Radiant HL2-DS-30-65, HL2-DS Series, HL2-DS-30-80, HL2-DS-30-100 Installation Manual

Page 1
!
!
HL2-DS Series
Installation Manual
The HL2-DS Series Infrared Tube Heater is a positive pressure, two-stage radiant heater system designed
for unvented use outdoors. This manual provides specic information related to the HL2-DS series
models. All persons involved with the installation, operation, and maintenance of the heater system must read and understand the information in this manual.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
re, or property damage.
In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater thermostats or, in the absence of such thermostats, in a conspicuous location.
Not for residential use! Do not use this heater in the home, sleeping quarters, attached garages, etc. Installation of a commercial tube heater system in
residential indoor spaces may result in property damage, serious injury, asphyxiation, or death.
For Your Safety
If you smell gas:
• Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s phone.
• Do not touch any electrical switch. • Follow the gas supplier’s instructions.
• Do not use any phone in your building. • If you cannot reach your gas supplier, call the re department.
INSTALLER: Present this manual to the end user.
Keep these instructions in a clean and dry place for future reference.
Model#: ______________________ Serial #: _____________________________
(located on rating label)
LIOHL2DS-Rev. 12917
Print: 1M-10/18 (CDS)
Replaces: 5c-04/18 (WHI)
Page 2
HL2-DS Series
Contents
1.0 Introduction.............................................................................3
Overview..........................................................................3
Heater Components ..............................................................3
Specications.....................................................................3
Safety Labels and Their Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0 Safety ...................................................................................6
Applications ......................................................................6
Standards, Certications, and Government Regulations ..........................7
Clearances to Combustibles ......................................................8
3.0 Installation .............................................................................10
Design Considerations and Prechecks...........................................10
Recommended Mounting Heights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Heater Assembly Instructions....................................................12
Heater Placement and Suspension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Sway Bracing for High Air Movement and Outdoor Applications .................17
Outdoor Unvented Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Gas Supply Installation Instructions..............................................19
Installation of the Gas Line to the Heater .........................................21
Leak Testing .....................................................................24
Electrical Requirements and Wiring Diagrams....................................25
Field Wiring Supply Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Thermostat Connection..........................................................27
4.0 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sequence of Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.0 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.0 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Routine Maintenance and Inspection.............................................34
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.0 Parts .................................................................................36
Burner Assembly Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Tube and Reector Components.................................................37
Limited Warranty Terms and Conditions..........................................38
Kit Contents Check List ..........................................................40
2
Page 3
HL2-DS Series
1.0 Introduction Overview Heater Components Specications
1.0 Introduction
Overview
The intent of this manual is to provide information regarding general safety, installation, operation, and maintenance of this radiant tube heater. You must read and understand all instructions and safety warnings before installing or servicing the radiant tube heater.
Heater Components
Prior to installation, verify that the heater’s gas type and voltage (as listed on the rating plate) match that of your application. Also verify that you have received all heater components included with your radiant tube heater. Refer to page 40 for a list of the kit contents for your series heater. Materials not included in the heater kit contents (e.g., screws, terminals, etc.) are the responsibility of the installer. Notify your product representative or Detroit Radiant Products of any discrepancy or missing kit contents prior to installing unit.
Specications
Chart 1.1 HL2-DS Specications
Radiant
Gas Type Model Number
HL2-DS-30-65 Nat. or Prop. 65,000 50,000 16’-4” 170 9’ to 16’ 20.2 4
HL2-DS-30-80 Nat. or Prop. 80,000 52,000 16’-4” 170 9’ to 16’ 20.2 4
HL2-DS-30-100 Nat. or Prop. 100,000 65,000 16’-4” 170 9’ to 16’ 20.2 4
* Typical or recommended mounting heights are provided as a guideline. Actual conditions may dictate
variations from this data.
(select
one)
BTU/H
(High
Fire)
BTU/H
(Low
Fire) Length
Unit
Weight
(lbs.)
Recommended
Mounting
Height*
Surface
Area (sq.
ft.)
Sections
36”
Bae
3
Page 4
!
LLTCL016b-1M-08/17 (CDS)
1.0 Introduction Safety Labels and Their Locations
HL2-DS Series
WARNING
Read and understand all safety information and warnings in this manual before installation, operation, and maintenance of the radiant tube heater system.
Safety Labels and Their Locations
Product safety signs or labels should be replaced by the product user when they no longer are legible. Contact either your local distributor or the product manufacturer for obtaining replacement signs or labels.
Back Panel
Top Panel
LOW-INTENSITY INFRARED HEATER
RADIATEUR À INFRAROUGE À FAIBLE INTENSITÉ
MODEL NUMBER
SERIAL NUMBER
NUMÉRO DE MODÈLE
NUMÉRO DE SÉRIE
HL2-DS-30-80N YYMMREPCSHIPPE#### 09/17
MAX. HEAT INPUT
MANIFOLD PRESSURE
MAX. DEBIT CALORIFIQUE
PRESSION A LA TUBULURE D'ALIMENTATION
BTU/h
80,000
MAXIMUM INLET PRESSURE
MIN. HEAT INPUT
PRESSION D'ALIMENTATION MAXIMALE
MIN. DEBIT CALORIFIQUE
14.0
BTU/h
52,000
MINIMUM INLET PRESSURE FOR PURPOSE OF ADJ.
TYPE OF GAS
PRESSION D'ALIMENTATION EN GAS MIN. ADMISE
TYPE DE GAZ
NATURAL
VENT CATEGORY
ORIFICE SIZE
DIM DE L'INJECTEUR
ÉVENT CATÉGORIE
CATEGORY I
THIS DESIGN COMPLIES WITH STANDARD(S):
COMPLES DE CETTE CONCEPTION AVEC LA NORME:
ANSI Z83.20-2016 • CSA 2.34-2016 Low-Intensity Infrared Heater
FOR U.S.A. THIS HEATER IS APPROVED FOR ALTITUDES OF 0-2000 FT. IN CANADA FOR ALTITUDES OF 4-4500 FT (0-1,370M) ABOVE SEA LEVEL
AU CANADA POUR ALTITUDE DE 0 A 4500 PIEDS (0-0,370M) D’ALTITUDE
DETROIT RADIANT PRODUCTS COMPANY
21400 HOOVER ROAD - WARREN, MI 48089 (586) 756-0950 www.reverberray.com
F/N: LLTB018 (Natural Gas)
F/N: LLTB019 (Propane Gas)
FIRE HAZARD. Always maintain published clearances to combustibles. In locations used for the storage of combustible materials, signs must be posted. Consult manual for additional guidelines.
CLEARANCES TO COMBUSTIBLES (in inches)
MODEL NO.
MOUNTING ANGLE*
TOP
6
HL2-DS-30-65/ HL2-DS-30-80
9
30°
6
HL2-DS-30-100
9
30°
SIDE VIEW END VIEW
EndEnd
* Heaters mounted on an angle between 1° and 30° must maintain clearances posted for 0° or 30°; whichever is greater. ** This heater must be installed at least 79” above the floor/ground level (as applicable).
SIDE(S)
FRONT
25 36
25 4525 10
END VIEW
0° Mounting
Side Side
Below
ENDS
BEHIND
25
12
10
12
12
12
30° Mounting
Top
Front
Max.
30˚ Angle
This heater must be installed in accordance with the manufacturer’s instruction and local codes, if any. In absence of local codes, follow the latest edition of the National Fuel Gas Code, NFPA 54 (ANSI Z223.1) or the CAN/CCA B149 installation codes.
Hot while in operation. DO NOT Touch. Keep children, clothing, and
BELOW**
combustible materials away. DO NOT store combustible materials under
60
this heater while in operation.
47
77
Keep burner and control compartment clean. See installation and
64
operating instructions accompanying heater.
APPLICATION: Minimum mounting height 79” above finished floor.
If this appliance is installed in one or more of the following locations, then the installation
Top
must be in accordance with the latest edition of the applicable standard(s):
• Aircraft Hangers - ANSI / NFPA 409
• Parking Structure - ANSI / NFPA 88A
Back
• Repair Garages - ANSI / NFPA 88B
Below
LOW-INTENSITY INFRARED HEATER
112671
VERSION
VOLTAGE
VAC
INCHES W.C.
1203.5
AMPS
INCHES W.C.
1.2
PHASE
INCHES W.C.
5.0 SINGLE
FREQUENCY
Hz
D.M.S.
22
60
MIN. MOUNTING ANGLE
MIN. ANGLE DE SUPPORT
MAX. MOUNTING ANGLE
MAX. ANGLE DE SUPPORT
30°
HEATER BUILD TYPE
C1
FOR OUTDOOR USE ONLY
MADE IN U.S.A.
RADIATEUR À INFRAROUGE À FAIBLE INTENSITÉ
MODEL NUMBER
NUMÉRO DE MODÈLE
MAX. HEAT INPUT
MAX. DEBIT CALORIFIQUE
MIN. HEAT INPUT
MIN. DEBIT CALORIFIQUE
TYPE OF GAS
TYPE DE GAZ
VENT CATEGORY
ÉVENT CATÉGORIE
COMBUSTION CHAMBER
THIS DESIGN COMPLIES WITH STANDARD(S):
COMPLES DE CETTE CONCEPTION AVEC LA NORME:
ANSI Z83.20-2016 • CSA2.34-2016 RADIANT TUBE HEATER
Detroit Radiant Products Company
21400 Hoover Road Warren MI 48089
(586) 756-0950 www.reverberray.com
MODEL NO.
HL2-DS-30-65/ HL2-DS-30-80
HL2-DS-30-100
* Heaters mounted on an angle between 0° and 30° must maintain clearances posted for 0° or 30°, whichever is greater. ** This heater must be installed at least 79” above the floor/ground level (as applicable).
SERIAL NUMBER
NUMÉRO DE SÉRIE
HL2-DS-30-80N
80,000 52,000 NATURAL
N/A - UNVENTED
TP-877
YYMMREPCSHIPPE####
MANIFOLD PRESSURE
PRESSION A LA TUBULURE D'ALIMENTATION
BTU/h
MAXIMUM INLET PRESSURE
PRESSION D'ALIMENTATION MAXIMALE
BTU/h
MINIMUM INLET PRESSURE FOR PURPOSE OF ADJ.
PRESSION D'ALIMENTATION EN GAS MIN. ADMISE
ORIFICE SIZE
DIM DE L'INJECTEUR
SAMPLE
FIRE HAZARD. Always maintain published clearances to combustibles. In locations used for the storage of combustible materials, signs must be posted. Consult manual for additional guidelines.
CLEARANCES TO COMBUSTIBLES (in inches)
MOUNTING ANGLE*
TOP
6
9
30°
6
9
30°
SIDE VIEW END VIEW
EndEnd
INCHES W.C.
14.0
INCHES W.C.
INCHES W.C.
5.0
D.M.S.
18
MIN. MOUNTING ANGLE
MIN. ANGLE DE SUPPORT
MAX. MOUNTING ANGLE
MAX. ANGLE DE SUPPORT
HEATER BUILD TYPE
THIS HEATER IS TO BE UN-VENTED ONLY
FOR OUTDOOR USE ONLY.
MADE IN U.S.A.
SIDE(S)
BEHIND
FRONT
25
25
10
36
25
4525 10
END VIEW
0° Mounting
Top
Side Side
Below
VOLTAGE
AMPS
PHASE
FREQUENCY
VERSION
09/17
1203.5
4.8
SINGLE
Max.
30˚ Angle
112671
60
ENDS
Front
VAC
Hz
0° 30° C1
12
12
12
12
30° Mounting
Rating Plate
BELOW**
60
47
77
64
Top
Back
Below
F/N: LLTCL018
LLTCL016a-1x-05/17 (CDS)
Clearances to Combustibles Label
This heater must be installed in accordance with the manufacturer’s instruction and local codes, if any. In absence of local codes, follow the latest edition of the National Fuel Gas Code, NFPA 54 (ANSI Z223.1) or the CAN/CCA B149 installation codes.
Hot while in operation. DO NOT Touch. Keep children, clothing, and combustible materials away. DO NOT store combustible materials under this heater while in operation.
Keep burner and control compartment clean. See installation and operating instructions accompanying heater.
APPLICATION: Minimum mounting height 79” above finished floor.
If this appliance is installed in one or more of the following locations, then the installation must be in accordance with the latest edition of the applicable standard(s):
• Aircraft Hangers - ANSI / NFPA 409
• Parking Structure - ANSI / NFPA 88A
• Repair Garages - ANSI / NFPA 88B
F/N: LLTCL016a Safety Label
Bottom Panel
HL2-DS-30-80N
HL2-40-125N
HL2-125
Production Code:
9.14
Version:
Data on this label is for the model shown on this label. If your heater has been converted, this information is not accurate. Please contact the factory for assistance.
BURNER COMPONENTS:
Gas Valve: Circuit Board: Wire Harness: N.O. Switch: N.O. VL Orifice: N.C. Switch: N.C. VL Orifice: Diff Switch: Diff VL Orifice: Igniter: Burner: 16” Tube: Ind. Lights:
HEATER
TYPE:
C1
For parts replacement information, contact factory at 586-756-0950 or visit www.drp-co.com/parts.
(Specify TP-#’s)
36E96-224-N Micro60-24 3 PCS Harness None None None None
SAMPLE
IS22010051F5169 Grey (+ / -) Norton Low-Mid 4” Gen. Yellow - 120V
C1 C2 C3
Orifice Type: Gas:
3
TP-204#
Air:
1 1/2”
TP-44#31 5/8”
840
Diag. Light:
851
Term. Block:
852
Transformer:
N/A
Fan: Alt. Fan:
N/A
Alt. Fan Usage: Relay:
264E
Filter: 24 Volt In:
50
120 Volt In:
3072
Gas In:
380
Extra VL Orifice:
828
3
1 5/8”
Serial No.: 0914XXXXXXXXXX 0001
None
Stock:
Add-On:
N/A
On Circuit Board None 40 VA Fasco Lg. 50Hz - 120V When Specified None None 3 T-plug 2 x 4 Box 7/8” FC Flare None
Internal Use Only:
Electric: Tag:
LLWT038 None
Special 1: Special 2:
F/N: LLLOGO032
4
N/A 826 55A 55B
N/A N/A 832 66 83
Burner Control Box
Micro60
Component Label
Plug-Wh.
under the top panel)
(located
Page 5
HL2-DS Series
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
- INSTALLER: READ AND POST THIS NOTICE -
Left Panel (Fan Compartment)
1.0 Introduction Safety Labels and Their Locations
LED CODE FAULT STATUS FAULT CODE DELAY
Initial flash on power up,
then steady off
Steady on Module failure / Internal fault No delay
1 flash Ignition failure 3 minutes
2 flashes
4 flashes Erroneous flame signal No delay
No flash on 117V start-up Transformer fault No delay
NOTE: Lockout LED CODE appears on completion of the soft lockout operation.
No fault, normal operation No delay
APS air flow fault
NOTE: fan/intake/exhaust
F/N: LLTB007(3)
(Axed under the lid)
1-30 seconds
Avoid Serious Injury, Death, or Property Damage.
Maintain Clearances to Combustible to Prevent the Risk of Fire.
Clearances to combustibles must be maintained at all times in order to prevent the ignition of combustible materials. In locations used for the
storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater’s thermostats or, in the absence of such thermostats, in a conspicuous location. Clearances are provided on the heater’s safety label and in the heater’s Installation, Operation, and Maintenance manual. Product installation and operation must comply with applicable standards, codes, and regulations. Post this tag adjacent to the heater’s thermostat or controls before operating the heater.
F/N: LL001 - Clearance Safety Tag
(Ax adjacent to heater’s thermostat)
Right Panel (Valve Compartment)
WARNING
California Proposition 65
This product can expose you to chemicals including
!
lead and carbon monoxide, which are known to the State of California to cause birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov.
LL001-XM-07/18 (CDS)
16” Burner Tube
F/N: LLV2EP15
F/N: LLV2EP9
F/N: LLV3EP4
White Crescent
24V
- 24V HEATER OUTPUT -
HIGH
LOW
24V OUT
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
F/N: LLTB026
5
Page 6
2.0 Safety Warning Symbols Applications
!
!
!
HL2-DS Series
2.0 Safety
Read and understand all safety information and warnings in this manual prior to installation, operation, and maintenance of this tube heater. Warnings indicate a potentially hazardous situation which, if not avoided, could result in death or injury.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, serious injury, or death. Read and understand the installation, operation, and maintenance instructions thoroughly before installing or servicing this
equipment. Only trained qualied gas installation and service personnel may install or
service this equipment.
Warning Symbols
Safety is the most important consideration during installation, operation, and maintenance of the heater. You will see the following symbols and signal words when there is a hazard related to safety or property damage.
Warning indicates a potentially hazardous situation which, if not avoided, could result in death or injury.
Caution indicates a potentially hazardous
CAUTION
NOTICE
situation which, if not avoided, could result in minor or moderate injury.
Notice indicates a potentially hazardous situation which, if not avoided, could result in property damage.
Applications
This is not an explosion proof heater. This heater may not be used in a Class 1 or Class 2 Explosive
Environment. Consult your local re marshal, insurance carrier, and other authorities for approval if the
proposed installation is in question.
Patio
This patio heater is specically designed to provide heated comfort in a non-residential outdoor environment. When properly integrated into a patio design, the heaters generally increase the comfort
levels.
6
Page 7
HL2-DS Series
!
!
2.0 Safety Standards, Certications, and Government Regulations
Standards, Certications, and Government Regulations
Installation of this tube heater must conform with all applicable local, state, and national specications, regulations, and building codes. Contact the local building inspector and/or re marshal for guidance.
In the absence of local codes, the installation must conform to the latest edition of:
United States: National Fuel Gas Code, ANSI Z223.1 (NFPA 54).
Copies of the Standards can be viewed or purchased at www.nfpa.org.
WARNING
Not For Use in Indoor Living Spaces. Installing this unit in residential indoor living spaces or
sleeping quarters, such as bedrooms or basements, may result in property damage, serious injury, or death. This unit is approved for unvented commercial/industrial outdoor use only.
WARNING
California Proposition 65
This product can expose you to chemicals including lead and carbon monoxide, which are known to the State of California to cause birth defects or other reproductive harm.
For more information, go to www.P65Warnings.ca.gov.
7
Page 8
2.0 Safety Clearances to Combustibles
!
!
HL2-DS Series
Clearances to Combustibles
A critical safety factor to consider before installation is the clearances to combustibles. Clearance to combustibles
reector, and the combustible item
tube heater. The following is a partial list of items to maintain clearances from:
Combustible items: Moving Objects:
• Wood • Overhead doors
• Paper • Vehicle lifts
• Fabric • Cranes
• Chemicals • Hoists
Hazards:
For maximum safety the building must be evaluated for hazards before installing the heating system. Examples include, but are not limited to:
is dened as the minimum distance you must have between the tube surface, or
. Considerations must also be made for moving objects around the
• Paint
• Parked vehicles
• Gasoline
• Storage racks
• Gas and electrical lines
• Combustible and explosive materials
• Chemical storage areas
• Areas of high chemical fume concentrations
• Provisions for accessibility to the heater
• Adequate clearances around air openings
• Combustion and ventilating air supply
• Vehicle parking areas
• Vehicles with lifts or cranes
• Storage areas with stacked materials
• Lights
• Sprinkler heads
• Overhead doors and tracks
• Dirty, contaminated environment
WARNING
Placement of explosive objects, ammable objects, liquids, and vapors close to the heater may result in explosion, re, property damage, serious
injury, or death. Do not store or use explosive objects, liquids, and vapor in the vicinity of the heater.
CAUTION
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same space as the heater.
Clothing or other ammable materials should not be hung from the heater or placed on or near the
heater.
Any guard or other protective device removed for servicing the heater must be replaced prior to operating the heater.
Installation and repair should be done by a qualied service person. The heater should be inspected before use and at least annually by a qualied service person. More frequent cleaning may be required
as necessary. It is imperative that the control compartment, air passageways, and burner(s) of the heater be kept clean.
When installing the tube heating system, the minimum clearances to combustibles for your series tube
heater and system conguration must be maintained. These distances are shown in Chart 2.1 on page 9 and on the burner control box. If you are unsure of the potential hazards, consult your local re marshal, re insurance carrier, or other qualied authorities on the installation of gas red tube heaters for
approval of the proposed installation.
8
Page 9
HL2-DS Series
!
2.0 SafetyClearances to Combustibles
In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater’s thermostat or in a conspicuous location.
The stated clearance to combustibles represents a surface temperature of 90°F (50°C) above room temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent materials are protected from degradation.
WARNING
Failure to comply with the stated clearances to combustibles may result in personal injury, property damage, and/or death.
Chart 2.1 Clearances to Combustible Materials in Inches (see Figure 2.1)
Mounting
Model Number
HL2-DS-30-65 [N, P]
HL2-DS-30-80 [N, P]
HL2-DS-30-100 [N, P]
Heaters mounted on an angle between 0° and 30° must maintain clearances posted for 0° or 30°; whichever is
*
greater.
Angle*
25 25 6 60 12
30° 36 10 9 47 12
25 25 6 60 12
30° 36 10 9 47 12
25 25 6 77 12
30° 45 10 9 64 12
Sides
Front Behind To p Below End
Figure 2.1 Mounting Angles
0° Mounting Angle
To p
To p
30° Mounting Angle
Side Side
Below
Front
Behind
Below
9
Page 10
3.0 InstallationDesign Considerations and Prechecks
!
HL2-DS Series
3.0 Installation
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, serious injury, or death.
Read and understand, the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
Only trained, qualied gas installation and service personnel may install or service this
equipment.
Design Considerations and Prechecks
Placement of infrared heaters is inuenced by many factors. All installation manuals, along with national,
state, provincial, and local codes, address these issues. It is critical that you read, understand, and follow all guidelines and instructions.
To ensure a properly designed heating system, a layout should be developed for the correct placement
of the burner control box, tubes, and reectors. Inspect and evaluate the mounting conditions, gas
supply, and wiring.
When designing an infrared radiant heating system for a patio, consider the following:
• What expectations does the end user have for coverage and comfort level of the space?
• Does the design meet the needs of the space?
• Have recommended mounting heights been observed?
• Have all clearances to combustible situations been observed?
• Is the supply (burner) end of the heater located where more heat is required?
• Is it best to oset the heaters?
IMPORTANT: Fire sprinkler heads must be located at an appropriate distance from the heater. This distance may exceed the published clearances to combustibles as posted on the heater. Certain applications may require the use of high temperature sprinkler heads or relocation of the heaters.
Sprinkler systems containing propylene glycol or other ammable substances are not to be used in conjunction with this heater without careful consideration for and avoidance of potential re or
explosion hazards. For further information consult NFPA 13.
The comfort level of a person or space may be diminished with wind velocities above 5 mph. The use of adequate wind barrier(s) may be required (see page 18).
10
Page 11
HL2-DS Series
Figure 3.1 Heater Dimensions
3.0 InstallationRecommended Mounting Heights
59.4”
3.25”
18.25”
END VIEW
9.5”
SIDE VIEW
11.75”
90.5” 45.6”
195.5”
Chart 3.1Recommended Mounting Heights and Coverages for HL2-DS Series Heaters
Distance
Max.
Input
(BTU/h)
Typical or
Recommended
Mounting Height*
Coverage Area
Straight Cong.
(LxW)
Between
Heaters (ft.)
Dim. A
65,000 9’ - 16’ 26’ x 12’ 10’ - 20’ 20’ - 40’ 16’
Distance Between
Heater Rows
Dim. B
Max. Distance
Between Heaters and Wall - Dim. C
80,000 9’ - 16’ 26’ x 12’ 10’ - 20’ 20’ - 40’ 16’
100,000 9’ - 16’ 26’ x 12’ 10’ - 20’ 20’ - 40’ 16’
* Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted too
low or too high, they may result in discomfort due to excessive heat or lack of heat. Detroit Radiant Products Company generally recommends observing the recommended mounting heights to optimize comfort conditions. However, certain applications such as spot heating, freeze protection, outdoor patio heating or very high ceilings may result in the heaters being mounted outside of the factory recommended mounting heights.
Figure 3.2 Mounting Height Dimensions (see Chart 3.1 for dimensions)
Dim. A
Dim. B
Dim. A
Dim. C
Dim. C
NOTE: Dimensions A, B, & C are based upon heaters hung at the factory recommended mounting height.
11
Page 12
3.0 InstallationHeater Assembly Instructions
!
HL2-DS Series
Heater Assembly Instructions
WARNING
At least two people are required to assemble and hang this heater. Failure to follow these instructions can result in property damage, serious injury, or death.
Read and understand the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
Only trained, qualied gas installation and service personnel may install or service this
equipment.
Remove the lids from the two (2) tube and reector boxes and set end to end in assembly area. Place
1
one (1) tube and reector assembly on each box, with the “U” end on the outside and the tubes
facing upward (see Fig. 3.3).
Open the burner carton, remove the burner box, and place the empty carton at the burner end of the
2
rst tube and reector assembly.
Disconnect the pressure switch hose, Glo-Bar connector, and electrode wire from their respective
3
connections on the burner tube. Remove the conduit nut from the end of the conduit and set aside.
Holding the burner box on its side so as to keep the Glo-Bar clear, place the burner tube through the reector, lining the swaged end up with the combustion tube (see Fig. 3.3). Rotate the burner box at
so the lid is facing downward. Carefully slide the burner tube into the combustion tube, and the
conduit and wires through the conduit hole in the reector. Screw the nut onto the conduit and
securely fasten.
Figure 3.3 Assembly Layout
Conduit
Glo-Bar
Combustion Tube
Reector
Burner Tube
Box Lid
Exhaust Downturn
Burner End Tubes and Reector
Box Lid
U-End Tubes and Reector
Burner
Box
12
Page 13
HL2-DS Series
Figure 3.4 Service Access Panel Connections
Burner Box
Pressure Switch Hose
3.0 InstallationHeater Assembly Instructions
Service Access Panel
Glo-Bar
Electrode Wire
Rotate the service access panel up so the Glo-Bar compartment is accessible. Re-connect the
4
Glo-Bar, pressure switch hose, and electrode wire, leaving the Glo-Bar connector just outside of the
conduit (see Fig. 3.4). Carefully rotate the service access panel back to its closed position.
Ensure that swedged end of the burner tube is completely inserted into the combustion tube, then
5
secure with one (1) included sheet metal screw.
Align both tube and reector assemblies, then carefully slide the assemblies together, guiding the
6
radiant tubes into one another. The exhaust end reector will slightly overlap the burner end reector. The tube and reector assemblies are in the correct position when the reector screw
holes are aligned (see Fig. 3.7).
Remove the screw holding the exhaust downturn and set aside. Insert the bae into the exhaust
7
tube, locking each bae together as they are inserted. Once in the tube, ensure the baes are in the vertical position and ush with the end of the tube (see Fig. 3.5). Reattach the exhaust downturn
and secure with one (1) sheet metal screw.
Figure 3.5 Bae Placement Figure 3.6 Bae Assembly
Bae
Radiant Tube
13
Page 14
3.0 InstallationHeater Assembly Instructions
Secure both radiant tube sections together with one (1) included self-tapping screw in each.
8
Using the four (4) screws provided and a nut driver, attach the reectors together so that the screws
9
HL2-DS Series
are hand tight. Do not overtighten as this will not allow for the expansion and contraction of the
reectors.
Figure 3.7 Tube and Reector Assembly
Sheet
Metal
Screw
Reector Overlap with Reector Screw Holes
Aligned
14
Page 15
HL2-DS Series
10
Insert the bolt in the nutsert and secure (see Fig. 3.8).
11
With one person positioned at each end of the heater, carefully ip the unit over and set back down
3.0 InstallationHeater Assembly Instructions
onto the cartons. Using the supplied bolts attach the hanging brackets to the top of the unit (see Fig.
3.8).
Figure 3.8 Mounting Bracket Placement
Bolt
Lock Washer
Flat Washer
Bolt
Flat Washer
Hanging Bracket
Hanging Chain Bracket
Hanging Bracket
15
Page 16
!
3.0 InstallationHeater Placement and Suspension
HL2-DS Series
Heater Placement and Suspension
WARNING
Improper suspension of the tube heater may result in collapse and being crushed. Always suspend from a permanent part of the building structure that can evenly support the total force and weight of the heater.
Failure to maintain minimum clearances to combustibles may result in re and/or explosion,
property damage, serious injury, or death. Always maintain minimum clearances and post clearance safety limit signs or the clearance safety tag where needed.
Suspension of the heater must conform to applicable codes referenced in the Safety section and these instructions.
Mark locations for hanging points.
1
Prepare mounting surface. If necessary, weld blocks and drill holes.
2
Fasten beam clamp, screw hook, or other type of suspension anchor to hanging point.
3
Attach and close stainless steel S-hook and 1/0 stainless steel bulldog chain to anchor. Check that it
4
is securely attached. NOTE: Threaded rod may be used.
Attach stainless steel S-hooks to turnbuckles and hanging bolts inserted through the hanging
5
brackets. Adjust chain lengths until heater is level and equal weight distribution is achieved.
Once heater is level, insert egg crate assemblies by sliding into the reector, 2 from each end (see Fig.
6
3.10).
Attach the end panel brackets to the reector on the burner box end and U-end to secure egg crates.
7
Figure 3.9 Mounting the Hangers
Turnbuckle
Bolt, Nut, Flat Washer, and Lock Washer
1/0 Stainless Steel Bulldog Chain
1/0 Stainless Steel Bulldog Chain
16
Page 17
HL2-DS Series
3.0 InstallationSway Bracing for High Air Movement and Outdoor Applications
Figure 3.10 Egg Crate Installation
Egg Crate
End Panel Bracket End Panel Bracket
Egg CrateEgg Crate Egg Crate
Sway Bracing for High Air Movement and Outdoor Applications
For high air movement and outdoor applications, install side restraints (eld supplied) to reduce side to
side swaying (Fig. 3.11). Side restraints should be installed so that they are angled at 45° ± 10° and should be placed at every designated suspension point. It may be necessary to add additional support structures at the ceiling level for the connection of these side suspensions. Apply longitudinal (forward/
backward) bracing (eld supplied) at each reector hanging bracket. The desired suspension material
shall have a minimum work load rating of 200 pounds.
Figure 3.11 Heater with Sway Bracing Installation
1/0 Stainless Steel
Bulldog Chain
Longitudinal
Bracing
(Field Supplied)
Side Restraints (Field Supplied)
Stainless Steel S-Hook
Turnbuckle Side Restraint
Longitudinal Bracing
1/0 Stainless Steel Bulldog Chain
17
Page 18
3.0 InstallationOutdoor Unvented Operation
!
HL2-DS Series
Outdoor Unvented Operation
WARNING
This appliance must be used outdoors only! Use of this heater indoors may result in
property damage, serious injury, or death.
This is an unvented, outdoor appliance. If the use of wind barriers is required, consider the following:
• Where wind barriers are used, natural or mechanical means must be provided to supply and exhaust a minimum of 4 cfm/1000 BTU/h input of installed heaters.
NOTE: Gravity or mechanical means may be used to accomplish the air displacement. Local
codes may require that the mechanical exhaust system be interlocked with the electrical supply line to the heaters, enabling both to function simultaneously.
• When the space requires mechanical ventilation, the exhaust openings for removing the ue
products must be located above the level of the heater(s).
Figure 3.12 Minimum End Clearances
12 in. Min.
All heaters
12 in. Min.
Unvented
heaters
18
Page 19
HL2-DS Series
!
!
3.0 Installation Gas Supply Installation Instructions
Gas Supply Installation Instructions
The gas supply to the unit heater must be connected and tested in accordance with national, state, provincial, and local codes along with guidelines in this manual. In the United States refer to the latest
edition of the ANSI Z223.1 (NFPA54) Standard.
Supply gas piping to the unit should conform with the local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Avoid pipe sizes smaller than 1/2”.
WARNING
Improperly connected gas lines may result in serious injury and death, explosion, poisonous fumes, toxic gases, or asphyxiation. Connect gas lines in accordance to national, state, provincial, and local codes.
Gas pressure to the appliance controls must never exceed ½” PSI (14” W.C.). Damage to the controls
may result.
CAUTION
Gas lines should be purged of air as described in ANSI Z223.1 (NFPA 54) or CSA-B149.1– latest
version. Installation of the piping must also conform with the local building codes or, in the
absence of local codes, with the latest edition of the National Fuel Gas Code (NFPA 54).
NOTICE
The total input to the appliance must fall within +/- 5% of the rated input as indicated on the rating plate. Otherwise the heat exchanger may prematurely fail.
IMPORTANT! Before connecting the gas supply to the burner control box:
• Verify that the heater’s gas type (as listed on the rating plate) matches that of your application and the installation complies with national and local codes and requirements of the local gas company.
• Unless otherwise noted on the rating plate, this infrared heater is designed and oriced to operate
on standard BTU gas. Contact the factory if utilizing non-standard BTU gas.
• Check that the gas piping and service has the capacity to handle the total gas consumption of all heaters being installed, as well as any other gas appliances being connected to the supply line.
• Check that the main gas supply line is of proper diameter to supply the required fuel pressures.
• If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas supply lines in accordance with local codes.
19
Page 20
3.0 Installation Gas Supply Installation Instructions
!
!
HL2-DS Series
To connect the gas:
WARNING
Failure to install, operate, or service this appliance in the approved manner may result in
property damage, injury, or death. Only trained, qualied gas installation and service
personnel may install or service this equipment.
The HL2-DS series heater is equipped to connect to the corrugated stainless steel tube (CSST) exible
gas connector (Included). Do not connect the main gas line directly to the heaters gas inlet without the use of the exible connector. All piping must be installed in accordance with the requirements
outlined in the National Fuel Gas Code ANSI/Z223.1 (latest edition) or CSA-B149.1. Support all gas
piping with pipe hangers, metal strapping, or other suitable material. Do not rely on the heater to support the gas pipe.
When connecting piping to the unit, the use of a thread joint compound is required. The thread
compound (pipe dope) shall be resistant to the action of liqueed petroleum gas or any other chemical constituents of the gas to be conducted through piping. Use of Teon
®
tape is not permitted.
WARNING
Always use two (2) opposing wrenches to tighten mating pipe connections to prevent excessive torque on the gas valve and manifold pipe. Excessive
torque can damage the valve and/or misalign the orice, resulting in re,
explosion, serious injury, or death.
Connect the main gas supply line with an approved exible connector or, if the authority having
jurisdiction requires rigid piping, the use of approved swing joints may be used. If swing joints are utilized, the heater must be allowed to freely expand and contract without causing undue stress on the gas pipe.
The heater shall not be connected to the building piping system with rigid pipe or semi-rigid metallic tubing, including copper. When using such material, an intermediate connection device that allows for the heater expansion must be used.
The gas outlet must be in the same room as the appliance is installed, and must be accessible. It may not
be concealed within or run through any wall, oor, or partition. When installing the heater in a corrosive
environment (or near corrosive substances), use a gas connector suitable for the environment. Do not use the gas piping to electrically ground the heater.
20
Page 21
HL2-DS Series
!
3.0 Installation Installation of the Gas Line to the Heater
Installation of the Gas Line to the Heater
Install a sediment trap / drip leg in the supply line at the lowest spot prior to the gas ball valve. The
1
trap length shall be at least three inches long. Ideally, the trap would be installed as close as possible
to the shut o. NOTE: For high pressure gas above 14” W.C., a high pressure regulator and ball valve must be utilized and located upstream of the ex connector.
Install manual shut o ball valve with optional 1/8” NPT Test connection towards the supply line. The
2
manual shut o ball valve must be located within 6 feet of the appliance’s service access door.
Install the 5/8 inch are to ½” NPT adapter piece downstream of the gas valve as shown in Figures
3
3.13-3.14. This piece is typically included with the exible gas connector, loosely installed on one of
the are nuts. NOTE: Keep are surfaces clean and free of sealing compounds. Only the pipe
threads require sealing compounds.
Form the 1/2” x 24” stainless steel exible gas connector into a smooth C-shape, allowing
4
approximately 12 inches between the exible connector’s end nuts (see Figure 3.13). The connector
must reach from the gas supply to the appliance without stretching, kinking, or twisting.
Attach the exible connector to the 5/8” are adapter on the gas line and the other end to the 5/8”
5
are on the heaters inlet pipe. DO NOT connect the connector are nuts directly to pipe threads.
Use only the adapters provided. DO NOT kink, twist, or over-torque the connector when installing.
CAUTION
When using a stainless steel exible gas connector, do not attach the connector nuts directly to the gas pipe supply. Connector nuts must be installed to an approved adapter.
Figure 3.13 Gas Connection (Flexible Gas Connection Shown)
NOTE: Do not exceed 14 Inches W.C. to the appliance.
Ball Valve / Inlet Tap
Adapter
Ball Valve / Inlet Tap
45°
45°
Horizontal
Remove cap to clean
sediment trap
12”
2” max displacement
Heater Movement
Adapter
Drip Leg/ Sediment Trap
SERVICE ACCESS PANEL
IGNITER & FLAME SENSE COMPARTMENT
1. Turn off gas & electricity.
2. Remove cover by lifting top
cover upward and outward.
CAUTION: HOT SURFACE.
KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.
Burner Control Box
Burner Control Box
Stainless Steel Gas Connector,
formed into smooth C-Shape
In Canada, the infrared heater shall only be connected with a Type I hose connector that is (a) certied
as being in compliance with the
Conducting Propane and Natural Gas, CAN/CGA 8.1
Standard for Elastomeric Composite Hose and Hose Couplings for
; and (b) of a length of 36 ± 6 in (90 ± 15 cm).
21
Page 22
3.0 Installation Installation of the Gas Line to the Heater
HL2-DS Series
Refer to Chart 3.2 for natural gas and Chart 3.3 for propane to determine the cubic feet per hour (CFH) required for the type of gas and size of unit to be installed. To determine the proper pipe diameter, use the CFH value and the length of pipe necessary from Chart 3.4. In the case where several units are serviced by the same main gas line, the total capacity (CFH) and length of main must be adequate to service all appliances downstream of this main.
Chart 3.2 Natural Gas Consumption
Max. Inlet
Pressure
(Inches W.C.)
Model
HL2-DS-30-65
HL2-DS-30-80
HL2-
DS-30-100
Manifold
Input
High/Low
65,000 (High) 3.5
50,000 (Low) 2.2 47.6
80,000 (High) 3.5
52,000 (Low) 1.7 49.5
100,000 (High) 3.5
65,000 (Low) 1.8 61.9
Pressure
(Inches W.C)
Min. Inlet Pressure
(Inches W.C.)
5.0 14.0
5.0 14.0
5.0 14.0
* Assumes an average heating value of 1050 BTU/SCF and a Specic Gravity of 0.60.
Chart 3.3 Propane Gas Consumption
Model
HL2-DS-30-65
HL2-DS-30-80
HL2-
DS-30-100
Manifold
Input
High/Low
65,000 (High) 10.0
50,000 (Low) 4.8 20 .54
80,000 (High) 10.0
52,000 (Low) 4.8 21 .56
100,000 (High) 10.0
65,000 (Low) 4.8 26 .71
Pressure
(Inches W.C.)
Min. Inlet Pressure
(Inches W.C.)
11.0 14.0
11.0 14.0
11.0 14.0
Max. Inlet
Pressure
(Inches W.C.)
Consumption
Gas Consumption
(CFH)*
61.9
76.2
95.2
Gas
Gallons
(CFH)*
26 .71
32 .87
40 1.08
p/ Hour
* Assumes an average heating value of 2500 BTU/SCF and a Specic Gravity of 1.53.
Chart 3.4 allows for a 0.3 inch W.C. pressure drop in the supply pressure from the building main to the inlet of the unit. Refer to the chart for the appropriate range of inlet pressures for each gas type. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3 inch W.C. pressure drop has been subtracted from the main pressure. If the 0.3 inch W.C. pressure drop is too high,
refer to NFPA 54 or the Gas Engineer’s Handbook for other gas pipe capacities.
Install ground joint union with a brass seat and a manual shut-o valve adjacent to the unit for emergency shut-o and easy servicing of controls. A 1/8” NPT plugged tap that is accessible for a test
gauge connection is also recommended, as illustrated in Figure 3.14.
A sediment trap must be installed in the supply line in the lowest spot prior to connecting to the heater. The trap length shall be at least three inches long. Ideally, the trap would be installed as close as
possible to the shut-o, as shown in Figure 3.14.
22
Page 23
HL2-DS Series
3.0 Installation Gas Supply Installation Instructions
Figure 3.14 Recommended Hardware Manual Shut O and Sediment Trap
In Canada, infrared heater shall only be connected with a Type I hose connector
that is (a) certied as being in compliance
with the
Composite Hose and Hose Couplings for
Conducting Propane and Natural Gas, CAN/ CGA 8.1
± 15 cm).
Standard for Elastomeric
; and (b) of a length of 36 ± 6 in (90
1/2” x 24” 304 Stainless Steel Gas
Connector formed into smooth
C-Shape
Shut O
Flow of Gas
1/8-in. NPT Test Connection (Plugged)
Ground Joint
Union
Sediment
Tra p
To Unit
3-in. Minimum
Chart 3.4 Maximum Capacity for Schedule 40 Metallic pipe, in CFH
Pipe
Length
10 feet 132 86 278 182 520 340 1050 686 1600 1046 3050 1993
20 feet 92 60 190 124 350 229 730 477 1100 719 2100 1373
30 feet 73 48 152 99 285 186 590 386 890 582 1650 1078
40 feet 63 41 130 85 245 160 500 327 760 497 1450 948
50 feet 56 37 115 75 215 141 440 288 670 438 1270 830
60 feet 50 33 105 69 195 127 400 261 610 399 1150 752
70 feet 46 30 96 63 180 118 370 242 560 366 1050 686
80 feet 43 28 90 59 170 111 350 229 530 346 990 647
90 feet 40 26 84 55 160 105 320 209 490 320 930 608
100 feet 38 25 79 52 150 98 305 199 460 301 870 569
125 feet 34 22 72 47 130 85 275 180 410 268 780 510
150 feet 31 20 64 42 120 78 250 163 380 248 710 464
175 feet 28 18 59 39 110 72 225 147 350 229 650 425
200 feet 26 17 55 36 100 65 210 137 320 209 610 399
1/2” 3/4” 1” 1-1/4” 1-1/2” 2”
Nat Prop Nat Prop Nat Prop Nat Prop Nat Prop Nat Prop
The HL2-DS series heater is equipped to receive a gas supply line nipple of ½”NPT Schedule 40
metallic pipe. All piping must be installed in accordance with the requirements outlined in the National
Fuel Gas Code ANSI/Z223.1 (latest edition) or CSA-B149.1. Support all gas supply piping with pipe
hangers, metal strapping, or other suitable material. Do not rely on the heater to support the gas pipe.
23
Page 24
!
!
!
3.0 Installation Gas Supply Installation Instructions • Leak Testing
When connecting piping to the unit, the use of a thread joint compound is required. The thread
compound (pipe dope) shall be resistant to the action of liqueed petroleum gas or any other chemical constituents of the gas to be conducted through the piping. Use of Teon
permitted.
HL2-DS Series
®
tape is not
WARNING
Always use two (2) opposing wrenches to tighten mating pipe connections to prevent excessive torque on the gas valve and manifold pipe. Excessive
torque can damage the valve and/or misalign the orice, resulting in re,
explosion, serious injury, or death.
Leak Testing
WARNING
Use a soap solution or equivalent for leak testing. Never test for leak with an open
ame. Failure to comply could result in personal injury, property damage, or death.
Always leak test nal gas assembly for gas leaks according to the procedures outlined in NFPA 54 and
all local codes and/or Standards.
For leak testing on pressures below ½” PSI
Before leak testing, close the eld installed manual shut o valve shown on Figure 3.14 on the supply
line to isolate the gas valve from the pressure.
NOTE: All factory installed gas connections have passed an approved leak test.
For leak testing on pressures above ½” PSI
When leak testing with pressures above ½” PSI (14” W.C.), the unit must be isolated from the supply pipe. Close the eld installed manual shut o valve, disconnect the supply line to the unit, and
temporarily cap the supply line for testing purposes.
WARNING
Gas pressures to the appliance controls must never exceed 14” W.C. (1/2” PSI). Supply
pressures greater than 14” W.C. can damage the controls, resulting in personal injury, property damage, or death.
24
Page 25
BK
LIGHT
LIGHT
LIGHT
HL2-DS/HL3/AG2 SERIES
LLWT106
HL2-DS Series
!
3.0 Installation Electrical Requirements and Wiring Diagram Internal Wiring Diagram
Electrical Requirements and Wiring Diagrams
WARNING
Shock hazard. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C minimum voltage.
All eld installed wiring to the tube heater must be must be done in accordance with the national,
state, provincial, local codes, and to the guidelines in this manual. In the United States, refer to the most current revisions to the Electrical Code ANSI/NFPA 70. The unit must be electrically grounded
according to these codes. Line polarity must be observed when making eld connections.
Internal Wiring Diagram
Before wiring this appliance, check the existing wiring; replace if necessary. If any of the original wire supplied with the appliance must be replaced, it must be replaced with copper wiring material having a rating of at least 300 V, 105°C.
Figure 3.15 Internal Wiring Diagram
L2L1
W
G
BK
G
Y
W
BK
BK
INDICATOR
GAS VALVE
TRANSFORMER
120V
BK
G
24V
BL
BL
GY
BK
BLOWER
G
BK
BK
LOW FIRE HIGH FIRE P.S.
INDICATOR
G
BK
BKBK
INDICATOR
PRESSURE
W
TERMINAL*
R
BL
SWITCH
G
IGNITER
BK BK
T'STAT
O
BK
FLAME
SENSOR
IGN/120
L1
IGN/240
L2
IGN/FS
IGNITION
PS
MODULE
TH
24V
VAL
GND
PRPK O
C
G
*W/YELLOW CORD
R
O
BL
W GBK
25
Page 26
!
!
!
3.0 Installation Field Wiring Supply Voltage
HL2-DS Series
WARNING
Incorrect or improper wiring may result in shock, injury, or death. Field wiring to the heater must be connected and grounded in accordance with national, state, provincial, local codes, and to the guidelines in this manual. Refer to the most current revisions to the ANSI/NFPA 70 Standard.
All eld wiring to the HL2-DS series heater must be done in accordance with the national, state,
provincial, local codes, and the guidelines in this manual. In the United States, refer to the most current revisions to the Electrical Code ANSI/NFPA 70. The unit must be electrically grounded according to these codes.
Field Wiring Supply Voltage
Before proceeding with electrical connections, ensure that the supply voltage, frequency, phase, and
current capacity meet the requirements specied on the rating plate. A dedicated line voltage supply
with properly sized wire should run directly from the main electrical panel to the heater. The power to the unit must be protected with a circuit breaker appropriate for the load. The unit must be electrically grounded in accordance with local codes, or in their absence, with the latest edition of the National Electrical Code, ANSI / NFPA 70 and/or the Canadian Electrical Code CSA C22.1, latest edition.
CAUTION
The power supply to the heater must be within +/- 5% of the voltage rating as indicated on the
rating plate of the appliance. If input power does not meet these specications, contact your utility
company.
The heater comes equipped with a supply cord to connect the main power supply. It is located at the rear of the heater’s burner box, and utilizes a grounding prong. This plug must be connected into an appropriate outlet receptacle that is properly installed and grounded in accordance to local codes and ordinances.
The grounding receptacle must be installed within 5 feet of the heater’s service panel, and located in the space occupied by the appliance. When plugging in the heater, make sure the supply cord is protected from damage, and keep all cords away from the heater’s surfaces and out of the clearance to combustible zones (see page 9). When routing the electrical supply for the unit, ensure that it does not interfere or obstruct the heater’s service panel. Keep any electrical supply cord away from any heated surfaces.
WARNING
Electric Shock Hazard
Do not force the three-prong plug into the grounded outlet, modify the plug, or use an adapter. Never operate this appliance if the cord or plug is damaged.
26
Page 27
HL2-DS Series
R
W1
W2
CONTROL DEVICE
TYP. TWO-STAGE T-STAT OR
SWITCH
G
W
B
3.0 Installation Thermostat Connection Thermostat Location
Thermostat Connection
NOTE: Dierent thermostats operate according to their particular features. Refer to thermostat
specications for details.
HL2-DS series heaters may be controlled by a thermostat or switch. The control voltage is 24 VAC and the burner control box is equipped with a 60” yellow 24 VAC control wire. Do not supply 120 VAC to the 24 VAC connection.
Figure 3.16 Field Wiring Diagram - Controlling a single heater with a single control device
Starting Amp Draw: 4.8 Amps Running Amp Draw: 1.1 Amps
Figure 3.17 Field Wiring Diagram - Controlling multiple heaters with a single control device
Starting Amp Draw: 4.8 Amps Running Amp Draw: 1.1 Amps
CONTROL DEVICE
TYP. TWO STAGE T-STAT OR
TRANSFORMER
L1
L2
Field Wiring:
1
When controlling multiple heaters with a single control device, one ERK or ERK-HE per heater is
required.
2 An external 24 VAC transformer (.2 Amp) per heater is required (supplied by installer). 3 Maintain electrical polarity when hooking up multiple heaters. 4 Allow heaters to be switched by zones for heating exibility. 5 Do not attempt to install transformer inside of heater.
SWITCH
R
W1
W2
C
120V
G W B
OPTIONAL 24V COMMON CHECK THERMOSTAT INSTRUCTIONS TO SEE IF NEEDED
24V
RELAY BOX
P/N: ERK
(1 PER HEATER)
W1
C
W2
G W B G W B
RELAY BOX
P/N: ERK
(1 PER HEATER)
W1
C
W2
RELAY BOX
P/N: ERK
(1 PER HEATER)
W1
C
W2
27
Page 28
4.0 Operation Sequence of Operation
HL2-DS Series
4.0 Operation
Sequence of Operation
Standby: The circuit board continually checks for internal faults, circuit integrity, and relay contact
positioning.
Starting Circuit: Upon a call for heat, the control veries that the dierential switch is in the proper
position (open). The control energizes the fan. Once operational static pressure is achieved, the
dierential switch will close initiating the ignition sequence. The glo-bar is powered and the gas valve opens after 45 seconds. If the ame is not sensed, the heater will attempt to re-ignite for a
total of three (3) trials for ignition before proceeding to soft lockout.
Low Fire Running Circuit: After ignition, the ame rod monitors burner ame. If sense of ame is lost,
the control closes the gas valve within one second and a new trial sequence (identical to the
starting sequence) is initiated. If ame sense is not established within 8.5 seconds, the heater will
attempt two (2) additional ignition sequences before proceeding to soft lockout. The control can
be reset by briey interrupting the power source.
High Fire Running Circuit: The second stage on the gas valve is powered directly from the second
stage of the thermostat. In order for two stage to ow to a higher output, single stage must be
energized as well. The thermostat determines which stage to maintain for the desired temperature.
Shut Down: When the thermostat is satised, the fan will enter a two (2) minute post-purge cycle.
28
Page 29
HL2-DS Series
4.0 Operation Diagnostics
Diagnostics
Lockout:
The controls will automatically lockout the heater system when an external or system fault occurs. There are two types of lockout:
Soft Lockout: The heater will attempt to light three times. In the event of a failed attempt to light, (gas
pressure, valve, no ame sense, etc.), the heater will enter a Soft Lockout period for 30
minutes and then attempt to light three more times before entering Hard Lockout mode.
Hard Lockout: If proof of ame is not established, a component failure occurs, or blockages are
evident, the heater will enter Hard Lockout. If lockout occurs, the control can be reset
by briey interrupting the power source. Refer to Chart 4.1 below for a description of
LED codes.
Figure 4.1 External LED Operation Indicator Lights
NOTE: Hard lockout LED CODE will appear upon completion of the soft lockout sequence of operation.
Light 3 (green)
Indicates Pressure
Switch Closes
Operational Indicator Lights
Light 1 (amber)
Indicates Low
Fire Mode
Light 2 (amber)
Indicates High
Fire Mode
Chart 4.1 LED Fault Code Status (Located on Circuit Board Inside Control Box)
LED Code Fault Status Fault Code Delay*
Initial ash on power up, then steady o
Steady ON Module failure / Internal fault No Delay
1 ash Ignition failure 3 minutes
2 ash
4 ashes Erroneous ame signal No Delay
No ash on 117 V startup Transformer fault No Delay
* Some LED codes have a time delay before the LED will ash.
No fault, normal operation No Delay
APS (Air Proving Switch)
Fan / Intake / Exhaust
1 - 30 seconds
29
Page 30
5.0 Troubleshooting Guide
5.0 Troubleshooting Guide
Turn up thermostat.
HL2-DS Series
Does the fan
blower turn on?
Ye s
Find the source of the
electrical problem
between panel and
external transformer.
External transformer is faulty and must be
replaced.
Is the power at the
No
heater 120 V?
Ye s
No
Find the source of the electrical problem between panel and heater.
No
Is there 120 V on the
primary side of the
external transformer?
No
Check the power across the green and white wires of the
yellow control cord.
Is there 24 V power?
Ye s
Is there 24 V on the
No
secondary side of the external transformer?
Ye s
Is there
24 V to the
thermostat?
No
Find source of electrical problem between
the external transformer and thermostat.
Ye s
Ye s
The thermostat or wiring is faulty and
should be replaced
or repaired.
Does the green pressure
switch light illuminate?
Ye s
Does the igniter
warm up and
glow red?
Ye s
No
No
Is the igniter
physically
damaged?
Is the green light burnt out?
Yes
Replace igniter.
If so, replace.
Check voltage at igniter
sequence (usually 5 to 15
No
seconds after power to
No
No
heater). Is it 120 V?
Yes
Is the resistance through
the igniter 50-400 Ω?
Ye s
Replace circuit board.
Is the inlet or the outlet
of the unit plugged or
obstructed?
Remove obstruction.
No
No
Ye s
Continued on page 32
Consult factory.
30
Page 31
HL2-DS Series
5.0 Troubleshooting Guide
NOTICE
Start Question
Is the power across
the 24 V terminal and
ground on the
circuit board 24 V?
during normal operation or the heater’s built-in safety mechanisms will be compromised.
No
Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
Key
Process Question
Ye s
Is the power across the TH terminal and
ground on the circuit
Corrective Action
board 24 V?
No
The low re relay is faulty
and must be replaced.
Check circuit board for
Ye s
ashing fault code. Is the
circuit board sending
Is the pressure
switch stuck in the
closed position?
120 V to the fan?
No
Ye s
Remove
obstruction.
Ye s
Ye s
Replace switch.
Is the fan
obstructed?
No
Is there 120 V on the
primary side of the
internal transformer?
No
Repair wiring between
power in and transformer.
Check for loose wiring or
restrictions in hose connec-
tions to pressure switch.
Are they OK?
No
Replace wiring or hose
connections.
Ye s
Ye s
The internal
transformer is
faulty and must
be replaced.
*A
fter 1-30 seconds of
non-operation has passed,
is there a ash code for
APS fault (2 ashes)?
The circuit board is
faulty and must be
No
Consult factory.
No
replaced.
Ye s
The fan is faulty and must be replaced.
Replace the pressure switch after
verifying:
• Bae(s) are in the radiant tube furthest
from the burner.
• Heater, fan blowers ,squirrel cage, intake and exhaust are clean and free from dirt and obstructions.
• There is not a negative pressure experienced at the area of air intake (e.g.; high winds, attic space, tightly sealed building).
*Refer to LED diagnostic Fault Code Chart; p.29.
31
Page 32
5.0 Troubleshooting Guide
Continued from page 30.
HL2-DS Series
After igniter is warmed up, does gas
valve open (low light illuminates)?
Ye s
Does the
burner light?
No
in the ON position?
Ye s
Does the burner
stay on?
Ye s
No
Does the burner stay on
for approx. 8 seconds
Does the burner come
No
Is the ball valve/
shut-o valve
No
Turn on.
and then shut o?
No
on and turn o
immediately
(1 or 2 seconds)?
Test for 24 V at valve opening period (usually 30 to 45 seconds
after power to heater). Is there 24 V to valve for 8 seconds?
No
Replace circuit board.
Check to make sure gas pressure is within
Ye s
minimum and maximum inputs, as indicated on
the heater’s rating plate. Is gas pressure OK?
No
Correct problem.
Ye s
Check to make sure gas pressure
Ye s
is within minimum and maximum
inputs, as indicated on the heater’s
rating plate. Is gas pressure OK?
Ye s
Ye s
Ye s
Pressure switch may be faulty or
there is a
restriction in
the exhaust.
Does the heater
stay ON until a
call for heat ends?
Ye s
Troubleshooting ends.
The heater can shut down due to:
No
• Improper grounding.
• High winds.
• Dirty environment.
• Improperly positioned baes.
• Fluctuating gas pressure.
No
Correct problem.
32
Page 33
HL2-DS Series
5.0 Troubleshooting Guide
NOTICE
Check to make sure gas pressure is within minimum and
maximum inputs, as indicated on the heater’s rating plate.
during normal operation or the heater’s built-in safety mechanisms will be compromised.
Is gas pressure OK?
No
Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
Correct problem.
Were the gas lines purged of air?
Ye s
No
Purge gas line.
Is the heater properly
grounded? Is the heater’s
polarity correct?
Ye s
With micro-ammeter, check amperage
at ame rod (or pins on circuit board).
Is it greater than 1.0 µA (micro-amp)?
Ye s
Replace gas valve.
Check to make sure ame
Ye s
sensor wire is OK and then
replace circuit.
No
Correct problem.
Sensing rod is faulty or ame is weak.
Check to make sure heater is operating
at proper gas pressure as indicated on the
heater’s rating plate and then, if needed,
No
replace sensing rod.
If the heater does not enter High Fire mode, check the following:
Check the power across the green
and black wires of the yellow
control cord. Is there 24 V?
No
NOTE: To conrm that the heater is not in high re
mode, check the manifold pressure. If it is 3.5” (natural gas) or 10” (propane), the indicator light is faulty and should be replaced. If approximately 2.0” to 2.5” (natural gas) or 5.0” to 6.5” (propane), the heater is in low
re mode and the troubleshooting steps described here
should be followed.
Repair or replace the faulty
wiring or thermostat.
Ye s
Measure the voltage across
the red wire on the relay
board and ground on the
circuit board. Is there 24 V?
Ye s
The valve is
faulty and must
be replaced.
No
The high re relay is faulty
and must be replaced.
33
Page 34
6.0 Maintenance • Routine Maintenance and Inspection
!
HL2-DS Series
6.0 Maintenance
WARNING
Personal injury or death may result if maintenance is not performed by properly trained gas installer or service personnel. Contact the installing distributor or place of purchase for service. Do not operate heating system if repairs are necessary.
Allow heater to cool prior to servicing. Disconnect power to heater before servicing. Use protective glasses when maintaining the heater.
Routine Maintenance and Inspection:
At least once per year, the heating system should be inspected and serviced by trained gas installation and service personnel only. This inspection should be performed at the beginning of the heating season to ensure that all heater components are in proper working order and that the heating system operates at peak performance. Particular attention should be paid to the following items.
• Clearances to Combustibles: Inspect the area near the unit to be sure there is no combustible material located within the minimum clearance requirements listed in this manual. Under no
circumstances should combustible material be located within the clearances specied in this
manual. Failure to provide proper clearance could result in personal injury or equipment damage
from re.
• Gas Connection: Inspect the integrity of the gas connection to the heater. Check for leaks,
damage, fatigue or corrosion. Do not operate if repairs are necessary and turn o gas supply to
the heater. Contact service personnel.
To check gas tightness of the safety shut-o valves, turn o the manual valve upstream of the appliance
combination control. Remove the hex head plug on the inlet side of the combination control and connect a manometer to that tapping.
Turn the manual valve on the apply pressure to the combination control. Note the pressure reading on
the manometer, then turn the valve o. Any loss of pressure indicates a leak. If leak is detected, use a
soap solution to check all threaded connection. If no leak is found, combination control is faulty and must be replaced before putting appliance back in service.
• Blower Motor: Annual oiling of the blower motor with SAE 20 oil will extend bearing life
signicantly. Ensure that the squirrel cage in the blower is kept clean. If dirt becomes a
problem, installation of outside air intake ducts for combustion is recommended.
Check lubrication instructions on motor. If oiling is required, add three or four drop of SAE 20
electric motor oil.
• After three years or 25,000 hour (for light-duty operation).
• Annually after three years or 8,000 hours (for medium-duty operation).
• Annually after one year or 1,500 hours (for heavy-duty operation).
Never over-oil the motor or premature failure may occur.
NOTICE
34
Page 35
HL2-DS Series
6.0 Maintenance Routine Maintenance and Inspection
• Heat exchangers: Check the integrity of the heat exchangers. Replace if there are signs of
structural failure. Check for corrosion and/or buildup within the tube exchanger passageways.
• Burner: Check for proper ignition, burner ame and ame sense. Flame should extend directly outward from burner without oating or lifting.
• Wiring: Check electrical connections for tightness and/or corrosion. Check wires for damage.
• Gas Connection: Inspect the integrity of the gas connection to the heater. Check for leaks,
damage, fatigue or corrosion. Do not operate if repairs are necessary and turn o gas supply to
the heater. Contact service personnel.
Reector: To maintain eective infrared heating, always keep both sides of the reector clean. Maintenance can vary signicantly depending on the environment. Dirt and dust can be vacuumed or wiped with a soap and water solution. Use metal polish if the reectors are severely
dirty.
Contact service personnel if repairs are necessary. Do not operate unit.
Maintenance Log
Date Maintenance Performed Replacement Parts Required
35
Page 36
7.0 Parts Heater Components and Parts List
HL2-DS Series
7.0 Parts
Figure 7.1 Burner Assembly Components
802B
70
1428
828
1018
55A
851B
3252
826
33B
31B
301
68A
886
212
264B
207
31B
219
223
204
1S
17
804B
3072
14 15
16
5
202
9C
10D
205
206
383A
50A
321
221
222
222A
83
84
76
TP-840A, 841A
208A
303B
Chart 7.1 Parts List
Part No. Description Part No. Description
TP-1S Control Box Cover - Stainless Steel TP-83 24” Stainless Steel Flexible Gas Connector
TP-5 Flange Gasket TP-84 1/2” Female/Male Flare Fitting
TP-9C 3/4” Conduit Coupling and Nut TP-202 16” HSI Burner Tube with Flange
TP-10D
TP-14 Sight Glass Gasket TP-205 Glo-Bar™ Holder
TP-15 Sight Glass TP-206 Glo-Bar™ Holder Spring Clip
TP-16 Sight Glass Washer TP-207 Pressure Switch Mounting Bracket
TP-17
TP-31B
TP-33B 1/2” Shut-O Ball Valve / Inlet Tap TP-219 Di. Vinyl Sensing Tube (Burner)
TP-50A Glo-Bar™ Ignitor TP-221 Glo-Bar™ Holder Gasket
TP-55A Fan Blower TP-222 Flame Rod
TP-65I 36” Interlocking Turbulator Bae TP-222A Flame Rod Wire
TP-68A Strain Relief Bushing TP-223 Gas Manifold
TP-70 Control Box Cover Gasket (per foot**) TP-264B Dierential Pressure Switch
TP-76 Rubber Grommet TP-301 Burner Control Box Center Panel
3” x 3/4” Metal Conduit
Sight Glass Kit
Control Box Mounting Bracket
TP-204 Gas Orice (consult factory)
TP-208A Gas Valve Mounting Bracket
TP-212 1/2” x 3” Pipe Nipple
36
Page 37
HL2-DS Series
Figure 7.2 Tube and Reector Components
7.0 Parts Heater Components and Parts List
801
809
880
885
879A
875
884
65I
7079
877
883 811A
881
877
876
809
803
7075
Chart 7.1 Parts List (cont.)
Part No. Description Part No. Description
TP-303B End Panel, Right - Black TP-876 7’ Unswedged Tube
TP-321 Ignition Plate Gasket TP-877 7’ Swedged Tube
TP-383A Glo-Bar™ Ignitor Plate TP-879A Mounting Bracket Assembly
TP-801 Reector Front Panel TP-880 Burner End Reector
TP-802B End Panel, Left - Black TP-881 U-End Reector
TP-803 Reector U-End Panel TP-883 Exhaust Downturn
TP-804B Burner Control Box Outer Shell - Black TP-884 Service Access Panel
TP-809 Support Bracket TP-885 Mounting Bracket
TP-811A Egg Crate Assembly (4 Per Heater) TP-886 Air Intake Hood with Birdscreen
TP-826 40 VA Transformer TP-1018 Di. Switch Silicone Sensing Tube (Exhaust)
TP-828 Amber Operational Indicator Light TP-1428 Green Operational Indicator Light
TP-840A Two-Stage Natural Gas Valve Assembly TP-3072 Burner (Green)
TP-841A Two-Stage Propane Gas Valve Assembly TP-3252 Wire Harness
TP-851B 35-66 Diagnostic Circuit Board TP-7075 U-Bend
TP-875 5’ Swedged Tube TP-7079 Mounting Bracket Assembly Support (Qty. 2)
37
Page 38
7.0 Maintenance Limited Warranty Terms and Conditions
HL2-DS Series
Limited Warranty Terms and Conditions
Three-Year Limited Warranty: The heaters covered in this manual are warranted by Detroit Radiant Products Company to the
original user against defects in workmanship or materials under normal use for three years after date of purchase. Any part which is determined to be defective in material or workmanship and returned to an authorized service location, as Detroit Radiant Products Company designates, shipping costs prepaid, will be, as the exclusive remedy, repaired or replaced at Detroit Radiant Products Company’s option. For limited warranty claim procedures, see PROMPT DISPOSITION below. This limited
warranty gives purchasers specic legal rights which vary from jurisdiction to jurisdiction.
Additional Limited Warranty: In addition to the above mentioned three-year warranty, Detroit Radiant Products Company warrants the original purchaser an additional extension on the heat exchangers and burners. This extension excludes electrical/purchased components.
General Conditions: The Company will not be responsible for labor charges for the analysis of a defective condition of the heater or for the installation of replacement parts. The warranties provided herein will not apply if the input of the heater exceeds the rated input at time of manufacturing or if the heater in the judgment of the Company has been subjected to misuse, excessive dust, improper conversion, negligence, accident, corrosive atmospheres, excessive thermal shock, excessive vibration, physical damage to the heater, alterations by unauthorized service personnel, operation contrary to the Company’s instructions or if the serial number has been altered, defaced, or removed. The Company shall not be liable for any default or delay in the performance of these warranties caused by contingency beyond its control, including war, government
restriction or restraints, strikes, re, ood, short or reduced supply of raw materials, or parts.
Limitation of Liability: To the extent allowable under applicable law, Detroit Radiant Products Company’s liability for consequential and incidental damages is expressly disclaimed. Detroit Radiant Products Company’s liability in all events is limited to and shall not exceed the purchase price paid.
Warranty Disclaimer: Detroit Radiant Products Company has made a diligent eort to provide product information and
illustrate the products in this literature accurately; however, such information and illustrations are for the sole purpose of
identication, and do not express or imply a warranty that the products are merchantable, or t for a particular purpose, or that the products will necessarily conform to the illustrations or descriptions. Except as provided below, no warranty or armation of fact, expressed or implied, other than as stated in the “LIMITED WARRANTY” above is made or authorized by Detroit Radiant
Products Company.
Product Suitability: Many jurisdictions have codes and regulations governing sales, construction, installation, and/or use of products for certain purposes, which may vary from those in neighboring areas. While Detroit Radiant Products Company attempts to assure that its products comply with as many codes, it cannot guarantee compliance, and cannot be responsible for how the product is installed or used. Before purchase and use of a product, review the product applications, and all applicable national and local codes and regulations, and be sure that the product, installation, and use will comply with them. Certain aspects of disclaimers are not applicable to consumer products: e.g., (a) some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you: (b) also, some jurisdictions do not allow a limitation on how long an implied warranty lasts, consequently the above limitation may not apply to you: and (c) by law, during the period of this limited warranty,
any implied warranties of implied merchantability or tness for a particular purpose applicable to consumer products
purchased by consumers, may not be excluded or otherwise disclaimed.
Prompt Disposition: Detroit Radiant Products Company will make a good faith eort for prompt correction or other
adjustment with respect to any product which proves to be defective within limited warranty. For any product believed to be
defective within limited warranty, rst write or call dealer from whom the product was purchased. Dealer will give additional
directions. If unable to resolve satisfactorily, write to Detroit Radiant Products Company at 21400 Hoover Road, Warren, Michigan 48089, listing dealer’s name, address, date and number of dealer’s invoice, and describe the nature of the defect.
Title and risk of loss pass to buyer on delivery to common carrier. If product was damaged in transit to you, le claim with
carrier.
38
Page 39
HL2-DS Series
Notes
7.0 Maintenance Notes
39
Page 40
7.0 Parts Kit Contents Check List
!
!
Kit Contents Check List
Chart 7.2 Kit Contents for HL2-DS Series
HL2-DS Series Kit Contents
TP-83
1/2” x 24” 304 Stainless Steel
Flexible Gas Connector
HL2DS-HANG*
Hanging Kit
HL2-DS Series
TP-885
Hanging Bracket (x2)
HL2DS-ASSY
Assembly Kit
TP-33B 1/2” Shut-O Valve
(Ball Valve & Inlet Tap)
LIOHL2DS
HL2-DS
Series
Installation,
Operation,
and
Maintenance
Manual
Detroit Radiant Products Company
HL2-DS Series Manual
The HL2-DS Series Infrared Tube Heater is a positive pressure, two-stage radiant heater system. This
manual provides specic information related to the HL2-DS series models. All persons involved with
the installation, operation, and maintenance of the heater system must read and understand the information in this manual.
For Your Safety
If you smell gas:
• Do not try to light any appliance. • Immediately call your gas supplier from a neighbor’s phone.
• Do not touch any electrical switch. • Follow the gas supplier’s instructions.
• Do not use any phone in your building. • If you cannot reach your gas supplier, call the re department.
INSTALLER: Present this manual to the end user.
Keep these instructions in a clean and dry place for future reference.
Model#: ______________________Serial #: _____________________________
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operation, and maintenance instructions thoroughly before installing or servicing this equipment.
This heater must be installed and serviced by trained gas installation and service personnel only. Failure to comply could result in personal injury, asphyxiation, death,
re, or property damage.
In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater thermostats or, in the absence of such thermostats, in a conspicuous location.
Not for residential use! Do not use this heater in the home, sleeping quarters,
hed garages, etc. Installation of a commercial tube heater system in
attac
residential indoor spaces may result in property damage, serious injury, asphyxiation, or death.
(located on rating label)
Part No. Description Quantity
TP-33B 1/2” Shut-O Valve and Inlet Tap 1
TP-83 1/2” x 24” 304 Stainless Steel Flexible Gas Connector 1
TP-885 Hanging Bracket 2
HL2DS-ASSY
#10 x 1/2” Screw (5), #8 x 1/2” S.S. Self-Tapping Screw (4), 3/8-16 x 3/8” Bolt, Flat Washer, End Panel Bracket (2)
1
3/8-16 x 3/8” Bolt (6), Flat Washer (6), Split Washer (6), Stainless Steel Bolts
HL2DS-HANG*
(4), Stainless Steel Keps Nuts (4), Stainless Steel S-Hooks (12), Zinc-Plated
1
Turnbuckle (4), #2 Stainless Steel Bulldog Chain (6)
Filled By:
* HL2DS-HANG Kit is not included when optional hanging bracket kit (P/N: DS-BKT20 or DS-BKT33) is ordered.
Approvals
• CSA
• Outdoor Approval
Limited Warranty
• 3 year - Burner box components
• 5 years - Combustion and radiant tubes
• 10 years - Stainless steel burner
• See page 38 for terms and conditions.
LIOHL2DS-Rev. 12917
Print: 1X-08/17 (DRPC)
Phone: (586) 756-0950 Fax: (586) 756-2626
www.detroitradiant.com • sales@drp-co.com
Printed in U. S. A.
© 2018 Detroit Radiant Products Co.
21400 Hoover Road • Warren, MI 48089
40
Loading...