Quantech QCC3 User Manual

Page 1
FORM QCC3-EG1 (517)
MODEL QCC3
AIR-COOLED SCROLL COMPRESSOR
CONDENSING UNITS
STYLE A
80 – 160 TON
281 – 562 kW
60 Hz
Page 2
FORM QCC3-EG1 (517)
Nomenclature
QC C 3 145C Z E 46 X C
DESIGN SERIES
TYPE START X = ACROSS THE LINE
VOLTAGE CODE: 17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60
Z = STANDARD EFFICIENCY Y = HIGH EFFICIENCY
NOMINAL CAPACITY
CONDENSING
UNIT
Quantech Air-Cooled Scroll Condensing Units
Approvals
• ASME Boiler and Pressure Vessel Code – Section Vlll Division 1
• UL 1995 – Heating and Cooling Equipment
• ASHRAE 15 – Safety Code for Mechanical Refrigeration
REFRIGERANT R-410a
• ASHRAE Guideline 3 – Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-Conditioning Equipment and Systems
• N.E.C. – National Electrical Code
• OSHA – Occupational Safety and Health Act
2
QUANTECH
Page 3
FORM QCC3-EG1 (517)
Table Of Contents
INTRODUCTION ...................................................................................................................................................... 5
CONTROL CENTER ................................................................................................................................................ 6
ACCESSORIES AND OPTIONS ........................................................................................................................... 10
SELECTION DATA ................................................................................................................................................. 13
RATINGS ................................................................................................................................................................ 18
PART LOAD RATINGS .......................................................................................................................................... 24
PHYSICAL DATA ................................................................................................................................................... 25
DIMENSION DRAWINGS ......................................................................................................................................26
ISOLATORS ........................................................................................................................................................... 29
ELECTRICAL DATA .............................................................................................................................................. 34
ELECTRICAL NOTES ........................................................................................................................................... 38
ELECTRICAL DRAWINGS .................................................................................................................................... 40
APPLICATION DATA ............................................................................................................................................. 50
GUIDE SPECIFICATIONS ..................................................................................................................................... 52
QUANTECH
3
Page 4
FORM QCC3-EG1 (517)
THIS PAGE INTENTIONALLY LEFT BLANK.
4
QUANTECH
Page 5
Introduction
FORM QCC3-EG1 (517)
GENERAL
The 80-160 Ton (273 - 560 kW) QCC3 Condensing Unit Models are shipped complete from the factory ready for field installation.
The unit is pressure-tested, evacuated and given a nitrogen holding charge and includes an initial oil charge (R-410A refrigerant supplied by others). After assembly, a operational test is performed to assure that each control device operates correctly.
The unit structure is heavy-gauge, galvanized steel. This galvanized steel is coated with baked-on powder paint, which, when subjected to ASTM B117 1000 hour, salt spray test­ing, yields a minimum ASTM 1654 rating of “6”. Units are designed in accordance with NFPA 70 (National Elec tric Code), ASHRAE/ANSI 15 Safety code for mechanical refrig­eration, and are cETL listed. All units are produced at an ISO 9000-registered facility.
COMPRESSORS
The chiller has suction-gas cooled, hermetic, scroll com pressors. The compressors in­corporate a compliant scroll design in both the axial and radial direction. All rotating parts of the compressors are statically and dynamically balanced. A large internal volume and oil reservoir pro vides greater liquid tolerance. Compressor crankcase heaters are also included for extra protection against liquid migration.
CONDENSER
Coils – Fin and tube condenser coils of seamless, inter nally-enhanced, corrosion resis-
tant copper tubes are arranged in staggered rows, mechanically expanded into aluminum fins. Integral subcooling is included. The design working pressure of the coil is 650 psig (45 barg).
Fans – The condenser fans are composed of corro sion-resistant aluminum hub and glass­fiber-reinforced polypropylene composite blades molded into a low noise airfoil section. The are designed for maximum efficiency and are statically and dynamically balanced for vibration free operation. They are directly driven by independent motors, and positioned for vertical air discharge. The fan guards are constructed of heavy-gauge, rust-resistant, coated steel. All blades are statically and dynamically balanced for vibration-free opera­tion.
Motors – The fan motors are Totally Enclosed Air-Over, squirrel-cage type, current pro­tected. They feature ball bearings that are double-sealed and permanently lubri cated.
REFRIGERANT CIRCUIT
Two inde pendent refrigerant circuits will be furnished on each unit. All unit piping will be copper, with brazed joints. The liquid line will include a field connection shutoff valve with charg ing port located on each condenser circuit. Suction line connections are provided on each refrigeration circuit. A filter drier and sight glass are shipped loose for field installation on each refrigerant circuit.
All expansion valves, liquid line solenoid valves, refriger ant, and refrigerant field piping are supplied by others.
QUANTECH
5
Page 6
FORM QCC3-EG1 (517)
Control Center
All controls are contained in a NEMA 3R/12 cabinet with hinged outer door and include:
Liquid Crystal Display with light emitting diode (LED) backlight ing suitable for outdoor viewing:
• Two display lines
• Twenty characters per line
Color coded 12-button keypad with sections for:
DISPLAY/PRINT of typical information:
• Suction temperatures (optional)
• Ambient temperature
• System pressures (each circuit)
• Operating hours and starts (each compressor)
• Print calls up to the liquid crystal display:
• Operating data for the systems
• History of fault shutdown data for up to the last six fault shutdown conditions
• An RS-232 port, in conjunction with this press-to-print button, is provided to permit
the capability of hard copy print-outs via a separate printer (by others).
FIGURE 1 - CONTROL PANEL WITH KEYBOARD
6
LD22323
QUANTECH
Page 7
Control Center (Cont'd)
ENTRY section to:
• Enter SETPOINTS or modify SYSTEM VALUES SETPOINTS updating can be per- formed to:
• Suction pressure setting
• Suction pressure control zone
• Remote reset temperature range
• Set daily schedule/holiday for start/stop
• Manual override for servicing
• Low and high ambient cutouts
• Number of compressors
• Low suction pressure cutout
• High discharge pressure cutout
FORM QCC3-EG1 (517)
• Anti-recycle timer (compressor start cycle time)
• Anti-coincident timer (delay compressor starts) UNIT section to:
• Set clock
• Set options
• Set unit option
Set unit control for Discharge Air Temperature Control or for Suction Pressure Control (requires Suction Pres sure Transducers – standard.
UNIT ON/OFF switch
The microprocessor control center is capable of display ing the following:
• Suction temperatures (optional)
• Low ambient temperature cutout setting
• Outdoor air temperature
• English or Metric data
• Suction pressure cutout setting
• Each system suction pressure
• System discharge pressure
• Discharge Air Temperature Reset via a Quantech ISN DDC or Building Automation
QUANTECH
System (by oth ers) via:
• - a pulse width modulated (PWM) input as standard
• - a 4-20 milliamp or 0 -10 VDC input, or contact closure with the optional B.A.S.
interface option
7
Page 8
FORM QCC3-EG1 (517)
Control Center (Cont'd)
• Anti-recycle timer status for each system
• Anti-coincident system start timer condition
• Compressor run status
• No cooling load condition
• Day, date, and time
• Daily start/stop times
• Holiday status
• Automatic or manual system lead/lag control (Discharge Air Temperature control
only)
• Automatic lead/lag of compressors within a system
• Compressor starts & operating hours (each compressor)
• Status of hot gas valves, and fan operation
• Run permissive status
• Number of compressors running
• Liquid solenoid valve status
• Load & unload timer status
Provisions are included for: pumpdown at shutdown; optional remote discharge air tem­perature reset and two steps of demand load limiting from an external building automation system. Unit alarm contacts are standard.
The operating program is stored in non-volatile memory (EPROM) to eliminate chiller failure due to AC powered
failure/battery discharge. Programmed setpoints are retained in lithium battery-backed RTC memory for 5 years minimum.
Ambient Kit (High) – Required if units are to operate when the ambient temperature is above 115°F (46°C). Includes sun shield panels and discharge pressure transducers. (This option includes the Discharge Pressure Transducer /Readout Capabil ity option). (Field mounted).
COMMUNICATIONS
• Native communication capability for BACnet (MS/TP) and Modbus
• Optional communciation available for N2 and LON via eLink option
8
QUANTECH
Page 9
Control Center (Cont'd)
POWER PANEL
Each panel contains:
• Compressor power terminals
• Compressor motor starting contactors per l.E.C.*
• Control power terminals to accept incoming for 115-1-60 control power
• Fan contactors & overload current protection
The power wiring is routed through liquid-tight conduit to the compressors and fans.
* International Electrotechnical Commission
FORM QCC3-EG1 (517)
QUANTECH
9
Page 10
FORM QCC3-EG1 (517)
Accessories and Options
All options are factory installed unless otherwise noted.
COMPRESSOR AND PIPING OPTIONS:
Chicago Code Relief Valves – Unit will be provided with relief valves to meet Chicago
code requirements.
Hot Gas By-Pass – Permits continuous, stable operation at capacities below the mini­mum step of compressor by unloading to as low as 5% capacity (depending on both the unit and operating conditions). This is accomplished by introducing an artificial load. Hot gas by-pass is available installed on refrigerant system #1 or on both systems of two cir­cuited units..
Service Isolation Valve – Service suction and discharge (ball-type) isolation valves are added to unit per system. This option also includes a system high pressure relief valve in com pliance with ASHRAE 15.
CONDENSER AND CABINET OPTIONS:
Condenser coil protection against corrosive environments is available by choosing any of the following options. For additional application recommendations, refer to FORM 150.12­ES1.
Pre-Coated Fin Condenser Coils – The condenser coils are constructed of black epoxy­coated aluminum fins. This can provide corrosion resistance comparable to copper-fin coils in typical seashore loca tions. Either these or the post-coated coils (below), are rec­ommended for units being installed at the seashore or where salt spray may hit the unit.
Post-Coated Dipped Condenser Coils – The unit is built with dipped and cured con­denser coils. This is another choice for seashore and other corrosive appli cations (with the exception of strong alkalies, oxidizers and wet bromine, chlorine and fluorine in con­centrations greater than 100 ppm).
Copper-Fin Condenser Coils – The unit constructed with condenser coils which have copper fins. (This is not recommended for units in areas where they may be exposed to acid rain).
Enclosure Panels (Unit) – Tamperproof Enclosure Panels prevent unauthorized access to units. Enclosure Panels can provide an aesthetically pleasing alternative to expensive fencing. Additionally, for proper head pressure control, Quantech recommends the use of Condenser Louvered Panels for winter applications where wind gusts may exceed five mph (eight km/h).
The following types of enclosure panels are available:
Wire Panels (Full Unit) – Consists of welded-wire mesh guards mounted on the exterior of the unit. Prevents unauthorized access, yet provides free air flow.
Wire/Louvered Panels – Consists of welded-wire-mesh panels on the bottom part of unit and louvered panels on the condenser section of the unit.
10
QUANTECH
Page 11
Accessories and Options (Cont'd)
Louvered Panels (Condenser Coil Only) – Louvered panels are mounted on the sides and ends of the condenser coils for protection.
Louvered Panels (Full Unit) – Louvered panels sur round the front, back, and sides of the unit. These prevent unauthorized access and visually screen unit components. Unre­stricted air flow is permitted through generously sized louvered openings. This option is applicable for any outdoor design ambient temperature up to 115°F (46°C).
Sound Attenuation – One or both of the following sound attenuation options are recom­mended for residential or other similar sound sensitive locations:
Compressor Acoustic Sound Blanket – Each compressor is individually enclosed by an acoustic sound blanket. The sound blankets are made with one layer of acoustical absor­bent textile fiber of 5/8” (15mm) thickness and one layer of anti-vibrating heavy material thickness of 1/8” (3mm). Both are closed by two sheets of welded PVC, reinforced for temperature and UV resistance.
Ultra Quiet Fans – Lower RPM, 8-pole fan motors are used with steeper-pitch fans.
Vibration Isolators – Level adjusting, spring type 1” (25.4mm) or seismic deflection or
neoprene pad isolators for mounting under unit base rails.
FORM QCC3-EG1 (517)
CONTROL OPTIONS:
Ambient Kit (Low) –Units will operate to 32°F (-4°C) (standard). This accessory includes
all necessary components to permit condensing unit operation to 0°F (-18°C). (This op­tion includes the Discharge Pressure Transducer / Readout Capa bility option.) For proper head pressure control in applications below 25°F (-4°C) where wind gusts may exceed five mph (eight km/h), it is recommended that Optional Condenser Louvered Enclosure Panels also be included.
Building Automation System Interface – The factory addition of a Printed Circuit Board to accept a 4-20 milliamp, 0-10VDC or contact closure input to reset the discharge air tem­perature from a Building Automation System. (The standard control panel can be directly connected to a Quantech Building Automated System via the standard on board RS485 communication port.)
Language LCD And Keypad Display – Spanish, French, German, and Italian unit LCD controls and keypad display avail able. Standard language is English.
Discharge Pressure Transducers And Readout Capability – the addition of pressure trans ducers allows models to sense and display discharge pressure. (This option as in­cluded with either the low or high ambient kits).
Suction Pressure Transducers And Readout Capability – The addition of suction transduc ers allows models to sense and display suction pressure.
Suction Temperature Readout – The addition of tem perature sensors allow models to sense and display suction temperature.
Motor Current Module – Capable of monitoring com pressor motor current. Provides extra protection against com pressor reverse rotation, phase-loss and phase imbalance. Option consists of one module per electrical system.
QUANTECH
11
Page 12
FORM QCC3-EG1 (517)
Accessories and Options (Cont'd)
POWER OPTIONS:
Compressor Power Connections – Single-point terminal block connection(s) are pro-
vided as standard. The following power connections are available as options. (See electri­cal data for specific voltage and options availability.)
Single Point Non-Fused Disconnect Switch – Unit-mounted disconnect switch(es) with external, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied to isolate the unit power voltage for servicing. Separate external fusing must be supplied, by others in the power wiring, which must comply with the National Electrical Code and/ or local codes.
Single Point Non-Fused Disconnect Switch With Individual System Breakers - In­cludes unit-mounted disconnect switch with external, lockable handles (in compliance with Article 440-14 of N.E.C.) to isolate unit power voltage for servicing. Factory intercon­necting wiring is provided from the disconnect switch to factory supplied system circuit breakers.
Single Point Circuit Breaker – A unit mounted circuit breaker with external, lockable handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power voltage for servicing. (This option includes the Single-Point Power connection.)
Control Transformer – Converts unit power voltage to 115-1-60 or 115-1-50 (0.5 or 1.0 kVA capacity). Factory mounting includes primary- and secondary-wiring between the transformer and the control panel.
Power Factor Correction Capacitors – Will cor rect unit compressor power factors to a
0.90-0.95.
12
QUANTECH
Page 13
Selection Data
The ratings shown on pages 18 through 24 are based on unit operation in a well designed and properly piped system.
SELECTION RULES
For normal air conditioning applications, size the suction line for a pressure drop of 3 PSI, corresponding to 2°F, for R-410A refrigerant. Thus, the evaporator temperature will be ap­proximately 2°F higher than the compressor suction temperature. Line loss must be taken into consideration when selecting the evaporator.
FORM QCC3-EG1 (517)
1. Capabilities are based on Refrigerant R-410A.
2. Ratings may interpolated, but must not be extrapolated.
3. Ratings shown are at saturated suction temperatures corresponding to pressures at the compressor. In actual practice, suction line pressure drop has the effect of reducing compressor capacity, forcing the compressor to operate at a lower suction pressure to maintain the desired evaporator temperature.
SELECTION PROCEDURE
The air-cooled condensing unit may be selected from the Ratings on pages 12 through 17, if the ambient air temperature at the condenser and the saturated suction temperature at the compressor are known. The ambient air temperature is a known design parameter, but the suction temperature at the compressor, in many cases, is known only within cer­tain allowable limits. The actual compressor operating suction temperature and the overall performance of the system will depend directly upon the choice of the evaporator. Starting with a preliminary evaporator selection at a nominal evaporator temperature and using data supplied by the evaporator manufacturer, enter the ratings tables and select a unit to meet the required cooling load at a suction temperature at least 2°F below the evaporator temperature. The 2°F allows for normal suction line loss.
If more accurate selection is required, the evaporator capacity should be plotted against the condensing unit capacity to determine the balanced system performance. Again, it is necessary to factor in the suction line loss.
After the system balance point has been determined, the compressor KW input may be interpolated from the ratings tables.
QUANTECH
13
Page 14
FORM QCC3-EG1 (517)
Selection Data (Cont'd)
SAMPLE SELECTION
Select an R-410A Air-Cooled Condensing Unit with a matched central station air handling unit having the following operating conditions:
DESIGN CONDITIONS
1. An air handling unit with four large DX coils (two per circuit) having a total cooling load of 100 MBH (83 tons).
2. The coil suction temperature required 45°F.
3. The design outdoor ambient temperature is 95°F.
4. The power supply is 460V/3/60 hz.
Selection
1. Enter the QCC3080CZE Rating Table (page 12).
2. The model QCC3080CZE will provide 84.1 tons with 73.5 compressor KW input at 95°C ambient air and 45°F suction pressure.
3. CalculatethecompressorKwinputforthespecicdesignconditionsof148Kwand 35°C ambient air.
Kw =
The QCC3080CZE is the suitable selection for the design capacity.
REFRIGERANT PIPING
General – When the unit has been located in its final position, the unit piping may be con-
nected. Normal installation precautions should be observed in order to receive maximum operating efficiencies. System piping should conform to the YORK DX piping guide form
050.40-ES2 or ASHRAE refrigeration handbook guidelines. All piping design and installa­tion is the responsibility of the user.
QUANTECH ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM OPERATION OR FAILURES DUE TO IMPROPER PIPING OR PIPING DESIGN.
Filter driers and sight glasses are shipped loose for field installation on each refrigerant circuit. Field refrigerant piping can be connected to the condensing unit.
All expansion valves, liquid line solenoid valves, refrigerant and refrigerant piping are sup­plied and installed by others.
Table 1 - FITTING EQUIVALENT LENGTHS* on page 16 lists refrigerant line connec­tions sizes per unit model number.
83
84.1Kw
x 73.5Kw = 72.5Kw
14
QUANTECH
Page 15
Selection Data (Cont'd)
REFRIGERANT LINE SIZING
Refrigerant piping systems must be designed to provide practical line sizes without exces­sive pressure drops, prevent compressor oil from being “trapped” in the refrigerant piping, and ensure proper flow of liquid refrigerant to the thermal expansion valve. Consider­ations should be give to:
1. Suctionlinepressuredropduetorefrigerantow.
2. Suction line refrigerant velocity for oil return.
3. Liquidlinepressuredropduetorefrigerantow.
4. Liquid line pressure drop (or gain) due to vertical rise of the liquid line.
Table 4 - REFRIGERANT LINE CONNECTIONS on page 17 provides the pressure drops for given pipe sizes for both liquid and suction lines. The pressure drops given are per 100 equivalent ft. (30.5 m) of refrigerant piping. These friction losses do not include any allowances for strainer, filter drier, solenoid valve, isolation valve or fittings.
Nominal pressure drop for solenoids, sight glass, and driers are shown in Table 2 - MIS- CELLANEOUS LIQUID LINE PRESSURE DROPS on page 16.
FORM QCC3-EG1 (517)
Table 3 - REFRIGERATION PIPING CHARGES on page 16 includes approximate equivalent lengths for copper fittings.
To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line pressure drop should never exceed 50 psi (3.4 bar). Refrigerant vapor in the liquid line will measurably reduce valve capacity and poor system performance can be expected.
To allow adequate oil return to the compressor, suction risers should be sized for a mini­mum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to ensure oil return up the suction riser. Refer to Table 5 under column labeled Nominal Tons (KW) Unloaded.
Evaporator Below Condensing Unit
On a system where the evaporator is located below the condensing unit, the suction line must be sized for both pressure drop and oil return. In some cases a double suction riser must be installed to ensure reliable oil return at reduced loads. Table 3 indicates when a double suction riser should be used for listed pipe sizes to provide adequate oil return at reduced loads. The calculated information was based on maintaining a minimum of 1000 fpm (5.08 m/s) refrigerant vapor velocity.
Condenser Below Evaporator
When the condensing unit is located below the evaporator, the liquid line must be de­signed for both friction loss and static head loss due the vertical rise. The value of static head loss of 5 psi/ft.(3.4 kPa/30 cm) must be added to the friction loss pressure drop in addition to all pressure drops due to driers, valves, etc.
QUANTECH
15
Page 16
FORM QCC3-EG1 (517)
Selection Data (Cont'd)
OIL TRAPS
All horizontal suction lines should be pitched at least 1/4” per foot (2 cm/m) in the direction of the refrigerant flow to aid in the return of oil to the compressor. All suction lines with a vertical rise exceeding 3 feet (.91 meters) should have a “P” trap at the bottom and top of the riser. Suction lines with a vertical rise exceeding 25 feet (7.6 meters) should be trapped every 15 feet (4.6 meters).
REFRIGERANT CHARGE
The condensing unit is charged with a dry nitrogen holding charge. The remaining operat­ing charge for the condensing unit, evaporator coil, and refrigerant piping must be weighed in after all refrigerant piping is installed, leak checked, and evacuated. Final adjustment of refrigerant charge should be verified by subcooling values (refer to section on Pre-Startup for checking subcooling).
REFRIGERANT PIPING REFERENCE
For more details, refer to ASHRAE Refrigeration Handbook, Chapter 2.
TABLE 1 - FITTING EQUIVALENT LENGTHS*
QCC3 SHORT RADIUS ELL LONG RADIUS ELL
3/4” (19mm) 6.5ft. (2m) 4.5 ft.(1.4m)
7/8” (22mm) 7.8 ft. (2.4m) 5.3 ft (1.6m) 1-1/8” (29mm) 2.7ft. (0.8m) 1.9 ft. (0.6m) 1-3/8” (35mm) 3.2 ft. (1m) 2.2 ft. (0.7m) 1-5/8” (41mm) 3.8 ft. (1.2m) 2.6 ft. (0.8m) 2-1/8” (54mm) 5.2 ft. (1.6m) 3.4 ft. (1m) 2-5/8” (67mm) 6.5 ft (2.0m) 4.2 ft. (1.3m)
*Copper Fitting Equivalent Lengths
TABLE 2 - MISCELLANEOUS LIQUID LINE PRESSURE DROPS
SOLENOID VALVE 2-3 PSI (13.8 - 20.7kPa)
FILTER/DRIER 2-3 PSI (13.8 - 20.7kPa) SIGHT GLASS 0.5PSI (3.4 kPa)
TABLE 3 - REFRIGERATION PIPING CHARGES
R-410A SUCT @ 36 DEG LIQ @ 105 DEG
SUCTION LINES
SIZE
1-3/8 1.3 0.0 2.1 0.3 8.1 1-5/8 1.5 0.0 2.1 0.4 11.5 2-1/8 2.0 0.0 2.1 0.7 20.0 2-5/8 2.5 0.0 2.1 1.1 30.9
3/4 0.7 0.0 60.9 2.4 66.8
7/8 0.8 0.0 60.9 3.3 92.8 1-1/8 1.0 0.0 60.9 5.6 158.3 1-3/8 1.3 0.0 60.9 8.5 241.1
INSIDE
DIAMETER
CU FT
LIQUID LINES
DENSITY
LB/CU
FT
OZ./FT. GRAMS/30 CM
16
QUANTECH
Page 17
Selection Data (Cont'd)
TABLE 4 - REFRIGERANT LINE CONNECTIONS
REFRIGERANT LINE
MODEL
NUMBER
TONS
QCC3
080CZE 81.3
085CZE
84.3
090CZE 91.1
100CYE 98.5
110CYE
130CZE
111.5
131.5
145CZE 145.3
160CZE 158.3
SYSTEM
NUMBER
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
CONNECTION
SUCTION LIQUID
2.7 1.1 2-5/8 1656
2.7 1.1 2-5/8 1656
2.7 1.1 2-5/8 1818
2.7 1.1 2-5/8 1572
2.7 1.1 2-5/8 1812
2.7 1.1 2-5/8 1896
2.7 1.1 2-5/8 1896
2.7 1.1 2-5/8 1896
2.7 1.1 2-5/8 1812
2.7 1.1 2-5/8 2598
2.7 1.1 2-5/8 2658
2.7 1.1 2-5/8 2658
3.1 1.4 3-1/8 2790
2.7 1.1 2-5/8 1926
3.1 1.4 3-1/8 2658
2.7 1.1 2-5/8 2556
FORM QCC3-EG1 (517)
SUCTION LINE LIQUID LINE
COPPER
TYPE L
INCHES OD
VELOCITY
@ NOMINAL
CAPACITY
IN FPM
NOMINAL
TONS
UNLOADED
13.5 1-1/8
3.5 1-1/8
14.9 1-1/8
13.2 1-1/8
14.9 1-1/8
14.9 1-1/8
14.9 1-1/8
14.9 1-1/8
14.9 1-1/8
33.6 1-1/8
32.8 1-1/8
32.8 1-1/8
31.3 1-3/8
14.9 1-1/8
30.7 1-3/8
33.1 1-1/8
COPPER
TYPE L
INCHES OD
Refrigerant Piping Notes
1. Based on R-410A at the nominal capacity of the unit or system, an ambient temperature of 95°F (35°C) and a suction temperature of 45°F (7.2°C).
2. Suction line sizes were calculated based on a nominal maximum pressure drop to 3 PSI/100 ft. (20.7 kPa/30.5 m). When calculating suc-
tionlinepressuredropforaspecicapplication,itshouldbenotedthatsystemcapacitydecreasesassuctionlinepressuredropincreases.
3. Nominal Tons (KW) Unloaded is based on one compressor (per system) operating at design conditions.
4. Based on minimum compressor staging for the given pipe size, a double suction riser should be used to ensure proper oil return to the compressor on all vertical suction risers. Oil returning up the riser moves up the inner surface of the pipe and depends on the mass velocity of the refrigerant vapor at the wall surface to move the oil up the vertical rise.
5. Hotgasbypasslinesaretypically7/8”forlinesupto40feetand1-1/8”forlinesover40feetinlength(12meters).Theeldconnectionssiz- es are 7/8” for the optional factory mounted hot gas bypass valve. Note: Hot gas bypass is only available for refrigerant system number 1.
6. For more information, please refer to either the YORK DX Piping Guide (Form 050.40-ES2) or the ASHRAE Refrigertion Handbook.
QUANTECH
17
Page 18
FORM QCC3-EG1 (517)
Ratings
MODEL: QCC3080CZE IPLV: 16.1 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 78.1 62.8 13.5 75.9 66.1 12.5 73.6 69.6 11.6 71.3 73.4 10.7 68.9 77.4 9.8
37.0 80.8 63.5 13.8 78.5 66.8 12.8 76.2 70.4 11.9 73.7 74.1 10.9 71.2 78.2 10.1
39.0 83.6 64.3 14.1 81.2 67.6 13.1 78.8 71.1 12.1 76.2 74.9 11.2 73.7 78.9 10.3
41.0 86.5 65.0 14.5 83.9 68.4 13.4 81.4 71.9 12.4 78.8 75.7 11.5 76.2 79.7 10.6
43.0 89.4 65.9 14.8 86.8 69.2 13.7 84.1 72.7 12.7 81.4 76.5 11.7 78.7 80.5 10.8
45.0 92.3 66.7 15.1 89.6 70.0 14.0 86.9 73.5 13.0 84.1 77.4 12.0 81.3 81.4 11.1
47.0 95.3 67.6 15.4 92.5 70.9 14.3 89.7 74.4 13.3 86.8 78.2 12.3 83.9 82.2 11.3
49.0 98.4 68.4 15.7 95.5 71.8 14.6 92.6 75.4 13.5 89.6 79.1 12.5 86.6 83.1 11.6
51.0 101.6 69.4 16.0 98.5 72.7 14.9 95.5 76.3 13.8 92.5 80.0 12.8 89.4 84.0 11.8
53.0 104.8 70.3 16.3 101.6 73.7 15.2 98.5 77.2 14.1 95.3 80.9 13.1 92.1 84.9 12.1
55.0 108.0 71.3 16.6 104.8 74.6 15.5 101.5 78.2 14.3 98.2 82.0 13.3 95.0 85.9 12.3
MODEL: QCC3085CZE IPLV: 15.2 EER
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 81.1 69.3 12.8 78.7 73.0 11.8 76.3 77.1 10.9 73.9 81.5 10.1 71.3 86.1 9.2
37.0 83.9 70.1 13.1 81.4 73.8 12.1 79.0 77.9 11.2 76.4 82.3 10.3 73.8 86.9 9.5
39.0 86.8 70.9 13.4 84.2 74.7 12.4 81.7 78.7 11.5 79.0 83.1 10.6 76.4 87.8 9.7
41.0 89.7 71.8 13.7 87.1 75.6 12.7 84.4 79.6 11.7 81.7 84.0 10.8 79.0 88.6 9.9
43.0 92.7 72.7 14.0 90.0 76.5 13.0 87.2 80.6 12.0 84.5 84.9 11.1 81.6 89.5 10.2
45.0 95.8 73.7 14.3 93.0 77.5 13.3 90.1 81.5 12.3 87.3 85.8 11.3 84.3 90.5 10.4
47.0 98.9 74.7 14.6 96.0 78.5 13.5 93.1 82.5 12.5 90.1 86.9 11.6 87.1 91.4 10.6
49.0 102.0 75.8 14.8 99.1 79.5 13.8 96.0 83.5 12.8 93.0 87.9 11.8 89.9 92.4 10.9
51.0 105.3 76.8 15.1 102.2 80.6 14.0 99.1 84.6 13.0 95.9 88.9 12.0 92.8 93.5 11.1
53.0 108.6 78.0 15.4 105.4 81.7 14.3 102.2 85.7 13.3 98.9 90.0 12.3 95.7 94.6 11.3
55.0 111 . 9 79.2 15.6 108.6 82.9 14.5 105.3 86.9 13.5 102.0 91.1 12.5 98.6 95.7 11.6
75.0 80.0 85.0 90.0 95.0
AIR TEMPERATURE ON - CONDENSER (°F)
75.0 80.0 85.0 90.0 95.0
MODEL: QCC3090CZE IPLV: 15.0 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 87.8 77.0 12.6 85.2 81.1 11.6 82.6 85.6 10.7 79.9 90.5 9.9 77.1 95.6 9.0
37.0 90.9 77.9 12.9 88.2 82.1 11.9 85.5 86.5 11.0 82.7 91.4 10.1 79.8 96.5 9.3
39.0 93.9 78.9 13.2 91.2 83.1 12.2 88.4 87.6 11.2 85.5 92.4 10.4 82.6 97.5 9.5
41.0 97.1 79.9 13.4 94.2 84.1 12.4 91.3 88.6 11.5 88.4 93.4 10.6 85.4 98.5 9.7
43.0 100.3 81.0 13.7 97.3 85.2 12.7 94.3 89.7 11.7 91.3 94.5 10.8 88.2 99.6 10.0
45.0 103.5 82.1 14.0 100.5 86.3 13.0 97.4 90.8 12.0 94.2 95.6 11.1 91.1 100.7 10.2
47.0 106.8 83.3 14.2 103.7 87.5 13.2 100.5 92.0 12.2 97.3 96.8 11.3 94.0 101.8 10.4
49.0 110.2 84.5 14.5 106.9 88.7 13.4 103.6 93.2 12.4 100.3 98.0 11.5 97.0 103.0 10.6
51.0 113.6 85.8 14.7 110.2 90.0 13.7 106.8 94.5 12.7 103.4 99.2 11.7 100.0 104.2 10.8
53.0 117.0 87.1 15.0 113.6 91.3 13.9 110.1 95.7 12.9 106.6 100.5 11.9 103.1 105.5 11.0
55.0 120.5 88.5 15.2 117.0 92.7 14.1 113.4 97.1 13.1 109.8 101.9 12.1 106.2 106.9 11.2
75.0 80.0 85.0 90.0 95.0
18
QUANTECH
Page 19
FORM QCC3-EG1 (517)
Ratings (Cont'd)
MODEL: QCC3080CZE IPLV: 16.1 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
(°F)
35.0 66.0 81.4 9.0 63.1 85.5 8.2 60.1 89.9 7.5 57.1 94.4 6.8
37.0 68.3 82.1 9.2 65.3 86.3 8.4 62.2 90.6 7.7 59.1 95.2 7.0
39.0 70.7 82.9 9.5 67.6 87.0 8.6 64.4 91.4 7.9 61.1 96.0 7.1
41.0 73.0 83.7 9.7 69.8 87.8 8.9 66.6 92.2 8.1 63.2 96.8 7.3
43.0 75.5 84.5 9.9 72.2 88.6 9.1 68.8 93.0 8.3 65.4 97.6 7.5
45.0 78.0 85.3 10.2 74.5 89.5 9.3 71.1 93.8 8.5 48.5 60.2 8.7#
47.0 80.5 86.1 10.4 77.0 90.3 9.5 73.4 94.7 8.7 50.1 60.6 8.9#
49.0 83.1 87.0 10.6 79.4 91.2 9.7 75.8 95.5 8.9 51.8 61.1 9.2#
51.0 85.7 87.9 10.9 81.9 92.1 10.0 78.2 96.4 9.1 53.6 61.5 9.4#
53.0 88.3 88.9 11.1 84.5 93.0 10.2 80.6 97.3 9.3 55.4 62.0 9.7#
55.0 91.1 89.8 11.3 87.1 93.9 10.4 83.1 98.3 9.5 57.2 62.5 9.9#
MODEL: QCC3085CZE IPLV: 15.2 EER
SST
(°F)
35.0 68.4 90.7 8.4 65.4 95.5 7.7 62.3 100.5 7.0 50.3 83.1 6.7#
37.0 70.8 91.5 8.7 67.7 96.3 7.9 64.6 101.4 7.2 52.1 83.7 6.9#
39.0 73.2 92.3 8.9 70.1 97.2 8.1 66.8 102.2 7.4 54.0 84.3 7.1#
41.0 75.7 93.2 9.1 72.4 98.0 8.3 69.1 103.1 7.5 55.9 84.9 7.3#
43.0 78.3 94.1 9.3 74.9 98.9 8.5 71.4 104.0 7.7 57.9 85.5 7.5#
45.0 80.9 95.0 9.5 77.4 99.9 8.7 73.8 104.9 7.9 59.8 86.2 7.7#
47.0 83.5 96.0 9.8 79.9 100.8 8.9 76.3 105.9 8.1 52.3 67.3 8.5#
49.0 86.2 97.0 10.0 82.5 101.8 9.1 67.1 83.3 8.9# 54.1 67.8 8.7#
51.0 89.0 98.0 10.2 85.2 102.9 9.3 69.3 84.1 9.2# 55.9 68.3 8.9#
53.0 91.8 99.1 10.4 87.8 103.9 9.5 71.6 84.8 9.4# 57.8 68.8 9.2#
55.0 94.6 100.2 10.6 90.6 105.0 9.7 73.9 85.6 9.6# 59.7 69.3 9.4#
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
100.0 105.0 110.0 115.0
AIR TEMPERATURE ON - CONDENSER (°F)
100.0 105.0 110.0 115.0
MODEL: QCC3090CZE IPLV: 15.0 EER
SST
(°F)
35.0 73.9 100.6 8.3 70.6 105.9 7.5 67.3 111 . 5 6.8 55.3 94.7 6.5#
37.0 76.5 101.6 8.5 73.1 106.9 7.7 69.7 112.5 7.0 48.1 72.8 7.3#
39.0 79.1 102.6 8.7 75.7 107.9 7.9 72.1 113.5 7.2 49.8 73.3 7.5#
41.0 81.8 103.6 8.9 78.2 108.9 8.1 74.6 114.5 7.4 51.6 73.8 7.7#
43.0 84.6 104.6 9.1 80.9 110.0 8.3 77.1 115.6 7.6 53.4 74.3 7.9#
45.0 87.3 105.7 9.3 83.5 111.1 8.5 79.7 116.7 7.7 55.3 74.9 8.1#
47.0 90.2 106.9 9.5 86.3 112.2 8.7 71.3 94.7 8.4# 57.2 75.5 8.4#
49.0 93.0 108.1 9.7 89.0 113.4 8.9 62.0 72.4 9.4# 59.1 76.1 8.6#
51.0 96.0 109.3 9.9 91.8 114.6 9.1 64.0 73.0 9.6# 61.1 76.7 8.8#
53.0 98.9 110.6 10.1 94.7 115.9 9.3 66.1 73.7 9.9# 63.1 77.4 9.0#
55.0 101.9 111.9 10.3 97.6 117.2 9.4 68.2 74.4 10.1# 65.1 78.0 9.2#
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
100.0 105.0 110.0 115.0
QUANTECH
AIR TEMPERATURE ON - CONDENSER (°F)
19
Page 20
FORM QCC3-EG1 (517)
Ratings (Cont'd)
MODEL: QCC3100CYE IPLV: 15.8 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 93.7 71.1 13.9 91.1 74.7 12.9 88.4 78.7 11.9 85.6 83.1 11.0 82.8 87.7 10.2
37.0 97.0 71.8 14.2 94.3 75.5 13.2 91.6 79.5 12.3 88.7 83.8 11.3 85.8 88.4 10.5
39.0 100.5 72.6 14.6 97.7 76.3 13.6 94.8 80.3 12.6 91.9 84.6 11.7 88.9 89.2 10.7
41.0 104.0 73.5 14.9 101.1 77.1 13.9 98.2 81.1 12.9 95.1 85.4 12.0 92.0 90.0 11.0
43.0 107.6 74.3 15.3 104.6 78.0 14.3 101.5 81.9 13.2 98.4 86.2 12.3 95.2 90.8 11.3
45.0 111 . 2 75.3 15.6 108.1 78.9 14.6 105.0 82.8 13.6 101.8 87.1 12.6 98.5 91.7 11.6
47.0 114.9 76.2 16.0 111.7 79.8 14.9 108.5 83.7 13.9 105.2 88.0 12.9 101.7 92.6 11.9
49.0 118.6 77.3 16.3 115.4 80.8 15.2 112.0 84.7 14.2 108.6 89.0 13.2 105.1 93.6 12.2
51.0 122.5 78.3 16.6 119.1 81.8 15.6 115.7 85.7 14.5 112.1 90.0 13.4 108.5 94.6 12.4
53.0 126.4 79.4 16.9 122.9 82.9 15.9 119.4 86.8 14.8 115.7 91.1 13.7 112.0 95.7 12.7
55.0 130.4 80.6 17.3 126.8 84.0 16.2 123.1 87.9 15.1 119.3 92.2 14.0 115.5 96.7 13.0
MODEL: QCC3110CYE IPLV: 15.6 EER
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 106.7 85.4 13.4 103.7 89.9 12.4 100.6 94.8 11.5 97.4 100.1 10.6 94.1 105.7 9.8
37.0 110.5 86.3 13.8 107.3 90.9 12.8 104.1 95.7 11.8 100.8 101.0 10.9 97.4 106.6 10.0
39.0 114.3 87.3 14.1 111.1 91.9 13.1 107.8 96.7 12.1 104.3 102.0 11.2 100.9 107.6 10.3
41.0 118.3 88.4 14.4 114.9 92.9 13.4 111 . 5 97.8 12.4 108.0 103.1 11.5 104.4 108.7 10.5
43.0 122.3 89.5 14.7 118.8 94.0 13.7 115.2 98.9 12.7 111.6 104.1 11.7 107.9 109.8 10.8
45.0 126.3 90.6 15.1 122.7 95.1 14.0 119.1 100.0 13.0 115.3 105.3 12.0 111 . 5 110.9 11.1
47.0 130.4 91.8 15.4 126.8 96.3 14.3 123.0 101.2 13.3 119.1 106.4 12.3 115.2 112.1 11.3
49.0 134.6 93.1 15.7 130.9 97.5 14.6 126.9 102.4 13.5 123.0 107.7 12.5 118.9 113.3 11.6
51.0 138.9 94.4 16.0 135.0 98.8 14.9 131.0 103.7 13.8 126.9 109.0 12.8 122.7 114.6 11.8
53.0 143.3 95.7 16.2 139.2 100.2 15.2 135.1 105.1 14.1 130.9 110.3 13.0 126.6 115.9 12.1
55.0 147.7 97.1 16.5 143.5 101.6 15.4 139.2 106.4 14.3 134.9 111 . 7 13.3 130.5 117.2 12.3
75.0 80.0 85.0 90.0 95.0
AIR TEMPERATURE ON - CONDENSER (°F)
75.0 80.0 85.0 90.0 95.0
MODEL: QCC3130CZE IPLV: 14.7 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 126.6 107.8 12.9 122.9 113.4 11.9 119.1 119.2 11.1 115.2 125.6 10.2 111 . 2 132.3 9.4
37.0 131.0 109.2 13.2 127.1 114.7 12.2 123.2 120.6 11.3 119.2 127.0 10.4 115.0 133.7 9.6
39.0 135.4 110.6 13.5 131.4 116.2 12.5 127.4 122.1 11.6 123.2 128.4 10.7 119.0 135.1 9.8
41.0 139.9 112.0 13.7 135.8 117.6 12.8 131.6 123.5 11.8 127.3 129.9 10.9 122.9 136.6 10.1
43.0 144.5 113.5 14.0 140.2 119.2 13.0 135.9 125.1 12.1 131.5 131.5 11.1 127.0 138.1 10.3
45.0 149.1 115.1 14.3 144.7 120.7 13.3 140.2 126.8 12.3 135.7 133.0 11.4 131.1 139.7 10.5
47.0 153.8 116.7 14.6 149.2 122.4 13.5 144.6 128.4 12.5 140.0 134.7 11.6 135.2 141.4 10.7
49.0 158.5 118.4 14.8 153.8 124.0 13.8 149.0 130.1 12.8 144.3 136.4 11.8 139.4 143.1 10.9
51.0 163.3 120.1 15.1 158.5 125.8 14.0 153.5 131.9 13.0 148.6 138.2 12.0 143.6 144.8 11.1
53.0 168.2 121.9 15.3 163.2 127.6 14.2 158.1 133.7 13.2 153.0 140.0 12.2 147.9 146.7 11.3
55.0 173.1 123.7 15.5 167.9 129.5 14.4 162.7 135.5 13.4 157.5 141.9 12.4 152.3 148.5 11.5
75.0 80.0 85.0 90.0 95.0
20
QUANTECH
Page 21
FORM QCC3-EG1 (517)
Ratings (Cont'd)
MODEL: QCC3100CYE IPLV: 15.8 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
(°F)
35.0 79.5 92.3 9.3 76.1 97.3 8.5 72.7 102.4 7.8 69.2 107.8 7.0
37.0 82.4 93.1 9.6 78.9 98.0 8.8 75.4 103.1 8.0 71.8 108.6 7.3
39.0 85.3 93.9 9.9 81.8 98.7 9.0 78.1 103.9 8.2 74.4 109.4 7.5
41.0 88.4 94.7 10.1 84.7 99.5 9.3 80.9 104.7 8.5 77.1 110.2 7.7
43.0 91.4 95.5 10.4 87.6 100.4 9.5 83.7 105.5 8.7 79.8 111 . 0 7.9
45.0 94.5 96.4 10.7 90.6 101.2 9.8 86.6 106.4 8.9 82.6 111 . 8 8.1
47.0 97.7 97.3 10.9 93.7 102.1 10.0 89.6 107.3 9.2 85.4 112.7 8.3
49.0 101.0 98.2 11.2 96.8 103.1 10.3 92.5 108.2 9.4 88.2 113.7 8.6
51.0 104.2 99.2 11.4 99.9 104.0 10.5 95.6 109.2 9.6 91.2 114.6 8.8
53.0 107.6 100.2 11.7 103.2 105.0 10.8 98.7 110.2 9.8 94.1 115.6 9.0
55.0 111. 0 101.3 12.0 106.4 106.1 11.0 101.8 111 . 2 10.1 97.1 116.7 9.2
MODEL: QCC3110CYE IPLV: 15.6 EER
SST
(°F)
35.0 90.2 111.3 8.9 86.3 117.1 8.1 82.4 123.3 7.4 69.5 107.8 7.1#
37.0 93.5 112.2 9.2 89.4 118.1 8.4 85.4 124.3 7.6 72.1 108.5 7.3#
39.0 96.8 113.2 9.4 92.6 119.1 8.6 88.4 125.3 7.8 74.7 109.3 7.5#
41.0 100.1 114.3 9.7 95.8 120.2 8.8 91.5 126.3 8.0 53.3 68.9 8.1@
43.0 103.5 115.4 9.9 99.1 121.2 9.1 94.6 127.4 8.3 55.2 69.3 8.3@
45.0 107.0 116.5 10.1 102.5 122.4 9.3 97.9 128.6 8.5 57.2 69.7 8.6@
47.0 110.6 117.6 10.4 105.9 123.5 9.5 89.9 107.2 9.2# 59.2 70.2 8.9@
49.0 114.2 118.9 10.6 109.3 124.7 9.7 92.9 108.2 9.4# 61.3 70.7 9.1@
51.0 117.8 120.1 10.9 112.8 126.0 10.0 95.9 109.1 9.7# 63.4 71.2 9.4@
53.0 121.5 121.4 11.1 116.4 127.3 10.2 68.6 68.2 10.5@ 65.5 71.7 9.6@
55.0 125.3 122.8 11.3 120.0 128.6 10.4 70.8 68.8 10.8@ 67.7 72.3 9.9@
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
100.0 105.0 110.0 115.0
AIR TEMPERATURE ON - CONDENSER (°F)
100.0 105.0 110.0 115.0
MODEL: QCC3130CZE IPLV: 14.7 EER
SST
(°F)
35.0 106.5 138.8 8.6 101.7 145.8 7.8 96.9 153.0 7.1 92.0 160.6 6.5
37.0 110.2 140.2 8.8 105.3 147.2 8.0 100.3 154.4 7.3 95.3 162.0 6.6
39.0 114.0 141.7 9.0 108.9 148.6 8.2 103.8 155.9 7.5 55.0 71.8 8.1#
41.0 117.8 143.2 9.2 112.6 150.1 8.4 107.3 157.4 7.7 57.0 72.3 8.3#
43.0 121.7 144.7 9.4 116.3 151.7 8.6 110.9 158.9 7.9 59.1 72.8 8.6#
45.0 125.6 146.3 9.6 120.1 153.3 8.8 114.5 160.5 8.1 61.2 73.3 8.8#
47.0 129.6 148.0 9.8 123.9 154.9 9.0 118.2 162.2 8.2 63.3 73.8 9.1#
49.0 133.6 149.7 10.0 127.8 156.6 9.2 121.9 163.9 8.4 65.4 74.4 9.3#
51.0 137.7 151.5 10.2 131.7 158.4 9.4 70.8 71.4 10.4# 67.6 75.0 9.5#
53.0 141.8 153.3 10.4 135.6 160.2 9.6 73.1 72.0 10.7# 69.9 75.6 9.8#
55.0 146.0 155.1 10.6 139.6 162.1 9.7 75.5 72.7 10.9# 72.1 76.2 10.0#
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
100.0 105.0 110.0 115.0
QUANTECH
AIR TEMPERATURE ON - CONDENSER (°F)
21
Page 22
FORM QCC3-EG1 (517)
Ratings (Cont'd)
MODEL: QCC3145CZE IPLV: 15.2 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 139.7 115.4 13.0 135.6 121.3 12.1 131.5 127.6 11.2 127.2 134.5 10.3 122.9 141.6 9.5
37.0 144.6 116.8 13.3 140.4 122.7 12.4 136.1 129.0 11.5 131.7 135.8 10.6 127.2 143.0 9.8
39.0 149.5 118.2 13.6 145.2 124.2 12.7 140.7 130.5 11.7 136.2 137.3 10.8 131.6 144.5 10.0
41.0 154.6 119.7 13.9 150.1 125.7 12.9 145.5 132.1 12.0 140.9 138.8 11.1 136.1 146.0 10.2
43.0 159.7 121.3 14.2 155.1 127.2 13.2 150.3 133.6 12.3 145.6 140.3 11.4 140.7 147.5 10.5
45.0 164.9 122.9 14.5 160.1 128.9 13.5 155.2 135.3 12.5 150.3 142.1 11.6 145.3 149.1 10.7
47.0 170.2 124.6 14.8 165.3 130.6 13.8 160.2 136.9 12.8 155.1 143.7 11.8 150.0 150.8 11.0
49.0 175.6 126.4 15.1 170.5 132.3 14.0 165.3 138.7 13.0 160.0 145.4 12.1 154.8 152.6 11.2
51.0 181.1 128.2 15.3 175.8 134.2 14.3 170.4 140.5 13.3 165.0 147.2 12.3 159.6 154.4 11.4
53.0 186.6 130.1 15.6 181.1 136.0 14.5 175.6 142.4 13.5 170.1 149.1 12.6 164.5 156.2 11.6
55.0 192.2 132.1 15.8 186.5 138.0 14.8 180.9 144.3 13.8 175.2 151.1 12.8 169.4 158.2 11.8
MODEL: QCC3160CZE IPLV: 15.2 EER
SST
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
(°F)
35.0 152.5 131.2 12.7 148.0 138.0 11.7 143.5 145.2 10.9 138.8 152.9 10.0 134.0 161.1 9.2
37.0 157.8 132.8 12.9 153.2 139.6 12.0 148.5 146.8 11.1 143.7 154.5 10.3 138.7 162.7 9.5
39.0 163.2 134.5 13.2 158.4 141.3 12.3 153.6 148.5 11.4 148.6 156.2 10.5 143.5 164.4 9.7
41.0 168.7 136.2 13.5 163.8 143.0 12.6 158.7 150.3 11.6 153.6 158.0 10.8 148.4 166.2 9.9
43.0 174.3 137.9 13.8 169.2 144.8 12.8 163.9 152.1 11.9 158.7 159.8 11.0 153.3 168.0 10.1
45.0 179.9 139.8 14.1 174.6 146.6 13.1 169.3 154.0 12.1 163.8 161.7 11.2 158.3 169.9 10.4
47.0 185.6 141.7 14.4 180.2 148.6 13.3 174.6 155.9 12.4 169.0 163.7 11.5 163.3 171.8 10.6
49.0 191.4 143.7 14.6 185.8 150.6 13.6 180.1 157.9 12.6 174.3 165.7 11.7 168.5 173.8 10.8
51.0 197.3 145.8 14.9 191.5 152.6 13.8 185.6 160.0 12.8 179.7 167.7 11.9 173.6 175.9 11.0
53.0 203.3 147.9 15.1 197.3 154.7 14.1 191.2 162.1 13.1 185.1 169.9 12.1 178.9 178.0 11.2
55.0 209.3 150.1 15.4 203.1 157.0 14.3 196.9 164.3 13.3 190.6 172.1 12.3 184.2 180.2 11.4
75.0 80.0 85.0 90.0 95.0
AIR TEMPERATURE ON - CONDENSER (°F)
75.0 80.0 85.0 90.0 95.0
22
QUANTECH
Page 23
FORM QCC3-EG1 (517)
Ratings (Cont'd)
MODEL: QCC3145CZE IPLV: 15.2 EER
AIR TEMPERATURE ON - CONDENSER (°F)
SST
(°F)
35.0 117.8 148.7 8.7 112.6 156.3 8.0 107.3 164.2 7.3 83.7 125.3 7.2#
37.0 122.0 150.1 8.9 116.6 157.7 8.2 111 . 2 165.6 7.5 86.8 126.2 7.5#
39.0 126.2 151.6 9.2 120.7 159.1 8.4 115.1 167.0 7.7 90.0 127.1 7.7#
41.0 130.5 153.1 9.4 124.8 160.6 8.6 119.1 168.5 7.9 93.2 128.0 7.9#
43.0 134.9 154.7 9.6 129.0 162.2 8.8 101.2 122.7 8.9# 96.5 128.9 8.1#
45.0 139.3 156.3 9.9 133.3 163.8 9.0 104.7 123.7 9.2# 99.8 129.9 8.4#
47.0 143.8 158.0 10.1 137.6 165.5 9.2 108.3 124.7 9.4# 103.2 131.0 8.6#
49.0 148.4 159.7 10.3 142.0 167.2 9.4 111 . 9 125.8 9.6# 106.7 132.0 8.8#
51.0 153.1 161.5 10.5 146.5 169.0 9.6 115.5 126.9 9.9# 110.2 133.1 9.0#
53.0 157.8 163.3 10.7 151.0 170.8 9.8 119.3 128.1 10.1# 113.8 134.3 9.2#
55.0 162.5 165.3 10.9 128.6 123.4 11.3# 123.1 129.3 10.3# 117.4 135.5 9.5#
MODEL: QCC3160CZE IPLV: 15.2 EER
SST
(°F)
35.0 128.4 169.2 8.4 122.7 177.7 7.7 116.9 186.6 7.0 93.0 148.5 6.9#
37.0 132.9 170.8 8.7 127.0 179.3 7.9 121.0 188.2 7.2 96.4 149.7 7.1#
39.0 137.5 172.5 8.9 131.4 181.0 8.1 125.3 189.9 7.4 99.9 150.8 7.3#
41.0 142.2 174.3 9.1 135.9 182.8 8.3 129.6 191.7 7.6 103.5 152.0 7.5#
43.0 146.9 176.1 9.3 140.5 184.6 8.5 112.4 145.9 8.5# 107.1 153.2 7.7#
45.0 151.7 178.0 9.5 145.1 186.5 8.7 116.2 147.2 8.7# 110.7 154.5 7.9#
47.0 156.6 179.9 9.7 149.7 188.4 8.9 120.1 148.5 8.9# 114.4 155.8 8.1#
49.0 161.5 181.9 9.9 154.5 190.4 9.1 124.0 149.9 9.1# 118.2 157.1 8.3#
51.0 166.5 184.0 10.1 159.3 192.5 9.3 128.0 151.3 9.3# 122.0 158.5 8.5#
53.0 171.5 186.1 10.3 164.1 194.6 9.5 132.1 152.7 9.5# 125.9 160.0 8.7#
55.0 176.6 188.3 10.5 142.5 147.3 10.6# 136.2 154.2 9.7# 129.8 161.5 8.9#
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
100.0 105.0 110.0 115.0
AIR TEMPERATURE ON - CONDENSER (°F)
100.0 105.0 110.0 115.0
QUANTECH
23
Page 24
FORM QCC3-EG1 (517)
Part Load Ratings
QCC3080CZE
% FULL
LOAD DISPL.
100.0 97.0 72.2 80.0 14.7
83.3 82.4 59.2 80.0 15.0
66.7 67.9 44.4 80.0 15.9
50.0 50.8 32.9 80.0 16.1
33.3 33.7 21.4 80.0 16.3
16.7 16.9 10.7 80.0 16.3
% FULL
LOAD DISPL.
100.0 100.6 80.0 80.0 13.9
83.6 86.4 67.0 80.0 14.1
66.7 70.5 49.0 80.0 15.2
50.3 53.9 37.3 80.0 15.3
33.3 35.1 23.7 80.0 15.6
16.9 18.6 12.8 80.0 15.4
% FULL
LOAD DISPL.
100.0 108.6 89.3 80.0 13.6
83.6 92.7 73.6 80.0 13.9
49.3 56.0 38.8 80.0 15.3
32.8 37.2 25.3 80.0 15.6
16.4 18.6 12.7 80.0 15.6
% FULL
LOAD DISPL.
100.0 117.3 81.3 80.0 15.4
83.8 99.8 66.8 80.0 15.6
50.0 60.9 37.2 80.0 15.5
16.2 18.6 12.0 80.0 16.3
TONS KW
IPLV: 16.1 EER
QCC3085CZE
TONS KW
IPLV: 15.2 EER
QCC3090CZE
TONS KW
IPLV: 15.0 EER
QCC3100CYE
TONS KW
IPLV: 15.8 EER
AMBIENT
°F
AMBIENT
°F
AMBIENT
°F
AMBIENT
°F
EER
EER
EER
EER
QCC3110CYE
% FULL LOAD
DISPL.
100.0 132.9 98.2 80.0 14.7
86.1 117.1 82.5 80.0 15.2
57.0 79.0 50.7 80.0 15.6
43.0 58.3 39.7 80.0 15.6
13.9 18.5 12.3 80.0 15.8
% FULL LOAD
DISPL.
100.0 156.2 124.9 80.0 13.9
75.0 120.1 89.0 80.0 14.6
50.0 84.1 53.0 80.0 16.0
25.0 36.6 32.7 80.0 12.8
% FULL LOAD
DISPL.
100.0 173.1 133.2 80.0 14.2
77.7 140.3 95.9 80.0 15.4
67.0 121.7 82.1 80.0 15.3
44.7 79.9 54.8 80.0 15.6
22.3 39.4 27.3 80.0 15.4
% FULL LOAD
DISPL.
100.0 188.7 151.6 80.0 13.7
80.0 156.4 112.9 80.0 14.9
60.0 118.9 81.4 80.0 15.0
40.0 77.9 54.2 80.0 15.3
20.0 38.7 27.1 80.0 15.2
TONS KW
IPLV: 15.6 EER
QCC3130CZE
TONS KW
IPLV: 14.7 EER
QCC3145CZE
TONS KW
IPLV: 15.2 EER
QCC3160CZE
TONS KW
IPLV: 15.2 EER
AMBIENT
°F
AMBIENT
°F
AMBIENT
°F
AMBIENT
°F
EER
EER
EER
EER
24
QUANTECH
Page 25
FORM QCC3-EG1 (517)
Physical Data
MODEL NUMBER QCC3
REFRIGERANT R-410A
080CZE 085CZE 090CZE 100CYE 110CYE 130CZE 145CZE 160CZE
GENERAL UNIT DATA
Length 116.1 116.1 116.1 142.7 142.7 142.7 187.7 187.7
Width 88.0 88.0 88.0 88.0 88.0 88.0 88.0 88.0
Height 94.2 94.2 94.2 94.2 94.2 94.2 94.2 94.2
REFRIGERANT
Number of Refrigerant Circuits 2 2 2 2 2 2 2 2
Refrigerant Charge Circuit 1 (lbs) 54 56 56 78 56 81 81 108
Refrigerant Charge Circuit 2 (lbs) 49 49 51 73 98 76 76 96
Oil Charge, ckt1 / ckt2, gallons 2.6 / 2.6 3.3 / 2.6 3.3 / 2.8 2.8 / 2.8 3.3/3.3 3.3/3.3 5.0 / 2.8 5.0 / 3.3
UNIT WEIGHTS
Shipping Weight (lbs.) 3713 3989 4185 4911 5146 5221 6473 6628
Compressors, scroll type
Compressors per circuit 3/3 3/3 3/2 2/2 3/2 2/2 3/2 3/2
Compressors per unit 6 6 5 4 5 4 5 5
NOMINAL TONS PER COMPRESSOR
Circuit 1 13 15 15 15/32 15 32 32 32
Circuit 2 13 13 15/32 15/32 32 32 15/32 32
CONDENSER
Total Face Area ft
Number of Rows 3 3 3 3 3 3 3 3
Fins per Inch 17 17 17 17 17 17 17 17
CONDENSER FANS, LOW SOUND
Number of Fans, ckt1./ckt2. 2/2 2/2 2/2 3/3 2/4 3/3 4/4 4/4
Fan hp 2 2 2 2 2 2 2 2
Fan RPM 1160 1160 1160 1160 1160 1160 1160 1160
Total Chiller CFM 62400 62400 62400 93600 93600 93600 124800 124800
2
106.9 106.9 106.9 160.3 160.3 160.3 213.8 213.8
STANDARD EFFICIENCY UNITS
QUANTECH
25
Page 26
FORM QCC3-EG1 (517)
Dimension Drawings
LENGTH WIDTH HEIGHT
QCC3
L W H
080CZE 116.1 88.3 95.3 89.7 43.9 2-5/8 1-1/8 39.6 17.0 17.0 84.4 085CZE 116.1 88.3 95.3 89.7 43.9 2-5/8 1-1/8 39.6 17.0 17.0 84.4 090CZE 116.1 88.3 95.3 89.7 43.9 2-5/8 1-1/8 39.6 17.0 17.0 84.4
ISOLATOR LOCATION
QCC3 D1 D2
I1 I2 R1 R2 R3 R4
080CZE 31.6 35.5 19.5 76.6 1.3 85.5 23.2 68.3 085CZE 31.6 35.5 19.5 76.6 1.3 85.5 23.2 68.3 090CZE 31.6 35.5 18.5 76.6 1.3 85.5 23.2 68.3
26
F P
DIMENSIONS
SUCTION
CONNECTION SIZES
(OD)
LIQUID
IN 1/2
OUT 1/2
A B
SYSTEM 1
DIMENSIONS
SUCTION INLIQUID
OUT
RIGGING HOLE LOCATIONS
LD19670
SYSTEM 2
DIMENSIONS
SUCTION INLIQUID
OUT
QUANTECH
Page 27
L2-OUT
S2-IN
Dimension Drawings (Cont'd)
FORM QCC3-EG1 (517)
LENGTH WIDTH HEIGHT
QCC3
L W H
100CYE 142.0 88.3 95.3 89.7 43.9 2-5/8 1-1/8 41.0 26.9 26.9 84.4 110CYE 143.5 88.3 95.3 89.7 43.9 2-5/8 1-1/8 41.0 -17.1 26.9 84.4 130CZE 143.5 88.3 95.3 89.7 43.9 2-5/8 1-1/8 41.0 26.9 26.9 84.4
QCC3 D1 D2
100CYE 31.6 35.5 7.6 117.2 1.4 85.5 23.2 95.9 110CYE 31.6 35.5 7.6 117.2 1.4 85.5 23.2 95.9 130CZE 31.6 35.5 7.6 117.2 1.4 85.5 23.2 95.9
QUANTECH
LD19671
CONNECTION
F P
ISOLATOR LOCATION
DIMENSIONS
I1 I2 R1 R2 R3 R4
SUCTION
IN 1/2
SIZES (OD)
LIQUID
OUT 1/2
A B
SYSTEM 1
DIMENSIONS
SUCTION INLIQUID
OUT
RIGGING HOLE LOCATIONS
SYSTEM 2
DIMENSIONS
SUCTION INLIQUID
OUT
27
Page 28
FORM QCC3-EG1 (517)
Dimension Drawings (Cont'd)
LENGTH WIDTH HEIGHT
QCC3
L W H
145CZE 187.5 88.3 95.3 89.7 43.9
160CZE 187.5 88.3 95.3 89.7 43.9
ISOLATOR LOCATION
QCC3 D1 D2
I1 I2 I3 R1 R2 R3 R4
145CZE 31.6 35.5 7.6 69.0 80 1.4 85.5 39.0 66.0 58.0 160CZE 31.6 35.5 7.6 69.0 80 1.4 85.5 39.0 66.0 58.0
28
F P
DIMENSIONS
CONNECTION
SIZES (OD)
SUCTION
IN 1/2
3-1/8 /
2-5/8
3-1/8 /
2-5/8
LIQUID
OUT 1/2
1-3/8 /
1-1/8
1-3/8 /
1-1/8
A B
LD19672
SYSTEM 1
DIMENSIONS
SUCTION INLIQUID
OUT
41.4 26.5 111. 3 44.7
41.4 26.5 111. 3 44.7
RIGGING HOLE LOCATIONS
SYSTEM 2
DIMENSIONS
SUCTION INLIQUID
QUANTECH
OUT
Page 29
EQUIPMENT
LD18443
Isolators
FORM QCC3-EG1 (517)
CP
BASE
(BY OTHERS)
POSITIONING
PIN
MOUNT
TYPE
W D L B C T H
DIMENSION DATA (INCHES)
CP-1 3 5/8 7-3/4 6-1/2 4-3/4 1/2 5-5/8
CP-2 3 5/8 10-1/2 9-1/4 7-3/4 9/16 6
RATED CAPACITY
MODEL NUMBER COLOR CODE
(FOR UNITS WITH ALL LOAD POINTS
LESS THAN 1785 LBS (810 KG)
(LBS.) (KG)
CP-1D-510 BLACK Up thru 434 Up thru 197
CP-1D-900 DARK GREEN 435 thru 765 198 thru 347
CP-1D-1200 GRAY 766 thru 1020 348 thru 463
CP-1D-1360 WHITE 1021 thru 1156 464 thru 524
CP-1D-1785N GRAY/RED 1157 thru 1785 525 thru 810
RATED CAPACITY
(FOR UNITS WITH ANY LOAD POINT
MODEL NUMBER COLOR CODE
ABOVE 1518 LBS (689 KG)
(LBS.) (KG)
C2P-1D-1350 DARK PURPLE Up thru 1148 Up to 521 C2P-1D-1350 DARK PURPLE Up thru 1148 Up to 521 C2P-1D-1800 DARK GREEN 1149 thru 1530 522 - 694 C2P-1D-2400 GRAY 1531 thru 2040 695 - 925 C2P-1D-2400 GRAY 1531 thru 2040 695 - 925 C2P-1D-2720 WHITE 2041 thru 2312 926 - 1049
C2P-1D-3570N GRAY/RED 2313 thru 3570 1050 - 1619
QUANTECH
29
Page 30
FORM QCC3-EG1 (517)
LD17304
CD
CD
HF
HF
BT
BT
AL
L
AL
L
W
W
DW
DW
MOLDED
DURULENE
MOLDED
DURULENE
R = 0.280 Slot
Typ 2 Places
Ø = AD Thru Typ 2 Places
Islators (Cont'd)
RD-STYLE
ISOLATORS
MOUNT
TYPE
L W HF AL AD BT CD DW
RD1-WR 3.13 1.75 1.25 2.38 0.34 0.19
RD2-WR 3.88 2.38 1.75 3.00 0.34 0.22
RD3-WR 5.50 3.38 2.88 4.13 0.56 0.25
RD4-WR 6.25 4.63 2.75 5.00 0.56 0.38
VMC PART NUMBER
VMC ISOLator
DIMENSION DATA (INCHES)
WEIGHT RANGE
COLOR
(LBS)
5/16-18 UNC
X 3/4
3/8-16 UNC
X 1
1/2-13 UNC
X 1
1/2-13 UNC
X 1
WEIGHT RANGE
1.25
1.75
2.50
3.00
(KGS)
RD-3-CHARCOAL-WR CHARCOAL Up thru 825 UP TO 374
RD-4-BRICK RED-WR BRICK RED 826 thru 1688 375 - 766
RD-4-CHARCOAL-WR CHARCOAL 1689 thru 4000 767 - 1814
30
QUANTECH
Page 31
3/4”
7/8”
3/8” GAP
3/4”
TYP. (4)
5/8”
2-3/4”
1-1/8”
2-3/4”
8
P
4
8
STOP &
8-3/8” OPER. HEIGHT
4
4
LD18442
Isolators (Cont'd)
FORM QCC3-EG1 (517)
Y2RS
VMC PART NUMBER VMC ISOL. COLOR
Y2RSI-2D-460 GREEN Up thru 391 UP TO 177
Y2RSI-2D-460 GREEN Up thru 391 UP TO 177
Y2RSI-2D-710 DARK BROWN 392 thru 604 178 - 274
Y2RSI-2D-870 RED 605 thru 740 275 - 336
Y2RSI-2D-1200N RED/BLACK 741 thru 1020 337 - 463
Y2RSI-2D-1690 PINK 1021 thru 1437 464 - 652
Y2RSI-2D-2640N PINK/GRAY 1438 thru 2244 653 - 1018
Y2RSI-2D-2870N
Y2RSI-2D-3280N
PINK/GRAY/
PINK/GRAY/
ORANGE
DK.BROWN
WEIGHT RANGE
(LBS)
WEIGHT RANGE
(KGS)
2245 thru 2618 1019 - 1188
2619 thru 3740 1189 - 1696
QUANTECH
31
Page 32
FORM QCC3-EG1 (517)
B
I, I5
TYP
I2, I6
TYP
A
LD19673
AVM LOCATIONS
QCC3 I1 I2 A B
080CZE 19.5 76.6 1.36 85.5
085CZE 19.5 76.6 1.36 85.5
090CZE 19.5 76.6 1.36 85.5
B
I1
TYP TYP
QCC3
I1 I2 A B
100CYE 7.6 117.2 1.4 85.5
110CYE 7.6 117.2 1.4 85.5
130CZE 7.6 117.2 1.4 85.5
32
I2
AVM LOCATIONS
A
LD19674
QUANTECH
Page 33
FORM QCC3-EG1 (517)
TYP
B
I, I5
I2, I6
TYP
QCC3
145CZE 7.6 69.0 80.0 1.4 85.5
160CZE 7.6 69.0 80.0 1.4 85.5
I1 I2 I3 A B
AVM LOCATIONS
I3, I7
TYP
LD19675
A
QUANTECH
33
Page 34
FORM QCC3-EG1 (517)
Electrical Data
QCC3 VOLT HZ
200 60 351 400 400 400
230 60 350 400 400 400
080CZE
085CZE
090CZE
100CYE
110CYE
130CZE
145CZE
160CZE
380 60 186 250 200 200
460 60 160 200 175 175
575 60 136 200 150 150
200 60 366 600 400 400
230 60 365 600 400 400
380 60 216 250 225 250
460 60 173 200 200 200
575 60 148 200 175 175
200 60 391 600 450 500
230 60 390 600 450 450
380 60 249 400 300 300
460 60 192 250 225 225
575 60 168 200 200 200
200 60 404 600 450 500
230 60 403 600 450 500
380 60 255 400 300 300
460 60 200 250 225 250
575 60 176 200 200 225
200 60 460 600 500 500
230 60 458 600 500 500
380 60 291 400 350 350
460 60 227 250 250 250
575 60 200 250 225 225
200 60 511 600 600 600
230 60 510 600 600 600
380 60 321 400 350 350
460 60 256 400 300 300
575 60 227 250 250 250
200 60 582 800 700 700
230 60 581 800 700 700
380 60 366 600 400 400
460 60 291 400 350 350
575 60 257 400 300 300
200 60 636 800 700 700
230 60 635 800 700 700
380 60 399 600 450 450
460 60 318 400 350 350
575 60 283 400 300 300
MINIMUM
CIRCUIT
AMPS
MIN N/F
DISC SW
MIN DUAL
ELEMENT FUSE
& MIN CB
MAX DUAL
ELEMENT FUSE
& MAX CB
34
QUANTECH
Page 35
Electrical Data (Cont'd)
SYSTEM # 1 SYSTEM # 2
QCC3
080CZE
085CZE
090CZE
100CYE
110CYE
130CZE
145CZE
160CZE
COMPR 1 COMPR 2 COMPR 3 COND FANS COMPR 1 COMPR 2 COMPR 3 COND FANS
RLA LRA RLA LRA RLA LRA QTY FLA LRA RLA LRA RLA LRA RLA LRA QTY FLA LRA
51.3 300 51.3 300 51.3 300 2 7.6 30.9 51.3 300 51.3 300 51.3 300 2 7.6 30.9
51.3 300 51.3 300 51.3 300 2 7.4 37.0 51.3 300 51.3 300 51.3 300 2 7.4 37.0
26.9 139 26.9 139 26.9 139 2 4.5 22.3 26.9 139 26.9 139 26.9 139 2 4.5 22.3
23.1 150 23.1 150 23.1 150 2 4.0 19.0 23.1 150 23.1 150 23.1 150 2 4.0 19.0
19.9 109 19.9 109 19.9 109 2 2.9 14.6 19.9 109 19.9 109 19.9 109 2 2.9 14.6
55.8 425 55.8 425 55.8 425 2 7.6 30.9 51.3 300 51.3 300 51.3 300 2 7.6 30.9
55.8 425 55.8 425 55.8 425 2 7.4 37.0 51.3 300 51.3 300 51.3 300 2 7.4 37.0
36.0 239 36.0 239 36.0 239 2 4.5 22.3 26.9 139 26.9 139 26.9 139 2 4.5 22.3
26.9 187 26.9 187 26.9 187 2 4.0 19.0 23.1 150 23.1 150 23.1 150 2 4.0 19.0
23.7 148 23.7 148 23.7 148 2 2.9 14.6 19.9 109 19.9 109 19.9 109 2 2.9 14.6
55.8 425 55.8 425 55.8 425 2 7.6 30.9 109.6 599 55.8 425 2 7.6 30.9
55.8 425 55.8 425 55.8 425 2 7.4 37.0 109.6 599 55.8 425 2 7.4 37.0
36.0 239 36.0 239 36.0 239 2 4.5 22.3 69.2 358 36.0 239 2 4.5 22.3
26.9 187 26.9 187 26.9 187 2 4.0 19.0 54.5 310 26.9 187 2 4.0 19.0
23.7 148 23.7 148 23.7 148 2 2.9 14.6 49.4 239 23.7 148 2 2.9 14.6
109.6 599 55.8 425 3 7.6 30.9 109.6 599 55.8 425 3 7.6 30.9
109.6 599 55.8 425 3 7.4 37.0 109.6 599 55.8 425 3 7.4 37.0
69.2 358 36.0 239 3 4.5 22.3 69.2 358 36.0 239 3 4.5 22.3
54.5 310 26.9 187 3 4.0 19.0 54.5 310 26.9 187 3 4.0 19.0
49.4 239 23.7 148 3 2.9 14.6 49.4 239 23.7 148 3 2.9 14.6
55.8 425 55.8 425 55.8 425 2 7.6 30.9 109.6 599 109.6 599 4 7.6 30.9
55.8 425 55.8 425 55.8 425 2 7.4 37.0 109.6 599 109.6 599 4 7.4 37.0
36.0 239 36.0 239 36.0 239 2 4.5 22.3 69.2 358 69.2 358 4 4.5 22.3
26.9 187 26.9 187 26.9 187 2 4.0 19.0 54.5 310 54.5 310 4 4.0 19.0
23.7 148 23.7 148 23.7 148 2 2.9 14.6 49.4 239 49.4 239 4 2.9 14.6
109.6 599 109.6 599 3 7.6 30.9 109.6 599 109.6 599 3 7.6 30.9
109.6 599 109.6 599 3 7.4 37.0 109.6 599 109.6 599 3 7.4 37.0
69.2 358 69.2 358 3 4.5 22.3 69.2 358 69.2 358 3 4.5 22.3
54.5 310 54.5 310 3 4.0 19.0 54.5 310 54.5 310 3 4.0 19.0
49.4 239 49.4 239 3 2.9 14.6 49.4 239 49.4 239 3 2.9 14.6
109.6 599 109.6 599 109.6 599 4 7.6 30.9 109.6 599 55.8 425 4 7.6 30.9
109.6 599 109.6 599 109.6 599 4 7.4 37.0 109.6 599 55.8 425 4 7.4 37.0
69.2 358 69.2 358 69.2 358 4 4.5 22.3 69.2 358 36.0 239 4 4.5 22.3
54.5 310 54.5 310 54.5 310 4 4.0 19.0 54.5 310 26.9 187 4 4.0 19.0
49.4 239 49.4 239 49.4 239 4 2.9 14.6 49.4 239 23.7 148 4 2.9 14.6
109.6 599 109.6 599 109.6 599 4 7.6 30.9 109.6 599 109.6 599 4 7.6 30.9
109.6 599 109.6 599 109.6 599 4 7.4 37.0 109.6 599 109.6 599 4 7.4 37.0
69.2 358 69.2 358 69.2 358 4 4.5 22.3 69.2 358 69.2 358 4 4.5 22.3
54.5 310 54.5 310 54.5 310 4 4.0 19.0 54.5 310 54.5 310 4 4.0 19.0
49.4 239 49.4 239 49.4 239 4 2.9 14.6 49.4 239 49.4 239 4 2.9 14.6
FORM QCC3-EG1 (517)
QUANTECH
35
Page 36
FORM QCC3-EG1 (517)
Electrical Data (Cont'd)
QCC3 VOLT HZ MCA
200 60 351 500 MCM 428 (2) 4/0 AWG (2) #6 - 500 kcmil
080CZE
230 60 350 500 MCM 427 (2) 4/0 AWG (2) #6 - 500 kcmil
380 60 186 3/0 AWG 227 4/0 AWG (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
460 60 160 2/0 AWG 196 3/0 AWG (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
575 60 136 1/0 AWG 166 2/0 AWG (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
200 60 366 500 MCM 446 (2) 4/0 AWG (2) #6 - 500 kcmil
230 60 365 500 MCM 445 (2) 4/0 AWG (2) #6 - 500 kcmil
085CZE
380 60 216 4/0 AWG 263 300 MCM (1) #4 - 500 kcmil
460 60 173 2/0 AWG 211 4/0 AWG (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
575 60 148 1/0 AWG 181 3/0 AWG (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
200 60 391 600 MCM 476
230 60 390 600 MCM 475
090CZE
380 60 249 250 MCM 303 350 MCM (1) #4 - 500 kcmil
460 60 192 3/0 AWG 234 250 MCM (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
575 60 168 2/0 AWG 205 4/0 AWG (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
200 60 404 (2) 4/0 AWG 492
230 60 403 (2) 4/0 AWG 491
100CYE
380 60 255 250 MCM 311 400 MCM (1) #4 - 500 kcmil
460 60 200 4/0 AWG 244 250 MCM (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
575 60 176 3/0 AWG 215 4/0 AWG (1) #4 - 500 kcmil (1) #6 - 350 kcmil (1) #6 - 350 kcmil
MIN REQ.
WIRE
GAUGE,
75˚C, CU
MCA
MIN REQ.
WIRE
GAUGE
75˚C, CU
(2) 250
MCM
(2) 250
MCM
(2) 250
MCM
(2) 250
MCM
TERMINAL
BLOCK
LUGS
(2) #6 - 500 kcmil
(2) #6 - 500 kcmil
(2) #6 - 500 kcmil
(2) #6 - 500 kcmil
NON-FUSED
DISCONNECT
SWITCH
LUGS
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
"250 - 500kcmil &
(2)3/0-250kcmil"
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
250 - 500kcmil &
(2)3/0 -250kcmil
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
(2)250 - 500kcmil
& (3)2/0 -
400kcmil
250 - 500kcmil &
(2)3/0 -250kcmil
CIRCUIT
BREAKER
LUGS
(2)250 - 500kcmil
& (3)2/0 -
400kcmil"
(2)250 - 500kcmil
& (3)2/0 ­400kcmil
(2)250 - 500kcmil
&(3)2/0 - 400kcmil
(2)250 - 500kcmil
&(3)2/0 - 400kcmil
"250 - 500kcmil &
(2)3/0- 250kcmil"
(2)250 - 500kcmil
& (3)2/0 ­400kcmil
(2)250 - 500kcmil
& (3)2/0 ­400kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
(2)250 - 500kcmil
& (3)2/0 ­400kcmil
(2)250 - 500kcmil
& (3)2/0 ­400kcmil
250 - 500kcmil &
(2)3/0- 250kcmil
36
QUANTECH
Page 37
Electrical Data (Cont'd)
FORM QCC3-EG1 (517)
QCC3 VOLT HZ MCA
200 60 460
230 60 458
110CYE
130CZE
145CZE
160CZE
380 60 291 350 MCM 355 500 MCM
460 60 227 4/0 AWG 277 300 MCM
575 60 200 3/0 AWG 243 250 MCM
200 60 511
230 60 510
380 60 321 400 MCM 392 600 MCM
460 60 256 300 MCM 312 400 MCM
575 60 227 4/0 AWG 277 300 MCM
200 60 582
230 60 581
380 60 366 500 MCM 446
460 60 291 350 MCM 354 500 MCM
575 60 257 300 MCM 313 400 MCM
200 60 636
230 60 635
380 60 399 600 MCM 487
460 60 318 400 MCM 388 600 MCM
575 60 283 300 MCM 345 500 MCM
MIN REQ.
WIRE
GAUGE,
75˚C, CU
(2) 4/0
AWG
(2) 4/0
AWG
(2) 300
MCM
(2) 300
MCM
(2) 300
MCM
(2) 300
MCM
(2) 400
MCM
(2) 400
MCM
MCA
560
559
624
622
710
708
776
774
MIN REQ.
WIRE
GAUGE
75˚C, CU
(2) 300
MCM
(2) 300
MCM
(2) 350
MCM
(2) 350
MCM
(3) 300
MCM
(3) 300
MCM
(2) 4/0
AWG
(3) 300
MCM
(3) 300
MCM
(2) 250
MCM
TERMINAL
BLOCK
LUGS
(2) #6 - 500
kcmil
(2) #6 - 500
kcmil
(1) #4 - 500
kcmil
(1) #4 - 500
kcmil
(1) #4 - 500
kcmil
(2) #6 - 500
kcmil
(2) #6 - 500
kcmil
(1) #4 - 500
kcmil
(1) #4 - 500
kcmil
(1) #4 - 500
kcmil
(2) #6 - 500
kcmil
(2) #6 - 500
kcmil
(1) #4 - 500
kcmil
(1) #4 - 500
kcmil
(1) #4 - 500
kcmil
(2) #6 - 500
kcmil
(2) #6 - 500
kcmil
(2) #6 - 500
kcmil
(1) #4 - 500
kcmil
(1) #4 - 500
kcmil
NON-FUSED
DISCONNECT
SWITCH
LUGS
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
(1) #6 - 350 kcmil (1) #6 - 350 kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
250 - 500kcmil &
(2)3/0 -250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0-400kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0-400kcmil
250 - 500kcmil &
(2)3/0 -250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
CIRCUIT
BREAKER
LUGS
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
250 - 500kcmil &
(2)3/0
- 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
(2)250 - 500kcmil &
(3)2/0 -400kcmil
(2)250 - 500kcmil &
(3)2/0 -400kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0 - 400kcmil
(2)250 - 500kcmil &
(3)2/0-400kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
250 - 500kcmil & (2)3/0 - 250kcmil
QUANTECH
37
Page 38
FORM QCC3-EG1 (517)
Electrical Notes
NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3 amps; -58, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440-22.
5. CircuitbreakersmustbeULlistedandCSAcertiedandmaximumsizeisbasedon225%oftheratedload amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Oth­erwise, HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per
phaseofthewirerangespecied.Actualwiresizeandnumberofwiresperphasemustbedeterminedbased
on the National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.
7. AgroundlugisprovidedforeachcompressorsystemtoaccommodateaeldgroundingconductorperN.E.C. Table 250-95. A control circuit grounding lug is also supplied.
8. Thesupplieddisconnectisa“DisconnectingMeans”asdenedintheN.E.C.100,andisintendedforisolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
LEGEND ACR-LINE ACROSS THE LINE START C.B. CIRCUIT BREAKER D.E. DUAL ELEMENT FUSE DISC SW DISCONNECT SWITCH FACT MOUNT CB FACTORY MOUNTED CIRCUIT BREAKER FLA FULL LOAD AMPS HZ HERTZ MAX MAXIMUM MCA MINIMUM CIRCUIT AMPACITY MIN MINIMUM MIN NF MINIMUM NON FUSED RLA RATED LOAD AMPS S.P. WIRE SINGLE POINT WIRING UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT SWITCH) LRA LOCKED ROTOR AMPS N.E.C. NATIONAL ELECTRICAL CODE
VOLTAGE CODE
-17 = 200-3-60
-28 = 230-3-60
-40 = 380-3-60
-46 = 460-3-60
-58 = 575-3-60
38
QUANTECH
Page 39
FORM QCC3-EG1 (517)
THIS PAGE INTENTIONALLY LEFT BLANK.
QUANTECH
39
Page 40
FORM QCC3-EG1 (517)
Electrical Drawings
40
LD22075a
QUANTECH
Page 41
Electrical Drawings (Cont'd)
FORM QCC3-EG1 (517)
035-21583-101 REV O
QUANTECH
LD22075b
41
Page 42
FORM QCC3-EG1 (517)
LD22195b
Electrical Drawings (Cont'd)
42
LD22195a
QUANTECH
Page 43
Electrical Drawings (Cont'd)
FORM QCC3-EG1 (517)
035-21583-114 REV J
QUANTECH
LD22195b
43
Page 44
FORM QCC3-EG1 (517)
---> -AMB
Electrical Drawings (Cont'd)
-XP2
1D
1
2
2C
3
26B 129B 122B
5
120A
6
10
29B 131B 127B
30B 25B 128B
32A27A 228A
10
140A 28A 229A
3A 31A 231A
218C
1
2
3
4
5
222B
6
227B220B
-XP4
2
1
13I
19B
18B
43
-XP4
19C
13K 18C
43
21
NB41
7
8
9
7
8
9
7
8
9
-XP3
7
8
9
122A119A
127A
128A
228B221B
229B219B
231B
-XP2
-XP3
---> -AMB
10
131A 29A
11
12
25A
119B
4
120B
5
6
121B 118C
221A
4
222A
5
6
227A 220A
10
11
28B140B
12
31B
-ELINK
26A129A
134
14
30A121A118A
15
1
1E
2
2D
3
1
218A
2
219A
3
32B27B
13
14
3B
15
---> -AMB
NB34
NB19
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
10
1C 1D
140A 140C
131A
33
23
24
218A 218B
219A
220A 227A
221A
222A
218B
223A
227A
228A
229A
NB34
1
2
3
4
5
6
7
8
9
10
1
2
3
4
118A 118B
119A
120A 127A
121A
122A
118B
123A
127A
128A
129A
1B 1C
231A
NB34
TB7
TB10
TB5
TB6
1
1
1
1
TB8
TB9
1
031-02550-
1
+-COM
SHD
-
+
SHD
COM
HOT
J2
TB5
BLK
WHT
TB1
-AMB
43
2
1
ELINK/AMB:BLK
ELINK/AMB:RED
R
REF
ELINK/AMB:BLK
ELINK/AMB:RED
BLK
WHT
-T5
44
P/N 25-2698-18
NB4
SHD
REF-+
SHD
REFRXTX
5
2
NB49
NB49
NB34 NB39
1E
123I
223I
123E
223E
31I
29I
27I
33I
32I
30I
28I
32E
31E
30E
29E
33E
28E
25I
26I
27E
26E
25E
-XTBC2
NB19
NB4
5B
5I
23I
24I
23E
24E
24
5
NB41
2
2I
2I
GNDI
2E2ILELI5E
NB4
GNDE
2E
2E
NB49
NB19
LD22317a
QUANTECH
Page 45
Electrical Drawings (Cont'd)
-J15
7
S+
4
1
S-S- 98
5
2
6
S+
3
NB46
1
BRN-NEG
BRN-POS
2
-XP5
NB6
FORM QCC3-EG1 (517)
035-21589-102 REV M
-ADIS
12
TB1
PL1
J15
TB3TB2
J2
1
J1
1
TB4
­+
NB6
BRN-NEG BRN-POS
-SOA
13J
NB32
-J6
7
4
1
5
2
98
6
3
7
4
1
-J6
5
2
98
6
3
NB37
-J7
12
-J11
8
4
NB42
12
8
4
NB42
9
4
10
5
-XTBC1
A-NEG
A-POS
51
13H13J
13I
50
13G 13H
21
13F 13G
20
13E 13F 19A19B
13D 13E 18A18B
13C 13D
14
13B 13C
13A 13B
40A
41A
-SF
SFE:BLK
SFE:WHT
SFE:BRN
SFE:BLU
NB50
-SFE
NB19
14
11
9
18A12
19A
12
10
-AMB
9
5
1
J6
7
11111
7
4
J4
J7
5
99
J8
7
4
J9
4
1
9
5
1
6
2
5
2
6
2
1110
7
3
-J8
98
6
3
-J9
1110
7
3
-J10
NB37
98
6
3
8
3
-J13
51
5
7
50
8
6
5
J10
7
1
1
J14
J13
2
5B
5A
J12
9
5
1 1
11
6
4
J11
7
4
1
6
1
5
2
7
2
NB46
-F2
-F1
1
2 2
1
1
2
13A
20
3
21
4
-T1
41
40
41A
40A
3A
1
1E 1
NB39
NB19
QUANTECH
1
2
3
-J14
40
41
GND B
LD22317b
45
Page 46
FORM QCC3-EG1 (517)
Electrical Drawings (Cont'd)
JB1
-XTB1
149F
JB1
-XTB1
1
1
149G
2
2
2
AQ
+EXT
JB2
-FSC
+EXT
TB1
3
TB1
3
TB2
4
PE
144A
-FSC TB2
L3
4
PE
L1L2
+EXT
+EXT
V2U2W2
W1
U1
V1
E
GND 302301300
V2U2W2
W1
U1
V1
E
GND 305304303
V2
U2W2
W1
U1
V1
E
GND 302301300
V2
W2
U2
W1
U1
V1
E
GND 305304303
+EXT
GND
123
1
2
3
TB2
UL1L2L3
V
W
PE.
GND
+EXT
1
2
2
AV
3
TB2
U
V
W
PE.
+EXT+EXT
+EXT
=1-XTBF
+EXT
+EXT
SFE:WHT 2
SFE:BLU
+EXT
GND
223
2AS
226A
2AP
2
206
207
208
GND
1
+EXT
2
1AF
SFE:BRN
1
5
34
SFE:BLK
+EXT
13 14
=2-BDP:RED
=2-BDP:BLK
2
2
=2-BDP:WHT
3
225A
2AM
1 2 3
2
203
204
205
GND
1AD
A
B
C
232
+EXT
2
OR
224A
+EXT
1
2
3
231A
2AL
2
200
201
202
GND
+EXT
2
1AC
OR
GND
244A
+EXT
1
2
2
AW
3
46
235A
234A
233A
234
233
232A
LD22197a
QUANTECH
Page 47
Electrical Drawings (Cont'd)
149G
GND
+EXT
2
AQ
120A
220A
FORM QCC3-EG1 (517)
035-21589-106 REV N
GND
+EXT
1
2
2
AG
3
GND
+EXT
1
2
2
AH
3
120V
126A
2AN
2
GND
=2-BSP:RED =2-BSP:BLK
=2-BSP:WHT
1 2 3
OR
A
B
C
120V
JB2
=1-BSP:RED =1-BSP:BLK
=1-BSP:WHT
OR
=1-BDP:RED =1-BDP:BLK
=1-BDP:WHT
106
107
108
+EXT
1 2 3
125A
2AK
A
B
C
2
103
104
105
GND
132
+EXT
OR
+EXT
1
2
3
131A
124A
2AJ
2
100
101
102
GND
1 2 3
OR
A
B
C
120V
120V
+EXT
2
1AE
135A
134A
QUANTECH
133A
132A
2
1AA
133
120V
2
1AB
134
LD22197b
47
Page 48
FORM QCC3-EG1 (517)
NOITPIRCSEDnoitangiseDNOITPIRCSEDnoitangiseD
KFOL
FANOVERLOA D
F
Electrical Drawings (Cont'd)
- ADIS DISPLAY BOARD
- BAMB AMBIENT
- BDPDISCHARGE PRESSURE
- BECT ENTERING CHILLED TEMPERATURE REDRED
- BLCT LEAVING CHILLED TEMPERATURERPRUN PERMISSIVE
NOT FITTED ON REMOTE EVAP UNITS
-BMP MOTOR PROTECTOR COMPRESSOR SCRSCREEN
-CPF CA PACITOR POWER FACTOR - SOASWITCH OFF AUTO
-EPH PUMP HEATER
-EXT EX TERNAL
TO CONTROL PA NEL-UBRBRIGDE RECFIFIER
REKAERB TIUCRICBCQ-YROSSECCACCA
-QMMSC
-QSD SWITCH DISCONNECT
RU REMOTE UNLOAD Is t STEP
- SKPKEY PA D
MA NUAL MOTOR STARTER COMPRESSOR
RRESISTOR
HCTIWS WOLFFS -ERUSSERP NOITCUSPSB -
REMROFSNARTT -RETAEH ESACKNARCHCE -
PMUP RETRATS ROTOM LAUNAMPSMMQ-DRAOB ORCIMBMA -
TNERRUC REMROFSNARTCT-RETAEH ROTAROPAVEHEE-
ETIHWTHW ESUFF -
- FHPHIGH PRES SURE CUTOUT
-FSI FA N SPEED INHIBIT TWO SPEED- XTBC TERMINAL BLOCK CUSTOMER
YROTCAF KCOLB LANIMRETFBTX -YLNO NOITPO NAF
GNDGROUND
G/YGREEN / YELLOW
J PLUG BOARD CONNECTORFIELD MOUNTED AND WIRED ON REMOTE EV AP UNITS
-K CIRCUIT BOARD RELAY- ZCPR COMPRESSOR
-KFFAN CONTACTOR LINE
-KFH
-KFL
-
-KFS RELAY FA N SPEED
- MCOMPRES SOR MOTOR
-M
-MPMOTOR PUMP
FAN CONTACTOR HIGH SPEED (INCLUDING COIL SUPPRESSOR) FAN CONTACTOR LOW SPEED
(INCLUDING COIL SUPPRESSOR)
(INCLUDING COIL SUPPRESSOR)
(INCLUDING COIL SUPPRESSOR)
MOTOR FA N
-YHGSV HOT GA S SOLENOID VALVE
(INCLUDING COIL SUPPRESSOR)
- YLLSVLIQUID LINE SOLENOID VALVE (INCLUDING COIL SUPPRESSOR)
NB
WIRING A ND ITEMS SHOWN THUS
ARE STANDARD QUANTECH ACCESSORIES
ITEMS THUS ENCLOSED FORM A COMPONENTS OR SETS OFCOMPONENTS
NOTE WELL {SEE NOTE}
QUANTECH
KROY YB DEILPPUS TON ERA TRAP ROTCATNOC PMUPPK-
SEIROSSECCA KROY DRADNATS ERAROTCATNOC ROSSERPMOCMK-
SUHT NWOHS SMETI DNA GNIRIW YALER LORTNOCRCK-
NU NOT USED
PE PROTECTIVE EA RTH
PWMPULSE WIDTH MODULATION TEMP
RESET or REMOTE UNLOAD 2nd STEP
48
QUANTECH
Page 49
Electrical Drawings (Cont'd)
A. This drawing is based on IEC symbols. B. Field wiring to be in accordance with the relevant electrical code as well as all other applicable codes and
specications
C. All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by
the chiller manufacturer .
D. Green and yellow wire is used for earth, multi-coloured cable used for low voltage. Red wire used for AC
control, blue wire for neutral, black wire for AC and DC power. Orange wire should be used for interlock control wiring supplied by external source.
E. Legenddesignationdepictscomponentabbreviations.Number prexlocated,ifapplicable,onschematic
circuit, refers to system thereon, e.g.= 1-FHP2 refers to high pressure cutout no 2 on system no 1.
F. All wiring to control section voltage free contacts requires a supply provided by the customer maximum
voltage 240 volts. The customer must t ake particular care when deriving the supplies for the voltage free terminals with regard to a common point of isolation. Thus, these circuits when used must be fed via the common point of isolation the voltage to these ci rcuits is removed when the common point of isolation to the unit is opened. This common point of isolation is not supplied. The voltage free contacts are rated at 100VA. All inductive devices {relays} switch by the voltage free contacts must have their coil suppressed
using standard r/c suppressors. G. Customer voltage free contacts connected to terminal 13 must be rated at 30v 5ma H. No controls {relays etc.} Should be mounted in any section of the control panel. Additionally, control wiring
not connected to the control panel should not be run through the panel. If these precautions are not fol-
lowed, electrical noise could cause malfunctions or damage to the unit and its controls.
1. Refer to instalation commisioning operation and maintenance manual for customer connections and cus­tomer connection notes, non compliance to these instructions will invalidate unit warranty.
2. Wiringandcomponentsforcompressor3onlyttedwhenunithas3compressorsonthesystem.1-BMP3 is replaced by a link across terminals 134 & 135. 2-BMP3 is replaced by a link across terminals 234 & 235.
3. FHP2isonlyttedon0089andabove.Whennottted1-FHP2isreplacedbyalinkacrossterminals132 & 139. 2-FHP2 is replaced by a link across terminals 232 & 239
4. Fitted on units with hot gas bypass option.
5. EMS option is wired as shown
6. This wiring must be used for old display 031-0110-000
7. Network connection point
8. Printer port
9. Remote emergency stop can be wired between terminal l and 5 after removing link
10. Powerfactorcorrectionaccessory.Powerfactorcorrectionttedtoeachcompressorcontactor
11. Notttedoncompressorswithinternalmotorprotection.Forsytem1terminals132&133,133&134And 134 & 135 are linked. For sytem 2 terminals 232 & 233, 233 & 234 and 234 & 235 are linked.
12. Onlyttedonsystemswith3or4fans
13. Onlyttedonsystemswith4fans
14. Onlyttedonsystemswith5fans
15. Onlyttedonsystemswith6fans
16. Input switch disconnect or circuit breaker option replaces input terminal block
17. Input switch disconnect & system circuit breaker option replaces input terminal block
18. 115Vcontrolcirciutrequiresa115Vsupplyunlesscontrolcircuittransformer-T2&-F3aretted
19. Foroptionalhydrokit. Heater-EPHisttedandwiredasshown. Onsinlgepump-KP1,-QMMSP1 and
-MP1aretted&wiredas shown.Ontwopumphydro kits-KP2,-QMMSP2&-MP2arealso ttedand
wired as shown.
20. Current measurement option wired as shown
21. Onlyttedonsystemswithsinglespeedfans
22. Onlyttedonsystemswithtwospeedfans
23. Optional compressor manual motors starters.
24. See sheet 3 of connection diagram for power input options
FORM QCC3-EG1 (517)
QUANTECH
49
Page 50
FORM QCC3-EG1 (517)
Application Data
UNIT LOCATION
The QCC3 Condensing Units are designed for outdoor installation. When selecting a site for installation, be guided by the following conditions:
1. For outdoor locations of the unit, select a place having an adequate supply of fresh air for the condenser.
2. Avoid locations beneath windows or between structures where normal operating sounds may be objection able.
3. Installation sites may be either on a roof, or at ground level. (See FOUNDATION, below.)
4. The condenser fans are the propeller-type, and are not recommended for use with duct work in the condenser air stream.
5. When it is desirable to surround the unit(s), it is recom mended that the screening be able to pass the required chiller CFM without exceeding 0.1” of water external static pressure.
6. Protection against corrosive environments is available by supplying the units with eithercoppern,curedphenolic,orepoxycoatingonthecondensercoils.Thephe­nolic or epoxy coils should be offered with any units being installed at the seashore or where salt spray may hit the unit.
In installations where winter operation is intended and snow accumulations are expected, additional height must be provided to ensure normal condenser air flow.
Recommended clearances for units are given in Dimension Drawings on page 26. When the available space is less, the unit(s) must be equipped with the discharge pres­sure transducer option to permit high pressure unloading in the event that air recirculation were to occur.
FOUNDATION
The unit should be mounted on a flat and level foundation, ground or roof, capable of sup­porting the entire operating weight of the equipment. Operating weights are given in the Physical Data on page 25 tables.
Roof Locations – Choose a spot with adequate struc tural strength to safely support the entire weight of the unit and service personnel. Care must be taken not to damage the roof during installation. If the roof is “bonded”, consult the building contractor or architect for special installation requirements. Roof installations should incorporate the use of spring­type isolators to minimize the transmission of vibration into the building structure.
Ground Level Installations – It is important that the units be installed on a substantial base that will not settle, causing strain on the refrigerant lines and resulting in possible leaks. A one-piece concrete slab with footers extending below the frost line is highly rec­ommended, particularly in areas where winters are long and very cold. Additionally, the slab should not be tied to the main build ing foundation as noises will telegraph.
50
QUANTECH
Page 51
Application Data (Cont'd)
Mounting holes (11/16” diameter) are provided in the steel channel for bolting the unit to its foundation. See Dimension Drawings on page 26.
For ground level installations, precautions should be taken to protect the unit from tam­pering by or injury to unau thorized persons. Screws on access panels will prevent casual tampering; however, further safety precautions, such as unit enclosure options, a fenced­in enclosure, or locking devices on the panels may be advisable. Check local authorities for safety regulations.
REFRIGERANT PIPING
When sizing refrigerant pipe for split system air condition ing, consideration must be given to the: (1) Suction line pressure drop due to friction, (2) Liquid line pressure drop due to friction, (3) Suction line velocity for oil return, and (4) Liquid line pressure drop due to vertical rise.
On a system where the evaporator blower is located below the condensing unit, the suc­tion line must be sized for both pressure drop and oil return.
When the condensing unit is located below the evapora tor blower, the liquid line must be designed for pressure drop due to friction loss and vertical rise. If the pressure drop due to vertical rise and friction loss exceeds 30 psig (2.1 barg), some refrigerant will flash before it reaches the thermal expansion valve.
FORM QCC3-EG1 (517)
All horizontal suction lines should be pitched at least 1/4 inch (6 mm) per foot in the direc­tion of the refrigerant flow to aid the return of oil to the compressor. All suction lines with a vertical rise exceeding 3 feet (1 m) should have a ‘P’ trap at the bottom and the top to facilitate oil return. Suction lines with a vertical rise exceeding 25 feet (7.6 m) should be trapped every 15 feet (4.6 m) to provide drain points for the oil when the circuit is deacti­vated. When the circuit is reactivated, oil will return to the compressor more quickly and in smaller slugs.
For more details, refer to ASHRAE Refrigeration Hand book, System Practices for Halo­carbon Refrigerants.
QUANTECH
51
Page 52
FORM QCC3-EG1 (517)
Guide Specifications
PART 1 – GENERAL
1.01 SCOPE
A. The requirements of the General Conditions, Supplementary Conditions, Division 1,
and Drawings apply to all Work herein.
B. Provide Microprocessor controlled, multiple-scroll compressor, air-cooled, condensing
units of the scheduled capacities as shown and indicated on the Drawings, including but not limited to:
1. Condensing Unit package
2. Electrical power and control connections
3. DX Central Station Air Handling connections
1.02 QUALITY ASSURANCE
A. Products shall be Designed, Tested, and installed in compliance with applicable sec-
tions of the following Standards and Codes:
1. ANSI/ASHRAE Standard 15 – Safety Code for Mechanical Refrigeration
2. ASHRAE 90.1 - Energy efciency compliance.
3. ANSI/NFPA Standard 70 – National Electrical Code (N.E.C.).
4. Conform to Intertek Testing Services, formerly ETL, for construction of condensing units and provide E.T.L./c E.T.L. Listing label.
5. Manufactured in facility registered to ISO 9002.
B. Factory Test: Condensing Unit shall be pressure tested, evacuated and given a nitro-
gen holding charge and an initial oil charge, and shall be factory operational run tested to assure each control device operates properly.
C. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture
against defects in workmanship and material for a period of one year from date of initial
start-uporeighteen(18)monthsfromdateofshipment,whicheveroccursrst.
1.03 DELIVERY AND HANDLING
A. Unit shall be delivered to job site fully assembled, and given nitrogen holding charge
and a full oil charge by the Manufacturer. (R-410A refrigerant supplied by others).
B. Unit shall be stored and handled per Manufacturer’s instructions.
52
QUANTECH
Page 53
Guide Specifications (Cont'd)
PART 2 - PRODUCTS
2.01 CONDENSING UNITS MATERIALS AND COMPONENTS
A. General: Install and commission, as shown on the schedules and plans, factory as-
sembled, charged, and tested air cooled scroll compressor condensing unit as speci-
ed herein. Condensing Unit shall be designed, selected, and constructed using a refrigerantwithFlammabilityrating of “1”, asdened byANSI/ASHRAESTANDARD
-34NumberDesignationandSafetyClassicationofRefrigerants.Condensing Unit
shall include, but is not limited to: not less than two refrigerant circuits, scroll com­pressors, air-cooled condenser, refrigerant, lubrication system, interconnecting wiring, safety and operating controls including capacity controller, control center, motor start­ingcomponents, and specialfeaturesasspecied hereinor requiredforsafe, auto­matic operation.
B. Cabinet: External structural members shall be constructed of heavy gauge, galvanized
steel coated with baked on powder paint which, when subject to ASTM B117, 1000 hour, 5% salt spray test, yields minimum ASTM 1654 rating of “6”.
2.02 COMPRESSORS
FORM QCC3-EG1 (517)
Compressors: Shall be hermetic, scroll-type, including:
1. Compliant design for axial and radial sealing.
2. Refrigerantowthroughthecompressorwith100%suctioncooledmotor.
3. Large suction side free volume and oil sump to provide liquid handling capability.
4. Compressor crankcase heaters to provide extra liquid migration protection.
5. Annular discharge check valve and reverse vent assembly to provide low pressure drop, silent shutdown and reverse rotation protection.
6. Initial Oil charge.
7. Oil Level sightglass.
8. Vibration isolator mounts for compressors.
9. Brazed-type connections for fully hermetic refrigerant circuits.
2.03 REFRIGERANT CIRCUIT
Two independent refrigerant circuits will be furnished on each unit. All unit piping will be copper, with brazed joints. The liquid line will include a field connection shutoff valve with charging port located on each condenser circuit. Suction line connections are provided on each refrigeration circuit. Filter drier and sight glass are shipped loose for field instal­lation on each refrigerant circuit. All expansion valves and liquid line solenoid valves and refrigerant field piping are supplied by others.
QUANTECH
53
Page 54
FORM QCC3-EG1 (517)
Guide Specifications (Cont'd)
2.04 HEAT EXCHANGERS
A. Air Cooled Condenser:
1. Coils: Internally enhanced, seamless copper tubes, mechanically expanded into aluminumalloynswithfullheightcollars.Subcoolingcoilanintegralpartofcon­denser. Design working pressure shall be 650 psig (45 barg).
2. Fans: Shall be dynamically and statically balanced, direct drive, corrosion resistant
glassberreinforcedcompositebladesmoldedintolownoise,fullairfoilcrosssec­tion,providing verticalairdischarge fromextended orices forefciency and low sound.Eachfaninitsowncompartment to prevent crossow during fan cycling.
Guards of heavy gauge PVC (polyvinyl chloride) coated steel.
3. Fan Motors: High efciency, direct drive, 6 pole, 3 phase, insulation class “F”, current-protected, Totally Enclosed Air-Over (TEAO), rigid mounted, with double sealed, permanently lubricated, ball bearings.
2.05 CONTROLS
A. General: Automatic start, stop, operating, and protection sequences across the range
of scheduled conditions and transients.
B. Microprocessor Enclosure: Rain and dust tight NEMA 3R/12 (IP55) powder painted
steel cabinet with hinged, latched, and gasket sealed door.
C. Microprocessor Control Center:
1. Condensing Unit control is set for Discharge Air Temperature Control
2. Automatic control of compressor start/stop, anti-coincidence and anti-recycle tim­ers, automatic pump-down shut-down, condenser fans, unit alarm contacts, and condensing unit operation from 0°F to 125°F (-18°C to 52°C) ambient. Automatic reset to normal chiller operation after power failure.
3. Software stored in non-volatile memory, with programmed set-points retained in lithium battery-backed real time clock (RTC) memory for minimum 5 years.
4. Forty character liquid crystal display, descriptions in English (or Spanish, French, Italian, or German), numeric data in English (or Metric) units. Sealed keypad with sections for Setpoints, Display/Print, Entry, Unit Options & clock, and On/Off Switch.
5. Programmable Set-points (within Manufacturer limits): display language; suc­tion pressure setting and control range, remote reset temperature range, set daily schedule/holiday for start/stop, manual override for servicing, low and high ambi­ent cutouts, number of compressors, low suction pressure cutout, high discharge pressure cutout, anti-recycle timer (compressor start cycle time), and anticoincident timer (delay compressor starts).
6. Display Data: Suction temperatures (optional), low ambient temperature cutout set­ting, outdoor air temperature, English or metric data, suction pressure cutout setting, each system suction pressure, discharge pressure (optional), discharge air reset via Building Automation System (by others) via a 4-20milliamp or 0-10 VDC input with optional BAS interface, anti-recycle timer status for each system, anti-coincident
54
QUANTECH
Page 55
Guide Specifications (Cont'd)
system start timer condition, compressor run status, no cooling load condition, day, date and time, daily start/stop times, holiday status, automatic or manual system lead/lag control (when controlling based on Discharge Air Temperature only), auto­matic lead/lag of compressors within a system, compressor starts/operating hours (each), status of hot gas valves, and fan operation, run permissive status, number of compressors running, liquid solenoid valve status, load & unload timer status.
7. System Safeties: Shall cause individual compressor systems to perform auto shut down; manual reset required after the third trip in 90 minutes. Includes: high dis­charge pressure, low suction pressure, high pressure switch, and motor protector. Compressor motor protector shall protect against damage due to high input current or thermal overload of windings.
8. Unit Safeties: Shall be automatic reset and cause compressors to shut down if low ambient, or under voltage.
9. Alarm Contacts: Low ambient, low voltage, low battery, and (per compressor cir­cuit): high discharge pressure, and low suction pressure.
10. High Ambient Control: Permits unit operation above 115°F (46°C) ambient.
D. Manufacturer shall provide any controls not listed above, necessary for automatic con-
densingunitoperation.MechanicalContractorshallprovideeldcontrolwiringneces­sary to interface sensors to the condensing unit control system.
FORM QCC3-EG1 (517)
2.06 POWER CONNECTION AND DISTRIBUTION
A. Power Panels:
1. NEMA 3R/12 (IP55) rain/dust tight, powder painted steel cabinets with hinged, latched, and gasket sealed outer doors. Provide main power connection(s), control power connections, compressor and fan motor start contactors, current overloads, and factory wiring.
2. Power supply shall enter unit at a single location, be 3 phase of scheduled voltage, and connect to individual terminal blocks per compressor. Separate disconnecting means and/or external branch circuit protection (by Contractor) required per appli­cable local or national codes.
B. Exposed compressor, control and fan motor power wiring shall be routed through liquid
tight conduit.
2.07 ACCESSORIES AND OPTIONS
Some accessories and options supercede standard product features. Your Quantech Sales Representative will be pleased to provide assistance.
A. Microprocessor controlled, Factory installed Across-the-Line type compressor motor
starters as standard.
B. Outdoor Ambient Temperature Control
1. Low Ambient Control: Permits unit operation to 0°F (-18°C) ambient. Standard unit
QUANTECH
controls to 32°F (0°C) ambient.
55
Page 56
FORM QCC3-EG1 (517)
Guide Specifications (Cont'd)
C. Power Supply Connections:
1. SinglePointPowerSupply:SinglepointTerminalBlockforeldconnectionandin- terconnecting wiring to the compressors. Separate external protection must be sup­plied, by others, in the incoming power wiring, which must comply with the National Electric Code and/or local codes.
2. Single Point: Single point Non-Fused Disconnect(s) and lockable external handle (in compliance with Article 440-14 of N.E.C.) can be supplied to isolate the unit power voltage for servicing. Separate external fusing must be supplied, by others, in the in coming power wiring, which must comply with the National Electric Code and/or local codes.
3. Single Point Disconnect with Individual System Breakers: Single point Terminal Block with Non- Fused Disconnect and lockable external handle (in compliance with Article 440-14 of N.E.C.) can be supplied to isolate power voltage for servicing. Factory interconnecting wiring from disconnect to factory supplied circuit breakers.
4. Single Point Circuit Breaker: Single point Terminal Block with Circuit Breaker and lockable external handle (in compliance with Article 44014 of N.E.C.) can be sup­plied to isolate power voltage for servicing. Incoming power wiring must comply with the National Electric Code and/or local codes.
D. Pressure & Temperature Transducers and Sensors
1. Discharge Pressure Transducers: Permits unit to sense and display discharge pres­sure.
2. Suction Pressure Transducers: Permits unit to sense and display suction pressure.
3. Suction Temperature Sensors: Permits units to sense and display suction tempera­ture.
E. Control Power Transformer: Converts unit power voltage to 120-1-60 or 120-1-50 for
50Hz units (500 VA capacity). Factory mounting includes primary- and secondary-wir­ing between the transformer and the control panel.
F. Motor Current Module: Capable of monitoring compressor motor current. Provides ex-
tra protection against compressor reverse rotation, phase-loss and phase imbalance. Options consists of one module per electrical system. (Factory mounted)
G. Power Factor Correction Capacitors: Provided to correct unit compressor factors to a
0.900.95.
H. Condenser Coil Environmental Protection:
1. Pre-Coated:Epoxycoatedaluminumnstocktoguardfromcorrosiveagentsand insulate against galvanic potential. For mild seashore or industrial locations
2. CopperFin:Providecoppernsinlieuofaluminum.
3. Post-Coated Dipped: Dipped-cured coating on condenser coils for seashore and other corrosive applications (with the exception of strong alkalis, oxidizers, and wet
bromine,chlorineanduorineinconcentrationsgreaterthan100ppm).
56
QUANTECH
Page 57
Guide Specifications (Cont'd)
I. Protective Condensing Unit Panels (Factory or Field Mounted):
1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabi­net, over external condenser coil faces.
2. Wire Panels (full unit): Heavy gauge, welded wire-mesh, coated to resist corrosion, to protect condenser coils from incidental damage and restrict unauthorized access to internal components.
3. Louvered Panels (full unit): Painted steel as per remainder of unit cabinet, to protect condenser coils from incidental damage,visually screen internal components, and prevent unauthorized access to internal components.
4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces, painted as per remainder of unit cabinet. Heavy gauge, welded wire-mesh, coated to resist corrosion, around base of machine to restrict unauthorized access.
J. Service Isolation valves: Service suction and discharge (ball type) isolation valves are
added to unit per system. This option also includes a system high pressure relief valve in compliance with ASHRAE15. (Factory-mounted.)
K. Hot Gas By-Pass: Permits continuous, stable operation at capacities below the mini-
mum step of unloading to as low as 5% capacity (depending on both the unit & operat-
ingconditions) byintroducinganarticialload.Hotgasby-passis available installed
on one or both refrigerant circuit(s).
FORM QCC3-EG1 (517)
L. Microprocessor Membrane Keypad Graphics on in lieu of Standard English:
1. French language.
2. German language.
3. Spanish language.
4. Italian language.
M. Chicago Code Relief Valves to meet Chicago Code requirements.
N. Building Automation System (EMS) Reset Interface: Condensing Unit to accept 4 to
20mA, 0 to 10 VDC, input to reset the discharge air temperature.
O. Sound Reduction (Factory Mounted):
1. Low speed, reduced noise fans
2. Compressor Acoustic Sound Blankets
P. Vibration Isolation (Field Mounted):
1. Neoprene Pad Isolators.
2. 1InchDeectionSpringIsolators:Leveladjustable,springandcagetypeisolators for mounting under the unit base rails.
3. 2InchDeectionSeismicIsolators:Leveladjustable,restrainedmountsinrugged
QUANTECH
welded steel housing with vertical and horizontal limit stops. Housings shall be de­signed to withstand a minimum 1.0g accelerated force in all directions to 2 inches.
57
Page 58
FORM QCC3-EG1 (517)
Guide Specifications (Cont'd)
PART 3 - EXECUTION
3.01 INSTALLATION
A. General: Rig and Install in full accordance with Manufacturers requirements, Project
drawings, and Contract documents.
B. Location: Locate condensing unit as indicated on drawings, including cleaning and
service maintenance clearance per Manufacturer instructions. Adjust and level con­densing unit on support structure.
C. Components: Installing Contractor shall provide and install all auxiliary devices and
accessories for fully operational condensing unit.
D. Electrical: Coordinate electrical requirements and connections for all power feeds with
Electrical Contractor (Division 16).
E. Controls: Coordinate all control requirements and connections with Controls Contrac-
tor.
F. Finish:InstallingContractorshallpaintdamagedandabradedfactorynishwithtouch-
uppaintmatchingfactorynish.
58
QUANTECH
Page 59
Notes
FORM QCC3-EG1 (517)
QUANTECH
59
Page 60
Printed on recycled paper Form QCC3-EG1 (517) New Release P.O. Box 423, Milwaukee, WI 53201 Printed in USA Issued on 5/19/2017
Loading...