Racktivity ES2000 Seriesl, ES6000 Series User Manual

User
Manual
ES2000 Series ES6000 Series
EnergySwitch
© 2011 Racktivity NV 2/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Contents
Contents .................................................................................................................................................. 2
Preliminary Information .......................................................................................................................... 5
Applicable Models ............................................................................................................................... 5
Specifications ....................................................................................................................................... 6
Overview .......................................................................................................................................... 6
Operating Environment ................................................................................................................... 7
Dimensions ...................................................................................................................................... 7
User Account Overview ................................................................................................................... 8
CLI Specifications ............................................................................................................................. 9
Safety ................................................................................................................................................. 10
Certifications ................................................................................................................................. 11
Compliance .................................................................................................................................... 11
Recycling ............................................................................................................................................ 12
Servicing & Repair ............................................................................................................................. 12
Additional Documentation ................................................................................................................ 12
Getting Started .................................................................................................................................. 13
Receiving Inspection ...................................................................................................................... 13
Inventory ....................................................................................................................................... 13
Installation ............................................................................................................................................. 14
Rack Mounting Instructions .............................................................................................................. 14
Mounting the EnergySwitch .............................................................................................................. 15
Additional Earthing ............................................................................................................................ 15
Connecting the EnergySwitch ............................................................................................................ 15
Overview................................................................................................................................................ 16
Front Panel ........................................................................................................................................ 16
Status LEDs ........................................................................................................................................ 16
Outlet LED ...................................................................................................................................... 16
Alarm LED ...................................................................................................................................... 16
Power LED ...................................................................................................................................... 16
Quick Configuration ............................................................................................................................... 17
Using the TFT Panel Display............................................................................................................... 17
Activating the Display .................................................................................................................... 17
Controlling the Display .................................................................................................................. 17
Hot Keys ......................................................................................................................................... 17
Network Settings ............................................................................................................................... 18
Firmware version 1.2 or higher ..................................................................................................... 18
© 2011 Racktivity NV 3/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Firmware version 1.1 or lower ...................................................................................................... 20
Web Interface ........................................................................................................................................ 24
Getting Started .................................................................................................................................. 24
Supported Web Browsers ............................................................................................................. 24
Logging in ....................................................................................................................................... 24
Layout ................................................................................................................................................ 25
Tabs ................................................................................................................................................... 26
Power............................................................................................................................................. 26
Environment .................................................................................................................................. 26
Logging .......................................................................................................................................... 26
Modules ......................................................................................................................................... 26
Management ................................................................................................................................. 27
Settings .......................................................................................................................................... 27
Network Configuration ...................................................................................................................... 28
SNMP Configuration .......................................................................................................................... 29
SNMP Settings ............................................................................................................................... 29
Device Settings .................................................................................................................................. 30
Thresholds ......................................................................................................................................... 30
Resetting Measurements .................................................................................................................. 32
Startup Delay ..................................................................................................................................... 32
Priority ............................................................................................................................................... 33
Overheat Protection .......................................................................................................................... 33
Network Time Protocol (NTP) ........................................................................................................... 33
CLI .......................................................................................................................................................... 34
Connecting ......................................................................................................................................... 34
UPS Integration ..................................................................................................................................... 35
Configuration ..................................................................................................................................... 35
Compatible Devices ....................................................................................................................... 35
Connecting the UPS ....................................................................................................................... 35
Enabling the Link ........................................................................................................................... 37
Operation .......................................................................................................................................... 37
Rules .................................................................................................................................................. 38
Agent Communication ........................................................................................................................... 40
Configuration ..................................................................................................................................... 40
Agent Service ................................................................................................................................. 40
EnergySwitch Configuration .......................................................................................................... 43
Logging .................................................................................................................................................. 45
Event .................................................................................................................................................. 45
© 2011 Racktivity NV 4/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Measurement .................................................................................................................................... 46
Management Information Base (MIB) .................................................................................................. 47
Upgrade Firmware ................................................................................................................................. 48
Obtaining Files ................................................................................................................................... 48
Troubleshooting .................................................................................................................................... 49
Downloading the diagnostics ............................................................................................................ 49
Resetting Login Credentials ............................................................................................................... 49
Connecting to the Web Interface ...................................................................................................... 49
Knowing your EnergySwitch’ IP Address ........................................................................................... 49
Support .................................................................................................................................................. 51
© 2011 Racktivity NV 5/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Preliminary Information
Applicable Models
Unless specified otherwise, all information in this document is applicable to the following Racktivity EnergySwitch devices:
ES2024-16 ES2024-32
ES2124-30L ES2124-32
ES6024-16 ES6024-20L
ES6124-16 ES6124-30L ES6124-32
Specifications
Overview
ES2024-16
ES2024-32
ES2124-30L
ES2124-32
ES6024-16
ES6024-20L
ES6124-16
ES6124-30L
ES6124-32
Voltage
200V - 240V
200V - 240V
200V - 240V
200V - 240V
200V - 240V
200V - 240V
200V - 240V
200V - 240V
200V - 240V
Frequency
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
Input, total: CE
16A
32A
30A
32A
16A
20A
16A
30A
32A
Input, total: cULus - -
24A - -
16A - 24A
-
Phase(s)
1 Φ
1 Φ
1 Φ
1 Φ
3 Φ
3 Φ
3 Φ
3 Φ
3 Φ
C13 Outlets (#)
24
24
21
21
24
24
21
21
21
C19 Outlets (#) 0 0 3 3 0 0 3 3
3
Output, bank: CE
16A
20A
20A
20A
16A
20A
16A
20A
20A
Output, bank: cULus - -
16A - -
16A - 16A
-
Output, outlet: C13
8A
8A
8A
8A
8A
8A
8A
8A
8A
Output, outlet: C19 - -
16A
16A - -
16A
16A
16A
Circuit breaker: 20A
Thermal
Thermal
Magnetic
Magnetic
Thermal
Thermal
Magnetic
Magnetic
Magnetic
The model number, input ratings, output ratings and certification information for your EnergySwitch are also shown on the label found on the case of the unit.
© 2011 Racktivity NV 7/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Operating Environment
Operating temperature
0°C to 50°C
32°F to 122°F
Storage temperature
-10°C to 60°C
14°F to 140°F
Humidity
5% to 85% RH
non-condensing
Dimensions
For the models:
ES2024-16 ES2024-32 ES6024-16
ES6024-20L
Dimensions cm (WxHxD)
5 x 171 x 9
Dimensions inch (WxHxD)
2 x 67.3 x 3.5
For the models:
ES2124-30L ES2124-32 ES6124-16 ES6124-30L ES6124-32
Dimensions cm (WxHxD)
5 x 181 x 9
Dimensions inch (WxHxD)
2 x 71.3 x 3.5
Some newer models may exceed these dimensions in height, please contact Support for exact
specifications.
© 2011 Racktivity NV 8/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
User Account Overview
The EnergySwitch has 3 types (levels) of user accounts: admin, restricted and guest. The following table shows an overview of the functionality of each type:
admin
restricted
guest
Open website
Yes
Yes
Yes
Open CLI session
Yes
Yes
Yes
View current status (states, data & values)
Yes
Yes
Yes
Toggle outlets
Yes
Yes
No
Edit thresholds
Yes
No
No
Edit outlet names
Yes
No
No
Change SNMP notification settings
Yes
No
No
Edit device settings
Yes
No
No
View & download logs
Yes
No
No
Default user name
admin
restricted
guest
Default password
1234
1234
1234
The same features and options apply to both the website and the Command Line Interface (CLI). To change the login credentials for a user account please refer to the Device Settings chapter.
© 2011 Racktivity NV 9/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
CLI Specifications
The CLI connector on the EnergySwitch has the following pin lay-out (as seen on the male plug):
Compatibility
The following brands/devices can be connected directly to the RS232 ports of the EnergySwitch using a standard straight-through RJ45 patch cable (unless noted otherwise):
Cisco
Cisco devices that have a Console which uses the pin lay-out of the 72-3383-01 Management cable (RJ45 - DB9)
Hewlett-Packard
HP devices that have a Console which uses the pin lay-out of the 5188-3836 Console cable (RJ45 - DB9) require that Pin3 (RxD) and Pin6 (TxD) are switched
Fortinet
Depending of the model, Fortinet devices either require that Pin3 (RxD) and Pin6 (TxD) are switched or can be connected using a standard patch cable
Pin
Function
1
-
2
-
3
TxD
4
GND
5
GND
6
RxD
7 - 8
-
© 2011 Racktivity NV 10/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Safety
Save these instructions!
This Safety Information contains important instructions that should be followed during installation and maintenance of the EnergySwitch. It is intended for Racktivity customers who set up, install, relocate, or maintain Racktivity equipment. Changes and modifications to this unit not expressly approved by Racktivity could void the warranty.
Electrical Hazard!
Read the following information before installing or operating your EnergySwitch:
Do not work alone under hazardous conditions. High current through conductive materials could cause severe burns. Follow all local and national codes when installing the EnergySwitch. To avoid possible electrical shock and equipment damage, use only the supplied hardware. The EnergySwitch should be connected to a single-outlet dedicated circuit, protected by a
circuit breaker with the same current rating as the EnergySwitch.
The plug serves as the disconnect for the EnergySwitch. Make sure the utility power outlet
for the EnergySwitch will be close to the EnergySwitch and readily accessible.
Make sure the utility power outlet and the EnergySwitch power cord and plug are in good
condition.
Do not connect the EnergySwitch to an ungrounded utility power outlet. Do not operate your EnergySwitch with any covers removed or when it is damaged. This EnergySwitch contains potentially hazardous voltages. There are no user serviceable
parts inside the EnergySwitch. All repairs and service should be performed by authorized service personnel only.
The power requirement for each piece of equipment connected to the EnergySwitch must
not exceed the individual outlet’s load rating.
The EnergySwitch provides convenient multiple power outlets, but it does not provide surge
or line noise protection for connected equipment.
The EnergySwitch is designed for indoor use only in a controlled environment away from
excess moisture, temperature extremes, conductive contaminants, dust, direct sunlight or magnetic sources.
The total power requirement for equipment connected to the EnergySwitch must NOT
exceed the maximum load rating for the EnergySwitch.
Do not attempt to mount the EnergySwitch to an insecure or unstable surface. Never attempt to install electrical equipment during a thunderstorm. Use of this equipment in life support applications or any medical applications is strictly
prohibited since failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety.
Putting several EnergySwitch units in cascade is NOT allowed.
© 2011 Racktivity NV 11/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
CAUTION:
The EnergySwitch contains a lithium battery and should not be disposed of with general refuge. Dispose of the lithium battery in accordance with all local codes and regulations for products containing lithium batteries. Contact your local environmental control or disposal agency for further details. The battery is not intended to be user replaceable.
Certifications
Not all certifications are applicable to every model. Please check the label on your device.
CE / FCC
This device is designed in compliance with the requirements of the 4 following regulations: EN 55022: Class B, EN 61000-3-2, EN 6100-3-3 and EN 55024. This device is certified to comply with Part 15 of the FCC rules.
UL (US & Canada)
This device is in the certification process to comply with rule UL /CSA 60950-1 (2nd Edition) safety of Information Technology Equipment (ITE) Part 1.
Compliance
WEEE
Waste Electrical and Electronic Equipment
RoHS
Restriction of Hazardous Substances
© 2011 Racktivity NV 12/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Recycling
The materials used for shipping the EnergySwitch are recyclable, please save them for later use or dispose of them appropriately.
Servicing & Repair
There are no user serviceable parts inside the EnergySwitch. All repairs and service should be performed by authorized service personnel only.
Please refer to the Service manual for RMA procedure.
Additional Documentation
Additional documentation regarding the following subjects is available on the Racktivity Support Website http://www.racktivity.com/support/.
API
o Manual o GUID Overview o (python) examples
Energy Sensor User Manual Servicing (RMA)
© 2011 Racktivity NV 13/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Getting Started
Receiving Inspection
Inspect the package (see the Inventory chapter) and contents for shipping damage and make sure that all parts were received. Report any damage immediately to the shipping agent and report missing contents, damage, or other problems immediately to your reseller.
Inventory
Please verify the contents of the box:
Standard Package
Item
Quantity
EnergySwitch
1
Power cable
1
Mounting bracket set Flat
1
Mounting bracket set 90°
1
Retention brackets
24
Quick Start Guide
1
© 2011 Racktivity NV 14/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Installation
Rack Mounting Instructions
Elevated Operating Ambient
When installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) of 50 ºC.
Reduced Air Flow
Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised. It is recommended that 2.5cm (1 inch) of clearance be supplied around the sides of the unit.
Mechanical Loading
Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading. The unit should be mounted with screws suitable for up to 10kg (22lbs).
Circuit Overloading
Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.
Reliable Earthing
Reliable earthing of the unit should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips).
Outlet accessibility
The socket-outlet shall be installed near the equipment and shall be easily accessible.
© 2011 Racktivity NV 15/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Mounting the EnergySwitch
1. Attach the 2 mounting brackets to the back of the EnergySwitch using the provided screws.
The brackets may be positioned for mounting on either side of the rack.
2. Attach the PDU to a vertical rail in your rack or rack enclosure. (Use the mounting hardware
that came with your rack or rack enclosure to attach the mounting brackets to the rail.)
Additional Earthing
The metal case of the EnergySwitch is electrically bonded to the line cord ground wire. A threaded grounding point on the front of the case may be used as an additional means of protectively grounding this product and the rack.
Connecting the EnergySwitch
1. For North America Connect the NEMA input plug to a compatible NEMA outlet receptacle.
For Europe and other countries using IEC 309 based power receptacles, connect to the IEC 309 receptacle compatible to the IEC 309 cord plug provided.
Note: The AC power source should not share a circuit with a heavy electrical load. It is recommended that the EnergySwitch be connected to a dedicated branch circuit.
2. The POWER LED (blue) will become active.
3. When using the device for the first time all OUTPUT LEDs will light up consecutively
indicating that the outlets are being activated.
Connect your equipment’s input plugs to the outlet plugs of the EnergySwitch.
© 2011 Racktivity NV 16/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Overview
Front Panel
Status LEDs
Outlet LED
ON
The corresponding outlet is turned on
OFF
The corresponding outlet is turned off and
the connected device is not receiving input power
Alarm LED
ON
Warning, at least one alarm: visit the Web Interface for more info
OFF
OK, no alarms triggered
Power LED
ON
The EnergySwitch is receiving input power
OFF
The EnergySwitch is unpowered
1
R-BUS A
RS485 peripheral bus connector A (for external modules)
2
R-BUS B
RS485 peripheral bus connector B (for external modules)
3
CLI
RS232 Command Line Interface connector
4
LAN
Ethernet connector (with connectivity indicator LEDs)
5
TFT
Color graphics TFT display
6
UP
Move to the previous page or to browse upwards in a list
7
MENU
Access menu function or return to the previous screen
8
DOWN
Move to the next page or to browse downwards in a list
9
OK
Enter or validate
10
ALARM LED
Alarm LED
11
POWER LED
Power LED
-
OUTLET
Outlet banks with connectors (C13, C19, …)
-
FUSE
Fuse (see labeling for fuse specifications)
-
EARTH
Device earthing (M5)
-
INLET
Inlet plug
© 2011 Racktivity NV 17/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Quick Configuration
Using the TFT Panel Display
Activating the Display
When the Power LED is lit and the screen is black, push any of the 4 navigation buttons next to the TFT Display to activate it. The TFT Panel standby delay can be set at the Settings page on the Web Interface (the default value is 10 minutes).
Controlling the Display
The TFT Panel is controlled using the UP, DOWN, MENU and OK buttons next to the screen. Use the UP and DOWN buttons to navigate through the reporting screens or through a selection list in the menus. Press OK to select the highlighted item and MENU to go back. When in a menu, the ">" symbol indicates that clicking this item will open a submenu. The "●" symbol indicates that this menu item leads directly to a setting.
Hot Keys
Several Hot Key combinations are available by using the navigation buttons next to the display. To activate the functions, press the necessary buttons simultaneously for 4 seconds (until a notification is shown on screen).
Hot Key
Buttons
Action
Hot Reset
MENU + DOWN
Reboots the device
No outlets toggled, no settings changed
Credential Reset
UP + DOWN
Resets the login credentials
No outlets toggled, login credentials set to default
Factory Reset
MENU + OK
Resets all non-power related settings to factory
defaults (network, …), no outlets are toggled
© 2011 Racktivity NV 18/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Network Settings
There are two methods for setting up the IP address: Dynamic IP address assignment and Manual Assignment. If you are uncertain which method to use, contact your network administrator for assistance before continuing the installation process.
Depending on the firmware version of the EnergySwitch, the menu interface on the TFT has a different layout.
Note: As of firmware version v1.2 the EnergySwitch has secure HTTP (HTTPS) enabled by default. Use ‘https://’ instead of ‘http://’ in your browser to access the web portal.
Firmware version 1.2 or higher
Dynamic IP Address Assignment (DEFAULT)
1. Press the MENU button until the MAIN menu appears, select Network Settings using the
DOWN button and press OK.
2. Within the Network Settings menu, select DHCP. When the value at the bottom of the
screen shows Enabled, the device already has dynamic IP assignment enabled (skip to step
4). If not, press OK and verify that Enabled is displayed at the bottom of the screen.
3. Use the UP button to select Apply Settings and press OK. Press the MENU button to cancel
or the OK button to apply the settings.
© 2011 Racktivity NV 19/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
4. Press DOWN to select IP Address. The assigned IP-address is shown at the bottom of the TFT.
5. On a computer in the same network, use a browser to open the assigned IP-address, for
example https://192.168.14.250
6. When surfing to the web portal, a login screen appears. The default user name is admin and
the default password is 1234
Manual IP Address Assignment
1. Obtain the correct IP address, standard gateway, DNS Server IP and subnet mask from your
network administrator.
2. Press the MENU button until the MAIN menu appears, select Network Settings using the
DOWN button and press OK.
3. Within the Network Settings menu, select DHCP. When the value at the bottom of the
screen shows Disabled, the device already has manual IP assignment enabled (skip to the next step to enter a different IP). If not, press OK and verify that Disabled is displayed at the bottom of the screen.
© 2011 Racktivity NV 20/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
4. Use the UP button to select IP Address and press OK.
5. Use the UP and DOWN buttons to change the currently selected value and press OK to select
the next value. When holding the UP and DOWN buttons changing the values speeds up. When ready press MENU to confirm and return to the Network Settings menu.
6. Repeat the last two steps for the Subnet Mask, Standard Gateway and DNS Server settings.
7. Use the UP button to select Apply Settings and press OK. Press the MENU button to cancel
or the OK button to apply the settings.
8. On a computer in the same network, use a browser to open the chosen IP-address, for
example https://192.168.14.250
When surfing to the web portal, a popup appears requesting a username and password. The default username is admin and the default password is 1234
Firmware version 1.1 or lower
Dynamic IP Address Assignment (DEFAULT)
7. Press the MENU button until the MAIN menu appears, select NETWORK using the UP and
DOWN buttons and press OK.
© 2011 Racktivity NV 21/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
8. Within the NETWORK menu, select Use DHCP. When the value in yellow at the bottom of the
screen shows yes, the device already has dynamic IP assignment enabled; if not, press OK.
9. Use the UP and DOWN buttons to change the setting. Select yes and press MENU to confirm
and return to the NETWORK menu.
10. Use the UP and DOWN buttons to select Save IP Settings and press OK. Use the UP and
DOWN buttons to change the setting. Select yes and press MENU to save and return to the NETWORK menu.
11. Press UP to select CURRENT IP-ADDRESS. The assigned IP-address is shown in yellow at the
bottom of the TFT.
12. On a computer in the same network, use a browser to open the assigned IP-address, for
example http://192.168.14.250
13. When surfing to the web portal, a login screen appears. The default user name is admin and
the default password is 1234
© 2011 Racktivity NV 22/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Manual IP Address Assignment
9. Obtain the correct IP address, standard gateway, DNS Server IP and subnet mask from your
network administrator.
10. Press the MENU button until the MAIN menu appears, select NETWORK using the UP and
DOWN buttons and press OK.
11. Within the NETWORK menu, select Use DHCP. When the value in yellow at the bottom of the
screen shows no, the device already has a fixed IP; if not, press OK.
12. Use the UP and DOWN buttons to change the setting. Select no and press MENU to confirm
and return to the NETWORK menu.
13. Use the UP and DOWN buttons to select SET IP-ADDRESS and press OK.
14. Use the UP and DOWN buttons to change the currently selected value and press OK to select
the next value. When holding the UP and DOWN buttons changing the values speeds up. When ready press MENU to confirm and return to the NETWORK menu.
© 2011 Racktivity NV 23/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
15. Repeat the last two steps for the Subnet mask, StdGateway and DNS Server settings.
16. Use the UP and DOWN buttons to select Save IP Settings and press OK. Use the UP and
DOWN buttons to change the setting. Select yes and press MENU to save and return to the NETWORK menu.
17. On a computer in the same network, use a browser to open the chosen IP-address, for
example http://192.168.14.250
18. When surfing to the web portal, a popup appears requesting a username and password. The
default username is admin and the default password is 1234
© 2011 Racktivity NV 24/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Web Interface
Getting Started
Supported Web Browsers
The following browsers have been tested and work with the EnergySwitch’ Web Interface (on
most platforms):
Internet Explorer 8 or higher Firefox 3.6.16 or higher Chrome 11.0.696.71 or higher Opera 11.11 or higher Safari 5.0.5
Other available web browsers may work with the EnergySwitch but have not been fully tested by Racktivity.
Logging in
For instructions on how to set up the TCP/IP settings to connect to the Web Interface, please see the Network Settings chapter. To recover from a lost password, please refer to the Troubleshooting chapter.
Use an internet browser to open the EnergySwitch’ IP address. You will be asked for login credentials, the default values for the administrator account are:
User name
admin
Password
1234
To find out everything about the different types of user accounts see the User Account Overview chapter. If you are presented with a warning about the connection being untrusted (self-signed certificate) it can be ignored.
© 2011 Racktivity NV 25/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Layout
1
Sub tabs
Displays the different sections of the selected main tab
2
User account
Displays which type of User Account is currently logged in
3
Main tabs
Displays the different functions of the EnergySwitch
4
Device info
Displays the device name, rack name & rack location. Can
be changed at the settings tab
5
Outlet status
Displays the current status of each outlet:
GREY: the outlet is turned off GREEN: the outlet is on and working normally ORANGE: a warning threshold has been crossed, but the port
state has not yet changed (only visible on the Overview tab and the affected parameter’s tab)
RED: an off threshold has been crossed, port state has changed BLUE: the outlet will be toggled after the set delay has expired
(during boot and whilst power cycling)
6
Outlet toggle
Toggle the outlet state (ON/OFF/CYCLE)
7
Save
Save any changes made on this page
8
Outlet name
Change the outlet’s name
9
SNMP
Toggle a specific SNMP notification for that outlet
10
Device time
The time set on the Settings tab (either manual or through an
NTP server)
11
Banks
Power bank/module selection (only on 0U models)
© 2011 Racktivity NV 26/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Tabs
Power
Use the Power Tab for the following:
See the load and general status of both the EnergySwitch’s individual outlets and the
totals:
o Amps o Wattage o Power Factor o Energy (kWh) o Apparent Energy (kVAh) o Voltage
Control and manage outlets Configure thresholds for connected loads, banks (as applicable) Resetting measurements Change SNMP notifications for power related parameters (outlet toggle, amps, wattage) Manage outlet scheduling Control fuse and/or line currents Oscilloscope view for an outlet Overview of connected Agents
Environment
Use the Environment Tab to monitor and manage:
Internal sensors (as applicable) Voltage: status, history and management
Logging
The logging tab provides access to both the Event and the Detailed logging. After selecting the desired module and time-range the log can be downloaded or viewed inside the browser. For more information regarding this subject, please refer to the Logging chapter.
Modules
Use this tab to control connected Energy Sensors. For more information regarding the modules tab, please see the Energy Sensor documentation. Note: This tab is available as of firmware version 1.2 and above; and with a managed Energy Sensor.
© 2011 Racktivity NV 27/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Management
The management tab is used to manage the modules in an EnergySwitch setup, including Energy Sensors. For more information regarding the managing of Energy Sensors, please see the Energy Sensor documentation. Available as of firmware version 1.2
Settings
Use this tab to configure the following settings:
Network SNMP Telnet Device and User Accounts NTP (Network Time Protocol) Startup delay and priority Overheat protection Energy Cloud Sentinel Uninterruptible Power Supply (UPS)
© 2011 Racktivity NV 28/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Network Configuration
path: Settings > Network Settings
The Network Settings contains both the Network and the SNMP related settings. The SNMP related settings can be found in the SNMP Configuration chapter. The following Network settings are editable:
Device IP Address
o The IP address of the EnergySwitch*
Subnet Mask
o The subnet mask of the EnergySwitch
Standard Gateway
o The IP address of the default node on the network
DNS Server
o The IP address of the Domain Name System (DNS) server
Enable DHCP
o Check to enable DHCP
Force secure web access (HTTPS)
o Check to force secure HTTP web access
Force secure telnet access (SSL)
o Check to force SSL telnet access
* Note: When DHCP is enabled, the Network Settings are not necessarily the ones shown here,
since they are provided by the DHCP server. Disabling DHCP will force the EnergySwitch to use the provided Network Settings.
© 2011 Racktivity NV 29/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
SNMP Configuration
The EnergySwitch offers SNMPv2 communication (GETs, SETs and traps). Notifications (traps) can be enabled or disabled for many of the device’s functions:
Outlet state change Outlet thresholds (current, power, …) Totals thresholds (current, power, …) Temperature thresholds Voltage thresholds Overheat protection
To toggle SNMP for a specific parameter or function, (un)check that parameter’s checkbox and
press the Save button. The SNMP checkboxes can be found next to most measurements.
SNMP Settings
path: Settings > Network Settings
The Network Settings contains both the Network and the SNMP related settings. The network related settings can be found in the Network Configuration chapter. The following SNMP settings are editable:
SNMP Community read
The community read string for GET requests
SNMP Community write
The community write string for SET requests
SNMP Trap Community string
Community string used when sending SNMP traps
SNMP Trap Receiver port
The port (1 - 65535) on which traps will be sent
SNMP Trap Receiver IP
IP address of the trap receiver
Enable SNMP write protection
Check this box to disable SNMP write (SET) access to the EnergySwitch completely
Enable SNMP Traps for device
The EnergySwitch will not send any traps when unchecked, regardless of individual settings
Use ECS authentication
Toggles the use of an external authentication server
ECS Authentication server IP
The IP address of the authentication server
ECS Authentication server port
The port (1 - 65535) of the authentication server on which the connection will be made
© 2011 Racktivity NV 30/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Device Settings
The Device Settings give access to
EnergySwitch identification
o Device name: the name of the EnergySwitch o Rack name: the name of the rack where the EnergySwitch is located o Rack position: the identifier of the position in the rack
UPS Integration
o Uninterruptible Power Supply: select UPS to connect to (enables the UPS tab)
User account settings (see the User Account Overview chapter)
o Admin o Restricted user o Guest
TFT settings
o TFT timeout: the idle time in minutes after which the TFT goes into standby o TFT display lock: when checked the TFT (and buttons) cannot be used to change
settings. All changes must be made through the website.
Temperature
o Temperature unit: degrees Celsius (°C) or Fahrenheit (°F)
Clock settings (see the Network Time Protocol (NTP) chapter)
o Date & Time Settings: The real-time clock dialog features several options.
Uncheck the Use NTP checkbox to be able to set a custom date & time. Uncheck the Use default NTP checkbox to not use an NTP server from pool.ntp.org and enter the custom IP address into the NTP address field.
Note: Making changes to the date/time settings might clear all logged data!
Thresholds
Thresholds can be configured and used so that you are notified through SNMP at certain events.
Many of the EnergySwitch’s parameters have settable thresholds. To configure a specific
threshold, open the tab where the appropriate parameter is shown.
At least the following parameters have one or more settable thresholds:
Amperage
o path: Power > Current
Wattage
o path: Power > Power
Voltage
o path: Environment > Voltage
Ambient
o path: Environment > Ambient
© 2011 Racktivity NV 31/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
External modules
o path: Environment > External Modules
Overheat Protection
o path: Settings > Overheat Protection
Depending on the parameter one or more of the following types of thresholds will be available:
Warning: The outlet state is not changed, only an SNMP notification is sent Switch Off: The designated outlet is toggled off and an SNMP notification is sent Low: When the measurement goes below this value an SNMP notification is sent High: When the measurement goes above this value an SNMP notification is sent
To change a threshold enter the desired value into the appropriate input area and press the Save button. If the background of the input area turns red an incorrect value has been entered.
Note: Most thresholds have corresponding SNMP checkboxes that enable/disable the
notification. Please ensure both the threshold and the appropriate SNMP notifications are set correctly.
© 2011 Racktivity NV 32/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Resetting Measurements
For many parameters the minimum, maximum and/or total is saved to give an easy overview of load activity. These values van be easily reset by pressing the Reset link for that value.
The following parameters have resettable values:
Individual & total amperage
o path: Power > Current
Individual & total wattage
o path: Power > Power
Individual & total power factor
o path: Power > Power
Individual & total real energy (kWh)
o Note: The Accumulated kWh counter is not resettable! o path: Power > Energy
Individual & total Apparent Energy (kVAh)
o Note: The Accumulated kVAh counter is not resettable! o path: Power > Energy
Temperature
o path: Environment > Ambient
Voltage
o path: Environment > Electrical
Note: Clicking a Reset link in the column header will reset all values in that column, except for
the value in the Total row.
Startup Delay
path: Settings > Startup Delay & Outlet Importance
The startup delay shown in the table is the time in seconds at which the designated outlet will switch on after boot. By default the delay is set incrementally over the outlets to reduce the overall power peaks of booting loads.
Note: An outlet will only switch on at boot if it was on before the EnergySwitch was powered
down.
© 2011 Racktivity NV 33/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Priority
path: Settings > Startup Delay & Outlet Importance
The Importance column gives a rating from 1 to 8 to each outlet. A rating of 1 indicates the highest importance, whilst 8 is the lowest. When the Total (device) off threshold for the amperage and/or wattage is crossed (but none of the individual off thresholds) the EnergySwitch will use the importance rating to determine which outlet to switch off first. If two or more outlets have the same rating, the outlet with the last peak load will be switched off first.
Overheat Protection
path: Settings > Overheat Protection
The EnergySwitch has built in temperature sensors that can help prevent overheating. For more information regarding the thresholds and event notifications please refer to the Thresholds and SNMP Configuration chapters.
Note: The EnergySwitch has a built-in safety that switches off all ports when the temperature
hits 60°C (140°F) regardless of the settings in the Overheat Protection section.
Network Time Protocol (NTP)
path: Settings > Device Settings
The Network Time Protocol (NTP) is a protocol for synchronizing the clocks of computer systems over networks. The EnergySwitch is equipped with an onboard clock that can be setup to sync with:
pool.ntp.org (default) a custom NTP server date & time picker
For more information regarding the configuration of the onboard clock please refer to the Device Settings chapter.
© 2011 Racktivity NV 34/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
CLI
The EnergySwitch has a built in Command Line Interface that can be accessed through both the CLI connector on the front or via Telnet. Commands are typically sent to the separate modules. An EnergySwitch consists of exactly 1 master module and 1 or more power modules, controlled by the master. Each module is of a specific type: ‘M’ for master module, ‘P’ for power module, ‘A’ for sensor module. The master will always have address M1, power modules can have addresses P1, P2, P3, ….
Connecting
CLI connector
Connect a standard cat. 5e patch cable to both the CLI connector and your pc (i.e. by using an RS232 to USB adapter). For the CLI Specification, see the CLI Specifications chapter.
Connection settings: 115200/8-N-1 (115200Bd, 8 data bits, no parity, 1 stop bit)
Telnet
Connect to the device IP on port 23 over Telnet. Please note that only Telnet over SSL is enabled by default. This can be changed on the Settings tab on the WebGUI of the energy switch.
Telnet-SSL
Connecting to Telnet over SSL can be achieved through several 3rd party tools. For example using stunnel (cross platform):
Edit the configuration file for stunnel called stunnel.conf so it contains only the following:
fips = no cert = stunnel.pem
client = yes [pdu] accept = 127.0.0.1:23 connect = [DEVICE_IP]:992 sslVersion = SSLv3
(with [DEVICE_IP] being the IP address of the PDU)
Start stunnel with this config:
# stunnel stunnel.conf
If you now Telnet to 127.0.0.1 on port 23, stunnel will tunnel the traffic over SSL to the specified IP.
Once connected, you will be presented with a log-in screen. Use the admin credentials to gain full access. From here it is possible to access the majority of the EnergySwitch’s functions. Type “help” for more information.
© 2011 Racktivity NV 35/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Note: The complete CLI interface is available as from firmware version 1.1.x.x Version 1.0.x.x
and below only have a reduced interface (or less). For more information regarding a firmware upgrade see the Upgrade Firmware chapter.
UPS Integration
As of firmware version 1.3, your EnergySwitch PDU features UPS integration functionality. This enables the EnergySwitch to receive vital battery information from a connected UPS and perform actions when set parameters and rules are met. In order to use the full capabilities of the functionality, 2 components need to be installed and configured correctly:
UPS Integration
The link with the UPS in the rack, as explained in this chapter.
Agent Communication
Communication with the Agent service on connected servers (for more details see the Agent Communication chapter).
Configuration
Compatible Devices
The following UPS models can be linked to your EnergySwitch PDU:
Most APC Smart-UPS® models (except Microlink enabled devices)
Connecting the UPS
The EnergySwitch and the UPS are connected using the following cable configuration:
On the side of the EnergySwitch: a standard RJ45 plug (with the pin layout as described in the
© 2011 Racktivity NV 36/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
CLI Specifications chapter) connected to the CLI connector on the front of the unit.
On the side of the UPS: a DB9 male connector.
RJ45
DB9
Function
Pin Pin
Function
Tx 3 1 Rx
GND 4
9
GND
GND 5
Rx 6 2 Tx
© 2011 Racktivity NV 37/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Enabling the Link
Once the EnergySwitch and UPS are physically connected it is necessary to enable the functionality on the Web Interface of the EnergySwitch.
1. Open the EnergySwitch' Web Interface
2. Click the Settings tab, followed by the Device Settings subtab
3. Select the appropriate option from the list under Uninterruptible Power Supply (UPS)
4. Press the Save button
5. The Uninterruptible Power Supply (UPS) subtab is now available on the Settings tab
Note: When UPS integration is enabled the CLI connector on the front of the EnergySwitch can no longer be used to access the Command Line Interface. CLI over Telnet remains accessible. To restore CLI functionality over the CLI connector, UPS Integration must be disabled.
WARNING: If both UPS Integration is enabled and Agent Communication is correctly configured the EnergySwitch will perform automated actions according to strict pre-defined rules (based on battery level, UPS status, etc.). Please review these rules and actions carefully to avoid
unexpected behavior.
Operation
Once the UPS communication has been configured and established successfully, the following items are available on the Settings > Uninterruptible Power Supply (UPS) sub tab:
Communication status
o Checked: The communication between the EnergySwitch and UPS is operational o Unchecked: No communication with the UPS, the settings below can be ignored
UPS running on battery
o Checked: The connected UPS is running on battery power (batteries draining) o Unchecked: The connected UPS is running on mains power (batteries charging)
Battery Level
The current level of battery power left in the connected UPS (in %), refreshed every 10 seconds.
UPS Emergency Threshold
The emergency battery level threshold of the connected UPS (in %). When the UPS battery is draining and this level is crossed certain actions will be performed automatically.
UPS Recovery Threshold
The recovery battery level threshold of the connected UPS (in %). When the UPS battery
© 2011 Racktivity NV 38/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
is charging and this level is crossed certain actions will be performed automatically.
UPS Recovery Power Threshold
The powered outlets and outlets marked as AlwaysOn with respective power consumptions below the recovery power threshold (in W) will be power cycled when the UPS is running on mains power and the battery level goes above the Battery Recovery Threshold (assuming that the battery level dropped below the Battery Emergency Threshold first). For more information see the Rules chapter.
SNMP Warning
o Checked: SNMP traps will be sent when:
UPS Communication status changes UPS switches between battery or mains UPS Emergency Threshold is crossed UPS Recovery Threshold is crossed
o Unchecked: No SNMP traps are sent
To enable the EnergySwitch to perform actions based on the UPS Integration data please also refer to the Agent Communication chapter.
Rules
If both UPS Integration is enabled and Agent Communication is correctly configured the EnergySwitch will perform automated actions according to strict pre-defined rules (based on
battery level, UPS status, etc.).
Please review the following rules and actions carefully to avoid unexpected behavior.
1. When the EnergySwitch boots, communication with the UPS is OK and the Battery Level
is above the UPS Recovery Threshold the outlets will be powered as configured by the user.
2. When the EnergySwitch boots, communication with the UPS is OK and the Battery Level
is below the UPS Recovery Threshold only outlets marked with Prevent Outlet Shutdown (see the EnergySwitch Configuration chapter) will be powered.
3. When the EnergySwitch boots and communication with the UPS fails, only outlets
marked with Prevent Outlet Shutdown will be powered.
4. When the UPS is running on battery and the Battery Level drops below the UPS
Emergency Threshold the EnergySwitch will send a shutdown command to all associated agents.
5. When the communication with the UPS fails for 5 minutes a shutdown command is sent
to all associated agents of powered outlets.
6. When the UPS switches from mains to battery power while the Battery Level is below
the UPS Emergency Threshold a shutdown command is sent to all associated agents of powered outlets.
© 2011 Racktivity NV 39/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
7. After the Battery Level dropped below the UPS Emergency Threshold and the UPS is
running on mains power again and the Battery Level goes above the UPS Recovery Threshold: All powered outlets and outlets marked with Prevent Outlet Shutdown will be power cycled if their respective power consumptions are below the UPS Recovery Power Threshold.
© 2011 Racktivity NV 40/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Agent Communication
As of firmware version 1.3, your EnergySwitch PDU features Agent Communication functionality. This enables the EnergySwitch to communicate to installed Agents on connected devices (servers, etc.) and perform actions when set parameters and rules are met. The Agent will also
monitor the system it is installed on. In order to use the full capabilities of the functionality, 2 components need to be installed and configured correctly:
Agent Communication
Communication with the Agent service on connected servers.
UPS Integration The link with the connected UPS in the rack (for more details see the UPS Integration chapter).
When UPS Integration is not enabled, communication to connected Agents will be limited to manual actions only.
Configuration
Setting up Agent Communication is a 2-step process:
1. Installing and configuring the Agent service on the connected devices.
2. Configuring the EnergySwitch to communicate to the installed Agent.
WARNING: If both UPS Integration is enabled and Agent Communication is correctly configured the EnergySwitch will perform automated actions according to strict pre-defined rules (based on battery level, UPS status, etc.). Please review these rules and actions carefully to avoid
unexpected behavior.
Agent Service
The Racktivity Agent service can be installed on both physical and virtual machines and is used to monitor certain system parameters and to allow the EnergySwitch or the user to perform a graceful shutdown or restart. The system monitoring is performed at a 30 second interval and collapsed every 5 minutes. The collapsed data can be retrieved from the Agent or sent to a predefined URL. This data will allow the Racktivity DCPM platform to provide very detailed and accurate power consumption down to application level.
The current version (v1.0) of the Agent service monitors the following:
Global CPU usage Total number of processes Top 10 processes according to CPU usage Disks and their storage info: mount point, used bytes, available bytes
Future releases will add the following monitored items:
© 2011 Racktivity NV 41/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Network interfaces and their info: IP, transmitted bytes, received bytes CPUs and their info: speed, cores, sockets, cores per socket, load All processes and their info: name, CPU usage, memory usage, connections (src IP, src
port, dst IP, dst port, duration, amount)
Installation
The Agent installation package can be obtained by contacting Support and is available for the following operating systems and distributions:
Windows Linux Debian
After installation, the Agent configuration file (agent.ini) can be found at:
Windows
C:\Program Files\Racktivity\agent.ini or C:\Program Files (x86)\Racktivity\agent.ini
Linux
/etc/racktivity/agent.ini
Configuration
The agent.ini file contains the following sections and editable parameters:
MAIN
host: The IP on which the Agent listens
0.0.0.0 means listen on any available IP address.
Default: 0.0.0.0
port: The port on which the Agent listens
Default: 6666
workers: The amount of worker threads that are used to handle the connections.
Don’t change this setting
Default: 4
allowed: A comma separated list of IPs (cannot contain whitespace characters) that are
allowed to communicate with the Agent. If the IP is not in the list the connection is closed instantly.
Default: an empty list
debug: Whether or not the Agent adds debug information the logs and/or console. Set to
1 to enable.
Default: 0
SHUTDOWN
url: The URL of the web page that will be called when the shutdown command is
received. When this value is left empty the machine on which the Agent is running will be
© 2011 Racktivity NV 42/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
shut down. When this value is set to 'disabled' no action will be performed. Default: disabled
REBOOT
url: The URL of the web page that will be called when the restart command is received.
When this value is left empty the machine on which the Agent is running will be restarted. When this value is set to 'disabled' no action will be performed. Default: disabled
MONITOR
interval: The interval (in milliseconds) at which the system is monitored.
Default: 30000
pushurls: A comma separated list of URLs that receive the data that is collapsed every 5
minutes. The data is sent in JSON format to the URLs by POST as the data parameter. Default: an empty list
backlogsize: The amount of collapsed monitored data points sets that are kept in
memory. Default: 6
Additional Commands
The following binary commands are accepted by the Agent service:
shutdown: Calls the shutdown URL or shuts down the machine (depending on the
configuration). Example: shutdown
reboot: Calls the reboot url or reboots the machine (depending on the configuration).
Example: reboot
reconfigure: Sets a configuration parameter on the agent side.
Example: reconfigure:shutdown.url=disabledA0B1C2D3E4F5G6H7I8J9 In the example we set the URL parameter of the shutdown section to disabled. "A0B1C2D3E4F5G6H7I8J9" is the SHA1 hash of "reconfigure:shutdown.url=disabled" appended with the IP where the command is coming from. For instance if we send the command from 192.168.1.1 the SHA1 hash is calculated from "reconfigure:shutdown.url=disabled192.168.1.1".
configuration: Gets a configuration parameter from the agent.
Example: configuration:shutdown.urlA0B1C2D3E4F5G6H7I8J9 In the example we get the URL parameter of the shutdown section. "A0B1C2D3E4F5G6H7I8J9" is the SHA1 hash of "configuration:shutdown.url" appended with the IP where the command is coming from. For instance if we send the command from 192.168.1.1 the SHA1 hash is calculated from
"configuration:shutdown.url192.168.1.1".
For more information regarding the binary commands, please contact Support.
The following HTTP command is also accepted by the Agent service:
/getlast5min: Gets the monitored data of the last 5 minutes in a JSON format. Make sure
that the IP requesting the command is added to the allowed list of the Agent configuration. Example: http://192.168.14.250:6666/getlast5min
© 2011 Racktivity NV 43/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
EnergySwitch Configuration
To configure Agent Communication on the EnergySwitch: login to the web interface and open the Power > Agent sub tab.
For each outlet the following options are available:
State
Toggle the state of the outlet. Outlets can be switched on, off or power cycled.
Name
Change the name of the outlet.
Prevent Outlet Shutdown
When checked the outlet can no longer be toggled off manually and - with UPS integration enabled - will be managed differently (see the Rules chapter for more information). Mostly used for vital rack equipment.
Agent IP
IP of the machine where the Agent for that outlet is installed. Shutdown and/or restart commands will be sent to this IP.
Agent Port
Network port of the machine where the Agent for that outlet is installed.
Agent SNMP Flag
When checked, SNMP traps are sent when the command was sent successfully or unsuccessfully.
Clean Shutdown
Clicking the Shutdown link will send the shutdown command to the configured Agent of that outlet.
Restart
Clicking the Restart link will send the shutdown command to the configured Agent of that outlet.
© 2011 Racktivity NV 44/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
A Shutdown or Restart command can also be sent to an associated agent manually through the use of an HTTP API (when logged in as administrator):
https://[DEVICE_IP]/agent.cgi? ADDR=P[X]&INDEX=[Y]&CMD=[z]
o [DEVICE_IP]: IP of the PDU o [X]: Number of the power module
ES1000 Series: 1 ES2000-6000 Series: 1-3
o [Y]: Number of the outlet (1 - 8) o [Z]: Command switch:
0 = shutdown command 1 = restart command
© 2011 Racktivity NV 45/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Logging
There are currently 2 types of logging available. Both can be downloaded from the Web Interface or through the API for your convenience.
Event
path: Logging > Event
The Event log is used to keep a history of all important events. Fill in the available fields and view the log in your browser or download it for offline use.
Module
Select the appropriate module.
Start time
The starting date & time for the log.
End time
The ending date & time for the log.
Download
Download the log as a text file.
Show
View the log in your browser.
The Log is displayed as a table with the following columns (from left to right):
Timestamp
The timestamp of the event.
Event type
The type of event: outlet toggle, threshold violation, …
GUID
The GUID of the control. For more info regarding GUIDs please refer to the ES Series - API Manual.
Value
The value that was returned by the event (voltage, temperature, etc.)
© 2011 Racktivity NV 46/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Measurement
path: Logging > Measurement
The Measurement log returns a binary file with monitoring data of the selected module. For interpretation of the data in this file, refer to the manual of the selected device.
It’s possible to select a specific Measurement log file by configuring the following options:
Type
The type of Measurement log
Module
Select the appropriate module.
Start time
The starting date & time.
End time
The ending date & time.
Download
Download the log as a text file.
© 2011 Racktivity NV 47/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Management Information Base (MIB)
A management information base (MIB) is a virtual database used for managing the entities in a communications network and is most often associated with the Simple Network Management Protocol (SNMP). The EnergySwitch features a built-in mib file which can be found at the following location:
For firmware version v1.3.x.x and above: https://[DEVICE_IP]/ES-RACKTIVITY-MIB.txt
A direct link to the MIB file is also available under Settings > Network Settings
For firmware version v1.2.x.x and above: https://[DEVICE_IP]/ES-RACKTIVITY-MIB.txt
For firmware version v1.1.x.x and above: http://[DEVICE_IP]/ES-RACKTIVITY-MIB.txt
For firmware version v1.0.1.x and below: http://[DEVICE_IP]/ES202430-MIB.txt
Where [DEVICE_IP] is the IP of your EnergySwitch (i.e.: 192.168.14.250).
Use this file to translate the OIDs (Object IDentifiers) available over SNMP to a more human­readable state. For more information on how to use the MIB file, please refer to the documentation of your network monitoring software.
© 2011 Racktivity NV 48/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Upgrade Firmware
Racktivity is always working on improving and fine-tuning its products. It is possible that a new firmware is available for your device. During a firmware update the device continues working as normal.
Note: Make sure all active connections to the EnergySwitch - such as the website, telnet and
SNMP - are closed before updating. Open connections might result in a failed update!
Obtaining Files
If you are unsure whether a firmware update is available for your device, have a look at http://www.racktivity.com/support or contact Racktivity Support (see Support chapter). If applicable the necessary files and instructions will be provided.
© 2011 Racktivity NV 49/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Troubleshooting
Downloading the diagnostics
As of firmware version 1.3 it is possible to download a diagnostics file (diag.txt) directly from the device containing a lot of vital system information. To download the file:
Login to the Web Interface Change the URL in the address bar to the following and press Enter:
https://[DEVICE_IP]/diag.txt
Resetting Login Credentials
In case of lost login credentials, resetting them can be done on the device itself:
Press and hold the UP and DOWN buttons simultaneously for 3 seconds until a
notification is shown on the display. The credentials will now be reset to their default settings:
Credential
User name
admin
Password
1234
Connecting to the Web Interface
If you are unable to connect to the Web Interface please try one or more of the following options:
Ping the device on its IP address. When unsuccessful, the EnergySwitch is most likely not
on the same network as your PC, or communication is blocked by a network device.
Connect the EnergySwitch directly to your computer (please note that for this both
devices need to have a valid fixed IP).
Try opening the Web Interface with another browser. Connect to the EnergySwitch using a different computer. If possible, power cycle the EnergySwitch.
Knowing your EnergySwitch’ IP Address
If you want to easily find out the IP address of your EnergySwitch, use the navigational buttons next to the TFT on the front.
If the TFT is black, press any button once to activate it.
© 2011 Racktivity NV 50/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Press MENU to enter the Menu. Select Network or Network Settings (v1.2) and press OK. Press the DOWN button and select Current IP address or IP Address (v1.2). The IP of your EnergySwitch is displayed in yellow at the bottom of the TFT.
© 2011 Racktivity NV 51/52 Antwerpsesteenweg 19 - 9080 Lochristi - Belgium - www.racktivity.com v 2014.3.27
Support
Feel free to contact us if you need any support or have any other questions or remarks:
Online
www.racktivity.com/support
E-mail
support@racktivity.com
Phone
003293242095 (GMT+1)
Loading...