Qcells Q.Pro-G3, Q.Peak BLK-G3, Q.Pro BFR-G3, Q.Peak-G3, Q.PLUS-G3 Installation And Operation Manual

InstallatIon and operatIon Manual
Q.PRO-G3 · Q.PRO BFR-G3 · Q.PEAK-G3 · Q.PEAK BLK-G3 · Q.PLUS-G3
Valid for North America
TABLE OF CONTENTS
1 INTRODUCTION
1 INTRODUCTION 3
2 PLANNING 5
2.1 Technical specications 5
2.2 Requirements 7
2.3 Mounting options 8
2.4 Electrical layout 10
3 INSTALLATION 11
3.1 Safety and transport 11
3.2 Preparation of installation 13
3.3 Module installation 14
4 ELECTRICAL CONNECTION 15
4.1 Safety 15
4.2 Electrical installation safety 16
4.3 Connection of modules 17
4.4 After installation 18
5 GROUNDING 19
6 FAULTS AND DEFECTS 19
7 DISPOSAL 19
8 MAINTENANCE AND CLEANING 20
With solar modules from Hanwha Q CELLS GmbH (hereafter referred to as "Q CELLS") you can directly transform the sun’s limitless energy into environmentally-friendly solar electricity.
In order to ensure the maximum performance of your Q CELLS solar modules, please read the following instructions completely and care­fully and observe all guidelines. Non-compliance may result in damage and/or physical injury.
This installation manual provides instructions for the safe installa­tion of crystalline solar modules.
Ä Please read these instructions carefully before proceeding with
your installation.
Ä Please retain these instructions for the life of the solar modules. Ä Please ensure that this installation manual is available to the
operator at all times.
Ä
This installation manual should be given to all subsequent owners
or users of the solar modules.
Ä All supplements received from the manufacturer should be
included.
Ä Please observe all other applicable documents.
Intended Use
This manual is valid in North America for Q CELLS solar modules. These instructions contain information regarding the safe handling and use of quality crystalline solar modules from Q CELLS and for their installation, mounting, wiring, and maintenance.
Symbols and Labels
The following symbols and labels are used throughout the installation manual for ease of use.
SYMBOL DESCRIPTION
Ä
• Lists of items
Procedure with one or more steps.
Ensure that when carrying out a pro­cedure, you check the results of said procedure.
Units
Where both metric and U.S. units (for example inches) are shown,
metric units are denitive. References to “Data Sheet” or “Module Data Sheet” refer to the Module Data Sheet applicable to the module
being used.
Safety Regulations
The installer and solar module operator are responsible for compliance with all applicable statutory requirements and regulations.
Ä The following regulations and standards must be upheld at all
times during the installation, operation, and maintenance of the solar modules:
• Installation and Operation Manual.
•
Other applicable documents (such as country-specic regulations
for pressure equipment, operational safety, hazardous goods, and environmental protection).
• Regulations and requirements specic to the system.
• Applicable country-specic laws, regulations, and provisions
governing the planning, installation, and operation of solar power systems and work on roofs.
•
Valid international, national, and regional regulations governing work with direct current, especially those applicable to the installation of electrical devices and systems, and regulations issued by the respective energy provider governing the parallel operation of solar power systems.
• Accident-prevention regulations.
Certied Personnel
Both, the operator and installer are responsible for ensuring that installation, maintenance, connection to the grid, and dismantling
are carried out by trained and qualied electricians and engineers with approved training certicates (issued by a state or federal
organization) for the respective specialist trade.
Electrical work may only be performed by an ofcially certied
tradesperson in accordance with the applicable safety standards, accident prevention regulations, and the regulations of the local energy provider.
Prohibited.
Beware of possible danger or damage. Categories:
• Danger: Risk of fatal injury
• Attention: Risk of serious injury
or damage to property
• Note: Risk of damage to product
Document Revision 03 This Installation Manual is valid for USA and Canada as of January 2015 for Q.PRO-G3, Q.PRO BFR-G3, Q.PEAK-G3, Q.PEAK BLK-G3 and Q.PLUS-G3 solar modules, and replaces all earlier versions.
Technical parameters and the design are subject to change. The data sheets and customer information valid at the point in time when the relevant module was manufactured apply to the installation, mounting, and maintenance procedures for the respective solar modules.
2 3INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
1 INTRODUCTION
2 PLANNING
2.1 Technical specifications
Validity
These instructions are only valid for crystalline solar modules from Q CELLS. Q CELLS assumes no liability for damage resulting from failure to observe these instructions.
Ä Please observe the wiring and dimensioning of the system. Ä The installer of the system is responsible for compliance with all
necessary safety regulations during set-up and installation. Q CELLS assumes no liability on the basis of these instructions. Q CELLS is only liable in the context of contractual agreements or in the context of accepted guarantees. Q CELLS accepts no other responsibility for the functionality and safety of the modules.
Ä
Please observe the instructions for any other system components
that may be part of the complete solar power system. It may be
necessary to carry out a structural analysis for the entire project.
Ä If your questions are not satisfactorily answered in the manual,
please contact your system supplier.
Additional information can be found on our website at: www.q-cells.com.
Information for the Operator
Ä Please keep this manual for the entire life of the solar power
system.
Ä Please contact your system supplier for information concerning
the formal requirements for solar power systems.
Ä
Please be sure to contact the relevant local authorities and energy
providers regarding regulations and permit requirements prior
to installation of the solar power system. Your nancial success
depends on the fulllment of these requirements.
MISUSE OR INCORRECT USE OF SOLAR MODULES VOIDS THE LIMITED WARRANTY AND MAY CREATE A SAFETY HAZARD AND RISK PROPERTY DAMAGE. THIS INCLUDES IMPROPER INSTALLATION OR CONFIGURATION, IM PROPER MAINTENANCE, UNINTENDED USE, AND UNAUTHORIZED MODIFICATION.
For the electrical data and additional information of the solar modules please refer to the respective currently valid data sheets available at www.q-cells.com.
PRODUCT LINE Q.PRO-G3 / Q.PLUS-G3 Q.PRO BFR-G3
Type Polycrystalline / Q.ANTUM Polycrystalline
Length [in (mm)] 65.7 (1670) 65.7 (1670)
Width [in (mm)] 39.4 (1000) 39.4 (1000)
Height [in (mm)] 1.38 (35) 1.38 (35)
Area [yd² (m²)] 2 (1.67) 2 (1.67)
Weight [lb (kg)] 41.89 (19.0) 41.89 (19.0)
Max. system voltage V
[V] 1000 1000
SYS
Max. series fuse rating [A] 20 20
Permissible operating
–40 to +185 (–40 to +85)
temperature range [°F (°C)]
Junction box protection class IP67 with bypass diode
Connector protection class IP68 IP68
Fire protection class C C
Snow load [Pa]
Wind load [Pa]
1
1
5,400 5,400
5,400 5,400
Certicates UL 1703; VDE Quality Tested; CE-compliant; IEC 61215 (Ed.2) see page 9 et sqq.; IEC 61730
(Ed.1) Application Class A
PRODUCT LINE Q.PEAK-G3 Q.PEAK BLK-G3
Type Monocrystalline Monocrystalline
Other applicable documents
This installation manual is only valid in combination with the following technical information.
DOCUMENT TYPE
Product data sheet
Packaging and transport of crystalline modules
Length [in (mm)] 65.7 (1670) 65.7 (1670)
Width [in (mm)] 39.4 (1000) 39.4 (1000)
Height [in (mm)] 1.38 (35) 1.38 (35)
Area [yd² (m²)] 2 (1.67) 2 (1.67)
Weight [lb (kg)] 41.89 (19.0) 41.89 (19.0)
Max. system voltage V
[V] 1000 1000
SYS
Max. series fuse rating [A] 20 20
Permissible operating
–40 to +185 (–40 to +85)
temperature range [°F (°C)]
Junction box protection class IP67 with bypass diode
Connector protection class IP68 IP68
Fire protection class C C
Snow load [Pa]
Wind load [Pa]
1
1
5,400 5,400
5,400 5,400
Certicates UL 1703; VDE Quality Tested; CE-compliant; IEC 61215 (Ed.2) see page 9 et sqq.; IEC 61730
(Ed.1) Application Class A
1
tested according to IEC 61215
4 5INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
2 PLANNING
Product label
45.67" (1160 mm)
38.6" (980 mm)
5.91" (150 mm)
37.76" (959 mm)
mounting slots and grounding holes
1.38" (35 mm)
6 × grounding holes Ø 0.177" (4.5 mm)
65.7" (1670 mm)
39.4" (1000 mm)
Junction bo×
4 × mounting slots DETAIL A
8 × Drainage holes
Cable with connectors
Frame
DETAIL A
0.630" (16 mm)
0.315" (8 mm)
0.799" (20.3 mm)
2.1 Technical specifications
Fig. 1: External dimensions in inch (mm) and components for Q.PRO-G3, Q.PRO BFR-G3, Q.PEAK-G3, Q.PEAK BLK-G3, Q.PLUS-G3
2 PLANNING
2.2 Requirements
Installation Site
Please note the following guidelines that apply to the installation site:
• The modules have been tested according to UL 1703 and IEC
61215 for operation in a temperate climate.
• Solar modules are not explosion-proof.
Ä Do not operate solar modules near highly ammable gas and
vapors (e.g. gas tanks, gas stations).
Ä Do not install modules in enclosed space. Ä
Do not install modules in locations where they may be submerged
in water for lengthy periods.
Ä Do not use modules as a substitute for the normal roong
(e.g. modules are not rainproof).
Prevention of Shadowing Effects
Optimal solar irradiation leads to maximum energy output:
Ä For this reason, install the modules so that they face the sun. Ä Avoid shadowing (due to objects such as buildings, chimneys or
trees).
Ä Avoid partial shading (for example through overhead lines, dirt,
snow).
Limitations
The solar modules are designed for the following applications:
• Operating temperatures from –40 °F to +185 °F.
• Wind and snow loads up to max. 5,400 Pa (as tested according
to IEC 61215).
• Installation using a mounting frame for solar modules.
• Long-term stable clamps that securely afx the module to the
mounting frame.
Module Orientation Requirements
• Vertical or horizontal installation is permitted.
• Installation with a junction box at the bottom is permitted for
modules with junction boxes classied as IP67.
Ä Ensure that rain and melting snow can run off freely. No water
accumulation.
Ä Ensure that the drainage holes in the frame are not covered. No
sealing.
Ä Maintain the permissible angle of inclination.
• Minimum angle of inclination: 3°
• Maximum angle of inclination: 80°
• > 20°: self-cleaning effect.
Mounting Frame Requirements
Requirements for the mounting frame:
• Conforms to the necessary structural requirements.
• Compliant with local snow and wind loads.
• Properly fastened to the ground, the roof, or the façade.
•
Forces acting on the module are relayed to the mounting substructure.
• Ensures sufcient rear ventilation of the module.
• Guarantees long-term stability.
•
Has electrochemical series that prevent corrosion among different
metals.
•
Allows for stress-free expansion and contraction due to temperature
uctuations.
Ä Ensure that no mechanical stresses (e.g., caused by vibrations,
twisting, or expansion) are generated on the module.
Ä Ensure that the clamps and the mounting frame are compatible.
Clamp System Requirements
Use customary clamps that satisfy the following requirements:
• Clamp width: 1.50 in (38 mm).
• Clamp height compliant with a 1.38 in (35 mm) frame height.
• Clamp depth: 0.20–0.47 in (5–12 mm).
• Clamps are not in contact with the front glass.
• Clamps do not deform the frame.
•
Clamps that satisfy the structural requirements of the installation site.
Inverter
Inverter
6 7INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
• A module with 45.67 in long (1,160 mm) cable
can be wired as a "2nd next neighbor".
"2nd next neighbor" - Wiring without a return
cable.
Standard wiring with a return cable
1
2
2 PLANNING
0 - 11.81 (0 - 300)
0 - 11.81 (0 - 300)
9.65 - 17.52 (245 - 445)
7.09 - 14.96 (180 - 380)
4 x mounting slots
4 x mounting slots
4 x mounting slots
4 x mounting slots
2.3 Mounting options
2 PLANNING
2.3 Mounting options
Fig. 2: Installation options for crystalline Q CELLS modules. All dimensions are given in inch (mm). Also observe the allowed static
loads and clamping range as specied on the following page. The illustrated installation options apply for both horizontal and vertical module orientation.
Module Clamp Subconstruction Mounting prole
TYPE OF
MODULE POINT MOUNTING SYSTEM LINEAR MOUNTING SYSTEM
INSTALLATION
INSTALLATION WITH CLAMPS
Q.PRO-G3 Q.PRO BFR-G3 Q.PEAK-G3 Q.PEAK BLK-G3 Q.PLUS-G3
9.65 - 17.52 (245 - 445)
CL1
9.65 - 17.52 (245 - 445)
CL3 CL4
0 - 11.81 (0 - 300)
Specications
MODULE TYPE MOUNTING OPTION CLAMPING RANGE1 [IN (MM)]
Q.PRO-G3 Q.PRO BFR-G3 Q.PEAK-G3 Q.PEAK BLK-G3 Q.PLUS-G3
CL1 Push 9.65 - 13.58 (245 - 345)
13.62 - 17.51 (346 - 445)
Pull 9.65 - 13.58 (245 - 345)
13.62 - 17.51 (346 - 445)
CL3 Push 9.65 - 17.51 (346 - 445) 4000
Pull 9.65 - 13.58 (245 - 345)
13.62 - 17.51 (346 - 445)
CL4 Push 0 - 11.81 (0 - 300) 1800
Pull 0 - 11.81 (0 - 300) 1600
FB1 Push 3500
Pull 3100
FB2 Push 4000
Pull 3100
IP1 Push - 3700
Pull - 3700
ALLOWED STATIC LOAD2 [PA]
3500 2400
4000 3400
4000 3400
TEST LOAD ACC. IEC 61215 [PA]
5400
INSTALL ATION ON MOUNTING POINTS
INSTALLATION WITH INSERTION PROFILES
Q.PRO-G3 Q.PRO BFR-G3 Q.PEAK-G3 Q.PEAK BLK-G3 Q.PLUS-G3
Q.PRO-G3 Q.PRO BFR-G3 Q.PEAK-G3 Q.PEAK BLK-G3 Q.PLUS-G3
13.58 (345)
not permitted
FB1
4 x mounting slots
13.58 (345)
FB2
IP1 IP2
4 x mounting slots
IP2 Push - 1800
Pull - 1800
1
Distance between outer edge of module and middle of the clamp.
2
Describes the maximum module surface load (vertical to the module surface) regarding safety factors (e.g. EUROCODE). For this purpose,
2400
the load value determined by load tests according to various criteria: laminate overlay, plastic deformation, module failure, and were divided with a safety factor. The minimum calculated load value corresponds to the maximum permitted load.
8 9INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
2 PLANNING
2.3 Mounting options
2 PLANNING
2.4 Electrical layout
SPECIFICATION OF THE CLAMPING RANGE
Ä In case of varying clamping range for push and pull loads the smaller clamping range must be applied.
DISTANCE BETWEEN MODULES
Ä Maintain an interval of at least 0.39 in (10 mm) between two modules along the short side.
Ä Maintain an interval of at least 0.20 in (5 mm) between two modules along the long side.
MOUNTING OPTION CL1
Ä Ensure, that the subconstruction does not run below the junction box.
MOUNTING OPTION CL4
Ä Ensure, that the subconstruction runs exactly below the frame, not below the laminate (module less frame).
MOUNTING OPTIONS FB1 AND FB2
• The fastening points are located on the backside of the module frame.
Module Selection
For detailed key electrical data, please refer to the product data sheet for the respective product.
Ä Only connect modules of the same type and the same power
class.
Safety Factor
During normal operation, a module may generate a greater current and / or higher voltage than that determined under standardized test conditions. Accordingly, the values of I module should be multiplied by a facot of 1.25 when determining:
• the component voltage ratings,
• conductor ampacities,
• fuse sizes,
• size of controls connected to the PV output.
Refer to Section 690-8 of the National Electrical Code for an additional multiplying factor of 125 percent (80 percent derating) which might be applicable.
Ä Please follow the valid national guidelines for the installation
of electrical systems (refer to section 690-8 of the NEC for an
additional multiplying factor of 125 percent [80 percent derating]
which may be applicable).
and VOC marked on the
SC
Parallel Connection
Modules may be damaged by the occurrence of reverse currents (caused by module defects, ground leaks, or defective insulation).
Ä
Ensure that the maximum reverse current load capacity indicated
in the data sheet is observed. In order to limit reverse currents that may occur, we recommend using the following safety options:
1) Layout with a limited number of parallel connected strings :
Without undertaking further current blocking measures, a maximum of two module strings may be operated in parallel on an inverter or MPP tracker.
2) Layout with string fuses :
place fuses for each string of modules at the plus and minus ends. Observe the maximum permitted number of strings as indicated in the specications provided by the respective string fuse manu­facturer and the technical guidelines.
NOTE!
When installing different product versions, the lowest minimum permitted reverse current load capacity applies.
Series Connection
Connection of modules in series is only permitted up to the maximum system voltage as listed in the applicable data sheet.
Ä
Take into account all possible operating situations and all relevant technical norms and regulations when designing the system. This will ensure that the maximum system voltage, including all necessary safety margins, is not exceeded.
Ä
Take the voltage limit of the inverter into account when determining the maximum number of modules in the string.
Inverters
Inverters with or without transformers may be used.
10 11INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
3 INSTALLATION
3.1 Safety and transport
3 INSTALLATION
3.1 Safety and transport
Ä Ensure that all personnel are aware of and adhere
to accident-prevention and safety regulations.
Ä While working wear clean gloves.
I
§
Ä Inspect the packaging for damages. Ä Contact the transport company regarding any
damage to the packaging.
Ä Follow any instructions on the packaging.
GB
D
§
§
DANGER! Risk of fatal injury due to electric shock!
Ä Do not install damaged modules. Ä Inform your vendor of any damages
immediately.
DANGER! Risk of fatal injury due to electric shock!
Ä Cover the modules with an opaque material during
installation.
NOTE! Module damage may occur!
Ä Never lift or move the module with the connection
cables or junction box.
Ä Carry modules upright and horizontally as
shown.
NOTE! Module damage may occur!
Ä Do not drop modules.
NOTE! Module damage may occur!
Ä Never step on modules. Ä Do not subject modules to any mechanical
stress.
Ä Do not allow any objects to fall onto modules
NOTE! Module damage may occur!
Ä Only make modications to the module which have
been conrmed in writing by Q CELLS.
Ä Leave modules in their original packaging until
installation.
Ä Store the modules securely in cool and dry rooms.
The packaging is not weatherproof.
12 13INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
WARNING! Fire Risk!
Ä Do not install modules indoors. Ä Do not install modules on moving objects.
NOTE! Module damage may occur!
Ä Do not stack modules.
NOTE! Module damage may occur!
Ä Do not install modules near ammable
gas / vapors.
3 INSTALLATION
3.2 Preparation of installation
3 INSTALLATION
3.3 Module installation
DANGER! Risk of fatal injury due to electric shock!
Ä Block off the installation zone. Ä Keep children and unauthorized individuals away
from the solar power system.
DANGER! Risk of fatal injury due to electric shock!
Ä Only use dry, insulated tools.
WARNING! Risk of injury due to falling modules!
Ä Secure modules during installation. Ä Do not install modules in windy or wet weather.
Ä Do not carry out the installation alone.
Option 1:
Ä Fasten the module with 4 clamps in the specied
clamping range, see g. 3, page 8.
Ä Tighten clamps according to manufacturer’s
instructions.
Option 2:
Ä Install the module at the 4 mounting points, see
g. 4, page 8.
Ä Tighten screws according to manufacturer’s
instructions.
Ä Maintain an interval of at least 0.39 in (10 mm)
between two modules along the short side and
0.20 in (5 mm) along the long side.
0.20 in
(5 mm)
0.39 in (10mm)
NOTE! Module damage may occur!
Ä Do not subject modules to mechanical tension.
Max. torsion 0.39 in/yd (10 mm/m).
DANGER! Risk of fatal injury due to electric shock!
Ä Ensure that modules and tools are not subject to
moisture or rain at any time during installation.
• Only install undamaged modules and
components.
Ä Do not drill any other holes.
Option 3:
Ä Install the module using mounting proles, see g.
4, page 8.
15INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA14 INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
4 ELECTRICAL CONNECTION
4.1 Safety
4 ELECTRICAL CONNECTION
4.2 Electrical installation safety
DANGER! Risk of fatal injury due to electric shock!
When disconnecting an electric circuit carrying direct current, electric arcs can occur that may result in life-threatening injuries.
Ä Do NOT unplug the cable when under load. Ä Do NOT connect any exposed cable ends. Ä Do NOT touch the poles at the same time.
A solar module generates electrical current and voltage even at a low intensity of illumination. Sparks and electric arcs may result from the separation of a closed circuit. These can result in life­threatening injuries. The danger increases when several modules are connected in series.
Ä Please ensure that the entire open circuit voltage is active even
at low levels of solar irradiation.
Ä
Please follow the valid national regulations and safety guidelines for the installation of electrical devices and systems.
Ä Please make sure to take all necessary safety precautions. With
module or phase voltages of more than 120 V, the extra-low voltage range is exceeded.
Ä
Carry out work on the inverter and the wiring with extreme caution.
Ä Ensure that the modules are disconnected at the inverter prior
to separation.
Ä
Be sure to observe the specied time intervals after switching off
the inverter. High-voltage components need time to discharge.
DANGER! Risk of fatal injury due to electric shock!
Ä Never open the junction box. Ä Do not remove bypass diodes.
DANGER! Risk of fatal injury due to electric shock!
Ä Never touch live contacts with bare hands. Ä Do not touch the poles at the same time.
DANGER! Risk of fatal injury due to electric shock!
Ä Ensure correct polarity.
DANGER! Risk of fatal injury due to electric shock!
Ä Be sure to maintain the time intervals as specied
by the inverter manufacturer between switching off the inverter and beginning any further work.
DANGER! Risk of fatal injury due to electric shock!
Ä Never unplug the cable when under load.
1. Switch off the inverter.
AUS
2. Cover the modules to be disconnected.
DANGER! Risk of fatal injury due to electric shock!
Ä Only use dry, insulated tools for electrical work.
DANGER! Risk of fatal injury due to electric shock!
Ä Insulate any exposed cable ends. Ä Only connect cables with plugs.
3. Switch off the DC circuit breaker.
Ä Disconnect plugs by the use of appropriate
and qualied tools of the manufacturer Tyco or
Multicontact (adequate for PV4 plug type).
17INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA16 INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
4 ELECTRICAL CONNECTION
4.3 Connection of modules
4 ELECTRICAL CONNECTION
4.4 After installation
Ä Use solar cables for the connection at the junction
box outlet.
Ä Use the same, inverter-compatible plugs.
SOLAR
DANGER! Risk of fatal injury due to electric shock!
Ä Ensure that all electrical components are in a
proper, dry, and safe condition.
NOTE! Module damage may occur!
Ä Ensure that the cabling is not under stress. Ä Ensure that the cables do not run between module
and subconstruction (danger of pinch).
Ä Do not connect modules with different orientations
or angles of inclination in the same string.
Ä Ensure that all necessary safety and functional
tests have been carried out according to current industry standards.
Ä Integrate the system into the existing lightening
protection system in accordance with the applicable local regulations.
NOTE! Module damage may occur!
Ä Ensure that the plug connections are not level with
a water-channeling surface.
WARNING! Fire Risk!
Ä Do not use light concentrators (e.g. mirrors or
lenses).
Ä Ensure for a tight connection between the plugs.
Plugs click together audibly.
click
• A module with 47.24 in -long (1,210 mm) cable
can be wired as a “2nd next neighbor”.
“2nd next neighbor” - Wiring without a return
cable.
Standard wiring with a return cable
1
Inverter
2
Inverter
Ä Ensure that the cabling is not exposed and/
or hanging and is protected from dirt and moisture.
19INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA18 INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
5 GROUNDING
0.59”
8 ELECTRICAL CONNECTION
In order to prevent electrical shock or re, the frame of the module
as well as any non-current-carrying metal parts of the system must be grounded. While this section provides some information about grounding the Q CELLS frames and modules, reference should be
made to local statutes and regulations for specic requirements
on grounding. The U.S. National Electrical Code addresses these issues in Article 250.
Proper grounding is achieved by bonding all exposed non-current­carrying metal equipment to the appropriately sized equipment grounding conductor (EGC) or racking system that can be used for integrated grounding.
Q CELLS frames are protected from corrosion with an anodized coating, which has to be penetrated in order to ensure proper bonding. The different methods listed below are suggested methods for an appropriate bond between the frame and the EGC or racking system (that will have to be properly grounded). The method appropriate for any individual installation will depend on multiple factors.
Option A: Use of a grounding lug
A listed grounding lug can be bonded to the frame using the grounding holes pre-drilled in the frame. These holes are marked with a ground symbol, as shown below on the frame section drawing:
To install the grounding lug, follow the specied instructions of
the manufacturer. The grounding lug should be made of stainless steel or tin plated metals such as aluminum to avoid corrosion. The grounding lug should be attached to the frame grounding hole using a stainless steel screw, toothed lock washer or KEPS nut (in order to penetrate the anodized layer) and backing nut. Care should be taken to avoid the use of grounding hardware of dissimilar metals, which may lead to corrosion.
PV Laminate
Aluminum Frame
Equipment Grounding Conductor
Backing Nut (Stainless Steel)
Toothed Lock Washer (Stainless Steel or tin-plated metal)
Grounding Lug (Stainless Steel)
Screw (Stainless Steel)
Option B: Integrated grounding methods
The Q CELLS modules can be bonded with the racking system
using UL1703 or UL2703 certied integrated grounding methods.
The racking system will then have to be grounded so that the overall system is properly grounded. The listed racking system and grounding device should be installed in accordance with the manufacturers’ instructions.
An example of such integrated grounding method is the use of a washer recognized as meeting UL2703 requirements between the module and the racking system, when mounting the module. For example, WEEB washers are generally compatible with Q CELLS modules, however each combination module / racking system
requires a specic WEEB washer size. Note that WEEB washers
are intended for single use only; they must not be reused after removal or loosening. Refer to Wiley’s installation instructions for
the specic use of WEEB washers.
Q CELLS solar modules are known for a long operating life and minimal maintenance effort and expense. Dirt and grime are usually washed away by rain. If the module is fully or partially shaded by dirt or debris (e.g., plants, bird droppings), it needs to be cleaned to prevent a loss of performance.
Maintenance
Ä
The system should be inspected by an installer annually to check the following:
•
all system components sit securely and are corrosion free.
•
the connection is secure and all electrical components are clean and undamaged.
transfer resistances of the grounding
Cleaning
WARNING! Risk of injury due to hot and live modules!
Ä Only clean modules that have cooled down. Ä Do not carry or wear any electrically conductive
parts.
WARNING! Risk of falling due to unsecured access!
Ä Never access the installation area alone or without
taking adequate security precautions.
Ä Please commission a trade specialist.
Clean the modules as follows:
NOTE! Module surface damage may occur!
NOTE! Module damage may occur!
Ä Do not clean modules with water if there is a risk
of frost.
Ä Remove dirt with lukewarm water, a broom, or a
soft cloth.
Ä Do not use tensides, scrapers, or any high-pressure
water cleaning equipment.
• Dimensions shown are in inches.
±0.02
0.80”
+0
0.18 - 0.008
±0.04
±0.04
0.39”
6 FAULTS AND DEFECTS
DANGER! Risk of fatal injury due to electric shock!
Ä Do not attempt to x any problems yourself (e.g., glass cracks,
damaged cables).
Ä Please contact an installer or Q CELLS Technical Customer
Service Department.
7 DISPOSAL
Ä Do not disconnect modules yourself.
Ä Please commission a trade specialist.
Ä Dispose of modules in accordance with the local disposal
regulations.
Ä Remove snow and ice without force (e.g. with a very
soft broom)
Ä Do not scratch off dirt. Ä Rinse dirt off with lukewarm water (dust, leaves, etc.) Ä Use a soft cellulose cloth (kitchen roll) or sponge to
carefully wipe off stubborn dirt. Do not use micro eece
wool or cotton cloths.
Ä
Use an alcohol based glass cleaner. Do not use abrasive
detergents or tensides.
Isopropyl alcohol (IPA) can be used selectively to remove stubborn dirt and stains within one hour after emergence.
Ä Please follow the safety guidelines provided by the IPA
manufacturer.
Ä Do not let IPA run down between the module and the
frame or into the module edges.
Ä Free the substructure from any dirt and debris
(leaves, bird nests, etc.).
21INSTALLATION AND OPERATION MANUAL SOLAR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA20 INSTALLATION AND OPERATION MANUAL SOL AR MODULES GENERATION 3 (G3) – HANWHA Q CELLS GMBH – NA
ContaCt
HanwHa Q CELLS USa Corp.
8001 Irvine Center Drive Suite 1250 Irvine CA 92618 USA
tEL +1 848 748 59 96 FaX +1 949 748 59 84
EMaIL q-cells-usa@q-cells.com wEB www.q-cells.us
Subject to change without notice. © Hanwha Q CELLS GmbH Installation manual G3 modules_2015-01_Rev03_NA
Loading...