Pyromation 440 User Manual

Series 440 Installation and Operating Instructions
1 SAFETY NOTES
Safe and secure operation of the head transmitter can only be guaranteed if the operating instructions and all safety notes contained are understood and followed.
The unit is a universal, presettable temperature transmitter for resistance thermometer (RTD). The unit is constructed for mounting in a connection head and a field housing. The manufacturer cannot be held responsible for damage caused by misuse of the unit.
1.2 Installation, commissioning and operation
The unit is constructed using the most up-to-date production equipment and complies with the safety requirements of the EU guidelines. If it is installed incorrectly or is misused, certain application dangers can occur. Trained personnel must do installation, wiring, and maintenance of the unit. These personnel must have read and understood these instructions and must follow them to the letter.
2 FUNCTION AND SYSTEM CONSTRUCTION
2.1 Function
Provides electronic monitoring of input signals into an analog output signal in industrial temperature measurement. The head transmitter is mounted in a connection head or separated from the sensor in a field housing. Setting up of the head transmitter is done using PC and configuration software. The configuration kit is required for setting up the head transmitter.
2.2 Measurement system
Transforming the following input signals:
• Resistance thermometers (RTD) (in 2 or 3 wire connection systems)
Fault monitoring of:
• Measurement range override or undercut
• Sensor breakage and short circuit
3 INSTALLATION
3.1 Installation conditions
Ambient temperature: (-40 to 85) °C [-40 to 185] °F Installation area: Field housing; connection head Installation angle: No limit
Safety notes: The unit must only be powered by a power supply that operates using an IEC 61010-1 compliant energy limited circuit.
3.2 Installation
• Feed the sensor leadwires through the central hole in the head transmitter
• Position the head transmitter in the connection head
• Feed the installation screws through the slots in the head transmitter.
• Screw the head transmitter into the field housing using a screwdriver while not over tightening.
4 WIRING
4.1 Overview
Power supply and current output
Terminal layout
SETUP socket
(10 to 30) V dc (4 to 20) mA
2-Wire
3-Wire
© Copyright 2006 Pyromation, Inc., All Rights Reserved.
Phone (260) 484-2580 • FAX (260) 482-6805 or (800) 837-6805 • www.pyromation.com
440-D1 of 4
4.2 Measurement unit connection
Attention: Switch off power supply before opening the housing cover. Do not install or connect the unit to mains power. If this is
not followed parts of the electronic circuit will be damaged.
• Sensors:
Connect the sensor leads to the respective head transmitter terminals (Terminals 1 to 3) by following the wiring diagram (see figure 4.1).
• Output signal and power supply: Open the PG cable gland on the head transmitter or field housing. Feed the cable through the opening in the PG cable gland
and then connect the cable cores to terminals 4 and 5 according to the wiring diagram (see figure 4.1).
• PC configuration (SETUP socket): Open the flap on the SETUP socket (Figure 4.1) and connect the SETUP connection cable.
Hint: The screws on the terminals must be screwed tightly. Head transmitter configuration during measurement operation is possible. There is no need to disconnect leads.
Potential leveling
Please take note when installing the head transmitter remotely in a field housing. The screen on the (4 to 20) mA signal output must have the same potential as the screen at the sensor connections. When using earthed thermocouples, screening of the output (4 to 20) mA cable is recommended. In plants with strong electromagnetic fields, screening of all cables with a low ohm connection to the transmitter housing is recommended.
5 OPERATION
5.1 Short form instructions (SETUP)
PRESETTABLE PARAMETERS
• Sensor type
Standard settings
Expanded settings
Service functions • Simulation (on/off)
For detailed TransComm operating instructions, please read the online documentation contained in the software.
• Connection mode (2 or 3 wire connection)
• Units (°C or °F)
• Measurement range start (depends on sensor)
• Measurement range end (depends on sensor)
• Compensation resistance (0 to 20) Ω on 2 wire connection
• Fault condition reaction (≤ 3.6 mA or ≥ 21.0 mA)
• Output (analog standard/inverse)
• Damping (0 to 8) s
• Offset (-9.9 to +9.9) ˚C [-17.8 to +17.8] ˚F
• Measurement point identification/TAG Service functions
5.2 Communication
The head transmitter must be set up using a PC and configuration kit. The following points must be taken into account if trouble free setting up is to be achieved:
• Configuration software installation.
• Connect the head transmitter to the PC using the connection cable from the configuration kit.
CONFIGURATION SOFTWARE INSTALLATION
• IBM PC or compatible computer (minimum Pentium 166 MHz)
• Windows 95/98/ME/NT4.0/2000
System conditions
Recommended minimum configuration
• 64 MB RAM
• Minimum 30 MB free memory on hard drive
• CD-ROM drive
• Screen resolution 800 x 600 Pixel
• Free serial interface
• Pentium 400 MHz
• 128 MB main RAM
• 120 MB free hard drive memory
• Screen resolution 1024 x 768 Pixel
Installation start
Start Windows
1. Place installations-CD in the respective drive
2. Start “Setup.exe” and follow the installation instructions
3. If required, the help/operating manual can be printed once the software has been successfully installed.
© Copyright 2004 Pyromation, Inc., All Rights Reserved.
Phone (260) 484-2580 • FAX (260) 482-6805 or (800) 837-6805 • www.pyromation.com
2 of 4440-D
Loading...
+ 2 hidden pages