Quietside DPW-099, DPW-120 User Manual

DPW-099 DPW-120
Bottom of DPW-099A and DPW-120A
DPW
Product Specifications
27
3.5"
10.5" WC
8"
0.5 to 0.7 GPM
DPW-099A DPW-120A
Heating System Data
Heat Input (Btu/h) 47,800 - 99,000 47,800 - 120,000 AFUE (%) 90 90 Htg Water Temp (DegF) Working Pressure (psi) Freeze Protection Device Heating Min Flow (GPM) Htg Heat Exch Water Volume (gal) 0.2 0.2 Ignition Type
Domestic Hot Water
DHW Production Energy Factor 0.83 0.85 Temperature Setting DHW Minimum Flow Rate (GPM) GPM at 50F in 100F Out 3.7 4.5 GPM at 50F in 110F Out 3.1 3.7 GPM at 50F in 120F Out 2.6 3.2 GPM at 50F in 130F Out 2.3 2.8
General Data
Control Voltage
24V DC - Requires X-X or Zero Voltage Contact for Zone applications Fuel Type Natural Gas Inlet Press ("WC) LP Gas Inlet Pressure ("WC) Gas line Size (inch) Unit Voltage (V) Power Consumption (W) 120 140 Pump Flow @ 10ft Head NOX Levels (ppm) 20 20
122 to 176 DegF leaving unit Heat Exchanger
15 - 20
Thermistor, will energize pump/combustion
1.2
Electronic Spark
Controlled : Settings of 98 - 114°F, 120°F, 130°F, 140°F
0.7 GPM
NG or Field Conversion to LP
Minimum 5.8" WC to Maximum 9.7" WC
Minimum 9" WC to Maximum 13" WC
Min Size 3/4"
115V-1Ph-60Hz
2.5 GPM
Venting
Max Flue Temp (DegF) Venting Material Max Vent Length (feet) Max number of Elbows*
Ø3" Schedule 40 PVC
45ft Equivalent each for both Intake and Exhaust
3 per Individual Vent pipe
136
*One Elbow = 5 ft equivalent length, which must be deducted from the total vent length
Dimensions
Weight (lbs) 70 70 Unit Height (less vent conns) (") 27 5/8" 27 5/8" Width (") 18 1/8" 18 1/8" Depth (") 8" 8" Gas Connection Size (") Heating Supply/Return (") DHW Inlet/Outlet (") Flue/Air Intake (")
Quietside maintains a policy of continuous product development and specifications can change
Vent Connection ø3.5" to accept 3" PVC
3/4" 3/4" 1/2"
Quietside West : 8750 Pioneer Blvd, Santa Fe Springs CA 90670 : Tel 562 699 6066, Fax 562 699 4351
Quietside East : 6 Pine Hill Drive, Carlisle PA 17013 : Tel 717 243 2535, Fax 717 243 7917
www. Quietside.com
28
Isometric View - DPW-099 & 120
User's Manual
29
Burner Assembly
User's Manua
l
30
Water Line
User's Manua
l


31
Parts List
User's Manual
1R 3DUW1R 3DUW1DPH
 6 3&%DVVHPEO\
 6 6SDUNSOXJ)ODPHURGVHQVLQJURG

 
 6 /DWHQWKHDWH[FKDQJHUDVVHPEO\
  6HQVLEOHKHDWH[FKDQJHUDVVHPEO\
 %XUQHUDVVHPEO\
6 *DV9DOYH$6$VVHPEO\
43
44
45
46
47
48
DPW
DPW Models
49
DPW-099A DPW-120A
50
D
PW Un
it
DPW-099A
51
DPW
52
DPW
53
54
DPW
55
56
57
DPW
58
DPW
DPW
DPW
DPW
59
60
(2) Factory Installed Brown Zone Control Wires Attached To Terminals 9 & 12
61
62
DPW Dip Switch Settings
63
Depending on the application of the DPW unit it may be necessary to alter the Dip Switch settings from the standard positions
The unit has 5 Dip Switches located on the Microprocessor
Dip Switch Standard Setting Controls 1 ON Fuel Gas Type 2 OFF Fuel Gas Type 3 OFF Unit Options 4 OFF Forced Maximum Firing rate 5 OFF Forced Minimum Firing rate
Setting for Natural Gas Operation
Dip Switch Setting for NG
1 ON 2 OFF
Setting for LP Gas Operation
Dip Switch Setting for LP
1 OFF 2 ON
Unit Options
Switch Dip Switch #3 to ON
On DSR-100F press the Timers and Anti Freeze buttons simultaneously for 5 seconds. This will allow unit to enter the programming mode
Temperature display can be changed between DegF and DegC by pressing the Timer button 3 times until Lc is displayed in the top RH corner of the unit display, and f is displayed in the center of the screen
Press the Up temperature arrow and the f will change to a c
Hit the Power On/Off button to exit and switch Dip Switch #3 to OFF, the unit will now display in DegC
Cont
Zone Control
This can be also be set up using this control (see zone control wiring section for more detail)
Maximum Firing Rate
Setting Dip Switch #4 to ON will lock the unit into the maximum firing rate at all times. This is occasionally used for troubleshooting and gas pressure set up purposes. Move the switch back to OFF to allow the unit to modulate capacity
Minimum Firing Rate
Setting Dip Switch #5 to ON will lock the unit into the minimum firing rate at all times. This is occasionally used for troubleshooting and gas pressure set up purposes. Move the switch back to OFF to allow the unit to modulate capacity.
64
Specific requirements for installation in Massachusetts
In the Commonwealth of Massachusetts these units must be installed by a licensed gas fitter or plumber
Venting :
For the Quietside models DPW-099A, DPW-120A where the bottom of the vent termination and combustion air intake is installed at a height BELOW 4 ft above the grade level the following requirements must be satisfied
1. If there is not one presently installed, on each floor level where there is a bedroom(s), a Carbon Monoxide detector and alarm shall be installed in the living area outside the bedroom(s). The Carbon Monoxide detector shall comply with NFPA 720 (2005 Edition)
2. A Carbon Monoxide detector shall be installed in the room where the ODW unit is installed, the detector shall be :
a) Powered from the same power circuit that provides power for the ODW
unit. A single electrical service switch shall be used to service both the unit and the detector
b) Have battery back up power c) Meet ANSI/UL std 2034 and comply with NFPA 720 (2005 Edition) d) Approved and listed by a NRTL recognized under 527 CMR
3. A Quietside approved vent termination must be used. Installation of the vent terminal must be in strict compliance with Quietside’s written instructions, and a copy of these instructions must remain with the unit after the installation is completed.
4. A metal or plastic identification plate shall be mounted on the exterior of the building, 4ft above the vent termination. The plate shall read “Gas Vent Directly Below” with text size visible from a minimum of 8ft.
65
Cont
For the Quietside models listed above where the bottom of the vent termination and combustion air intake is installed at a height of 4ft ABOVE the grade level the following requirements must be satisfied
1. If there is not one presently installed, on each floor level where there is a bedroom(s), a Carbon Monoxide detector and alarm shall be installed in the living area outside the bedroom(s). The Carbon Monoxide detector shall comply with NFPA 720 (2005 Edition)
2. A Carbon Monoxide detector shall be installed in the room where the ODW unit is installed, the detector shall be :
a) Powered from the same power circuit that provides power for the ODW
unit. A single electrical service switch shall be used to service both the unit and the detector
b) Have battery back up power c) Meet ANSI/UL std 2034 and comply with NFPA 720 (2005 Edition) d) Approved and listed by a NRTL recognized under 527 CMR
3. A Quietside approved vent termination must be used. Installation of the vent termination must be in strict compliance with Quietside’s written instructions, and a copy of these instructions must remain with the unit after the installation is completed.
Vent Termination requirements As the DPW unit is a condensing product
The Vent for all Quietside DPW units shall not terminate
Over Public Walkways; or
Near soffit vents or crawl space vents or other area where condensate or vapor could create a nuisance or hazard or cause property damage; or
Where condensate or vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment
66
Specific requirements for installation in Canada
The provinces of Ontario and Alberta have adopted standard ULC S636 requiring the following additional items to be noted.
1. Maximum flue temperature as tested is 136 DegF, allowing these units to be vented with Schedule 40 PVC under the regulation of ULC S636.
2. Under the new requirements of ULC S636 regarding vent connections to the unit, Quietside requires the Schedule 40 Vent piping to be secured to the unit using approved PVC cement, following the cement manufacturers instructions regarding methodology and curing time. A bead of high temperature silicone should be also run around the joint to ensure no leaks can occur.
Silicone seal
67
Combustion and Leak Testing of DPW units
As the front cover of the unit is mechanically attached and cannot be removed in operation without the use of a tool, it is not permissible to conduct combustion testing or leak testing of the unit with the front cover removed.
Combustion testing must be achieved by using a calibrated combustion tester, with the probe inserted either in the flue exhaust of the vent termination or it is permissible to take reading by accessing the flue pipe approximately 12” above the unit, providing adequate provisions are made for sealing any access after testing to ensure no leakage of flue gases into the occupied space.
Leak testing must take place with the end of the “sniffer probe” at least 1” from any surface of the unit to ensure that false readings cannot be obtained.
Auto Fill – Closed Loop System
The DPW unit is fitted with a MANUAL Auto Fill valve, supplied in the closed position.
The Fill Valve is not pressure regulated therefore care must be used when opening the valve to prevent overfilling of the closed loop system and opening of the pressure relief valve.
Quietside recommends that the valve be left in the closed position and an external Boiler Feed Valve e.g. Taco 335/329 be installed in the piping system to maintain an even pressure in the closed loop system
Manual Auto Fill Valve located on base of cabinet
68
Zone control of DPW unit
Zone control of the DPW unit is performed by a zero voltage or X-X contact from a relay or zone control panel closing when unit operation is required.
You will find two brown wires attached to the upper Molex connector of the main PC board. These wires can be extended with 18 gauge thermostat wire and only connected to dry contacts from your zone control panel end switch. See example wire diagrams on the last four pages of this manual.
Brown Wires
69
Anti Freeze & Freeze Protection
For Anti Freeze protection in the Quietside units the following products are recommended “No Burst”
“Fernox Alphii”
The maximum concentration allowed is 30% by volume which will protect the unit down to approximately 5 DegF or -11 DegC
Water Quality
DPW models potable side must have the water quality within the following limits for long life and reliable operation. The water supply should be tested to make sure the quality is within specified limits. If there is a problem with the water quality, contact your local water conditioning company for equipment to condition the water supply to these appliances. Operating this water heater with water conditions outside the specified limits will void the warranty.
Description PH TDS
Maximum
Levels
6.5 to 8.5 Up to
(Total
Dissolved
Solids)
500 ppm
Total
Hardness
Up to
200 ppm
or 11.7
grains
hardness
Aluminum Chlorides Copper Iron Manganes
Up to
0.2 ppm
Up to
250 ppm
Up to
1.0ppm
Up to
0.3 ppm
e
Up to
0.05ppm
Zinc
Up to
5 ppm
70
Pump Curves & Primary – Secondary Piping
The DPW units include a pump assembly that is used to provide the flow through the unit heat exchangers, and has a nominal flow of heating water for external piping arrangements.
This pump is not designed to be the system pump providing flow to radiant loops or baseboard.
Therefore Quietside insists on using a Primary – Secondary pumping arrangement, the recommended method uses the traditional large diameter Primary loop
The main circulation pump or the zone pumps will then provide circulation into the zones or the heating system
The only exception to this Primary – Secondary rule is for Air Handling units with a hot water coil where the Air Handling unit is located less than 10ft from the DPW unit.
Unit Controls & Zoning
A DSR-100F Controller is provided with the unit.
This is not used as a thermostat, but is a unit controller and should be mounted adjacent to the DPW unit. It is connected to the DPW via the 2 Yellow wires and is powered by 20V DC.
The DSR controller allows both the heating loop and DHW water temperatures to be set
When the unit is started using the X – X or dry contacts on the microprocessor it will operate and provide heating loop water at the set temperature until the zone(s) are satisfied. If a DHW call is experienced during heating operation the unit will automatically switch over to provide DHW.
DO NOT APPLY 24V AC OR LINE VOLTAGE TO THE X – X CONTACTS UNIT MICROPROCESSOR WILL FAIL IF IT RECEIVES 24V AC OR LINE VOLTAGE ON THESE CONTACTS
It is not permissible to power the secondary loop pump from the Primary loop pump installed in the unit. Power for the Secondary loop pump should come from a switching relay e.g Taco SR501
71
Anti Scald Valve
Y
72
highest point Supply
zones
System Circulation Pump
Field Installed
8750 Pioneer Blvd, Santa Fe Springs CA 90670
additional expansion tank on closed loop system
DPW UNIT
closed loop system to be filled with DPW
valve on the unit can be used provide a drain
Closed
Loop
Supply
DHW
Hot Out
DHW
Cold In
Closed
Loop
Return
connections on DPW Air Vent at Hot Water
apart on tee centerline Return from Heating
Space max of 4 Pipe Dia's (No detail shown)
Use 1 1/4"
primary loop Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
pipe diameter
for heating
Title : DPW Recommended Piping Layout, Heating & DHW
Drg # : QUI-DPWP-001 Drawn : JLM 8/26/2008 Rev : 001
Cold Water Supply Notes :
from House to 1/2" When brazing always wrap valves, drains
male connection on etc with a wet rag to prevent damage
DPW
Use 1/2" Unions Check system design for requirement for
Shut Off Valves to isolate
both Inlet and Supply of Boiler drain installed on Primary Loop
DHW system from DPW should be below DPW Isolation valve to allow
"Boiler Drains" to allow isolated from the closed loop to protect unit
maintenance of the DHW A Drain can also be installed on return piping above
Shut Off Valves to isolate Supply to Heating
both Supply & Return 2 x 1 1/4" x 1 1/4" x 3/4" Tees zones
Plate Heat Exchanger shut off valve to drain the unit or Pressure Relief
Pressure Relief Valve
(Factory Supplied)
Pipe to building drain
(See local codes)
See local codes to 3/4" Male Supply and Return of 120DegF House
Backflow prevention 3/4" Unions to connect Set for Maximum
Boiler Feed Valve with MANDATOR
"Boiler Drain" - see notes (No detail shown)
Anti Scald Valve
Y
73
Coil Inlet
Air Handler to be located no
more than 10ft from the DPW
and no more than 5ft above
Air Handler should not have
it's own circulator installed
Disconnect pump if installed
8750 Pioneer Blvd, Santa Fe Springs CA 90670
should be below DPW Isolation valve to allow
DPW UNIT
A Drain can also be installed on return piping above
Closed
Loop
Supply
DHW
Hot Out
DHW
Cold In
Closed
Loop
Return
highest point Supply
connections on DPW Air Vent at Hot Water
HW Coil
Unit
AHU
Drg # : QUI-DPWP-002 Drawn : JLM 8/26/2008 Rev : 001
Title : DPW Recommended Piping Layout, AHU (No Pump) & DHW
Cold Water Supply Notes :
from House to 1/2" When brazing always wrap valves, drains
male connection on etc with a wet rag to prevent damage
DPW
Use 1/2" Unions Boiler drain installed on piping
Shut Off Valves to isolate closed loop system to be filled with DPW
both Inlet and Supply of isolated from the closed loop to protect unit
DHW system from DPW
"Boiler Drains" to allow shut off valve to drain the unit or Pressure Relief
maintenance of the DHW valve on the unit can be used provide a drain
Plate Heat Exchanger
Pressure Relief Valve
(Factory Supplied)
Pipe to building drain
(See local codes)
See local codes to 3/4" Male Supply and Return of 120DegF House
Backflow prevention 3/4" Unions to connect Set for Maximum
Boiler Feed Valve with MANDATOR
"Boiler Drain" - see notes or below the DPW
Shut Off Valves to isolate
both Supply & Return System is designed for the
length (Supply & Return) 20ft Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
Use max ø1" pipe for Supply
& Return to AHU. Max total pipe
Y
TANK
74
QSDHS
20 GAL
SYSTEM
DHW STORAGE
ø1" NPT
CAPACITY
8750 Pioneer Blvd, Santa Fe Springs CA 90670
These should be installed and piped in
DPW DHW Inlet & Anti Scald Valve
Closed
Loop
Supply
DHW
Hot Out
DPW
DPWH
DHW
Cold In
Closed
Loop
Return
From ø3/4" NPT Connection
Shut Off Valves to
isolate DPW
from Air Handler
ø3/4"NPT
zones Taco 008 Bronze Pump
Supply to Heating
zones
(No detail shown) c/w IFC and Shut offs Cold Water Inlet
(No detail shown)
Return from Heating Supplied with QSDHS from House supply
Title : DPW Piping, Primary Loop Htg c/w QSDHS DHW Storage
Drg # : QUI-DPWP-003 Drawn : JLM 9/18/2008 Rev : 001
Closed Loop Heating System Notes : QSDHS DHW System Notes :
When brazing always wrap valves, drains Tank system also includes Tank Drain and
etc with a wet rag to prevent damage P/R Valve (supplied loose)
Check system design for requirement for accordance with local codes
additional expansion tank on closed loop system
Boiler drain installed on Supply to closed loop
should be below DPW Isolation valve to allow
closed loop system to be filled with DPW House
isolated from the closed loop to protect unit Hot Water
A Drain can also be installed on return piping above Supply
shut off valve to drain the unit or Pressure Relief
Use ø1 1/4" pipe
Pipe to building drain sizes are 1/2" Supplied with QSDHS
(See local codes) Max Setting 120DegF
Pressure Relief Valve Outlet connection MANDATOR
3/4" Unions to connect DPW DHW
to 3/4" Male Supply and Return To DPW Outlet
connections on DPW DHW Inlet
Air Vent at "Boiler Drain" - see notes
valve on the unit can be used provide a drain
highest point ø3/4"NPT
Secondary or Zone Pump Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
for Primary Loop
These should be installed and piped in
Y
75
TANK
QSDHS
20 GAL
SYSTEM
DHW STORAGE
ø1" NPT
CAPACITY
from House supply
8750 Pioneer Blvd, Santa Fe Springs CA 90670
DPW
DPWH
Closed
Loop
DHW
DHW
Closed
Loop
Outlet connection MANDATOR
Supply
Hot Out
Cold In
Return
Shut Off Valves to
isolate DPW
from Air Handler
Taco 008 Bronze Pump ø3/4"NPT
c/w IFC and Shut offs
Supplied with QSDHS Cold Water Inlet
Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
Drg # : QUI-DPWP-004 Drawn : JLM 9/18/2008 Rev : 001
Title : DPW Piping, Close coupled AHU c/w QSDHS DHW Storage
Closed Loop Heating System Notes : QSDHS DHW System Notes :
When brazing always wrap valves, drains Tank system also includes Tank Drain and
etc with a wet rag to prevent damage P/R Valve (supplied loose)
System is designed for the Air Handler to be located accordance with local codes
no more than 10ft from the DPW and no more
than 5ft above or below the DPW
Boiler drain installed on Supply to closed loop
should be below DPW Isolation valve to allow House
closed loop system to be filled with DPW Hot Water
isolated from the closed loop to protect unit Supply
A Drain can also be installed on return piping above
Use max ø1" pipe for Supply
& Return to AHU. Max total pipe
Pressure Relief Valve sizes are 1/2" Supplied with QSDHS
Pipe to building drain Max Setting 120DegF
(See local codes) From ø3/4" NPT Connection
3/4" Unions to connect DPW DHW
to 3/4" Male Supply and Return To DPW Outlet
connections on DPW DHW Inlet
Air Vent at "Boiler Drain" - see notes
shut off valve to drain the unit or Pressure Relief
valve on the unit can be used provide a drain DPW DHW Inlet & Anti Scald Valve
highest point ø3/4"NPT
Unit
length (Supply & Return) 20ft
HW Coil
AHU
DPW
76
DPWH
DSR-100F
YEL
BRN BRN
Title : DPW & TACO SR501 ZONE CONTROL PANEL WIRING
Drg # : QUI-ZCW-003 Drawn : JLM 9/24/2008 Rev : 001
NOTES
TO SET DSR-100F
1 PRESS UNIT ON/OFF BUTTON
TEMPERATURE BUTTON
2 PRESS HEATING SET
TO SELECT DESIRED HEATING YEL
WATER TEMPERATURE
3 USE UP AND DOWN ARROWS
RANGE 122-176 DEGF
TEMPERATURE BUTTON
4 PRESS DHW SET
TO SELECT DESIRED DHW
WATER TEMPERATURE
98-114 DEGF, 120, 130, 140 DEGF
5 USE UP AND DOWN ARROWS
WHEN X-X CONTACT IS CLOSED UNIT
WILL START AND PROVIDE CLOSED LOOP
HEATING WATER AT THE
TEMPERATURE SELECTED
DHW PRIORITY WILL BE MAINTAINED
WHEN THE ZONE(S) SATISFY THE UNIT
WILL SHUT DOWN, DSR WILL REMAIN LIT
AT ALL TIMES
THIS IS THE PREFERRED METHOD TO
CONTROL THE SECONDARY LOOP PUMP
REQUIRED IN ALL NON CLOSE COUPLED 8750 Pioneer Blvd, Santa Fe Springs CA 90670
AHU & HW COIL APPLICATIONS Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
DPW
77
DPWH
BRN BRN
YEL
Drg # : QUI-ZW-002 Drawn : JLM 9/24/2006 Rev : 001
Title : DPW & TACO SR504 ZONE CONTROL PANEL WIRING
NOTES DSR-100F
TO SET DSR-100F
1 PRESS UNIT ON/OFF BUTTON
TEMPERATURE BUTTON
2 PRESS HEATING SET
TO SELECT DESIRED HEATING YEL
WATER TEMPERATURE
3 USE UP AND DOWN ARROWS
RANGE 122-176 DEGF
TEMPERATURE BUTTON
4 PRESS DHW SET
TO SELECT DESIRED DHW
WATER TEMPERATURE
98-114 DEGF, 120, 130, 140 DEGF
5 USE UP AND DOWN ARROWS
WHEN X-X CONTACT IS CLOSED UNIT
WILL START AND PROVIDE CLOSED LOOP
LOOP HEATING WATER AT THE TEMPERATURE
TEMPERATURE SELECTED
DHW PRIORITY WILL BE MAINTAINED
WHEN THE ZONE(S) SATISFY THE UNIT
WILL SHUT DOWN, DSR WILL REMAIN LIT
AT ALL TIMES
DIAGRAM SHOWS AN SR504, HOWEVER
DIAGRAM CAN BE USED WITH ALL
ZONE CONTROL PANELS (SR, ZV, ETC) 8750 Pioneer Blvd, Santa Fe Springs CA 90670
WITH AN X - X OR 0V CONTACT Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
8750 Pioneer Blvd, Santa Fe Springs CA 90670
78
DSR-100F
DPW
DPWH
YEL
BRN BRN
SR501
e.g. Taco
Pump Control
To Secondary
Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
Title : DPW & TACO ZVC ZONE CONTROL PANEL WIRING
Drg # : QUI-ZCW-005 Drawn : JLM 10/17/2008 Rev : 001
NOTES
TO SET DSR-100F
1 PRESS UNIT ON/OFF BUTTON
BUTTON (LHS OF ON/OFF BUTTON)
2 PRESS HEATING SET TEMP
TO SELECT DESIRED HEATING YEL
WATER TEMPERATURE
3 USE UP AND DOWN ARROWS
RANGE 122-176 DEGF
BUTTON (RHS OF ON/OFF BUTTON)
4 PRESS DHW SET TEMP
TO SELECT DESIRED DHW
WATER TEMPERATURE
98-114 DEGF, 120, 130, 140 DEGF
5 USE UP AND DOWN ARROWS
WHEN DRY CONTACT IS CLOSED UNIT
WILL START AND PROVIDE CLOSED
LOOP HEATING WATER AT THE
TEMPERATURE SELECTED
DHW PRIORITY WILL BE MAINTAINED
WHEN THE ZONE(S) SATISFY THE UNIT
WILL SHUT DOWN, DSR WILL REMAIN LIT
AT ALL TIMES
THIS IS THE PREFERRED METHOD TO
INTEGRATE ZONE VALVES AND
THE SECONDARY LOOP PUMP
DPW
79
DPWH
YEL
YEL
RELAY
FAN COILSTD 24V AC
HYDRONIC
HEAT
COOL
TSTAT
8750 Pioneer Blvd, Santa Fe Springs CA 90670
Drg # : QUI-DPW-ZW-001 Drawn : JLM 9/6/2006 Rev : 001
NOTES
WIRING DIAGRAM FOR CONTROL OF A
AIR HANDLER & HW COIL, WHERE
PRIMARY PUMP IN DPW IS CAPABLE
OF PROVIDING FLOW TO FAN COIL DSR-100F
TO SET DSR-100F CONTROLLER
1 PRESS UNIT ON/OFF BUTTON
TEMPERATURE BUTTON BRN BRN
2 PRESS HEATING SET
TO SELECT DESIRED HEATING
WATER TEMPERATURE
RANGE 122-176 DEGF SPST
3 USE UP AND DOWN ARROWS
TEMPERATURE BUTTON
4 PRESS DHW SET 24V AC
TO SELECT DESIRED DHW
WATER TEMPERATURE
98-114 DEGF, 120, 130, 140 DEGF
5 USE UP AND DOWN ARROWS
OF THE AIR HANDLER - WIRE TO FAN C C
MOTOR TO STOP FAN OPERATION IF
COIL TEMPERATURE FALLS e.g. DHW
PRIORITY OR INITIAL START UP W W
WHEN T-STAT CALLS FOR HEAT, RELAY WILL
CLOSE AND DPW UNIT WILL START
WHEN T-STAT IS SATISFIED RELAY WILL OPEN AND
UNIT WILL STOP Tel : 562 699 6066, Fax : 562 699 4351, Web : www.Quietside.com
DSR CONTROL WILL REMAIN LIT AT ALL TIMES Title : DPW & SPST RELAY CONTROL WIRING
6 INSTALL AN AQUA STAT IN THE HTG COIL
8750 Pioneer Blvd Santa Fe Springs CA 90670 Tel : 562 699 6066 Fax : 562 699 4351 Web : www.Quietside .com
6 Pine Hill Dr Carlisle PA 17013 Tel : 717 243 2535 Fax : 717 243 7917 Web : www.Quietside .com
Quietside maintains a policy of continuous improvement to it’s product, therefore specifications may vary without notice, always contact your Quietside distributor for the latest specifications
Loading...