LOW NOx TURBOPOWER® • PACKAGED WATER HEATER
®
NICKELSHIELD
NICKEL-PLATED STORAGE TANK
TANK SERIES 225 GALLONS VERTICAL
MODEL
NUMBER
1000 N 225A-TPL 1000 800 800,000 4.5 8TPL 800 MBtu/h 44 8 1 1/2 7 1540
c Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
d With standard gas train
* The information presented is for natural gas 0.6 S.G.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form #PV 6452.
Recovery gph
40° - 120°F 40° - 140°F
c
INPUT
Btu/h
Min. Inlet
Flow Gas
Pressure
" W.C. d
SCAQMD Energy
Model No.
Dimensions
(inches)
A B C HP Amps
Blower
Motor
Shipping
Weight
#
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL.
MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON
THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK
NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."
PV 6525 02/25/04 (800) 784-8326 • www.pvi.com
STANDARD ELECTRICAL REQUIREMENTS:
VOLTAGE: 120V, 1Ø, 60 HZ., 20 AMPS.
OTHER VOLTAGES REQUIRE AN EXTERNAL
STEPDOWN TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111