Qmark DSH User Manual [en, es, fr]

CSH and DSH
Commercial Sill Height Convection Heaters (Type CSH)
Convectors
Decorative Sill Height Convection Heaters (Type DSH)
Installation, Operation & Maintenance Instructions
IMPORTANT INSTRUCTIONS
GENERAL
This heater is designed to provide years of efficient, trouble free operation as a primary or supplementary heat source for comfort heating in residential and commercial applications. CSH and DSH convector heaters must be thermostatically controlled for efficient, safe operation. A thermostat is not provided with this heater. However, a single or double pole thermostat accessory is available for installation into this heater at your place of purchase, or the heater may be connected to any suitable wall mounted thermostat that will meet the electrical load requirements. Installation or use of this product in any manner not described herein will void the warranty and could result in injury, damage to property, or permanent damage to heater.
WARNING
WHEN USING ELECTRICAL APPLIANCES, BASIC PRECAU­TIONS SHOULD ALWAYS BE FOLLOWED TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, AND INJURY TO PERSONS, INCLUDING THE FOLLOWING:
2. A heater has hot and arcing or sparking parts inside. Do not use in areas where gasoline or flammable liquids are used or stored. Do not use in corrosive environment or any area where explosive materials are used or stored.
3. This heater is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture, pillows, bedding, papers, clothes, and cur­tains away from heater.
RECEIVING
Material when shipped was in good order and Marley Engineered Products holds clear bill of lading, therefore any concealed damage must be reported at once to the carrier for inspection and settlement.
SAVE THESE INSTRUCTIONS
!
4. To prevent a possible fire, do not block air intakes or exhaust in any manner.
5. Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock or fire, or damage the heater.
6. Serious injury or death could result from electric shock. Make sure electrical power supply circuit coming to heater is disconnected at main disconnect or service panel before installing or servicing this heater.
This heater is not for residential or household use.
7.
Note:
It is advisable to store cartons in a central area to be drawn upon as needed per room requirements. If called for on order, the cartons will have been tagged with proper room number.
SPECIFICATIONS
Table A
Model CSH05A, DSH05A (H=5 1/2”; D=3”)
Catalog Length Total Amperage Number* “L” Watts/Ft. Watts 120V 208V 240V 277V
-2125 125 250 2.4 1.2 1.0 0.9
-2188 28” 188 375 3.1 1.8 1.6 1.4
-2250 250 500 4.2 2.4 2.1 1.8
-3125 125 375 3.1 1.8 1.6 1.4
-3188 3’ 188 564 4.7 2.7 2.4 2.0
-3250 250 750 6.2 3.6 3.1 2.7
-4125 125 500 4.2 2.4 2.1 1.8
-4188 4 188 750 6.2 3.6 3.1 2.7
-4250 250 1000 8.3 4.8 4.2 3.6
-5125 125 625 5.2 3.0 2.6 2.2
-5188 5 188 940 7.8 4.5 3.9 3.4
-5250 250 1250 10.4 6.0 5.2 4.5
-6125 125 750 6.2 3.6 3.1 2.7
-6188 6 188 1125 9.4 5.4 4.7 4.1
-6250 250 1500 12.5 7.2 6.2 5.4
-8125 125 1000 - 4.8 4.2 3.6
-8188 8’ 188 1500 - 7.2 6.2 5.4
-8250 250 2000 - 9.6 8.3 7.2
-10125 125 1250 - 6.0 5.2 4.5
-10188 10’ 188 1875 - 9.0 7.8 6.7
-10250 250 2500 - 12.0 10.4 9.0
1
* Prefix with: CSH05A (5
DSH05A (5 1/2” height heaters)
CLEARANCE CHART
For safe and efficient operation, maintain at least the following minimum clearances at all times:
Bottom of Heater to Finished Floor:
Front Inlet Models:
- May be installed on floor. However, for best performance, install bottom of heater approximately 3 inches (76 mm) off floor.
Bottom Inlet Models:
- 100-250 watts per foot – 1-3/4 inch (44 mm)
- 375-750 watts per foot – 3 inches (76 mm)
NOTE: linoleum, etc. may be installed around and under the heater without adversely affecting the performance of the heaters.
Top of Heater to Ceiling (all models):
- Minimum 36 inches (914 mm) Top of Heater to Bottom of Drapes Above Heater:
- Minimum 12 inches (305 mm) IMPORTANT NOTE:
as vinyl blinds) may become damaged by the heated air from the heater and should not be installed above the heater.
Front of Heater to Full Length Drapes in Front of Heater:
- Minimum between bottom of drapes and floor – 2-1/2 inches (64 mm)
- Minimum between top of drapes and ceiling – 1/2 inch (13 mm)
- Minimum between front of heater and nearest fold of drape – 2 inches (51 mm)
Top of Heater to Bottom of Window Sill:
- Minimum 12 inches (305 mm)
Up to ¾” thick floor covering, such as carpet, tiles,
/2” height heaters)
Certain fabrics and vinyl materials (such
Table A (continued)
Model CSH07A, DSH07A (H=7”; D=5”) Model CSH14A, DSH14A (H=14”; D=5”)
Amperage Catalog Length Total 208V 240V 277V Number** “L” Watts/Ft Watts 1Ø
-2125 125 250 1.2 - 1.0 - 0.9
-2188 188 375 1.8 - 1.6 - 1.4
-2250 250 500 2.4 - 2.1 - 1.8
-2375 28” 375 750 3.6 - 3.1 - 2.7
-2500 500 1000 4.8 - 4.2 - 3.6
-2564 564 1125 5.4 3.1 4.7 2.7 4.0
-2625 625 1250 6.0 3.5 5.2 3.0 4.5
-2750 750 1500 7.2 4.2 6.2 3.6 5.4
-3125 125 375 1.8 - 1.6 - 1.4
-3188 188 564 2.7 - 2.4 - 2.0
-3250 250 750 3.6 - 3.1 - 2.7
-3375 3’ 375 1125 5.4 - 4.7 - 4.0
-3500 500 1500 7.2 - 6.2 - 5.4
-3564 564 1690 8.1 4.7 7.4 4.3 6.1
-3625 625 1875 9.0 5.2 7.8 4.5 6.7
-3750 750 2250 11.0 6.5 9.4 5.4 8.1
-4125 125 500 2.4 - 2.1 - 1.8
-4188 188 750 3.6 - 3.1 - 2.7
-4250 250 1000 4.8 - 4.2 - 3.6
-4375 4’ 375 1500 7.2 - 6.2 - 5.4
-4500 500 2000 9.6 - 8.3 - 7.2
-4564 564 2250 10.8 6.2 9.4 5.4 8.0
-4625 625 2500 12.0 6.9 10.4 6.0 9.0
-4750 750 3000 14.4 8.3 12.5 7.2 10.8
-5125 125 625 3.0 - 2.6 - 2.2
-5188 188 940 4.5 - 3.9 - 3.4
-5250 250 1250 6.0 - 5.2 - 4.5
-5375 5’ 375 1875 9.0 - 7.8 - 6.7
-5500 500 2500 12.0 - 10.4 - 9.0
-5564 564 2820 13.5 7.8 11.8 6.8 10.2
-5625 625 3125 15.0 8.7 13.0 7.5 11.3
-5750 750 3750 18.0 10.4 15.6 9.0 13.5
-6125 125 750 3.6 - 3.1 - 2.7
-6188 188 1125 5.4 - 4.7 - 4.0
-6250 250 1500 7.2 - 6.2 - 5.4
-6375 6’ 375 2250 10.8 - 9.4 - 8.1
-6500 500 3000 14.4 - 12.5 - 10.8
-6564 564 3380 16.2 9.4 14.1 8.1 12.2
-6625 625 3750 18.0 10.4 15.6 9.0 13.5
-6750 750 4500 21.6 12.5 18.7 10.8 16.2
-8125 125 1000 4.8 - 4.2 - 3.6
-8188 188 1500 7.2 - 6.2 - 5.4
-8250 250 2000 9.6 - 8.3 - 7.2
-8375 8’ 375 3000 14.4 - 12.5 - 10.8
-8500 500 4000 19.2 - 16.7 - 14.4
-8564 564 4500 21.6 12.5 18.7 10.8 16.2
-8625 625 5000 24.0 13.9 20.8 12.0 18.0
-8750 750 6000 28.6 16.5 15.0 14.4 21.6
-10125 125 1250 6.0 - 5.2 - 4.5
-10188 188 1875 9.0 - 7.8 - 6.7
-10250 250 2500 12.0 - 10.4 - 9.0
-10375 10’ 375 3750 18.0 - 15.6 - 13.5
-10500 500 5000 24.0 - 20.8 - 18.0
-10564 564 5640 27.2 15.7 23.5 13.6 20.4
-10625 625 6250 30.0 17.3 26.0 15.0 22.6
-10750 750 7500 36.0 20.8 31.3 18.1 27.0
** Prefix with: CSH07A (7” height heaters)
DSH07A (7” height heaters) CSH14A (14” height heaters) DSH14A (14” height heaters)
2
INSTALLATION INSTRUCTIONS
TO REDUCE THE RISK OF FIRE AND ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Serious injury or death could result from electric shock. Make sure electrical power supply circuit coming to heater is disconnected at main disconnect or service panel before installing this heater.
2. Wiring procedures and connections must be in accordance with the National Electrical Code (NEC) and local codes. Refer to Wiring Diagram on heater and Figure 8 as well as Tables B and C. Make sure all electrical connections are tight to prevent possible overheating. Use Copper Supply Wire Only.
3. Verify the electrical power supply voltage matches the volt­age rating as printed on the heater nameplate.
CAUTION - Never connect a heater to a voltage greater than the nameplate voltage as this will damage the heater and could cause a fire.
4. Remove and discard foam packing material inside heater before installing or energizing the heater.
5. Do not install the heater against combustible low-density cellulose fiberboard surfaces, against or below vinyl wall coverings, or below any materials that may be damaged by heat such as vinyl or plastic blinds, curtains, etc. If heater must be installed against vinyl surfaces or surfaces that may be damaged by heat, Standoff Kits Cat. No. S01 or S02 must be used. Refer to installations instructions provided with these kits when installing.
6. Do not install heater below an electrical convenience recep­tacle (outlet).
CAUTION
7. Electrical Cords (including telephone and computer cables), Drapes, and Other Furnishings Away From Heater. For effi­cient and safe operation, we recommend maintaining a min­imum of 6 inches (152 mm) clearance above and in front of the heater at all times. See Clearances Chart for minimum clearance requirements.
8. To reduce the risk of fire, do not store or use gasoline or other flammable vapors or liquids in the vicinity of the heater.
9. Do not install heater upside down or in any position other than as shown in this manual.
10. Do not recess heater in wall or install heater inside any type enclosure (unless specifically approved by the manufactur­er) as this will cause heater to overheat and could create a hazard.
11. When mounting heater, use care when drilling mounting holes and mounting heater to building structure to avoid damaging internal heater components. Be sure to loosen mounting screws 1/4 to 3/4 turn to allow for expansion and contraction.
12. Do not remove or bypass the safety limit control(s) as this could allow heater to become a fire hazard – see heater wiring diagram supplied with heater.
13. The factory installed wires inside wireway are used to con­nect the built-in controls. Limit the maximum current to no more than 35 amps for CSH05 and DSH05 units and 45 amps for CSH07, DSH07, CSH14 and DSH14 units. Refer to instructions and current capacity rating as provided with the accessory.
– Heater Operates at High Temperatures. Keep
14. Heaters that are not installed end to end must have end caps installed to cover exposed ends of heater. Heaters joined together must have appropriate filler sections or other approved assemblies (see Accessories Data listing on Page 8) installed to cover exposed openings between heaters.
15. All field wiring brought into the heater or any attached accessories must be rated at least 75 °C.
16. Do not allow objects to be placed on top of heater as they may be damaged or create a fire hazard.
17. Before energizing, make sure front cover is properly installed onto the back housing along the entire length of the heater – See Fig. 4. Do not operate heater without front cover installed.
Rough-in Wiring
1. Run branch circuit of proper voltage and wire size to location of left or right junction box as indicated on heater wiring dia­gram. Basic heaters are prewired and can be connected to branch circuit at either end. Heaters with controls are prewired for connection to branch circuit at one end only (refer to heater wiring diagram), however, heater can be wired from opposite end by running wire through heater wire­way.
2. If it is necessary to run wires through the heater wireway, use Table B to size the field installed wiring.
3. The factory installed wires in the heater wireway can be loaded up to 35 amps in CSH05 and DSH05 units, and up to 45 amps in, CSH05, CSH14, DSH07 and DSH14 units. Refer to Table C and D for maximum length of heater run when the heaters are connected in parallel.
Table B. Sizing Field Installed Wiring
Copper Maximum no. wire size of wires Up to 3 4 to 6 7 thru 9 75º C in wireway Conductors Conductors Conductors
No. 12 AWG 9 11.5 amps 9.3 amps 8.1 amps No. 10 AWG 8 17.4 amps 14.0 amps 12.1 amps No. 8 AWG 4 24.0 amps 21.0 amps
Table C. Maximum Length of Heater Run (CSH05-1Ø; DSH05-1Ø)
Watts/Ft. of Maximum allowable length of heater run (feet) the heaters 120 Volts 208 Volts 240 Volts 277 Volts
125 33 58 67 77 188 22 38 44 51 250 16 29 33 38
Note:
For mix of watt densities, calculate amp draw. Do not
exceed values indicated in step 3 above.
Maximum allowable current
3
Thermostat
HEATER
HEATERS
BUTTED
TOGETHER
HEATER
FILLER
SECTION
HEATER
INSIDE
CORNER
HEATER
OUTSIDE CORNER
HEATER
END CAP
TYPICAL INSTALLATION
SPLICE PLATE 
KIT
SPLICE PLATE 
KIT
24 amps @ 120-240 VAC 22 amps @ 277 VAC Pilot duty– 125 VAC (all voltages)
Transformer relay
05A units: 22 amps @ 120-240 VAC
19 amps @ 277 VAC
07A-14A Units: 25 AMPS @ 120-240 VAC
22 AMPS @ 277 VAC
Power relay
25 amps @ 120-277 VAC- see wiring dia­gram on heater
Disconnect switch
20 amps @ 120-277 VAC
4. Standard 75ºC wiring must be used in junction boxes, wire­ways, blank sections, filler sections, and corner sections.
Room Layout
Refer to heating plans for exact room arrangements of heaters (with or without thermostat and/or relays and/or switches and accessories.)
Check the heater section dimensions and the additional wall length required for telescoping accessories (Figure 1) before starting wall-to-wall type installation. Be certain all heaters and accessories needed are at hand and are of correct finish.
10
N
7
N
3
Figure 1 Typical Installation See page 9 for N dimensions
N
2
4
1
N
10
8
N
5
6
N
9
Figure 2
Mounting Height
At correct height, draw a pencil line on the wall, level and/or par­allel with the window sill. Minimum mounting heights above the floor shall be as follows:
Minimum Mounting Height Above Floor
Watts/Ft. Heater Length Bottom Inlet/Front Inlet 125, 188 and 250 Watts/Ft. 1-3/4” 0” 376, 500, 625, and 750 3” 0” Watts/Ft.
Note:
Up to 3/4” thick floor covering, such as carpet, tiles, linoleum, etc., may be installed around and under the heater without adversely affecting the performance of the heaters.
Installation of Single Unit
Note:
For ease of installation, it is important that the sequence of operations indicated below be followed in order.
1. Remove front cover by removing mounting screws (Figure
2).
2. Remove appropriate electrical knockout from either junction
box. See Figure 3 for location of knockouts.
3. Install end caps (must be purchased separately) on both
ends of the heater housing. Refer to Figure 4 for details of end cap installation.
Figure 3
4
Figure 4
4. If filler section is desired to terminate the heater, install the filler section in the end of the heater and extend to desired length. Mark the mounting hole locations, remove the filler section and drill the required mounting holes. Install the filler section in the heater and the end cap on the filler section as shown in Figure 2.
Note:
If a thermostat and/or disconnect switch are installed in the heater left junction box, it may be necessary to cut away a portion of the filler section to allow access to these controls (Figure 2).
5 Position heater housing on wall to check for evenness of
wall. do not draw the heater against an uneven wall surface. If an uneven wall is encountered, use shims to keep the heater housing straight.
6. Run proper size branch circuit to the junction box through the
selected knockout.
7. Drill the required size mounting holes in the back of the
heater housing and install the housing on the wall using screws, bolts or anchors (by installer) to suit the wall con­struction.
Note:
Predrilled 1/4” diameter mounting holes are provided in each junction box. Additional mounting holes will have to be drilled in the housing to support the weight of long length heaters (6’ and longer). Do not drill any additional holes in the junction boxes.
8. Tighten mounting screws and back off 1/4 to 3/4 turn to
allow for expansion and contraction of the heater.
9. Following the wiring diagram secured to the heater, make
electrical connections. Ground the heater using the ground screws provided (Figure 2).
10. Replace front cover and secure with mounting screws. (See
Figure 2).
Figure 5
Installation of Multiple Wall to Wall Units
Note:
For ease of installation, it is important that the sequence
of operations indicated below be followed in order.
1. Remove all the front covers from the heaters by removing mounting screws (Figure 2).
2. Refer to wiring diagram for power supply entry and remove appropriate electrical knockout (Figure 3) from the heater in which power supply connections are to be made. The power supply may be brought in to the end of only one heater and the remaining heaters may be connected in parallel using the wireway. Use Table B to size the field installed wiring in the wireway.
3. If conduit cover (must be purchased separately) is desired, cut off the appropriate length and install to the wall.
4. If required by plan, install filler section (1, Figure 1) to either heater (2) or (3) by means of four #6 screws supplied with filler section. (Refer to Figure 5.) Discard filler section end cap in this application.
Note:
Heaters may butt against each other, thus eliminating the
filler piece, if so desired. Note:
If a heater has a disconnect switch and / or thermostat and is to have a filler section or a corner section at the left end, the section must be mounted to the heater since the thermostat or disconnect switch will prevent the section from telescoping into the heater.
5 If the wall run has inside or outside corners, install corner (4
and 5) to the heater (2 and 9) by means of four #6 screws supplied with corner section. (Refer to Figure 5).
6. Install end caps (6) on the outer end of the last heater(7) and
(9) using four #6 screws supplied with end caps. (Refer to Figure 4 for details of end cap installation.)
7. Drill the required size mounting holes in all the heater hous-
ings.
5
Note:
Predrilled 1/4” diameter mounting holes are provided in each junction box. These holes may be used only when no slip­in accessory is to be installed in that end of the heater ( such as when heater(3 and 7) are butted together as shown in Figure 1). Additional mounting holes will have to be drilled in the housing to support the weight of long-length heaters (6’ and longer). Do not drill any additional holes in junction boxes.
8. Check for evenness of wall. Do not draw the heaters
against an uneven wall surface. If an uneven wall is encountered, use shims to keep the heater housing straight.
9. Run proper size branch circuit to the junction box through
the selected knockout.
10. Mount the heater (2, Figure 1) on the wall using screws,
bolts or anchors (by installer) to suit the wall construction.
11. Telescope the heater housing (3) over the filler section (1)
by the desire amount and mount the housing to the wall.
12. Telescope the heater housing (8) over the corner section
(4) by the desired amount and mount the housing to the wall.
13. Mount the remaining heaters as described above, making
sure that the heaters with end caps are installed at the end of the run.
14. Blank sections, if any are installed in the same manner as
the heaters.
Note:
75ºC field wiring may be run through the blank sections, filler sections and corner sections.
15. Control sections, if any, are installed in the same manner
as heaters. Refer to wiring diagram on control sections for connecting the wiring to the heaters
Installation of Mullion to Mullion Units
The back of the heater housing contains no mounting holes (other than those at the ends) and therefore is ideal for installa­tion in front of glass curtain walls. The housing back presents an attractive appearance when viewed from the outside through the glass wall.
Installation procedures are similar to those for wall-to-wall instal­lation (Step Six) except for the following differences.
1. Attach the housing to the mullion using the mounting holes
provided in the junction boxes as shown in Figure 6.
2. On horizontal mullion installation, install support brackets as
shown in Figure 7.
Figure 7
OPERATION INSTRUCTIONS
1. After heaters are completely assembled and installed, set thermostat or operating controls for NO HEAT and energize heater circuit (s). Verify the heaters are not producing heat.
2. Adjust thermostat or operating control to call for heat. Allow heater(s) to operate for a few minutes and verify the heaters are producing heat.
3. The thermostat or operating controls may be adjusted to cycle the heater(s) on and off to maintain the desired room temperature.
Note:
If built-in thermostat is provided, rotation in the clockwise direction will allow heater to remain on MORE and will main­tain a higher room ambient. Likewise, rotation in the counter­clockwise direction will result in the heater remaining on LESS and the room ambient will be lower. If remote thermo­stat or other types of controls are provided, refer to the instructions provided with these controls for proper operation.
Figure 6
6
Figure 8 - Wiring Diagram
MAINTENANCE INSTRUCTIONS
For efficient and safe operation and to extend the life of the heaters, they should be cleaned and inspected for damage at least annually (preferably at the beginning of the heat season) or more often in dirty environments. Other than cleaning, your heaters require no other preventative maintenance. The user and / or cleaning personnel can perform routine cleaning of the heater that may be done without disassembly of the heater. However, any cleaning or servicing that requires disassembly of the heater must be done by qualified service personnel.
SERIOUS INJURY OR DEATH COULD RESULT FROM ELECTRIC SHOCK. MAKE SURE ELECTRICAL POWER SUPPLY CIRCUIT(S) COMING TO HEATER IS/ARE DIS­CONNECTED AT MAIN DISCONNECT OR SERVICE PANEL BEFORE CLEANING OR SERVICING THIS HEATER. ALLOW HEATER TO COOL BEFORE CLEANING TO PRE­VENT A POSSIBLE BURN.
NOTE: HEATER. BE SURE ALL POWER IS DISCONNECTED TO HEATER BEFORE CLEANING OR SERVICING.
1. Heater cabinet may be cleaned using a damp cloth to
2. A vacuum cleaner and /or compressed air may be used to
FINS ARE SHARP AND MAY CAUSE CUTS SO AVOID CONTACT.
3. After cleaning and servicing, always reassemble replacing
MORE THAN ONE POWER SOURCE MAY ENTER
remove dust that may have accumulated on surfaces. Do not use harsh cleaners and waxes on surfaces since these could damage the finish or discolor in use.
remove dust and lint that may have accumulated inside heater around element fins. If heater must be disassembled for cleaning, use care when cleaning element fins to avoiding damaging fins.
any hardware removed and check units to make sure they are operating properly.
789
RENEWAL PARTS IDENTIFICATION CSHCSA, DSHCSA
For part numbers, refer to the Renewal
arts Identification covering the appro-
P priate height heater (7” or 14”), and then select the front, back panel, or grille listed under the 28” length.
RENEWAL PARTS IDENTIFICATION CSHCRA, DSHCRA
CSH05A, CSH07A and CSH14A
Catalog Number
CSH07-ECL(R) CSH07-ECR(R) CSH07-FL3(R) CSH07-FL6(R)
CSH07-FL9(R) CSH07-FL12(R) CSH07-FL18(R)
CSH07-IC1
CSH07-OC-1 CSH07-BL2-1 CSH07-BL3-1 CSH07-BL4-1 CSH07-BL5-1 CSH07-BL6-1 CSH07-BL8-1
CSH07-BL10-1
CSH07-BCS-1
SHCC-07-14
CSH14-ECL(R) CSH14-ECR(R)
CSH14-FL3(R) CSH14-FL6(R)
CSH14-FL9(R) CSH14-FL12(R) CSH14-FL18(R)
CSH14-IC-1 CSH14-OC-1 CSH14-BL2-* CSH14-BL3-* CSH14-BL4-* CSH14-BL5-* CSH14-BL6-* CSH14-BL8-*
CSH14-BL10-*
CSH14-BCS-*
SHCC-07-14
Description
End Cap-Left
End Cap-Right
Filler
Section
Inside Corner
Outside Corner
Blank Section
Blank Control
Section
Conduit Cover
* Add suffix “1” for bottom inlet top outlet. Add suffix “3” for bottom inlet front outlet. † Intended for the installation of components. (R) Suffix on catalog number refers to accessories with 120 VAC receptacle.
CSH05A CSH07A CSH14A
CSH05-ECL(R) CSH05-ECR(R) CSH05-FL3(R) CSH05-FL6(R)
CSH05-FL9(R) CSH05-FL12(R) CSH05-FL18(R)
CSH05-IC1
CSH05-OC-1 CSH05-BL2-1 CSH05-BL3-1 CSH05-BL4-1 CSH05-BL5-1 CSH05-BL6-1 CSH05-BL8-1
CSH05-BL10-1
SHCC-05
ACCESSORIES DATA
Length
Addition “N”
1/8"
1/8" 0" 3" 3" 6" 6" 9" 9" 12" 15" 18"
3-12''
5-1/2''
1/2''
28''
3' 4' 5' 6'
8' 10' 28''
Description
End Cap-Left
End Cap-Right
Filler
Section
Inside Corner
Outside Corner
Blank Section
Blank Control
Section
Conduit Cover
* Add suffix “1” for bottom inlet, top outlet, add suffix “2” for front inlet, top outlet. † Intended for the installation of components. (R) Suffix on catalog number refers to accessories with 120 VAC receptacle.
DSH05A, DSH07A and DSH14A
Catalog Number
DSH05A DSH07A DSH14A
DSH05-ECL(R) DSH05-ECR(R) DSH05-FL3(R) DSH05-FL6(R) DSH05-FL9(R) DSH05-FL12(R) DSH05-FL18(R) DSH05-IC1
DSH05-OC-1 DSH05-BL2-1 DSH05-BL3-1 DSH05-BL4-1 DSH05-BL5-1 DSH05-BL6-1 DSH05-BL8-1 DSH05-BL10-1
SHCC-05
DSH07-ECL(R) DSH07-ECR(R) DSH07-FL3(R) DSH07-FL6(R) DSH07-FL9(R) DSH07-FL12(R) DSH07-FL18(R)
— DSH07-IC1 DSH07-OC-1 DSH07-BL2-1 DSH07-BL3-1 DSH07-BL4-1 DSH07-BL5-1 DSH07-BL6-1 DSH07-BL8-1 DSH07-BL10-1 DSH07-BCS-1
SHCC-07-14
DSH14-ECL(R) DSH14-ECR(R) DSH14-FL3(R) DSH14-FL6(R) DSH14-FL9(R) DSH14-FL12(R) DSH14-FL18(R)
DSH14-IC1 DSH14-OC-1 DSH14-BL2-1 DSH14-BL3-1 DSH14-BL4-1 DSH14-BL5-1 DSH14-BL6-1 DSH14-BL8-1 DSH14-BL10-1 DSH14-BCS-1
SHCC-07-14
Length
Addition “N”
1/8"
1/8" 0" 3" 3" 6" 6" 9" 9" 12" 15" 18"
3-12''
5-1/2''
1/2''
28''
3' 4' 5' 6'
8' 10' 28''
Loading...
+ 21 hidden pages