Q CELLS Q.PEAK DUO-G6 Series, Q.PEAK DUO-G6+, Q.PEAK DUO BLK-G6 Installation And Operation Manual

INSTALLATION AND OPERATION MANUAL
Q.PEAK DUO-G6.X+ solar module series
Valid for Africa, Europe, LatinAmerica, South America
TABLE OF CONTENTS

1 INTRODUCTION

1 INTRODUCTION 3 2 PLANNING 5
2.1 TECHNICAL SPECIFICATIONS 5
2.2 REQUIREMENTS 6
2.3 MOUNTING OPTIONS 7
2.4 ELECTRICAL LAYOUT 9
3 INSTALLATION 10
3.1 SAFETY AND TRANSPORT 10
3.2 PREPARATION OF INSTALLATION 12
3.3 MODULE INSTALLATION 13
4 ELECTRICAL CONNECTION 14
4.1 SAFETY 14
4.2 ELECTRICAL INSTALLATION SAFETY 15
4.3 CONNECTION OF MODULES 16
4.4 AFTER INSTALLATION 17
5 GROUNDING 18 6 FAULTS AND DEFECTS 18 7 DISPOSAL 18 8 MAINTENANCE AND CLEANING 19
With solar modules from Hanwha Q CELLS (hereafter referred to as "Q CELLS") you can directly transform the sun’s limitless energy into environmentally-friendly solar electricity. In order to ensure the maximum performance of your Q CELLS solar modules, please read the following instructions carefully and observe all guidelines. Non-compliance may result in damage and/or physical injury.
This installation and operation manual (hereafter also referred to as the “Manual”) provides instructions for the safe installation and operation of crystalline solar modules.
Ä Please read these instructions carefully before proceeding
with your installation.
Ä Please retain these instructions for the life of the solar
modules.
Ä Please ensure that this Manual is available to the operator
at all times.
Ä This Manual should be given to all subsequent owners or users
of the solar modules.
Ä All supplements received from the manufacturer should be
included.
Ä Please observe all other applicable documents. Ä If your questions are not satisfactorily answered in the manual,
please contact your system supplier.
Additional information can be found on our website at www.q-cells. com.
Intended Use
This manual is valid for Africa, Asia, Europe, Latin America, South America. These instructions contain information regarding the safe handling and use of quality crystalline solar modules from Q CELLS and their installation, mounting, wiring, maintenance and disposal.
Symbols and Labels
The following symbols and labels are used throughout the Manual for ease of use.
SYMBOL DESCRIPTION
Ä
Procedure with one or more steps.
Lists of items.
Ensure that when carrying out a procedure, you check the results of said procedure.
Prohibited.
Beware of possible danger or damage. Cate­gories:
Danger: Risk of fatal injury
Attention: Risk of serious injury or dam-
age to property
Note: Risk of damage to product
Safety Regulations
In particular the installer as well as the operator of a module is responsible for compliance with all applicable statutory requirements and regulations.
Ä Unless otherwise specified by any laws or regulations, the
following stipulations must be upheld at all times during the installation, operation, and maintenance of the solar modules:
This manual.
Other applicable stipulations (such as country-specific
regulations for pressure equipment, operational safety, hazardous goods, and environmental protection).
Regulations and requirements specific to the system.
Any applicable laws and requirements, in particular inter-
national, country specific, regional laws and stipulations governing the planning, installation, and operation of solar power systems and work on roofs.
Any valid international, national and regional regulations
governing work with direct current, especially those appli­cable to the installation of electrical devices and systems, and regulations issued by the respective energy provider governing the parallel operation of solar power systems.
Any international, country specific and regional accident-pre­vention regulations.
Other applicable stipulations provided by the relevant
national institutions regarding safety in the installation and operation of electrical items. For example, in Germany the Bau-Berufsgenossenschaft (German institution for statutory accidence insurance and prevention in the building trade).
Qualified and Skilled Personnel
Both, the installer and operator are responsible for ensuring that the installation (including connection to the grid), maintenance and dismantling are carried out by trained and qualified specialists with approved training certificates (issued by a state or federal organization) for the respective specialist trade. Electrical work may only be performed by an officially certified tradesperson in accordance with the stipulations applicable in the relevant country with regard to standard and regulations (in Germany e. g. DIN standards, VDE regulations) and the stipulations of the local grid operator and/or energy provider.
DOCUMENT REVISION 01 This Manual is valid for Africa, Asia, Europe, Latin America and South America as of May 1st 2019 for Q.PEAK DUO-G6, Q.PEAK DUO-G6+, Q.PEAK DUO BLK-G6 and Q.PEAK DUO BLK-G6+ solar modules, and replaces all earlier versions.
This manual is subject to change. The data sheets and customer information valid at the point in time when the relevant module was manufactured apply to the installation, mounting, and maintenance procedures for the respective solar modules, as far as no updated document is provided.
2 3INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS
DETAIL A
16 mm
8.5 mm
24.5 mm
980 mm
1740 mm
4 × Mounting slots (DETAIL A)
Frame
1030 mm
981 mm
32 mm
8 × Drainage holes
380 mm
4 × Grounding points ø 4.5 mm
Label
1150 mm
1150 mm

1 INTRODUCTION 2 PLANNING

2.1 TECHNICAL SPECIFICATIONS

Validity
These instructions are only valid for crystalline solar modules from the company Q CELLS as specified at chapter „2.1 Technical Specifications“. Q CELLS assumes no liability for damage resulting from failure to observe these instructions.
Ä Please observe the wiring and dimensioning of the system. Ä The installer of the system is responsible for compliance with all
necessary safety regulations during set-up and installation. Q CELLS assumes no liability on the basis of these instructions. Q CELLS is only liable in the context of contractual agreements or in the context of accepted guarantees. Q CELLS accepts no other responsibility for the functionality and safety of the modules.
Ä Please observe the instructions for any other system compo-
nents that may be part of the complete solar power system.
It may be necessary to carry out a structural analysis for the
entire project.
Additional information for the Operator
Ä Please keep this manual for the entire life of the solar power
system.
Ä Please contact your system supplier for information concerning
the formal requirements for solar power systems.
Ä Please be sure to contact the relevant local authorities and
energy providers regarding regulations and permit requirements
prior to installation of the solar power system. Your financial
success depends on the fulfillment of these requirements.
Other applicable documents
In addition to this Manual following technical information are relevant:
For additional information see the relevant datasheet of the module provided at www.q-cells.com.
PRODUCT LINE Q.PEAK DUO-G6
Q.PEAK DUO-G6+
Q.PEAK DUO BLK-G6 Q.PEAK DUO BLK-G6+
Type Q.ANTUM DUO Q.ANTUM DUO
Length
Width
1740 mm 1740 mm
1030 mm 1030 mm
Frame height 32 mm 32 mm
Area 1.79 m² 1.79 m²
Weight 19.9 kg 19.9 kg
Max. system voltage V
SYS
1000 V 1000 V
Max. reverse current 20 A 20 A
Permissible temperature range
Junction box protection class
–40 °C to +85 °C (–40 °F bis +185 °F)
IP67 with bypass diode
Connector protection class IP68
Fire protection class C / Type 2 C / Type 2
Max. test load Push/Pull
1
Max. design load Push/Pull
5,400 Pa / 4,000 Pa 5,400 Pa / 4,000 Pa
1
3,600 Pa / 2,667 Pa 3,600 Pa / 2,667 Pa
Certificates VDE Quality Tested; CE-compliant; IEC 61215:2016; IEC 61730:2016;
Application Class II; UL 1703
1
Test and design load in accordance with IEC 61215:2016, depending on mounting options (see section „2.3 Mounting Options“)
DOCUMENT TYPE
Product data sheet
Packaging and transport information
4 5INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS
Fig. 1: External dimensions and components for
Q.PEAK DUO-G6, Q.PEAK DUO-G6+, Q.PEAK DUO BLK-G6 and Q.PEAK DUO BLK-G6+
2 PLANNING
300 - 450
0 - 250
CL5
CL2a
0 - 300
CL2b
0 - 300
IP1 IP2
CL2b
0 - 300
4 × Mounting points
380
FB2
4 x Mounting points
380
FB1
0 - 250 250 - 450 450 - 550
CL1
250 - 450
0 - 300
CL3 CL4
2 PLANNING

2.2 REQUIREMENTS

Installation Site
Please note the following guidelines that apply to the installation site:
The modules have been tested according to IEC 61215.
Solar modules are not explosion-proof and are not suitable
for use in explosive environments.
Ä Do not operate solar modules near highly flammable gas and
vapors (e.g. gas tanks, gas stations).
Ä Do not install modules in enclosed space. Ä Do not install modules in locations where they may be sub-
merged in water (e.g. floodplains).
Ä Do not use modules as a substitute for the normal roofing
(e.g. modules are not watertight).
Ä Do not install modules in close proximity to air conditioning
systems.
Ä Do not install modules above 4,000 m (13120 ft) altitude
above sea level.
Ä In locations with increased salt content in the air (e.g. close to
the sea) special precautions must be taken (see „Grounding“
and „Maintenance and Cleaning“).
Ä Do not bring any chemical substance (e.g. oil, solvent etc.)
into contact with any part of the panel. Only substances,
which are released by Q CELLS, are allowed to be used during
installation, operation and maintenance.
Ä Any installation of modules on surfaces of water is prohibited.
This includes installations on floating as well as pile-based
platforms. Q CELLS may extend the coverage of its warranty
to such installations, based on a case by case assessment of
the system design and location. A prior written consent by
the warrantor is required in any case.
The solar modules are designed for the following applications:
Operating temperatures from –40 °C to +85 °C
(–40 °F to +185 °F).
Pull loads up to max. 4,000 Pa and push loads up to max.
5,400 Pa (see chapter „Mounting Options“).
Installation using a mounting structure for solar modules.
Prevention of Shadowing Effects
Optimal solar irradiation leads to maximum energy output:
Ä For this reason, install the modules so that they face the sun. Ä Avoid shadowing (due to objects such as buildings, chimneys
or trees).
Ä Avoid partial shading (for example through overhead lines,
dirt, snow).
Mounting Structure Requirements
The Modules shall be installed and operated on mounting structures that comply with any applicable laws and stipulations as well as with the following:
Conform to the necessary structural requirements.
Compliant with local snow and wind loads.
Properly fastened to the ground, the roof, or the façade.
Forces acting on the module are relayed to the mounting
substructure.
Ensures sufficient rear ventilation of the module.
Avoid the usage of different metals to prevent contact corrosion.
Allows for stress-free expansion and contraction due to
temperature fluctuations.
Ä Ensure that no additional forces are applied through the
mounting system into the module except for the wind and snow loads. Additional forces and moments of torque at the mounting positions caused by torsions, displacements or vibrations in the mounting system are not allowed.
Ä Ensure that the clamps and the mounting frame are com-
patible.
Clamp System Requirements
Use customary clamps that satisfy the following requirements:
Clamp width: ≥ 40 mm.
Clamp height compliant with a 32 mm frame height.
Clamp depth: 7-12 mm. (applicable for all CL clamping mounting options at section „2.3 Mounting Options“)
Clamps are not in contact with the front glass.
Clamps do not deform the frame.
Clamps that satisfy the structural requirements of the installation site.
Long-term stable clamps that securely affix the module to
the mounting frame.
Module Orientation Requirements
Vertical or horizontal installation is permitted.
Ä Ensure that rain and melting snow can run off freely. No water
accumulation.
Ä Ensure that the drainage holes in the frame are not covered.
No sealing.
Ä Maintain the permissible angle of inclination.
Minimum angle of inclination: 3°
Inclination angles above 75° may be limited
by local regulations
Ä ≥ 20°: self-cleaning effect Ä Follow the directions for installation angles < 5°
(„Grounding“, page 18)
75°

2.3 MOUNTING OPTIONS

Fig. 2: Installation options for crystalline Q CELLS modules. All dimensions are given in mm. Also observe the maximum
test loads and clamping range as specified on the following page. The illustrated installation options apply for both horizontal and vertical module orientation.
Module Clamp Subconstruction Mounting profile
TYPE OF INSTALLATION
IN STAL L ATI ON WITH CLAMPS
HYBRID CLAMPING
IN STAL L ATI ON ON MOUNTING POINTS
IN STAL L ATI ON WITH INSERTION PROFILES
MODULE POINT MOUNTING SYSTEM LINEAR MOUNTING SYSTEM
Q.PEAK DUO-G6 Q.PEAK DUO-G6+ Q.PEAK DUO BLK-G6 Q.PEAK DUO BLK-G6+
Q.PEAK DUO-G6 Q.PEAK DUO-G6+ Q.PEAK DUO BLK-G6 Q.PEAK DUO BLK-G6+
Q.PEAK DUO-G6 Q.PEAK DUO-G6+ Q.PEAK DUO BLK-G6 Q.PEAK DUO BLK-G6+
Q.PEAK DUO-G6 Q.PEAK DUO-G6+ Q.PEAK DUO BLK-G6 Q.PEAK DUO BLK-G6+
NOT PERMITTED
6 7INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS
2 PLANNING
2 PLANNING
2.3 MOUNTING OPTIONS
Specifications
MODULE TYPE
Q.PEAK DUO-G6 Q.PEAK DUO-G6+ Q.PEAK DUO BLK-G6 Q.PEAK DUO BLK-G6+
Ä The below mounting options are only possible under certain conditions.
MODULE TYPE
Q.PEAK DUO-G6 Q.PEAK DUO-G6+ Q.PEAK DUO BLK-G6 Q.PEAK DUO BLK-G6+
MOUNTING OPTION
CL1 / CL3 250 - 450
FB1 / FB2 380
IP1 -
CL1
CL2a (with rails) / CL2b (without rails)
CL4 0 - 300
CL5
MOUNTING OPTION
IP2 - 2400/2200 1600/1470 1.5
POSITION OF CLAMPS* [MM]
0 - 250 450 - 550
0 - 300
short side: 0 - 250 long side: 300 - 450
POSITION OF CLAMPS* [MM]
TEST LOAD PUSH/PULL** [PA]
5400/4000 3600/2670
2400/2400 1600/1600
4000/4000 2670/2670
TEST LOAD PUSH/PULL*** [PA]
DESIGN LOAD PUSH/PULL** [PA]
DESIGN LOAD PUSH/PULL*** [PA]
SAFETY FACTOR
1.5
SAFETY FACTOR

2.4 ELECTRICAL LAYOUT

Module Selection
For detailed key electrical data, please refer to the actual data sheet referring to the relevant Module (available at www.q-cells.com).
Ä For maximum energy yields, mismatches of specified electric
current (I connected in series.
Safety Factor
During normal operation, a module may generate a greater current and / or higher voltage than that determined under standardized test conditions. Please use a safety factor of 1.25 for the following:
Calculating the voltage measurement values (VOC) of components
Calculating the current measurement values (ISC) of conductors
Sizing of control systems connected to the outlets of the solar modules
Ä Please follow the valid national guidelines for the installation
of electrical systems.
Series Connection
Connection of modules in series is only permitted up to the maximum system voltage as listed in the applicable data sheet of all the relevant modules to be installed.
Ä Take into account all possible operating situations and all
relevant technical norms and regulations when designing the system. It has to be ensured that the maximum system voltage, including all necessary safety margins, is not exceeded.
Ä Take the voltage limit of the inverter into account when
determining the maximum number of modules in the string.
) of more than 5 % should be avoided for all modules
MPP
Parallel Connection
Modules may be damaged by the occurrence of reverse currents (caused by module defects, ground leaks, or defective insulation).
Ä Ensure that the maximum reverse current load capacity
indicated in the data sheet is met. In order to limit reverse currents that may occur, we recommend using the following safety options:
1) Layout with a limited number of
parallel connected strings :
Without undertaking further current blocking measures, a maximum of two module strings may be operated in parallel on a single inverter or MPP tracker.
2) Layout with string fuses :
Place fuses for each string of modules at the plus and minus ends. Use gPV-fuses according to IEC 60269-6. Observe the maximum permitted number of strings as indicated in the specifications provided by the respective string fuse manufacturer and the technical guidelines.
NOTE!
When installing different product versions, the lowest minimum permitted reverse current load capacity applies.
Inverters
Inverters with or without transformers may be used.
*
Distance between outer edge of module and middle of the clamp.
**
Loads according to IEC 61215-2:2016 and UL 1703.
***
Test procedure according to IEC 61215-2:2016 and UL 1703. Mounting options do not fulfill the requirements of the standards.
ATTENTION
Ä The loads in the table are related to the mechanical stability of the solar modules. The mechanical stability of the mounting
system including clamps has to be evaluated by the system supplier. The Q CELLS listed test load values were determinded with the following clamp parameters: clamp width = 40 mm and clamp depth = 10 mm. The system installer is responsible for the determination of location-specific load requirements.
Ä Ensure, that the subconstruction does not touch the junction box (even under load). Ensure that the clamps or insertion profiles
etc. do not touch the glass (even under load).
Ä Ensure, that the connection cables of the junction box do not run between laminate and mounting rails. Ä Ensure, minimum support depth of 15 mm on the back side of the module for IP1, IP2, CL2b, CL3, CL4 and CL5. Ensure
minimum support depth of 10 mm on the front side of the module for IP1 and IP2.
Ä CL1, CL2a and CL3 with rails: Ensure that module frame is fixed directly on the rail of the substructure (no spacer allowed
between the module and substructure).
Ä Module bend under loads. Therefore, sharp objects (e.g. screws) must not be mounted near the module backside. Ä Use M8 corrosion-proof screws and washers (diameter ≥ 15.8 mm or ≥ 0.62 in) for FB1 and FB2 mounting.
8 9INSTALLATION AND OPERATION MANUAL SOL AR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOL AR MODULES Q.PEAK DUO-G6.X+ – Q CELLS

3 INSTALLATION

3 INSTALLATION

3.1 SAFETY AND TRANSPORT

Ä Ensure that all personnel are aware of and
adhere to accident-prevention and safety regulations.
Ä While working wear clean gloves.
GB
I
D
§
§
§
Danger! Risk of fatal injury due to electric shock!
Ä Do not install damaged modules. Ä Inform your distributor of any damages
immediately.
3.1 SAFETY AND TRANSPORT
Note! Module damage may occur!
Ä Never lift or move the module with the
connection cables or junction box.
Ä Carry modules upright and horizontally as
shown.
Note! Module damage may occur!
Ä Never step on modules. Ä Do not subject modules to any mechanical
stress.
Ä Do not allow any objects to fall onto modules
Ä Inspect the packaging for damages. Ä Contact the transport company regarding
any damage to the packaging and follow their instructions.
Ä Follow any instructions on the packaging.
Ä Leave modules in their original packaging until
installation.
Ä Store the modules securely in cool and dry
rooms. The packaging is not weatherproof.
Warning! Fire Risk!
Ä Do not install modules indoors. Ä Do not install modules on moving objects.
Note! Module damage may occur!
Ä Do not drop modules.
Note! Module damage may occur!
Ä Do not stack modules.
Note! Module damage may occur!
Ä Only make modifications to the module which
have been confirmed in writing by Q CELLS.
confirmation letter
Note! Module damage may occur!
Ä Do not install modules near flammable
gas / vapors.
Ä Do not install modules in close proximity to air
conditioning systems.
10 11INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS10 11
3 INSTALLATION
3 INSTALLATION

3.2 PREPARATION OF INSTALLATION

Danger! Risk of fatal injury due to electric shock!
Ä Block off the installation zone. Ä Keep children and unauthorized individuals
away from the solar power system.
Warning! Risk of injury due to falling modules!
Ä Secure modules during installation. Ä Do not install modules in windy or wet weather.

3.3 MODULE INSTALLATION

Option 1:
Ä Fasten the module with 4 clamps in the
specified clamping range, see Fig. 2, p. 7.
Ä Tighten clamps according to
manufacturer’s instructions.
Ä Maintain an interval of at least 10 mm between
two modules along the short side and 5 mm along the long side.
5 mm
10 mm
Danger! Risk of fatal injury due to electric shock!
Ä Only use dry, insulated tools.
Danger! Risk of fatal injury due to electric shock!
Ä Ensure that modules and tools are not subject
to moisture or rain at any time during instal­lation.
Ä Do not carry out the installation alone.
Only install undamaged modules and
components.
Ä Do not modify the module
(e.g. do not drill any additional holes).
Option 2:
Ä Install the module at the 4 mounting points,
see Fig. 2, p. 7.
Ä Tighten screws according to
manufacturer’s instructions.
Option 3:
Ä Install the module using mounting profiles,
see Fig. 2, p. 7.
Note! Module damage may occur!
Ä Do not subject modules to mechanical tension.
Max. torsion 10 mm/m.
12 13INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS12 13

4 ELECTRICAL CONNECTION

4 ELECTRICAL CONNECTION

4.1 SAFETY

DANGER! Risk of fatal injury due to electric shock!
When disconnecting an electric circuit carrying direct current, electric arcs can occur that may result in life-threatening injuries.
Ä Do NOT unplug the cable when under load.
Ä Do NOT connect any exposed cable ends.
Ä Electrical work may only be performed by qualified and
skilled personnel (see page 3).
A solar module generates electrical current and voltage even at a low intensity of illumination. Sparks and electric arcs may result from the separation of a closed circuit. These can result in life-threatening injuries. The danger increases when several modules are connected in series.
Ä Please be aware of that the entire open circuit voltage is
active even at low levels of solar irradiation.
Ä Please follow the valid national regulations and safety guidelines
for the installation of electrical devices and systems.
Ä Please make sure to take all necessary safety precautions.
With module or phase voltages of more than 120 V, the safety extra-low voltage range is exceeded.
Ä Carry out work on the inverter and the wiring with extreme
caution.
Ä Ensure that the modules are disconnected at the inverter
prior to separation.
Ä Be sure to observe the time intervals specified by the inverter
manufacturer after switching off the inverter.
Ä Make sure that the plugs can not be connected unintentionally. Ä Before working on the contacts, check them for safety extra-low
voltage.
Danger! Risk of fatal injury due to electric shock!
Ä Never open the junction box. Ä Do not remove bypass diodes.
Danger! Risk of fatal injury due to electric shock!
Ä Never touch live contacts with bare hands. Ä Cover connectors by suitable protective caps
until installation.

4.2 ELECTRICAL INSTALLATION SAFETY

Danger! Risk of fatal injury due to electric shock!
Ä Electrical work may only be performed by
qualified and skilled personnel (see page 3).
Ä Ensure correct polarity.
Danger! Risk of fatal injury due to electric shock!
Ä Be sure to maintain the time intervals as
specified by the inverter manufacturer between switching off the inverter and beginning any further work.
Danger! Risk of fatal injury due to electric shock!
Ä Never plug or unplug the cable when under
load. Modules must not carry any current.
1. Switch off the inverter.
2. Switch off the DC circuit breaker.
3. Measure shutdown in DC String.
(no DC current flow).
4. Disconnect plugs by the use of appropriate
and qualified tools of the manufacturer.
5. When connecting the modules proceed in
reverse order.
OFF
Danger! Risk of fatal injury due to electric shock!
Ä Only use dry, insulated tools for electrical work.
14 15INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS14 15
Danger! Risk of fatal injury due to electric shock!
Ä Insulate any exposed cable ends. Ä Only connect cables with plugs.
4 ELECTRICAL CONNECTION
4 ELECTRICAL CONNECTION

4.3 CONNECTION OF MODULES

Ä Use solar cables for the connection at the
junction box outlet.
Ä Use the same, inverter-compatible plugs. Ä Use minimum 4 mm
a minimum of 90 °C for field connections.
2
copper wires insulated for
SOLAR
Note! Module damage may occur!
Ä Ensure that the cabling is not under mechanical
stress (Comply with bending radius of ≥ 60 mm).
Ä Ensure that the cables do not run between module
and mounting rail or structure (danger of pinch).

4.4 AFTER INSTALLATION

Ä Ensure that all necessary safety and functional
tests have been carried out according to applicable standards.
Note! Module damage may occur!
Ä Ensure that the plug connections are secured
away from any water-channelling surface.
Danger! Risk of fatal injury due to electric shock!
Ä Ensure that all electrical components are in a
proper, dry, and safe condition.
Ä Ensure for a tight connection between the
plugs. Plugs click together audibly.
Ä Do not connect modules with different
orientations or angles of inclination in the same string.
Ä To avoid complex cabling arrangements, it is
often advantageous to rotate some modules 180°.
Ä Module orientation can clearly be identified
from the front side by the serial number and barcode labelled behind the module glass on the side with negative connection cable.
Ä Integrate the system into the existing lightening
protection system in accordance with the applicable local regulations.
Ä Ensure that the cabling is not exposed and/or
hanging and is protected from dirt, moisture and mechanical friction.
Warning! Fire Risk!
Ä Do not use light concentrators (e.g. mirrors or
lenses).
Ä No dry cleaning or use of rotating brushes. Ä Modules must be cleaned manually and only
with sufficient Water.
Inverter
click
180° 180°
16 17INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS16 17

5 GROUNDING 6 FAULTS AND DEFECTS

8 MAINTENANCE AND CLEANING

Protective Grounding
Ä The modules must be grounded in accordance with the local
statutory regulations.
Functional grounding
For installations located in tropic regions (between 23.5° N
and 23.5° S) with a module tilt of < 5°, functional grounding at the negative generator connection on the DC side must be implemented.
Ä Ensure that the difference of potential between the negative
generator connection and the local earth potential (e.g. substructure, PE of the inverter) on each string in operation mode is positive or 0 V.
Ä Follow the directions of the inverter manufacturer and local
statutory regulations.
Ä Only use inverters which include lincensed grounding kits. Ä Functional grounding has also to be implemented in installation
sites with increased salt content in the air. (e.g. close to the
sea).
DANGER! Risk of fatal injury due to electric shock!
Ä Do not attempt to fix any problems yourself (e.g. glass cracks,
damaged cables).
Ä Please contact an installer or Q CELLS Technical Customer
Service Department.

7 DISPOSAL

Ä Do not disconnect modules by yourself. Ä Please contact an installer or Q CELLS Technical Customer
Service Department.
Ä Dispose of modules in accordance with the local disposal
regulations.
Q CELLS solar modules are known for a long operating life and minimal maintenance effort and expense. Dirt and grime are usually washed away by rain. If the module is fully or partially shaded by dirt or debris (e.g., plants, bird droppings), it needs to be cleaned to prevent a loss of performance.
Maintenance
Ä The PV system has to be inspected regularly by certified
personnel
Ä The time intervals and extent of the inspection can depend
on local circumstances (e.g. salt, ammonia content in the air, high humidity etc.). The customer/operator must inform himself about time intervals and extend of necessary inspections.
Ä Inspections have to be performed especially after extraordinary
events (e.g. storm, hail, high snow loads etc.)
Ä During the inspections it has to be checked that the compo-
nents are secure, undamaged and clean
Cleaning
WARNING! Risk of injury due to hot and live modules!
Ä Only clean modules that have cooled down. Ä Do not carry or wear any electrically conductive parts.
Note! Module damage may occur!
Ä Do not clean modules with water if there is a
risk of frost.
Ä Remove dirt with lukewarm water or alcohol
based glass cleaner, a broom, or a soft cloth.
Ä Do not use surfactants, rotating brushes,
scrapers, or any high-pressure water cleaning equipment.
WARNING! Risk of falling due to unsecured access!
Ä Never access the installation area alone or without taking
adequate security precautions.
Ä Please commission a trade specialist.
NOTE! Module surface damage may occur!
Ä Remove snow and ice carefully without force (e.g. with a
very soft broom).
Ä Do not scratch off dirt. Ä Rinse dirt (dust, leaves, etc.) off with lukewarm water or use an
alcohol based glass cleaner. Do not use abrasive detergents
or surfactants.
Ä Use a soft cellulose cloth (kitchen roll) or sponge to carefully
wipe off stubborn dirt. Do not use micro fleece wool or
cotton cloths.
Isopropyl alcohol (IPA) can be used selectively to remove stubborn dirt and stains within one hour after emergence.
Ä Please follow the safety guidelines provided by the IPA
manufacturer.
Ä Do not let IPA run down between the module and the frame
or into the module edges.
Ä Free the substructure from any dirt and debris
(leaves, bird nests, etc.).
18 19INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO-G6.X+ – Q CELLS18 19
HANWHA Q CELLS GMBH
OT Thalheim Sonnenallee 17 – 21 06766 Bitterfeld-Wolfen Germany
TEL +49 (0)3494 66 99 – 23222 FAX +49 (0)3494 66 99 – 23000 EMAIL sales@q-cells.com WEB www.q-cells.com
Subject to change without notice. © Q CELLS Installation manual solar modules Q.PEAK DUO-G6.X+_2019-06_Rev01_EN
Loading...