PH-3.8L-HW
High Temperature Condensate Pump
Installation Instructions
Pump House
Glaisdale Drive East
Nottingham
NG8 4LY
Tel: 0115 900 5858
sales@pumph.co.uk
www.pumph.co.uk
![](/html/bf/bf75/bf75fd6f853ea54cdf6db0c1d4c7f6f04dcd05a013cdc7b29cd2eef4d247c75d/bg2.png)
PH-3.8L-HW Installation Instructions
SPECIFICATION PH-3.8 L-HW*
Model PH-3.8L-HW
Max Flow 312 lph
Max Head 8m
Tank Capacity 3.8 litres
Volts 240 V / 0.75 A
Hz 50 Hz
Discharge Size 3/8"
High-level Alarm Volt Free
Height 249 mm
Inlet Height 115 mm
Length 325 mm
Width 160 mm
Cable Length 1.8 m
*Suitable for boilers up to 300kW (when used for boiler condensate only)
INSTALLATION
1. This condensate pump is designed for pumping away condensate from condensing boilers, PRV discharge
and high temperature water up to 100˚c. The pump is controlled by a float / switch mechanism which
turns the pump on to discharge the condensate when approximately 57mm of condensate collects in the
tank. The pump switches off automatically when the tank drains to approximately 19mm, giving a drink
cycle of 1.5 litre.
2. This pump is carefully packaged, inspected and tested to ensure safe operation and delivery. When you
receive the pump, examine it carefully to determine that there are no broken or damaged parts that may
have occurred during shipment. If damaged has occurred, please contact your supplier. They will assist
you in replacement or repair, if required.
3. Read the instructions carefully before attempting to install, operate or service the pump. Know the pump
application, limitations and potential hazards. Protect yourself and others by observing all safety information.
Failure to comply with instructions could result in personal injury and/or property damage! Please retain
these instructions for fututre reference. Installation and connections are to be made by a qualified person.
4. If installed for combined boiler condensate & PRV discharge, this pump is only suitable for boilers up to 42kW.
SAFETY
1. Do not use to pump flammable or explosive fluids such as petrol, fuel oil, kerosene, etc. Do not use in
explosive atmospheres. This pump should be used with liquids compatible with the pump component
materials.
2. Do not handle the pump with wet hands or when standing on a wet or damp surface, or in water.
To reduce the risk of electrical shock, be certain that the electrical supply is connected to a
permanent EARTH.
3. For installations where property damage and/or personal injury might result from an inoperative or leaking
pump due to power cuts, discharge line blockage, or any other reason, a backup system and/or alarm
should be used.
4. Support the pump and piping when assembling and when installed. Failure to do so may cause piping to
break, pump to fail, motor bearing failures, etc
For further installation advice please call the technical support helpline on 0115 900 5858.