Quietside QSVMI-09A, QSVMI-12A, QSVMI-18A Service Manual

Page 1
1
Summary and features
Summary and features
Model
Service Manual
QSVMI-09A QSVMI-12A QSVMI-18A

Page 2
Page 3
QSVMI-09A
QSVMI-12A
QSVMI-18A
Fan Motor Speed (r/min) (SH/H/M/L)
1150/1050/900/750 1150/1050/900/750 1250/1050/950/800
Output of Fan Motor (w) 20 20 20
Input Power of Heater (w) / / /
Fan Motor Capacitor (uF) 1 1 1
Fan Motor RLA(A) 0.26 0.26 0.26
Fan Type-Piece Cross flow fan – 1 Cross flow fan – 1 Cross flow fan – 1
Diameter-Length (
inch) Φ3.82×22.95 Φ3.82×22.95 Φ3.62×24.25
Evaporator Aluminum fin-copper tube Aluminum fin-copper tube Aluminum fin-copper tube
Pipe Diameter (
inch) Φ0.28 Φ0.28 Φ0.28
Row-Fin Gap(
inch) 2-0.06 2-0.06 2.5 -0.06
Coil length (l) x height (H) x coil width (L)
(inch)
22.83X8.98X1 22.83X8.98X1 26.81X12.76X1.5
Swing Motor Model MP28VB MP28VB MP28EC
Output of Swing Motor (W) 2 2 2
Fus e (A)
PCB 3.15A
Transformer 0.2A
PCB 3.15A
Transformer 0.2A
PCB 3.15A
Transformer 0.2A Sound Pressure Level dB (A) (H/M/L)
37/34/31/28 38/34/31/28 40/34/32/30
Sound Power Level dB (A) (H/M/L)
47/44/41/38 48/44/41/38 50/44/42/40
Dimension (W/H/D) (
inch) 30.32X9.84X7.48 30.32X9.84X7.48 32.68X11.22X7.87
Dimension of Package (L/W/H)( inch)
33.66X12.99X10.70 33.66X12.99X10.70 35.67X15.16X10.43
Net Weight /Gross Weight
(lb) 18.74/27.56 18.74/27.56 24.25/30.86
Technical specifications
Technical specifications
2
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Page 4
Front panel
Air inlet
Displayer
Air guide board
Air out
Remote control
Heating
Cooling
Setting temp.
Auto
Power/Run
Fan Dehumidify
Remote control receiving window
Water drainage pipe
Connection pipe and connection wire
Wrapping tape
Amplified sketch for displayer
Part name
Part name3
Page 5
Air inlet grid
Mark for left outlet pipe hole
Top view diagram
Mark for right outlet pipe hole
Back view
Ceiling
4
Outline and installation dimension
Outline and installation dimension
QSVMI-09A QSVMI-12A
9.84 inch
30.32 inch
7.48 inch
7.87 inch
2.76 inch
7.87 inch
Page 6
Air inlet grid
Mark for left outlet pipe hole Top view diagram Mark for right outlet pipe hole
Back view
Ceiling
QSVMI-18A
11.22 inch
32.68 inch
7.87 inch
7.87 inch
2.76 inch
7.87 inch
Page 7
Electrical circuit diagram
Electrical circuit diagram
55
55
5
These circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
QSVMI-09A QSVMI-12A
QSVMI-18A
Page 8
66
66
6
 
Controller Function Manual and Operating Method
Controller Function
The unit for temperature is centigrade in this function manual. If there's Fahrenheit, the transition relation is TFahrenheit =TCentigrade 1.8+32.
Temperature Parameter
Indoor ambient temperature (T
amb.
)
Indoor copper tube temperature (T
tube
)
Evaporator inlet pipe temperature (T
inlet pipe
)
Evaporator outlet pipe temperature (T
outlet pipe
)
System Basic Function
2.1 Cooling Mode
(1) Fan motor and swing works under setting status (2) Indoor unit will run under the original status when outdoor unit malfunction or stop to run protection, malfunction displays. (3) The fan motor stops when the modes conflicts. The temperature setting range is 60.8-86
under the mode.
2.2 Dry Mode
(1) Fan motor runs under low speed, swing runs by setting status. (2) Indoor unit will run under the original status when outdoor unit malfunction or stop to run protection, malfunction displays. The temperature setting range is 60.8-86 under the mode.
2.3 Fan Mode
In this mode, only indoor fan is running at setting status. Under auto fan speed, it will run by cooling auto fan.
2.4 Heating Mode
(1) The indoor unit goes to anti-cool wind when the unit is ON; it goes to blow residual heat when the unit is OFF and indoor fan motor was ON before. (2) Protection function, compressor is OFF as malfunction (including any temperature sensor malfunction), indoor fan motor runs with blowing residual heat. (3) Anti-cool wind: indoor fan motor runs after 2 minutes delayed. Blow residual heat: the indoor unit runs 60S with the original fan speed then stop; the fan speed cannot shift and the guide board changes to the heating minimum angle when blowing residual heat. (4) Indoor fan motor stops and does not blow residual under defrost and oil return; the temperature sensor of indoor unit cannot be inspected during defrost, oil return and exit in 3min process. The temperature setting range is 60.8-86 under the mode.
2.5 Auto Mode
In this mode, the unit will select the cooling, heating running mode or fan mode automatically according to the change of ambient temperature. Protection function is the same as that in heating, cooling mode.
2.6 Mode Clash
When the indoor receiving the information mode clash from outdoor unit and the digit is 1, the indoor load (indoor fan motor, swing) stops, the malfunction indicator displays, the mode send to outdoor unit is the mode receiving by remote control. When the time of TIMER ON reach, if the indoor receiving the information mode clash from outdoor unit and the digit is 1, the indoor load (indoor fan motor, swing) stops, the malfunction indicator displays, the mode send to outdoor unit is the mode receiving by remote control.
3. Others
3.1 Buzzer
When the controller energized, receiving signal from remote controller and auto button, the buzzer will give out beep.
3.2 Auto Button
Press the button when turn off the unit, the unit runs by auto mode, indoor fan motor runs under auto fan speed, turn on swing. Press auto button under the unit is ON, it will OFF.
3.3 Auto Fan Speed Control
Under cooling, heating, fan mode, the indoor fan motor will select the high, med, low fan speed automatically according to the change of ambient temperature, the auto fan speed is low speed under FAN mode. The spacing of shift each fan speed is 3.5 min.
3.4 Sleep
O
F
O
F
O
F
Page 9
In cooling and fan mode, after setting sleep procedure 1h, Tpreset will increase 33.8 ; 2h later, Tpreset will increase 35.6
, then remain the temperature, Tpreset will not exceed 86 ; under heating, after setting sleep procedure 1h, Tpreset will decrease 33.8 ; 2h later, Tpreset will decrease 35.6 , then remain the temperature, Tpreset will not exceed 60.8 ; the setting temperature will not change under fan and auto mode.
3.5 TIMER Function
General timer:
a. TIMER ON: The timer on can be set when the unit is OFF, the controller will run under original setting mode
when the time of timer on reaches, the timer space is 0.5h, and setting range is 0.5-24h.
b. TIMER OFF: The timer off can be set when the unit is ON, the unit is OFF when the timer time reaches, the
timer space is 0.5h, and setting range is 0.5-24h.
Clock timer:
a. TIMER ON: If set timer on when the unit is running, it will goes to run; if set the timer on when the unit is off,
the unit will run with the pre-setting mode when the time of setting timer on reaches.
b. TIMER OFF: If set timer off when the unit is off, when setting timer off, the unit will maintain stand-by status; if
set timer off when the unit is on, when the time of setting timer off reaches, the system will stop to run.
c. TIMER changing: When the unit under timer status, it can set ON and OFF by remote control, and reset timer
time, the unit will run under the last setting status. Set timer on and timer off together when the unit is running, the unit will maintain the current status, once the time of setting timer off reaches, the unit will stop to work. Set timer on and timer off together when the unit is off, the unit will maintain off status until the time of timer on reaches, the unit will start to work, hereafter the time of timer on reaches everyday, the unit will run under the original setting mode, and the unit stop to work when the time of timer off reaches. When the time of setting timer on and setting timer off is the same, the unit is off.
3.6 Memory Function
Memory contents: mode, swing (up and down), light, set Temp., set fan speed, general timer (clock timer doesn’t memory) The unit will on automatically with memory content after re-energized. There is no setting timer function in the last remote control order, and the system memory the last remote control order and working under that setting method. There is general timer function in the last remote control order, the system is energized before the timer time haven’t reach, the unit will memory timer function of the last remote control order after re-energized, and the timer time will star to calculate after re-energized. There is timer function in the last remote control order, but the timer time reaches, the system will de-energize after timer on and timer off, after re-energized, the system will memory the running status which before power-off, and no timer action; the clock timer doesn’t memory.
3.7 I FEEL Function
If controller receives I FEEL command, it will run at the ambient temp sent by remote controller (but it will also run at sampling temp. of AC temp sensor itself except defrost and anti-cool air). The remote controller will send ambient temp to controller every 10min, so if the controller hasn’t received ambient temp from remote controller after 11min, it will run at temp. of AC itself. If this function is not set, all ambient temp will adopt sampling value of AC temp. sensor itself.
3.8 Turbo Function
The TURBO function can be set only under COOLING and HEATING mode, when controller receiving turbo order, the indoor fan motor will run with high speed, and send turbo signal and high speed to outdoor unit.
3.9 Swing (up and down) Control
After energization, up & down swing motor will totate guide louver to position 0 to close air outlet. After turn on the unit, if swing function has not been set, up & down guide louver will clockwise turn to position D under heating mode, or clockwise
tur
n to level position L1 under other modes. If the unit is turn on with swing function setting, guide louver will swing between L and D. There are 7 kinds of swing states of guide louver. Position L,A,B,C,D, swing between L and D, stop between L and D (included angle L and D is equiangular). Upon stop of unit, guide louver will close to position 0. Swing action is valid only when swing command is set and indoor fan is running.
°
°
Heating Angle
Cooling Angle
3.10 Cold Plasm Function
Remote control the cold plasm function to ON and turn on the cold plasm when the fan motor is ON; remote control the cold plasm to OFF or turn off the cold plasm when the dan motor is OFF.
O
F
O
F
O
F
O
F
O
F
O
F
Page 10
4. Display
4.1 Basic Display
(1) When the unit is energized, the display symbol display, then only power lamp is light. (2) When use remote control to turn on the unit, the running LED is light, and the current setting running mode lamp displayed at the same time. COOLING: running lamp and cooling lamp are light; HEATING: running lamp and heating lamp are light; DRY: running lamp and dry lamp are light; FAN: running lamp and fan lamp are light; AUTO: auto lamp, running lamp and actual running mode lamp are light. (3) If turn off the LIGHT button, all the display is off (it is valid when the unit is OFF). (4) After set SLEEP function, the display maintains the original display status, it means the light switch does not influence sleep function.
4.2 Dual-8 Display
If the digital pipe display current setting temperature, the setting temperature range is 60.8-86 . It will display 77 for cooling and fan under auto mode, and display 68 for heating, and the cooling controller displays 77 . The temperature range is 32-140 when the indoor temperature displays.
4.3 Fan Speed Display
There are 3 status dynamic circle display for fan symbol, they are middle two segments, middle four segments and display six segments, and the middle two segments is displaying. The fan speed symbol blinks the fastest when remote control super-fan; the fan speed symbol blinks the lowest when remote control low-fan; the blink speed of display symbol is between high fan and low fan when remote control med fan; the blink speed of display depends on the indoor actual running speed when remote control auto fan speed; if the indoor fan motor stops, it blink display at the lowest speed.
4.4 Indoor unit Malfunction Lamp Display
Mal Malfunction Name Dual-8
Display
Running
Lamp
Heating
Lamp
Cooling
Lamp The system is abnormal (anti-high temp. power off, cooling overload)
H4 Blink 4 times
Compressor overload protection H3 Blink 3 times Module protection H5 Blink 5 times High-pressure protection E1 Blink once Anti-freeze protection power-off E2 Blink Twice Discharge temperature protection E4 Blink 4 times Low voltage over-current protection E5 Blink 5 times Mode Clash E7 Blink 7 times Communication malfunction E6 Blink 6 times Defrost or heating oil return H1 Blink once The indoor ambient temperature sensor is open, short circuit
F1 Blink once
Any indoor evaporator temperature sensor is open, short circuit
F2 Blink twice
The outdoor ambient temperature sensor is open, short circuit
F3 Blink 3 times
The outdoor condenser temperature sensor is open, short circuit
F4 Blink 4 times
The outdoor discharge temperature sensor is open, short circuit
F5 Blink 5 times
Fail to start up H7 Blink 7 times PFC malfunction HC Blink 6 times Compressor demagnetizing protection HE Blink 14 times The malfunction below need used by remote controller, it will display when press sleep button 6 times continuously in 3S, and exit inspect state(it is not valid under auto mode) automatically in 5min, or will exit when press sleep button 6 times continuously in 3S. Cooling overload down frequency F6 Blink 6 times Unit overflow down frequency F8 Blink 8 times Compressor discharge down frequency F9 Blink 9 times Unit AC voltage decreasing down frequency E0 Blink 10 times Heating anti-high temperature down frequency H0 Blink 10 times Anti-cool air protection E9 Blink 9 times Cooling oil return F7 Blink 7 times
Note: The malfunction code will circular display when different malfunctions exist together. The indicator will light 0.5S and display 0.5S when it blinks. The indoor temperature sensor malfunction will not inspected under defr ost, oil return.
O
F
O
F
O
F
O
F
O
F
Page 11
Disassemble Front Panel
Lift the front panel upward. Firstly, screw off a screw
fixing the upper protection plate at the receiving window and remove the protection plate. Then, pull
away the connection terminal. Pull the panel outward with force along the groove fixing the panel of the panel body to remove the panel
Disassemble Cope of Electric Box
Firstly, screw off the screw fixing the cope of electric box,
open the cope of electric box, loose the clasp and remove
the cope of electric box.
Disassemble Filter
Push the filter inward, and then pull it upward to
remove it.
Protection plate
Panel
the cope of electric box.
clasp
Filter
Screws
Dissassembly Procedures
Dissassembly Procedures
77
77
7
Operating Procedures / Photos
Page 12
Disassemble Lower Guide Louver
Manually bend the lower guide louver to loose the
clasp at the guide louver. Remove the lower guide louver.(Note:to remove the upper guide louver,you
must open the front case first, then screw off the screws fixing the upper guide louver and the water tray , bend
the upper guide louver and remove the upper guide louver)
Guide Louver
clasp
Disassemble Front Case
Unscrew the three screw covers at the front case,
unscrew the three screws, pull open the clasp at the
front case, and remove the front case.
clasp
sensor
screw covers
screws
Disassemble Water Tray
Screw off the fixing screws fixing the water tray with a
screw driver. Loose the clasp at the other end and pull
out the terminal board of the step motor. Pull upward
the water tray and take it out. Remove the water tray.
Water Tray
Operating Procedures / Photos
Page 13
Operating Procedures / Photos
Loosen the three clasps, and pull upward to
remove the cover of the electric box.
Disassemble Cover of Electric Box
cover of the electric box
clasp
Disassemble Electric Box
Remove the grounding wire of the evaporator.
Take out the pipe temp. sensor.
Unplug the plugging connector of the indoor motor
at the electric box, use screwdriver to
unscrew the screw fixing the electric box,
loose the clasp and remove the electric box.
pipe temp. sensor
room sensor
grounding wire
plugging connector
clasp
screw
Disassemble Evaporator
rear pipe clamp
screw
Screw off one screw which fix the connection
board clamp.Take down the connection board
clamp.
Screw off 4 screws fixing the left and right side of
the evaporator, then elevate left side the evapora-
tor to remove it backward.
CAUTION:
When repair, Carefully take out the evaporator and
pay attention to protect the connecting pipe.
Page 14
Operating Procedures / Photos
Evaporator
clasp
screw
screw
Evaporator
Disassemble Motor
Use screwdriver to unscrew the two screws fixing
the motor clamp, and remove the motor clamp.
Unscrew the three holding screws at the shaft
sleeve, and remove the motor.
motor clamp
Screw
screw
Motor
Axial fan
Page 15
Disassemble Cross Flow Fan
After remove the motor, pull out it from the
left bearing holder.
Cross Flow Fan
Bearing Holder
Operating Procedures / Photos
Page 16
8
Explosive view and spare parts list
Explosive view and spare parts list
Exploded View of Component 1
Page 17
1 Wall-Mounting Frame 1 2Rear Case 1 3Evaporator Assy 1 4 Cros s Flow Fan 1 5 Ring of Bearing 1 6/ / 7 Drainage Pipe 1 8 Water Tray 1
9 Swing Louver 12 10 Swing Linkage 1 1 11 Swing Linkage 2 1 12 Front Cas e 1 13 Front Panel 1 14 Decorate piece 1 15 Remote control YT1F 1 16 Filter 2 17 Receiver Board D5K3 1 18 Screw Cover 3 19 Guide Louver 1 1 20 Guide Louver 2 1 21 Moto r MP 2 8VB 1 22 Motor Clamp 1 23 Motor FN14P-PG 1 24 Electric box cover 1 25 Covering plate 1 26 Terminal board T4B3A 1 27 Electric box 1 28 Main PCB MB803F2AJ 1 29 Room Sensor15K 1
1 1
1 31 Jumping Connector 1 32 Transformer 48X26P 1 33 Wire clamp 1 34 Rear clamp 1 35 Connecting Cable 1 36 swing louver clamp 1 37 swing louver 1 38 swing louver(up) 1 39 swing louver(down) 1
Qty
Part Code
30 Tube Sensor 20K
No Description
QSVMI-09A
01252220 222020016 010020534
10352001
76512203
/
0523001401
201820270
10512088
10582002
10582003 200022107
200022092C
68012019
30510049 111200511
30545041 242520062 105120332 105120342
15012086
26112014 150120763
20122082
20112058
42011233
20112057
30038004 390000451
3900019814 3900019815 3900019816 4202300102
43110293
10582408
10542004
10542005
71010103
24242001
/
10582409
Components and Parts List 1
The above data are subject to be changed without notice.
Page 18




























Exploded View of Component 2
Page 19
Part Code
QSVMI-12A
1 Wall-Mounting Frame 01252384 1 2 Rear Case 222020503 1 3 Evaporator Assy 01002250 1 4 Cross Flow Fan 10352005 1 5 Ring of Bearing 76712015 1 6\ \ \ 7 Drainage Pipe 0523001401 1 8 Water Tray 201820306 1
9 Swing Louver 105120413 12 10 Swing Linkage 105824397 1 11 Front Case `200022958 1 12 Screw Cover 242520072 3 13 Filter 11122440 2 14 Remote Control YT1F 30510049 1 15 Decorate Piece 68012019 1 16 Receiver Board 30545042 1 17 Front Panel 200022921 1 18 Guide Louver 261120432 1 19 Guide Louver 261120422 1 20 Motor MP28EC 15212002 1 21 \ \ \ 22 \ \ \ 23 Right Motor Clamp 26112429 1 24 Bearing Holder 26152423 1 25 Motor FN20M-PG 150120873 1 26 Electric Box Cover 20122081 1 27 Terminal Board T4B3A 42011233 1 28 Covering Plate 20112060 1 29 Electric Box 20112059 1 30 Main PCB M803F2AJ 30038004 1 31 Transformer 48X26P 43110293 1 32 Wire Clamp 71010003 1 33 Rear Clamp 26112430 1 34 Connecting Cable 400204056 1 35 \ \ \ 36 Room Sensor 15K 390000451 1
3900019814 1 3900019815 1 3900019816 1
37 Tube Sensor 20K
No Description Qty
Components and Parts List 2
The above data are subject to be changed without notice.
Page 20
Exploded View of Component 3
Page 21
Part Code
QSVMI-18A
1 Wall-Mounting Frame 01252004 1 2 Rear Case 22202329 1 3 Fan Bearing 76512203 1 4 Screw Cover 24252015 3 5 Swing Louverb 105120472 11 5 Swing Louver 10512430 1 6 Swing Link 1 10582057 1 7 Swing Link 2 10582058 1 8 Water Tray 20182057 1 9 Guide Louver(up
10512085 1
10 Guide Louver(down
10512086 1 11 Cross Flow Fan 10352022 1 12 Evaporator Assy 01002913 1 13 Drainage Pipe 05230014 1 14 Evaporator Support 24212067 1 15 Filter 11122048 2 16 Front Case 200026524 1 17 Front Panel 2000284402 1 18 Remote Controller YT1F 30510049 1 19 Displaying Light Board 22432071 1 20 Electric Box Cover 1 20112019 1 21 Wire Clamp 71010103 1 22 Terminal Board (3位) 4201026601 1 23 Electric Box Cover 20112020 1 24 Main PCB 30038022 1 25 Transformer 57X25F 43110257 1 26 Room Sensor 15k 390001912 1
3900019814 1 3900019815 1
3900019816 1 28 Sensor Insert 42020063 3 29 Electric Box 20112018 1 30 Lower Shield of Electric Box 01592037 1 31 Upper Shield of Electric Box 01592038 1 32 Stepping Motor MP35XX 15213001 1 33 Motor Clamp 26112095 1 34 Helicoid tongue 26252009 1 35 Motor FN20K-PG 15012718 1 36 Pipe Clamp 24242001 1 37 Connecting Cable / 1 38 Plank Cable 4003004201 1 39 Jumping Connector 4202300106 1
No Description Qty
27 Tube Sensor 20k
Components and Parts List 3
The above data are subject to be changed without notice.
Page 22
Page 23
Page 24
QUIETSIDE CORPORATION www.quietside.com
West Off ice 8750 Pioneer Blvd. Santa Fe Springs, CA 90670 USA Phone: 562-699-6066 Fax: 562-699-4351
East Office 6 Pine Hill Drive Carlisle, PA 17013 Phone: 886-243-6498/ 717-243-2535 Fax: 717-243-7917
TX Office 3001 Northern Cross Blvd. Suite 361 Fort Worth, TX 76137 Phone: 817-838-6066 Fax: 817-838-8670
66129908658
Loading...