QTM-DC Power Supply
(DC and DC+CAP)
Installation Instructions
Must be installed by licensed electrician.

Installation Instructions
QTM-DC Field Wiring Made Simple
PRIMARY
TAP4 TAP3
Land Neutral
on one tap.
Line Voltage
TAP2 TAP1 HOT GND
Primary Input Load
Land
Hot
Land
Ground
SECONDARY
+ 1 -
RED = Positive
YELLOW = Negative
+ 2 -
Low Voltage
+ 3 -
Chose either tap
1,2,3 or 4
NOTE: Primary Input - connect the 120V hot into block labeled Hot. Connect the neutral wire into Tap 1 - Tap 5 depending on desired output Voltage.(Not to exceed 12V or 24V)
"0.8
mm2.302
QTM-DC/DC+CAP
Model
QTM60
QTM100
QTM120
QTM150
QTM180
QTM200
QTM240
QTM300
QTM360
QTM400
QTM500
QTM600
QTM60
QTM100
QTM120
QTM200
This product must be installed in accordance with the applicable installation code by a person familiar with the
construction and operation of the product and the hazards involved.
WALL MOU NT ONLY
FOR SU PPLY CONNECTIO NS USE
WIRE R ATED FOR AT LEAST 75 C.
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC+CAP
DC+CAP
DC+CAP
DC+CAP
Input Voltage
(V)
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
SUITABLE FOR DAMP LOCATIONS
USE DI MMERS RATED FOR MAGN ETIC
LOW VOLTAGE LOAD
ISOLATION TOROIDAL TRANSFORM ER
Input Current
(A)
0.67 / 0.29
1.1 / 0.49
1.3 / 0.58
1.7 / 0.7
2.0 / 0.87
2.3 / 0.98
2.7 / 1.2
3.4 / 1.5
4.1 / 1.8
4.5 / 2.0
5.6 / 2.4
6.7 / 2.9
0.9 / 0.4
1.3 / 0.5
1.4 / 0.6
2.4 / 1.0
Frequency Nominal Output
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60 CYCLE A.C. O NLY
MADE I N THE U.S .A.
Voltage (VDC)
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
24
24
12/24
12/24
12/24
24
LU MI NA IR E POWE R
Nominal Output
Wattage (W)
60
100
120
150
180
200
240
300
360
400
500
600
60
100
120
200
LOW VOLTAGE
SU PP LY C EN TER
WIRE CONNECTION
Yellow
-
Red
+
Q-Tran, Inc.
239924
CLASS:
3425 - 15
3425 - 95
Q-TRAN, INC.
MILFORD, CT U.S.A.
(203) 367-8777
WWW.Q-TRAN.COM
14.5"
368.3mm
Secondary
Breakers
LV
compartment
Class II wiring
TAP2 TAP1 HOT GNDTAP4 TAP3
Primary Input Load
Rectifier
Class I
Wiring
Choke
Must test all voltage readings with a True RMS Voltage Meter.
1
© Copyright Q-Tran, Inc. 2013
Q-Tran 155 Hill Street Milford, CT 06460 www.Q-Tran.com

Installation Instructions
QTM-DC+CAP Field Wiring Made Simple
PRIMARY
TAP4TAP5 TAP3
Land Neutral
on one tap.
Line Voltage
TAP2 TAP1 HOT GND
Primary Input Load
Land
Hot
Land
Ground
SECONDARY
+ 1 -
RED = Positive
YELLOW = Negative
+ 2 -
Low Voltage
+ 3 -
Chose either tap
1,2,3,4 or 5
NOTE: Primary Input - connect the 120V hot into block labeled Hot. Connect the neutral wire into Tap 1 - Tap 5 depending on desired output Voltage.(Not to exceed 12V or 24V)
"0.8
mm2.302
QTM-DC/DC+CAP
Model
QTM60
QTM100
QTM120
QTM150
QTM180
QTM200
QTM240
QTM300
QTM360
QTM400
QTM500
QTM600
QTM60
QTM100
QTM120
QTM200
This product must be installed in accordance with the applicable installation code by a person familiar with the
construction and operation of the product and the hazards involved.
WALL MOU NT ONLY
FOR SU PPLY CONNECTIO NS USE
WIRE R ATED FOR AT LEAST 75 C.
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC
DC+CAP
DC+CAP
DC+CAP
DC+CAP
Input Voltage
(V)
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
SUITABLE FOR DAMP LOCATIONS
USE DI MMERS RATED FOR MAGN ETIC
LOW VOLTAGE LOAD
ISOLATION TOROIDAL TRANSFORM ER
Input Current
(A)
0.67 / 0.29
1.1 / 0.49
1.3 / 0.58
1.7 / 0.7
2.0 / 0.87
2.3 / 0.98
2.7 / 1.2
3.4 / 1.5
4.1 / 1.8
4.5 / 2.0
5.6 / 2.4
6.7 / 2.9
0.9 / 0.4
1.3 / 0.5
1.4 / 0.6
2.4 / 1.0
Frequency Nominal Output
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60 CYCLE A.C. O NLY
MADE I N THE U.S .A.
Voltage (VDC)
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
24
24
12/24
12/24
12/24
24
LU MI NA IR E POWE R
Nominal Output
Wattage (W)
60
100
120
150
180
200
240
300
360
400
500
600
60
100
120
200
LOW VOLTAGE
SU PP LY C EN TER
WIRE CONNECTION
Yellow
-
Red
+
Q-Tran, Inc.
239924
CLASS:
3425 - 15
3425 - 95
Q-TRAN, INC.
MILFORD, CT U.S.A.
(203) 367-8777
WWW.Q-TRAN.COM
14.5"
368.3mm
Secondary
Breakers
LV
compartment
Class II wiring
Class I
Wiring
Rectifier
Cap
Must test all voltage readings with a True RMS Voltage Meter.
© Copyright Q-Tran, Inc. 2013
Q-Tran 155 Hill Street Milford, CT 06460 www.Q-Tran.com
2

Installation Instructions
QTM-DC & DC+CAP Housing Mounting
This face of bracket
mounts to: Wall
Surface Wall
Note: Surface Mounting can be done on six different planes.
9
8
25
8
25
9
8
8
25
9
8
8
9“
25
8
9
8
25
8
25
8
8
9 1/2”
O.C.
9
Surface Stacking
8
9
17
9 1/2”
More
9
units
can be
stacked
O.C.
Minimum
9
9
Surface Spacing
16” O.C.
Minimum
8
16 25
More units can be spaced
PRIMARY
8
9
8
17
9
8
8
9 1/2” O.C.
Minimum
SECONDARY
Note:
knockouts are located
where are shown.
= Number of available Knockouts per side
#
= Total number of available Knockouts per unit
#
#
8
17
9
9
More units can be spaced
9
17
9
8
8
19”
3
© Copyright Q-Tran, Inc. 2013
Q-Tran 155 Hill Street Milford, CT 06460 www.Q-Tran.com