• The device is a universal and configurable temperature field transmitter for resistance
thermometers (RTD), thermocouples (TC) and resistance and voltage transmitters. The device is
designed for installation in the field.
• The manufacturer does not accept liability for damage caused by improper or non-designated use.
1.2Installation, commissioning, operation
Please note the following:
• Mounting, electrical installation, commissioning and maintenance of the device must only be
carried out by trained technical personnel authorised to perform such work by the owneroperator. They must have read and understood these Operating Instructions and must follow the
instructions they contain.
• The device may only be operated by staff authorised and instructed by the owner-operator. Strict
adherence to the instructions in these Operating Instructions is mandatory.
• The installer must ensure that the measuring system is correctly connected in accordance with
the electrical wiring diagrams.
• Observe local regulations governing the opening and repair of electrical devices.
1.3Operational safety
The measuring device meets the general safety requirements of EN 61010 and the EMC
requirements of EN 61326 as well as NAMUR recommendations NE 21, NE 43 and NE 89.
Power supply
► Power must be fed to the device from an 11 to 40 VDC power supply in accordance with NEC
Class 02 (low voltage/current) with short-circuit power limit to 8 A/150 VA.
Hazardous area
Separate Ex documentation is provided for measuring systems used in hazardous areas. This
documentation is an integral part of these Operating Instructions. The installation instructions and
connection data it contains must be observed!
1.4Return
To reuse later or in case of repair, the device must be packed in protective packaging, preferably the
original packaging. Repairs must only be carried out by your supplier's service organisation or
specially trained personnel.
Enclose a note describing the fault and the application when sending the unit in for repair.
4Pyromation, Inc.
Series 642Safety instructions
1.5Notes on safety conventions and icons
The safety instructions in these Operating Instructions are labelled with the following safety icons
and symbols:
SymbolMeaning
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result
A0011190-EN
in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result
A0011191-EN
in minor or medium injury.
NOTICE!
This symbol contains information on procedures and other facts which do not result in
A0011192-EN
personal injury.
Indicates additional information, Tip
A0011193
Pyromation, Inc.5
IdentificationSeries 642
2Identification
2.1Device designation
2.1.1Nameplate
Compare the nameplate on the device with the following diagram:
Fig. 1: Nameplate of the field transmitter (example)
1Order code and serial number of the device
2Degree of protection and approvals
3Power supply and output signal
4Ambient temperature
2.2Scope of delivery
The scope of delivery of the field transmitter comprises:
• Temperature field transmitter
• Dummy plug
• Mounting bracket
• Operating Instructions
2.3Certificates and approvals
CE mark, declaration of conformity
The temperature field transmitter is designed to meet state-of-the-art safety requirements, has been
tested and left the factory in a condition in which it is safe to operate. The device meets the relevant
standards and directives as per IEC 61 010 "Safety requirements for electrical equipment for
measurement, control and laboratory use".
The device described in these Operating Instructions thus meets the legal requirements of the EU
directives. The manufacturer confirms that the device has been tested successfully by affixing the
CE mark.
CSA GP approved
6Pyromation, Inc.
Series 642Installation
3Installation
3.1Quick installation guide
If the sensor is fixed then the unit can be fitted directly to the sensor.
If the sensor is to be mounted at a right angle to the cable gland, swap the dummy plug and cable
gland.
The device can be mounted directly on the wall. A mounting bracket is available for pipe mounting
(see Fig. 4). The illuminated display can be mounted in four different positions (→ å 2):
Fig. 2: Temperature field transmitter with sensor, 4 display positions, can be plugged-in in 90° steps
Fig. 3: Turning the display
1.Remove the cover clamp (Pos. 1).
2.Unscrew the housing cover together with the O-ring (Pos. 2).
3.Remove the display with retainer (Pos. 3) from the electronics module (Pos. 4). Adjust the
display with retainer in 90°stages to your desired position and rearrange it on the particular
slot in the electronics module.
4.Then screw on the housing cover together with the O-ring. Mount the cover clamp.
Pyromation, Inc.7
InstallationSeries 642
3.2Installation conditions
3.2.1Dimensions
The dimensions of the device can be found in chapter 10 ''Technical data".
3.2.2Installation point
Information on installation conditions, such as ambient temperature, protection classification,
climatic class etc., can be found in chapter 10 "Technical data".
3.3Installation
3.3.1Direct wall mounting
Proceed as follows to mount the device directly on wall:
• Drill 2 holes
• Attach the device to the wall with 2 screws (M6).
3.3.2Pipe installation
The mounting bracket is suited for pipes with a diameter between 1.5" - 3.3".
Proceed as follows to mount the device on a pipe:
• Attach the mounting bracket to the pipe
• The additional mounting plate must be used for pipes with a diameter of 1.5" to 2.2".
• Fix the device to the mounting bracket with the two screws supplied. The mounting plate is not
needed for pipes with a diameter of 2.2" - 3.3".
Fig. 4: Mounting the field transmitter with the mounting bracket, see 'Accessories' section
3.4Installation check
After installing the device, always run the following final checks:
Device condition and specificationHint
Is the device visibly damaged (visual check)?-
Does the device comply to the measurement point specifications, such as
ambient temperature, measurement range etc.?
8Pyromation, Inc.
See chapter 10 "Technical data"
Series 642Wiring
NOTICE
NOTICE
4Wiring
Installation in hazardous area
► When installing Ex-approved devices in a hazardous area please take special note of the
instructions and connection schematics in the respective Ex documentation added to this
operating manual. The local representative is available for assistance if required.
For wiring the device proceed as follows:
1.Remove the cover clamp (→ å 3, item 1).
2.Remove the device cover (→ å 3, item 2).
3.Remove the display from the electronics module (→ å 3, item 3).
4.Open the 2 screws of the electronics unit and remove the electronics unit (→ å 3, item 4).
5.Open the cable gland at the device (→ å 3, item 5).
6.Feed the cable through the opening in the cable gland.
7.Connect the wires (→ å 5).
8.Make sure that the terminal screws are tight. Re-seal the cable gland by screwing the cover
back on.
9.In order to avoid connection errors always take note of the hints given in the section
connection check!
4.1Quick wiring guide
Terminal layout
Fig. 5: Wiring the field transmitter
ESD - Electrostatic discharge
► Protect the terminals from electrostatic discharge. Failure to observe this may result in
destruction of parts of the electronics.
Pyromation, Inc.9
WiringSeries 642
NOTICE
4.2Connecting the sensor
Please refer to Section 4.1 "Quick wiring guide" for the terminal assignment of the sensor
connections.
4.3Connecting the measuring unit
Electronic parts may be damaged
► Switch off power supply before installing or connecting the device. Failure to observe this may
result in destruction of parts of the electronics.
► If the device has not been grounded as a result of the housing being installed, grounding it via
one of the ground screws is recommended.
4.3.1HART® connection
If the HART
communication resistor must be fitted into the 2-wire supply lines.
For connection hints, please take special notice of the documentation supplied by the
HART
overview”.
®
communication resistance is not built into the power supply, a 250 Ω
®
Communication Foundation, specifically HCF LIT 20: “HART, a technical
Connection using a transmitter power supply
HART® connection with a transmitter power supply
10Pyromation, Inc.
Series 642Wiring
Connection using other power supplies
HART® connection using other power supplies, e. g. a SPS
4.4Screening and potential equalization
Please take note when installing the device:
If screened (shielded) cables are used then the screen connected to the output (output signal 4 to
20mA) must be at the same potential as the screen at the sensor connection!
When operating in plants with high electromagnetic fields, it is recommended that all cables be
screened using a low ohm ground connection. Due to the possible danger of lightning strikes
screening is also recommended for cables that are run outside buildings!
Pyromation, Inc.11
WiringSeries 642
4.5Degree of protection
The device conforms to the requirements to IP 67 ingress protection. In order to fulfil an IP 67
degree of protection after installation or service, the following points must be taken into
consideration:
• The housing seals must be clean and undamaged before they are replaced into the sealing rebate.
If they are found to be too dry then they should be cleaned or even replaced.
• All housing screws and covers must be pulled tight.
• The cables used for connection must be of the correct specified outside diameter (e.g. M20 x 1.5,
cable diameter from 8 to 12 mm; 0.315 to 0.47 in).
• Tighten cable gland (→ å 6).
• Loop the cable before placing into the cable entry ("Water sack", → å 6). This means that any
moisture that may form cannot enter the gland. Install the device so that the cable entries are not
facing upwards.
• Cable entries not used are to be blanked off using the blanking plates provided.
• The protective olive must not be removed from the cable gland.
Fig. 6: Connection hints to retain IP 67 protection
4.6Connection check
After the electrical installation of the device, always perform the following final checks:
Device condition and specificationHint
Are the device or the cables undamaged (visual check)?-
Electrical connectionHint
Is the cable installation correctly separated, with no loops or crossovers?-
Are the cables load relieved?-
Have the cables been correctly connected? Compare with the
connection schematic on the terminals or → Fig. 5.
Are all terminal screws tightened?
Is the cable entry sealed?
Is the housing cover screwed tight?
See connection schematic on the
housing
Visual check
12Pyromation, Inc.
Series 642Operation
°C
°F
%
K
10
0
20
30
40
50
60
70
80
90
100
!
Ê
Ë
Ì
Í
Î
Ï
Ð
5Operation
5.1Display and operating elements
5.1.1Display
Fig. 7: LC display of the field transmitter (illuminated, can be plugged in 90° stages)
5.1.2Display symbols
Item
FunctionDescription
No.
1Bargraph display In 10 % stages with indicators for overranging/
2'Caution' indicatorThis appears in the event of an error or warning
3Unit display K, °F, °C or %Unit display for the measured value displayed
4Measured value display (digit height 20.5 mm)The measured value is displayed. In the event of a warning,
5Status and information displayIndicates which value is currently shown on the display. A
6'Communication' displayThe communication symbol appears for read and write
7'Configuration blocked' displayThe 'configuration blocked' symbol appears if configuration
underranging. The bargraph display flashes when an error
occurs.
the display switches between the measured value and the
code of the warning. In the event of an error, the error code
is displayed instead of the measured value.
customer-specific text can be entered for PV. In the event
of a warning, 'WARN' is displayed along with the code for
the warning. In the event of an error, 'ALARM' is displayed.
®
access via the HART
via software or hardware is blocked.
protocol
Pyromation, Inc.13
OperationSeries 642
NOTICE
5.2Local operation
5.2.1Hardware setting
Fig. 8: Hardware settings via jumpers J1, J2 and J3
ESD - Electrostatic discharge
► Protect the terminals from electrostatic discharge. Failure to observe this may result in
destruction of parts of the electronics.
Jumpers J1, J2 and J3 for the hardware setting are located at the electronics module. To set the
jumper, open the threaded joint of the electronics module (opposite the threaded joint of the
connection compartment) and remove the display if necessary.
Hardware locking the configuration with jumper J1
TRANSMITTER SECURITY
ONConfiguration locked
OFFConfiguration enabled
The hardware setting for configuration locking has priority over the software setting.
Setting the failsafe mode via the hardware with jumper J2
FAILURE MODE
LO≤ 3.6 mA
HI≥ 21.0 mA
The failsafe mode set via the jumpers only takes effect if the microcontroller fails.
14Pyromation, Inc.
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.