Qmark Environmental Electric Heated User Manual

ENVIRONMENTAL SERIES
®
15 3/4”
1
3”
Refer to individual model numbers
f
or unit width
8
1/4”
4 7/8”
11 7/8”
ELECTRICALLY HEATED AIR CURTAINS
8 KW THROUGH 48 KW
36” THROUGH 144”
Installation & Maintenance Instructions
Dear Owner,
Congratulations! Thank you for purchasing this new air curtain manufactured by M arley Engineered Products. You have made a wise investment selecting the highest quality product in the industry. Please carefully read the installation and maintenance instructions shown in this m anual. You should enjoy years of efficient serv ice with this product from Marley Engineered Products... the industry’s leader in design, m anufacturing, quality and service.
... The Employees of Marley Engineered Products
WARNING
Read Carefully - These instructions are written to help you
prevent difficulties that might arise during installation of the unit. Studying the instructions first may save you consider­able time and money later. Observe the following proce­dures, and cut your installation time to a minimum.
CAUTION - TO REDUCE RISK OF FIRE AND ELECTRIC SHOCK OBSERVE THE FOLLOWING:
1. Disconnect all power coming to the unit at main service panel before wiring or servicing. Lock service panel to prevent power from being switched on accidentally.
NOTE: Do not depend upon a thermostat or other switch as the sole means of disconnecting power when installing or servicing the unit. Always disconnect power at the main service panel as described above.
2. All wiring should be done by a qualified electrician, using copper wire only and in accordance with the National Electrical Code (NEC), all applicable code and ordinances, including fire rated construction, and all sections of this manual. Any variance voids the warranty and may create unsafe conditions.
3. To prevent the risk of electric shock, the unit must be properly grounded. This should be accomplished by connecting a bond­ing conductor between the disconnecting means and the grounding lug provided in the Main Control Box of the unit. Each
cabinet wiring compartment is provided with grounding lugs for connecting bonding conductors between each cabinet and the Main Control Box. To ensure a proper ground, the grounding means must be tested by a qualified electrician.
4. Verify the power supply voltage coming to unit matches the rat­ings printed on the heater nameplate before energizing.
5. This unit can be hot when in use. To avoid burns, do not let bare skin touch hot surfaces.
6. Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock, fire or damage to the unit.
7. Do not block air intakes or exhaust in any manner. Keep com­bustible materials, such as crates, drapes, etc., away from air curtain.
8. This unit has hot and arcing or sparking parts inside. Do not use it in areas where gasoline, paint or flammable liquids are used or stored.
9. Use this unit only as described in this manual. Any other use not recommended by the manufacturer may cause fire, electric shock, or injury to persons. If you have questions contact the manufacturer.
10. This unit is not approved for use in corrosive atmospheres such as marine, green house or chemical storage areas.
!
READ AND SAVE THESE INSTRUCTIONS
1
Environmental Series Specifications and Performance
MODEL NOZZLE Volts Heater # MOTORS @ OF CONTROL MAX VEL AVG VEL AIRFLOW SHIPPING NUMBER WIDTH (IN) AC Watts BTU/HR HP CABINETS VOLTAGE (FPM) (FPM) (CFM) WEIGHT (LBS)
1/2 HP Models
E36081#50HE 36 # 8000 27,320 1 @ 1/2 1 24 3800 3040 2460 93 E42081#50HE 42 # 8000 27,320 1 @ 1/2 1 24 3800 2890 2730 98 E48081#50HE 48 # 8000 27,320 1 @ 1/2 1 24 3800 2815 3040 105 E60081#50HE 60 # 8000 27,320 1 @ 1/2 1 24 3800 2740 3350 117 E72162#50HE 72 # 16000 54,640 2 @ 1/2 2 24 3800 3040 4920 177 E84162#50HE 84 # 16000 54,640 2 @ 1/2 2 24 3800 2910 5460 181 E96162#50HE 96 # 16000 54,640 2 @ 1/2 2 24 3800 2815 6080 189 E108243#50HE 108 # 24000 81,960 3 @ 1/2 3 24 3800 3040 7380 261 E120243#50HE 120 # 24000 81,960 3 @ 1/2 3 24 3800 2950 7920 273 E132243#50HE 132 # 24000 81,960 3 @ 1/2 3 24 3800 2875 8540 285 E144243#50HE 144 # 24000 81,960 3 @ 1/2 3 24 3800 2815 9120 297 E36121#50HE 36 # 12000 40,980 1 @ 1/2 1 24 3800 3040 2460 93 E42121#50HE 42 # 12000 40,980 1 @ 1/2 1 24 3800 2890 2730 98 E48121#50HE 48 # 12000 40,980 1 @ 1/2 1 24 3800 2815 3040 105 E60121#50HE 60 # 12000 40,980 1 @ 1/2 1 24 3800 2740 3350 117 E72242#50HE 72 # 24000 81,960 2 @ 1/2 2 24 3800 3040 4920 177 E84242#50HE 84 # 24000 81,960 2 @ 1/2 2 24 3800 2910 5460 181 E96242#50HE 96 # 24000 81,960 2 @ 1/2 2 24 3800 2815 6080 189 E108363#50HE 108 # 36000 122,940 3 @ 1/2 3 24 3800 3040 7380 261 E120363#50HE 120 # 36000 122,940 3 @ 1/2 3 24 3800 2950 7920 273 E132363#50HE 132 # 36000 122,940 3 @ 1/2 3 24 3800 2875 8540 285 E144363#50HE 144 # 36000 122,940 3 @ 1/2 3 24 3800 2815 9120 297 E36161#50HE 36 # 16000 54,640 1 @ 1/2 1 24 3800 3040 2460 93 E42161#50HE 42 # 16000 54,640 1 @ 1/2 1 24 3800 2890 2730 98 E48161#50HE 48 # 16000 54,640 1 @ 1/2 1 24 3800 2815 3040 105 E60161#50HE 60 # 16000 54,640 1 @ 1/2 1 24 3800 2740 3350 117 E72322#50HE 72 # 32000 109,280 2 @ 1/2 2 24 3800 3040 4920 177 E84322#50HE 84 # 32000 109,280 2 @ 1/2 2 24 3800 2910 5460 181 E96322#50HE 96 # 32000 109,280 2 @ 1/2 2 24 3800 2815 6080 189 E108483#50HE 108 # 48000 163,920 3 @ 1/2 3 24 3800 3040 7380 261 E120483#50HE 120 # 48000 163,920 3 @ 1/2 3 24 3800 2950 7920 273 E132483#50HE 132 # 48000 163,920 3 @ 1/2 3 24 3800 2875 8540 285 E144483#50HE 144 # 48000 163,920 3 @ 1/2 3 24 3800 2815 9120 297 # - INDICATE VOLTAGE: 3 = 208V 3-PH, 4 = 240V/208V 3-PH, 5 = 480V 3-PH. Note: Multiply listed wattage by .75 for actual 208V rating. Maximum 15 kilowatts per cabinet at 240V.
NUMBER AIR DELIVERY @ NOZZLE OUTLET APPROX.
3/4 HP Models
E42081#75HE 42 # 8000 27,320 1 @ 3/4 1 24 4850 3685 3480 108 E48081#75HE 48 # 8000 27,320 1 @ 3/4 1 24 4850 3595 3880 115 E60081#75HE 60 # 8000 27,320 1 @ 3/4 1 24 4850 3395 4580 131 E72162#75HE 72 # 16000 54,640 2 @ 3/4 2 24 4850 3880 6280 195 E84162#75HE 84 # 16000 54,640 2 @ 3/4 2 24 4850 3715 6960 208 E96162#75HE 96 # 16000 54,640 2 @ 3/4 2 24 4850 3595 7760 221 E108243#75HE 108 # 24000 81,960 3 @ 3/4 3 24 4850 3880 9420 288 E120243#75HE 120 # 24000 81,960 3 @ 3/4 3 24 4850 3765 10100 301 E132243#75HE 132 # 24000 81,960 3 @ 3/4 3 24 4850 3670 10900 314 E144243#75HE 144 # 24000 81,960 3 @ 3/4 3 24 4850 3595 11640 327 E42121#75HE 42 # 12000 40,980 1 @ 3/4 1 24 4850 3685 3480 108 E48121#75HE 48 # 12000 40,980 1 @ 3/4 1 24 4850 3595 3880 115 E60121#75HE 60 # 12000 40,980 1 @ 3/4 1 24 4850 3395 4580 131 E72242#75HE 72 # 24000 40,980 2 @ 3/4 2 24 4850 3880 6280 195 E84242#75HE 84 # 24000 81,960 2 @ 3/4 2 24 4850 3715 6960 208 E96242#75HE 96 # 24000 81,960 2 @ 3/4 2 24 4850 3595 7760 221 E108363#75HE 108 # 36000 81,960 3 @ 3/4 3 24 4850 3880 9420 288 E120363#75HE 120 # 36000 122,940 3 @ 3/4 3 24 4850 3765 10100 301 E132363#75HE 132 # 36000 122,940 3 @ 3/4 3 24 4850 3670 10900 314 E144363#75HE 144 # 36000 122,940 3 @ 3/4 3 24 4850 3595 11640 327 E42161#75HE 42 # 16000 122,940 1 @ 3/4 1 24 4850 3685 3480 108 E48161#75HE 48 # 16000 54,640 1 @ 3/4 1 24 4850 3595 3880 115 E60161#75HE 60 # 16000 54,640 1 @ 3/4 1 24 4850 3395 4580 131 E72322#75HE 72 # 32000 54,640 2 @ 3/4 2 24 4850 3880 6280 195 E84322#75HE 84 # 32000 54,640 2 @ 3/4 2 24 4850 3715 6960 208 E96322#75HE 96 # 32000 109,280 2 @ 3/4 2 24 4850 3595 7760 221 E108483#75HE 108 # 48000 109,280 3 @ 3/4 3 24 4850 3880 9420 288 E120483#75HE 120 # 48000 109,280 3 @ 3/4 3 24 4850 3765 10100 301 E132483#75HE 132 # 48000 163,920 3 @ 3/4 3 24 4850 3670 10900 314 E144483#75HE 144 # 48000 163,920 3 @ 3/4 3 24 4850 3595 11640 327 # - INDICATE VOLTAGE: 3 = 208V 3-PH, 4 = 240V/208V 3-PH, 5 = 480V 3-PH. Note: Multiply listed wattage by .75 for actual 208V rating. Maximum 15 kilowatts per cabinet at 240V.
2
CAUTION
THIS HEATED AIR CURTAIN AND ITS SUB-ASSEMBLIES AND CONTROLS SHOULD BE INSTALLED BY QUALIFIED PER­SONNEL, USING COPPER WIRES AND IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) AND ALL APPLICABLE LOCAL CODES AND ORDINANCES.
NOTE: A MAIN DISCONNECT OR CIRCUIT BREAKER IS REQUIRED AHEAD OF THE MAIN PANEL OF THIS HEATED AIR CURTAIN.
!
WARNING
ALWAYS DISCONNECT POWER AT THE MAIN DISCONNECT OR CIRCUIT BREAKER BEFORE INSTALLING OR SERVIC­ING THIS HEATED AIR CURTAIN. IF THE POWER DISCON­NECT IS OUT OF SIGHT OR IS LOCATED GREATER THAN 50 FEET FROM THE MAIN PANEL OF THIS HEATED AIR CURTAIN, LOCK THE MAIN DISCONNECT IN THE OPEN POSITION AND TAG IT TO PREVENT UNEXPECTED APPLI­CATION OF POWER. FAILURE TO DO SO COULD RESULT IN FATAL ELECTRICAL SHOCK.
!
When facing the inlet grille of the unit, the main control box is attached on the right side of the combination. A maximum of three supplementary 60 amp rated circuit breakers (or 60A load fuses) will be provided for units with full load rating greater than 48 amps. Field control terminal blocks are also provided with the Main Control box. A class 2 certified, 24V secondary, 75 VA control transformer is provided. Class 2 wiring may be used for controls but it is recommended to use Class 1 wiring for controls since these are usually located in a commercial-industrial environment. The load on the thermostat will always be one small relay (4VA) for heat and another relay for the fan circuit whether the unit is a sin­gle, a double or a triple cabinet installation. Any standard low volt­age (24V) heating thermostat may be used.
On the Main Control Panel are three indicator lights. These lights serve the following functions:
Top Light - Power is on to the unit. Middle Light - The heating elements are on in the unit. Bottom Light - The fan is on in the unit.
If the “HEAT ON” light is lit at the Main Control Box, the indicator light at each cabinet control compartment should also be lit. The cabinet with an unlit light in this instance will need investigation. Either the bulb is burned out or the automatic reset protective device in this cabinet has functioned and taken the heating con­tactor out of circuit. The airflow should also be checked on this cabinet. The air passageways may be blocked or the blower wheel is loose or turning in the wrong direction.
!
WARNING
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT USE THIS AIR CURTAIN WITH ANY SOLID STATE SPEED CONTROL DEVICE.
GENERAL INFORMATION
Air curtains produce a wall of continuously flowing air that acts as a thermal barrier against outside air and provides protection against insects, dust, odor, fumes and other contaminants. Air cur­tains maintain interior conditioned temperature by preventing heat­ed or cooled air from escaping through open doorways. Heated air curtains are engineered to treat incoming cold air at customers’ entrance areas. Used over front door entrances, heated air cur­tains supplement existing heat to prevent infiltration of colder out­side air. Heated units are not recommended for areas subject to high winds.
The heated air curtains covered by this Installation & Maintenance Instructions are permanently installed units intended for permanent connection to a single electrical supply source and are intended to be located over doorways at least 7 ft. above the floor. The units may be installed with zero minimum clearances from combustibles on three sides of the unit and the minimum clearance from the adjacent wall to the hinged door of the main control box is 16 inch­es.
Each cabinet employs a dual shaft motor, driving two blower type air circulators causing air flow over a heater assembly. The heater assembly consists of two sections, one section per blower. The heater assembly is controlled by contactors with 24 volt AC low voltage coils. A replaceable thermal cut-off or one shot protective device is provided on each leg of each assembly. Each section is provided with an automatic reset overheat protective device. In case of overheating, the automatic resets will shut off only the heat contactor for the heater assembly in the cabinet associated with it and not the fan contactor and thus airflow should continue. Each cabinet in a multiple cabinet installation are independent of each other as far as the operation of the auto resets are concerned. Each cabinet will have its own control compartment with a heating contactor with an indicator light and a fan contactor and the required control terminals for interconnection.
!
WARNING
DURING INITIAL POWER UP OF HEATED AIR CURTAINS, HINGED CONTROL DOOR MUST BE IN CLOSED POSITION FOR CORRECT OPERATINO OF THE PRESSURE DIFFERENTIAL SWITCH. ENERGIZING UNIT WITH DOOR OPEN MAY CAUSE PERMANENT DAMAGE TO HEATING ELEMENTS. SEE DETAILS BELOW.
Initial Start Up - Checking For Correct Fan Motor Rotation:
On all three phase units, it is essential for the units to be checked for correct fan rotatino since it is always possible the motor could be rotating backwards. Before energizing the units, make sure units are fully assembled, all wiring is correct and cabinet doors are closed. Energize units and observe air flow from exhaust. If correct, the discharge airflow will be strond and the heater ele­ments will come on in a short time to provide heaterd air. All three indicator lights will be on when the heater and fan are on. If motor rotation is backwards, interchange any two wires to the motor and check to see that the motor rotation is correct.
When Removing Blower Assembly From Cabinet(s):
If it becomes necessary to remove the blower assembly from the cabinets, care must be given to assure the sensing tube for the pressure differential switch is reassembled correctly and in the poper locations.
CAUTION
INCORRECT INSTALLATION OF THESE TUBES WILL RESULT IN THE UNITS NOT OPERATING PROPERLY AND COULD CAUSE PERMANENT DAMAGE TO UNITS
The sensing tube is provided with an in-line quick connector located near the blower assembly so the tube can be easily dis­connected and reconnected. This is the only portion of the tube that should be disturbed during this process. To separate, hold the body of the connector and push the release ring towards the center of the connector body and then pull the tube from the con­nector. To reconnect, push the tube into the connector unitil it is secured in place.
!
3
Important Note: The portion of the sensing tube that attaches to the blower has an opening that must face the blower and be posi­tioned near the center of the blower inlet. This should not be removed or disturbed during the romoval and reinstallation of the blower assembly into the cabinet. After reasembly, check to make sure this sensing tube has not been damaged or dislodged. In the control compartment, the sensing tube attaches to the “LOW” port on the pressure differential switch.
Sensing tube location
Quick connector
4. Unscrew six (6) knurled nuts and remove air intake grille. (See Figure 3)
5. Carefully disconnect motor electric cord from socket and plug assembly and remove two wing nuts on blower base. (See Figure 4)
6. Carefully disconnect pressure switch hose quick connector at blower by holding body of connector and pushing the release ring towards the center of connector while pulling the hose to disconnect.
7. To remove motor blower assembly, lift from rear of motor hous­ing to prevent damage and misalignment to shaft and blower wheels. Once the motor/blower assembly is removed, the heater assembly will be accessed.
NOTE: After unpacking unit, inspect carefully for any damage that may have occurred during transit. Check for loose, missing or dam­aged parts. The hinged cabinet wiring compartment cover should also be opened to inspect the components and wiring inside.
8. Make sure the open coil elements do not touch any metal part and all the porcelains holding the elements are not broken and are in their proper place.
Figure 3: Sensing Tube Location
When powering the unit for the first time, always check the wiring for correctness and tightness, make sure the power supply matches the nameplate rating of the unit, make sure the sensing tubes of each PD switch are in the proper position and location and all the cabinet compartment covers are closed. It is also rec­ommended that the front grille covers should be in place. This will make sure the pressure switch will sense enough vacuum and turn on heater.
Figure 3
UNPACKING
For Single Cabinet Units: 36”, 42”, 48” and 60”
1. With packaged unit on the floor, carton arrows should point upward.
2. Carefully remove staples from top of carton and fold back sides.
3. Carefully remove cabinet from carton by lifting out unit using fin­ger holes in styrofoam side inset and place on work surface.
CAUTION: Do not attempt to lift this air curtain by its louver or damage may result.
!
WARNING
MAKE SURE NO COMBUSTIBLE MATERIAL NOR ANY OTHER FOREIGN MATERIAL FALLS ON THIS HEATING ELEMENT CAVITY WHILE IT IS EXPOSED WITH THE MOTOR/ BLOWER ASSEMBLY OUT OF THE CABINET
For 2 Cabinet Units: 72”, 84” and 96” See Figure 5, Page 5
1. With packaged units on the floor, carton arrows should point upward. Cartons are marked A & B.
2.
Follow Steps 2 through 8 for Single Cabinet Units.
NOTE: Cabinet A (left), Cabinet B (right). Carton labeled Cabinet B will contain the Main Control Box and all harness wires and parts bag to interconnect the two cabinets.
For 3 Cabinet Units: 108”, 120”, 132” and 144” See Figure 6, Page 6
1. With packaged units on the floor, carton arrows should point upward. Cartons are marked A, B and C.
2.
Follow Steps 2 through 8 for Single Cabinet Units.
NOTE: CabinetA (left), Cabinet B (center), Cabinet C (right). Carton labeled Cabinet C will contain the Main Control Box and harness wires and parts bag to interconnect the three cabinets. Cabinet B may also have harness wires to inter­connect to Cabinet A.
INSTALLATION
For Single Cabinet Units:
CAUTION
THE HARDWAREAND THE SUPPORTING STRUCTURE MUST BE CAPABLE OF SUPPORTING A MINIMUM 150 LB LOAD.
!
4
Figure 4
NOTE:All installation should be done to meet local building codes.
1. Using template provided, determine mounting location.
2. Drill holes and attach mounting hardware (not included).
3. Mount cabinet on wall and securely tighten hardware.
4. Replace motor/blower assembly in cabinet. Pass pres-
sure switch hose through proper hole on blower base. Reconnect motor electric cord plug assembly.
5. Attach pressure switch hose to quick connector at right
blower housing.
6. Secure two wing nuts on blower base.
7. Replace intake grille with louvers facing down and fasten knurled nuts.
Field Power Wiring: Refer to Wiring Diagram and Nameplate.
!
WARNING
ALL HEATED AIR CURTAINS SHOULD BE INSTALLED BY QUALIFIED PERSONNEL.
1. Before wiring be sure that available power supply, voltage,
phase and frequency corresponds to that specified on unit rat­ing plate. In addition, make certain that service capacity is suf­ficient to handle load imposed by the heated air curtain.
2. Install all wiring, protection and grounding in accordance with
the National Electrical Code (NEC) and all local requirements.
3. Run proper size copper power supply conductors from the field
power supply disconnecting means (supplied by others) with insulation rated 75 degrees C minimum (167º F) to the power supply blocks provided at the Main Control Box of the air cur­tain. This field supplied disconnecting means shall be provided to disconnect the heater, motor controller(s) and any supple­mentary overcurrent protective devices from all ungrounded conductors. This disconnecting means shall be within sight of the heater, motor controller(s) or supplementary protective devices. If it is not within sight or is located greater than 50 feet, disconnecting means shall be capable of being locked in the open position.
4. The heater control box must have an unbroken electrical
ground from its Main Control Box to its field supplied discon­necting means to minimize personal injury in case an electrical fault should occur.
5. Always refer to nameplate data and wiring diagram located on
the inside of the hinged cover of the main control box for important information and other data before proceeding with wiring of the unit.
!
WARNING
THE MOTORS OF THIS HEATED AIR CURTAIN HAVE AN INTERNAL SELF RESETTING THERMAL OVERLOAD PRO­TECTOR. ALWAYS DISCONNECT FROM POWER SUPPLY BEFORE SERVICING.
NOTE: This heated air curtain is equipped with a step-down transformer 24V control circuit. Any standard 24V heating ther­mostat with or without fan control may be used. Door switches may be used to control the operation of the unit. A door switch may be connected to control the operation of the fan only or it can be connected in parallel with the heating thermostat to call for fan and heat every time the door is opened. The thermostat may call for fan and heat even when door is closed. The step down transformer is a 75 VA approved Class 2 transformer and a control knockout is provided with the control terminal blocks spaced away from power wire to allow Class 2 wiring for controls but it is recommended to use Class 1 wiring, especially to door switches to protect it from physical damage in an industrial or commercial environment.
6. Replace hinged cover of the main control box.
7. Unit is ready for operation.
8. Restore power to the unit. Call for heat through the thermostat
or through the door switch if supplied. Unit should run. Check for correct air flow.
9. Inspect unit for excessive vibration during operation. If exces-
sive vibration is noticeable, disconnect power supply. Inspect mounting installation and refer to “Trouble Shooting Chart”, page 7 for probable cause.
Field Control Wiring: Refer to Wiring Diagram, pages 8-10.
FOR INSTALLATION OF MULTIPLE CABINET AIR CURTAINS
For 2 Cabinet Units: 72”, 84” and 96” See Figure 5
CAUTION
THE HARDWAREAND THE SUPPORTING STRUCTURE MUST BE CAPABLE OF SUPPORTING A MINIMUM 300 LB LOAD.
NOTE: All installation should be done to meet local building codes.
1. Using template provided, determine mounting location for Cabinet A (left side), left of centerline.
2. Drill holes and attach mounting hardware (not included) for Cabinet A.
3. Mount Cabinet A on wall and securely tighten hard­ware.
4. Repeat steps 1,2 and 3 for mounting Cabinet B (right side), right of centerline.
5. Secure Cabinet A to Cabinet B using parts provided in installation kit. After alignment of cabinets is complet­ed, carefully secure all assembly mounting hardware.
6. Install motor/blower assembly in Cabinet A. Pass pres­sure switch hose through proper hole on blower base. Attach hose to right blower. Secure two wing nuts on blower base. Reconnect motor (A) electric cord plug assembly.
7. Install motor/blower assembly (B) in Cabinet B. pressure switch hose through proper hole on blower base. Attach hose to right blower. Secure two wing nuts on blower base. Reconnect motor (B) electric cord plug assembly.
8. Replace intake grilles with louvers facing down and refasten knurled nuts.
9. Refer to “Field Power Wiring” and “Field Control Wiring” sec­tions for single cabinet installation in this manual. All instructions and safety warnings and notes also apply to electrical connections of multiple cabinets. Additional steps are necessary only for harness connections of Cabinet A to Cabinet B and/or to the Main Control Box.
10. Refer to wiring diagram on the inside of the hinged cover of
the Main Control Box and to applicable wiring diagrams in this manual. Harness wires are provided with the right ends of the harness wires already connected to the unit and the installer has to connect the left ends of the harness wires to the correct terminal points as shown in the diagram. The Cabinet wiring compartment covers will have to be opened. These covers are also hinged to the cabinets. Route and locate wiring and wire strap the wires as shown in Figure 9, page 7 and allow for the movement of the wires as the covers are opened and closed.
11. Replace all hinged covers.
12. Unit is ready for operation.
13. Restore power to the unit. Call for heat through the thermo­stat or through the door switch if supplied. Unit should run. Check for correct air flow.
14. Inspect unit for excessive vibration during operation. If excessive vibration is noticeable, disconnect power supply. Inspect mounting installation and refer to “Trouble Shooting Chart”, page 7 for probable cause.
Cabinet A
Figure 5
Cabinet B
!
Pass
5
For 3 Cabinet Units: 108”, 120”, 132” and 144” See Figure 6
CAUTION
THE HARDWAREAND THE SUPPORTING STRUCTURE MUST BE CAPABLE OF SUPPORTING A MINIMUM 500 LB LOAD.
NOTE: All installation should be done to meet local building codes.
1. Determine mounting location of center cabinet (See Figure 6).
2. Using template provided, determine mounting location for Cabinet A (left side), left of center cabinet.
3. Drill holes and attach mounting hardware (not included) for Cabinet A.
4. Mount Cabinet A on wall and securely tighten hardware.
5. Repeat steps 1, 2, 3 and 4 for mounting Cabinet B (center).
6. Repeat steps 1, 2, 3 and 4 for mounting Cabinet C (right), right of center cabinet.
7. Secure Cabinet A to Cabinet B to Cabinet C using parts pro­vided in installation kit. After alignment of cabinets is com­pleted, carefully secure all assembly mounting hardware.
8. Install motor/blower assembly (A) in Cabinet A. Pass pres­sure switch hose through proper hole on blower base. Attach hose to right blower. Secure two wing nuts on blower base. Reconnect motor (A) electric cord plug assembly.
9. Install motor/blower assembly (B) in Cabinet B. Pass pres­sure switch hose through proper hole on blower base. Attach hose to right blower. Secure two wing nuts on blower base. Reconnect motor (B) electric cord plug assembly.
10. Install motor/blower assembly (C) in Cabinet C. Pass pres­sure switch hose through proper hole on blower base. Attach hose to right blower. Secure two wing nuts on blower base. Reconnect motor (C) electric cord plug assembly.
11. Replace intake grilles with louvers facing down and fasten knurled nuts.
12. Refer to “Field Power Wiring” and “Field Control Wiring” sections, page 5 for single cabinet installation in this manual. All instruction and safety warning and notes also apply to electrical connections of multiple cabinets. Additional steps are necessary only for harness connection of Cabinet A to Cabinet B and Cabinet B to Cabinet C and/or to the Main control Box.
13. Refer to wiring diagram on the inside of the hinged cover of the Main control Box and to applicable wiring diagrams in this manual. Harness wires are provided with the right ends of the harness wires already connected to the unit and the installer has to connect the left ends of the harness wires to the correct terminal points as shown in the diagram. The cabinet wiring compartment covers will have to be opened. These covers are also hinged to the cabinets. Route and locate wiring and wire strap the wires as shown in Figure 9 and allow for the movement of the wires as the hinged covers are opened and closed.
14. Replace all hinged covers.
15. Unit is ready for operation.
16. Restore power to the unit. Call for heat through the thermo­stat or through the door switch if supplied. Unit should run. Check for correct air flow.
17. Inspect unit for excessive vibration during operation. If excessive vibration is noticeable, disconnect power supply. Inspect mounting installation and refer to “Trouble Shooting Chart” page 7 for probable cause.
!
OPERATION
1. After power has been connected to unit, unit is ready to respond to its control devices such as the thermostat or door switches.
2. Air direction at outlet can be controlled by adjustable vanes at the nozzle which compensates for possible draft condi­tions.
NOTE: Air direction settings shown in Figures 7 & 8. NOTE: Cold air will try to escape near top of doorway. Air flow
can be controlled by direction of nozzle louvers. NOTE: Each unit is supplied with an air flow probing switch which
is located in each cabinet compartment and this is supplied with a hose located in the suction side of the blower. A blower turning in the wrong direction may be prevented from turning the heat on by this switch.
Figure 7 - Desired air flow adjustment for temperature and humidity control.
Figure 8 - Desired air flow adjustment for insect and dust control.
MAINTENANCE
!
WARNING
ALL ELECTRICAL POWER MUST BE DISCONNECTED WHEN INSTALLING OR SERVICING THIS EQUIPMENT. MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED TO REMOVE POWER FROM THE UNIT.
NOTE: Ball bearings are permanently lubricated and require no further lubrication.
Cleaning:
1. The air curtain cabinet(s) may be wiped off with a damp cloth. Do not allow motor to get wet. Do not use solvents or harsh detergents.
NOTE: Keep air intake louvers clear of dirt and dust accumula­tion which could affect performance.
2. Check blower wheels for accumulated dirt twice a year and clean. If disassembly is required, see “General Servicing” section.
6
Cabinet A
Figure 6
Cabinet B
Cabinet C
GENERAL SERVICING
!
WARNING
IF SERVICE IS REQUIRED, IT SHOULD BE DONE BY QUALIFIED PERSONS ONLY.
ALWAYS DISCONNECT POWER SUPPLY BEFORE SERVICING
1. To remove motor/blower assembly, repeat steps 4, 5, 6 and 7 in “Unpacking” section.
2. Place motor/blower assembly on workbench.
3. To replace blower wheel, remove the three slotted hex head screws on outer blower ring assembly (See Figure 10, Replacement Parts Illustration). The wheel is held onto shaft by two hex head screws.
4. To remove motor: a. Remove blower wheels. (See Step 3 above). b. Remove blower scroll (six hex head screws). c. Unscrew and remove motor mounts.
6. To replace heater assembly: Do the reverse of Step 5 above. NOTE: To re-assemble, repeat steps 4, 5 and 6 in installation
section for single cabinet units.
7. Replace motor/blower assembly.
IMPORTANT
NOTE POSITION OF WHEELS TO PREVENT RUBBING WHEN REPLACED.
5. To remove heater assembly: a. Remove blower wheels. (See Step 3 above). b. Remove heater assembly (two screws). Disconnect two yellow wires and blue, black and red wires from heating con­tactor. Pass wires through bushing as you pull out the heater assembly.
!
Figure 9 - Main control box cover & cabinet compartment cover shown open and with air intake grille removed.
TROUBLE SHOOTING CHART
Symptom Possible Cause Corrective Action
Fan inoperative 1. Blown fuse or open circuit breaker. 1. Replace fuse or reset circuit breaker
2. Electricity turned off. 2. Contact local power company.
3. Loose motor cord connection. 3. Re-check all connections.
4. Thermostat off/defective 4. Call for fan/Replace.
5. Defective fan relay/contactor. 5. Replace.
6. Defective fan relay/contactor. 6. Replace.
7. Defective capacitor (1 phase unit only) 7. Replace.
8. Defective motor. 8. Replace.
9. Wrong wiring. 9. Correct wiring.
Excessive noise 1. Wheel rubbing on housing. 1. Center wheel.
2. Motor base/blower loose. 2. Tighten mounting bolts.
3. Defective motor bearings. 3. Replace motor.
Insufficient air flow 1. Improper voltage. 1. Reconnect proper voltage or exchange unit
with proper voltage rating.
2. Outlet louvers closed. 2. Open louvers
3. Intakes obstructed. 3. Remove any obstruction.
4. Dirty blower wheels. 4. Clean.
5. Motor in reverse rotation. 5. Interchange red & black power leads.
Fan cuts out on thermal 1. Low voltage. 1. Check voltage/Use correct wire size. overload (self-resets) 2. Obstruction to blower wheel. 2. Remove obstruction.
No heat 1. Fuse link open. 1. Replace w/ G5AM0400117C
2. Heater element broken. 2. Replace w/ proper Ga and watts.
3. Control transformer open 3. Check wiring /Reset control breaker
4. Auto reset functioned* 4. Wait to reset/check for insufficient airflow.
*Heat indicator light On (Main Panel) BUT heat indicator light OFF (Cabinet) 4a. Auto reset functioned possibly due 4a. Remove cause of overheat/wait to reset.
to overheating.
4b. Air flow switch not closing its 4b. Check hose/switch/wiring & check for
normally open contact. insufficient air flow.
5. Heat Indicator light OFF (Main Panel) 5. Adjust/check thermostat. thermostat not calling for heat.
7
*
SEE
CHART
PLUG/SOCKET
CONNECTOR
K
W LOAD PER UNIT:
480
16 16
12 12
88
208
11.25 11.25
99
66
240
15 15
12 12
88
VOLTS
1/2 HP 3/4 HP
5
075
M
OTOR CODE
R
L
1L2L3
G
32
1
PLPLPL
R1 R1 R2
FU
T
G
MAIN PANEL
G
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
NO
C
FROM HEATER
B
LK
YEL
BLU
FR1 HR1
T
1
FR1
HR1
4
PL
T
2
PDS1
PWB1
CABINET COMPONENTS PANEL
G
WH F C
PWB1
LEGEND
A1, A2..............AUTOMATIC RESET PROTECTION
R1....................HEATINGRELAY
R
2....................FAN RELAY
HR1 .................HEATINGCONTACTOR
FR1..................FAN CONTACTOR
T
......................CONTROL TRANSFORMER
FU....................CONTROL FUSE
PL1, PL4..........PILOT LIGHT, HEATON
PL2..................PILOT LIGHT, POWER ON
PL3..................PILOT LIGHT, FAN ON
G......................GROUND LUG
L1L2L3 ............POWER TERMINAL BLOCKS
RGWHFC ........CONTROL TERMINAL BLOCKS
HHFFCC..........CONTROL TERMINAL BLOCKS
PWB1 ..............POWER WIRE BUNDLE (MAIN TO UNIT 1)
CWB1..............CONTROL WIRE BUNDLE (MAIN TO UNIT 1)
PDS1...............PRESSURE DIFFERENTIAL SWITCH
R
G
W
THERMOSTAT (FIELD INSTALLED)
C
WB1
DOOR SWITCH
(FIELD
INSTALLED)
FIELD WIRING
*
CONNECTION CHART FOR PRIMARY OF
M
ULTIPLE TAP TRANSFORMER:
V
OLTAGE: CONNECTION:
2
08 V BLACK AND RED
2
40 V BLACK AND ORANGE
4
80 V BLACK AND BLK/RED
T
3
R
2
R1
L1 L2 L3
* SEE CHART
PLUG/SOCKET CONNECTOR
(NO. OF UNITS) X KW LOAD PER UNIT:
480
(2) X 16
(2) X 16
(2) X 12
(2) X 12
(2) X 8
(2) X 8
208
(2) X 6 (2) X 6
240
(2) X 8
VOLTS
1/2 HP
3/4 HP
50
75
MOTOR CODE
R
L1 L2 L3
G
R2 R1 R1 R2
FU
T
G
MAIN PANEL
G
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
NO
C
G
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
NO
C
FROM HEATER FROM HEATER
BLK
YEL
BLU
FR2 HR2
T1
FR2
HR2
T2 T3
FR1 HR1
T1
FR1
HR1
T2 T3
PDS2 PDS1
PWB1
CWB2
CABINET COMPONENTS PANEL1
CWB1
FWB1
CABINET COMPONENTS PANEL2
CWB2
FWB1
GWHFC
PWB1
LEGEND
A1,A2....................AUTOMATIC RESET PROTECTION
R1.........................HEATING RELAY
R2.........................FAN RELAY
HR1, HR2 .............HEATING CONTACTORS
FR1, FR2..............FAN CONTACTORS
T...........................CONTROL TRANSFORMER
FU.........................CONTROL FUSE
PL1, PL4, PL5 ......PILOT LIGHT, HEAT ON
PL2.......................PILOT LIGHT, POWER ON
PL3.......................PILOT LIGHT, FAN ON
G...........................GROUND LUG
L1L2L3 .................POWER TERMINAL BLOCKS
RGWHFC .............CONTROL TERMINAL BLOCKS
HHFFCC...............CONTROL TERMINAL BLOCKS
PWB1 ...................POWER WIRE BUNDLE (MAIN TO UNIT 1)
FWB1....................FAN CONTACTOR WIRE BUNDLE (FR1 TO UNIT 2
CWB1...................CONTROL WIRE BUNDLE (MAIN TO UNIT 1)
CWB2...................CONTROL WIRE BUNDLE (UNIT 1 TO UNIT 2)
PDS1, PDS2.........PRESSURE DIFFERENTIAL SWITCH
*CONNECTION CHART FOR PRIMARY OF MULTIPLE TAP TRANSFORMER:
VOLTAGE: CONNECTION: 208 V BLACK AND RED 240 V BLACK AND ORANGE 480 V BLACK AND BLK/RED
R
G
W
THERMOSTAT (FIELD INSTALLED)
CWB1
DOOR SWITCH (FIELD INSTALLED)
FIELD WIRING
R1
BLU
L1 L2 L3
L1 L2 L3
32
1
PLPLPL
4
PL
5
PL
(2) X 8
WIRING DIAGRAM: 240V, 208V, 480V - Single cabinet, 8KW, 12KW and 16KW
WIRING DIAGRAM: 240V, 208V, 480V - Two cabinets, 8KW, 12KW and 16KW
8
*
SEE
C
HART
PLUG/SOCKET
CONNECTOR
(
NO. OF UNITS) X KW LOAD PER UNIT:
480 (3) X 12 (3) X 12
(3) X 8(3) X 8
VOLTS 1/2 HP 3/4 HP
50 75
M
OTOR CODE
R
L1 L2 L3
G
321
PLPLPL
R2 R1 R1 R2
F
U
T
G
MAIN PANEL
G
H H F F C C
F
ROM MOTOR
Y
EL
YEL
A
1
A
2
N
O
C
G
H H F F C C
F
ROM MOTOR
Y
EL
Y
EL
A
1
A
2
NO
C
G
FR3
H
R3
T
1
F
R3
HR3
6
PL
H H F F C C
F
ROM MOTOR
YEL
YEL
A
1
A
2
P
DS3
NO
C
F
ROM HEATER FROM HEATER FROM HEATER
BLK
YEL
BLU
T
2T3
F
R2
H
R2
T1
F
R2
HR2
5
PL
T2 T3
FR1
HR1
T
1
F
R1
HR1
4
PL
T
2T3
P
DS2 PDS1
PWB1
CWB2
CABINET COMPONENTS PANEL 1
CWB1
FWB1
CWB3
CABINET COMPONENTS PANEL2
C
WB2
FWB2
CABINET COMPONENTS PANEL 3
CWB3
FWB2
F
WB1
G
WH F C
PWB1
LEGEND
A1,A2...................AUTOMATICRESET PROTECTION
R
1......................HEATING RELAY
R2......................FAN RELAY
H
R1, HR2, HR3...........HEATING CONTACTORS
FR1, FR2, FR3...........FAN CONTACTORS
T
.. .....................CONTROL TRANSFORMER
F
U......................CONTROL FUSE
PL1, PL4, PL6...........PILOT LIGHT, HEAT ON
P
L2.....................PILOT LIGHT, POWERON
PL3.....................PILOT LIGHT, FAN ON
G.......................GROUND LUG
L1L2L3..................POWER TERMINAL BLOCKS
RGWHFC..................CONTROL TERMINAL BLOCKS
HHFFCC..................CONTROL TERMINAL BLOCKS
PWB1....................POWER WIRE BUNDLE (MAIN TO UNIT 1)
FWB1....................FAN CONTACTOR WIRE BUNDLE (FR1 TO UNIT 2)
FWB2....................FAN CONTACTOR WIRE BUNDLE (FR2 TO UNIT 3)
CWB1....................CONTROL WIRE BUNDLE (MAIN TO UNIT 1)
CWB2....................CONTROL WIRE BUNDLE (UNIT 1 TO UNIT 2)
CWB3....................CONTROL WIRE BUNDLE (UNIT 2 TO UNIT 3)
PDS1, PDS2, PPDS3.......PRESSURE DIFFERENTIAL SWITCH
*CONNECTION CHART FOR PRIMARY OF MULTIPLE TAP TRANSFORMER:
V
OLTAGE: CONNECTION:
480 V BLACK AND BLK/RED
R
G
W
THERMOSTAT (FIELD INSTALLED)
CWB1
DOOR SWITCH (FIELD INSTALLED)
FIELD WIRING
R1
BLU
L
1 L2 L3
L
1
L
2
L
3
L
1
L
2
L
3
* SEE CHART
PLUG/SOCKET
CONNECTOR
(NO. OF UNITS) X KW LOAD PER UNIT:
208
(2) X 11.25 (2) X 11.25
(2) X 9 (2) X 9
240
(2) X 15 (2) X 15
(2) X 12 (2) X 12
VOLTS 1/2 HP 3/4 HP
50 75
MOTOR CODE
R
L1 L2 L3
G
321
PLPLPL
R2 R1 R1 R2
FU
T
G
MAIN PANEL
G
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
NO
C
G
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
NO
C
FROM HEATER FROM HEATER
BLK
YEL
BLU
FR2 HR2
T1
FR2
HR2
5
PL
T2
T3
FR1 HR1
T1
FR1
HR1
4
PL
T2 T3
PDS2 PDS1
BWB1
CWB2
CABINET COMPONENTS PANEL 1
CWB1
BWB2
CABINET COMPONENTS PANEL2
CWB2
GWHFC
BWB1
LEGEND
A1,A2...............AUTOMATIC RESET PROTECTION
R1....................HEATING RELAY
R2....................FAN RELAY
CB1, CB2.........CIRCUIT BREAKERS
HR1, HR2 ........HEATING CONTACTORS
FR1, FR2.........FAN CONTACTORS
T......................CONTROL TRANSFORMER
FU....................CONTROL FUSE
PL1, PL4, PL5.PILOT LIGHT, HEAT ON
PL2..................PILOT LIGHT,POWER ON
PL3..................PILOT LIGHT,FAN ON
G......................GROUND LUG
L1L2L3 ............POWER TERMINAL BLOCKS
RGWHFC ........CONTROL TERMINAL BLOCKS
HHFFCC..........CONTROL TERMINAL BLOCKS
BWB1 ..............C-BREAKER WIRE BUNDLE (BRKR 1 TO UNIT 1)
BWB2 ..............C-BREAKER WIRE BUNDLE (BRKR 2 TO UNIT 2)
CWB1..............CONTROL WIRE BUNDLE (MAIN TO UNIT 1)
CWB2..............CONTROL WIRE BUNDLE (UNIT 1 TO UNIT 2)
PDS1, PDS2....PRESSURE DIFFERENTIAL SWITCH
*CONNECTION CHART FOR PRIMARY OF MULTIPLE TAP TRANSFORMER:
VOLTAGE: CONNECTION: 208 V BLACK AND RED 240 V BLACK AND ORANGE
R
G
W
THERMOSTAT (
FIELD INSTALLED)
CWB1
DOOR SWITCH (FIELD INSTALLED)
F
IELD WIRING
CB1 CB2
BWB2
R1
BLU
L1 L2 L3
L1
L2
L3
WIRING DIAGRAM: 480V - Three cabinets, 8KW and 12KW
WIRING DIAGRAM: 240V, 208V - Two cabinets, 8KW, 12KW and 15KW
9
* SEE CHART
PLUG/SOCKET
C
ONNECTOR
(
NO. OF UNITS) X KW LOAD PER UNIT:
208
(3) X 11.25 (3) X 11.25
(3) X 9 (3) X 9
(3) X 6 (3) X 6
2
40
(
3) X 15 (3) X 15
(
3) X 12 (3) X 12
(3) X 8 (3) X 8
V
OLTS
1/2 HP 3/4 HP
50 75
M
OTOR CODE
R
L1 L2 L3
G
PLPLPL
R
1
R1 R2
FU
T
G
MAIN PANEL
G
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
NO
C
G
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
NO
C
G
FR3
H
R3
T
1
FR3
HR3
H H F F C C
FROM MOTOR
YEL
YEL
A1
A2
PDS3
NO
C
FROM HEATER FROM HEATER FROM HEATER
B
LK
YEL
BLU
T
2 T3
F
R2
HR2
T
1
FR2
HR2
5
PL
T
2 T3
F
R1
HR1
T1
FR1
HR1
4
PL
T2 T3
P
DS2
PDS1
BWB1
CWB2
CABINET COMPONENTS PANEL 1
CWB1
BWB2
CWB3
CABINET COMPONENTS PANEL 2
CWB2
B
WB3
CABINET COMPONENTS PANEL 3
CWB3
G
W H F C
BWB1
*CONNECTION CHART FOR PRIMARYOF MULTIPLE TAP TRANSFORMER:
VOLTAGE: CONNECTION: 208 V BLACK AND RED 240 V BLACK AND ORANGE
R
G
W
T
HERMOSTAT
(FIELD INSTALLED)
CWB1
DOOR SWITCH (FIELD INSTALLED)
FIELD WIRING
CB1 CB2 CB3
BWB2 BWB3
R
2
R1
BLU
L1 L
2
L3
L
1 L2 L3
L
1 L2 L3
1
2 3
L
EGEND
A
1, A2...................AUTOMATIC RESET PROTECTION
R
1.........................HEATING RELAY
R
2.........................FAN RELAY
C
B1, CB2, CB3.....CIRCUIT BREAKERS
H
R1, HR2, HR3....HEATING CONTACTORS
F
R1, FR2, FR3.....FAN CONTACTORS
T
...........................CONTROL TRANSFORMER
F
U.........................CONTROL FUSE
PL1, PL4, PL6 ......PILOT LIGHT, HEAT ON
PL2.......................PILOT LIGHT, POWER ON
PL3.......................PILOT LIGHT, FANON
G...........................GROUND LUG
L1L2L3 .................POWER TERMINAL BLOCKS
RGWHFC .............CONTROL TERMINAL BLOCKS
HHFFCC...............CONTROL TERMINAL BLOCKS
BWB1 ...................FUSEBLOCK WIRE BUNDLE (FB1 TO UNIT 1)
BWB2 ...................FUSEBLOCK WIRE BUNDLE (FB2 TO UNIT 2)
CWB1...................CONTROL WIRE BUNDLE (MAIN TO UNIT 1)
CWB2...................CONTROL WIRE BUNDLE (UNIT 1 TO UNIT 2)
CWB3...................CONTROL WIRE BUNDLE (UNIT 2 TO UNIT 3)
PDS1, PDS2, PPDS3 PRESSURE DIFFERENTIAL SWITCH
6
PL
WIRING DIAGRAM: 240V, 208V - Three cabinets, 8KW, 12KW and 15KW
WIRING DIAGRAM: 480V - Three cabinets, 16KW
10
5
E
4808-1550
HE
C
FID: XXXXXXXXXX
MODEL NO.
D
ATECODE
0105
48” 480V HEATEDAIR CURTAIN
WARNING- RISK OF FIRE. DO NOT USE AS A RESIDENTIAL OR HOUSEHOLD HEATER.
480-3
480-3
8
MOTOR VOLTS-PH
HEATER VOLTS-PH
HEATER KW
60 HZ, .5 AMPS
60 HZ
10.12
16
15
TOTAL AMPS
MIN. CIR. AMPACITY
MAX CURRENT PROTECTION
AUTOMATICALLY OPERATED DEVICE. TO REDUCE THE RISK OF INJURY, DISCONNECT FROM POWER BEFORE SERVICING.
M
ARLEY ENGINEERED PRODUCTS
BENNETTSVILLE, SC 29512 USA
4104-2221-048
LISTED AIR HEATER
9900268
4
3
2
1
Figure 10 Replacement Parts List for Air Curtain Cabinets
Ref.
No. Description
1 Cabinet Intake Grille 2 Electric Box Cover 3 Front Control Panel 4 Motor Assembly
5 Heater Element Set 6 Cabinet Box Assembly
7 Main Control Panel
6
7
Nameplate
SAMPLE
For Replacement Parts please call for assistance 1-800-642-4328. Please have the Configuration ID number for the specific unit. The Configuration ID (example- CFID: XXXXXXXXXX) is a ten digit number found on the nameplate in the upper right just below the date code . (Refer to sample nameplate at right)
11
All products manufactured by Marley Engineered Products are warranted against defects in workmanship and materials for eighteen months from date of installation. This
LIMITED WARRANTY
warranty does not apply to damage from accident, misuse, or alteration; nor where the connected voltage is more than 5% above the nameplate voltage; nor to equipment improperly installed or wired or maintained in violation of the product’s installation instructions. All claims for warranty work must be accompanied by proof of the date of installation.
The customer shall be responsible for all costs incurred in the removal or reinstallation of products, including labor costs, and shipping costs incurred to return products to Marley Engineered Products Service Center.Within the limitations of this warranty, inoperative units should be returned to the nearest Marley authorized service center or the Marley Engineered Products Service Center, and we will repair or replace, at our option, at no charge to you with return freight paid by Marley. It is agreed that such repair or replacement is the exclusive remedy available from Marley Engineered Products.
THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT. MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT, WHETHER BASED UPON NEGLIGENCE, TORT, STRICT LIABILITY, OR CONTRACT.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above exclusion or limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
For the address of your nearest authorized service center, contact Marley Engineered Products in Bennettsville, SC, at 1-800-642-4328. Merchandise returned to the facto­ry must be accompanied by a return authorization and service identification tag, both available from Marley Engineered Products. When requesting return authorization, include all catalog numbers shown on the products.
HOW TO OBTAIN WARRANTY SERVICE AND WARRANTY PARTS PLUS GENERAL INFORMATION
1. Warranty Service or Parts 1-800-642-4328
2. Purchase Replacement Parts 1-800-654-3545
3. General Product Information www.marleymep.com
Note: When obtaining service always have the following:
1. Model number of the product
2. Date of manufacture
3. Part number or description
Part No. 5200-2644-002
ECR 38002
2/09
12
Loading...