Quick Test microPAT User Manual

Page 1
microPAT
user manual
Page 2
microPATCalibration
Your microPAT is calibrated for twelve months from the date of purchase.
Have your microPAT re-calibrated with Quick Test any time during the twelfth month and the calibration will be valid for a full twelve months from the due date.
Contact calibration@quick-test.biz for details.
PAT Test Training
The Quick Test training team have successfully trained thousands of people with all levels of experience.
We provide training in a professional and friendly manner.
Contact training@quick-test.biz for details
Page 3
1
Contents
Contents - - - 1 Introduction - - - 2 Features - - - 2 In-service Inspection & Testing 2 Overview - - - 3 Getting Started - - 4 Accessories - - - 4 Charging - - - 4 Battery Indication - - 4 Controls - - - 5 Results Display - - 5 Switched On Indicator - 5 Tests - - - - 6 Test Table - - - 6 Identifying Class 1 and Class 2 7 Testing a Class 1 Appliance 7 Testing a Class 2 Appliance 8 Testing an Extension Lead 9 Testing an IEC Lead - 10 User Cal Check - - 10 110V & 3-Phase Equipment 11 Specifications - - 12 Regulatory Information - 12
For your future reference please record your tester serial number:
Issue 1
MPAT -
Page 4
2
Introduction
The microPAT Portable Appliance Tester provides the following features in an attractive compact unit:-
Testing of Class 1 and Class 2 Appliances Testing of IEC Leads Testing of Extension Leads
It uses high tech electronics to ensure accurate and reliable operation while being extremely simple and user friendly.
Features
In addition to carrying out the standard tests, the microPAT includes a number of features:-
Additional 250V insulation test for surge protected extension leads Tests different lengths of extension leads Appliance 'switched on' check User calibration check
In-service Inspection & Testing
Always carry out a full visual inspection of the appliance before undertaking any tests. Although the microPAT is easy to operate, the HSE recommend training to correctly carry out a regime of PAT testing. Training with Quick Test will include guidance on what to look for when carrying out a formal visual inspection, how to operate a PAT tester and how often to carry out formal visual inspection and tests on appliances in different environments.
Please contact Quick Test to arrange your training.
Page 5
3
Overview
Charger
Connector
Results
Indicators
Test
Buttons
Battery/Charge
Indicator
IEC
Connector
Test Lead
Connector
Switched On
Indicator
Appliance
Socket
Page 6
4
Getting Started
Accessories
The microPAT is supplied with the following accessories:-
Charger Test Lead Set Short IEC Lead ( used for testing extension leads )
Charging
The microPAT must only be charged with the supplied charger. It is supplied partly charged but we suggest you charge your tester for at least 1 hour to boost the charge before using for the first time.
Your MicroPAT tester will perform in excess of 2000 tests per full battery charge. It can also be used while plugged into the charger.
Battery Indicator
The Battery/Charging indicator will flash green for the first hour when connected to the charger. This is a fast charge period. After this the indicator will be a steady green. To fully charge the microPAT it needs to be charged for 24 hours. It is ok to leave it connected to the charger.
If an incorrect charger is connected the indicator will flash red and green.
During testing if the battery is low, the indicator will flash red. When the battery is too low for the microPAT to operate correctly the indicator will be steady red and the test will stop.
WARNING
Under no circumstance must mains voltage be
connected to the microPAT
Page 7
5
Controls
Results Display
Switched On Indicator
The microPAT is very simple to operate. The only controls are four buttons used to select the required test. To operate, simply press and release the appropriate test button. The indicator next to the test button will flash amber while the test is being performed.
The test results are displayed for ten seconds after the test is completed, the microPAT then shuts down.
When the test is complete the results appear on the results display. If all the required tests pass, the green PASS indicator will light up. If any of the required tests are a fail, the corresponding red FAIL indicator will light up. Additionally the indicator next to the test button will be green or red.
A new test can be started as soon as the results are being displayed, there is no need to wait until the microPAT has shut down.
Any appliance switch must be in the ‘on’ position during testing. When testing Class 1 or Class 2, the microPAT will attempt to determine if the appliance is switched on. If it is unable to detect the appliance is switched on, the ‘Switched on ?’ indicator will flash red. If the appliance is then switched on within five seconds the test will continue.
However because of the design of some appliances it is not always possible for the tester to determine if it is switched on. In this case pressing the corresponding test button will continue the test immediately.
Page 8
6
Tests
The microPAT carries out three different types of test. The actual tests carried out depend on the equipment connected to the tester.
Earth Continuity
The earth continuity test measures the electrical resistance from the earth pin of the mains plug to an earthed point on the appliance. This has to have a very low electrical resistance to provide safe earth protection.
Insulation Resistance
The insulation resistance applies a high voltage ( 500V ) to the live and neutral connections. This is then used to measure the electrical resistance of the appliance to earth, or any exposed metal part. This resistance has to be very high to protect the user.
Insulation Resistance - Surge Protected Extension Leads
The microPAT features an option to perform this test at 250V, this avoids false fail indications when testing surge suppressed extension leads.
Polarity
This is used for extension leads and IEC leads. It checks that there is correct connection between the live and neutral conductors through the lead.
Test Table
Test Selected Earth Continuity
Insulation
Resistance
Polarity
Class 1 Y 500V N
Class 2 N 500V N
Cable Y 500V Y
Cable Surge Y 250V Y
Page 9
7
Identifying Class 1 and Class 2
Testing a Class 1 appliance
1. Plug the test lead into the tester
2. Plug your class 1 appliance into the socket on top of the tester
3. Connect the crocodile clip or probe to some exposed metal on the appliance
4. Press the Class 1 button
If the appliance is not switched on, the ‘ Switched on? ’ indicator will flash to prompt you to do so. If the appliance is then switched on the tester will proceed with the test. If it is not possible to switch the appliance on, press the Class 1 button again to proceed with the test. The Class 1 test button will flash amber while the test is underway.
When the test is finished, either the green PASS indicator will light up, or the appropriate red FAIL indicators will light up. The Class 1 button will also be green or red.
If the Class 1 appliance has no accessible metal part (including fixing screws), then test as Class 2.
Class 1 appliances use an earth connection as a means of protection. Class 2 appliances do not use an earth connection. They are frequently referred to as ‘double insulated’. Class 2 appliances display the ‘double box’ symbol.
Class 2 Symbol
Page 10
8
Testing a Class 2 appliance
1. Plug the test lead into the tester
2. Plug your class 2 appliance into the socket on top of the tester
3. Connect the crocodile clip or probe to any exposed metal on the appliance
4. Press the Class 2 button
If the appliance is not switched on, the ‘ Switched on? ’ indicator will flash to prompt you to do so. If the appliance is then switched on the tester will proceed with the test. If it is not possible to switch the appliance on, press the Class 2 button again to proceed with the test. The Class 2 test button will flash amber while the test is underway.
When the test is finished, either the green PASS indicator will light up, or the appropriate red FAIL indicators will light up. The Class 2 button will also be green or red.
Page 11
9
Testing an Extension Lead
1. Plug the extension lead into the socket on top of the tester
2. Plug the IEC end of the short IEC lead into the IEC socket on the front of the microPAT
3. Plug the 13A plug end of the short IEC lead into the first socket of the extension lead
4. Press the Cable button, or Surge Cable button if the extension lead is surge protected
The Cable or Surge Cable test button will flash amber while the test is underway.
When the test is finished, either the green PASS indicator will light up, or the appropriate red FAIL indicators will light up. The test button will also be green or red.
The test must be repeated for ALL sockets on the extension lead.
If the extension lead has an earth connection, but the reading is high because the lead is exceptionally long, the green PASS indicator will light up, however the Earth Continuity FAIL indicator will flash amber. In this case the extension lead should only be used in exceptional circumstances where the risks are clearly understood.
Page 12
10
Testing an IEC Lead
An IEC ( kettle ) lead is tested in exactly the same way as an extension lead.
1. Plug the 13A plug end of the IEC lead into the socket on top of the tester
2. Plug the IEC end of the IEC lead into the IEC socket on the front of the microPAT
3. Press the Cable button
The Cable test button will flash amber while the test is underway.
When the test is finished, either the green PASS indicator will light up, or the appropriate red FAIL indicators will light up. The test button will also be green or red.
User Cal Check
In order to ensure that PAT testing equipment operates correctly, the IEE Code of Practice for In-service Inspection & Testing of Electrical Equipment states that ‘The accuracy of a test instrument should be
verified and recorded annually or in accordance with the manufacturer’s instructions.’ The microPAT should be formally calibrated annually. Please
contact Quick Test to arrange calibration.
While formal calibration is required on an annual basis, the IEE recommend that PAT testing equipment is checked on a regular basis to confirm correct operation.
The microPAT incorporates a unique feature to perform this.
1. Plug the 13A plug end of the short IEC lead into the socket on top of the tester
2. Plug the IEC end of the short IEC lead into the IEC socket on the front of the microPAT
3. Press both the Class 1 and Class 2 buttons simultaneously
The Class 1 and Class 2 buttons will both flash amber and all three FAIL indicators will flash red, but will turn off as each test passes. If the Cal check passes the green PASS indicator will light up as well as the Class 1 and Class 2 buttons.
Page 13
11
110V and 3-Phase Equipment
110V and 3-Phase equipment is tested in exactly the same way as any other equipment.
The only additional requirement is the use of appropriate adapters to connect to the microPAT.
Please contact Quick Test for details.
Page 14
Specifications
Earth Continuity Test
Current Approx 120mA OC Voltage 5V Tolerance 5% +/- 10mΩ Limits: Class 1 <=200mΩ Normal Ext <=300mΩ Long Ext <=640mΩ
Insulation Resistance Test
Test Voltage 500V / 250V SC Current 1mA Tolerance 5% Limits: Class 1 & Cable >=2MΩ Class 2 >=4MΩ
Supply
Voltage 12V +/-5% Current 400mA max
Regulatory Information
LVD EN 61010 EMC EN 55011
12
The microPAT is produced by a registered WEEE producer: Registration number WEE/HB3434XT. This product should not be disposed of with household waste, it should be handed over to an authorised collection site for recycling waste electrical & electronic equipment.
Page 15
Need Labels? Accessories?
Quick Test can supply tested labels, adapters, and spares for your microPAT.
Contact sales@quick-test.biz
Warranty Information
Quick Test warrants your microPAT against defects in materials and workmanship for a period of one year from the date of purchase.
This warranty covers only those defects which arise as a result of normal use of the product, and does not apply to improper use, modification, or maintenance.
This warranty does not affect your statutory rights.
Page 16
www.quick-test.biz