PYLE Audio MN300HGA User Manual

BLUE FLAME VENT-FREE
NATURAL GAS GARAGE
HEATER
OWNER’S OPERATION AND INSTALLATION MANUAL
Do not store, or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
l Do not try to light any appliance. l Do not touch any electrical switch; do not
use any phone in your building. l Immediately call your gas supplier from a neighbor’s phone. Follow the gas suppliers instructions. l If you cannot reach your gas supplier, call
MN300HGA MN300TGA
THERMOSTAT MODEL
Table of Contents
Important Safety Information..................................... 2
Fresh Air for Combustion and Ventilation ............... 4
Installation..................................................................... 8
Operating Your Heater............................................... 11
Cleaning&Maintenance.............................................13
Trouble Shooting.........................................................14
Specifications..............................................................17
Illustrate Parts Breakdown MN300TGA .................18
Parts List MN300TGA .................................................19
Illustrate Parts Breakdown MN300HGA .................20
Parts List MN300HGA .................................................21
WARNING: If the information in this
manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
WARNING: This is an unvented gas-fired
heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air For Combustion and Ventilation section on page 4 of this manual.
CONTINENTAL APPLIANCE INC/U.S. OFFICE
5 Musick 4600 Highlands Parkway S.E.
Irvine Suite # D/E
CA 92618 Smyrna, GA 30080
Nanjing PRO-COM Electric Appliance Co.,Ltd.
#6 Chuangye Road,High New Tech.Zone,
Great Bridge Road North,Nanjing,210061,
China.
PRO-COM PHONE NUMBER: (877)886-5989
the fire department.
Installation and service must be performed by a qualified installer, service agency or gas supplier.
WARNING: Improper installation,
adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or gas supplier.
This appliance may be installed in an aftermar­ket* permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS Water vaporis a by-product of gas combustion.An unvented room heater produces approximately one (1) ounce (30ml) of water for every 1,000 BTUs (.3KWs) of gas input per hour. Refer to page 3.
Installer: Please leave these instructions with the consumer.
Consumer: Please retain these instructions for future use.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
1
PR-ML062-09-0504
IMPORTANT SAFETY INFORMATION
IMPORTANT: Read this
owners manual carefully and completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
WARNING: Do not use any
accessory not approved for use with this heater.
WARNING: Any change to
this heater or its controls can be dangerous.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Due to high temperatures, heater should be kept out of traffic and away from furniture and draperies.
Surface of heater becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shut down. Allow surface to cool before touching.
Carefully supervise young children when they are in the same room with heater.
Make sure grill guard is in place before running heater.
State of Massachusetts: The
installation must be made by a li-
censed plumber or gas fitter in the
Commonwealth of Massachusetts. Sellers of unvented propane or natu-
ral gas-fired supplemental room heat-
ers shall provide to each purchaser a copy of 527 CMR 30 upon sale of the
unit.
In the state of Massachusetts,
unvented propane or nature gas-fired
space heaters shall be prohibited in
bedrooms and bathrooms.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
WARNING
Modeles MN300HGA, MN300TGA, are equipped for natural gas. Field conversion is not permitted.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. If you smell gas
l Shut off gas supply. l Do not try to light any appliance. l Do not touch any electrical switch;
do not use any phone in your building.
l Immediately call your gas supplier
from a neighbors phone. Follow the gas suppliers instructions.
l If you cannot reach your gas
supplier, call the fire department.
3. This heater shall not be installed in a bedroom or
bathroom, or the place which the strong wind would shut down the appliance.
4. This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensor (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Fresh Air For
Combustion And Ventilation
pages 4 and 5.
5. Keep all air openings in the front and bottom of heater clear and free of debris. This will insure enough air for proper combustion.
6. If heater shuts off. Do not relight until you provide fresh, outside air. If heater keeps shutting off, have it serviced.
7. Do not run heater l where flammable liquids or vapors
are used or stored
l under dusty conditions
2
8. Turn heater off ,Before using furniture polish, wax, carpet cleaner, or similar products. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
9. Do not use heater if any part has been under water.
Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
10. Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
11. Operating heater above elevations of 4,500 feet could cause pilot outage.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning:
Early signs of carbon monoxide poisoning resemble the flu with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes. Natural Gas: Natural gas is odorless. An odor-making agent is added to natural gas. The odor helps you de­tect a natural gas leak . However, the odor added to natural gas can fade. Natural gas may be present even though no odor exists.
Make certain you read and under­stand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
PRODUCT FEATURES
Figure1-Vent-Free Natural Gas Heater(Model MN300TGA Shown)
SAFETY DEVICE
A standard requirement for all vent-free room heaters. This heater has a pilot with an Oxygen Depletion Sensor(ODS) safety shutoff system. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater is equipped with a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.
THERMOSTATIC HEAT CONTROL ON THERMOSTAT
MODEL MN300TGA
These heaters have a control valve with a thermostat sensing bulb. This results in the greatest heater comfort and may result in lower gas bills.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vaporis a by-product of gas combustion.An unvented room heater produces approximately one (1) ounce (30ml) of water for every 1,000 BTUs (.3KWs) of gas input per hour. Unvented room heaters are remommended as supplemental heat (a room) rather than a primary heat source (an entire house) .In most supplemental heat application, the water vapor does not create a problem. In most applications, the water vapor enhances the low humidity atmosphere experience during cold weather.
3
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of National Fuel Gas code ANSZ223.1, also known as NFPA 54*. *Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to
heater for shipment.
3. Check heater for any shipping damage. If heater is damaged. promptly inform dealer where you bought heater.
The following steps will help insure that water vapor does not become a problem.
1. Be sure the heater is sized properly for the application, including ample combusion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used to help lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat source.
FRESH AIR FOR COMBUSTION AND
VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning
appliances in your home.
PRODUCING ADEQUATE VENTILATION
The following are excerpts from
National Fuel Gas Code. NFPA 54/ ANS Z223.1, Section 5.3. Air for
Combustion and Ventilation. All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6×10 per pa-sec-m2) or less with openings gasketed or sealed and b. weather stripping has been added on openable windows and doors and c. caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings. If your home meets all of the three criteria above, you must provide additional fresh air.
See Ventilation Air from Outdoors, page 6.
If your home does not meet all of the three criteria above, see
Determining Fresh-Air Flow for Heater Location, page 5
-11
kg
Confined and Unconfined Space
The National Fuel Gas Code ANS Z223.1 defines a confined space
as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space. This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
Adjoining rooms are
*
communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if you have a Confined or Unconfined Space*
Use this worksheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length×width×height) Length×Width×Height= cu.ft. (volume of space) Example: Space size 20ft. (length)×16ft.( width)×8ft. (ceiling height)=2560cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support. (volume of space)÷ 50 cu. ft.=(Maximum Btu/Hr the space can support) Example: 2560 cu. ft. (volume of space)÷50 cu.ft.=51.2 or 51.200(maximum Btu/Hr the space can support)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.
4
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater Btu/Hr Gas water heater* Btu/Hr Gas furnace Btu/Hr Vented gas heater Btu/Hr Gas Fireplace logs Btu/Hr
Example: Gas water heater 40,000 Btu/Hr Vent free heater + 20,000 Btu/Hr Total = 60,000 Btu/Hr
Other gas appliances* + Btu/Hr Total = Btu/Hr *Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used) Example : 51,200 Btu/Hr(maximum the space can support)
60,000 Btu/Hr(actual amount of Btu/Hr used) The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows: A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 5. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6 . C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
VENTILATION AIR
Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National
Fuel Gas Code NFPA 54/ANS Z223.1. Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts
WARNING: Rework worksheet, add­ing the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
Figure 2 -Ventilation Air from Inside Building
5
Figure 3 -Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is
intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run systems circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified service person must install heater. Follow all local codes.
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural, do not install heater. Call dealer where you bought heater for proper type heater.
INSTALLATION NEEDS
Before installing heater, make sure you have the items listed below.
l piping (check local codes) l sealant (resistant to natural
gas)
l equipment shutoff valve*
l ground joint union
l test gauge connection*
l sediment trap
l tee joint
l pipe wrench
VENTILATION AIR
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or duels: You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas
Code NFPA 54/ANS Z223.1, Section 5.3. Air for Combustion and Ventilation for
required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
*A CSA/AGA design-certified equip­ment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA/AGA design cer­tified equipment shutoff valve from your dealer. See Accessories, page
17.
LOCATING HEATER
This heater is designed to be mounted on a wall. You can locate heater on floor, away from a wall. An optional floor mounting stand is needed. Purchase the floor mounting stand from your dealer. See Accessories, page 17. For convenience and efficiency, install heater
l where there is easy access for
operation, inspection, and service
l in coldest part of room An optional fan kit is available from your dealer. See Accessories, page 17. If planning to use fan, locate heater near an electrical outlet.
CAUTION: If you install the heater in a home garage l heater pilot and burner must be at least 18 inches above floor. l locate heater where moving vehicle will not hit it.
CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist may discolor walls.
WARNING: Never install
the heater
l in a bedroom or bathroom. l in a recreational vehicle. l where curtains, furniture,
clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater.
l as a fireplace insert. l in high traffic areas. l in windy or drafty areas.
6
INSTALLATION
WARNING: Maintain the
minimum clearances shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.
Figure 4 -Mounting Clearaances As Viewed From Front Of Heater
IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See
Fresh Air for Combustion and Ventilation, pages 4 and 5.
INSTALLING THERMOSTAT SENSING BULB For MN300TGA
1. Pull out the sensing bulb from the two clips located in the shippng position according to the direction as shown by the arrow. There is no need to take out the two bulb clips.
2. Take out the bulb clip from the hardware package and insert it into the square hole and then insert the sensing bulb into the bulb clip (see Figure 5).
FASTENING HEATER TO WALL Mounting Bracket
The mounting bracket is located on back panel of heater (see figure 6). It has been taped there for shipping. Remove mounting bracket from back panel.
Figure 6 -Mounting Bracket Location
Removing Lower Front Panel Of Heater
1. Remove two screws near bottom corners of lower front panel .
2. Pull bottom of lower front panel forward, then down (see Figure 7).
Figure 7 - Removing Lower Front Panel Of Heater
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall. These two holes are 16 inches apart from their centers. Attach mounting bracket to wall only in one of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Stud: This method provides the strongest hold. Insert mounting screws through mounting bracket and into wall studs.
Attaching to Wall Anchor: This method allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Either method will provide a secure hold for the mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.
WARNING: Maintain minimum clearances shown in Figure 8. If you can, provide greater clearances from floor and joining wall.
2. Mark screw locations on wall. (see Figure 8) Note: Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only.
3. Remove tape and mounting bracket from wall.
Model MN300HGA MN300TGA
Figure 8 - Mounting Bracket Clearances
Figure 5 - Moving Thermostat Sensing Bulb
7
Attaching Mounting Bracket to Wall Note: Wall anchors, mounting
screws, and spacers are in hardware package. The hardware package is provided with heater.
Attaching to Wal l Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64" drill bit.
2. Place mounting bracket onto wall. Line up last hole on each end of bracket with holes drilled in wall.
3. Insert mounting screws through bracket and into wall studs.
4. Tighten screws until mounting bracket is firmly fastened to wall studs.
Attaching to Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls. (concrete or masonry)
1. Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1" deep.
2. Fold wall anchor as shown in Figure 9 below.
Figure 9 - Folding Anchor
3. Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
4. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to "pop" open anchor wings.
IMPORTANT: Do not ham­mer key! For thick walls (over 1/ 2" thick) or solid walls, do not pop open wings.
INSTALLATION
Figure 10 - Popping Open Anchor Wing for Thin Walls
5. Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors.
6. Insert mounting screws through bracket and into wall anchors.
7. Tighten screws until mounting bracket is firmly fastened to wall.
Placing Heater on Mounting
Bracket
1. Locate two horizontal slots on back panel of heater (see Figure 11).
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket.
Figure 11 - Mounting Heater Onto Mounting Bracket
Installing Bottom Mounting Screws
1. Locate two bottom mounting holes. These holes are near bottom on back panel of heater(see Figure 12).
Figure 12 - Installing Bottom Mounting Screws
2. Mark screw locations on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screws into hollow or solid wall, install wall anchors. Follow steps 1 through 4 under Attaching To Wall Anchor Method. If installing bottom mounting screw into wall stud, drill holes at marked locations using 9/64" drill bit.
5. Replace heater onto mounting
bracket.
6. Place spacers between bottom
mounting holes and wall anchor or drilled hole.
7. Hold spacer in place with one
hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.
8. Tighten both screws until heater
is firmly secured to wall. Do not over tighten. l Note: Do not replace lower front panel at this time. Replace lower front panel after making gas connections and checking for leaks (see page 9).
8
CONNECTING TO GAS SUPPLY
WARNING: A qualified
service person must connect heater to gas supply. Follow all local codes.
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: Never connect heater to private (non-utility) gas well. This gas is commonly known as well-head gas.
IMPORTANT: Check your gas line pressure before connecting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher, heater regulator damage could occur.
CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.
Typical Inlet Pipe Diameters
MN300HGA/MN300TGA 1/2 or greater
Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be up stream from heater (see Figure
13).
INSTALLATION
Figure 13 -Gas Connection
*A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA/AGA design-certified equipment shutoff valve from your dealer. See Accessories, page 17.
IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
CAUTION: Use pipe joint sealant that is resistant to natural gas.
Install sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings.
9
INSTALLATION
OPERATING YOUR HEATER
CHECKING GAS CONNECTIONS
WARNING: Test all gas
piping and connections for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping System Test Pressures In Excess Of 1/2 PSIG (3.5 K Pa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve
was connected.
3. Pressurize supply piping system by either using compressed air or opening
main gas valve located on or
near gas meter.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show
a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment
shutoff valve to gas supply. Check
reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 K Pa)
1. Close equipment shutoff valve
(see Figure 14).
2. Pressurize supply piping system
by either using compressed air or opening main gas valve located on or near gas meter.
3. Check all joints from gas meter to
equipment shutoff valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Pressure Testing Heater Gas Connections
1. Open equipment shutoff valve (see Figure 14).
2. Open main gas valve located on or near gas meter.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from equipment shutoff valve to control valve (see Figure 15 ). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, pages 11 for thermostat model or page 12 for
non-thermostat model). Check
the rest of the internal joints for
leaks.
7. Turn off heater (see To Turn Off Gas To Appliance, page 11 for thermostat model or page 12
for non-thermostat model).
8. Replace lower front panel.
Figure 14 -Equipment Shutoff Valve
Figure 15 -Checking Gas Joints
WARING:Do not over tighten gas
connections.
THERMOSTAT MODEL MN300TGA
nFOR YOUR SAFETYn
READ BEFORE LIGHTING
WARNING: If you do not
follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor .
WHAT TO DO IF YOU SMELL GAS
l Do not try to light any appliance. l Do not touch any electric switch;
do not use any phone in your building. l Immediately call your gas supplier from a neighbor’s phone. Follow the gas suppliers instructions. l If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, dont try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
10
OPERATING YOUR HEATER
THERMOSTAT MODEL MN300TGA
nLIGHTINGn
INSTRUCTIONS
1. STOP! Read the safety information on the side of heater.
2. Check that gas supply to heater is on.
3. Push in gas control knob slightly and turn clockwise to the OFF position. NOTE: knob cannot be turned from PILOT to “OFF unless knob is pushed in slightly. Do not force.
4. Wait five (5) minutes to clear out any air. Then smell for gas, including near the floor. If you smell gas, STOP! Follow B in the safety information on the side of the heater. If you do not smell gas, go to the next step.
5. Push in gas control knob slightly and turn counter­ clockwise to the PILOT/IGN position and depress for five(5) seconds NOTE: The first time that the heater is operated after connecting the gas supply , the control knob should be depressed for about thirty (30) seconds. This will allow air to bleed from the gas system.
6. With control knob pressed in, push down and release the ignitor button. This will light pilot. If needed, keep pressing ignitor button until pilot lights. NOTE: If pilot does not stay lit, refer to Troubleshooting, pages 14 through 16. Also contact a qualified service person or gas supplier for repairs. Until repairs are made, light pilot with match. To light pilot with match, see Manual Lighting
Procedure.
7. Keep control knob pressed in
for thirty (30) seconds after lighting pilot. After 30 seconds, release control knob. l If control knob does not pop up when released, contact a qualified service person or gas supplier for repairs. NOTE: If pilot goes out, repeat steps 3 through 7. Wait one (1) minute before lighting pilot again
8. Turn control knob
counterclockwise to desired heating Level. The main burner should light. Set control knob to any heat level between HI and LO.
Figure 16 - Control Knob in The OFF Position
Figure 17 - Pilot
nTHERMOSTAT n
CONTROL
OPERATION
The thermostatic control used on these models differs from standard thermostats. Standard thermostats simply turn on and off the burner.The thermostat used on this heater senses the room temperature. The thermostat adjusts the amount of gas flow to the burner.
This increases or decreases the burner flame height. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room tem­perature drops below the set temperature. The control knob can be set to any heat level between HI and LO. Selecting the HI setting will cause the burner to remain fully on without modulating down in most cases. NOTE: the thermostat sensing bulb measures the temperature of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction. installation location, room size, open air temperatures, etc.). frequent use of your heater will let you determine your own comfort levels.
nTO TURN OFFn
GAS TO APPLIANCE
Shutting Off Heater
1. Turn control knob clockwise
to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
SHUTTING OFF BURNER ONLY (PILOT STAYS LIT)
Turn control knob clockwise to
the PILOT/IGN position
nMANUAL LIGHTINGn
PROCEDURE
1. Remove lower front panel (see Figure 7 page 7).
2. Follow steps 1 through 5 under Lighting Instructions.
3. With control knob pressed in, strike match. Hold match to pilot until pilot lights.
4. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Follow step 8 under Lighting Instructions.
5. Replace lower front panel.
11
OPERATING YOUR HEATER
NON-THERMOSTAT MODEL
MN300HGA
nFOR YOUR SAFETYn
READ BEFORE LIGHTING
WARNING: If you do not
follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
l Do not try to light any appliance. l Do not touch any electric
switch, do not use any phone in your building. l Immediately call your gas
supplier from a neighbors
phone. Follow the gas suppliers instructions. l If you cannot reach your gas
supplier, call the fire department.
nLIGHTINGn
INSTRUCTIONS
1. STOP! Read the safety information on the side of heater.
2. Check that gas supply to
heater is on.
3. Push in control knob slightly and turn clockwise to the
OFF position (see Figure 18). NOTE: Knob cannot be turned
from "PILOT " to "OFF" unless knob is pushed in slightly. Do
not force.
4. Wait five minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the side of heater. If you dont smell gas, go to the next step.
5. Push in and turn control knob counterclockwise to PILOT position. Press in control knob
for five(5) seconds. Note: You may be running
this heater for the first time after hooking up to gas supply. If so, you may need to press in control knob for 30 seconds. This will allow air to bleed from
the gas system.
6. With control knob pressed in, push down and release the ignitor button. This will light pilot. If needed, keep pressing
ignitor button until pilot lights.
7. Keep control knob depressed for ten (10) seconds after lighting pilot. if pilot goes out, repeat
steps 5,6 and 7.
8. To select the desired heating level, partially press down the control knob slightly and rotate counterclockwise . Release the downward pressure on the knob while continuing to turn until the knob locks at the desired setting position. Do not
operate between locked positions.
nTOTURN OFFn
GAS TO APPLIANCE
Shutting Off Heater
1. Turn control knob clockwise
to the OFF position.
2. Turn off all electric power to the appliance if service is to
be performed.
Shutting Off Burner Only (pilot stays lit )
Slightly press in control turn control knob clockwise to the PILOT position.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, dont try to repair it , call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Figure 18 - Control Knob in The OFF Position
Figure 19 - Pilot
12
nMANUAL LIGHTINGn
PROCEDURE
1. Remove lower front panel (see Figure 7 page 7).
2. Follow steps 1 through 5 under Lighting Instructions.
3. With control knob pressed in, strike match. Hold match to pilot until pilot lights.
4. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Follow step 8 under Lighting Instructions.
5. Replace lower front panel.
INSPECTING BURNER
Check pilot flame pattern and burner flame pattern often.
PILOT FLAME PATTERN
Figure 20 shows a correct pilot flame pattern. Figure 21 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down. If pilot flame pattern is incorrect, as shown in Figure 21: l turn heater off (see To Turn
Off Gas To Appliance on page
12 for non-thermostat model or page 11 for thermostat model) l see Troubleshooting pages 14 through 16.
Figure 20 - Correct Pilot Flame Pattern
BURNER FLAME PATTERN
Figure 22 shows a correct burner flame pattern. Figure 23 shows an incorrect burner flame pattern. If pilot flame pattern is incorrect, as shown in Figure 23: l turn heater off (see To Turn Off
Gas To Appliance on page 12 for non-thermostat model and page
11 for thermostat model). l see Troubleshooting on pages 14 through 16.
WARNING: If yellow tipping occurs, your heater could produce increased levels of carbon monoxide. If burner flame pattern shows yellow tipping, follow instruc­tions at bottom of this page.
Notice: Do not mistake orange flames with yellow tipping. Dirt or other fine particles enter the heater and burn causing brief patches of orange flame.
Figure 22 - Correct Burner Flame Pattern
Figure 23 - Incorrect Burner Flame Pattern
CLEANING ODS/PILOT AND BURNER
l Use a vacuum cleaner,
pressurized air or a small, soft
bristled brush to clean.
CLEANING BURNER PILOT AIR INLET HOLE
We recommend that you clean the unit every 2,500 hours of operation or every three months. We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSl. Your local computer store, hardware store. or home center may carry com­pressed air in a can. You can use a vacuum cleaner in the blow position. If using compressed air in a can, please follow the directions on the can. If you dont follow directions on the can, you could damage the pilot assembly.
1. Shut off the unit, including thepilot Allow the unit to cool for
at least thirty minutes.
2. Inspect burner and pilot for dust
and dirt.
3. Blow air through the ports/slots
and holes in the burner. Also, clean the pilot assembly . A yellow tip on the pilot flame indi­cates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 24). With the unit off lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.
Figure 21 - Incorrect Pilot Flame Pattern
CLEANING AND
MAINTENANCE
WARNING: Turn off heater
and let cool before servicing.
CAUTION: You must keep control areas, burner, and circulating air pas­sageways of heater clean. Inspect these areas of heater before each use. Have heater Inspected yearly by a qualified service person. Heater may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
13
Figure 24 - Pilot Inlet Air Hole
CLEANING HEATER CABINET
Air Passageways
l Use a vacuum cleaner or pressurized air to clean.
Exterior
l Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabinet to remove dust.
TROUBLESHOOTING
Note : All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
When ignitor button is pressed in, there is no spark at ODS/pilot.
When ignitor button is pressed in, there is a spark at ODS/pilot but no ignition.
WARNING: Only a qualified service person should service and repair heater.
POSSIBLE CAUSE
1. Ignitor electrode is positioned wrong.
2. Ignitor electrode is broken.
3. Ignitor electrode is not connected to ignitor cable.
4. Ignitor cable pinched or wet.
5. Broken ignitor cable.
6. Bad piezo ignitor.
1. Gas supply turned off or equipment shutoff valve is closed.
2. Control knob not fully pressed in while pressing ignitor button.
3. Air in gas lines when installed.
4. ODS/pilot is clogged.
5. Gas regulator setting is not correct
6. Control knob not in PILOT position.
CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/pilot unit.
REMEDY
1. Replace ignitor.
2. Replace ignitor.
3. Reconnect ignitor cable.
4. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry.
5. Replace ignitor cable.
6. Replace piezo ignitor.
1. Turn on gas supply or open equipment shutoff valve.
2. Fully press in control knob while pressing ignitor button.
3. Continue holding down control knob. Repeat igniting operation
until air is removed.
4. Clean ODS/pilot (see Cleaning
and Maintenamce, Page 13) or
replace ODS/pilot assembly.
5. Replace gas regulator.
6. Turn control knob to PILOT position.
ODS/pilot lights but flame goes out when control knob is released.
1. Control knob is not fully pressed in.
2. Control knob is not pressed in long enough.
3. Equipment shutoff valve is not fully open.
4. Thermocouple connection is loose at control valve. 5 Pilot flame is not touching thermo­ couple, This allows thermocouple to cool, causing pilot flame to go out. This problem could be caused by one or both of the following: A) Low gas pressure. B) Dirty or partially clogged ODS/pilot.
6. Thermocouple damaged.
7. Control valve damaged.
14
1. Press in control knob fully.
2. After ODS/pilot lights, keep control
knob pressed in 30 seconds.
3. Fully open equipment shutoff valve.
4. Hand tighten until snug, then
tighten 1/4 turn more.
5. A) Contact local natural gas
company. B) Clean ODS/pilot (see Cleaning and Maintenance, Page 13) or replace ODS/pilot assembly.
6. Replace thermocouple.
7. Contact Dealer or PRO-COM.
TROUBLESHOOTING
Continued
OBSERVED PROBLEM
Burner(s)does not light after ODS/pilot is lit.
Delayed ignition of burner(s).
Burner backfiring during combustion.
Yellow flame during burner combustion.
POSSIBLE CAUSE
1. Burner orifice is clogged.
2. Burner orifice diameter is too small.
3. Inlet gas pressure is too low.
1. Manifold pressure is too low.
2. Burner orifice is clogged.
1. Burner orifice is clogged or damaged.
2. Burner is damaged.
3. Gas regulator is defective.
1. Not enough air.
2. Gas regulator defective.
3. Inlet gas pressure is too low .
REMEDY
1. Clean burner orifice (see Cleaning and Maintenance, Page 13) or replace burner orifice.
2. Replace burner orifice.
3. Contact local natural gas company.
1. Contact local natural gas company.
2. Clean burner (see Cleaning and Maintenance, Page 13) or replace burner orifice.
1. Clean burner orifice (see Cleaning and Maintenance, Page 13) or replace.
2. Contact Dealer or PRO-COM.
3. Replace gas regulator.
1. Check burner for dirt and debris. If found, clean burner(see Cleaning And Maintenance, Page 13).
2. Replace gas regulator.
3. Contact local natural gas company.
Slight smoke or odor during initial operation.
Heater produces a whistling noise when burner is lit.
Heater produces a clicking/ticking noise just after burner is lit or shut off.
White powder residue forming within burner box or on adjacent walls or furniture.
1. Residues from manufacturing processes .
1. Turning control knob to HI position when burner is cold.
2. Air in gas line.
3. Air passageways on heater are blocked.
4. Dirty or partially clogged burner orifice.
1. Metal is expanding while heating or contracting while cooling.
1. When heated the vapors from furniture polish, wax, carpet cleaners, etc. turn into white powder residue.
1. Problem will stop after a few hours of operation.
1. Turn control knob to LO position and let warm up for a minute.
2. Operate burner until air is removed from line. Have gas line checked by local natural gas company.
3. Observe minimum installation clearances (see Figure 4, page 7).
4. Clean burner (see Cleaning and Maintenance, Page 13) or replace burner orifice.
1. This is common with most heaters. if noise is excessive, contact qualified service person.
1. Turn heater off when using furniture polish, wax, carpet cleaner, or similar products.
15
TROUBLESHOOTING
Continued
WARNING: If you smell gas
l Shut off gas supply.
l Do not try to light any appliance.
l Do not touch any electrical switch; do not use any phone in your building.
l Immediately cal l your gas supplier from a neighbors phone. Follow the gas
suppliers instructions.
l If you cannot reach your gas supplier, call the fire department.
IMPORTANT : Operating heater where impurities in air exist may create odors. Clean-
ing supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or
textiles, etc, create fumes. These fumes may mix with combustion air and create odors.
OBSERVED PROBLEM
Heater produces unwanted odors.
Heater shuts off in use (ODS operates).
Gas odor exists even when control knob is in OFF position.
Gas odor during combustion.
POSSIBLE CAUSE
1. Heater is burning vapors from paint, hair spray, glues, etc. (See IMPORTANT statement above).
2. Gas leak. See Warning Statement at top of page.
1. Not enough fresh air is available.
2. Low line pressure.
3. ODS/pilot is partially clogged.
1. Gas leak. See Warning Statement at top of page.
2. Control valve is defective.
1. Foreign matter between control valve and burner.
2. Gas leak. See Warning Statement at top of page.
REMEDY
1. Ventilate room. Stop using odor
causing products while heater is running.
2. Locate and correct all leaks(see
Checking Gas Connections, Page 10).
1. Open window and/or door for
ventilation.
2. Contact local natural gas
company.
3. Clean ODS/pilot (see Cleaning
Page 12).
1. Locate and correct all leaks(see
Checking Gas Connections, Page 10).
2. Contact Dealer or PRO-COM
1. Take apart gas tubing and
remove foreign matter.
2. Locate and correct all leaks
(see Checking Gas Connections, Page 10).
Moisture/condensation noticed on windows.
1. Not enough combustion/ventilation air.
16
1. Refer to Air for Combustion and
Ventilation requirements, Page
4.
SPECIFICATIONS
MN300HGA
Btu(available)
Gas Type
Ignition
Pressure Regulator Setting
Inlet Gas Pressure (inches of water)
Maximum
Minimum
Dimensions, Inches (HxWxD)
Heater
Carton
Weight (pounds)
Heater
Shipping
Note: Dimensions listed are outer most points on the heater (includes control knobs and grill). * For purposes of input adjustment.
REPLACEMENT PARTS
Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY Contact authorized dealer from whom you purchased this product. If they are unable to supply original replacement part(s), call the number on the back of this manual. When contacting your dealer or PRO-COM, have ready:
l your name l your address l model and serial numbers of
your heater
l how heater was malfunctioning l type of gas used (propane/LP or
natural gas)
l purchase date l Warranty Card
Usually, we will ask you to return the defective part to the factory.
ACCESSORIES
Purchase these heater accessories from your local dealer. If they can not supply these accessories, contact PRO-COM for information. You can also write to the address listed on the back page of this manual.
15,000/30,000
Natural Only
Piezo 3" W.C.
10.5" 4"
23 1/2×26 5/8×8
26 1/2×28 1/2×91/4
26
31
MN300TGA
14,000/30,000
Natural Only
Piezo 3"W.C
10.5" 4"
23 1/2×26 5/8×8
26 1/2×28 1/2×91/4
26
31
For all models, provides better heat distribution. Makes heater or efficient. Complete installation and operating instructions included. Thermostatically-controlled PF06­YJLF-B, includes three settings ON/OFF/AUTO
FAN PF06-YJLF-B
EQUIPMENT SHUTOFF VALVE PARTS NOT UNDER WARRANTY
Contact authorized dealers of this product. If they cant supply original replacement part(s), contact PRO-COM.
For all models. Equipment shutoff
valve with 1/8" NPT tap. This part
is not currently available from
PRO-COM.
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact PRO-COM.The information is listed on the back of manual.
17
ILLUSTRATED PARTS
BREAKDOWN
MN300TGA
18
ODS/Pilot Assembly
PARTS LIST
MN300TGA
This list contains replaceable parts for your heater. When ordering replacement parts, follow the instructions listed under Replacement Parts on page17 of this manual.
KEY NO.
10 11 12 13 14 15 16 17 18 19 20 21 22 23
24 24_1 24_2
25
26
27
MN300TGA
PART NO.
1
MB10052
2
MB09052
3
MB11052
4
ML089-01
5
ML157-01
6
MB29001
7
ML069-02
8
SIT545-250
9
845-4.8x60Z ML111-01 ML083-03 ML073-01 NRV81FI-3 96-4Z ML079-01 MB40006 MB40022 MB40023 NBB30-000B1 ML101-01 ML091-02 ML103-01 ML104-01 ND1103x800x9 ND0803-8 ND0807 ML105-03 6170-5Z ML060-01
DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Steel Wind Shield Middle Panel Grill Guard Assembly Self Tapping Screw Thermostat Valve Assembly Screws Thermostat Valve Base/Bracket Ignitor Assembly Ignitor Line Pressure Regulator Washer Self Locking Screw Main Inlet Tube Assembly ODS Line Assembly Burner Inlet Tube Assembly Burner Burner connector Injector Left Burner Support Bracket Right Burner Support Bracket ODS/pilot Assembly Thermocouple Ignitor Electrode ODS Upper Deflector Nut Mounting Bracket
QTY
1 1 1 1 1 1
12
1 2 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2 1
MB28001 ML070-27 ML071-01 ML072-01 ML065-01
Assembly Hardware AGA/CSA Label Gas Instruction Decal Inside Warning Label Thermostat Sensing Bulb Clip
19
1 1 1 1 2
ILLUSTRATED PARTS
BREAKDOWN
MN300HGA
20
ODS/Pllot Assembly
PARTS LIST
MN300HGA
This list contains replaceable parts for your heater. When ordering replace­ment parts, follow the instructions listed under Replacement Parts on page17 of this manual.
KEY NO.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
28-1 28-2
29 30 31
MN300HGA
PART NO.
MB10053 MB09051 MB11052 ML089-01 MB29001 ML157-01 ML083-03 ML069-02 NV2020-14 ML073-01 MB16002 ML029-01 NRV81FI-3 96-4Z ML079-01 MB40016 MB40018 MB40019 MB40020 MB40021 ML096-01 MB40017 NBB30-000B1 ML101-01 ML091-01 ML103-01 ML104-01 ND1103x800x9 ND0803-8 ND0807 ML105-03 6170-5Z ML060-01
DESCRIPTION
Cabinet Assembly Lower Front Panel Assembly Reflector Unit Steel Wind Shield Grill Guard Assembly Middle Panel Ignitor Assembly Self Tapping Screw Control Valve Ignitor Line Control Knob Control Valve Fixed Nut Pressure Regulator Washer Self Locking Screw Main Inlet Tube Assembly ODS Line Assembly Lower Gas Outline Tube Assembly Medium Gas Outline Tube Assembly High Gas Outline Tube Assembly 4-Way Connector Burner Inlet Tube Assembly Burner Burner Connector Injector Left Burner Support Bracket Right Burner Support Bracket ODS/pilot Assembly Thermocouple Ignitor Electrode ODS Upper Deflector Nut Mounting Bracket
QIY
1 1 1 1 1 1 1
12
1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1
MB28001 ML160-25 ML071-01 ML072-01 ML065-01
Assembly Hardware AGA/CSA Label Gas Instruction Decal Inside Warning Label Thermostat Sensing Bulb Clip
21