UNIT IDENTIFICATION.............................................................................................................................................................................................2
FAN COIL DESCRIPTION & TROUBLESHOOTING.....................................................................................................................................2 - 25
CARE & MAINTENANCE................................................................................................................................................................................25 - 28
FF1A/FF1V/FF1C SERVICE & TROUBLESHOOTING.................................................................................................................................28 - 32
FD3A SERVICE & TROUBLESHOOTING.....................................................................................................................................................32 - 35
FG3A SERVICE & TROUBLESHOOTING.....................................................................................................................................................35 - 36
CIRCUIT BOARD FUNCTION & TROUBLESHOOTING............................................................................................................................36 - 56
HK61GA001 and 003 PCB............................................................................................................................................................................45 - 56
ELECTRIC HEATER FUNCTION AND TROUBLESHOOTING..................................................................................................................56 - 58
COIL AND CONDENSATE PAN REMOVAL & REPLACEMENT.............................................................................................................59 - 63
FOR FV/FA/FB/FC/FK FAN COILS ..........................................................................................................................................................59 - 61
FOR FX4 AND FV4 FAN COILS................................................................................................................................................................61 - 63
Form: F-6SMCancels: F-5SM / SM03-5Printed in U.S.A.02-05Catalog No. 03FA-4A6
A98023
This symbol → indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, oruse can cause explosion, fire, electrical shock, or other conditions whichmay
cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance.
The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual installation
instructions packaged with the kits or accessories for detailed information.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read
these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and National Electrical Code
(NEC) for special installation requirements.
It is important to recognize safety information. This is the safety-alert symbol
. When you see this symbol on the unit or in instructions and
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the
most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or
death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
WARNING: UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution could result in personal injury or possible equipment damage.
Puron (R-410A) systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on
R-410A equipment. Ensure service equipment is rated for R-410A.
INTRODUCTION
The "F" series fan coil units are designed for flexibility in a variety of applications, meeting upflow, horizontal, or downflow requirements. Units
are available in 1-1/2 through 5 ton nominal cooling capacities. Factory-authorized, field-installed electric heater packages are available in 3
through 30 kilowatts.
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or possible equipment damage.
Before installing orservicing fan coil,always turn off all power to unit. There may be morethan 1 disconnectswitch. Turn offaccessory
heater power if applicable.
UNIT IDENTIFICATION
The 16 position numbering chart allows identification of all available fan coil units. (See Fig. 2.)
FAN COIL DESCRIPTION
AND TROUBLESHOOTING
FK4B
The FK4B has an integrated control and motor (ECM/ECM/ICM) and special circuit board.
Setting up desired airflow on the FK4B is obtained by the selections made on Easy Select™ circuit board. The motor delivers requested airflow
as defined by signals received from Easy Select Board and its internal programming. The major differenceis that the FK4Bmotor reacts to changes
in system static pressures to maintain constant airflow.
Unlike conventional fan coils where static pressure affects airflow, the FK4B is a constant airflow unit. The blower delivers requested airflow up
to about 0.7 in. of static pressure. The motor is pre-programmed and contains airflows for all modes of operation. Blower characteristics (airflow,
torque, and speed-vs-static pressure) are known from laboratory testing. If any 3 characteristics are known, the fourth is defined.
Requested airflow is known because of Easy Select board configuration and thermostat signals. Torque is known because it is directly related to
armature current which is measured by motor control. Speed is measured from its generated back EMF. This information is entered into an
expression which calculates torque from speed and airflow numbers. If calculation does not match stored blower characteristics, torque is adjusted
every 0.8 seconds until agreement is reached. The unit does not directly measure static pressure, but does react to a change in static to maintain
constant airflow.
PROCEDURE 1—INTEGRATED CONTROLS AND MOTOR - FK4B
The motor is similar to the ECM/ICM1 used in FK4A series units, but cannot be used as a replacement without some modification to FK4A unit.
The electronics of motor are built into rear of motor, deriving the name ECM/ICM. (See Fig. 3.)
An ECM/ECM/ICM is first fed high voltage AC power through the 5-pin connector. The AC power is then rectified to DC by a diode module.
After rectification, DC signal is electronically communicated and fed in sequential order to 3 stator windings. The frequency of communication
pulses determines motor speed. The rotor is permanently magnetized.
An ECM/ICM is powered with high voltage at all times. The motor will not run with high voltage alone. Low voltage must be applied to control
plug to run motor.
PROCEDURE 2—PCB LAYOUT AND DESCRIPTION - FK4B
NOTE: Layout of actual PCB is depicted in Fig. 4 and 5.
The control is a single PCB which interfaces a variable-speed motor with other system components.
Power for system is supplied from a 230-vac, 60-Hz line. Class 2 voltage (24 vac nom), used for thermostat connections, is derived from a
transformer located in close proximity to control. The primary and secondary of transformer are connected to control board. The 24-vac secondary
circuit includes a socket, soldered into circuit at SEC2, to receive a 5-amp automotive-type fuse.
—2—
Variations
A - Standard Unit
Minor Series
Coil Type
A - Standard
B - Modular
F - Single Piece
6th Position—Fan Coil
A - Original
Variations
A - Common Unit
⁄2 Ton)
1
Cooling Size
018 (1
024 (2 Ton)
001 (Multi Tons)
002 (Multi Tons)
Etc.
Electrical
A - 115-1-60
N - 208/230-1-60
S - 230-1-50
5th Position—Fan Coil
Heating Size (KW)
005
010
Etc.
10th, 11th, 12th Positions—Fan Coil
A98114
1234567 8 910 11 12131415 16
Airflow
1 - Upflow
2 - Downflow
3 - Horizontal
Type of Unit
F - Fan Coil
4 - Multipoise
5 - Upflow/Downflow
—3—
Major Series
A - Original
B - Second Series
Unit Specifics
A - RNC
B - Standard
C - Deluxe
D - Furred in, Cased
2nd Position—Fan Coil
E - Furred in, Uncased
F - Through the Wall
G - Commercial
H - Standard Electric Furnace
J - Standard Hot Water
K - ICM Motor, High Efficiency
V - ICM Motor, Puron R-410A
X - Standard, Puron R-410A
Fig. 2—Fan Coil 16-Position Numbering System
DO NOT REMOVE
OPTIONAL SAFETY GROUND
OPTIONAL
SAFETY
GROUND
DRAIN
HOLE
Fig. 3—FK4B, FK4C and FV4A motor Motor
12345
POWER CONNECTOR
9
10 11 12 13 14 15 16
12345678
CONTROL CONNECTOR
A94079
MOLEX 7-PIN
CONNECTOR (1)
3
⁄16-IN. MALE
FASTON
AMP–TYP
(21) PLCS
LOW VOLTAGE
TERMINAL BLOCK
HEATER
5 AMP
ST1
MAX
0-5
600
5
FS1
D10
HP-EFFHP-COMFORTAC
R1
HIMEDLO
ENH
CESS430023–01
D11
R3
CEBD430023–01
24VDC
JW3
AUX1
JW4
D3
AUX2
R2
D2 D9D4
P1
D8 D7 D5 D6
D1
EASY SELECT
AUX HEATRANGE
KW
0-30
CFM
VIO
BLU
ORN
BLK
ON
OFF090309000
GRY
GROUND
SCREW
REQUIRED
MOTOR
0-20
1200
1000
AC/HPSIZE
042036030024
TYPE
AC/HPCFMADJUST
AC/HP
TIME
RED
SEC2SEC1
XFORM
T1
M1
240
VAC
M2
240
T2
VAC
T3
24VAC
0-10
800
DELAY
MOTOR
P2
CES0130007–00
AMP 12-PIN MATE-N-LOCK
CONNECTOR (1)
Fig. 4—Easy Select Board (FK4B)
HUM1
HUM2
L
R
C
O
Y/ Y2
Y1
G
JW2
E
W2
W3
JW1
PRINTED
CIRCUIT
BOARD
W2-E JUMPER
3RD STAGE
W2-W3 JUMPER
2ND STAGE
1
⁄4-IN. MALE
FASTON
AMP–TYP
(9) PLCS
A94076
Connection to heater panel is made through 12-circuit connector P1. Connectionsto thermostat are madeat screw terminals. Linevoltage for motor
is made through 12-circuit connector P1. Eighteen quick-connect terminals comprise field select taps for motor.
—4—
Y/Y2
ST1
8
E
ST1
W2
ST1
W3
ST1
C
ST1
R
ST1
G
ST1
ST1
Y1
ST1
L
ST1
O
9
10
3
2
7
5
4
1
3
JW2
JW3
JW1
JW4
SEC1
SEC2PS1
R2
1K 2W
R1
1K 2W
D1
D2
D2
R3
1K 2W
AUX. HEAT
RANGE
AC/HP
SIZE
AC/HP
TYPE
AC/HP
CFM TRIM
AC/HP
DELAY
P1
123
56
4
789
10 11 12
D7
D4
D5
D6
P2
1
W/W1
2
G
3
C1
4
C2
5
R
6
Y/Y2
7
Y1
5 – 30
1200
QC1
QC5
AC
QC9
LOW
QC12
ON
90
OFF
QC15
D8
D9
0
QC2
QC6
QC16
5 – 20
1000
D10
D11
QC10
QC13
30
90
HIGH VOLTAGE
QC3
QC7
HP–COM.
MED
QC17
M1
T1
T2
M2
T3
AUX1
HUM1
AUX2
HUM2
5 – 10
RED
QC19
QC4
QC8
QC11
QC14
QC18
0 – 5
600
024030036042
HP–EFF.
HI
0
0
800
30
30
A94077
Fig. 5—Easy Select Board Circuitry (FK4B)
Fuse Data: 5-amp automotive-type ATC/ATO (tan)
32v
200 percent current opening time of 5 sec maximum
A. Electrical Connections
Eighteen 0.187-in quick-connect terminals are used to provide programming selections for operating modes of motor. The 5 selection modes are
listed below. For additional information, refer to Easy Select Configuration Taps section.
AUX Heat Range—(Violet Wire)
AC/HP Size—(Blue Wire)
Type—(Orange Wire)
AC/HP CFM Adjust—(Black Wire)
AC/HP Time Delay—(Grey Wire)
PROCEDURE 3—SEQUENCE OF OPERATION - FK4B
A. Continuous Fan Mode
The thermostat closes circuit R to G. The G signal is sent directly to motor.
B. Cooling Mode—Single Speed or 2-Speed High
Thermostat closes circuits R to Y/Y2 and R to O (heat pump only) for single speed. A circuit from R to Y1 is also required for 2-speed high. The
Y/Y2 signal is sent directly to motor.
C. Cooling Mode—Two-Speed Low
Thermostat closes circuits R to Y1 and R to O (heat pump only). The Y1 signal is sent directly to motor.
D. Electric Heat Heating Mode
Thermostat closes circuit R to W2, W3, or E.
The terminal block positions W2, W3, and E are tied together by jumpers JW1 and JW2. These jumpers are provided for field staging of electric
heater banks through use of thermostats. When staging is a requirement, installer cuts jumpers and wires in thermostats as is the common practice
with other fan coils. To ensure motor operation if any 1 of the inputs is energized, the 3 electric heater inputs are also interlocked through diodes
D1, D2, and D3 to motor W input.
E. Heat Pump Heating Mode—Single Speed or 2-Speed High
Thermostat closes circuit R to Y/Y2 for single speed. A circuit from R to Y1 is also required for 2-speed high. The Y/Y2 signal is sent directly
to motor.
F. Heat Pump Heating Mode—Two-Speed Low
Thermostat closes R to Y1. The Y1 signal is sent directly to motor.
0.250 X 0.032M2Motor line voltage connection (230 vac 60 Hz)
T3Transformer line voltage connection (230 vac 60 Hz)
T2Transformer tap storage terminal for 208-vac lead
SEC1Secondary connection from transformer (24 vac)
This connection is common to chassis ground through eyelet marked GROUND SCREW REQUIRED.
SEC2Secondary connection from transformer (24 vac)
HUM1Low voltage ground for humidifier option (24 vdc)
HUM2Low voltage output for humidifier option (24 vdc)
AUX1Low voltage ground for auxiliary option (24 vdc)
AUX2Low voltage output for auxiliary option (24 vdc)
0.187 X 0.032M1Common connection to blower motor
T1Common connection for transformer
REDCommon to R screw terminal and SEC2
Table 2—Connections on FK4B Screw Terminal Block
Screw
Description
Terminal
W2Connection for W2 signal from thermostat
W3Connection for W3 signal from outdoor thermostat
EConnection for E signal from thermostat
Y/Y2Connection for Y signal from thermostat
GConnection for G signal from thermostat
OConnection for O signal from thermostat
LThis connection is a field termination for use in connecting L lines of thermostat and outdoor unit to-
gether. There is no connection of this terminal with control circuity.
Y1Connection for low-speed compressor operation
RConnection for R signal to thermostat (24 vac)
CConnection for C terminal to thermostat (24 vac common)
G. Heat Pump Heating With Auxiliary Electric Heat
Thermostat closes circuits R to Y/Y2 and/or R to Y1 with R to W2, W3, or E (and R to O in the case of defrost).
See previously described modes for circuit paths.
In the event that electric heating is called for by thermostat while heat pump is also operating in either heating or defrost mode, electric heating
signal will appear at motor connector pin 1 as described previously. If necessary, the motor will modify its airflow output to provide an airflow
which is defined as safe for operation of electric heater.
H. CFM Select Configuration Taps
The CFM Select taps are used by installer to configure system. The motor is capable of discerning wave shapes on some of its inputs and uses
this capability to modify its operation to a pre-programmed table of airflows and can be modified in response to other inputs such as the need for
de-humidification.
I. Motor Control Power
The motor control power is supplied from R circuit through printed circuit runs to motor control connector pin 6, through motor control harness
to motor. The C side of low-voltage control power circuit is connected by printed circuit runs to motor connector pins 4 and 5, then through motor
control harness to motor.
J. Low-Voltage Circuit Fusing and Reference
The low-voltage circuit is fused by a board-mounted 5-amp automotive-type fuse placed in series with transformer SEC2 and R circuit. The C
circuit of transformeris referenced to chassis ground through a printed circuit run atSEC1 connected to metal standoff marked GROUND SCREW
REQUIRED.
NOTE: A ground screw must be in place or erratic motor operation can result.
K. Transformer, Motor, and Electric Heater
Power Connections
The high-voltage (230-vac) power input to board is provided through electric heater connector pins 7 and 9. The high voltage is then connected
through printed circuit runs to motor power connections M1 and M2 and transformer power connections T1 and T3. Transformer connection T2
is a dummy terminal used for unused primary power lead. The transformer secondary connections are made at SEC1 and SEC2 connectors.
—6—
Table 3—Connections and Connector (FK4B)
Type
Connection
Heater
Connection
Type
Pin No.Description
Connector
12-PinPin 1Common to E screw terminal
Pin 2Common to W2 screw terminal
Pin 3Common to C screw terminal, SEC1 terminal, and chassis ground
Pin 4Common to C screw terminal, SEC1 terminal, and chassis ground
Pin 5No connection
Pin 6Common to W3 screw terminal
Pin 7Common to M2 and T3 quick-connects, 230 vac input
Pin 8No connection
Pin 9Common to M1 and T1 quick-connects, 230 vac input
Pin 10 No connection
Pin 11 No connection
Pin 12 No connection
Motor7-Pin HeaderPin 1Diode OR output of E or W3 or W2 thermostat signals
Pin 2Thermostat G signal
Pin 3Common to C, SEC1, and chassis ground
Pin 4Common to C, SEC1, and chassis ground
Pin 5Common to R and SEC2 (via 5-amp fuse)
Pin 6Thermostat Y/Y2 signal
Pin 7Thermostat Y1 signal
PROCEDURE 4—EASY SELECT CONFIGURATION TAPS - FK4B
The Easy Select taps are used by installer to configure system. The motor uses selected taps to modify its operation to a pre-programmed table
of airflows. Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such as the need
for de-humidification.
(See Fig. 4.)
The FK4B Fan Coil must be configured to operate properly with system components with which it is installed. To successfully configure a basic
system (see information printed on circuit board located next to select pins), move the 5 select wires to pins which match components used.
A. Auxiliary Heat Range
The installer must select the auxiliary heat airflow approved for application with kw size heater installed. If no heater is installed, skip this step.
Each select pin is marked witha range of heaters for which airflow (also marked) is approved. For increasedcomfort select the narrowest kw range
matching the heater size, for example, 0-10 for a 10-kw heater. This airflow must be greater than the minimum CFM for electric heater application
with the size system installed for safe and continuous operation. Note that airflow marked is the airflow which will be supplied in emergency heat
mode and heating mode on air conditioners when electric heat is primary heating source. To ensure safe heater operation in heat pump heating
mode when electric heaters are energized, the motor will run the higher of heat pump efficiency airflow and electric heater airflow. The factory
selection is largest heater range approved. (See Fig. 4.)
B. AC/HP Size
The factory setting for air conditioner or heat pump size is largest unit meant for application with model of fan coil purchased. The installer needs
to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for size of unit installed in all operational
modes. (See Fig. 4.)
C. System Type
The type of system must be selected.
1. AC—air conditioner
2. HP-COMFORT—provides same airflow as air conditioner selection (approximately 375 CFM/ton)
3. HP-EFF—provides most efficient airflow for heating and cooling modes (approximately 410 CFM/ton heating and 375 CFM/ton cooling)
The factory setting is AC. (See Fig. 4.)
D. AC/HP CFM Adjust
Select low, medium, or high airflow. The factory selection is LO. The adjust selections HI/LO will regulate airflow supplied for all operational
modes, except non heat pump heating modes, +10 percent and -10 percent respectively. The adjust selection options are provided to adjust airflow
supplied to meet individual installation needs for such things as noise, comfort, and humidity removal. (See Fig. 4.)
E. AC/HP Time Delay
Select desired time delay profile. Four motor operation delay profiles are provided to customize and enhance system operation. (See Fig. 4.) The
selection options are:
NOTE: Selectable ON and OFF delay active in heat pump heating and cooling modes only. Auxiliary heat modes have a fixed delay profile: 0
seconds ON or 2 minutes OFF. This cannot be overridden.
—7—
1. The standard 90 sec off delay (factory setting).
2. No delay option used for servicing unit or when a thermostat is utilized to perform delay functions.
3. A 30 sec on/90 sec off delay profile used when it is desirable to allow system coils time to heat up/cool down prior to airflow. This profile
will minimize cold blow in heat pump operation and could enhance system efficiency.
4. ENH, enhanced selection provides a 30 sec on/180 sec off delay at half airflow, adding comfort and efficiency.
PROCEDURE 5—TROUBLESHOOTING CIRCUIT BOARD - FK4B
Use Fig. 5 and 6 and Tables 3, 4, 5, and 6 as guides in troubleshooting PCB unless otherwise noted.
A. If Fan Will Not Turn On From Thermostat:
IF THERE IS NO HIGH VOLTAGE TO PCB:
1. Check connection of 12-pin plug from heaters to receptacle on Easy Select board. This supplies power to PCB. Be sure plug is connected
properly.
2. Check sequencer number 1and plug wiring. Yellow wireshould be connected to pinnumber 9 of plug andto limit switch. Black wireshould
be connected to pin number 7 of plug and to sequencer number 1.
3. Check power leads L1 and L2. If these are not receiving power, system cannot function.
IF PCB HAS HIGH VOLTAGE APPLIED TO IT:
1. Check low-voltage transformer leads (red and brown). Be sure they are wired to correct locations. (See Fig. 14)
and 18.)
2. Check output voltage of transformer secondary side SEC2 and SEC1. Be sure transformer output is around 24 vac. If transformer output
is zero vac and transformer is receiving correct input voltage (208v or 240v), then transformer needs to be replaced with recommended
transformer. If transformer output is 24 vac, proceed to items 3 and 4.
3. Check low-voltage fuse shown in Fig. 4. If fuse is blown, replace it. The transformer cannot supply power to boardwith fuse blown orloose.
If fuse blows when unit has power applied to it, the system most likely has 1 of the following problems:
a. Check control circuit for a short or miswiring problem.
b. The maximum load on transformer is 40 VA. If load on transformer is excessive, the low-voltage 5-amp fuse will blow to protect
transformer. If load exceeds VA rating of transformer, a larger VA rated transformer needs to be installed. Check sequencers for
excessive current draw.
c. Check wiring of heaters. If a heater is miswired, fuse may blow. If a heater is miswired, correct miswiring.
4. Check T1, T2, and T3 connections on primary side of transformer. If they are not connected properly, low-voltage terminal board cannot
supply 24-v signal to energize fan motor. If transformer is receiving correct primary voltage but isnot putting out correct secondary voltage,
transformer needs to be replaced.
B. If Electric Heat Stages Will Not Turn On But Fan Will Turn On:
1. Check wiring of sequencers. Pay particular attention to high- and low-voltage wiring of sequencers.
2. Check plug wiring to make sure that it is wired correctly.
3. Check voltage to sequencer. Sequencer number 1 receives a 24-vac signal. If it is receiving correct voltage, check to see if sequencer is
closing. If sequencer is not closing but is receiving correct voltage, replace sequencer. If sequencer is closing, check high-voltage wiring
as discussed in items 1 and 2.
IF THERE ARE BLOWN DIODES:
If diodes are blown, it is probable that electric heater plug is miswired. Correct miswiring.
NOTE: Board will need to be replaced if diode is bad.
IF TRACES ARE OVERHEATED ON BACK OF PCB:
Usually whenever there isa trace blown on PCB,it means either there hasbeen a high-voltage short orhigh voltage has been appliedto low-voltage
circuit. This can be prevented by making sure PCB is wired correctly before PCB has power applied to it.
C. If PCB Fuse Keeps Blowing:
When low-voltage fuse blows, it means transformer would have blown if fuse had not been in circuit to protect it. The fuse usually blows when
there is a high current drawn on transformer, high voltage applied to low-voltage circuit, or a direct secondary short. When there is a high current
drawn on transformer, it is most likely because transformer has been shorted or system is trying to draw more VA than transformer rating allows.
When fuse blows because of high voltage, the system has mixed high- and low-voltage signals.
1. Check transformer and thermostat wiring. (See Fig. 4 and 6.) Be sure transformer is not shorting out because thermostat wires are miswired.
2. Check wiring of sequencers. (See Fig. 4 and 6.) Be sure low-voltage and high-voltage wiring are connected to proper sequencers.
3. Check VA draw on transformer. If VA draw is more than VA rating of transformer, fuse will blow. If this is the case, replace transformer
with one that has a higher VA rating and meets system specifications.
PROCEDURE 6—TROUBLESHOOTING FAN MOTOR - FK4B
A. If Motor Does Not Run:
1. With power turned off, check all plugs and receptacles on circuit board and at motor for any deformation that may cause a bad connection.
Be sure all plugs are placed fully seated.
—8—
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
BLOWER MOTOR
ROTATION
30KW 1PH SCHEMATIC DIAGRAM
HVTB
L1
YEL
YEL
CB/FU4
YEL
CB/FU2
FIELD POWER WIRING
FU6
YEL
YEL
YEL
YEL
YEL
YEL
BLU
GND
LS6
LS5
LS4
LS3
LS2
LS1
YEL
PLUG 1
DISCONNECT PER NEC
HTR6
BLK
1211
ORN
SEQ2
SEQ3
SEQ 3
BLK
109
BLK
8
SEQ 2
BLK
65
BLK
43
SEQ 1
BLK
21
BLU
BLK
SEQ1
BRN
GRY
BLK
VIO
BRN
YEL ORN GRN
HTR5
HTR4
HTR3
HTR2
HTR1
RED
SEE RATING PLATE
FOR VOLTS & HERTZ
BLK
BLKBLK
BLK
7
BLK
BLK
123456789101112
PLUG 2
24567
RED BRN VIO
(SEE NOTE 1)
13
FU5
CB/FU3
CB/FU1
BLK
BLK
BLK
NOT SUITABLE FOR USE ON SYSTEMS
NE CONVIENT PAS AUX INSTALLATIONS
SCHEMATIC DIAGRAM
FIELD POWER WIRING
L2
BLU
ORN
BLK
GRY
RED
BRN
RED
TRAN
BLK
COMMON
RED
BLU
BLK
(SEE NOTE 3)
YELBLK
9
VIO
A–C HP–COMFORT HP–EFF
LO
0/30 30/30 30/30 0/0
7
SEC2
M1
YEL
M2
BLU
RED
YEL
54321
PLUG 3
PLUG 4
SEE RATING PLATE
FOR VOLTS & HERTZ
(SEE NOTE 1)
COOLING CONTROL WIRING
COOLING CONTROL ONLY
AUX HEAT RANGE
AC/HP SIZE
TYPE
AC/HP CFM TRIM
MEDHI
AC/HP DELAY ON/OFF
1
RECP 2
SEC1
T1
3
6
9
12
2
5
8
11
1
4
7
10
RECP 1
T2
T3
GRN/YEL
YEL
BRN
RED
16
BLU
BLK
GRY
BLK
CAUTION:
EXCEEDING 150V TO GROUND
ATTENTION:
DE PLUS DE 150 V A LA TERRE
DISCONNECT PER NEC
GND
PLUG
7
F
L
R
C
O
Y1
G
E
W
2
W
3
AUX1 HUM1
AUX2 HUM2
24VAC
LVTB
JW2
JW1
OLRY
INDOOR THERMOSTAT
PCB
RECP 3
VIO
ORN
ORN
RED
VIO
192103114125136147158
BRN
ICM
RECP 4
Y
E
Y
1
Y
(SEE NOTE 2)
0
W
2
O
L
R
HPTB
EY
1Y0W2
NOTES:
1. Use copper wire only between disconnect switch and unit.
2. Connect (Y) to (Y), (C) to (C), etc. in pattern shown.
3. Transformer primary leads: BLUE 208V, RED 230V.
4. To be wired in accordandce with NEC and local codes.
5. If any of the original wire, as supplied, must be replaced, use the same or
6. Replace low voltage fuse with no greater than 5 amp fuse.
7. Fuse is wired in series between transformer SEC2 and low voltage "R" circuit.
8. 20KW heater uses one double pole LS on middle top element.
9. 18, 24 and 30KW heaters use double pole limit switches.
10. Largest heaters are shown, smaller heaters will have fewer elements and
components.
11. 1 phase heaters are shown wired for single supply circuit. Multiple
supply circuits may be wired directly to fuse/C.B.'S.
Fig. 6—Typical FK4B Wiring Diagram with 6-Element Heater
equivalent type wire.
—9—
MARKED TERMINAL
UNMARKED TERMINAL
FIELD POWER WIRING
PLUG AND RECEPTACLE
PCB BREAKOFF JUMPER
AUXILIARY
AUX
PRINTED CIRCUIT BOARD
PCB
HEAT PUMP TERM BRD
HPTB
LOW VOLT TERM BRD
LVTB
SEQUENCER
SEQ
HEATER
HTR
HIGH VOLTAGE TERMINAL BOX
HVTB
HUMIDIFIER
HUM
- LEGEND -
LS
LIMIT SWITCH
ICM
FAN MOTOR
TRAN
TRANSFORMER
GND
EQUIPMENT GROUND
FU
FUSE
RECP
RECEPTACLE
CB
CIRCUIT BREAKER
F
LOW VOLTAGE FUSE
320486 - 301 REV. C
A94078
Table 4—FK4B Motor Control Test Values
(With 16-pin connector at motor unplugged)
Terminals Jumpered Volt Meter on 16 PIN
Harness Plug
Volt Meter on 7-pin
Easy Select Board Plug
Voltage
+-+ -
R to W1 or W2Pin 2Pin 1 or 3Pin 1Pin 3 or 412vdc
R to Y1Pin 6Pin 1 or 3Pin 7Pin 3 or 424vac
R to Y/Y2Pin 14Pin 1 or 3Pin 6Pin 3 or 424vac
R to GPin 15Pin 1 or 3Pin 2Pin 3 or 424vac
2. Verify that there are approximately 230v at terminals M1 and M2. If not, determine if high voltage is entering board. It enters through black
and yellow wires at pins 7 and 9 in 12-pin plug.
3. Verify that there is a low-voltage control signal to motor.The motor receives its controlsignals through the 7-pin motor plug P2. The voltage
output of each pin in plug will be different for each mode of operation. Table 4 lists circuit board screw terminals that have 24 vac present
(powered by thermostat) and lists voltage that is present at each pin of 7-pin plug for each operating mode. Tests should be taken between
points listed and common (C screw terminal). If all values of any 1 of operating modes checks OK and motor fails to run, then motor is
defective and should be replaced.
B. If Motor Does Not Run Smoothly:
First verify that the cause is not an out of balance or damaged blower wheel. If it is not blower wheel, motor is defective and should be replaced.
C. If Motor Shaft Does Not Rotate Smoothly:
When manually turning shaft of ECM/ICM, the shaft does not rotate smoothly. The shaft has steps during rotation referred to as motor cogging.
The cogging is caused by permanent magnets passing each pole of motor. However, shaft should not require excessive force to turn. If shaft is
VERY difficult to turn, motor control or bearings have failed and motor must be replaced.
D. If Motor Does Not Stop Running
1. Check for good ground between motor ground lead and transformer common lead.
2. If motor continues to run, remove all thermostat wires. If motor stops, check thermostat wiring for short.
3. If motor continues to run, remove the 7-pin plug. If motor continues to run after 2 minutes, replace motor.
PROCEDURE 7—CONDENSED VERSION OF TROUBLESHOOTING FK4B MOTOR AND CONTROLS
This section provides a quick summary of howto troubleshoot the FK4B.If more information is needed, refer to appropriate sectionsof this service
manual.
+ MOTOR
- If motor is hard to turn manually, but turns freely, replace module.
- If motor does not run, check the components listed below according to their instructions.
- If motor runs in some operation modes and not in others, check for a good ground connection between motor ground lead and circuit board
screw marked "ground screw" and check the room thermostat and wiring harness according to instructions listed in Table 4.
- If motor does not stop running, remove the 7-pin plug from circuit board. If motor continues to run, replace motor. If motor stops running
after 2 minutes, it is either the circuit board or thermostat causing the problem. Test whether thermostat is at fault by disconnecting it from the
board.
+ CIRCUIT BOARD
- Check 5-amp fuse.
- Check for 230v between terminals M1 and M2.If no voltage ispresent, check power toboard. 230-v power enters the board through the black
and yellow lead in the 12-pin plug.
- Check for 24v between SEC1 and SEC2. If no voltage is present, check the transformer.
- Check for burn traces or burnt components. If burn spots are present, replace board.
+ ROOM THERMOSTAT
- Remove thermostat wires from the circuit board.
- Jumper screw terminals (1 at a time) R-G, R-Y/Y2, R-Y1, and R-W2. If motor runs in all cases, thermostat or thermostat wiring is bad. If
motor does not run, or runs in some cases but not in others, continue by checking the wiring harness.
+ WIRING HARNESS
- Shut off power to unit.
- Remove 5-pin plug from motor.
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or possible equipment damage.
Never remove 5-pin high voltage plug from the motor with the power on.
- Remove 16-pin plug from motor.
- Replace 5-pin plug and turn on power.
—10—
- Check for 24vbetween pin-1 and pin-12 on the 16-pin plug. (See Fig. 7.) If no voltage is present, replacewiring harness. If voltage is present,
16 15 14 13 1211 109
87654321
16-PIN PLUG
A94375
Fig. 7—Wiring Harness 16-Pin Plug
jumper screw terminal R-Y/Y2 on circuit board and check for 24v between pin 1 and pin 12 and pin 1 and pin 14 on 16-pin plug. (See Fig. 7.)
If voltage is present, replace harness.
- If 24v is present on both pins, the motor or module is bad. Replace motor.
PROCEDURE 8—ACCESSORIES (FK4B)
A. Electronic Air Cleaner (EAC)
Familiar 230-vac EAC control/power signal EAC1 and EAC2 is not available, because the motor blower motor used in the FK4B Fan Coil is
controlled by low-voltage signals. This signal is replaced by a 24-vdc signal which is provided at circuit board terminals AUX1 and AUX2. (See
Fig 16.)
This signal is present when either G or W is present and is active in all heating and cooling modes. Because 24-vdc relays may not be readily
available to installer, a kit exists, KFAIR0101ACR, containing a 24-vdc relay which mounts directly inside EAC cabinet. User-supplied 110 vac
is switched by relay to power air cleaner when G or W are present. (See Fig. 8)
MOUNT FLUSH WITH
THESE TWO EDGES
A93216
Fig. 8—Mounting KFAIR0101ACR Relay Kit
In heat pump applications, the G signal is present in both cooling and heating modes, permitting EAC to be controlled from G signal only. For
this application, a user-supplied 24-vac relay can be driven by G terminal eliminating need for relay kit.
B. FK4B De-Humidify Mode
NOTE: Humidistat must open on humidity rise.
Latent capacities for systems using the FK4B Fan Coil are better than average systems. If increased latent capacity is an application requirement,
the FK4B can be wired to provide this requirement by adjusting its airflow in response to standard humidistat input. Fig. 9 illustrates the wiring
connections to activate de-humidify mode. Carefully consult product airflow data for cooling and dehumidifying mode.
HUMIDISTAT
RED WIRE
FROM ICM2
MOTOR
HUMIDISTAT WIRING FOR
DE-HUMIDIFY MODE
TO PCB TERMINAL
MARKED 'RED'
A93215
Fig. 9—Humidistat Wiring for De-Humidify Mode
FV4B, FK4D, FK4C, FV4A, AND 40FKA
The FK4C fan coil was introduced several years before the FV4A and 40FKA models. All three units contain the motor and use the same control
board. The 40FKA was introduced as part of the Comfort Heat Pump system and is identical to the FK4C except it is factory supplied with a
Thermidistat Control. Both the 40FKA and FK4 R-22 units with a factory supplied R-22 TXV. Other than the pressure differences in the Puron
system, all three units are constant airflow machines and operate the same way. The FV4B and FK4D include the added benefits of low sweat/low
leak cabinet.
—11—
OPTIONAL SAFETY GROUND
DRAIN HOLE
12345
POWER CONNECTOR
9
10 11 12 13 14 15 16
12345678
OPTIONAL SAFETY GROUND
CONTROL
POWER
ENDSHIELD
DRAIN HOLE
DRAIN HOLE
CONTROL CONNECTOR
A98201
Fig. 10—FK4C, FV4A, and 40FKA motor/ECM2.3 Motor
Constant Air Flow
Unlike fan coils using induction motors where static pressure affects airflow, these fan coils are constant airflow units. The blower delivers
requested airflow regardless of static pressure. Consult fan coil Product Data for static pressure limits. The motor/ECM2 is pre-programmed and
contains airflow tables for all modes of operation. Blower characteristics (requested airflow, torque, and speed) are known from laboratory testing.
If any 2 characteristics are known, the third is defined.
Requested airflow is known from Easy Select board configuration and thermostat signals. Torque is known because it is directly related to stator
current which is measured by motor control. Speed is measured by counting back EMF pulses from stator windings. This information is entered
into an expression which calculates torque from speed and airflow numbers. If calculation does not match stored blower characteristics, torque is
adjusted until agreement is reached. This calculation and adjustment is performed every 0.8 sec while motor is in operation. There is no direct
measure of static pressure, but unit does react to a change in static to maintain constant airflow. A change in pressure will result in a change in
stator speed and torque. The motor will begin to adjust on the next sampling, calculate new desired speed and torque, and adjust as necessary.
PROCEDURE 1—INTEGRATED CONTROLS AND MOTOR ECM / /ECM2)
An motor/ECM2 is fed high voltage AC power through the 5-pin connector. (See Fig. 10.) The AC power is then internally rectified to DC by
a diode module. After rectification, DC signal is electronically communicated and fed in sequential order to 3 stator windings. The frequency of
these commutation pulses determines motor speed. The rotor is permanently magnetized.
An motor/ECM2 is powered with high voltage at all times. The motor will not run with high voltage alone. Low voltage must be applied to control
plug to run motor.
ECM/ICM 2 CONTROL POWER
The motor/ECM2 control power is supplied from R circuit through printed circuit runs to motor control connector pin 8, through motor control
harness to motor. The C side of low-voltage control power circuit is connected by printed circuit runs to motor connector pins 9, 10, and 11 then
through motor control harness to motor.
LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE
The low-voltage circuit is fused by a board-mounted 5-amp automotive-type fuse placed in series with transformer SEC2 and R circuit. The C
circuit of transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked.
NOTE: The PCB must be mounted with 2 screws and motor ground lead secured to blower housing or erratic motor operation can result.
TRANSFORMER, MOTOR, AND ELECTRIC HEATER POWER CONNECTION
Transformer high voltage supplied from electric heater package or high voltage leads through 12-pin heater connector plug/recp2. The
motor/ECM2 power connections are made at the transformer primary terminals. The transformer secondary connections are made at SEC1 and
SEC2 connectors.
COMFORT HEAT PUMP SYSTEM
In 1998, the ComfortHeat Pump System was introduced in whicha 40FK, FK4 or FV4fan coil can be installed. This introduced many new features
for enhanced comfort. To activate these modes, they must be configured into the indoor control. The Thermidistat Control and current zoning have
the capability of both of these modes.
To initiate these operating modes, the control drops out the G signal to reduce airflow for extra comfort in heating and maximum dehumidification
in cooling. This must be kept in mind while troubleshooting these fan coils. Be aware that a cooling or heating input without the G input energized
will result insignificantly lower airflow than may be expected. When verifying airflow in normal heating and cooling modes (including emergency
heat in newer motors), remember that G must be energized to achieve full airflow.
—12—
Table 5 — Motor & Modules Capable of Comfort Heat / SuperDehumidfy Modes
*These motors will not adjust airflow with G in electric heat modes.
The FK4 has some earlier series that were produced before the Comfort Heat Pump System was introduced. Some of the motors will not have the
programming that slows the fan down on a loss of the G signal. The following units are factory programmed for Super Comfort Heat and
SuperDehumidify Modes:
40FKA/B.........ALL
FV4A/B..........ALL
FK4C..........Series A through E (1995-1997)NONE
FK4C..........Series F reduces airflow in heat pump heating and cooling modes only (not in electric heating modes).
FK4C/D..........Series G reduces airflow in all modes
FK4A..........NONE with original motor. If upgraded to motor/ECM2 motor, it may have programming
FK4B..........NONE with original motor. Replacement motor or module may have programming.
IF an original motor or module has been replaced, it may have Super Comfort Heat and SuperDehumidify capability.
PROCEDURE 2—PCB LAYOUT AND DESCRIPTION (FK4, FV4, 40FK)
NOTE: Layout of actual PCB is depicted in Fig. 11 and 25.
The Easy Select Board is the interface between the ECM motor and other system components. The board offers choices of electric heater size,
outdoor unit size and type, comfort or efficiency settings, on and off delay profiles, and continuous fan speed. The installer should select the correct
size of components that are being installed in each installation. If no selections are made, the factory default settings are for the largest heater,
largest outdoor unit, AC system type, nominal airflow adjust, and 0/90 time delay.
NOTE: Outdoor unit model should have an ARI rating with the variable speed fan coil. Some outdoor unit models will not work properly with
this fan coil.
Power for system is supplied from a 230-vac, 60-Hz line. Class 2 voltage (24 vac nom.), used for thermostat connections, is derived from
transformer located in close proximity to PCB. The 24-vac secondary circuit includes 5-amp automotive-type fuse in SEC2 circuit.
Connection to heater panel is made through 12-pin connector PL-1. Connections to thermostat are made at screw terminals. Twenty-one pin
terminals comprise field select taps for motor.
Fuse Data: 5-amp automotive-type ATC/ATO (tan)
32v
200 percent current opening time of 5 sec maximum
A. Electrical Connections
Twenty-one 0.110-in pin terminals are used to provide programming selections for operating modes of motor/ECM2. The 6 selection modes are
listed below. For additional information, refer to Easy Select Configuration Taps section.
AUX Heat Range—(Violet Wire)
AC/HP Size—(Blue Wire) Type—(Orange Wire)
AC/HP CFM Adjust—(Black Wire)
AC/HP Time Delay—(Grey Wire)
Continuous Fan—(Yellow Wire)
PROCEDURE 3—SEQUENCE OF OPERATION (FK4, FV4, 40FK)
A. Continuous Fan Mode
The thermostat closes circuit R to G. The unit delivers the airflow selected for fan only operation.
B. Cooling Mode—Single Speed or 2-Speed High
Thermostat closes circuits R to G, R to Y/Y2 and R to O (heat pump only). A circuit R to Y1 is required for 2-speed high operation. Airflow
delivered the airflow selected by AC/HP SIZE selection and CFM ADJUST selection.
C. Cooling Mode—Two-Speed Low
Thermostat closes R to G and R to Y1 and R to O (heat pump only). Unit delivers 2-speed low airflow for AC/HP SIZE and CFM ADJUST
selected.
D. Cooling + Dehumidify Mode (Thermidistat or Comfort Zone II-B and Single-Speed Outdoor Unit Installed)
J1 jumper must be pulled from Easy Select Board. Control closes R to G, R to Y/Y2, and R to O (heat pump only) and open R to DH.
Dehumidification is active when 24vac is removed from DH terminal. Unit delivers 20% less airflow.
E. SuperDehumidify Mode
(Thermidisat or Comfort Zone II-B indoor control, Single-Speed Outdoor Unit)
This mode is only activated by the indoor control when COOL to DEHUMIDIFY and SUPERDEHUMIDIFY are configured at the control and
there is a call for dehumidfication without a call for cooling. The control closes R to Y/Y2, R to O (heat pump only) and opens R to DH and R
to G. This signals the fan coil to run at minimum airflow for maximum humidity removal. The control will cycle the equipment 10 minutes on
and 10 minutes off until satisfied.
—13—
®
SEC1
®
EASY SELECT
AUX/HEAT KW/CFM
0-30
0-20
1075
875
VIO
AC/HP SIZE
036030024018
BLU
SYSTEM TYPE
AC HP-COMFORT HP-EFF
ORN
BLK
WHT
YEL
AC/HP CFM ADJUST
NOMLOHI
ON/OFF DELAY
0
309000ENH
90
CONTINUOUS FAN
LOMEDHIYEL
SEC2
0-10
725
0-5
625
5 AMP.
MAX.
D4
D5D2
J1
5
F1
J2
R1
R2
D3
D1
AUX1 HUM1
AUX2
YYWWX
STI
HUM2
D
R
W
W
Y
Y/Y
G
O
C
H
1
2
1
2
AUX1
HUM1
AUX2
HUM2
GRY
PL1
HEATER/MOTOR
24VAC
1
GRY
CES0130035-00
A96430
Fig. 11—Easy Select Board
SYSTEM DIAGRAM
HEATER/MOTOR
987654321
1
/4"
1
/4"
1
/4"
1
/4"
1
/4"
DIODE
LOGIC
121110
SEC1 SEC2
1
/4"
/4"
1
D
R
W
W
Y
Y/Y
G
O
C
H
1
2
1
2
5 AMP
J1
J2
AUX HEAT
KW/CFM
AC/HP
SIZE
SYSTEM
TYPE
AC/HP CFM
ADJUST
ON/OFF
DELAY
CONTINUOUS
FAN
A96431
Fig. 12—Easy Select Board Schematic
F. Heat Pump Heating Mode — Single Speed or 2-Speed High
Thermostat closes R to Y/Y2 and R to G. A circuit R to Y1 is required for 2-speed high operation. The unit delivers airflow selected by AC/HP
SIZE selection and CFM ADJUST selection. Selected delay profile is active in this mode.
G. Heat Pump Heating Mode — 2-Speed Low
Thermostat closes R to G and R to Y1. Unit delivers 2-speed low airflow for AC/HP SIZE and CFM ADJUST selected. Selected delay profile
is active in this mode.
—14—
Table 6—Connections and Connector (FK4C)
Type
Connection
Heater
Connection
Type
Pin No.Description
Connector
12-PinPin 1Common to screw terminal G
Pin 2Common to screw terminal Y/Y2 through diode D3
Pin 3Common to Y1 through diode D2
Pin 4Common to W2 screw terminal
Pin 5Common to W2 screw terminal
Pin 6Common to screw terminal W1 screw terminal
Pin 7Common to W1 screw terminal
Pin 8R 24VAC
Pin 9Common to transformer C
Pin 10 Common to transformer C
Pin 11 Common to transformer C
Pin 12 Common to DH screw terminal
H. Non-Staged Auxiliary Heat with Heat Pump Heating Mode
Thermostat should already have closed R to G, R to Y2 for heat pump heating operation. With J2 jumper in place, energizing either W1 or W2
will produce the W2 airflow. This is the greater of heat pump heating and auxiliary heat airflow plus an additional 15%. The elected delay profile
is not active in this mode.
I. Staged Auxiliary Heat with Heat Pump Heating Mode
The auxiliary heat can be staged by removing the J2 jumper that ties W1 and W2 terminals together. Staging can be done by using outdoor
thermostats or by using the Intelligent Heat Staging option where the indoor control can be configured for 3-stage electric heat. The unit will
automatically adjust airflow when the different stages of heat are energized. The airflow delivered will depend on the heat pump size selected and
electric heat size selected. The greater of the two airflows will be delivered. The selected delay profile is not active in this mode.
J. Electric Heat without Heat Pump
Thermostat closes R to W andthermostat should be set up to energize G with W. This is due to the Super Comfort Heat programmingin the motor.
Energizing W without G will result in 25% lower airflow delivery. The selected delay profile is not active in this mode.
K. Super Comfort Heat Mode
This is a special heating mode only available on FK4, FV4, and 40FK fan coils combined with aThermidistat Control or Comfort Zone II-B. When
this option is selected, the indoor control will monitor the outdoor temperature. The control will drop the G signal to the fan coil when the outdoor
temperature is between 10° and 40° F. This triggers the motor to slow to approximately 213 CFM per ton. The heaters will stage as needed during
this mode and the motor will adjust airflow as required. Below 10° F., theW1 control output will automatically energize on a call for heat. The
motor/ECM2 power connections are made at the transformer primary terminals. The transformer secondary connections are made at SEC1 and
SEC2 connectors.
PROCEDURE 4—EASY SELECT CONFIGURATION TAPS
The Easy Select taps are used by installer to configure system. The motor/ECM2 uses selected taps to modify its operation to a pre-programmed
table of airflows. Airflows are based on system size and mode of operation and those airflows are modified in response to other inputs such as
the need for de-humidification. (See Fig. 11.)
The FK4, FV4, and 40FK Fan Coils must be configured to operate properly with system components with which it is installed. To successfully
configure a basic system (see information printed on circuit board located next to select pins), move the 6 select wires to pins which match
components used, along with homeowner preferences.
A. Auxiliary Heat Range
The installer must select the auxiliary heat airflow approved for application with kw size heater installed. Each select pin is marked with a range
of heaters for which airflow (also marked) is approved. For increased comfort select the narrowest kw range matching the heater size, for example,
0-10 for a 10-kw heater. This airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe
and continuous operation. Note that airflow marked is the airflow which will be supplied in emergency heat mode and heating mode on air
conditioners when electric heat is primary heating source. To ensure safe heater operation in heat pump heating mode when electric heaters are
energized, the motor/ECM2 willrun the higher of heat pump airflow and electricheater airflow. The factory default selection is largest heaterrange
approved. (See Fig. 11.)
B. AC/HP Size
The factory default setting for air conditioner or heat pump size is largest unit meant for application with model of fan coil purchased.The installer
needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for size of unit installed in all operational
modes. (See Fig. 11.)
C. System Type
The type of system must be selected.
1. AC—air conditioner (approx. 350 CFM/ton)
2. HP-COMFORT—provides lower airflow than air conditioner selection (approximately 315 CFM/ton) in heating mode. In cooling mode
supplies 350 CFM/ton.
—15—
Table 7—Typical Operating Modes
Operating
Terminals Energized
Mode
Heat Pump Only HeatingR, Y/Y2, G, DH
Heat Pump Only Heating + Super Comfort Heat Mode R, Y/Y2, DH
CoolingR, Y/Y2, G, DH, O
Cooling + DehumidificationR, Y/Y2, G, 0
Cooling + SuperdehumidifyR, Y/Y2, O
3. HP-EFF—provides same airflow for heat pump heating and cooling modes (approximately 350 CFM/ton).
The factory setting is AC. (See Fig. 11.)
D. AC/HP CFM Adjust
Select low, nominal, or high airflow. The factory selection is NOM. The adjust selections HI/LO will regulate airflow supplied for cooling and
heat pump heating modes only, +15 percent and -10 percent respectively. The adjust selection options are provided to adjust airflow supplied to
meet individual installation needs for such things as noise, comfort, and humidity removal. (See Fig. 11.)
E. ON/OFF Delay
NOTE: ON/OFF Delay is active only in cooling and heat pump only heating modes. In auxiliary heat mode or emergency heat mode, the ON
delay is 0 seconds and the OFF delay is fixed and cannot be overridden.
Select desired time delay profile. Four motor operation delay profiles are provided to customize and enhance system operation. (See Fig. 11.) The
selection options are:
1. The standard 90 sec off delay (factory setting 0/90).
2. No delay option used for servicing unit or when a thermostat is utilized to perform delay functions (0/0).
3. A 30 sec on/90 sec off delay profile used when it is desirable to allow system coils time to heat up/cool down prior to airflow. This profile
will minimize cold blow in heat pump operation and could enhance system efficiency (30/90).
4. ENH, enhanced selection provides a 30 sec on/150 sec at 70 percent airflow and no off delay.
F. Continuous Fan
Select desired Continuous fan profile LO, MED, or HI. Airflow are provided to customize and enhance the continuous fan functions. (See Fig.
11.) The possible selections are:
1. LO—provides 50% of Y/Y2 Cool airflow.
2. MED—provides 65% of Y/Y2 Cool airflow (71% on 006 model).
3. HI—provides 100% of Y/Y2 Cool airflow.
The factory setting is LO.
NOTE: If applied to two-speed unit, do not select continuous fan as HI since low speed cooling will also run at HIGH airflow and insufficient
dehumidification may result.
G. Easy Select Board Jumpers
J1 - This jumper must be pulled to activate dehumidification mode. The jumper connects R to DH. With the jumper in, the DH terminal is always
energized. With the jumper pulled, the DH terminal is de-energized. A control such as the Thermidistat must be used to supply the 24-volt signal
when there is no call for dehumidification, and turn off the 24 volts when there is a call for dehumidfication.
J2 - This jumper activates heat staging. The jumper connects the W1 and W2 terminals together. If either is energized, W2 airflow is delivered.
With the jumper pulled, there are separate airflows for W1 and W2.
H. Airflow Delivery
These units deliver airflow depending on the system size selections and operating mode. The thermostat energizes a combination of terminals on
the Easy Select Board which tells the motor what CFM to deliver. The following are typical operating modes and the terminals that should be
energized on the Easy Select Board.
NOTE: The DH terminal on the Easy Select Board is for dehumidification. It is de-energized on a call for dehumidification.
I. Variable Speed Motor Logic Sequence:
The ECM motors in these fan coils are programmed to deliver a variety of airflows. The motor goes through:
COOLING
The nominal cooling airflow for these fan coils is 350 CFM per ton. Selecting the HI adjust tap increases the airflow to 400 CFM per ton. The
LO tap decreases airflow to 315 CFM per ton. The low adjustment is only active during normal cooling mode. Removing the signal from the DH
terminal reduces the airflow to 80% of cooling airflow. Removing the G signal for Superdehumidify reduces the airflow to 50% of cooling.
HEATING
The base heat pumponly heating airflow is determinedby the SYSTEM TYPE selectionon the Easy Select Board. If HP-EFFICIENCY is selected,
the airflow is the same as Cooling. IF HP-COMFORT is selected, the airflow is 315 CFM per ton. The airflow will adjust up if necessary when
auxiliary heating is required. When both theY/Y2 and W1 orW2 terminals are energized,the motor will run the higher of the heat pump or electric
heat airflows. During Super Comfort Heat mode, the indoor control removes the G signal from the board. This slows the motor to 75% of heat
pump airflow. If the CFM adjust is set to LO, it will deliver 67.5% of heat pump airflow during Super Comfort Heat mode.
—16—
PROCEDURE 5—TROUBLESHOOTING
A. Troubleshooting Easy Select Board (FK4, FV4, 40FK)
IF TRACES ARE OVERHEATED ON BACK OF PCB:
Usually whenever there is a trace broken on PCB, it means either there has been a high-voltage short or high voltage has been applied to
low-voltage circuit. This can be prevented by making sure PCB is wired correctly before fan coil has power applied to it.
If PCB Fuse Keeps Blowing:
When low-voltage fuse blows, it means transformer would have blown if fuse had not been in circuit to protect it. The fuse usually blows when
there is a high current drawn on transformer, high voltage applied to low-voltage circuit, or a direct secondary short. When there is a high current
drawn on transformer, it is most likely because transformer has been shorted or system is trying to draw more vac than transformer rating allows.
When fuse blows because of high voltage, the system has mixed high- and low-voltage signals.
1. Check transformer and thermostat wiring. (See Fig. 11 and 13.) Be sure transformer is not shorting out because thermostat wires are
miswired.
2. Check wiring of relays. (See Fig. 11 and 13.) Be sure low-voltage and high-voltage wiring are connected to proper sequencers.
3. Check VA draw on transformer. If VA draw is more than VA rating of transformer, fuse will blow. If this is the case, replace transformer
with one that has a higher VA rating.
B. Troubleshooting Common Problems
Airflow Too Low:
Y1 instead of Y/Y2 on single-speed air conditioner or heat pump application. Y1 input is only for 2-speed applications. Using this terminal will
deliver about 60% of full cooling airflow.
Wrong Easy Select Board selection. Selecting an outdoor unit or electric heater smaller than actually installed will result in low airflow for the
application.
G not energized with call for cooling or heating. This triggers Super Comfort Heat or SuperDehumidify mode which delivers 50% of cooling
airflow.
J1 jumper pulled with no Thermidistat or dehumidistat installed. The J1 jumper ties the DH terminal to R and is installed at the factory. When
pulled, a Thermidistat or dehumidistat supplies a 24-volt signal to DH when there is no call for dehumidification (reverse logic). When there is
no signal on DH, the motor reduces airflow to 80% for better dehumidification.
Airflow Too High:
Wrong Easy Select Board selection. Fan coil is factory set for the largest outdoor unit and largest electric heater. Select sizes that are actually
installed.
Continuous fan set too high for 2-speed applications. Set to MED or LO.
Motor Will Not Stop:
Allow time for off delay to time out. In units built before serial number 0101A, any W call will have a 2 minute off delay independent of delay
selection. This is programmed into the motor and cannot be overridden.
In units built after 0101A, the off delay on any W call is 1 minute and cannot be overridden.
Some power stealing thermostats could bleed enough voltage to cause motor to run slowly when there is no heating or cooling call. Disconnect
thermostat wires and wait 2 minutes to see if motor stops. If it stops, replace thermostat, or install resistor per thermostat installation instructions.
Motor Will Not Start:
See following section, ″Troubleshooting motor/ECM2 Motor and Controls″
C. Troubleshooting motor/ECM2 Motor and Controls
CAUTION: ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
High voltage is always present at motor. Disconnect power to unit before removing or replacing connectors or servicing
motor. Wait at least 5 minutes after disconnecting power before opening motor.
The ECM/ICM motor used with this product contains two parts: the control module and the motor winding section. Do not assume the motor or
module is defective if it will not start. Go through the steps described below before replacing control module, Easy Select Board or entire motor.
The control module is available as a replacement part.
D. If Motor Turns Slowly:
1. It is normal operation to run noticeably slower if G terminal is not energized in cooling or heat pump heating modes.
2. Attach blower access panel. Motor may appear to run slowly if access panel is removed.
E. If Motor Does Not Run:
Turn power off, wait 5 minutes and check the following:
1. With power turned off, check 5 amp fuse on Easy Select Board
2. Check all plugs and receptacles for any deformation or corrosion that could cause bad connections. Be sure plugs are fully seated.
CAUTION: ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
DO NOT remove or apply 5-pin plug on motor with power on. Arcing could occur which can damage control module.
—17—
THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING
BLOWER MO TOR
ROTATI ON
20KW 1PH SCHEMA TIC DIAGRAM
FIELD POWER WIRINGDISCONNECT PER NEC
L3
L1
FU1
YEL
BRN
VIO
RED
PLUG 1
L1
CB2
CB1
YEL
YEL
YEL
YEL
YEL
Com
G
ORN
B
RED
V
W
BLK
YE
GRN
ORN
GRY
VIO
RED
WHT
YEL
GRN
PLUG 4
BLU
TRAN
208V
Y
R
RN
O
I
BLK
T
H
L
9
1
2
3
11 10
4
12
5
13
6
14
7
15
8
16
YEL
9
9
YEL
12
11
10
9
8
7
6
5
4
3
2
1
SEE RATING PLATE
FOR VOLTS & HERTZ
L3
230V
5 4 3 2 1
VIO
WHT
BLK
GND
INTERNAL PROTECTION MAY
BE EITHER FUSES OR CIRCUIT
BREAKERS
HTR3
LS3
HTR2
LS2
HTR1
LS1
HTR4
LS4
BLK
7
11
11
7
RED
BRN
BLK
VIO
BLU
ORN
BLK
YEL
WHT
PLUG 3
GRN/YEL
GND
BRN
ORN
BLU
BLK
SEE NOTE #1
CB2
RELAY 3
BLK
4
2
RELAY 2
BLK
4
2
RELAY 2
BLU
VIO
BLU
ORN
BLK
WHT
YEL
KW
CFM
PL1
BLK
BLK
6
8
RELAY 1
2
4
BLK
SEC2SEC1
AUX HEAT KW/CFM
AC/HP SIZE
SYSTEM TYPE
ACHP-COMFORT HP-EFF
AC/HP CFM ADJUST
NOM
ON/OFF DELAY
0
30
90
90
CONTINUOUS FAN
LOMEDHIYEL
HEATER / MOTOR
L4
LO
SEE INSTRUCTION FOR INSTALLATION
L2
CB1
BLK
BLK
RELAY 1
22 VDC COIL
REC
VIO
ORN
23
2
3
PCB
0
0
RECP 3
ICM
RECP 4
L4
L2
FU2
FU4
BLK
BLK
RED
GRY
16
1
6
F1
HI
HI
1
GRY
LABEL (2)
RELAY 2
22 VDC COIL
T D R
RELAY 3
22 VDC COIL
R E C
BRN
FU3
AUX1 HUM1
HUM2
AUX 2
24 VAC
GRY
NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING
150V TO GROUND
NE CONVIENT PAS AUX INSTALLATIONS DE PLUS DE 150
V A LA TERRE
CAUTION:
ATTENTION:
LEGEND
LS
COM
COMMON
F1
LOW VOLTAGE FUSE
ICM
FAN MOTOR
FIELD POWER WIRING
FU
LINE FUSE
GND
EQUIPM EN T GR O U ND
HVTB
HIGH VOLTAGE TERM BLOCK
HTR
HEATER
REC
RECTIFIER
LIMIT SWITCH
MARKED TERMINAL
PLUG AND RECEPT A CLE
PCB
PRINTED CIRCUIT BOARD
TRAN
TRANSFORMER
RECP
RECEPT ACLE
CB
CIRCUIT BREAKER
R
RELAY
TDR
TIME DELAY RECTIFIER
FIELD POWER W IRING
COOLING CONTROL ONLY
FIELD
POWER
L1L2
WIRING
YEL
9
208/240VA C24VA C
BRN
BRN
D
R
W
W
Y
Y/Y
G
O
C
PLUG 2
4
4
RECP 2
H
1
2
1
2
9
HTR1
LS1
60A 60A
OUTDOOR UNITINDOOR THE RMOSTAT
RELAY 1
6
8
1
REC
RELAY 2
6
8
1
TDR
RELAY 3
6
8
1
REC
NOTES:
1. USE COPPER WIRE (75*C MIN) ONLY BETWEEN DISCONNECT
SWITCH AND UNIT .
2. TO BE WIRED IN ACCORDANCE WITH NEC AND LOCAL CODES.
3. TRANSFORMER PRIMARY LEADS, BLUE 208V, RED 230V.
4. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED,
USE THE SAME OR EQUIVALENT TYPE WIRE.
5. REPLACE LOW VOLTAGE FUSE WITH NO GREATER THAN 5 AMP FUSE.
6. DUAL CIRCUIT WIRING SHOWN.
7. USE 60 AMP CLASS K FUSES ONLY, FOR REPLACEMENT.
8. CONNECT R TO R, G TO G, ETC., SEE OUTDOOR INSTRUCTION FOR
DET AILS.
L4 L3
CB1
2
4
2
4
2
4
11
11 7
HTR3
0
0
0
BLK
7
3
LS
4
&
HTR4
L2
CB2
60A 60A
L1
SYSTEM TRANSFORMER: 40.0VA
FAN COIL/HEATER: 8.2VA
REMAINING V A AVAILABLE: 31.8VA
23
23
COMPONENT ARRANGEM ENT
HTR2
RED
24 V
R3
BRN
FU4
FU2
FU1
FU3
PCB
R1
PL1
GND
LS2
R2
L4
L2
L1
L3
SEC2SEC1
HEATER / MOTOR
24VAC
F1
ICM
PLUG 2
4
RECP 2
4
COM
TRAN
208 V
230 V
D
H
R
W
1
W
2
Y
1
Y/Y
2
G
O
C
16
16
325653-101 REV . B
Fig. 13—FK4C, FV4A, and 40FKA Wiring Diagram
with 20kw heater after heater serial # 1900A56372
—18—
A00178
Turn power back on and check the following:
3. Check for 24vac on SEC1 and SEC2. If no voltage is present, check transformer.
4. Verify that approximately 230vac is present at motor.
5. Verify low voltage control signals to motor according to procedure below.
Use following procedure to check low voltage signals:
The ECM motor in these fan coils receive low voltage signals from the Easy Select Board through the wiring harness assembly. The combination
of pins energized at the motor determines the speed the motor will run. The procedure below isolates the fan coil from all external devices such
as a thermostat, condensing unit, humidifier or electronic air cleaner. There is also a specific troubleshooting example to demonstrate the process.
Table 7 provides information needed to verify that the correct voltages are present at the motor and the Easy Select Board.
THERMOSTAT:
1. Remove all thermostat and accessory wires from Easy Select Board.
2. On Easy Select Board, jumper screw terminals (1 at a time): R-G, R-Y/Y2, R-Y1, R-W1, R-W2. If motor runs in all cases, check thermostat
outputs. Thermostat wires may be broken, or thermostat may be miswired, configured incorrectly, or defective. If the motor does not run,
or runs in some cases, but not others, continue this procedure to check wiring harness and circuit board.
WIRING HARNESS:
1. Remove 16-pin plug from motor.
2. Check for appropriate voltages on 16-pin connector with screw terminals jumpered. (See Table 6.)
3. If signals check correctly, and motor does not run, inspect wiring harness for loose pins or damaged plastic that could cause poor
connections.
4. If connections are good, either control module or motor is defective.
5. If proper signals are not present, check circuit board using procedure below:
12-PIN PLUG (PL-1) ON EASY SELECT BOARD:
1. Completely disconnect wire harness from Easy Select Board.
2. Jumper the screw terminals one at a time; R-G, R-Y/Y2, R-Y1, R-W1, R-W2 and check for appropriate voltages on the Easy Select Board
pins. If proper signals are not present, replace Easy Select Board. If proper signals are present at the pins and not at 16-pin connector to
the motor, the wiring harness is defective.
TROUBLESHOOTING EXAMPLE:
Motor is not running on a call for heat pump heating after jumpering the Easy Select Board screw terminals as described in Thermostat section
above:
With all thermostat wires removed from Easy Select Board, place a jumper wire between R and Y/Y2 low-voltage screw terminals on the Easy
Select Board
1. Check Table 8 for pin number on 16-pin connector associated with the Y/Y2 signal. The correct pin is #14. The far right column of Table
8 shows that (-) 12vdc should be present between pin #14 and pin #1 (common) on the 16-pin connector.
2. Set meter to readDC voltage. Place meter leads between pins #1 (common) and #14 and check for(-) 12vdc. If signal ispresent, the problem
is in the module or motor. If signal is not present, the problem is either in wiring harness or Easy Select Board.
These steps can be repeated for other modes of operation.
To check Easy Select Board:
1. Leave jumper wire in place between R and Y/Y2.
2. Check Table 8 under ″Volt Meter on Easy Select Board Plug″ column and row for pin #14 on motor plug to see pin # on Easy Select Board
that should have voltage. The correct pin is #2. The column on far right will show voltage that should be present between pin #2 and pin
#9 (common).
3. Place meter leads between pins #2 and #9 on Easy Select Board and check for (-) 12vdc.
4. If voltage is present, the wiring harness is bad. If not, the Easy Select Board is bad.
Verify Motor Winding Section:
Before proceeding with module replacement, check the following to ensure motor winding section is functional. With control module removed
and unplugged from winding section:
1. The resistance between any 2 motor leads should be similar.
2. The resistance between any motor lead and the unpainted motor end plate should be greater than 100K ohms.
If motor winding fails one of these tests, it is defective and must be replaced.
F. Accessories
AUXILIARY TERMINALS
The AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal, and provide a 24-vac signal whenever the G terminal
is energized (See Fig. 5 and Fig. 6). During Superdehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If
the installation includes theuse of this operating mode, do not use theseterminals to control accessories. SeeElectronic Air Cleaner and Humidifier
sections for further information.
—19—
Table 8—FK4C Motor Control Test Values
(With 16-pin connector at motor unplugged)
Terminals Jumpered Volt Meter on 16 PIN
Harness Plug
Volt Meter on 12-pin
Easy Select Board Plug
Voltage
+-+ R to W1Pin 2Pin 1Pin 7Pin 924vac
R to W2Pin 13Pin 1Pin 4Pin 924vac
R to Y1Pin 6Pin 1Pin 3Pin 9(-)12vdc
R to Y/Y2Pin 14Pin 1Pin 2Pin 9(-)12vdc
R to G (LO)Pin 15Pin 1Pin 3Pin 9Ovac
R to G (MED)Pin 6Pin 1Pin 3Pin 9(-)12vdc
R to G (HI)Pin 14Pin 1Pin 2Pin 9(-)12vdc
FAN COIL
AUX1
AUX2
(C)
RED
(G)
RED
24 VAC RELAY
230 VAC OR
115 VAC BRANCH CKT
GND HOT NEUT
BLK
GRN
BLK
NO
COM
WHT
WHT
TO EAC
BLK
A98625
Fig. 14—KFAIR0201ACR Relay Kit
Wiring Schematic
ELECTRONIC AIR CLEANER CONNECTIONS
The AUX1 and AUX2 terminals are not always energized during blower operation, as described above. When using an electronic air cleaner with
the FV4 fan coil, use Airflow Sensor . The airflow sensor turns on electronic air cleaner when the fan coil blower is operating.
HUMIDIFIER / HUMIDISTAT CONNECTIONS
Easy Select Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard
humidistat. These terminals are energized with 24vac when G thermostat signal is present. Alternately, the 24-vac signal may be sourced from the
W and C terminal block connections when electric heaters are used as primary heating source. When using a Thermidistat™ Control, Zone Perfect
Plus, or Comfort Zone II, the 24-vac signal may be source directly from the Thermidistat HUM terminal.
G. FK4, FV4, and 40FK Dehumidify Mode
NOTE: Humidistat must open on humidity rise.
Latent capacities for systems using the FK4, FV4, and 40FK fan coils are better than average systems. If increased latent capacity is an application
requirement, the field wiring terminal block provides connection terminals for use of a standard humidistat. The FK4, FV4, and 40FK fan coils
will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode
airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts.
When the contacts close, airflow will return to 100 percent of the selected cooling airflow. To activate this mode, remove jumper J1 and wire in
a standard humidistat. (See Fig. 15.) Carefully consult product airflow data for cooling and dehumidification modes.
FE4
Model FE4A fan coil is designed to be installed with a communicating user interface. The FE4A fan coil will provide airflow at a rate commanded
by the User Interface.The nominal airflow/ton rate is350 CFM/ton. The User Interfacewill modify the commanded airflowunder certain operating
modes. Refer to the User Interface literature for further system control details. This fan coil will not respond to commands from a common
thermostat except under certain emergency situations explained in this document.
PROCEDURE 1—ELECTRONICALLY COMPUTED MOTOR (ECM2.5)
An ECM2.5 is fed high voltage AC power through the 5-pin connector. The AC power is then internally rectified to DC by a diode module. After
rectification, DC signal is electronically communicated and fed in sequential order to 3 stator windings. The frequency of these communication
pulses determines motor speed. The rotor is permanently magnetized.
—20—
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.