[ Figure 5-17 : PV Connector Connection (MC4 Type Connector Connection) ]
[ Figure 5-18 : Wire Connection and Disconnection ]
[ Figure 5-19 : Power Cable Connection to the AC Connector ]
[ Figure 5-20 : Power Cable Connection to the Load Connector ]
[ Figure 5-21 : Power Cable Connection to the Load Connector ]
[ Figure 5-22 : AC Cable Gland ]
This is the installation manual for the Q.HOME+ ESS HYB G2. Please read this installation and user manual
carefully before installing and operating the Q.HOME+ ESS HYB G2. It contains important safety instructions.
The warranty will be void if you fail to follow the instructions in this manual.
1.2 Target Group
This installation manual applies only to the Q.HOME+ ESS HYB G2.
1.3 Additional Information
The user manual and installation manual can be downloaded from the product download section
at “https://www.q-cells.de/service-support/downloadbereich.html”,
The specifications of the product can be changed for improvement without notice.
Also, the software can be updated automatically without notice over the Internet.
1.4 Symbols Used
DescriptionSymbols
CAUTION
This symbol indicates a hazardous situation which could result in
a light injury, if not avoided.
NOTICE
This symbol indicates a hazardous situation which could result in
damage to the property, if not avoided.
INFORMATION
This symbol indicates valuable tips for optimum installation and
operation of the product.
DANGER
High touch current, earth connection essential befoer connecting supply
01 I Information in this Manual
Page 9
DescriptionSymbols
Beware dangerous voltage.
The ESS operates at high voltage. All works related to the ESS can only
be performed by an electrical technician.
Beware of hot surface.
The INVERTER can become hot during operation.
Avoid contact during operation.
Follow the guidelines in all relevant documents enclosed along
with the INVERTER.
Do not dispose of the INVERTER with household wastes.
For further information on disposal, refer to the installation manual
provided.
The CE Indication :
The relevant equipment complies with the requirements in the
EC guidelines.
[ Table 1-1 : Symbol Description 1 ]
DescriptionSymbolsDescriptionSymbols
Direct current
Alternating current
Both direct and alternating
current
Three-phase alternating current
Three-phase alternating
current with neutral conductor
Earth terminal
Protective conductor terminal
Refer to the operating
instructions
On (supply)
Off (supply)
Equipment protected
throughout by double insulation
or reinforced insulation
Caution : Risk of Electric Shock
Caution : Hot Surface
Caution : Risk of Danger
Frame or chassis terminal
In position of a bi-stable
push control
Information in this Manual I02
Page 10
DescriptionSymbolsDescriptionSymbols
Out position of a bi-stable
push control
Input terminal or rating
Output terminal or rating
[ Table 1-2 : Symbol Description 2 ]
Energy Storage Device
To help avoid burns of electric shock :
- Service by qualified personnel only
- Disconnect main power before maintenance
- Turn off the Battery System before maintenance
Electric shock hazard
Do not remove cover or disassemble.
Bidirectional terminal rating
Caution : Risk of Electric Shock
and Energy Storage Timed
Discharge
Caution : Risk of Hearing Damage
and Wear Hearing Protection
Wear hearing protection
DescriptionSymbols
Explosive gas
Do not expose to flame, incinerate, puncture, or impact
Shield eyes
Wear safety goggles at ALL times (Installation, maintenance, etc.)
Electrolyte hazard
A
Do not contact eyes, skin or clothing.
If it happens, Flush with water and seek medical aid immediately.
Do not dispose in trash
Transport legally. Follow manufacturer’s instructions for disposal.
Please recycle Lithium ion Battery. Do not discard.
Qualified technicians use this manual for service and replacement.
[ Table 1-3 : Symbol Description (Battery) ]
03 I Information in this Manual
Page 11
2. Safety
2.1 Intended Use
NOTICE
• The Q.HOME+ ESS HYB G2 is intended for residential use only.
• The Q.HOME+ ESS HYB G2 should not be used for commercial or building.
The Q.HOME+ ESS HYB G2 is designed for residential use. It is a single-phase, Grid-connected system of
solar energy sources and Li-Ion Battery energy storage.
The Q.HOME+ ESS HYB G2 uses solar energy power connected to the input/output terminal installed on
the side of the device in order to :
1) charge the Li-Ion Battery energy storage,
2) provide a supply to the household load, and
3) convert direct current (DC) electricity of the Battery to alternating current (AC) to discharge as
household single-phase load or electric system.
This device should not be used for any purpose other than the purpose described in this installation
manual. Any substitute use of this device, random change in any of its parts, and use of components
other than sold or recommended by Q CELLS will nullify the product’s guarantee.
For example, Q CELLS Li-Ion Battery energy storage should not be replaced by other manufacturer’s
Battery storages. For further information on proper use of this device, contact the Q CELLS
Service-Hotline.
2.1.1 MEN Link
[ Figure 2-1 : MEN Link ]
1. K1 is PV input DC Switch. K2 is battery breaker. K3 is grid breaker, k5 is main load breaker.K6 is total grid breaker. K4 is sub_load breaker.
2. MEN Link : The INVERTER maintains connection for the internal relay(RL603, RL601) on neutral wire
when entering the off-gird mode.
Safety I04
Page 12
2.1.2 Network System Connection Diagram
[ Figure 2-2 : TN-S Network System Connection Diagram ]
872
872
[ Figure 2-3 : TT Network System Connection Diagram ]
872
872
05 I Safety
Page 13
2.2 Safety Precautions
CAUTION
High voltages in power conditioning circuits. Lethal hazard of electric shock or serious
burns. All work on the PV modules, INVERTER, converters, and Battery systems must be
carried out by qualified personnel only. Wear rubber gloves and protective clothing
(protective glasses and boots) when working on high voltage/high current systems
such as INVERTER and Battery systems.
CAUTION
Li-Ion Battery energy storage system (ESS) outside. When assembling the system, do not
intentionally short the positive (+) and negative (-) terminals with metallic object.
All work on the ESS and electrical connections must be carried out by qualified personnel
only. Q.HOME+ ESS HYB G2 provides a safe source of electrical energy when operated
as intended and as designed. A potentially hazardous circumstance such as excessive
heat or electrolyte mist may occur due to improper operating conditions, damage, misuse
and/or abuse. The following safety precautions and the warning messages described in
this section must be observed. If any of the following precautions are not fully understood,
or if you have any questions, contact Customer Support for guidance (see chapter 13).
The safety section may not include all regulations for your locale; personnel working with
Q.HOME+ ESS HYB G2 must review applicable federal, state and local regulations
as well as the industry standards regarding this product.
CAUTION
This product is intended to be used for PV source inputs and residential home
Grids (AC 230V). If not used as intended, the protection provided by the equip
-ment may be impaired.
CAUTION
This device is designed appropriate for two-PV string structure. Therefore, the
PV string 1 and PV string 2 must be connected to PV input 1 and PV input 2,
respectively. Do not split one PV string output for connecting it into the PV input
terminal 1 and input terminal 2.
CAUTION
After disconnecting the INVERTER from Battery or PV, Wait 5minutes to discharge the
INVERTER.
Safety I06
Page 14
2.3 Product Overview
The Q.HOME+ ESS HYB G2 includes the PV INVERTER, Battery charger/discharger, Li-Ion Battery,and EMS.The basic operating modes consist of Stand-Alone (Back-up) mode, PV generation mode, PV generation + charge/discharge mode. The operation mode of this product is automatically determined by the EMS algorithm.
2.3.1 INVERTER Product Overview
INSIDE
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
⑪
⑫
⑬,⑭
①
②
③
⑥ ⑨⑫⑩
⑤
⑦
⑪
⑧
[ Figure 2-4 : Part View of INVERTER ]
DescriptionNo.
LCD Board
LCD Panel
LED Indications
INVERTER (PV INVERTER and Battery charger / discharger)
Cable Gland for Battery
DC Disconnection Switch (PV Isolator)
Battery Communication
PV Input Connector (MC4 type 2set)
AC Connector and Load Connector
PCS Communication
Ethernet Communication
Demand Response Mode / See ‘page 16’ for more information.
Bracket Connected Part
④
⑬
⑭
07 I Safety
[ Table 2-1 : Part Description of INVERTER ]
Page 15
2.3.2 Battery Product Overview
①
⑥
⑦
①
②
③
④
⑤
⑥,⑦
②
④
⑤
[ Figure 2-5 : Part View of Battery Pack ]
Battery (Made by Samsung SDI)
BMS Board
Terminal and Circuit Breaker
Cable Gland
BMS Communication Connector
Bracket Connected Part
[ Table 2-2 : Part Description of Battery Pack ]
③
DescriptionNo.
Safety I08
Page 16
2.3.3 Basic Specifications (Germany)
PV Generator Data (DC)
Max. input total power
Max. input power per string
Max. input voltage
Min. input voltage / Initial input voltage
MPPT voltage range
Max. input current per string
Number of independent MPPT trackers
Battery nominal capacity
Usable capacity
DOD (Depth of Discharge) Range
Battery voltage range / nominal voltage
Max. discharge current
Max. charge current
Battery DC/DC converter data
Max. charge power
Max. discharge power
Technology
6.6 kWp
3.3 kWp
550 V
125 V / 150 V per string
125 V ~ 500 V
15 A per string
2
Battery Data (DC)
1 Battery Pack
2 or more Battery Pack
4.0 kWh
3.6 kWh
90 %
176.4 Vdc ~ 225.12 Vdc / 203.84 Vdc
17 A
9.8 A17 A
2.0 kW3.0 kW
3.0 kW
Non-Isolated
4.0 kWh x Pack
3.6 kWh x Pack
Rated power (at 230V, 50Hz)
Max. output apparent AC power
Max. current
Nominal AC voltage / range
Rated power frequency / range
[ Table 2-3 : Basic Specifications (Germany) ]
Grid Connection Data (AC)
4.6 kW
4.6 kVA
25 A
230 V / 184 Vac ~ 264 Vac
50 Hz / 47.5 Hz ~ 51.5 Hz
09 I Safety
Page 17
2.3.4 Basic Specifications (Australia & New Zealand)
High touch current, earth connection essential before connecting supply
The PV INVERTER complies with the local requirements for grounding the PV INVERTER.
Q CELLS recommends connecting and grounding the PV INVERTER’s frame and other electricity
conducting surfaces in such a way that there is continuous conduction in order to achieve maximum
protection for systems and persons. And the PV INVERTER’s DC (+) pole and DC (-) pole are not
permitted to be grounded.
* Double Grounding Point
Q.HOME+ ESS HYB G2 must be connected to an additional ground on the enclosure.
The grounding method on the enclosure is as follows :
Included in this box are a Battery and printed circuit board. Therefore, special care
must be taken in handling. Make sure to have at least two persons deliver and remove
the package.
3.1 Package Removal
3.1.1 Removing the INVERTER Enclosure Package
As shown in the [Figure 3-1], remove the package components from the enclosure in the following order.
1. Place the system on the installation location.
2. Turn the box upside down.
3. Open the box.
4. Remove the cover on the back of the product.
5. Remove the protective cover on the side of the product.
6. Prepare the lower bracket for the INVERTER. (3 Down Bracket Screws, 1 Down Bracket)
7. Assemble the lower bracket to the INVERTER.
8. Lift the INVERTER.
PCS
(1)(2)(3)(4)
(5)(6)(7)(8)
[ Figure 3-1 : Process for the INVERTER Enclosure Package Removal ]
PCS
Package Removal and Inspection I12
Page 20
3.1.2 Removing the Battery Enclosure Package
As shown in the [Figure 3-2], remove the package components from the enclosure in the following order.
1. Place the system on the installation location.
2. Turn the box upside down.
3. Open the box.
4. Remove the cover on the back of the product.
5. Remove the protective cover on the side of the product.
6. Prepare the lower bracket for the BATTERY. (3 Down Bracket Screws, 1 Down Bracket)
7. Assemble the lower bracket to the BATTERY.
8. Lift the BATTERY.
BATTERY
BATTERY
(1)(2)(3)(4)
(5)(6)(7)(8)
[ Figure 3-2 : Process for the Battery Enclosure Package Removal ]
13 I Package Removal and Inspection
Page 21
3.1.3 Checking Components on the Packing List
Once the product has been delivered, refer to the [Figure 3-3], [Figure 3-4], [Figure 3-5], [Table 3-1],
[Table 3-2], and [Table 3-3] check the entire components included in the package and the correct
number of the quantity listed in the table.
INVERTER Packing List
B
USER
MANUAL
QUICK
GUIDE
A
CDEFG
HIJ
No.Part Name
A
B
C
D
E
F
G
H
I
J
INVERTER ASSY
Upper Wall Bracket
Lower Wall Bracket
Wall Mount Screw
Down Bracket Screw
User manual
Quick Guide
PV Stick(+)
PV Stick(-)
RJ45 Sleeve Housing
[ Figure 3-3 : Packing List of INVERTER ]
Code No. Quantity
0147000122CA
6447300054AD
6447300055AD
67613074AAAD
67613075AAAD
6547310111AD
6547310114AD
4925310128KD
4925310129KD
4635150094WD
1
1
1
5
3
1
1
2
2
1
[ Table 3-1 : Component Description of INVERTER ]
Package Removal and Inspection I14
Page 22
Battery Packing List
B
A
CDEFG
[ Figure 3-4 : Packing List of Battery Pack ]
No.Part Name
A
B
C
D
E
F
G
H
Battery ASSY
Upper Wall Bracket
Lower Wall Bracket
Bridge Bracket
Wall Mounting Screw
Down Bracket Screw
Bridge Screw
BMS Communication Cabletor
[ Table 3-2 : Component Description of Battery Pack ]
Option List
Code No. Quantity
0147000123CA
6447300054AD
6447300055AD
74190024AAAD
67613074AAAD
67613075AAAD
67613078AAAD
4635150030WD
H
1
1
1
1
5
3
4
1
A
No.Part Name
A
*
B
*
C
D
Adaptor
External Battery Power Cable
Cable Gland
Stand (ESS Stand Long, 470 x 380 x 1079 mm)
Stand (ESS Stand Short, 470 x 380 x 787 mm)
* A : Adaptor
- If using more than one battery, a separate adaptor is requried. (Adaptor is an accessory, requires separate purchase)
When opening the box that contains Q.HOME+ ESS HYB G2 in it, check for any possible damage caused
in transit and ensure the correct number of the components therein. If there is a scratch on the enclosure,
contact your local dealer for inspection and service.
3.3 Identifying Q.HOME+ ESS HYB G2
Attached on the enclosure of this product is the Type Label where the identity of this product is described.
For safe usage, make sure that the following product information is indicated on the Type Label.
■ Device Type (Model)
■ Serial Number (Serial No.)
■ Device-specific characteristics
■ Certification Lists
■ Warnings and Notification
Q.HOME+ ESS HYB G2
■ Q.HOME+ ESS HYB G2
• Q CELLS’s ESS For Home with Hybrid Inverter G2
INVERTER
■ G2 for Germany : Q.VOLT G2 HYB-4.6kW.1.1, HSHP-4601-1
• HYB-4.6kW.1.1 : Hybrid Inverter rated power 4.6kW single phase ver.1
■ G2 for Australia : Q.VOLT G2 HYB-5kW.1.1
• HYB-5kW.1.1 : Hybrid Inverter rated power 5kW single phase ver.1
Q.VOLT G2 HYB-4.6kW.1.1
: Model with DRM hole
BATTERY
■G2 for Germany : Q.SAVE G2 4kWh B1.1.1, HSBE-4001
The Type Label is shown in the [Figure 3-6], [Figure 3-7], [Figure 3-8] and [Figure 3-9].
Model Name :
HSHP-4601-1,
Q.VOLT G2 HYB-4.6kW.1.1
(The specifications are
the same.)
[ Figure 3-6 : INVERTER Name Plate
(Germany) ]
Model Name :
HSBE-4001
Q.SAVE G2 4.6kWh B1.1.1
(The specifications are
the same.)
[ Figure 3-7 : INVERTER Name Plate
(Australia & New Zealand) ]
[ Figure 3-9 : DRM Name Plate ]
17 I Installation
[ Figure 3-8 : Battery Name Plate ]
Page 25
4. Installation
4.1 Selection of Installation Location
CAUTION
Danger to life due to fire or explosion!
Danger to life due to high voltages!
Despite careful construction, a fire can occur with electrical devices.
Do not install the Q.HOME+ ESS HYB G2 on the following locations:
On flammable construction materials;
In potentially explosive areas; and
In areas where highly flammable materials are stored!
CAUTION
Li-Ion Battery energy storage is mounted outside Q.HOME+ ESS HYB G2.
Q.HOME+ ESS HYB G2 provides a safe source of electrical energy when operated as
intended and as designed. A potentially hazardous circumstance such as excessive heat
or electrolyte mist may occur due to improper operating conditions, damage, misuse
and/or abuse. The following safety precautions and the warning messages described in
this section must be observed.
If any of the following precautions are not fully understood, or if you have any questions,
contact Customer Support for guidance. The Safety Section may not include all
regulations for your locale; Personnel working with Q.HOME+ ESS HYB G2 must review
applicable federal, state and local regulations as well as the industry standards regarding
this product.
CAUTION
All work on the ESS and electrical connections must be carried out by qualified
personnel only.
Installation I18
Page 26
4.1.1 Dimensions
Once the Q.HOME+ ESS HYB G2 has been assembled, its dimension is 467.6 x 721.6 x 212.5mm.
The [Figure 4-1] show the outer dimensions of the device after assembly, respectively.
467.6 mm212.5 mm
721.6 mm
[ Figure 4-1 : Dimension of Q.HOME+ ESS HYB G2 ]
467.6 mm212.5 mm
721.6 mm
4.1.2 Ambient Conditions and Temperatures
Check a proper installation location to install and remove the device easily at any time.
This device must be located within reach distance. The ambient temperature of the installation location is
-20°C ~ 50°C for the inverter, 0°C ~ 40°C for the battery.
4.1.3 Environmental checks
When choosing installation location, observe the following conditions :
• The installation location must be easily accessible.
• Prevent access to the installation location by children.
• Installation of the unit in a location exposed to solar rays must be avoided as it may cause :
- power limitation phenomena in the INVERTER (with a resulting decreased energy production by the system)
- premature wear of the electrical/electromechanical components
- premature wear of the mechanical components (gaskets) and of the user interface (display)
- reduction in performance, lifetime and possible damage of the Battery pack
• Always ensure that the flow of air around the INVERTER is not blocked so as to prevent overheating.
• Do not install in locations where flammable substances or gases may be present.
• You can install in locations with a constant presence of water and/or high humidity level,
but not recommended.
• Do not install in rooms where people live or where the prolonged presence of people or animals is
expected, because of the noise that the INVERTER produces during operation.
When choosing the place of installation, observe the following conditions:
• Install on a wall or strong structure capable of bearing the weight of the equipment.
• If possible, install at eye-level so that the display can be seen easily.
• Install at a height that considers the heaviness of the equipment. Failure to meet this condition could
result in problems during servicing, unless suitable means are provided to carry out the operation.
• Install vertically with a maximum inclination of 5° (backward). If this condition cannot be met, the INVERTER
could undergo derating due to high temperature because of poor heat dissipation.
• The installation must take account of any electrical devices (e.g. lamps, switches, etc.) which must be
at least 60cm from the equipment. These distances must be maintained also to facilitate the circulationof the air needed to cool the unit and to facilitate the operations to install/maintain hardware and softwarewhich is done by dismantling the covers placed on the front.
OO
XXX
[ Figure 4-3 : Restriction for the Surface Gradient ]
Installation I20
Page 28
4.2 Mounting Instructions
CAUTION
There is risk of injury if the ESS is lifted incorrectly or dropped while being transported
or when attaching it to or removing it from the wall mounting bracket.
Transport and lift the ESS carefully.
It is important to ensure the drilling locations are not located on any electrical wiring
within the wall.
This product must be installed on the wall considering appropriate environments described in previous
pages. Follow the mounting instruction described below exactly and securely.
* NOTE
When attaching the wall bracket to a wall, adjust the horizontal level using inclinometer.
STEP 1STEP 2
• Step 1 : Mark guideline on wall.
- Drill hole : size = Ø10 / Length = 45~55mm
- Upper bracket : 3 EA
- Lower bracket : 2 EA
208.5 mm
208.5 mm
498 mm
• Step 2 : Get ready for the upper bracket.
- Step 2-1 : Detach Anchor bolt.
- Step 2-2 : Insert the Anchor bolt into the bracket.
STEP 2-1
STEP 2-2
Wall Mount Screw
21 I Installation
150 mm150 mm
GND Screw
[ Figure 4-4 : Bracket on the Wall in Step 1, 2 ]
Diameter
M8
M4
[ Table 4-1 : Screw Specification ]
LTouque
45mm
8mm
20kgf
10kgf
Page 29
• Step 3 : Secure the upper bracket.
UPPER BRACKET-2
STEP 3
UPPER BRACKET-1
[ Figure 4-5 : Bracket on the Wall in Step 3 ]
STEP 4
• Step 4 : If you secure the upper bracket, Use the bridge bracket.
[ Figure 4-6 : Bracket on the Wall in Step 4 ]
Installation I22
Page 30
STEP 5
• Step 5 : Lift the INVERTER and secure it to the upper bracket.
- Step 5-1 : Hang the INVERTER to upper bracket.
- Step 5-2 : Secure the lower bracket.
STEP 5-1
STEP 5-2
[ Figure 4-7 : Bracket on the Wall in Step 5 ]
STEP 6
• Step 6 : The method of mounting the Battery is the same as that of the INVERTER.
23 I Installation
[ Figure 4-8 : Bracket on the Wall in Step 6 ]
Page 31
4.3 Stand - Mounting Instructions
NOTICE
• Please refer to the STAND Installation Manual for installation instructions and precautions.
• The stand must use the frame provided by the manufacturer, All four directions should be
fastened with bolts to the bottom.
• Step 3 : After assembling Stand Column on
Stand plate, tighten Screw(M8x16, 4point).
STEP 4STEP 5
tighten the nut (M8, 2point).
M8x45, Washer
(2 point)
* Use the Wall Mount Screw
to disassemble it.
• Step 5 : Secure the stand to the floor. • Step 4 : After tightening the Upper Wall Bracket,
M12~16 Nut,
Washer (4Point)
Installation I24
Page 32
STEP 6STEP 7
stand, tighten SCREW.
* Use the Wall Mount Screw
to disassemble it.
M8x45, Washer
(2 point)
[ Figure 4-10 : Stand assembly Step 1~7 ]
• Step 7 : Assemble the battery in the same way. • Step 6 : After assembling INVERTER A’SSY and
5. Electrical Connections
NOTICE
The Q.HOME+ ESS HYB G2 system can be damaged by static discharge.
Before you touch a component inside the Q.HOME+ ESS HYB G2, ground yourself
by touching PE or a grounded object.
CAUTION
When handling with the Li-Ion Battery for the Q.HOME+ ESS HYB G2, you must
wear the following personal protective equipment : High voltage rated rubber gloves
Safety goggles or other protective eye equipment 40-minute standby period of time
to complete discharging in the system before testing electrical parts inside the system!
Follow the guidelines below when handling the Li-Ion Battery.
Do not intentionally short circuit the positive (+) and negative (-) terminals with a metallic
object.
Do not remove the cap on the terminals. If the cap is removed, avoid contact between the
metals and the Battery terminals. Do not damage the screw thread.
Do not use seriously scarred or deformed Battery. Dispose immediately according to
proper regulations.
Do not damage sheath of cable and connectors.
25 I Electrical Connections
Page 33
5.1 The Overview of Electrical Connection
5.1.1 Electrical System Connection
The Q.HOME+ ESS HYB G2 has two solar energy inputs (PV1, PV2). 3.3kW (per string) is the maximumoutput for each PV input. The AC output of Q.HOME+ESS HYB-G2 is connected to the Home Loadand the Grid. Between the Grid and PCS, the Digital Energy Meter is placed for power metering.The Home Load is directly connected to PCS. PCS is installed between the AC circuit breaker and DCDisconnect for safety reasons. Refer to Chapter 2.1 for detail system diagram.
The Q.HOME+ ESS HYB G2 uses the two independent channels of the PV Input ({PV1+, PV1-}, {PV2+,PV2-}). They are used independently for running the maximum power from the sources of PV1 and PV2.Two channels are recommended for independent use for the two PV Inputs. Make sure not to connectone PV string in parallel with the two independent PV inputs (PV1, PV2).
A PV string must not be commonly connected to the two input terminals of the Q.HOME+ ESS HYB G2.That is, make sure not to connect the split wiring from one PV string output with the two independentPV inputs (PV1+, PV1- and PV2+, PV2-). (Refer to the PV String connection method in the [Figure 5-1]).
* PV modules shall have an IEC61730 Application Class A rating or equivalent.
[ Figure 5-1 : PV Connections ]
5.1.2 Power Line Specification
As shown in the [Table 5-1], the input / output power cables correspond to the AC / DC input / outputspecifications for this system. Battery Power Cable is not provided. Please prepare it seperately.
Recommended cables for the Q.HOME+ ESS HYB G2.
AreaInsulation(Germany) Color (Australia) Color
Grid (L,N)
Load(L,N)
PE
PV (+), (-)
Battery (+), (-)
6mm
6mm
6mm
4~6mm
6mm
600V or more
600V or more
600V or more
600V or more
400V or more
[ Table 5-1 : Power Line Specification ]
L (Blue), N (Brown & Black)
-
Green / Yellow, Green
-
-
L (Brown or Red), N (Blue & Black)
-
Green / Yellow, Green
-
-
Electrical Connections I26
Page 34
5.1.3 Cable Gland Specification
Grid, Load, Battery Cable Gland (M25)
External cable diameter10mm ~ 17mm
IPIP66
External cable diameter4.5mm ~ 9mm
Communication Cable Gland (M16)
IPIP66
[ Table 5-2 : Cable Gland Specification ]
5.1.4 Overall Drawing of the Q.HOME+ ESS HYB G2
5.1.4.1 Overall Drawing of the INVERTER
The [Figure 5-2] and [Figure 5-3] shows the overall drawing of the INVERTER.Please refer to the figure of the drawing for installation and maintenance.
BF
I
A
C
D
E G H
[ Figure 5-2 : INVERTER Bottom View ]
J
M
No.Part List
A
B
C
D
E
F
G
H
I
J
K
L
M
Battery Connector
PV Disconnection Switch
Battery Communication
PV Connector
Grid & Load Connector
Communication Part
Ethernet Communication
Demand Response Mode (Used in Australia)
Switching Board
Filter Board
Sub Filter Board
Out Connector Board
Control Board
K
L
[ Figure 5-3 : INVERTER Front inside View 1 ]
Bottom of the INVERTER
Inner of the INVERTER
27 I Electrical Connections
[ Table 5-3 : Component Description of INVERTER ]
Page 35
5.1.4.2 Overall Drawing of the Battery
The [Figure 5-4] and [Figure 5-5] shows the overall drawing of the Battery pack.Please refer to the figure of the drawing for installation and maintenance.
A
B
[ Figure 5-4 : Battery Bottom View ]
D
No.Part List
A
B
C
D
E
Cable Gland
BMS Communication Connector
BMS Board
Battery (Made by Samsung SDI)
Terminal and Circuit Breaker
[ Table 5-4 : Component Description of Battery Pack ]
C
[ Figure 5-5 : Battery Front inside View ]
Bottom of the Battery
Inner of the Battery
E
Electrical Connections I28
Page 36
5.2 Opening the Front Case Cover
NOTICE
The LCD connector and ground are connected to center of top cover. Be careful when
you detach the front cover. Make sure to connect the connector and ground before
reassembling the front cover.
As shown in the [Table 5-5], The Q.HOME+ ESS HYB G2 front cover consists of a top cover with LCD and
LED, and a bottom cover for electrical connection. Do not remove the top cover except for special events
(A / S). The Battery pack also has the same method of opening the bottom cover.
Front View
(A), (C) Screw
L : 75mm
A
B
Insert the flat-head screwdriver
as shown below and lift it up.
C
Turn the screws (A, B, C, and D)
counterclockwise to disassemble.
D
Side View
(B), (D) Screw
L : 35mm
29 I Electrical Connections
[ Table 5-5 : Front Case Open Process ]
Page 37
5.3 Battery Connections
CAUTION
• Make sure the AC circuit breaker, PV switch and DC circuit breaker of the Battery are
disconnected before starting electrical cable connections.
• Battery replacement can only be carried out by qualified personnel. If the Battery needs
to be changed, it should be placed with a product which meets the manufacturer’s
specifications.
• Do not mismatch the connection of the electric poles (+) to (-) and (-) to (+) when
installing. It may cause electric shock or the product may permanently be damaged.
You can connect a Battery to this product. The electricity generated from the connected PV array will be
stored in the Battery. Before connecting the Battery to this product, install the Battery on the place where
the Battery cables are easily accessible to this product. Refer to the installation manual of the Battery for
more information about Battery installation.
1. Open the bottom cover of INVERTER and Battery case.
• Incorrect Battery polarity connection will damage the product seriously.
This damage is not covered by the warranty.
• All other connections should be done defore Battery assembly and the Battery
interrupter must be off.
[ Figure 5-6 : Outside of Q.HOME+ ESS HYB G2 ]
Electrical Connections I30
Page 38
2. Check inner circuit breaker and terminal in Battery case.
[ Figure 5-7 : Inside of Q.HOME+ ESS HYB G2 ]
3. Connect the (+) and (-) wire (PCS) to the marked terminal (Battery). And then connect the ground
terminal.(See Chapter 5.8.4)
[ Figure 5-8 : Battery Pack and INVERTER Connection ]
4. Turn the cable gland clockwise to check the tightness.
5. As shown in the [Figure 5-10], connect Battery communication connector is composed of BMS Communication Adaptor and connect from outside. If you use more than one Battery (8kwh or more), use the adaptor (Amphenol) for Battery communication. (EX. If you use 3 Battery, you need 2 adaptor for BMS communication.) When using the adaptor, hold the communication cable and fasten the silver color of the adaptor to anticlockwise.
[ Figure 5-10 : BMS Communication Wire Connection ]
6. Change the switch on.
Switch
Move
the switch.
Switch
[ Figure 5-11 : Battery Pack Switch ]
7. Close the bottom cover of INVERTER and Battery case.
[ Figure 5-12 : Outside of INVERTER and Battery Case ]
Electrical Connections I32
Page 40
5.4 Closing the Front Case Cover
NOTICE
Make sure that connection between connector and ground match correctly, before
reassembling front lower cover.
1. Hold the front lower cover with both hands. As shown in the [Figure 5-13], slide the bottom cover atan angle and connect it to the top cover.
[ Figure 5-13 : Front Cover Assembly Process 1 ]
2. As shown in the [Figure 5-14], Use a hexagon wrench (size : M4) to fasten the bolt clockwise.
Screwing
Torque = 1.4Nm
[ Figure 5-14 : Front Cover Assembly Process 2 ]
33 I Electrical Connections
Page 41
5.5 Circuit Breaker
5.5.1 AC Circuit Breaker and DC Disconnect Switch
The circuit breaker populated on the distribution board varies depending on the installer.Follow the installation standards to install a circuit breaker satisfying the voltage, the current specificationof the Grid and the PV. Refer to Chapter 5.1.2 for cable specification.
AC circuit breaker
DC disconnect switch
[ Table 5-6 : Circuit breaker and DC Disconnection Switch ]
Standard
230Vac / 32A
650Vdc / 27A or more
Short circuit current rating
10kA minimum
-
5.5.2 RCD (residual current device) Leakage Circuit Breaker
This product can cause a DC current in the external protective earthling conductor. Where a residualcurrent-operated protective (RCD) or monitoring (RCM) device is used for protection in case of direct orindirect contact, rcd should be type b type a should have rcmu and rcmu can make inverter protect when dc conponent large than 6ma.
ItemDescription
Detecting AC residual currents and pulsating DC residual
currents of mains frequency, as well as smooth DC residual
currents and AC residual currents ≠ mains frequency
Electrical Connections I34
Page 42
5.6 An Installation Method of Energy Meter Electrical Connection
The electrical installation method of the digital energy meter (energy meter) must comply with installation
method provided by the digital energy meter manufacturer. However, the digital energy meter must be
selected.
The [Figure 5-15] shows the electrical cable connection and the communication lines of the digital energy
meter. Refer to the [Figure 5-15] and the communication description in Chapter 6 to install the digital
energy meter.
Battery
Power
Grid Output
Power
Energy
Meter for
Utility
Load Output
PV Input
Power
Power(Main)
Load Output
Power(Sub)
[ Figure 5-15 : Electric Cable Connection for Energy Meter Installation ]
The end system of the used lead wiring may be different with the energy meter chosen.
Therefore, refer to the energy meter manual.
35 I Electrical Connections
Page 43
5.7 A Connecting Method of the DC Line from the PV
Refer to the [Figure 5-15] for the PV module connection. The lead wire coming from the PV module
is connected to the distribution box. For the structure of the distribution box, refer to subsection 5.5.
For the connection to the distribution box, connect each to the terminals of the solar energy of PV1+,
PV1-, PV2+, and PV2-. On the other hand, connect the distribution box terminals with the main body
terminals (PV1+, PV1-, PV2+, and PV2-) of the Q.HOME+ ESS HYB G2 in proper order. For the connectors
(PV1+, PV1-, PV2+, and PV2-) between the distribution box and the QQ.HOME+ ESS HYB G2 input,
the following types of connectors are used. Refer to Chapter 5.1.2 for cable specification.
[ Figure 5-16 : PV Connector (Female) and PV Line (Male) ]
Check the cable connection of PV strings for the correct polarity and that the open circuit voltage
does not exceed the INVERTER input limit 550 V. If open circuit voltage is higher than 550 V,
status of INVERTER is fault.
The Male product is connected to the lead wire coming from the distribution box in the PV side,
and the Female part is attached to the Q.HOME+ ESS HYB G2. The two products are properly docked
when connected together.
When inserting or pulling out the PV connector (MC4 Type), be sure to turn off the DC disconnection
switch.
In the Q.HOME+ ESS HYB G2, the AC power input/output ports are plug type. Each cord shall be 6mm
and the diameter of the cable shall be approximately 18mm . The PE terminal is connected from the inside
2
2
of the product to the frame ground of the enclosure.
Electrical Connections I36
Page 44
* Wire connection
As shown in the [Figure 5-18], Remove the sheathed wire to conform to the connector specification,
and then roll the wire in one direction. Be careful not to bend or tangle the wires at this time.
Push the wire in until the connector "Click!" Sounds. When pulling the wire back and forth, the wire
should not be disconnected.
15,0 ... 16,5 mm
Click!
3 ... 4 Nm
[ Figure 5-18 : Wire Connection and Disconnection ]
37 I Electrical Connections
Page 45
5.8 Connection Method between Grid and Load
CAUTION
Any failure of the INVERTER when it is not connected to ground through the appropriate
terminal is not covered by the warranty.
5.8.1 Grid Connection Method
To connect the Grid of the INVERTER, you need 3 connections : Ground, Neutral and Phase. In any case, connection of the INVERTER to ground is mandatory.Insert the Grid cable into the INVERTER through the AC cable gland. Strip 9 mm of cable from the cableto connect to the Grid. Connect the Grid cable to the Sub Filter Board CN1. And then raise the handleof the connector, insert the cable, and then lower the handle of the connector to secure the Grid cable.Be sure to use the correct size cable and be free from flicker.
[ Figure 5-19 : Power Cable Connection to the AC Connector ]
5.8.2 Load Connection Method
To connect the Load of the INVERTER, you need 3 connections : Ground, Neutral and Phase. In any case, connection of the INVERTER to ground is mandatory.To connect the Load output, insert the cable into the INVERTER through the Load cable gland.Strip 9 mm of cable from the cable to connect to Load. Connect the Load cable to the Filter Board CN603.After lifting the handle of connector, insert the cable and lower the handle of the connector to secure theLoad cable. Be sure to use the correct size cable and be free from flicker.
[ Figure 5-20 : Power Cable Connection to the Load Connector ]
Electrical Connections I38
Page 46
5.8.3 Battery Connection Method
To connect the Battery, you need 3 connections : Ground, (+) and (-). In any case, connection of the INVERTER to ground is mandatory.To connect the Battery, insert the cable into the INVERTER through the Battery cable gland.Strip 9 mm of cable from the cable to connect to Load. Connect the Battery cable to the Filter Board CN401.After lifting the handle of connector, insert the cable and lower the handle of the connector to secure theBattery cable. Be sure to use the correct size cable and be free from flicker.
[ Figure 5-21 : Power Cable Connection to the Load Connector ]
5.8.4 Feature and Size of Cable
The following lists the insulation strip length details for each conductor cross section.Refer to Chapter 5.1.2 for cable specification. The ground wire should be grounded by crimping the ringterminal. Refer to Chapter 2.3.4 for work on ring terminal.
Type
Strip Length
PE = 120 mm
7-8 mm
PE
//
Grid
9 mm
//
9 mm
L
N
L = N = 210 mm
PE = 115 mm
7-8 mm
PE
//
Load
9 mm
//
9 mm
L
N
L = N = 230 mm
PE = 150 mm
7-8 mm
PE
//
Battery
9 mm
//
9 mm
39 I Electrical Connections
L = N = 170 mm
[ Table 5-8 : Insulation Strip Lengths ]
Page 47
As shown in [Figure 5-23], use the ring terminal to connect the ground wire to the correct location.When the Grid cable is connected, tighten the cable gland clockwise as shown in [Figure 5-22] andcheck the tightness.
[ Figure 5-22 : AC Cable Gland ]
BatteryLoad Grid
[ Figure 5-23 : Ground Location of Grid and Load ]
Electrical Connections I40
Page 48
5.8.5 A connecting method of DRM connection
The INVERTER supports the DRM (Demand Response Mode) function as specified in AS 4777.2 2015.
The terminal block inside the INVERTER is used for connecting to a demand response enabling device (DRED).
The DRED asserts DRMs. The INVERTER detects and initiates a response to all supported demand response
commands within 2s. The following table lists the DRMs supported by the INVERTER.
(DRM 3 and DRM7 will supply or sink reactive power.)
ModeExplanation
DRM 0
DRM 1
DRM 2
DRM 3
DRM 4
DRM 5
DRM 6
DRM 7
DRM 8
The INVERTER is in the state of “Key-stop.”
The import power from the grid is 0.
The import power from the grid is no more than 50% of the rated power.
The import power from the grid is no more than 75% of the rated power.
The import power from the grid is no more than 100% of the rated power,
but subject to the constrains from other active DRMs.
The export power from the grid is 0.
The export power from the grid is no more than 50% of the rated power.
The export power from the grid is no more than 75% of the rated power.
The export power from the grid is no more than 100% of the rated power,
but subject to the constrains from other active DRMs.
Step 1 ) Enter SIM (Installer) Page.
* Enter http://Your_IP:8000 or http://17.91.23.196:8000 (Static IP)
Step 2 ) Click Operating Test button.
3
4
Step 3 ) Click DRM-HW button.
* Make sure that the color of button changes to yellow.
Step 4 ) Click Return to Top Menu button.
• This process is valid when using DRM Hardware.
• If you want to use DRM via Modbus, see Modbus Protocol Document.
• If the ESS is rebooted, the previous setting is invalid. If you have rebooted, please try again.
Electrical Connections I42
Page 50
6. Communication Connection
6.1 Internet Connection
6.1.1 Components
• Wired Router (not provided in the product package)
• RJ45 general LAN Cable (not provided in the product package, the length of the cable must be
less than 10m.)
6.1.2 Connection Block Diagram
• LAN (Common carrier → Router) → ESS
Router
RJ45 LAN CABLERJ45 LAN CABLE
[ Figure 6-1 : Internet Connection ]
Common
Carrier
6.1.3 Connection Method
Plug the RJ45 LAN Cable between the LAN terminal and the Router.Use the Ethernet crimper to crimpthe cable and connect the cable to RJ45 plug. The RJ45 cable is responsible for communication betweenthe web and the PMS board.
1 2 3 4 5 6 7 8
RJ45 PlugRJ45 Port
[ Figure 6-2 : RJ45 Cable ]
Sealing Nut
Seal
Housing Sub-Assy
43 I Communication Connection
Pass the screw nut, seal and support through the RJ-cable
(Cable OD range : 5.0~6.5mm)
Support
Tighten the screw nut (Tightening torque range : 5~15kgf·cm)
[ Figure 6-3 : RJ45 External Connector Assembly ]
Page 51
6.2 The Communication Terminal
• Energy meter : Connect to RS-485 Energy Meter, Out Connector Board CN2.
• Short bar is connected to CN1. Refer to Chapter 7.2.
Energy Meter
CN2
CN1
RS485/CAN
CN3
I/O EXT
CN4
CN906
CN905CN901CN902CN904
Emergency
CN5
[ Figure 6-4 : Communication Terminal ]
Short bar locationDescription
①, ②
③, ④
⑤, ⑥
⑦, ⑧
⑨, ⑩
You can connect to the System
Install Manager (SIM) and set IP.
Using this pins is permitted only
to the qualified personnel.
Using this pins is permitted only
to the qualified personnel.
Using this pins is permitted only
to the qualified personnel.
Default
Pin map
① ②
③ ④
⑤ ⑥
⑦ ⑧
⑨ ⑩
[ Table 6-1 : Description of Short Bar Location ]
Communication Connection I44
Page 52
6.3 Energy Meter Connection
6.3.1 RS-485 Interface
6.3.1.1 Components
• RS-485 Meter
- The Energy Meter uses RS-485 Interface for communication.
• Connection line (Not provided in the product package)
- It should be applied to a twisted-pair type.
• Cable length limit
- The RS-485 meter communication cable must be used within 100 m.
Make sure that the housing and connector are connected. As shown in the [Figure 6-5], separatehousing from connector. And press the lock with a flat-head screwdriver to connect the communicationcable. The RS-485 meter communication cable must be used within 100m.
6.3.2 Connection Energy Meter
Pass the communication cable through the cable gland and tighten the cable gland. Connect the energymeter to the INVERTER as shown in the [Table 6-2].
INVERTER
RS458-A
RS485-B
[ Table 6-2 : Recommended Meter List ]
Energy Meter
42
41
45 I Communication Connection
Page 53
[ Figure 6-6 : Energy Meter Connection Method ]
CN906
CN2
CN1
RS485-A
CN2
CN3
CN4
CN5
CN906
CN1
CN905CN901CN902CN904
OUT Connector Board
RS485-B
CGND
CGND
[ Figure 6-7 : Energy Meter Connection Method ]
6.4 Recommended Energy Meter List
No.CompanyModelInterfaceDirection
1
2
CARLO GAVAZZI
CARLO GAVAZZI
EM24-DIN.AV9.3.X.IS.X
EM112-DIN.AV0.X.S1.X
RS-485
RS-485
Bi-direction
Bi-direction
[ Table 6-3 : Recommended Meter List ]
Communication Connection I46
Page 54
6.5 Homepage
Any customer who has purchased this device can use a web browser (https://myess.hansoltechnics.com)or a smart phone to check its current operation status and receive various statistical information on operationin the house or remotely.
6.5.1 Service Terms
This service is provided only when the device is connected to the Internet, and specific services may requireadditional information only after approval from the customer.
6.5.2 Membership
To use this service, you must register for membership through our homepage.During membership registration, the member’s information such as ID, password, name and the addressare collected, and additional data may also be collected to provide statistical information upon customer’sapproval.
6.5.3 Membership Withdrawal
For a customer who does not want to use this service, membership withdrawal is available through thepersonal information modification menu on the homepage.
6.5.4 Log-In
Log in to the homepage through the ID and the password generated through membership registration.You can monitor the product online only when you are logged in. Also, if a log-in ID error or a passworderror occurs five consecutive times, access is blocked for 10 minutes for security reasons, and accessis permitted after this waiting period of time.
47 I Communication Connection
[ Figure 6-8 : Log-in Page ]
Page 55
6.5.5 Password Initialization
A customer who forgets the password during use can initialize the password by using the passwordinitialization menu on the homepage. On the log-in page, select the “Forgot your id or password?” menu,and when the customer confirms the ID and the e-mail address created during membership registration,the initialized password is sent to the registered e-mail address.
[ Figure 6-9 : Password Initialization Page ]
6.5.6 Types of Service Offered
After completing log-in, normal service is available. This service currently provides such menu itemsas monitoring, consumption reports, ESS reports, ESS forecasts, and notices.
6.5.6.1 Monitoring
The operational status of the product is indicated. You can check the current status of operation, thecustomer's power consumption information, and power generation amount information in real-time.You can also check event codes generated during run time on the monitoring page. You can checkthe details of the event codes by clicking the exclamation marks which appear on the ESS icon.If the Internet is not available, the event codes cannot be checked.
[ Figure 6-10 : Monitoring Page ]
Communication Connection I48
Page 56
The [Figure 6-11] shows the backup mode screen. This mode can be specified by the user.Since the Grid does not consume power separately in the backup mode, it shows only the ESS.In the figure below, warning on ESS is an error that power does not come on the Grid.
[ Figure 6-11 : Backup Mode Monitoring Page ]
6.5.6.2 Consumption Report
The household power consumption information collected during energy meter linkage is provided.In particular, such information on as the household type, the size, and the number of family residentsis collected according to the customer's approval. You can use these data to identify various typesof statistics and comparative analysis data.
[ Figure 6-12 : Consumption Report Page ]
6.5.6.3 ESS Report
On the ESS Report page, you can check various types of data generated through ESS operation.You can also use the ESS Report to check the amount of energy charged or discharged and otherdata comparisons with the solar energy production amount or the power sales amount.
49 I Communication Connection
Page 57
6.5.6.4 ESS Forecast
In the ESS Forecast menu, the generation amount forecast information and the guide for optimizedoperation can be checked through the algorithm mounted on the product.
[ Figure 6-13 : Forecast Page ]
6.5.6.5 Notices
You can check the notice message whenever there is an update or any other change in the service.
6.5.6.6 Software Versions
You can check the software version of the product on the monitoring page.
Software
Version
[ Figure 6-14 : Setting Page ]
Communication Connection I50
Page 58
6.5.7 Mobile Service
Customers who use Android or I-Phone can use a smart phone to easily check the product statusanytime, anywhere. To use the mobile service, the customer must first register the membership throughthe webpage and use the ID and the password to log-in.
[ Figure 6-15 : Mobile Service Page ]
51 I Communication Connection
Page 59
7. Entering Initial Installation Information
You can use the following procedure to enter the initial installation information and to monitor the operational
information of this system appropriately on server.
7.1 Information Input Administrator
You have to use a laptop or a smart phone to enter the installation information.
7.2 System Information Input Stage
• 1st Step : Direct Connection to PC → Input Local Setting Value
• 2nd Step : Connection to Web Page → Input Webpage Setting Value
7.3 PC Direct Connection and Local Setting Value
7.3.1 PC Direct Connection Flow
• System Off Status → Insert Jumper Wire, Connect PC LAN cable → System AC on → PC Direct Connection → Input Setting Value → System off → Remove Jumper Wire →Connect Internet LAN Cable
7.3.2 LAN Cable Connection between PC and System
7.3.2.1 LAN Cable Type
• UTP cable/category 5E
• 1:1 direct cable
7.3.3 SIM (System Install Manager) Connection
7.3.3.1 Connection
• To enable direct communication between the computer and the Q.HOME+ ESS HYB G2, changethe TCP/IP settings on the computer as shown below :
1. Set on your laptop[Control Panel → Network and Sharing Center → Change adapter settings → Local Area Connector→ Properties → Internet Protocol Version 4 (TCP/Ipv4)]
IP address: 17.91.23.1
Subnet mask: 255.255.224.0
Default gateway: 17.91.1.2
Entering Initial Installation Information I52
Page 60
[ Figure 7-1 : Setting Laptop IP ]
CAUTION
• Turn off Wifi.
• Only turn on Local Area Connection.
2. Connect the short bar to the connector. (*If you want to connect System Install Manager (SIM) page, connect the short bar to pin 1 & 2as shown in the [Figure 7-2].)
Short Bar
CN906
CN2
53 I Entering Initial Installation Information
CN905CN901CN902CN904
CN1
CN3
CN4
[ Figure 7-2 : Connecting Short Bar ]
CN5
Page 61
3. Connect the LAN cable between Q.HOME+ ESS HYB G2 and Laptop.
4. Turn the power On (Grid On) and PV S/W On.
5. Access to SIM (System Install Manager)http://17.91.23.196:8000
6. Install the settings (As shown in the [Figure 7-3]).
7. Turn the power Off (Grid Off) and PV S/W Off. → Remove Jumper Wire.
8. Connect Internet LAN Cable.
9. Turn the power On (Grid On) and PV S/W On.
7.3.3.2 Connection URL
• http://17.91.23.196:8000
7.3.3.3 Connection Screen
4
5
1
2
3
1 - Value : INVERTER Active Power
• Input Range : 0 ~ 100% (P/Pmax)
• Pmax = Maximum INVERTER Output Power
2 - SL,SH : Rate of change of power with respect to frequency change
Save the selected Country / Region and proceed to the next step.
7.3.4.2 Battery Install - Initialize
1
2
Step 1 ) Click here.Step 2 ) Select Initial ID function and click SELECT button.
55 I Entering Initial Installation Information
Page 63
34
Step 3 ) Connect the Communication Cable of all the Batteries you want to install.Step 4 ) Then click the START button.
5
Step 5 ) If it completes normally, the same screen appears. If there is a problem return to “Step 1”.Then click the FINISH button to complete Initialize.
Entering Initial Installation Information I56
Page 64
7.3.4.3 Battery installation process.
1
Step 1 ) Click here.Step 2 ) Select Auto function and click SELECT button.
2
Step 3 ) Select the number of batteries you want to install.Step 4 ) Click the ENTER button.
43
57 I Entering Initial Installation Information
Page 65
56
Step 5 ) Connect the Communication Cable of the first Battery you want to install.Step 6 ) Then click the ‘Configure ID !!!’ button.
7
Step 7 ) Wait until the battery connected the communication Cable is installed.
Entering Initial Installation Information I58
Page 66
8
Step 8 ) When the installation is completed for the desired Number of batteries, ‘SAVE BMS ID’ button
will Appear as below.
Then click the ‘SAVE BMS ID’ button to complete The installation.
Step 9 ) If there are still batteries left to install, the following Screen appears. Repeat the previous step.
59 I Entering Initial Installation Information
Page 67
7.3.5 Battery Installation Process with HMI
1
2
Step 1 )
Touch Battery Icon 10 times.
Step 2 )
Select. [Initial ID]
3
5
6
Step 3 )
Click Next Button.
Step 4 )
※ All Battery Pack Communication Cables are
Connected.
Step 5 )
Click Next Button.
Step 6 )
Check Initialization Success Message.
※ If there is Failure Message, Click Stop Button
and Check Communication Line.
Go to Sequence No.2. [Initial ID]
7
Step 7 )
Click Finish Button when Initialization is successful.
Entering Initial Installation Information I60
Page 68
Step 8 )
9
※ Disconnect all communication cable.
Open Circuit Breakers.
Step 9 )
Select [Auto] and set the amount of the battery to install.
※ Example) Amount of batteries to install : 2
13
10
12
14
Step 10 )
Click Next Button.
Step 11 )
※ Connect the communication cable of the First battery.
(The communication cable of the 2nd battery is
not connected.)
Step 12 )
Click Next Button.
Step 13 )
Check Initialization Success Message.
※ If there is Failure Message, Click Stop Button
and Check Communication Line.
Go to Sequence No.2. [Initial ID]
Step 14 )
Click Next Button.
16
61 I Entering Initial Installation Information
17
Step 15 )
※ Connect the communication cable of the 2nd battery.
(The communication cable of the 1st battery is not connected.)
Step 16 )
If there is Failure Message, Click Stop Button
and Check Communication Line.
Go to Sequence No.2. [Initial ID]
Step 17 )
Click Finish Button.
Step 18 )
※ When installing more batteries, Follow and Repeat
this procedure above.
Page 69
7.3.6 Entering Setting Value
7.3.6.1 S/N
• Enter shipment value from the factory (a subsequent modification is not available.)
7.3.6.2 Region
• Select a city and enter the city name for installation on the menu.
7.3.6.3 Country / Region Configure
• Save the selected Country / Region and proceed to the next step.
7.3.6.4 PV Install Value
• Enter installation capacity of each PV string.
• Enter by typing by hand.
7.3.6.5 Sever IP & Port
• Enter as basic value.
• Perform any modification for relevant issues only.
7.3.6.6 Energy Meter Selection
• Meter Type
- RS-485
• RS-485 Meter model selection
- Energy Meter recommends using EM24.
Refer to the Quick Guide for Energy Meter self-configuration and installation.
7.3.6.7 Date / Time setting
• Enter the current date and time.
7.3.6.8 Save and Restart
• Save onto the system after all the procedures above are completed.
7.3.6.9 Grid Feed in Limit Regulation Setting
• For some countries that have a regulation for the Grid feed in limit, the device allows the installerto set up a limit value. You can select the required limit value in the [Feed in Limit Percentage]on the set up screen. The selectable values is 0%,10%,20%,30%,40%,50%,60%,70%,80%,90%,and unlimited. The term unlimited means that is that there is no Grid feed-in limit.
Entering Initial Installation Information I62
Page 70
7.4 Web Page Connection
7.4.1 Web Page Connection
Open an Internet browser of your laptop or smart phone, then enter the designated address.Then the system information input page pops up.
• Input URL : https://myess.hansoltechnics.com
• Concurrent support of PC and Mobile
1. By typing ““https://myess.hansoltechnics.com,”access the corresponding website. Then click the“Go to Installer” icon at the top.
CLICK!
NOTICE
• Note that the URL starts with "http://".
• In case your computer, tablet, or smartphone does not support HTML5, it may not
operate normally.
• Some older smart devices may not operate normally, if its browser version is lower.
63 I Entering Initial Installation Information
[ Figure 7-4 : Main Page ]
Page 71
2. Enter your ID and password in the login window. If you have no account, please join as a Member
NOTICE
• To install the product, you must obtain an installer membership instead of a general
membership.
• To join as an installer member, a special number is required. First check the special
number from the local dealer or service center.
3. Click the “Join Membership” link.
4. In order to join as a member, you must consent to the terms for personal privacy protection.The terms have been prepared in accordance with applicable local laws.If you do not agree to the terms, you cannot join as a member.
5. Enter the required information for registration.
NOTICE
• The optional items for company name and eamil address are necessary for quick contact
and response from the service center.
• Enter the number identified through a pre-contact in Special Number.
6. After obtaining a membership, a completion message appears. Click the "Log In" button.
7. After login, the main installer page appears. After selecting the menu button at the upper left corner,select Product → Installation.
[ Figure 7-5 : Installer in Page ]
8. The installation wizard runs automatically. Explain the terms for personal privacy protection to yourcustomer and obtain the consent to the terms with a signature.
NOTICE
• The data collected during the installation process is used only for installation purpose.
• The consent and signature acquisition process proceeds according to the local laws.
We at Q CELLS are making the utmost effort to protect personal information
in accordance with the laws.
Entering Initial Installation Information I64
Page 72
9. Enter the product information and customer information in Step 1. The product serial number and
user telephone number are required. The product serial number is on the upper area of the cover.
Please also enter your country and BATT.
[ Figure 7-6 : Product Information Entry Screen in Step 1 ]
NOTICE
• If you enter the product serial number (21 characters), the rest of the information is
automatically filled in.
• The user telephone number is used for after-sales service purpose.
10. Enter the information of the installation site in Step 2. In the address input field, enter the address or
select the installation site on the map. After the installation site entry is finished, click the "Next" button.
[ Figure 7-7 : Address Entry in Step 2 ]
NOTICE
• In the address input box, enter the country and city. It is recommended to move the
focus on the map and select the installation site.
• If the location is incorrect, the smart operation algorithm may not operate normally.
65 I Entering Initial Installation Information
Page 73
11. Enter the product Setup Information details in Step 3. Enter values for installed capacities for eachPV string, feed-in limit (e.g. 60% in Germany), maximum INVERTER power, whether or not to usethe basic mode, energy meter type, and its model. Q CELLS supports stable country default settings.(Countries that do not have their current default settings will be supported in the future.)
EM112
[ Figure 7-8 : Product Setup Information Details Entry in Step 3 ]
CAUTION
If configuration in this page has errors, it may cause product failure.
Accordingly, first check specific installation conditions of the house for accuracy.
12. Enter the energy rate Information of the house in Step 4. If a house uses a variable tariff , the charge
and discharge operations may differ depending on the input price. Enter the time-based electricity
tariff correctly. If a house uses a fixed payment tariff, the charge and discharge operations are not
affected depending on the input price. The entry of energy price is used only for reference to calculate
energy costs and it may not be the same as the actual electricity rate.
[ Figure 7-9 : Energy Rate Information Entry in Step 4 ]
Entering Initial Installation Information I66
Page 74
NOTICE
The entry of energy price is used only for reference to calculate energy costs and it may
not be the same as the actual electricity rate. Q CELLS will not assume responsibility for
incorrect estimated rates.
13. End the installation. If you click the "Done" button, the product monitoring details page appears.
Check whether the login is finished within 2 to 3 minutes. Some products immediately run
“Automatic Update.”
67 I Entering Initial Installation Information
[ Figure 7-10 : Installation Completion Screen ]
Page 75
8. Operating Test
8.1 LED Indications
As shown in the [Figure 8-1], the LED of Q.HOME+ ESS HYB G2 is located at bottom of LCD.The color of LED depend on current status of INVERTER and LED display information can be checkedin [Table 8-1].
ABC
[ Figure 8-1 : LCD Location ]
Solar (A)Battery (B)Grid (C)
OFF
Green
Red
8.2 Starting the System
After completing the installation, turn on the AC circuit breaker installed in the distribution box and thenturn on the DC disconnect switch on the product.Check the system check message on the front LCD screen.
Energy is not being generated.
Energy is being generated.
Fault
[ Table 8-1 : LED Indications ]
Battery is not connected.
Battery is connected.
Fault
Grid is not connected.
Grid is connected.
Fault
8.2.1 Loading Screen & Update Screen
The [Figure 8-2] is displayed at the time of initial boot, and the home screen is displayed wheninternal communication is normal. The time setting is automatically renewed when connectedto the network. The [Figure 8-3] is a screen display when ESS Software (PMS & PCS) is updated.
[ Figure 8-2 : Initial Indication Screen on Power On ][ Figure 8-3 : Update Screen ]
Entering Initial Installation Information I68
Page 76
8.2.2 Home Screen Configuration Information
② ③ ④
①
02 : 52 PM
PV
5.06kw
BATTERY
⑬
No.Screen Information
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
⑪
⑫
⑬
1.60kw
⑥⑤
[ Figure 8-4 : Standby State Indication Screen before the EMS Command ]
Time Information
Operation Status
Network Connection Status
Meter Connection Status
Home Button
Previous Button
Next Button
PV Power
Load Power
Battery Power
Grid Power
ESS Status Information
Battery SOC
Hybrid ESS
⑧⑨
ESS
⑩⑪
Normal
Display time information
Internal communication connection status
(PV, Battery, Indication during independent operation)
Display status when connecting to Ethernet network
Display status when connecting to meter
Go to home display
Go to previous screen
Go to next screen
Display current PV power
Display current Load power
Display current Battery power
Display current Grid power
Display ESS normal operation
(Standby/Normal/Fault/Fault Lock/Error Comm)
Battery SOC status
⑫
LOAD
1.47kw
GRID
1.98kw
⑦
Description
[ Table 8-2 : Screen Configuration Information ]
You will receive the command from the EMS to convert to operation mode.For individual operation mode screen, refer to 8.4.
69 I Operating Test
Page 77
8.2.2.1 Home menu structure
If you touch next or previous button, the screen is displayed as shown in the [Figure 8-5].The description of each screen refer to Chapter 8.5
[ Figure 8-5 : Home Menu Structure ]
8.3 Turning off the System
To turn-off the system, turn off the DC disconnection switch and then push down the manual AC circuitbreaker in the distribution board.
Operating Test I70
Page 78
8.4 Descriptions of Operation Mode
This system is composed of six modes: PV Auto, PV Only, Battery discharge, Standby, Maintenance(forced charge), and Stand-Alone (Back-up). The event check status should not be considered as any specific mode.
8.4.1 Status Description
ModeScreen Information
PV
Generation
Battery
Charge
Battery
Discharge
Grid Input
Grid Output
Load Input
ESS
ESS
ESS
ESS
ESS
ESS
Description
The electrical power is generated by PV.
The Battery is charging.
The Battery is discharging.
Supply the electrical power of
Grid to INVERTER.
The power generated from the
PV is fed into the Grid.
The power generated by INVERTER
is supplied to Load.
[ Table 8-3 : Status Description ]
8.4.2 Operation Sequence
ELAELA Mode
PVBatteryGridLoad
Auto W/S Mode
PV Output
Grid Charge
Battery Discharge
Stand Alone
O
O
X
O
O
O
X
O : It enters when there is a battery fault.
O
O
O
O
O
O
O
O
O
Battery fault
or No Battery
PV
Output
Battery Voltage
emergency
Auto w/s
(Basic Mode)
No
Grid
PV Voltage
No
Grid
Stand
Alone
No
No
Grid
X : Don’t care. One of the PV and the battery
is in a steady state.
Grid
Charge
Battery
Discharge
[ Table 8-4 : ELA Mode ]
8.4.3 Standby Mode
This is the standby mode before converting to operation mode (PV Auto, PV Only, Battery discharge mode).Conversion to the operation mode (PV Auto, PV Only, Battery discharge mode) is made by the EMS decision.
71 I Operating Test
Page 79
8.4.4 PV-Auto Mode
This mode is divided into three types depending on the state of the Battery power.
8.4.4.1 Weak
Solar energy generation and Battery discharging are available. The solar-generated power is supplied to sub and load. In case of insufficient power, the battery is discharged on the EMS decision. When LoadOutput Power (Sub) is higher than power generation of PV and Battery, Grid power is supplied to the Sub.
• Use smart meter. The energy supply priority is : load (sub+main) > grid
• Not use smart meter. The energy supply priority is : sub_load > grid
Battery
Power
Grid Output
Power
Energy
Meter for
Utility
Load Output
Power(Main)
PV Input
Power
Load Output
Power(Sub)
One Way
Bi-directional way
Inactive
[ Figure 8-6 : Diagram of PV-Auto Weak Mode ]
8.4.4.2 Strong
Solar energy generation and Battery charging are available. The solar-generated power is chargedto the Battery based on the EMS decision.
• Use smart meter. The energy supply priority is : load (sub+main) > battery > grid
• Not use smart meter. The energy supply priority is : sub_load > battery > grid
Battery
Power
PV Input
Power
Grid Output
Power
Energy
Meter for
Utility
Load Output
Power(Main)
Load Output
Power(Sub)
[ Figure 8-7 : Diagram of PV-Auto Strong Mode ]
One Way
Bi-directional way
Inactive
Operating Test I72
Page 80
8.4.4.3 Both
Both solar energy generation and Battery charge-discharge are available. The solar-generated power ischarged or discharged to the Battery based on the EMS decision.
• Use smart meter. The energy supply priority is : load (sub+main) > battery > grid
• Not use smart meter. The energy supply priority is : sub_load > battery > grid
Battery
Power
Grid Output
Power
Energy
Meter for
Utility
Load Output
Power(Main)
PV Input
Power
Load Output
Power(Sub)
One Way
Bi-directional way
Inactive
[ Figure 8-8 : Diagram of PV-Auto Strong Both Mode ]
8.4.5 PV-Only Mode
This mode enables the solar energy to be generated. However, the Battery charge-discharge doesnot operate. A maximum of power or less of solar energy generation power can be sent to Grid basedon the EMS decision.
• Use smart meter. The energy supply priority is : load (sub+main) > grid
• Not use smart meter. The energy supply priority is : sub_load > grid
73 I Operating Test
Battery
Power
PV Input
Power
Grid Output
Power
Load Output
Power(Main)
Load Output
Power(Sub)
[ Figure 8-9 : Diagram of PV-Only Mode ]
Energy
Meter for
Utility
One Way
Bi-directional way
Inactive
Page 81
8.4.6 Battery-Discharge Mode
This mode permits of no solar energy generation. Battery discharge is only available on this mode.Based on the EMS decision, the Battery discharge power can be sent maximum 3kW or less only to the Load.
• Use smart meter. The energy supply priority is : only load (sub+main)
• Not use smart meter. The energy supply priority is : sub_load
Battery
Power
Grid Output
Power
Energy
Meter for
Utility
Load Output
Power(Main)
PV Input
Power
Load Output
Power(Sub)
One Way
Bi-directional way
Inactive
[ Figure 8-10 : Diagram of Battery-Discharge Mode ]
8.4.7 Stand-Alone (Back-up) Mode
When Q.HOME+ ESS HYB G2 is disconnected from the grid, Q.HOME+ ESS HYB G2 enters into the Stand-Alone (Back-up) Mode.
• Use smart meter. The energy supply priority is : sub_load > battery
• Not use smart meter. The energy supply priority is : sub_load > battery
Battery
Power
PV Input
Power
Grid Output
Power
Energy
Meter for
Utility
Load Output
Power(Main)
Load Output
Power(Sub)
[ Figure 8-11 : Diagram of Stand-Alone (Back-up) Mode ]
One Way
Bi-directional way
Inactive
Operating Test I74
Page 82
8.4.8 Grid Charge Mode
The grid charging function operates when the battery is in the emergency mode.
(Battery soc works when less than 3%) Maximum input power is only 4600W.
• Use smart meter. The energy supply priority is : load > battery
• Not use smart meter. The energy supply priority is : load > battery
Battery
Power
Grid Output
Power
Energy
Meter for
Utility
Load Output
Power(Main)
PV Input
Power
Load Output
Power(Sub)
One Way
Bi-directional way
Inactive
[ Figure 8-12 : Grid Charge Mode ]
8.4.9 Event Check Mode
This mode stops solar energy generation and put it in standby mode as an event occurs.
75 I Operating Test
Page 83
8.5 Information Display
8.5.1 PV Information display
[ Figure 8-13 : PV Information Display ]
Display
PV1 Voltage
PV1 Current
PV1 Power
PV2 Voltage
PV2 Current
PV2 Power
Today Power
Total Power
Graph
Description
Display current PV1 voltage
Display current PV1 current
Display current PV1 power
Display current PV2 voltage
Display current PV2 current
Display current PV2 power
Display today’s PV power
Display the mount of PV power
Display PV power graph (Daily/Weekly/Monthly/Yearly)
(If you want to see the next graph, touch graph screen.)
[ Table 8-5 : PV Information Display Description ]
Operating Test I76
Page 84
8.5.2 Grid Information display
[ Figure 8-14 : Grid Information Display ]
Display
Voltage
Frequency
Current
Power
Power Factor
Today Feed-in Power
Today Feed-out Power
Total Feed-in Power
Total Feed-out Power
Graph
Description
Display Grid voltage
Display Grid frequency
Display Grid current
Display Grid active power
Display Grid power factor
Display today’s power received from the Grid
Display today’s electricity sent to the Grid
Display the amount of electricity received from the Grid
Display the amount of electricity sent to the Grid
Display Grid power graph (Daily/Weekly/Monthly/Yearly)
(If you want to see the next graph, touch graph screen.)
[ Table 8-6 : Grid Information Display Description ]
77 I Operating Test
Page 85
8.5.3 Load Information display
[ Figure 8-15 : Load Information Display ]
Display
Voltage
Current
Frequency
Power
Today Power
Total in Power
Graph
Description
Display Load voltage
Display Load current
Display Load frequency
Display Load active power
Display today’s Load power
Display the amount of power used in today's Load
Display Load power graph (Daily/Weekly/Monthly/Yearly)
(If you want to see the next graph, touch graph screen.)
[ Table 8-7 : Load Information Display Description ]
Operating Test I78
Page 86
8.5.4 Battery Information display
[ Figure 8-16 : Battery Information Display ]
Display
Voltage
Current
Power
SOC
SOH
Today Charge Power
Today Discharge Power
Total Power Charge
Total Power Discharge
Graph
Description
Display Battery voltage
Display Battery current
Display Battery charging / discharging power
State of charge
State of health
Display today's Battery charge power
Display Battery power factor
Display the amount of Battery charge power
Display the amount of Battery discharge power
Display Battery power graph (Daily/Weekly/Monthly/Yearly)
(If you want to see the next graph, touch graph screen.)
[ Table 8-8 : Battery Information Display Description ]
79 I Operating Test
Page 87
8.5.5 System Information display
[ Figure 8-17 : System Information Display ]
Display
Product Model
Product Country
IP Address
Software Version
PMS Version
PCS Master Version
PCS Slave Version
HMI Version
BMS Version
Description
Name of this product
Country using this product
IP Address
Software version of this product
Software version of PMS
Software version of PCS master
Software version of PCS slave
Software version of HMI
Software version of BMS (up to 5 types)
[ Table 8-9 : System Information Display Description ]
Operating Test I80
Page 88
8.5.6 Error Information display
[ Figure 8-18 : Error Information Display ]
Date
Time
Error
Display
Description
The date the fault occurred.
The time the fault occurred.
Type of fault (See Chapter 9.1)
If there are more than 10 errors, the first error is cleared.
[ Table 8-10 : Error Information Display Description ]
81 I Operating Test
Page 89
9. Problem Confirmation
Checking event codes is available on the website (https://myess.hansoltechnics.com).
If the Internet is not available, the event codes cannot be checked.
9.1 General Events
The general events contain warnings and protection.
The warning level events does not stop the generating process. A displayed warning message automatically
disappears as soon as the issue is resolved.
When protection level events occur, the product stop the generating process. The process may automatically
resume as long as the issue is resolved.
9.1.1 INVERTER General Events (Protection)
Type : PROTECTION
WEB DisplayHMI DisplayDescriptionMeasures
BDC I TZM PD01P
BDC I TZS PD02P
BDC1 COC PD03P
BDC Current Trip
Zone Master Protection
BDC Current Trip
Zone Slave Protection
BDC1 Charge RMS
Over Current Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BDC1 COCP PD04P
BDC1 Charge Over
Current Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Problem Confirmation I82
Page 90
WEB DisplayHMI DisplayDescriptionMeasures
BDC1 DOC PD05P
BDC1 DOCP PD06P
BDC2 COC PD13P
BDC1 Discharge
RMS Over Current
Protection
BDC1 Discharge
Over Current Peak
Protection
BDC2 Charge RMS
Over Current Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BDC2 COCP PD14P
BDC2 DOC PD15P
BDC2 DOCP PD16P
BDC2 Charge Over
Current Peak Protection
BDC2 Discharge RMS
Over Current Protection
BDC2 Discharge Over
Current Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. nbWait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
83 I Problem Confirmation
Page 91
WEB DisplayHMI DisplayDescriptionMeasures
BDC UV PD21P
BDC RMS Under
Voltage Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BDC OV PD22P
BDC RMS Over
Voltage Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BDC OVP PD23P
BDC Over Voltage
Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BDC OW PD24P
BDC RMS Over Watt
Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BDCM OT PD25P
BDC Module Over
Temp Protection
When the switch temperature is high.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
BDCM UT PD26P
BDC Module Under
Temp Protection
When the switch temperature is low.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Problem Confirmation I84
Page 92
WEB DisplayHMI DisplayDescriptionMeasures
INV I TZM PG01P
INV I TZS PG02P
INV OW PG03P
INV Current Trip Zone
Master Protection
INV Current Trip Zone
Slave Protection
INV Over Watt
Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
INV OC PG04P
INV OCP PG05P
INV OT PG06P
INV RMS Over Current
Protection
INV Over Current
Peak Protection
INV Module Temp
Over Temp Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
When the switch temperature is high.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
85 I Problem Confirmation
Page 93
WEB DisplayHMI DisplayDescriptionMeasures
INV UT PG07P
INV Module Temp
Under Temp Protection
When the switch temperature is low.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
GRID OW PG11P
Grid Over Watt
Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
GRID UV PG12P
Check the connection of Grid Voltage cable.Grid RMS Under
Voltage Protection
GRID OV PG13P
Grid RMS Over
Voltage Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
GRID OVP PG14P
Grid Over Voltage
Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
GRID OF PG15P
Grid Over Frequency
Protection
The operation mode is terminated when
a power system event occurs.
Restart 1 minute after the electric power
system event is settled
GRID UF PG16P
Grid Under Frequency
Protection
The operation mode is terminated when
a power system event occurs.
Restart 1 minute after the electric power
system event is settled
Problem Confirmation I86
Page 94
WEB DisplayHMI DisplayDescriptionMeasures
G24P
RCMU N PG22P
RCMU SD PG23P
GRID OV
10Min P
DC Injection ProtectionDC Injection PG21P
Residual Current
Monitoring Unit
Normal Protection
Residual Current
Monitoring Unit
Sudden Protection
Grid 10 Minute
Average Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Turn off system power when the leakage
current level is above standard level.
Check the leakage current level, then restart
or turn off to get back to the below standard
level.
Turn off system power when the leakage
current level is above standard level.
Check the leakage current level, then restart
or turn off to get back to the below standard
level.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
G25P
ANTI
ISLANDING P
GRID AD PG31P
Relay L1 PG32P
Relay L2 PG33P
Anti-Islanding
Protection
Grid V AD
Measurement
Protection
Relay L1 Abnormal
Operation Protection
Relay L2 Abnormal
Operation Protection
If the electric power system blacks out,
it automatically detects the state and
turns off the Q.HOME+ ESS HYB G2.
(shifting the frequency of the inverter away
from nominal conditions in the absence of
a reference frequency. (frequency shift))
The error of Master & slave AD value
is more than 2%. A/S is required.
Relay L1 is burned out.
A / S is required.
Relay L2 is burned out.
A / S is required.
87 I Problem Confirmation
Page 95
WEB DisplayHMI DisplayDescriptionMeasures
Relay L3 PG34P
Relay L3 Abnormal
Operation Protection
Relay L4 PG35P
Relay L4 Abnormal
Operation Protection
Load OC PL01P
Load RMS Over
Current Protection
Relay L3 is burned out.
A / S is required.
Relay L4 is burned out.
A / S is required.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Load OCP PL02P
Load Over Current
Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Load UV PL03P
Load RMS Under
Voltage Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Load OV PL04P
Load RMS Over
Voltage Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Load OVP PL05P
Load Over Voltage
Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Problem Confirmation I88
Page 96
WEB DisplayHMI DisplayDescriptionMeasures
Load OF PL06P
Load UF PL07P
Load OW PL08P
Load Over Frequency
Protection
Load Under Frequency
Protection
Load Over Watt
Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
PV1 RC PS01P
PV1 OV PS04P
PV1 OVP PS05P
PV1 String Reverse
Connection Protection
PV1 RMS Over
Voltage Protection
PV1 Over Voltage
Peak Protection
Please check PV1 (+) and (-) wiring. If the
connection is successful, wait until the event
message disappears. When the event
message is removed, it automatically returns
to the normal state. If it is not removed until
the time limit is reached, it is converted to
a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
89 I Problem Confirmation
Page 97
WEB DisplayHMI DisplayDescriptionMeasures
PV1 OC PS06P
PV1 RMS Over
Current Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
PV1 OCP PS07P
PV1 Over Current
Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
PV1 OW PS08P
PV1 RMS Over Watt
Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
PV2 RC PS11P
PV2 String Reverse
Connection Protection
Please check PV2 (+) and (-) wiring. If the
connection is successful, wait until the event
message disappears. When the event
message is removed, it automatically returns
to the normal state. If it is not removed until
the time limit is reached, it is converted to
a significant event.
PV2 OV PS14P
PV2 RMS Over
Voltage Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
PV2 OVP PS15P
PV2 Over Voltage
Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Problem Confirmation I90
Page 98
WEB DisplayHMI DisplayDescriptionMeasures
PV2 OC PS16P
PV2 OCP PS17P
PV2 OW PS18P
PV2 RMS Over
Current Protection
PV2 Over Current
Peak Protection
PV2 RMS Over Watt
Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
S23P
S24P
PVM OT PS21P
PVM UT PS22P
PV1
INSULATION P
PV2
INSULATION P
PV Module Over
Temp Protection
PV Module Under
Temp Protection
PV1 Insulation
Protection
PV2 Insulation
Protection
When the switch temperature is high.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
When the switch temperature is low.
Wait until the event message disappears.
After the event message is removed, it
automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Turn off system power if PV1 insulation
resistance is at the standard level.
Turn off system power if PV2 insulation
resistance is at the standard level.
91 I Problem Confirmation
Page 99
WEB DisplayHMI DisplayDescriptionMeasures
S31P
DCLINK V
TZM P
DCLINK UV PS32P
DCLINK OV PS33P
DCLINK Voltage Trip
Zone Master Protection
DCLINK RMS Under
Voltage Protection
DCLINK RMS Over
Voltage Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
S34P
DCLINK OVP
P
[ Table 9-1 : INVERTER General Events Warning List ]
DCLINK Over Voltage
Peak Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Problem Confirmation I92
Page 100
9.1.2 Battery General Events (Protection)
Type : PROTECTION
WEB DisplayHMI DisplayDescriptionMeasures
B01P
B02P
B03P
BAT1 CHG
OC P
BAT1 DCHG
OC P
BAT1 CEL V
HOLD P
BAT1 Charge Over
Current Protection
BAT1 Discharge Over
Current Protection
BAT1 Cell Voltage
Sensing Data Hold
Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
Power reset of the system is required.
If the symptom still occurs after reset, repair
of BMS or PCS Control Board is necessary.
B04P
B05P
B06P
BAT1 CEL OV
P
BAT1 CEL UV
P
BAT1 CEL OT
P
BAT1 Cell or Rack
Over Voltage Protection
BAT1 Cell or Rack
Under Voltage
Protection
BAT1 Cell Over Temp
Protection
When the maximum cell or rack voltage is
above protection level, thus terminating the
system. Automatically returns to normal
when the maximum cell or rack voltage goes
below the limit value.
When the minimum cell or rack voltage is
below protection level, thus terminating the
system. Automatically returns to normal
when the minimum cell or rack voltage goes
above the limit value.
When the maximum cell temperature is
above protection level, thus terminating the
system. Automatically returns to normal
when the maximum cell temperature goes
below the limit value.
93 I Problem Confirmation
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.