Quantum DXi690 Series, DXi6802 Quick Start Manual

Quantum DXi6802 and
DXi690x: Rack Mount Rails
Follow the steps in this document to replace the rack mount rails in the DXi6802 or DXi690x:
1 Shutting Down the System on page 2
2 Replacing the rack mount rails:
Replacing the DXi6802 or DXi690x Node Rails on page 3:
Replacing the DXi6802 Array or Expansion Module Rails on page 8
Replacing the DXi690x Array or Expansion Module Rails on page 12
3 Turning On the System on page 17

Necessary Tools

Before you begin, gather the necessary tools:
• Small flat head screwdriver
• Large flat head screwdriver
• #2 PHILLIPS screwdriver
Caution: Use appropriate ESD precautions, including the use of a grounding
strap, when performing any of these procedures.
© 2015 Quantum Corporation. All rights reserved. Quantum, the Quantum logo, DLT, DLTtape, the DLTtape logo, SuperLoader, Scalar, DXi, StorageCare, StorNext, GoProtect, and Vision are registered trademarks of Quantum Corporation and its affiliates in the United States and/or other countries. All other trademarks are the property of their respective owners. Quantum specifications are subject to change.
6-68446-01, April 2016
*6-68446-01*
Quantum DXi6802 and DXi690x: Rack Mount Rails Replacement
Port 1 Port 2
ID/Diag
Lnk Lnk
Power switches
Array Module (rear view)
ID/Diag
Port 1
Power switches
Expansion Module (rear view)
6-68446-01 April 2016

Shutting Down the System

To shut down the system:
Caution: Before shutting down the DXi6802 or DXi690x, make sure that all
backup and replication jobs are finished, and that space reclamation activity is complete.
1 Shut down the system from the remote management console using the
Shutdown option on the Utilities > Reboot & Shutdown page.
Note: Shutting down the system can take up to 15 minutes. Only the
Node will completely shut down.
Figure 1 Turning Off the Array Modules (RBODs)
Figure 2 Turning Off the Expansion Modules (EBODs)
Note: If you need help accessing remote management, see the
User’s Guide DXi690x User’s Guide
(6-67199) at www.quantum.com/DXi6800docs or the
(6-68159) at www.quantum.com/
DXi6000
DXi6900docs.
2 After the Node shuts down, turn off both power switches on the back of
each Array Module (RBOD) (see
Figure 1). Wait until the seven segment
display on the rear of the module turns off.
3 Turn off both power switches on the back of each Expansion Module (EBOD)
(see
Figure 2).
2 Shutting Down the System
Quantum DXi6802 and DXi690x: Rack Mount Rails Replacement

Replacing the DXi6802 or DXi690x Node Rails

Follow the steps below to replace the DXi6802 or DXi690x Node rails:
1 Removing the DXi6802 or DXi690x Node from the Rack on page 3
2 Installing the DXi6802 or DXi690x Node Rack Mounting Rails on page 5
3 Installing the DXi6802 or DXi690x Node on page 6
6-68446-01
April 2016

Removing the DXi6802 or DXi690x Node from the Rack

To remove the DXi6802 or DXi690x Node from the rack:
1 Shut down the DXi6802 or DXi690x system (see Shutting Down the System
on page 2).
2 If installed, remove the front bezel from the Node by lifting the latch on the
left side of the bezel.
3 Remove all power, SAS, Ethernet, and Fibre Channel cables from the rear of
the Node. Make sure to label the cables so they can be easily identified when they are re-connected to the Node after the replacement procedure is complete.
4 Press the locking tab on either side of the Node, and slide the Node out
from the rack until the inner rails lock.
Note: If necessary, remove the optional screws securing the Node to the
front of the rack (behind the locking tab).
5 Locate the lock levers on the sides of the inner rails (see Figure 3). Unlock
each lever by rotating it up to its release position.
Replacing the DXi6802 or DXi690x Node Rails 3
Quantum DXi6802 and DXi690x: Rack Mount Rails Replacement
Inner slide rails
Rear rail standoffs
Rear rail J-slots
Slide-release lock button
Lock lever
Locking tab
Locking tab
6-68446-01 April 2016
Figure 3 Removing the Node from the Rack
6 Slide the Node forward until the rail standoffs are at the front of the J-slots.
7 Remove the Node from the rack and place it on a level surface.
WARNING: The DXi6802 Node (including hard drives) weighs 53.3
pounds (24.2 kg). The DXi6900 G1/G2 Node (including hard drives) weighs 53.0 pounds (24.0 kg). A minimum of two people are required to lift the chassis.
8 Use a flat head screwdriver to lift the latch release button on the end piece
midpoint and unseat each rail (see the rack.
4 Replacing the DXi6802 or DXi690x Node Rails
Figure 4), and then remove the rails from
Figure 4 Removing the Node
Latch release button
Rails
Quantum DXi6802 and DXi690x: Rack Mount Rails Replacement
6-68446-01
April 2016

Installing the DXi6802 or DXi690x Node Rack Mounting Rails

To install the replacement DXi6802 or DXi690x Node rack mounting rails:
1 If present, remove the orange plastic clip from each mounting rail so that
the rail can be extended. (The rails are marked right and left.)
2 Position the left and right rail end pieces labeled FRONT facing inward, and
orient each end piece to seat in the holes on the front side of the vertical rack flanges (see
Figure 5).
Replacing the DXi6802 or DXi690x Node Rails 5
Quantum DXi6802 and DXi690x: Rack Mount Rails Replacement
Rail front end
Rail back end
Latches click into place in rack flange (round or square holes)
Latch release button
6-68446-01 April 2016
Figure 5 Installing the Node Rails

Installing the DXi6802 or DXi690x Node

3 Align each back end piece in the bottom and top holes of the desired U
spaces.
4 Engage the back end of the rail until it fully seats on the vertical rack flange
and the latch clicks into place. Repeat these actions to position and seat the front end piece on the vertical rack flange.
To install the DXi6802 or DXi690x Node:
1 Pull the inner slide rails out of the rack until they lock into place (see
Figure 6).
6 Replacing the DXi6802 or DXi690x Node Rails