Quietside QSCE-093, QSCC-093, QSCE-123, QSCC-123, QSCE-183 User/instalation Manual

...
This manual to is to aid the qualified HVAC contractor in the Installation and Maintenance of this Quietside R410a Ductless Mini Split Please read and understand these instructions prior to installing the unit, failure to comply with these instructions may result in improper installation, operation and maintenance, possibly resulting in fire, electrical shock, property damage, personal injury or death
Installers please retain this manual for future reference, please pass warranty registration to end user
www.quietside.com
or call 866 243 6498 to speak to a Technical Service Assistant When calling please have the Model numbers and Serial numbers available
Read all the Instructions, Install and apply the system per those instructions Use the unit only in the manner described in this manual
1 Check Rating Plate for correct system voltage before installing the unit
Installing and operating a unit with the incorrect voltage may result in malfunction or
other issues and will void the warranty
2 Units must be connected to a correctly grounded Electrical Supply
3 Do not use the units if they have been dropped or otherwise damage or installed
incorrectly
The manufacturer of the unit will not be liable for any damages caused by failure to comply with the installation and operating instructions in this manual The unit Rating Plate contains pertinent information to the unit operation, please refer to it as required
Completely read all Instructions prior to assembling installing, operating, or working on these units Inspect all parts for damage prior to installation and start up Units must be installed by a Qualified HVAC Contractor
This symbol is an indication of Important Safety Information
Safety Instructions
Installation and Maintenance Manual
Report all Shipping Damage to Carrier IMMEDIATELY, Check units and box exterior for damage
Note to Installer
Installer Supplied Items
Refrigerant Line Set : Flare Connection only, suitable for R410A with both lines insulated, max length 50ft Units manufactured prior to May 2007 do not include the female flare nuts for the refrigerant line sets Main System Breaker : Sized per unit requirements, to be mounted adjacent to Outdoor unit High Voltage Interconnect Wiring : 14 AWG wiring from Outdoor unit to Indoor unit for Power and Control Mounting Hardware : Wall Anchors, Condenser Pad etc Refrigerant : R410A required for additional line set charge Condensate Piping : Per local codes to remove condensate from the indoor unit
Items for Consideration
Application
Check the application of the unit prior to installation, certain applications require additional components or installation parameters
Computer or Data Server Rooms,
These require ballpark sizing of approximately 12,000 Btu/h Capacity per 250 SqFt of room size The units will be running 24/7, so a Low Ambient Head Pressure Controller (See accessories), a Crankcase
Heater and possibly a Wind Baffle (Field Supplied for cooling below 32 DegF) must be installed
Offices and Commercial Spaces, Churches etc
These require ballpark sizing of approximately 12,000 Btu/h Capacity per 400 SqFt of room size The units could have the possibility of providing cooling with ambient's below 65 DegF, so a Low Ambient Head Pressure Controller (See accessories) is required as is a Crankcase Heater (field supplied)
Residential, Bedrooms, Family Rooms etc
These require ballpark sizing of approximately 12,000 Btu/h Capacity per 600 SqFt of room size
Low Ambient is typically not needed, unless a home office application is required.
Heat Pumps are a great application, however the units do not feature any back up resistance heat, so we do not recommend their use as a primary source of heat in areas where the winter temperatures fall below 25 DegF.
Installation
Determine the best location for mounting the Indoor unit, it must be located a minimum of 4 ft from the floor Pay attention to the air circulation in the room, 9 & 12k units throw air 15ft, 18 & 24k units throw air 25ft, ensure no obstacles to airflow exist
Locate the Indoor and Outdoor units as close together as possible, maximum line set run and lift CANNOT
BE EXCEEDED, then determine how the Interconnect piping, wiring and condensate hose is to be run
Unit QSCE-09/12 QSCE-18/24 QSHE-09/12 QSHE-18/24
Ensure that all panels can be removed for service as required
Certification
All Quietside Ductless Mini Splits are certified by UL under UL standard 1995 in both Canada and the US Performance is certified by our certification under the ARI 210/240 Program
Installation and Maintenance Manual
3/8" & 5/8"
20 Feet
20 Feet
50 Feet
50 Feet
50 Feet
50 Feet
3/8" & 5/8"
20 Feet
20 Feet
1/4" & 1/2"
Max Line Set Run
Max Vertical Lift
Line Sizes
1/4" & 1/2"
Controls and Components
Units are supplied with a wireless remote controller, which communicates with the unit Microprocessor controller The return air temperature sensor mounted on the unit then controls the unit operation Heat Pump units require the defrost sensor connecting between the Outdoor & Indoor units prior to operation Several modes of operation are available to the end user depending on the type of comfort required All unit operating functions are controlled via the remote controller Unit operating modes are : Auto, Cool, Dry, Fan and Heat (Heat Pump only)
Optional Controls and Components
Low Ambient Controller : ICM 326H must be used in Data Room or Commercial applications
For a wiring diagram please contact Quietside or follow general diagram supplied with ICM Controller Probe must be located in the fin pack or on a return bend that measures approx 100 DegF during normal operation
Condensate Pump : Field Installed Mini Pump, Quietside recommend the Aspen brand of Condensate
Pump, follow their wiring diagram recommendations. This pump is installed externally to the unit
Follow Instructions, failure to follow instructions may cause possible malfunction and void any warranty
Step 1
Remove Indoor and Outdoor units from the carton/box
Indoor unit carton contains Remote Control, Batteries and 25ft Defrost Sensor interconnect wire (HP only)
Ensure these are kept in a safe place during the installation process.
Step 2
Locate area to Install Indoor unit
Indoor unit must be located a minimum of 4ft from the floor and 4" from the ceiling Choose an area where the wall is plumb and determine how to best to run the unit interconnects
4" from ceiling
8" from wall 8" from wall
Minimum 4ft from floor Optimum 6ft plus from floor
Ensure no obstacles to Airflow are directly in front of the unit, for a minimum of 12ft for 9/12,000 Btu/h units and 16ft for 18/24,000 Btu/h units Do not install the Indoor unit units in areas exposed to high humidity (RH of 80% plus), direct sunlight and direct heat from stoves or other devices
Installation and Maintenance Manual
Unit Installation
Indoor Unit
Step3
Drill Hole for Line Set etc
Remove mounting bracket from the rear of the Indoor unit, then use a Phillips head screwdriver to remove the unit pipe strap, and if unit is a heat pump the defrost sensor also must be taken from the retainer so that it can be connected to the Outdoor unit.
Using the wall templates provided position the unit on the wall Drill a ø 2 5/8" or 3" hole through the wall using templates provided Angle the wall penetration slightly down towards the outside to assist in draining the condensate from the unit
If mounting the unit on an inside wall, use the knockouts provided on the LHS and RHS of the unit to route the piping and wiring connections through
Step 4
Install Mounting Bracket
Locate and secure the mounting bracket to the wall, the Indoor unit weighs a maximum of 50lbs, use wall anchors and mount to a wall stud to ensure that the wall is capable of holding the weight of the unit Use a level to ensure mounting bracket is leveled, so condensate can drain properly
Step 5
Prepare Unit Line Set Connections
Rotate refrigerant line stubs set gently through 90° (if mounting on an outside wall), for other line set configurations align the stubs as required
Tip : Use Duct tape to tape the Condensate hose (make sure it is below the Line set stubs) and the Defrost Sensor (Heat Pump Only), this makes it easier to guide them though the hole drilled in the wall
Also if possible feed the 14 AWG Interconnect wiring between Indoor and Outdoor (Maximum # of wires required is 6) through the unit electrical connection (if required by local codes an liquid-tite electrical connector can be attached to the rear of the unit). Open front cover of unit and pull wire through wire chase. This step will allow installation of the unit without removing the front cover completely from the unit.
Note : Condensate hose is taped below line set stubs Wrap Duct tape to the end of the condensate hose for easier installation
Installation and Maintenance Manual
Unit Installation (Cont)
Step 6
Install unit on Mounting Bracket
Feed the line set stubs/condensate hose/wiring connections through the hole in the wall, then locate the unit key slots onto the tabs on the mounting bracket. Bottom of the unit then latches onto the mounting bracket. Indoor unit is now installed, it should be plumb, level and flush with the wall. If it is not check that the line set stubs are completely through the wall penetration, and the wall is plumb
Step 7
Locate Outdoor unit
Clearances for the Outdoor unit are :
6" Minimum Install the Outdoor
unit on a Condenser Service Pad or if a Heat Valves Pump use feet to
6" 12" raise unit up approx
Minimum Minimum 6" to allow for
defrost to drain away
24" Minimum
Do not install the Outdoor unit in a location exposed to high winds (field fabricated and installed wind baffle may be required). Ensure location does not impede access around unit and pose a disturbance to neighboring areas
Step 8
Refrigerant Line Set Piping
Interconnecting line set between the Outdoor unit and the Indoor unit, MUST have both refrigerant lines
insulated as condensing device is located in the Outdoor unit Gently bend the line set stubs from the Indoor unit to the desired position Using 2 x 10"/12" Crescent wrenches remove the flare nuts from the Indoor unit line stubs. Indoor unit has a holding charge of a dry gas, check for release of this to ensure that no leaks are present Use a small amount of vacuum pump oil on the male flare threads to ease installation. Connect the line set to the stubs. Using the 2 wrenches, 1 on the male & 1 on the female tighten the flare nuts
DO NOT INSTALL A LIQUID LINE SIGHT GLASS OR FILTER DRIER IN THE SYSTEM
Run the line set to the Outdoor unit, avoid tight bends and kinking the lines. Quietside does not recommend brazing line sets together or to the unit connections If line set length is in excess of that required, cut line set and re-flare or coil excess vertically to facilitate oil return to the compressor
Installing the Line Set on the Indoor unit stubs
Installation and Maintenance Manual
Unit Installation (Cont)
Outdoor Unit Rear
Front Condenser Fan
Line Set Connections under the GRAY caps
Step 11
Controls Wiring
Electrical Wiring should be done in accordance with all National Electrical Code (NEC) and local state/city building codes
ALL CONTROLS WIRING BETWEEN INDOOR AND OUTDOOR UNIT IS HIGH VOLTAGE
MINIMUM 14 AWG WIRE MUST BE USED
Remove terminal covers from Indoor unit and wire to the terminals, small electrical screwdriver required Control wiring from the Outdoor Unit must be a point to point i.e. the terminal that the wire is attached to on the Outdoor unit must be the same terminal it is wired to in on the Indoor unit
This is extremely important : Switching the L3 - L4 or N1 - L1 wires over will allow the Indoor unit to operate but it will not provide controls signals for the Outdoor unit so that the compressor will not operate Ground connection should be made to ground screw marked in Indoor unit
If unit is a Heat Pump, the Defrost Sensor must be connected from the Indoor unit to the Defrost Sensor
in the Outdoor unit. Standard lead length is 25ft, if a longer length is required then cut the lead and
extend it using 18 AWG thermostat wire. Sensor is resistance based using 3.5V DC
Defrost Sensor wire/connection in Outdoor unit is accessed
by removing top panel from unit, wire is coiled on base of
unit
Control Wiring at Outdoor unit (Heat Pump unit shown) Note use of colored wire (supplied with Line Set) and defrost sensor connected (Heat Pump only)
Ground wires connected to the terminal plate Indoor and Outdoor units must be grounded
Step 12
Condensate Hose
Unit is provided with approximately 18" of Condensate Hose
Hose connection is sized to accept a 3/4" OD or 5/8" ID Clear Plastic Hose to then extend to building drain All condensate hose extensions should be in accordance with local building codes Remember water only flows downhill to ensure positive draining from the unit
Check using water for a positive flow of Condensate
The basic system installation is now complete The unit is now ready for start up -
Use this time to ensure that worksite is tidy. Quietside recommend the use of Slimduct products to hide
the refrigerant line set interconnects - available from your Quietside distributor
Installation and Maintenance Manual
Unit Installation (Cont)
Loading...