Thank you for purchasing a MINUTEMAN power protection product. It has been
designed and manufactured to provide many years of trouble free service.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
Please read this manual before installing your Enterprise 1U Rackmount Series UPS, models E700RM1U, E1000RM1U, E1500RM1U, as it provides important information that should be followed during installation and maintenance
of the UPS and batteries allowing you to correctly set up your system for the
maximum safety and performance. Included is information on customer support and factory service if it is required. If you experience a problem with the
UPS please refer to the Troubleshooting guide in this manual to correct the
problem or collect enough information so that the MINUTEMAN T echnical Support Department can rapidly assist you.
This symbol indicates "ATTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Alternating Current Supply Phase"
This symbol indicates "Alternating Current Supply"
2
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
CAUTION! Connect the UPS to a two pole, three wire grounding
AC wall outlet. The receptacle must be connected to the appropriate
branch protection (circuit breaker or fuse). Connection to any other
type of receptacle may result in a shock hazard and violate local
electrical codes. Do not use extension cords, adapter plugs, or surge
strips.
CAUTION! T o reduce the risk of electrical shock with the installa-
tion of this UPS equipment and the connected equipment, the user
must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect
the UPS from the AC wall outlet before inst alling a computer interface
cable. Reconnect the power cord only after all signaling connections
are made.
English
WARNING:This Uninterruptible Power Supply contains potentially
hazardous voltages. Do not attempt to disassemble the UPS beyond
the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed
by QUALIFIED SERVICE PERSONNEL ONL Y.
WARNING: Risk of Electrical Shock. Hazardous live p arts inside
these power supplies are energized from the battery even when the
AC input is disconnected.
CAUTION! T o de-energize the outputs of the UPS:
1. If the UPS is on press and release the On/Off/Test button.
2. Disconnect the UPS from the AC wall outlet.
3. T o de-energize the UPS completely, disconnect the battery.
3
NOTICE: This equipment has been tested and found to comply with
the limits for a Class A computing device in accordance with the speci-
English
radio noise emissions from digital apparatus set out in the Radio Interference of
the Canadian Department of Communications. These limits are designed to
provide reasonable protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed
and used properly , that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception.
If this equipment does cause interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
Re-orient the receiving antenna.
Relocate the computer with respect to the receiver.
Move the computer away from the receiver.
Plug the computer into a different outlet so that the computer and receiver
Shielded communications interface cables must be used with this product.
fications in Subpart J of Part 15 of FCC Rules and the Class A limit s for
are on different branch circuits.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's
authority to operate the equipment.
Receiving Inspection
After removing your MINUTEMAN UPS from its carton, it should be inspected
for damage that may have occurred in shipping. Immediately notify the carrier
and place of purchase if any damage is found. Warranty claims for damage
caused by the carrier will not be honored. The packing materials that your UPS
was shipped in are carefully designed to minimize any shipping damage. In the
unlikely case that the UPS needs to be returned to MINUTEMAN, please use
the original packing material. Since MINUTEMAN is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SA VE THE PACKING MA TERIALS!
NOTE: These UPSs are shipped with the batteries disconnected. The batteries must be connected before putting these UPSs into service. Refer to Section 3 "Installation" for connecting the batteries.
4
Para Systems Life Support Policy
As a general policy , Para Systems Inc. (Para Systems) does not recommend
the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause
failure of the life support device or to significantly affect its safety or effectiveness. Para Systems does not recommend the use of any of its products in
direct patient care. Para Systems will not knowingly sell its products for use in
such applications unless it receives in writing assurances satisfactory to Para
Systems that (a) the risks of injury or damage have been minimized, (b) the
customer assumes all such risks, and (c) the liability of Para Systems Inc. is
adequately protected under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis
systems, neonatal ventilator incubators, ventilators for both adults and infants,
anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options
on many PARA SYSTEMS UPS systems. PARA SYSTEMS does not claim
that units with this modification are certified or listed as Hospital Grade by
PARA SYSTEMS or any other organization. Therefore, these units do not
meet the requirements for use in direct patient care.
English
5
English
CONTROL PANEL
The AC normal (green) LED illuminates in a steady st ate when the
UPS is on and operating in the AC normal mode. The AC normal
LED will extinguish when operating in the Battery mode.
The On-Battery (green) LED illuminates in a steady state when the
UPS is operating in the Battery mode. The On-Battery LED will
extinguish when operating in the AC normal, Boost and Buck modes.
The Boost (yellow) LED illuminates in a blinking state when the
UPS is operating in the Boost mode. The Boost LED will extinguish
when operating in the AC normal, Buck and Battery modes.
The Buck (yellow) LED illuminates in a blinking state when the UPS
is operating in the Buck mode. The Buck LED will extinguish when
operating in the AC normal, Boost and Battery modes.
The Fault (red) LED illuminates in a steady state when the UPS
detects an internal fault. The Fault LED is extinguished when the
UPS is operating properly .
The Weak/Bad Battery (red) LED illuminates in a steady state when
the UPS detects a weak battery, bad battery or if the battery is
disconnected. The Weak/Bad Battery LED is extinguished when
the battery's condition is good.
The Site Wiring Fault (red) LED illuminates in a steady state when
the UPS detects a site wiring problem. The Site Wiring Fault LED is
extinguished when the UPS is connected to proper site wiring.
6
The Load Level Bar Graph operates as follows:
LED #10: >10% load (green/red/yellow) LED will be green and illuminated when there is at least 10% of the rated capacity .
LED #30: >30% load (green/yellow) LED will be green and illuminated when there is at least 30% of the rated capacity .
LED #50: >50% load (green/yellow) LED will be green and illuminated when there is at least 50% of the rated capacity .
LED #70: >70% load (green/yellow) LED will be green and illuminated when there is at least 70% of the rated capacity .
LED #90: >90% to approximately 109% load (red/yellow) LED will
be yellow and illuminated when there is approximately 90% of the
rated capacity to indicate that unit is near full capacity. The LED
will turn red at 110% load capacity to indicate an Overload condition.
The Battery Capacity Bar Graph operates as follows:
LED #90: >90% battery capacity (red/yellow) LED will be yellow
and illuminated until the battery’s capacity drops below 80% capacity and then it will extinguish.
LED #70: >70% battery capacity (green/yellow) LED will be yellow
and illuminated until the battery’s capacity drops below 60% capacity and then it will extinguish.
LED #50: >50% battery capacity (green/yellow) LED will be yellow
and illuminated until the battery’s capacity drops below 40% capacity and then it will extinguish.
LED #30: >30% battery capacity (green/red/yellow) LED will be yellow and illuminated until the battery’s capacity drops below 30%
capacity and then it will turn red. When the battery capacity drops
below 20% capacity the LED will extinguish.
LED #10: >30% battery capacity (green/red/yellow) LED will be yellow and illuminated until the unit issues a Low Battery Warning
Alarm and then it will turn red to indicate a Low Battery Warning.
English
The Multi-Function On/Off/T est Button functions as follows:
When the UPS is Off, press and release the On/Off/Test button
after one beep to turn the UPS On.
When the UPS is On, press and release the On/Off/Test Button
after one beep to turn the UPS Off.
When the UPS is On, press and hold the On/Off/T est button for four
beeps, then release the button. The UPS will perform a 5-second
Self T est.
7
REAR PANEL
English
1. The input power cord has a NEMA 5-15P Plug.
2. The input circuit breaker will trip in the event the load exceeds the UPS’s
power rating.
3. The Battery Backup output power receptacles are NEMA 5-15R type. The
output receptacles are electrically wired into two segments to support the
"Load Shedding Function". The three receptacles on the left are Segment 1
and the three receptacles on the right are Segment 2.
4. The RS232 Communications Interface Port is for UPS monitoring and con trol.
5. The R-J1 1/R-J45 modular connectors are used for 10/100 Base-T Network/
single line Phone/Fax/Modem protection.
6. The USB Communications Interface Port is for UPS monitoring and control.
7. The Dipswitches are for setting the Inverter (On-Battery) output voltage.
8. The option slot will support MINUTEMAN option cards only .
INSTALLATION PLACEMENT
The Enterprise 1U Rackmount Series is intended to be install in a temperature
controlled environment that is free of conductive contaminants. Select a location which will provide good air circulation for the UPS at all times. A void locations near heating devices, water or excessive humidity , or where the UPS is
exposed to direct sunlight. Route power cords so they cannot be walked on or
damaged.
Operating T emperature (Maximum): 0 to 40 degrees C (+32 to 104 degrees F)
Operating Elevation: 0 to 3,000m (0 to 10,000 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage T emperature: -15 to +45 degrees C (+5 to +1 13 degrees F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
8
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.