RAB Lighting WP1FC FULL CUT-OFF Installation Instructions Manual

Page 1
WP1FC FULL CUT-OFF INSTALLATION INSTRUCTIONS
Thank you for buying RAB Lighting xtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments. Call the Marketing Department at 888-RAB-1000, or email: marketing@rabweb.com
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
RAB xtures must be wired in accordance with the National Electrical Code and applicable local codes. Proper grounding is required for safety. Wallpacks are for outdoor use and should not be used in areas with limited ventilation or high-ambient temperatures. Installation should be done by a qualied electrician.
MOUNTING
Use the Drilling Template on the inside back surface of the housing to match most standard junction boxes or for more secure installation, lag bolt housing to
mounting surface using locations shown below.
1. Swing open door by loosening two screws. Remove reector and lift door off hinges.
2. Prepare the housing for use by knocking out the ap­propriate holes.
3. Line up the housing in desired location and mount securely.
4. Complete the wiring to the supply wires and ground (see wiring instructions).
5. Replace the reector, install the lamp slide door onto hinges. Swing door close and tighten two screws.
6. To insure weatherproof seal make sure all holes (mounting, plugs, conduit, etc.) are sealed with weatherproof silicone sealant.
Drilling Template
LOCATION
Mount xture on a wall with lens facing down as shown above. Fixture must be level. Lamp must be in a horizon­tal position. DO NOT mount in a way that would entrap heat.
WIRING
HID ONLY CAUTION: 125°C supply wire required - Not for use in dwellings. To use 90°C supply wire, use
additionally supplied 12” leads and make supply connections inside the junction box.
All QT units are factory wired for 120V except those factory ordered with a 277V Photocell (/PC2). If other voltages are required, remove reector and rewire for the appropriate voltage. Do not use any supply voltage other than those specied below.
WP1FCSN35-150 HPS 120V only WP1FCSH50-150QT HPS 120,208,240,277V
WP1FCH50-100QT, 125PSQ MH 120,208,240,277V WP1FC26,32,42 CFL 120V thru 277V* *No internal wiring changes needed for various voltages as the ballast is quad tap electronic.
1. Connect the appropriate voltage xture lead to the HOT supply lead.
2. Connect the “COM” xture lead to the COMMON supply
lead.
3. Fixture ground screw must be connected to supply
ground.
4. All unused leads must be capped and insulated.
Lag Bolt Locations
Page 2
WP1FC FULL CUT-OFF INSTALLTION INSTRUCTIONS
PHOTOCELL INSTALLATION
A PHOTOCELL MAY BE INSTALLED IN THE FIELD.
1. Remove door and reector
2. Remove close up plug on top of xture
3. Install photocell and wire as per diagram
4. Use photocell rated for your supply voltage
“COM”
PHOTOCELL
FIXTURE
WP2FC
CLEANING
Caution: Be sure xture temperature is cool enough to touch. Be sure power is off.
Clean reector and refractor with a cloth moistened with non abrasive glass cleaning solution.
TROUBLESHOOTING
1. Is the proper lamp is installed? Check the wattage and ANSI code on the xture label against markings on the lamp. Refer to Replacement Lamp Table above for verication.
2. Make sure the lamp is not defective. Try a lamp known to be in operating condition.
3. Check that the line voltage at xture is correct. Refer to wiring directions.
RE-LAMPING
CAUTION: Prior to installing, check that the lamp is of proper type and wattage. Observe lamp manufacturer’s recommen­dations on lamp operation, burning position and ballast type.
1. Disconnect power
2. Make sure xture and lamp are cool enough to touch.
3. Loosen two screws holding lens and door.
4. Open door.
5. Replace lamp.
6. Close lens and tighten screws.
REPLACEMENT LAMPS AND BALLASTS
RAB Lamp ANSI RAB Ballast
Wattage Catalog# Code Catalog#
High Pressure Sodium
35 LHPS35 S55 BHPSN35 50 LHPS50 S68 BHPSN50 50 LHPS50 S68 BHPSH50QT 70 LHPS70 S62 BHPSN70 70 LHPS70 S62 BHPSH70QT 100 LHPS100 S54 BHPSN100 100 LHPS100 S54 BHPSH100QT 150 LHPS150 S55 BHPSN150 150 LHPS150 S55 BHPSH150QT
Metal Halide
50PS LMH50 M110 BMHH50QT 70PS LMH70 M98 BMHH70QT 100PS LMH100 M90 BMHH100QT 125PS LMH125PS M150 BMHH125PSQ
Compact Fluorescent Base
26 LCFL26 GX24q-3 BCFL42 32 LCFL32 GX24q-3 BCFL42 42 LCFL42 GX24q-4 BCFL42
4. Is there voltage at the lamp socket? If there is no voltage, check all connections.
5. Is the xture grounded properly?
6. Is the photocell functioning properly (if used)?
WP1FC-IN-0911
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.