades, please fill the system with anti-freeze liquid and insert and electrical resistances kit (see 1.1.14 ‘ANTI-FREEZE PROTECTION’).
1.1.3. REFERENCE LEGISLATION
This boiler must be installed in accordance with local codes, if any; if not, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CAN/CSA B149.1, as applicable.
10
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.4. UNPACKING
WARNING
Please unpack the boiler just before installing it. The Company is not responsible for the damages caused to the device due to incorrect storage.
WARNING
The packing elements (cardboard box, wooden crate, nails, fasteners, plastic bags, expanded polystyrene, etc.) are dangerous and must be kept out of the reach of children, they should be biscarded properly.
To unpack the boiler, proceed as follows:
› Place the packed boiler on the floor (fig. 1-A)
and remove the fasteners opening the four flaps of the box outwards.
› Turn the boiler at 90° holding it with your hand
(fig. 1-B).
› Lift the box (fig. 1-C) and remove the guards (fig.
1-D).
C
B
D
A
fig. 1
11
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.5. OVERALL DIMENSIONS (inch)
1.1.6. PIPING LAYOUT/IDENTIFICATION 1.1.7. HYDRAULIC CONNECTION KIT
An hydraulic kit equipped is available and supplied by RADIANT upon demand.
11.8
6.1
5.3
5.9
12.9
16
25.2
1.9 5.8 3.1 4 1.2
5.7 6.9
1.6
4.2
R
RB
G F A
AB
3.4
VS
R F
A
fig. 2
fig. 3
fig. 4
R- RETURN Ø 3/4
G- GAS Ø 3/4 NPT
F- COLD Ø 1/2
A- INFEED Ø 3/4
RB- REMOT E D.H.W. CYLINDER RETURN Ø 3/4 NPT
AB- REMOTE D.H.W. CYLINDER FLOW Ø 3/4 NPT
R - CENTRAL HEATING RETURN Ø 3/4 NPT F - COLD WATER INLET Ø 1/2 SWEAT A - CENTRAL HEATING SUPPLY Ø 3/4 NPT
12
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.8. POSITIONING AND
CLEARANCES TO COMBUSTIBLE MATERIAL AND SERVICE CLEARANCES
The boiler must be installed only on a vertical solid wall, able to sustain its weight.
This boiler has been certified to be installed with “0” clearances to combustible material.
In order to allow the access inside the boiler for maintenance operations, follow the minimum service clearances indicated in figure 5.
To facilitate the installation, the boiler is provided with a jig that allows setting in advance the connections to the tubes providing the ablility of connecting the boiler to completed masonry structure. To position the unit, proceed as follows (see fig. 6):
1. Trace a line using a spirit level (min. length 9.8 inch) on the installation wall.
2. Place the top of the jig along the traced line respecting the distances of the water connections; then
mark the two points to insert the fasteners, then trace the points for the exhaust vent;
3. Remove the jig and drill the wall;
4. Fix the wall bracket using the screws provided. Hang the unit on the bracket.
3
1
42
70 80 10249 3178
Ø80
Ø125
Ø100
35826 26
54 54
821
681
699
302
785
H
B
A
Y
X
A - 7.8 inch B - 11.8 inch X - 2.3 inch
Y - 2.3 inch
H - 36 inch
fig. 5
fig. 6
13
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
WARNING
Using a level, make sure the boiler is properly level (see fig. 6) to allow the condensate to drain.
1.1.9. CIRCULATOR PERFORMANCE CURVES
fig. 7
UPSO 15-58 AOKR
III
II
I
H (ft)
Q (US gpm)
0 2 4 6 8 10
22 20
18
16
14 12
10
8
6 4
2
0
PRE VALENCE (m)
FLOW RATE US gpm
III
Circulator priority maximum speed
- - - - Appliance Loss fig. 8
14
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.10. WATER CONNECTIONS
DANGER
Make sure that the tubes of the water and heating unit are not used as grounding system for the electrical unit. There are not suitable for such use.
WARNING
To prevent voiding the warranty and to ensure the proper operation of the boiler, wash the unit (if possible when hot) with suitable descaling solution to remove the impurities coming from tubes and radiators.
WARNING
If the boiler is installed in a hydrostatic position lower than those of the user devices (radiators, fan coils, etc.), mount the shut-off valves on the domestic water heating circuit to ease the performance of the maintenance operations if necessary to only empty the boi ler.
WARNING
When connecting the equipment to water supply, avoid excessive bending and recovery operations from improper positioning that may damage the tubes causing leaks, malfunction or premature wear.
WARNING
In order to avoid any vibrations and noises, do not use tubes with small diameters or elbows with small radius and significant cut-off of the passage sections.
DOMESTIC CIRCUIT
In order to prevent limestone build-up and damages to the domestic water heat exchanger, the hardness of the domestic supply water should not exceed 8.4° dh (degrees hardness). However, please check the characteristics of the water used and install suitable treating devices.
The heat exchanger coil cleaning frequency depends on the hardness of the supply water and on the presence of solid residues or impurities inside the water that are often present in case of recently installed plants. Based on the characteristics of the inlet water, you should install suitable water
treatment devices, for residues presence. Please install an inline filter.
The pressure of the cold inlet water should be between 7.2 psi (0.5 bar) and 150 psi (10.34 bar). In case of greater pressure values, please install a pressure reducer upstream from the boiler.Please refer to local jurisdictions on the requirements for cold inlet water pressure.
HEATING CIRCUIT
In order to avoid any scale or deposits on the primary exchanger, the hardness of the heating circuit inlet water should not exceed 14° dh (degrees hardness). However, please check the characteristics of the water used and install suitable treatment devices.
To protect the central heating system from damaging corrosion, flakes or deposits it is important to clean the hydronic system using cleaners such as Fernox F3 Cleaner. For long term protection against corrosion and deposits, the use of inibitor (such as Fernox F1 inhibitor) is required after cleaning and flushing of the hydronic system. It is important to monitor the concentration of the inibitor during commisioning and during servicing of unit.
WARNING
Failure to clean the central heating system or add adequate inibitor invalidates the compliance warranty.
Connect the boiler safety drains (heating circuit safety valve) to a discharge funnel. The manufacturer is not responsible for any floods due to safety valve opening in case of unit excessive presure build up.
WARNING
In case the boiler is installed as part of a low temperature circuit, please install a safety thermostat on the heating flow, which can stop the boiler activity in case of high heating flow temperature. The company assumes no liability for damage caused to persons or for failure to comply with these instructions.
15
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.11. PRESSURE RELIEF VALVE KIT
To complete the installation of the boiler, you must install an approved 3/4”, maximum 30 PSI (2 bar) pressure relief valve on the heating return.
A hydronic kit equipped with hydronic connections and safety valve (see ‘VS’ fig. 9) is available and supplied by RADIANT.
ATTENTION
The pressure relief valve MUST TO BE
INSTALLED in any case.
ATTENTION
The pressure relief valve should be placed as close to the boiler as possible. No other valve should be placed between the pressure relief valve and the boiler.
DANGER
Improper installation of the pressure relief valve may result in property damage, personal injury, or death. Follow all instructions and guidelines when installing the pressure relief valve. The valve should be installed only by a licensed professional.
When installing the valve, follow these guidelines:
› Direct the discharge piping of the pressure relief
valve so that hot water will not splash on anyone or any nearby equipment.
› Attach the discharge line to the pressure relief
valve and run the end of the line to within 6-12” (150-300mm) of the floor.
› Ensure that the discharge line will allow free and
complete drainage without restriction. Do not install a reducing coupling or other restriction on the discharge line.
VS
R F
A
fig. 9
16
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.12. SYSTEM FILLING
WARNING
For system filling use only clean tap water.
WARNING
If the system is filled by adding ethylene glycol-type chemical agents it is suggested to install a system fender on the hydronic system in order to separate the heating circuit from the domestic circuit.
Before powering up the boiler, fill the system as follows:
1. Make sure the circulator is not blocked;
2. Slightly loosen the cap of the circulator air
eliminator (1-fig. 10) to release the air from the system;
3. Slightly loosen the cap of the air eliminator
placed on the top of the condensing block (fig. 12) to release the air form the top of the system;
4. Open the feeding tap “R” (fig. 11);
5. Release all the air;
6. Use pressure gauge “M” (fig. 11) to make sure
that the system pressure reaches 1.2 bar (fig.
13);
7. After performing this operation, make sure
that the loading tap “R” (fig. 12) is properly closed.
1
2
M
R
fig. 10
fig . 11
fig. 12
17
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
8. Unscrew the circulator cap (2-fig.10) to release any air bubbles and close it to prevent water leakage;
9. Open the air relief valves of the radiators and check the air removal process. When the water starts to leak close the radiators air relief valves.
10. If after performing these operations you observe a decrease of the water pressure inside the system, open once again the loading tap “R” until the pressure gauge indicates the value of 1.2 bar (fig. 13)
1.1.13. FILLING THE CONDENSATE
COLLECTION SIPHON
Before starting the boiler you have to fill the condensate collection siphon in order to avoid fuel back up through the siphon.
Fill the condensate collection siphon as follows (see fig. 14):
› Unscrew the “T” cap from the siphon, fill three
quarters of the the siphon with water and screw the “T” cap back in;
› Connect the dedicated flexible condensate
draining tube “P” to a waste disposal system. The condensate can be drained directly in the sewer system by inserting an easily serviceable siphon.
WARNING
After the fir st months of boiler operation, it is recommended to clean the condensate trap, to eliminate possible deposits coming from the first flow of the condensate inside the boiler technical components. These deposits could cause a malfunctioning of the trap.
P
T
fig. 13
fig. 14
18
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
CONDENSATE DRAIN
The boiler produces a significant amount of condensate during operation. This condensation has an acidic pH of 3-5. Follow all local codes and regulations when disposing of condensate from the boiler.
The project engineer should consider the possibility of installing systems to eliminate the acidic condensation, according to system power and buildings’ use.
The system should be designed to avoid the condensate freezing. Before the boiler commissioning, check the correct condensate flow.
WARNING
Check before connecting the condensate
trap to the drain pipe, for the proper gradient of boiler as described in paragraph “1.1.8 POSITIONING AND MINIMAL TECHNICAL SPACES”.
WARNING
Properly connect the siphon condensate from the boiler to a drain system having adequate slope. Where possible, you should make this connection using transparent tubing to check for proper condensate drainage and avoid stagnation that could cause hazardous backflow of the condensate into the boiler.
To connect the condensate drain use only corrosion-resistant material for the drain line.
CONDENSATE NEUTRALIZER KIT
The condensate neutralization system neutralizes the condensate created by the products of combustion.
Acid condensate, introduced into the neutralization box, follows a two-step set course. First phase: nitrates and sulphates filtration through active carbons contained in the first part of the carbon site pipe. In the second phase the pH rises.
The acidity of the condensate can be controlled through the use of appropriate tools for the determination of Ph, such as the litmus paper.
Neutralized condensate can then be routed to the drainage system.
MAINTENANCE
The pH value of the condensate after the neutralizer must be in between <5,5 – 9,5>.
Every six months, you need to determine the pH of the condensate treated in the neutralizer. Litmus paper or a digital instrument can be used to measure the pH level.
Neutral point is on the 6,8-7 value; in case of lower value the condensate is acid, in case of a higher value it is basic.
If necesssary, replace the active carbon and the reagent granulate.
19
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.14. ANTI-FREEZE PROTECTION
The boiler is protected against freezing using the electronic board design with a function that start the burner and heat the water in the boiler when their water temperature goes below the minimum pre-set values, protecting the boiler up to an external temperature of 14 °F (-10 °C).
The device starts when the hot water temperature goes below 41 °F (5 °C), automatically starting the burner until the water reaches the temperature of 86 °F (30 °C).
The system starts even if display appears “OFF”, as long as the boiler is connected to the power (120 V) and gas supply.
For long periods of standby, please empty the boiler and the plant.
If the temperature goes below 14 °F (-10 °C) centigrades, please fill the plant with anti-freeze liquid (CLEANPASS FLUIDO AG cod. 98716LA) and insert and electrical resistances kit (cod. 65-
00200).
DILUTION PERCENTAGE OF CLEANPASS FLUIDO AG
ANTIFREEZE ­ETHYLENE GLYCOL
TEMPERATURE FREEZING POINT
(%) VOLUME °F (°C)
20 18 (-7.5 ) 30 8.6 (-13) 35 -0. 4 (-18) 40 -8.5 (- 22.5) 45 -18 (-28) 50 -28 (-33.5) 55 -44 (-42)
60 -58 (-50) RECOMMENDED MINIMUM PERCENTAGE OF GLYCOL : 20 %
20
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.15. GAS CONNECTION
WARNING
The gas piping must be installed according to all local and state codes, or in absence of local and state codes, with the latest “Natural gas and propane installation code”, CAN/CSA-B 149.1 or “National Fuel Gas Code”, ANSI Z223.1 (NFPA 54). Consult the “Natural gas and propane installation code” or “National Fuel Gas Code” for the recommended gas pipe size of other materials.
BEFORE PERFORMING THE GAS CONNECTION, MAKE SURE THAT:
› The gas line size and length meets requested;
› The gas line is equipped with all safety and
control devices required by the standards in force;
› The internal and external seals of the gas inlet
lines of the plant are checked;
› The device is suitable for use with the type of
gas available by checking the boiler data plate (located on the inner side of the front casing. If they do not match you must take the necessary measures to adapt the boiler to another type of gas (see 2.2.18 CONVERSION TO A DIFFERENT GAS TYPE);
› The gas supply pressure falls within the values
indicated on the data plate.
1.1.16. ELECTRICAL CONNECTION
DANGER
The equipment is electrically safe only if it is properly connected to an efficient grounding system, performed in compliance with the safety standards in force (National Electrical Code, ANSI/ NFPA 70 and or the Canadian Electrical Code Part I, CSA C22.1, Electrical Code). You should check this essential safety requirement. If in doubt, request an accurate check of the electrical system performed by qualified staff, as the manufacturer is not responsible for any damages caused by lack of grounding system.
› Make sure that the electrical systems is
suitable for the maximum power consumed by the equipment, value indicated on the data plate.
› Make sure that the cables section is appropriate
for the maximum power consumed by the equipment.
› The equipment works with alternating current
of 120 V and 60 Hz. The electrical connection must be installed using an all-pole switch with an opening of at least 0.12 in (3 mm) between contacts placed upstream from the device.
WARNING
Make sure that the phase and neutral cables connection is installed in compliance with the wiring diagram (see 1.1.17 POWER SUPPLY).
WARNING
It is strictly forbidden to use adaptors, multiple plugs and/or extensions for the general power supply of the equipment from the electrical supply.
21
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.17. POWER SUPPLY
To power the boiler connect the electrical cables to the terminal inside the control panel as follows:
DANGER
Cut off the voltage from the main switch.
› remove the boiler's front casing (refer to 2.2.13
ACCESSING THE BOILER).
› loosen the two screws and remove the plate “A”
(see fig. 15).
› after removing the plate, connect the electrical
cables to terminal “B” (see fig. 15):
· the yellow/green cable to the terminal marked with grounding symbol “ ”.
· the blue cable to the terminal marked with “N”.
· the brown cable to the terminal marked with “ L”.
After performing these operations, remount plate “A” and the front casing.
Note: A 3-prong plug is provide with every unit and the above wiring has been performed.
L
N
SeSe
A
TaTa
B
fig. 15
WHITE YELLOW/GREEN
BLACK
22
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.18. OPTIONAL ELECTRICAL
CONNECTIONS
The cables should be inserted inside the boiler using the cable glands ‘P1’ and ‘P2’ placed under the board (see fig. 16). Make a hole on the cable gland, smaller than the cable diameter, to make sure that the air cannot pass through.
To wire the options below:
• (SE) EXTERNAL TEMPERATURE PROBE COD. 73518L A
• (TA) ENVIRONMENT THERMOSTAT
• (CR) REMOTE CONTROL OPEN THERM COD. 40­00017
use the terminal placed inside the control panel as follows:
DANGER
Shutoff the voltage from the main switch.
› Remove the front casing of the boiler (see 2.2.13
ACCESSING THE BOILER); unscrew the screws and remove plate “A” (see fig. 16-B).
› After removing the plate, connect the electrical
cables to terminal “B” (see fig. 16-B):
· For the external temperature Probe connect the two non-polarized conductors to the Se­Se contacts.
· For the environment Thermostat or Remote control, first remove the bridge on the Ta­Ta contacts and then connect the two non­polarized conductors to the Ta-Ta contacts.
After performing these operations, remount plate “A” and the front casing.
NB: In case of simultaneous presence of external probe and
remote control, the modulation board only sends the external
temperature value to the remote device without using it for
modulation.
The communication between board and remote control takes
place independently from the boiler’s operating mode and after
establishing the connection, the used interface on the board is
disabled and the display shows the symbol ‘ ’.
P1 P2
L
N
SeSe
A
TaTa
B
SE
TA
CR
fig. 16-B
fig. 16
23
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
To wire the options below:
• (PM) MODULATING PUMP
• (TP) DOMESTIC HOT WATER PRE-HEATING DEACTIVATION TIMER
• (CT) TELEPHONE DIALER
• BUS 0-10V
• (SVZ) CONTROL BOARD FOR AREA VALVES CONNECTED TO A REMOTE CONTROL COD. 65­00030
Use the electronic board placed inside the control panel as follows:
DANGER
Shutoff the voltage from the main switch.
› Remove the boiler's front casing (refer to 2.2.13
ACCESSING THE BOILER).
› Remove the crankcase of the control panel (see
2.2.14 ACCESSING THE ELECTRONIC BOARD).
› After removing the crankcase, connect the
items below to the electronic board (see fig. 17):
After performing these operations, remount the crankcase and the front casing.
TP
CT
BUS 0-10V
GND
BUS+
11
10
98
7
12
13
14 15
16 17
M12
M9
M7
M5
M2
M4
M8
M10
M15
M16
1
2
3
4
57
61 60 59 58
4443424140
39
38
3736353433
32
31
30
29
28
27
26
MIAH4
bl
br
PM
SR
62
63
64
65
66
67
68
51
52
53
54
55
56
5
6
M13
M14
o
o
bk
bk
bl
br
120 V - 60 Hz
L
N
VZR
VZ2 VZ1
FC FC
TAZ 2
TAZ 1
SRB
N
1 2 3
4 5 6
9 8
7
M1
M4
M2
M3
SVZ
L
gy
o
r
bk
COD.40-00133
fig. 17
SR: RETURN PROBE FC: AREA VALVES LIMIT SWITCH
SRB: REMOTE LED FOR SIGNALLING BOILER LOCKOUT GY: G RE Y
TAZ1: ENVIRONMENT THERMOSTAT AREA 1 O: ORANGE
TAZ 2: ENVIRONMENT THERMOSTAT ARE A 2 BK: BLACK
VZ1: AREA 1 VALVE BR: BROWN
VZ2: ARE A 2 VALVE BL: LIGHT BLUE
VZR: REMOTE CONTROLLED AREA VALVE R: RED
24
R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
1. INSTALLATION
INSTALLER
1.1.19. DHW SENSOR INSTALLATION
To install the DHW sensor inside the remote water tank, please proceed as follows:
Remove the boiler front case panel (see Paragraph ACCESSING THE BOILER);
Grasp the left and right control panel support brackets and pull them outwards, at the same time rotating the panel downwards;
Take the 8 m. length DHW sensor cable (see C-figure), located onto the boiler bottom plate, and insert the sensor inside the water tank sensor holder.
Once this operation has been completed, rotate the control panel upwards and install the front case panel back to its original position.
C
Loading...
+ 56 hidden pages