![](/html/df/df89/df89209c1ffb0ff89fcf119b0a8a30288c056c19153d9e04a0250dd47c5aca1c/bg1.png)
LOW NOx MAXIM • PACKAGED GAS WATER HEATER
NICKELSHIELD® NICKEL-PLATED STORAGE TANK
119 GALLON TANK SERIES
MODEL NUMBER
GPH Recovery at 40° to 120° F 245
GPH Recovery at 40° to 140° F 195
Input Btu/h 199,000
Minimum gas inlet pressure – " W.C. 5.5
A Cold Inlet - NPT 2
B Hot Outlet - NPT 2
C Drain - NPT 1
D I - Beam Skids 3 X 34-1/2
E Overall Depth 47
F Overall Height 75
G Flue Outlet Diameter 5
H Gas Inlet - NPT 1/2
J Motor HP 120 V, 1Ø, 60 Hz. 1/6
Motor Amps 1.75
L Height to Outlet 65
M Height to Inlet 28
Approx. Shipping Weight - lbs 1070
Recoveries based on 82% thermal efficiency. ASHRAE 90.1 compliant.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see Form # PV6382.
34 1/2
20 N 119A-MXS
1
1. Control Enclosure
2. ASME Temperature &
Pressure Relief Valve
3. 3” NPT Handhole
41
G
B
2
F
L
C
J
23
M
D
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC PRESSURE: 9" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS
A
3
H
E
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE
FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE
VENT CONNECTION DIAMETER EXCLUSIVELY.
UNDER "FAN-ASSISTED".
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6434 01/06 (800) 784-8326 • www.pvi.com
Product is patented in the U.S., Canada, and Mexico.