CONTROL CENTER ................................................................................................................................................ 6
ACCESSORIES AND OPTIONS ........................................................................................................................... 10
SELECTION DATA ................................................................................................................................................. 13
PART LOAD RATINGS .......................................................................................................................................... 24
PHYSICAL DATA ................................................................................................................................................... 25
ELECTRICAL DATA .............................................................................................................................................. 34
APPLICATION DATA ............................................................................................................................................. 50
The 80-160 Ton (273 - 560 kW) QCC3 Condensing Unit Models are shipped complete
from the factory ready for field installation.
The unit is pressure-tested, evacuated and given a nitrogen holding charge and includes
an initial oil charge (R-410A refrigerant supplied by others). After assembly, a operational
test is performed to assure that each control device operates correctly.
The unit structure is heavy-gauge, galvanized steel. This galvanized steel is coated with
baked-on powder paint, which, when subjected to ASTM B117 1000 hour, salt spray testing, yields a minimum ASTM 1654 rating of “6”. Units are designed in accordance with
NFPA 70 (National Elec tric Code), ASHRAE/ANSI 15 Safety code for mechanical refrigeration, and are cETL listed. All units are produced at an ISO 9000-registered facility.
COMPRESSORS
The chiller has suction-gas cooled, hermetic, scroll com pressors. The compressors incorporate a compliant scroll design in both the axial and radial direction. All rotating parts
of the compressors are statically and dynamically balanced. A large internal volume and
oil reservoir pro vides greater liquid tolerance. Compressor crankcase heaters are also
included for extra protection against liquid migration.
CONDENSER
Coils – Fin and tube condenser coils of seamless, inter nally-enhanced, corrosion resis-
tant copper tubes are arranged in staggered rows, mechanically expanded into aluminum
fins. Integral subcooling is included. The design working pressure of the coil is 650 psig
(45 barg).
Fans – The condenser fans are composed of corro sion-resistant aluminum hub and glassfiber-reinforced polypropylene composite blades molded into a low noise airfoil section.
The are designed for maximum efficiency and are statically and dynamically balanced for
vibration free operation. They are directly driven by independent motors, and positioned
for vertical air discharge. The fan guards are constructed of heavy-gauge, rust-resistant,
coated steel. All blades are statically and dynamically balanced for vibration-free operation.
Motors – The fan motors are Totally Enclosed Air-Over, squirrel-cage type, current protected. They feature ball bearings that are double-sealed and permanently lubri cated.
REFRIGERANT CIRCUIT
Two inde pendent refrigerant circuits will be furnished on each unit. All unit piping will be
copper, with brazed joints. The liquid line will include a field connection shutoff valve with
charg ing port located on each condenser circuit. Suction line connections are provided on
each refrigeration circuit. A filter drier and sight glass are shipped loose for field installation
on each refrigerant circuit.
All expansion valves, liquid line solenoid valves, refriger ant, and refrigerant field piping
are supplied by others.
QUANTECH
5
Page 6
FORM QCC3-EG1 (517)
Control Center
All controls are contained in a NEMA 3R/12 cabinet with hinged outer door and include:
Liquid Crystal Display with light emitting diode (LED) backlight ing suitable for outdoor
viewing:
• Two display lines
• Twenty characters per line
Color coded 12-button keypad with sections for:
DISPLAY/PRINT of typical information:
• Suction temperatures (optional)
• Ambient temperature
• System pressures (each circuit)
• Operating hours and starts (each compressor)
• Print calls up to the liquid crystal display:
• Operating data for the systems
• History of fault shutdown data for up to the last six fault shutdown conditions
• An RS-232 port, in conjunction with this press-to-print button, is provided to permit
the capability of hard copy print-outs via a separate printer (by others).
FIGURE 1 - CONTROL PANEL WITH KEYBOARD
6
LD22323
QUANTECH
Page 7
Control Center (Cont'd)
ENTRY section to:
• Enter SETPOINTS or modify SYSTEM VALUESSETPOINTS updating can be per-
formed to:
Provisions are included for: pumpdown at shutdown; optional remote discharge air temperature reset and two steps of demand load limiting from an external building automation
system. Unit alarm contacts are standard.
The operating program is stored in non-volatile memory (EPROM) to eliminate chiller
failure due to AC powered
failure/battery discharge. Programmed setpoints are retained in lithium battery-backed
RTC memory for 5 years minimum.
Ambient Kit (High) – Required if units are to operate when the ambient temperature is
above 115°F (46°C). Includes sun shield panels and discharge pressure transducers.
(This option includes the Discharge Pressure Transducer /Readout Capabil ity option).
(Field mounted).
COMMUNICATIONS
• Native communication capability for BACnet (MS/TP) and Modbus
• Optional communciation available for N2 and LON via eLink option
8
QUANTECH
Page 9
Control Center (Cont'd)
POWER PANEL
Each panel contains:
• Compressor power terminals
• Compressor motor starting contactors per l.E.C.*
• Control power terminals to accept incoming for 115-1-60 control power
• Fan contactors & overload current protection
The power wiring is routed through liquid-tight conduit to the compressors and fans.
* International Electrotechnical Commission
FORM QCC3-EG1 (517)
QUANTECH
9
Page 10
FORM QCC3-EG1 (517)
Accessories and Options
All options are factory installed unless otherwise noted.
COMPRESSOR AND PIPING OPTIONS:
Chicago Code Relief Valves – Unit will be provided with relief valves to meet Chicago
code requirements.
Hot Gas By-Pass – Permits continuous, stable operation at capacities below the minimum step of compressor by unloading to as low as 5% capacity (depending on both the
unit and operating conditions). This is accomplished by introducing an artificial load. Hot
gas by-pass is available installed on refrigerant system #1 or on both systems of two circuited units..
Service Isolation Valve – Service suction and discharge (ball-type) isolation valves are
added to unit per system. This option also includes a system high pressure relief valve in
com pliance with ASHRAE 15.
CONDENSER AND CABINET OPTIONS:
Condenser coil protection against corrosive environments is available by choosing any of
the following options. For additional application recommendations, refer to FORM 150.12ES1.
Pre-Coated Fin Condenser Coils – The condenser coils are constructed of black epoxycoated aluminum fins. This can provide corrosion resistance comparable to copper-fin
coils in typical seashore loca tions. Either these or the post-coated coils (below), are recommended for units being installed at the seashore or where salt spray may hit the unit.
Post-Coated Dipped Condenser Coils – The unit is built with dipped and cured condenser coils. This is another choice for seashore and other corrosive appli cations (with
the exception of strong alkalies, oxidizers and wet bromine, chlorine and fluorine in concentrations greater than 100 ppm).
Copper-Fin Condenser Coils – The unit constructed with condenser coils which have
copper fins. (This is not recommended for units in areas where they may be exposed to
acid rain).
Enclosure Panels (Unit) – Tamperproof Enclosure Panels prevent unauthorized access
to units. Enclosure Panels can provide an aesthetically pleasing alternative to expensive
fencing. Additionally, for proper head pressure control, Quantech recommends the use of
Condenser Louvered Panels for winter applications where wind gusts may exceed five
mph (eight km/h).
The following types of enclosure panels are available:
Wire Panels (Full Unit) – Consists of welded-wire mesh guards mounted on the exterior
of the unit. Prevents unauthorized access, yet provides free air flow.
Wire/Louvered Panels – Consists of welded-wire-mesh panels on the bottom part of unit
and louvered panels on the condenser section of the unit.
10
QUANTECH
Page 11
Accessories and Options (Cont'd)
Louvered Panels (Condenser Coil Only) – Louvered panels are mounted on the sides
and ends of the condenser coils for protection.
Louvered Panels (Full Unit) – Louvered panels sur round the front, back, and sides of
the unit. These prevent unauthorized access and visually screen unit components. Unrestricted air flow is permitted through generously sized louvered openings. This option is
applicable for any outdoor design ambient temperature up to 115°F (46°C).
Sound Attenuation – One or both of the following sound attenuation options are recommended for residential or other similar sound sensitive locations:
Compressor Acoustic Sound Blanket – Each compressor is individually enclosed by an
acoustic sound blanket. The sound blankets are made with one layer of acoustical absorbent textile fiber of 5/8” (15mm) thickness and one layer of anti-vibrating heavy material
thickness of 1/8” (3mm). Both are closed by two sheets of welded PVC, reinforced for
temperature and UV resistance.
Ultra Quiet Fans – Lower RPM, 8-pole fan motors are used with steeper-pitch fans.
Vibration Isolators – Level adjusting, spring type 1” (25.4mm) or seismic deflection or
neoprene pad isolators for mounting under unit base rails.
FORM QCC3-EG1 (517)
CONTROL OPTIONS:
Ambient Kit (Low) –Units will operate to 32°F (-4°C) (standard). This accessory includes
all necessary components to permit condensing unit operation to 0°F (-18°C). (This option includes the Discharge Pressure Transducer / Readout Capa bility option.) For proper
head pressure control in applications below 25°F (-4°C) where wind gusts may exceed
five mph (eight km/h), it is recommended that Optional Condenser Louvered Enclosure
Panels also be included.
Building Automation System Interface – The factory addition of a Printed Circuit Board
to accept a 4-20 milliamp, 0-10VDC or contact closure input to reset the discharge air temperature from a Building Automation System. (The standard control panel can be directly
connected to a Quantech Building Automated System via the standard on board RS485
communication port.)
Language LCD And Keypad Display – Spanish, French, German, and Italian unit LCD
controls and keypad display avail able. Standard language is English.
Discharge Pressure Transducers And Readout Capability – the addition of pressure
trans ducers allows models to sense and display discharge pressure. (This option as included with either the low or high ambient kits).
Suction Pressure Transducers And Readout Capability – The addition of suction
transduc ers allows models to sense and display suction pressure.
Suction Temperature Readout – The addition of tem perature sensors allow models to
sense and display suction temperature.
Motor Current Module – Capable of monitoring com pressor motor current. Provides
extra protection against com pressor reverse rotation, phase-loss and phase imbalance.
Option consists of one module per electrical system.
QUANTECH
11
Page 12
FORM QCC3-EG1 (517)
Accessories and Options (Cont'd)
POWER OPTIONS:
Compressor Power Connections – Single-point terminal block connection(s) are pro-
vided as standard. The following power connections are available as options. (See electrical data for specific voltage and options availability.)
Single Point Non-Fused Disconnect Switch – Unit-mounted disconnect switch(es) with
external, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied
to isolate the unit power voltage for servicing. Separate external fusing must be supplied,
by others in the power wiring, which must comply with the National Electrical Code and/
or local codes.
Single Point Non-Fused Disconnect Switch With Individual System Breakers - Includes unit-mounted disconnect switch with external, lockable handles (in compliance
with Article 440-14 of N.E.C.) to isolate unit power voltage for servicing. Factory interconnecting wiring is provided from the disconnect switch to factory supplied system circuit
breakers.
Single Point Circuit Breaker – A unit mounted circuit breaker with external, lockable
handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power
voltage for servicing. (This option includes the Single-Point Power connection.)
Control Transformer – Converts unit power voltage to 115-1-60 or 115-1-50 (0.5 or 1.0
kVA capacity). Factory mounting includes primary- and secondary-wiring between the
transformer and the control panel.
Power Factor Correction Capacitors – Will cor rect unit compressor power factors to a
0.90-0.95.
12
QUANTECH
Page 13
Selection Data
The ratings shown on pages 18 through 24 are based on unit operation in a well designed
and properly piped system.
SELECTION RULES
For normal air conditioning applications, size the suction line for a pressure drop of 3 PSI,
corresponding to 2°F, for R-410A refrigerant. Thus, the evaporator temperature will be approximately 2°F higher than the compressor suction temperature. Line loss must be taken
into consideration when selecting the evaporator.
FORM QCC3-EG1 (517)
1. Capabilities are based on Refrigerant R-410A.
2. Ratings may interpolated, but must not be extrapolated.
3. Ratings shown are at saturated suction temperatures corresponding to pressures
at the compressor. In actual practice, suction line pressure drop has the effect of
reducing compressor capacity, forcing the compressor to operate at a lower suction
pressure to maintain the desired evaporator temperature.
SELECTION PROCEDURE
The air-cooled condensing unit may be selected from the Ratings on pages 12 through
17, if the ambient air temperature at the condenser and the saturated suction temperature
at the compressor are known. The ambient air temperature is a known design parameter,
but the suction temperature at the compressor, in many cases, is known only within certain allowable limits. The actual compressor operating suction temperature and the overall
performance of the system will depend directly upon the choice of the evaporator. Starting
with a preliminary evaporator selection at a nominal evaporator temperature and using
data supplied by the evaporator manufacturer, enter the ratings tables and select a unit to
meet the required cooling load at a suction temperature at least 2°F below the evaporator
temperature. The 2°F allows for normal suction line loss.
If more accurate selection is required, the evaporator capacity should be plotted against
the condensing unit capacity to determine the balanced system performance. Again, it is
necessary to factor in the suction line loss.
After the system balance point has been determined, the compressor KW input may be
interpolated from the ratings tables.
QUANTECH
13
Page 14
FORM QCC3-EG1 (517)
Selection Data (Cont'd)
SAMPLE SELECTION
Select an R-410A Air-Cooled Condensing Unit with a matched central station air handling
unit having the following operating conditions:
DESIGN CONDITIONS
1. An air handling unit with four large DX coils (two per circuit) having a total cooling
load of 100 MBH (83 tons).
2. The coil suction temperature required 45°F.
3. The design outdoor ambient temperature is 95°F.
4. The power supply is 460V/3∅/60 hz.
Selection
1. Enter the QCC3080CZE Rating Table (page 12).
2. The model QCC3080CZE will provide 84.1 tons with 73.5 compressor KW input at
95°C ambient air and 45°F suction pressure.
3. CalculatethecompressorKwinputforthespecicdesignconditionsof148Kwand
35°C ambient air.
Kw =
The QCC3080CZE is the suitable selection for the design capacity.
REFRIGERANT PIPING
General – When the unit has been located in its final position, the unit piping may be con-
nected. Normal installation precautions should be observed in order to receive maximum
operating efficiencies. System piping should conform to the YORK DX piping guide form
050.40-ES2 or ASHRAE refrigeration handbook guidelines. All piping design and installation is the responsibility of the user.
QUANTECH ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM
OPERATION OR FAILURES DUE TO IMPROPER PIPING OR PIPING DESIGN.
Filter driers and sight glasses are shipped loose for field installation on each refrigerant
circuit. Field refrigerant piping can be connected to the condensing unit.
All expansion valves, liquid line solenoid valves, refrigerant and refrigerant piping are supplied and installed by others.
Table 1 - FITTING EQUIVALENT LENGTHS* on page 16 lists refrigerant line connections sizes per unit model number.
83
84.1Kw
x 73.5Kw = 72.5Kw
14
QUANTECH
Page 15
Selection Data (Cont'd)
REFRIGERANT LINE SIZING
Refrigerant piping systems must be designed to provide practical line sizes without excessive pressure drops, prevent compressor oil from being “trapped” in the refrigerant piping,
and ensure proper flow of liquid refrigerant to the thermal expansion valve. Considerations should be give to:
4. Liquid line pressure drop (or gain) due to vertical rise of the liquid line.
Table 4 - REFRIGERANT LINE CONNECTIONS on page 17 provides the pressure
drops for given pipe sizes for both liquid and suction lines. The pressure drops given are
per 100 equivalent ft. (30.5 m) of refrigerant piping. These friction losses do not include
any allowances for strainer, filter drier, solenoid valve, isolation valve or fittings.
Nominal pressure drop for solenoids, sight glass, and driers are shown in Table 2 - MIS-CELLANEOUS LIQUID LINE PRESSURE DROPS on page 16.
FORM QCC3-EG1 (517)
Table 3 - REFRIGERATION PIPING CHARGES on page 16 includes approximate
equivalent lengths for copper fittings.
To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line
pressure drop should never exceed 50 psi (3.4 bar). Refrigerant vapor in the liquid line
will measurably reduce valve capacity and poor system performance can be expected.
To allow adequate oil return to the compressor, suction risers should be sized for a minimum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to ensure
oil return up the suction riser. Refer toTable 5 under column labeled Nominal Tons (KW)
Unloaded.
Evaporator Below Condensing Unit
On a system where the evaporator is located below the condensing unit, the suction line
must be sized for both pressure drop and oil return. In some cases a double suction riser
must be installed to ensure reliable oil return at reduced loads. Table 3 indicates when a
double suction riser should be used for listed pipe sizes to provide adequate oil return at
reduced loads. The calculated information was based on maintaining a minimum of 1000
fpm (5.08 m/s) refrigerant vapor velocity.
Condenser Below Evaporator
When the condensing unit is located below the evaporator, the liquid line must be designed for both friction loss and static head loss due the vertical rise. The value of static
head loss of 5 psi/ft.(3.4 kPa/30 cm) must be added to the friction loss pressure drop in
addition to all pressure drops due to driers, valves, etc.
QUANTECH
15
Page 16
FORM QCC3-EG1 (517)
Selection Data (Cont'd)
OIL TRAPS
All horizontal suction lines should be pitched at least 1/4” per foot (2 cm/m) in the direction
of the refrigerant flow to aid in the return of oil to the compressor. All suction lines with a
vertical rise exceeding 3 feet (.91 meters) should have a “P” trap at the bottom and top
of the riser. Suction lines with a vertical rise exceeding 25 feet (7.6 meters) should be
trapped every 15 feet (4.6 meters).
REFRIGERANT CHARGE
The condensing unit is charged with a dry nitrogen holding charge. The remaining operating charge for the condensing unit, evaporator coil, and refrigerant piping must be weighed
in after all refrigerant piping is installed, leak checked, and evacuated. Final adjustment of
refrigerant charge should be verified by subcooling values (refer to section on Pre-Startup
for checking subcooling).
REFRIGERANT PIPING REFERENCE
For more details, refer to ASHRAE Refrigeration Handbook, Chapter 2.
TABLE 1 - FITTING EQUIVALENT LENGTHS*
QCC3SHORT RADIUS ELLLONG RADIUS ELL
3/4” (19mm)6.5ft. (2m)4.5 ft.(1.4m)
7/8” (22mm)7.8 ft. (2.4m)5.3 ft (1.6m)
1-1/8” (29mm)2.7ft. (0.8m)1.9 ft. (0.6m)
1-3/8” (35mm)3.2 ft. (1m)2.2 ft. (0.7m)
1-5/8” (41mm)3.8 ft. (1.2m)2.6 ft. (0.8m)
2-1/8” (54mm)5.2 ft. (1.6m)3.4 ft. (1m)
2-5/8” (67mm)6.5 ft (2.0m)4.2 ft. (1.3m)
*Copper Fitting Equivalent Lengths
TABLE 2 - MISCELLANEOUS LIQUID LINE PRESSURE DROPS
3. Nominal Tons (KW) Unloaded is based on one compressor (per system) operating at design conditions.
4. Based on minimum compressor staging for the given pipe size, a double suction riser should be used to ensure proper oil return to the
compressor on all vertical suction risers. Oil returning up the riser moves up the inner surface of the pipe and depends on the mass velocity
of the refrigerant vapor at the wall surface to move the oil up the vertical rise.
5. Hotgasbypasslinesaretypically7/8”forlinesupto40feetand1-1/8”forlinesover40feetinlength(12meters).Theeldconnectionssiz-
es are 7/8” for the optional factory mounted hot gas bypass valve. Note: Hot gas bypass is only available for refrigerant system number 1.
6. For more information, please refer to either the YORK DX Piping Guide (Form 050.40-ES2) or the ASHRAE Refrigertion Handbook.
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory
Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3
amps; -58, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps.
It is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or
operation at ambient temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit, per N.E.C. Article 440-22.
5. CircuitbreakersmustbeULlistedandCSAcertiedandmaximumsizeisbasedon225%oftheratedload
amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225%
of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in
the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the
unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per
on the National Electrical Code, using copper connectors only. Field wiring must also comply with local
codes.
7. AgroundlugisprovidedforeachcompressorsystemtoaccommodateaeldgroundingconductorperN.E.C.
Table 250-95. A control circuit grounding lug is also supplied.
8. Thesupplieddisconnectisa“DisconnectingMeans”asdenedintheN.E.C.100,andisintendedforisolating
the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not
intended to be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
LEGEND
ACR-LINE ACROSS THE LINE START
C.B. CIRCUIT BREAKER
D.E. DUAL ELEMENT FUSE
DISC SW DISCONNECT SWITCH
FACT MOUNT CB FACTORY MOUNTED CIRCUIT BREAKER
FLA FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF MINIMUM NON FUSED
RLA RATED LOAD AMPS
S.P. WIRE SINGLE POINT WIRING
UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT
SWITCH)
LRA LOCKED ROTOR AMPS
N.E.C. NATIONAL ELECTRICAL CODE
VOLTAGE CODE
-17 = 200-3-60
-28 = 230-3-60
-40 = 380-3-60
-46 = 460-3-60
-58 = 575-3-60
38
QUANTECH
Page 39
FORM QCC3-EG1 (517)
THIS PAGE INTENTIONALLY LEFT BLANK.
QUANTECH
39
Page 40
FORM QCC3-EG1 (517)
Electrical Drawings
40
LD22075a
QUANTECH
Page 41
Electrical Drawings (Cont'd)
FORM QCC3-EG1 (517)
035-21583-101 REV O
QUANTECH
LD22075b
41
Page 42
FORM QCC3-EG1 (517)
LD22195b
Electrical Drawings (Cont'd)
42
LD22195a
QUANTECH
Page 43
Electrical Drawings (Cont'd)
FORM QCC3-EG1 (517)
035-21583-114 REV J
QUANTECH
LD22195b
43
Page 44
FORM QCC3-EG1 (517)
---> -AMB
Electrical Drawings (Cont'd)
-XP2
1D
1
2
2C
3
26B129B122B
5
120A
6
10
29B131B127B
30B25B128B
32A27A228A
10
140A28A229A
3A31A231A
218C
1
2
3
4
5
222B
6
227B220B
-XP4
2
1
13I
19B
18B
43
-XP4
19C
13K18C
43
21
NB41
7
8
9
7
8
9
7
8
9
-XP3
7
8
9
122A119A
127A
128A
228B221B
229B219B
231B
-XP2
-XP3
---> -AMB
10
131A29A
11
12
25A
119B
4
120B
5
6
121B118C
221A
4
222A
5
6
227A220A
10
11
28B140B
12
31B
-ELINK
26A129A
134
14
30A121A118A
15
1
1E
2
2D
3
1
218A
2
219A
3
32B27B
13
14
3B
15
---> -AMB
NB34
NB19
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
10
1C
1D
140A
140C
131A
33
23
24
218A
218B
219A
220A 227A
221A
222A
218B
223A
227A
228A
229A
NB34
1
2
3
4
5
6
7
8
9
10
1
2
3
4
118A
118B
119A
120A 127A
121A
122A
118B
123A
127A
128A
129A
1B
1C
231A
NB34
TB7
TB10
TB5
TB6
1
1
1
1
TB8
TB9
1
031-02550-
1
+-COM
SHD
-
+
SHD
COM
HOT
J2
TB5
BLK
WHT
TB1
-AMB
43
2
1
ELINK/AMB:BLK
ELINK/AMB:RED
R
REF
ELINK/AMB:BLK
ELINK/AMB:RED
BLK
WHT
-T5
44
P/N 25-2698-18
NB4
SHD
REF-+
SHD
REFRXTX
5
2
NB49
NB49
NB34NB39
1E
123I
223I
123E
223E
31I
29I
27I
33I
32I
30I
28I
32E
31E
30E
29E
33E
28E
25I
26I
27E
26E
25E
-XTBC2
NB19
NB4
5B
5I
23I
24I
23E
24E
24
5
NB41
2
2I
2I
GNDI
2E2ILELI5E
NB4
GNDE
2E
2E
NB49
NB19
LD22317a
QUANTECH
Page 45
Electrical Drawings (Cont'd)
-J15
7
S+
4
1
S-S-98
5
2
6
S+
3
NB46
1
BRN-NEG
BRN-POS
2
-XP5
NB6
FORM QCC3-EG1 (517)
035-21589-102 REV M
-ADIS
12
TB1
PL1
J15
TB3TB2
J2
1
J1
1
TB4
+
NB6
BRN-NEG
BRN-POS
-SOA
13J
NB32
-J6
7
4
1
5
2
98
6
3
7
4
1
-J6
5
2
98
6
3
NB37
-J7
12
-J11
8
4
NB42
12
8
4
NB42
9
4
10
5
-XTBC1
A-NEG
A-POS
51
13H13J
13I
50
13G
13H
21
13F
13G
20
13E
13F
19A19B
13D
13E
18A18B
13C
13D
14
13B
13C
13A
13B
40A
41A
-SF
SFE:BLK
SFE:WHT
SFE:BRN
SFE:BLU
NB50
-SFE
NB19
14
11
9
18A12
19A
12
10
-AMB
9
5
1
J6
7
11111
7
4
J4
J7
5
99
J8
7
4
J9
4
1
9
5
1
6
2
5
2
6
2
1110
7
3
-J8
98
6
3
-J9
1110
7
3
-J10
NB37
98
6
3
8
3
-J13
51
5
7
50
8
6
5
J10
7
1
1
J14
J13
2
5B
5A
J12
9
5
11
11
6
4
J11
7
4
1
6
1
5
2
7
2
NB46
-F2
-F1
1
2
2
1
1
2
13A
20
3
21
4
-T1
41
40
41A
40A
3A
1
1E
1
NB39
NB19
QUANTECH
1
2
3
-J14
40
41
GND B
LD22317b
45
Page 46
FORM QCC3-EG1 (517)
Electrical Drawings (Cont'd)
JB1
-XTB1
149F
JB1
-XTB1
1
1
149G
2
2
2
AQ
+EXT
JB2
-FSC
+EXT
TB1
3
TB1
3
TB2
4
PE
144A
-FSC
TB2
L3
4
PE
L1L2
+EXT
+EXT
V2U2W2
W1
U1
V1
E
GND302301300
V2U2W2
W1
U1
V1
E
GND305304303
V2
U2W2
W1
U1
V1
E
GND302301300
V2
W2
U2
W1
U1
V1
E
GND305304303
+EXT
GND
123
1
2
3
TB2
UL1L2L3
V
W
PE.
GND
+EXT
1
2
2
AV
3
TB2
U
V
W
PE.
+EXT+EXT
+EXT
=1-XTBF
+EXT
+EXT
SFE:WHT 2
SFE:BLU
+EXT
GND
223
2AS
226A
2AP
2
206
207
208
GND
1
+EXT
2
1AF
SFE:BRN
1
5
34
SFE:BLK
+EXT
13 14
=2-BDP:RED
=2-BDP:BLK
2
2
=2-BDP:WHT
3
225A
2AM
1
2
3
2
203
204
205
GND
1AD
A
B
C
232
+EXT
2
OR
224A
+EXT
1
2
3
231A
2AL
2
200
201
202
GND
+EXT
2
1AC
OR
GND
244A
+EXT
1
2
2
AW
3
46
235A
234A
233A
234
233
232A
LD22197a
QUANTECH
Page 47
Electrical Drawings (Cont'd)
149G
GND
+EXT
2
AQ
120A
220A
FORM QCC3-EG1 (517)
035-21589-106 REV N
GND
+EXT
1
2
2
AG
3
GND
+EXT
1
2
2
AH
3
120V
126A
2AN
2
GND
=2-BSP:RED
=2-BSP:BLK
=2-BSP:WHT
1
2
3
OR
A
B
C
120V
JB2
=1-BSP:RED
=1-BSP:BLK
=1-BSP:WHT
OR
=1-BDP:RED
=1-BDP:BLK
=1-BDP:WHT
106
107
108
+EXT
1
2
3
125A
2AK
A
B
C
2
103
104
105
GND
132
+EXT
OR
+EXT
1
2
3
131A
124A
2AJ
2
100
101
102
GND
1
2
3
OR
A
B
C
120V
120V
+EXT
2
1AE
135A
134A
QUANTECH
133A
132A
2
1AA
133
120V
2
1AB
134
LD22197b
47
Page 48
FORM QCC3-EG1 (517)
NOITPIRCSEDnoitangiseDNOITPIRCSEDnoitangiseD
KFOL
FANOVERLOA D
F
Electrical Drawings (Cont'd)
- ADISDISPLAY BOARD
- BAMBAMBIENT
- BDPDISCHARGE PRESSURE
- BECTENTERING CHILLED TEMPERATURE REDRED
- BLCTLEAVING CHILLED TEMPERATURERPRUN PERMISSIVE
NOT FITTED ON REMOTE EVAP UNITS
-BMPMOTOR PROTECTOR COMPRESSORSCRSCREEN
-CPFCA PACITOR POWER FACTOR - SOASWITCH OFF AUTO
-EPHPUMP HEATER
-EXTEX TERNAL
TO CONTROL PA NEL-UBRBRIGDE RECFIFIER
REKAERB TIUCRICBCQ-YROSSECCACCA
-QMMSC
-QSDSWITCH DISCONNECT
RUREMOTE UNLOAD Is t STEP
- SKPKEY PA D
MA NUAL MOTOR STARTER COMPRESSOR
RRESISTOR
HCTIWS WOLFFS -ERUSSERP NOITCUSPSB -
REMROFSNARTT -RETAEH ESACKNARCHCE -
PMUP RETRATS ROTOM LAUNAMPSMMQ-DRAOB ORCIMBMA -
TNERRUC REMROFSNARTCT-RETAEH ROTAROPAVEHEE-
ETIHWTHW ESUFF -
- FHPHIGH PRES SURE CUTOUT
-FSIFA N SPEED INHIBIT TWO SPEED- XTBCTERMINAL BLOCK CUSTOMER
YROTCAF KCOLB LANIMRETFBTX -YLNO NOITPO NAF
GNDGROUND
G/YGREEN / YELLOW
J PLUG BOARD CONNECTORFIELD MOUNTED AND WIRED ON REMOTE EV AP UNITS
-KCIRCUIT BOARD RELAY- ZCPRCOMPRESSOR
-KFFAN CONTACTOR LINE
-KFH
-KFL
-
-KFSRELAY FA N SPEED
- MCOMPRES SOR MOTOR
-M
-MPMOTOR PUMP
FAN CONTACTOR HIGH SPEED
(INCLUDING COIL SUPPRESSOR)
FAN CONTACTOR LOW SPEED
(INCLUDING COIL SUPPRESSOR)
(INCLUDING COIL SUPPRESSOR)
(INCLUDING COIL SUPPRESSOR)
MOTOR FA N
-YHGSVHOT GA S SOLENOID VALVE
(INCLUDING COIL SUPPRESSOR)
- YLLSVLIQUID LINE SOLENOID VALVE
(INCLUDING COIL SUPPRESSOR)
NB
WIRING A ND ITEMS SHOWN THUS
ARE STANDARD QUANTECH ACCESSORIES
ITEMS THUS ENCLOSED FORM A
COMPONENTS OR SETS OFCOMPONENTS
A. This drawing is based on IEC symbols.
B. Field wiring to be in accordance with the relevant electrical code as well as all other applicable codes and
specications
C. All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by
the chiller manufacturer .
D. Green and yellow wire is used for earth, multi-coloured cable used for low voltage. Red wire used for AC
control, blue wire for neutral, black wire for AC and DC power. Orange wire should be used for interlock
control wiring supplied by external source.
circuit, refers to system thereon, e.g.= 1-FHP2 refers to high pressure cutout no 2 on system no 1.
F. All wiring to control section voltage free contacts requires a supply provided by the customer maximum
voltage 240 volts. The customer must t ake particular care when deriving the supplies for the voltage free
terminals with regard to a common point of isolation. Thus, these circuits when used must be fed via the
common point of isolation the voltage to these ci rcuits is removed when the common point of isolation to
the unit is opened. This common point of isolation is not supplied. The voltage free contacts are rated at
100VA. All inductive devices {relays} switch by the voltage free contacts must have their coil suppressed
using standard r/c suppressors.
G. Customer voltage free contacts connected to terminal 13 must be rated at 30v 5ma
H. No controls {relays etc.} Should be mounted in any section of the control panel. Additionally, control wiring
not connected to the control panel should not be run through the panel. If these precautions are not fol-
lowed, electrical noise could cause malfunctions or damage to the unit and its controls.
1. Refer to instalation commisioning operation and maintenance manual for customer connections and customer connection notes, non compliance to these instructions will invalidate unit warranty.
2. Wiringandcomponentsforcompressor3onlyttedwhenunithas3compressorsonthesystem.1-BMP3
is replaced by a link across terminals 134 & 135. 2-BMP3 is replaced by a link across terminals 234 & 235.
3. FHP2isonlyttedon0089andabove.Whennottted1-FHP2isreplacedbyalinkacrossterminals132
& 139. 2-FHP2 is replaced by a link across terminals 232 & 239
4. Fitted on units with hot gas bypass option.
5. EMS option is wired as shown
6. This wiring must be used for old display 031-0110-000
7. Network connection point
8. Printer port
9. Remote emergency stop can be wired between terminal l and 5 after removing link
24. See sheet 3 of connection diagram for power input options
FORM QCC3-EG1 (517)
QUANTECH
49
Page 50
FORM QCC3-EG1 (517)
Application Data
UNIT LOCATION
The QCC3 Condensing Units are designed for outdoor installation. When selecting a site
for installation, be guided by the following conditions:
1. For outdoor locations of the unit, select a place having an adequate supply of fresh
air for the condenser.
2. Avoid locations beneath windows or between structures where normal operating
sounds may be objection able.
3. Installation sites may be either on a roof, or at ground level. (See FOUNDATION,
below.)
4. The condenser fans are the propeller-type, and are not recommended for use with
duct work in the condenser air stream.
5. When it is desirable to surround the unit(s), it is recom mended that the screening
be able to pass the required chiller CFM without exceeding 0.1” of water external
static pressure.
6. Protection against corrosive environments is available by supplying the units with
eithercoppern,curedphenolic,orepoxycoatingonthecondensercoils.Thephenolic or epoxy coils should be offered with any units being installed at the seashore
or where salt spray may hit the unit.
In installations where winter operation is intended and snow accumulations are expected,
additional height must be provided to ensure normal condenser air flow.
Recommended clearances for units are given in Dimension Drawings on page 26.
When the available space is less, the unit(s) must be equipped with the discharge pressure transducer option to permit high pressure unloading in the event that air recirculation
were to occur.
FOUNDATION
The unit should be mounted on a flat and level foundation, ground or roof, capable of supporting the entire operating weight of the equipment. Operating weights are given in the
Physical Data on page 25 tables.
Roof Locations – Choose a spot with adequate struc tural strength to safely support the
entire weight of the unit and service personnel. Care must be taken not to damage the roof
during installation. If the roof is “bonded”, consult the building contractor or architect for
special installation requirements. Roof installations should incorporate the use of springtype isolators to minimize the transmission of vibration into the building structure.
Ground Level Installations – It is important that the units be installed on a substantial
base that will not settle, causing strain on the refrigerant lines and resulting in possible
leaks. A one-piece concrete slab with footers extending below the frost line is highly recommended, particularly in areas where winters are long and very cold. Additionally, the
slab should not be tied to the main build ing foundation as noises will telegraph.
50
QUANTECH
Page 51
Application Data (Cont'd)
Mounting holes (11/16” diameter) are provided in the steel channel for bolting the unit to
its foundation. See Dimension Drawings on page 26.
For ground level installations, precautions should be taken to protect the unit from tampering by or injury to unau thorized persons. Screws on access panels will prevent casual
tampering; however, further safety precautions, such as unit enclosure options, a fencedin enclosure, or locking devices on the panels may be advisable. Check local authorities
for safety regulations.
REFRIGERANT PIPING
When sizing refrigerant pipe for split system air condition ing, consideration must be given
to the: (1) Suction line pressure drop due to friction, (2) Liquid line pressure drop due to
friction, (3) Suction line velocity for oil return, and (4) Liquid line pressure drop due to
vertical rise.
On a system where the evaporator blower is located below the condensing unit, the suction line must be sized for both pressure drop and oil return.
When the condensing unit is located below the evapora tor blower, the liquid line must be
designed for pressure drop due to friction loss and vertical rise. If the pressure drop due to
vertical rise and friction loss exceeds 30 psig (2.1 barg), some refrigerant will flash before
it reaches the thermal expansion valve.
FORM QCC3-EG1 (517)
All horizontal suction lines should be pitched at least 1/4 inch (6 mm) per foot in the direction of the refrigerant flow to aid the return of oil to the compressor. All suction lines with
a vertical rise exceeding 3 feet (1 m) should have a ‘P’ trap at the bottom and the top to
facilitate oil return. Suction lines with a vertical rise exceeding 25 feet (7.6 m) should be
trapped every 15 feet (4.6 m) to provide drain points for the oil when the circuit is deactivated. When the circuit is reactivated, oil will return to the compressor more quickly and
in smaller slugs.
For more details, refer to ASHRAE Refrigeration Hand book, System Practices for Halocarbon Refrigerants.
QUANTECH
51
Page 52
FORM QCC3-EG1 (517)
Guide Specifications
PART 1 – GENERAL
1.01 SCOPE
A. The requirements of the General Conditions, Supplementary Conditions, Division 1,
and Drawings apply to all Work herein.
B. Provide Microprocessor controlled, multiple-scroll compressor, air-cooled, condensing
units of the scheduled capacities as shown and indicated on the Drawings, including
but not limited to:
1. Condensing Unit package
2. Electrical power and control connections
3. DX Central Station Air Handling connections
1.02 QUALITY ASSURANCE
A. Products shall be Designed, Tested, and installed in compliance with applicable sec-
tions of the following Standards and Codes:
1. ANSI/ASHRAE Standard 15 – Safety Code for Mechanical Refrigeration
2. ASHRAE 90.1 - Energy efciency compliance.
3. ANSI/NFPA Standard 70 – National Electrical Code (N.E.C.).
4. Conform to Intertek Testing Services, formerly ETL, for construction of condensing
units and provide E.T.L./c E.T.L. Listing label.
5. Manufactured in facility registered to ISO 9002.
B. Factory Test: Condensing Unit shall be pressure tested, evacuated and given a nitro-
gen holding charge and an initial oil charge, and shall be factory operational run tested
to assure each control device operates properly.
C. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture
against defects in workmanship and material for a period of one year from date of initial
shall include, but is not limited to: not less than two refrigerant circuits, scroll compressors, air-cooled condenser, refrigerant, lubrication system, interconnecting wiring,
safety and operating controls including capacity controller, control center, motor startingcomponents, and specialfeaturesasspecied hereinor requiredforsafe, automatic operation.
B. Cabinet: External structural members shall be constructed of heavy gauge, galvanized
steel coated with baked on powder paint which, when subject to ASTM B117, 1000
hour, 5% salt spray test, yields minimum ASTM 1654 rating of “6”.
2.02 COMPRESSORS
FORM QCC3-EG1 (517)
Compressors: Shall be hermetic, scroll-type, including:
3. Large suction side free volume and oil sump to provide liquid handling capability.
4. Compressor crankcase heaters to provide extra liquid migration protection.
5. Annular discharge check valve and reverse vent assembly to provide low pressure
drop, silent shutdown and reverse rotation protection.
6. Initial Oil charge.
7. Oil Level sightglass.
8. Vibration isolator mounts for compressors.
9. Brazed-type connections for fully hermetic refrigerant circuits.
2.03 REFRIGERANT CIRCUIT
Two independent refrigerant circuits will be furnished on each unit. All unit piping will be
copper, with brazed joints. The liquid line will include a field connection shutoff valve with
charging port located on each condenser circuit. Suction line connections are provided
on each refrigeration circuit. Filter drier and sight glass are shipped loose for field installation on each refrigerant circuit. All expansion valves and liquid line solenoid valves and
refrigerant field piping are supplied by others.
QUANTECH
53
Page 54
FORM QCC3-EG1 (517)
Guide Specifications (Cont'd)
2.04 HEAT EXCHANGERS
A. Air Cooled Condenser:
1. Coils: Internally enhanced, seamless copper tubes, mechanically expanded into
aluminumalloynswithfullheightcollars.Subcoolingcoilanintegralpartofcondenser. Design working pressure shall be 650 psig (45 barg).
2. Fans: Shall be dynamically and statically balanced, direct drive, corrosion resistant
A. General: Automatic start, stop, operating, and protection sequences across the range
of scheduled conditions and transients.
B. Microprocessor Enclosure: Rain and dust tight NEMA 3R/12 (IP55) powder painted
steel cabinet with hinged, latched, and gasket sealed door.
C. Microprocessor Control Center:
1. Condensing Unit control is set for Discharge Air Temperature Control
2. Automatic control of compressor start/stop, anti-coincidence and anti-recycle timers, automatic pump-down shut-down, condenser fans, unit alarm contacts, and
condensing unit operation from 0°F to 125°F (-18°C to 52°C) ambient. Automatic
reset to normal chiller operation after power failure.
3. Software stored in non-volatile memory, with programmed set-points retained in
lithium battery-backed real time clock (RTC) memory for minimum 5 years.
4. Forty character liquid crystal display, descriptions in English (or Spanish, French,
Italian, or German), numeric data in English (or Metric) units. Sealed keypad with
sections for Setpoints, Display/Print, Entry, Unit Options & clock, and On/Off Switch.
5. Programmable Set-points (within Manufacturer limits): display language; suction pressure setting and control range, remote reset temperature range, set daily
schedule/holiday for start/stop, manual override for servicing, low and high ambient cutouts, number of compressors, low suction pressure cutout, high discharge
pressure cutout, anti-recycle timer (compressor start cycle time), and anticoincident
timer (delay compressor starts).
6. Display Data: Suction temperatures (optional), low ambient temperature cutout setting, outdoor air temperature, English or metric data, suction pressure cutout setting,
each system suction pressure, discharge pressure (optional), discharge air reset via
Building Automation System (by others) via a 4-20milliamp or 0-10 VDC input with
optional BAS interface, anti-recycle timer status for each system, anti-coincident
54
QUANTECH
Page 55
Guide Specifications (Cont'd)
system start timer condition, compressor run status, no cooling load condition, day,
date and time, daily start/stop times, holiday status, automatic or manual system
lead/lag control (when controlling based on Discharge Air Temperature only), automatic lead/lag of compressors within a system, compressor starts/operating hours
(each), status of hot gas valves, and fan operation, run permissive status, number
of compressors running, liquid solenoid valve status, load & unload timer status.
7. System Safeties: Shall cause individual compressor systems to perform auto shut
down; manual reset required after the third trip in 90 minutes. Includes: high discharge pressure, low suction pressure, high pressure switch, and motor protector.
Compressor motor protector shall protect against damage due to high input current
or thermal overload of windings.
8. Unit Safeties: Shall be automatic reset and cause compressors to shut down if low
ambient, or under voltage.
9. Alarm Contacts: Low ambient, low voltage, low battery, and (per compressor circuit): high discharge pressure, and low suction pressure.
10. High Ambient Control: Permits unit operation above 115°F (46°C) ambient.
D. Manufacturer shall provide any controls not listed above, necessary for automatic con-
densingunitoperation.MechanicalContractorshallprovideeldcontrolwiringnecessary to interface sensors to the condensing unit control system.
FORM QCC3-EG1 (517)
2.06 POWER CONNECTION AND DISTRIBUTION
A. Power Panels:
1. NEMA 3R/12 (IP55) rain/dust tight, powder painted steel cabinets with hinged,
latched, and gasket sealed outer doors. Provide main power connection(s), control
power connections, compressor and fan motor start contactors, current overloads,
and factory wiring.
2. Power supply shall enter unit at a single location, be 3 phase of scheduled voltage,
and connect to individual terminal blocks per compressor. Separate disconnecting
means and/or external branch circuit protection (by Contractor) required per applicable local or national codes.
B. Exposed compressor, control and fan motor power wiring shall be routed through liquid
tight conduit.
2.07 ACCESSORIES AND OPTIONS
Some accessories and options supercede standard product features. Your Quantech
Sales Representative will be pleased to provide assistance.
A. Microprocessor controlled, Factory installed Across-the-Line type compressor motor
starters as standard.
B. Outdoor Ambient Temperature Control
1. Low Ambient Control: Permits unit operation to 0°F (-18°C) ambient. Standard unit
QUANTECH
controls to 32°F (0°C) ambient.
55
Page 56
FORM QCC3-EG1 (517)
Guide Specifications (Cont'd)
C. Power Supply Connections:
1. SinglePointPowerSupply:SinglepointTerminalBlockforeldconnectionandin-
terconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming power wiring, which must comply with the National
Electric Code and/or local codes.
2. Single Point: Single point Non-Fused Disconnect(s) and lockable external handle
(in compliance with Article 440-14 of N.E.C.) can be supplied to isolate the unit
power voltage for servicing. Separate external fusing must be supplied, by others,
in the in coming power wiring, which must comply with the National Electric Code
and/or local codes.
3. Single Point Disconnect with Individual System Breakers: Single point Terminal
Block with Non- Fused Disconnect and lockable external handle (in compliance
with Article 440-14 of N.E.C.) can be supplied to isolate power voltage for servicing.
Factory interconnecting wiring from disconnect to factory supplied circuit breakers.
4. Single Point Circuit Breaker: Single point Terminal Block with Circuit Breaker and
lockable external handle (in compliance with Article 44014 of N.E.C.) can be supplied to isolate power voltage for servicing. Incoming power wiring must comply with
the National Electric Code and/or local codes.
D. Pressure & Temperature Transducers and Sensors
1. Discharge Pressure Transducers: Permits unit to sense and display discharge pressure.
2. Suction Pressure Transducers: Permits unit to sense and display suction pressure.
3. Suction Temperature Sensors: Permits units to sense and display suction temperature.
E. Control Power Transformer: Converts unit power voltage to 120-1-60 or 120-1-50 for
50Hz units (500 VA capacity). Factory mounting includes primary- and secondary-wiring between the transformer and the control panel.
F. Motor Current Module: Capable of monitoring compressor motor current. Provides ex-
tra protection against compressor reverse rotation, phase-loss and phase imbalance.
Options consists of one module per electrical system. (Factory mounted)
G. Power Factor Correction Capacitors: Provided to correct unit compressor factors to a
0.900.95.
H. Condenser Coil Environmental Protection:
1. Pre-Coated:Epoxycoatedaluminumnstocktoguardfromcorrosiveagentsand
insulate against galvanic potential. For mild seashore or industrial locations
3. Post-Coated Dipped: Dipped-cured coating on condenser coils for seashore and
other corrosive applications (with the exception of strong alkalis, oxidizers, and wet
I. Protective Condensing Unit Panels (Factory or Field Mounted):
1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabinet, over external condenser coil faces.
2. Wire Panels (full unit): Heavy gauge, welded wire-mesh, coated to resist corrosion,
to protect condenser coils from incidental damage and restrict unauthorized access
to internal components.
3. Louvered Panels (full unit): Painted steel as per remainder of unit cabinet, to protect
condenser coils from incidental damage,visually screen internal components, and
prevent unauthorized access to internal components.
4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces,
painted as per remainder of unit cabinet. Heavy gauge, welded wire-mesh, coated
to resist corrosion, around base of machine to restrict unauthorized access.
J. Service Isolation valves: Service suction and discharge (ball type) isolation valves are
added to unit per system. This option also includes a system high pressure relief valve
in compliance with ASHRAE15. (Factory-mounted.)
K. Hot Gas By-Pass: Permits continuous, stable operation at capacities below the mini-
mum step of unloading to as low as 5% capacity (depending on both the unit & operat-
welded steel housing with vertical and horizontal limit stops. Housings shall be designed to withstand a minimum 1.0g accelerated force in all directions to 2 inches.
57
Page 58
FORM QCC3-EG1 (517)
Guide Specifications (Cont'd)
PART 3 - EXECUTION
3.01 INSTALLATION
A. General: Rig and Install in full accordance with Manufacturers requirements, Project
drawings, and Contract documents.
B. Location: Locate condensing unit as indicated on drawings, including cleaning and
service maintenance clearance per Manufacturer instructions. Adjust and level condensing unit on support structure.
C. Components: Installing Contractor shall provide and install all auxiliary devices and
accessories for fully operational condensing unit.
D. Electrical: Coordinate electrical requirements and connections for all power feeds with
Electrical Contractor (Division 16).
E. Controls: Coordinate all control requirements and connections with Controls Contrac-
tor.
F. Finish:InstallingContractorshallpaintdamagedandabradedfactorynishwithtouch-
uppaintmatchingfactorynish.
58
QUANTECH
Page 59
Notes
FORM QCC3-EG1 (517)
QUANTECH
59
Page 60
Printed on recycled paper
Form QCC3-EG1 (517) New Release
P.O. Box 423, Milwaukee, WI 53201 Printed in USA
Issued on 5/19/2017
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.