Qmark EFF User Manual

Accessories
Cat. No. Description
F-PE Pneumatic/Electric Switch. Factory set at 10 psig (69 kPa) to
“make” on pressure drop. May be field wired to “break” on pressure drop. Pressure set point adjustable to 30 psig (207 kPa).
F-R2 (24V) Time Delay Relay. 45-60 seconds to close when energized. F-R12 (120V) Uses 120V or 24V power supply from remote source.
Painted White.
F-T1 Single pole built-in thermostat kit. FF-T2 Double pole built-in thermostat kit. F-TR4 208/240V Primary Transformer/24V Sec. and 24V Holding
Coil Control Relay.
F-TR7 277V Primary Transformer/24V Sec. and 24V Holding Coil
Control Relay.
Installation of Recessed Mounted
Heater in Plaster Ceiling
1. Determine the desired mounting location of the heater.
2. Cut a 14-1/2 inch (368mm) by 18-3/8 inch (467mm) hole in
the ceiling for the recessed back box, maintain 12 inch (305mm) minimum distance between edge of hole and adja­cent wall.
WARNING
THIS INSTRUCTION SHEET CONTAINS VITAL INFORMATION FOR THE PROPER INSTALLATION, USE, AND EFFICIENT OPERATION OF THE HEATER. CAREFULLY READ THE MANU­AL BEFORE INSTALLATION, OPERATION, OR CLEANING OF THE HEATER. FAILURE TO ADHERE TO THE INSTRUCTIONS COULD RESULT IN FIRE, ELECTRICAL SHOCK, DEATH, SERI­OUS PERSONAL INJURY OR PROPERTY DAMAGE. SAVE THESE INSTRUCTIONS AND REVIEW FREQUENTLY FOR CON­TINUING SAFE OPERATION AND INSTRUCTING FUTURE USERS.
1. To prevent a possible electrical shock, disconnect all power coming to heater at main service panel before wiring or ser­vicing.
2. All wiring must be in accordance with the National and Local Electrical Codes and the heater must be grounded as a pre­caution against possible electrical shock.
3. Verify the power supply voltage coming to the heater match­es the ratings printed on the heater nameplate before energiz­ing.
4. Do not install the heater closer than 12 inches (305mm) to any wall.
5. Do not operate heater without front cover installed.
6. This heater is hot when in use. To avoid burns, do not let bare skin touch hot surfaces.
7. Do not insert or allow foreign objects to enter any ventilation or exhaust openings as this may cause an electric shock, fire, or damage to the heater.
8. To prevent a possible fire, do not block air intakes or exhaust in any manner. Keep combustible materials, such as boxes, crates, etc., away from heater.
9. A heater has hot and arcing or sparking parts inside. Do not use it in areas where gasoline, paint or flammable liquids are used or stored.
10. Use this heater only as described in this manual. Any other use not recommenced by the manufacturer may cause fire, electric shock, or injury to persons.
11. This heater is not approved for use in corrosive atmospheres such as marine, green house or chemical storage areas.
Specifications
Cat. No. Volts Watts BTU/Hr. Amps
F-1500 120 1500 51,195 12.5 F-2008 208 2000 6826 9.8 F-2004 240/208 2000/1500 6826/5120 8.3/7.2 F-2007 277/240 2000/1500 6826/5120 7.2/8.2 F-1507 277 1500 5120 5.4 F-4008 208 4000 13,652 19.2 F-4004 240/208 4000/3000 13,652/10,239 16.7/14.4 F-4007 277/240 4000/3000 13,652/10,239 14.4/12.5 F-3007 277 3000 10,239 10.8 F-4804 240/208 4800/3600 16,382/12,287 20.0/17.3 F-4807 277/240 4800/3600 16,382/12,287 17.3/15.0
CONTRACTOR
PLEASE READ AND FOLLOW THESE INSTRUC­TIONS. LEAVE INSTALLATION INSTRUCTIONS FOR USER TO READ.
FAN DELAY NOTE: A fan delay is standard on all units. In order to have the fan delay operate correctly, separate wiring is required between the heater and the wall thermostat. See warning, page 2.
RISK OF FIRE - DO NOT INSTALL HEATER CLOSER THAN 12 INCHES (305mm) FROM ANY WALL.
RISK OF FALLING - THE HEATER BACK BOX MUST BE SECURELY MOUNTED TO THE BUILDING STRUCTURE AND THE BUILDING STRUCTURE MUST BE CAPABLE OF SUP­PORTING THE HEATER WITH ALL ACCESSORIES. THE HEATER WEIGHT IS AT LEAST 20 POUNDS (9 kg).
WARNING
Installation Instructions
and
RENEWAL PARTS IDENTIFICATION
“F” Series
Ceiling Mounted Fan-Forced Heater
1
FILE #E21609
3. Bring the power supply cable to the heater location providing
at least 12 inches (305mm) of cable for wiring.
4. Remove front cover and heater assembly from carton. NOTE: Screws to mount the front cover are packed sepa-
rately in an envelope. The kit contains four standard cross recess screws and four spanner head screws in case tam­per resistance is required.
5. Remove the heater assembly and disconnect switch assem-
bly from the back box.
6. Remove the desired knockout from the back box in the area
behind the disconnect switch, install cable clamp and bring power supply cable into box leaving at least six inches of cable in box for wiring.
7. Fit heater back box into hole in ceiling and secure in position
using mounting holes in side of back box with four fasteners (not provided). See WARNING at beginning of this section.
8. If there are any accessories to be installed with this heater,
these should be installed at this time. Refer to the instruc­tions provided with the accessories.
9. Remove the wiring compartment cover from heater assem-
bly by removing two screws. Mount the heater to the back box using four screws previously removed in step 5.
10. Attach the supply ground conductor to the green colored
screw in the heater back box.
11. Connect the power supply lead wires to the blue colored
lead wires on the disconnect switch using appropriately sized wire connectors. See Wiring Diagram, Figure 1.
12. Feed the heater (or accessory if provided) lead wires
through the smooth hole in the disconnect switch bracket and connect these leads to the black colored lead wires from the disconnect switch using appropriately sized wire connectors.
13. Carefully bundle lead wires under disconnect switch brack-
et and secure bracket to back box using two screws removed in step 5.
14. Install the wiring compartment cover removed in step 9.
Push the disconnect switch to the “ON” position.
15. Install the front cover using the four standard cross recess
or the spanner tamper resistant screws provided with the heater.
Installation of Heater Using the Cat. No. F-SM
Surface Mounting Frame
1. Determine the desired location for the heater.
2. Follow steps 3, 4, 5, and 6 of the “Installation of Recessed
Mounted Heater in Plaster Ceiling” instructions.
NOTE: The power supply cable must be routed between the heater back box and the surface mounting frame.
3. Mount the back box to the ceiling using mounting holes in
the back of the back box and four fasteners (not provided). See WARNING above.
4. Fit the Cat. No. F-SM Surface Mounting Frame over the
back box and secure in place with the two screws provided in kit.
5. Complete the installation by following steps 8 through 15 of
the “Installation of Recessed Mounted Heater in Plaster Ceil­ing” instructions.
Installation of Heater in T-Bar Ceiling
Using the Cat. No. F-TBF Kit
1. Determine the desired location for the heater.
2. Remove heater from carton, remove front cover, heater
assembly and disconnect switch from back box as described in steps 4 and 5 of the “Installation of Recessed Mounted Heater in Plaster Ceiling” instructions.
3. Mount the heater back box to the F-TBF kit frame using the
four screws provided with kit. See Figure 2.
4. Place the F-TBF frame with heater back box installed in ceil-
ing framing and secure in position. Secure the frame to the building structure as necessary using appropriate wire to prevent the heater and frame from falling.
5. Bring power supply cable to heater location, remove the
desired knockout in back box and install cable using an appropriate cable clamp, leaving at least six inches (150mm) of wire in box for connections.
NOTE: Power supply cable must enter back box in loca­tion behind the disconnect switch assembly.
6. Complete the installation by following steps 8 through 15 of
the “Installation of Recessed Mounted Heater in Plaster Ceil-
ing” instructions.
RISK OF FIRE - DO NOT INSTALL HEATER CLOSER THAN 12 INCHES (305mm) FROM ANY WALL.
RISK OF FALLING - THE HEATER BACK BOX MUST BE SECURELY MOUNTED TO THE BUILDING STRUCTURE AND THE BUILDING STRUCTURE MUST BE CAPABLE OF SUP­PORTING THE HEATER WITH ALL ACCESSORIES. THE HEATER WEIGHT IS AT LEAST 20 POUNDS (9 kg).
WARNING
TO REDUCE RISK OF FIRE OR PERMANENT DAMAGE TO HEATER, THERMOSTAT MUST NOT CUT POWER TO FAN. THERMOSTAT MUST BE WIRED AS SHOWN IN WIRING DIA­GRAM SO THAT IT CYCLES HEATING ELEMENTS ONLY.
WARNING
Figure 1
Figure 2
2
RISK OF FIRE - DO NOT INSTALL HEATER CLOSER THAN 12 INCHES (305mm) FROM ANY WALL.
RISK OF FALLING - THE HEATER BACK BOX MUST BE SECURELY MOUNTED TO THE BUILDING STRUCTURE AND THE BUILDING STRUCTURE MUST BE CAPABLE OF SUP­PORTING THE HEATER WITH ALL ACCESSORIES. THE HEATER WEIGHT IS AT LEAST 20 POUNDS (9 kg).
WARNING
Loading...
+ 2 hidden pages