Pulsar Measurement Zenith 140 UL User guide

Page 1
Zenith 140 UL
Instruction Manual
Page 2
2
Page 3
3
Zenith 140 UL (SIXTH EDITION REV 1)
April 2021 Part Number M-140-0-006-1U
COPYRIGHT
© Pulsar Measurement, 2005 -21. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form without the written permission of Pulsar Process Measurement Limited.
WARRANTY AND LIABILITY
Pulsar Measurement guarantee for a period of 2 years from the date of delivery that it will either exchange or repair any part of this product returned to Pulsar Process Measurement Limited if it is found to be defective in material or workmanship, subject to the defect not being due to unfair wear and tear, misuse, modification or alteration, accident, misapplication, or negligence.
DISCLAIMER
Pulsar Measurement neither gives nor implies any process guarantee for this product and shall have no liability in respect of any loss, injury or damage whatsoever arising out of the application or use of any product or circuit described herein.
Every effort has been made to ensure accuracy of this documentation, but Pulsar Measurement cannot be held liable for any errors.
Pulsar Measurement operates a policy of constant development and improvement and reserves the right to amend technical details, as necessary.
The Zenith shown on the cover of this manual is used for illustrative purposes only and may not be representative of the actual Zenith supplied.
CONTACT
For technical support, please contact: Europe: supporteurope@pulsarmeasurement.com
Outside Europe: supportnorthamerica@pulsarmeasurement.com If you have any comments or suggestions about this product, please contact: Europe: europe@pulsarmeasurement.com
Outside Europe: northamerica@pulsarmeasurement.com Pulsar Measurement website: www.pulsarmeasurement.com
United States
11451 Belcher Road South Largo, FL 33773 888-473-9546
Canada
16456 Sixsmith Drive Long Sault, Ont. K0C 1P0 855-300-9151
United Kingdom
Cardinal Building, Enigma Commercial Centre
Sandy’s Road, Malvern
WR14 1JJ 00 44 (0)1684 891371
Page 4
4
CONTENTS
Chapter 1: Start Here… ........................................................................................................... 9
About this Manual ............................................................................................................... 9
About the Zenith 140 ...................................................................................................... 10
Functional Description .................................................................................................... 10
Product Specification ....................................................................................................... 12
EU Certificate of Conformity ......................................................................................... 14
Fascia Mount ....................................................................................................................... 14
Chapter 2 Zenith 140 Installation .................................................................................... 15
Unpacking ............................................................................................................................ 15
Power Supply Requirements......................................................................................... 15
Safety Symbols ................................................................................................................... 16
Location ................................................................................................................................ 17
Dimensions .......................................................................................................................... 18
Fascia Mount ....................................................................................................................... 18
Terminal connection details .......................................................................................... 20
Terminal Connections ...................................................................................................... 21
Power ..................................................................................................................................... 21
Transducer ........................................................................................................................... 21
Voltage selector and fuse location............................................................................. 26
Preparation for Operation ............................................................................................. 28
Maintenance ....................................................................................................................... 28
Chapter 3 How To Use Your Zenith 140 ....................................................................... 29
Operating the Controls ................................................................................................... 29
Run Mode ............................................................................................................................. 30
Program Mode ................................................................................................................... 31
How to Access Program Mode .................................................................................... 31
Hot Keys ................................................................................................................................ 32
Menu Keys ........................................................................................................................... 33
Numeric Keys ...................................................................................................................... 33
Using the Menu System ................................................................................................. 34
Directly Editing Parameters ........................................................................................... 35
Page 5
5
Test Mode ............................................................................................................................ 36
Using the Serial Interface ............................................................................................... 37
Parameter Defaults ........................................................................................................... 39
Chapter 4 Quick Setup Guide ........................................................................................... 40
Enter Program Mode ....................................................................................................... 40
Choose Quick Setup ......................................................................................................... 40
Quick Setup ......................................................................................................................... 42
Example 1 Level Monitoring with Alarms ................................................................ 47
Example 2 Sump Control (pump down) ................................................................... 49
Example 2 Sump Control (pump up) ......................................................................... 51
Chapter 5 Parameter Guide ............................................................................................... 53
Menu System ...................................................................................................................... 53
Top Level Menu ................................................................................................................. 53
Application Menu .............................................................................................................. 53
Relays Menu ........................................................................................................................ 55
Pump “Advanced” Menu ................................................................................................ 56
Digital Inputs Menu.......................................................................................................... 57
Float Switch Menu ............................................................................................................ 58
Tariff Guard Menu ............................................................................................................. 59
Data Logs Menu ................................................................................................................ 60
Pumped Volume Menu ................................................................................................... 61
Efficiency Menu .................................................................................................................. 62
Display Menu ...................................................................................................................... 63
mA Output Menu .............................................................................................................. 64
Compensation Menu ....................................................................................................... 64
Stability Menu .................................................................................................................... 65
Echo Processing Menu .................................................................................................... 65
System Menu ...................................................................................................................... 66
Device Comm Menu ........................................................................................................ 67
Test Menu ............................................................................................................................ 68
Page 6
ZENITH 140 UL INSTRUCTION MANUAL
6
Application Parameters................................................................................................... 69
Operation ............................................................................................................................. 69
Dimensions .......................................................................................................................... 71
mA Input ............................................................................................................................... 73
Relay Parameters ............................................................................................................... 75
Alarms .................................................................................................................................... 77
Pumps .................................................................................................................................... 84
Control ................................................................................................................................... 88
Miscellaneous ..................................................................................................................... 93
Pump by Time .................................................................................................................... 94
Common Relay parameters........................................................................................... 97
Pump “Advanced” Parameters ..................................................................................... 99
Pump Run On ..................................................................................................................... 99
Starting .................................................................................................................................. 99
Stopping ............................................................................................................................. 100
Pump Exercising .............................................................................................................. 100
Wall Cling ........................................................................................................................... 101
Storm.................................................................................................................................... 101
Digital Inputs ..................................................................................................................... 102
Digital Input Parameters .............................................................................................. 108
Digital Input ....................................................................................................................... 110
Float Switch (FS) Backup .............................................................................................. 112
Digital Input ....................................................................................................................... 113
Tariff Guard ........................................................................................................................ 114
Data Log parameters ..................................................................................................... 117
Totaliser Audits ................................................................................................................ 117
Temperature ...................................................................................................................... 117
Pump Logs ......................................................................................................................... 118
Pumped Volume .............................................................................................................. 119
Volume ................................................................................................................................ 121
Conversion ......................................................................................................................... 121
Page 7
7
Breakpoints ........................................................................................................................ 126
Tables ................................................................................................................................... 127
Pump Efficiency ................................................................................................................ 128
Display Parameters ......................................................................................................... 131
Options ................................................................................................................................ 131
Failsafe ................................................................................................................................. 132
Auxiliary ............................................................................................................................... 133
Totaliser ............................................................................................................................... 135
mA Output Parameters ................................................................................................. 138
Range ................................................................................................................................... 138
Operation ........................................................................................................................... 138
Setpoint ............................................................................................................................... 139
mA Limits ............................................................................................................................ 139
mA Trim .............................................................................................................................. 139
mA Failsafe ......................................................................................................................... 140
Compensation Parameters .......................................................................................... 141
Offset.................................................................................................................................... 141
Temperature ...................................................................................................................... 141
Velocity ................................................................................................................................ 142
Stability Parameters ....................................................................................................... 143
Damping ............................................................................................................................. 143
Indicator .............................................................................................................................. 143
Rate ....................................................................................................................................... 143
Filters .................................................................................................................................... 144
Echo Processing Parameters ....................................................................................... 145
Transducer 1 Status ........................................................................................................ 145
Transducer 2 Status ........................................................................................................ 146
DATEM Parameters......................................................................................................... 147
System Parameters ......................................................................................................... 148
Passcode ............................................................................................................................. 148
Page 8
ZENITH 140 UL INSTRUCTION MANUAL
8
Backup ................................................................................................................................. 148
System Information ........................................................................................................ 149
Date & Time ...................................................................................................................... 150
LED Colour ......................................................................................................................... 150
Watchdog ........................................................................................................................... 151
Daylight Saving Time ..................................................................................................... 152
Device Comm. .................................................................................................................. 156
RS232 Set Up .................................................................................................................... 156
RS 485 Set Up ................................................................................................................... 156
Remote Alarm ................................................................................................................... 157
Test Parameters ............................................................................................................... 159
Simulation .......................................................................................................................... 159
Hardware ............................................................................................................................ 160
Chapter 6 Troubleshooting .............................................................................................. 162
Chapter 7 Disposal .............................................................................................................. 163
Notes ........................................................................................................................................ 164
Page 9
9

CHAPTER 1: START HERE…

Congratulations on your purchase of a Pulsar Zenith 140. This quality system has been developed over many years and represents the latest in high technology ultrasonic level measurement and control.
It has been designed to give you years of trouble-free performance, and a few minutes spent reading this operating manual will ensure that your installation is as simple as possible.

About this Manual

It is important that this manual is referred to for correct installation and operation. There are various parts of the manual that offer additional help
or information as shown.
Tips
TIP: Look for this ic on t h r o u g h o u t yo u r Pulsar Measuremen t manual to find helpful informat ion a n d a n s w e r s t o f r equently asked question s .
Additional Information
References
See Also
References to other parts of the manual.
Additional Information
At various parts of the manual, you will find sections like this that explain specific things in more detail.
Page 10
ZENITH 140 UL INSTRUCTION MANUAL
10

About the Zenith 140

The Zenith 140 is a state-of-the-art pump, and level controller, that provides advanced operating routines suitable for an extremely wide variety of applications. The system combines premium specification with high performance even in the most arduous applications where high turbulence and foam or froth is present.

Functional Description

The Zenith 140 level and pump controller is a highly developed ultrasonic level measurement system which provides non-contacting sophisticated pump and level control routines suitable for an extremely wide variety of applications.
Easy calibration and maintenance free “fit and forget” performance mean that you can install the Zenith 140 pump controller rapidly and with confidence. Six user-definable relays with adjustable, individual on and off points, seven user-definable digital inputs, isolated mA output, RS 232 and intelligent performance logging software features provide the user with a superior pump management system and comprehensive level measurement information.
The Zenith 140 operates on the principle of timing the echo received from a measured pulse of sound transmitted in air and utilises the unique DATEM software (Digital Adaptive Tracking of Echo Movement). This is an entirely new digital mapping technique developed especially for the Pulsar Ultra range.
Page 11
11
It gives the system the edge when identifying the “true target level” in the face of competing echoes from pipes, pumps or other obstructions. When coupled with the powerful, long range abilities of a dB transducer and radar range, the Zenith 140 level and pump controller has no equal.
The Zenith 140 can measure from 0 to 131 feet (40m) from the face of the transducer to the surface being monitored, dependent on the transducer used.
The Zenith 140 can show level, space, distance, on the display. The relays can be programmed to activate alarms, pump starters, or other control equipment. In addition, the digital inputs can be used to modify pump and control regimes to optimise performance. There is an isolated 4-20 mA output that can be connected to a chart recorder or PLC, to monitor level, space or distance, independently from that shown on the display. There is an RS232 port, so that the Zenith 140 can be operated remotely by a PC or other equipment.
The Zenith 140 is programmed by the built-in keypad or by PC via the RS 232 Serial Interface (optional). All the parameters are stored in non-volatile memory, so are retained in the event of power interruption. A second backup copy of all parameters can also be retained in the Zenith 140, in case a previous set of parameters needs to be restored.
Page 12
ZENITH 140 UL INSTRUCTION MANUAL
12

Product Specification

PHYSICAL
Fascia Mount dimensions
7.87 x 4.41 x 4.25” (200 x 112 x 108mm)
Weight
2.87lbs (1.3kg)
Enclosure material/description
Stainless steel back, Polycarbonate UL94-V0 front and bezel
Transducer Cable Extensions
3-conductor 20AWG screened.
Maximum Separation
3,680 feet (1,000m), 1.640 (500m) for mmWave
ENVIRONMENTAL
IP Rating/Relative Humidity
(IP64 from front panel) <35oC (95oF) at 93% relative
humidity. Pollution Degree 2
Max. & min. temperature (electronics)
-4oF to 140oF (-20ºC to +50ºC)
Flammable atmosphere approval
Safe area: compatible with approved dB transducers (see transducer spec' sheet)
CE Approval
See EU Declaration of Conformity
UL Approval
Certificate number E257330
PERFORMANCE
Accuracy
0.25% of the measured range or 0.24” (6 mm) (whichever is greater). mmWAVE ± 2mm.
Resolution
0.1% of the measured range or 0.08” (2 mm) (whichever is greater)
Max. Range
Dependant on transducer maximum 131.28ft (40m dB40)
Min. Range
Dependent upon application and transducer (minimum zero dB Mach3)
Rate Response
Fully adjustable
ECHO PROCESSING
Description
DATEM (Digital Adaptive Tracking of Echo Movement)
OUTPUTS
Analogue I/O
Isolated (floating) output (to 150V) of 4-20 mA or 0-20 mA into 500 (user programmable and adjustable)
0.1% resolution
Digital output
Full Duplex RS232
Volt free contacts, number, and rating
6 form "C" (SPDT) rated at 5A at 115V AC
Page 13
13
Display
6 digits plus 12-character text, plus bar graph with direction indicators, remote communicator identifier, and program/run/test mode indicators
ANALOGUE INPUTS
Available as an optional input only.
Isolated (floating) 4-20mA or 0-20mA source, open circuit voltage 33V, 22V at 4mA, 14V at 20mA (user programmable and adjustable) 0.1% resolution
DIGITAL INPUTS
Digital Inputs
Min. Input Voltage 4.5VDC. Max. Input Voltage 30VDC (Max Current 3mA). 24VDC Input Supply maximum total current 24mA.
PROGRAMMING
On-board programming
By integral keypad
PC programming
Via RS232
Programming security
Via passcode (user selectable and adjustable)
Programmed data integrity
Via non-volatile RAM, plus backup
SUPPLY
Power Supply
115V AC +5% / -10% 50/60 Hz, dc 18 - 30V (If using a battery then 24V minimum 1AH, dependant on life required, externally fused with 1A fast blow fuse. 10W maximum power (typically 6W)
Overvoltage Category
II
Mains Fuse (F1)
125 mA T at 115V AC
DC (Battery) (F2)
1A Thermal (self-resetting after power removed). Not user replaceable
Transducer (F3, F5 Ch1. & F4, F6 Ch. 2)
Littelfuse 242 series 100mA Part No. 0242.100. This fuse is not user replaceable and has a 4000A breaking capability to comply with certification of the Exm version of dB series transducers.
Pulsar Measurement operates a policy of constant development and improvement and reserve the right to amend technical details, as necessary.
Page 14
ZENITH 140 UL INSTRUCTION MANUAL
14

EU Certificate of Conformity

Fascia Mount

Page 15
15

CHAPTER 2 ZENITH 140 INSTALLATION

Unpacking

Power Supply Requirements

The Zenith 140 can operate from AC supply or from a DC battery and is designed for use in temperatures between -4ºF to +140ºF (-20ºC to +50ºC). The AC is 115V +5% / -10% 50/60Hz. The DC is 18-30V. In all cases the Zenith 140 will typically consume 6W of power, with a maximum of 10W. If Zenith has both an AC and DC supply available then the AC supply source will be automatically sensed and used, should the AC supply be removed for any reason then the DC supply will take over.
The AC and DC wiring should be completed using either 16 – 14AWG (1.5–
2.5mm2) stranded or 16 – 14AWG (1.5–4mm2) solid wire, with all terminals being tightened to 4.5in. lbs. (0.5Nm).
An external supply isolator/circuit breaker (AC or DC) must be fitted near to the unit and labelled to identify the instrument to which it refers.
Important Information
All shipping cartons should be opened carefully. When using a box cutter, do not plunge the blade deeply into the box, as it could potentially cut or scratch equipment components. Carefully remove equipment from each carton, checking it against the packing list before discarding any packing material. If there is any shortage or obvious shipping damage to the equipment, report it immediately to Pulsar Process Measurement Limited.
Page 16
ZENITH 140 UL INSTRUCTION MANUAL
16

Safety Symbols

Detailed below are descriptions and meanings of safety/warning symbols that are used on the Zenith 140 and in this manual:
SYMBOL
DESCRIPTION
DIRECT CURRENT (DC)
ALETRNATING CURRENT (AC)
PROTECTIVE CONDUCTOR TERMINAL
CAUTION (Refer to accompanying Documents)
!
Page 17
17

Location

The Zenith must be mounted in a non-hazardous (safe) area, and the transducer fitted in the hazardous area
When choosing a location to mount the enclosure, bear in mind the following:
Ensure that the Zenith 140 is installed in a “Safe”, non-hazardous
area.
For a clear view of the LCD display, it is recommended that it is
mounted at eye level.
The mounting surface is to be vibration free.
The ambient temperature is between -4ºF and 140ºF (-20ºC and
50ºC).
There should be no high voltage cables or inverters nearby,
Important Information
All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation.
Page 18
ZENITH 140 UL INSTRUCTION MANUAL
18

Dimensions

Fascia Mount

The dimensions of the wall fixing holes are as shown below:
Important Information
When mounting the fascia mount unit into a panel, in order to maintain the panel IP rating the panel should be of smooth/painted finish and be machined, as per the details contained in this manual.
Fit the unit through the hole then, using the components supplied place a plain washer then a spring washer followed by an elongated nut to each of the 4 off M3 threaded studs and tighten to 2.5lb in. (0.28Nm)
Care should be taken not to overtighten the screws.
Page 19
19
The full dimensions of the fascia mount enclosure are as shown below:
0.79” (20mm)
2.83” 72mm
0.63” (16mm)
7.87 inches (200mm)
4.41 inches (112 mm)
6.38 inches (162mm)
0.59” (15mm)
Page 20
ZENITH 140 UL INSTRUCTION MANUAL
20

Terminal connection details

Fascia Mount

The terminal details are as illustrated below:
Page 21
21

Terminal Connections

Power

The Zenith can operate from mains AC and automatically from DC or battery backup in the event of power failure or can be operated permanently from DC or batteries.
The AC and DC wiring should be completed using either 16 – 14AWG (1.5–
2.5mm2) stranded or 16 – 14AWG (1.5–4mm2) solid wire. An external supply isolator/circuit breaker (AC or DC) must be fitted near to
the unit and labelled to identify the instrument to which it refers.

Transducer

The transducer should be installed, and connected, in accordance with the installation instructions contained in the Transducer User Guide.
The entire range of standard dB transducers are certified for use in hazardous areas and different models, for each, are available for use in Zone 1 or Zone 0.
Wire the transducer to the Zenith 140’s transducer terminals, as follows:

Transducer 1

TERMINAL CONNECTION DETAILS
Red:
Power
White: Signal
Black:
0Volts
Green:
Screen
32
31
30
30
Important Information
All terminal connection screws should be tightened to 4.5in.lbs. (0.5Nm).
Care should be taken not to overtighten the screws.
Important Information
The protective earth must be connected prior to any other cabling taking place. In the case of the fascia unit the earth should be connected to the stud at the rear of the enclosure and tightened to 7.4lbF/10Nm.
Page 22
ZENITH 140 UL INSTRUCTION MANUAL
22

Transducer 2

TERMINAL CONNECTION DETAILS
Red:
Power
White: Signal
Black:
0Volts
Green:
Screen
35
34
33
33
If splicing, it is recommended using a junction box with standard twisted, shielded pair at 20 AWG.
When using 2 core screened extension cable, the Black and Green wires of the transducer should be connected to the screen of the extension cable, which in turn should be connected to the relevant 0 volts terminal (Terminal 30 or 33).
When installing a transducer in a hazardous area use an approved transducer suitable for the proposed application as detailed below:
FM
For EEx m (Zone 1) applications a transducer certified to FM Class I Div 1 Group A, B, C & D, ClassII Div 1 Group E, F & G, Class III is used, and must
be supplied via a 1500A breaking fuse, which is fitted as standard to the Zenith 140.
Restrictions do not use in the presence of these groups of Chemicals, Aliphatic Hydrocarbons, Ketones or Esters
For EEx ia (I.S.) a transducer certified to FM Class I Div 1 Group A, B, C & D, ClassII Div 1 Group E, F & G is used, which must be connected to the Zenith 140 via an external Zener barrier.

ATEX

For EEx m (Zone 1) applications a transducer certified to Sira 02ATEX5104X is used, and must be supplied via a 4000A breaking fuse,
which is fitted as standard to the Zenith 140. For EEx ia (Zone 0) a transducer certified to Sira 02ATEX2103X is used,
which must be connected to the Zenith 140 via an external Zener barrier.
See transducer label for certification details.
Page 23
23
Single Transducer mode is used to measure space, level, distance or volume and the transducer should be connected to Transducer 1 input terminals.
Dual Transducer mode is used to measure Differential and Average. For Differential, the upstream transducer should be connected to Transducer 1 input terminal and the downstream transducer to Transducer 2 input
terminal. In cases where the Zenith is required to measure Average, then transducers can be connected to either one.

Relay Outputs

The six relays can be programmed for a variety of alarms, pump control, or other process functions. The relay contacts are all rated at 5A at 115V AC.
Wiring should be completed by using suitable cable, to meet the specified 115V AC 5A contact rating, up to maximum size of 14AWG.
All connections should be such that the short circuit capacity of the circuits to which they are connected, is limited by fuses rated so that they do not exceed the relay rating.

Current Output

This is an isolated (floating) mA output (to 150 V), of 4 - 20mA or 0 - 20mA, and the load should not exceed 500 .
Important Information
Please note that if the output of the ultrasonic transducers used with the Zenith 140 are capable of emitting sound pressure levels more than 85dBA (above a
reference sound pressure level of 20µPA), then the Zenith 140 must be located remote from the transducer such that a sound pressure level of 85dBA is not exceeded when standing at the Zenith 140 in the operator’s position.
Page 24
ZENITH 140 UL INSTRUCTION MANUAL
24

Current Input (Optional)

This feature is available as an option only. Please consult Pulsar for further details. The current input is an isolated (floating) mA input (to 150 V), 4 ­20mA or 0 -20mA.

Temperature Input (Optional)

The external temperature sensor allows more localised compensation of the measured distance due to changes in temperature. There are two models, Type A and Type B as follows:
TYPE
RANGE
A
-25° to 50°C
B
-25° to 125°C
The temperature sensor should be placed close to the point of measurement.
Page 25
25
The Temperature sensor connections are as follows:
DESCRIPTION
TEMPERATURE
SENSOR
ZENITH
FASCIA
Power Supply
Terminal 1
Terminal 25
Return
Terminal 2
Terminal 24
Temp Source (P852), should be set to option 4 or 5 depending on the sensor range, set 4 for type A and 5 for type B (see above), the range is specified on the label of the sensor.
This feature is available as an option only, please consult Pulsar for further details.

Digital Inputs

Where the Zenith is required to provide power for a Device Input the appropriate Digital Input should be wired between the 24VDC supply terminal and the IN terminal. (TOTAL maximum current available, for all seven digital inputs, from the 24VDC supply is 24mA). When Device Inputs are self-powered, connection of the device should be made between the Common terminal and the IN terminal. (Min Input voltage 4.5VDC, and Maximum Input voltage 30VDC with a maximum current of 3mA).
92mm
182mm
100mm
M20 ENTRY
IP67 ABS HOUSING
316 STAINLESS STEEL
6mm
Page 26
ZENITH 140 UL INSTRUCTION MANUAL
26

RS2323 Serial Interface

If required, you can connect to the serial interface to operate your Zenith remotely.

Voltage selector and fuse location

Fascia Mount

The voltage selector switch and mains fuse, is located under the removable cover at the bottom of the unit, as illustrated below.
230
115
AC POWER FUSE
Page 27
27
DON’T FORGET
Make sure you move the voltage selector switch to the correct position for your power supply
Important Information
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
Important Information
The rear metal case of the fascia unit must be connected to earth via the earthing stud located on the rear of the unit, see drawing above, using wiring to meet local requirements.
Before applying AC power (mains), make sure the supply is 115V AC. Never operate the Zenith 140 with terminal access exposed. An external switch or circuit breaker should be installed near to the Zenith
to allow the supply to be removed during installation and maintenance. In addition, the relay contacts should also have a means of isolating them from the Zenith.
Interconnecting cables must be adequately insulated in accordance with local regulations. Strip back 30 mm of the outer insulation of the cable. Strip 5 mm of insulation from the end of each conductor. Twist all exposed strands of the conductor together. Insert the stripped conductor into the terminal block as far as it will go and tighten the terminal block screw. Ensure that all strands are firmly clamped in the terminal block and that there is no excess bare conductor showing, and no stray strands.
Page 28
ZENITH 140 UL INSTRUCTION MANUAL
28

Preparation for Operation

Before switching on, check the following:
The Zenith is mounted correctly and is in a ‘safe’ area. The power supply is correctly installed. The voltage selector switch is in the correct position. The relays are connected correctly.

Maintenance

There are no user serviceable parts inside Zenith, except the mains fuse. If you experience any problems with the unit, then please contact Pulsar Measurement for advice.
To clean the equipment, wipe with a damp cloth. Do not use any solvents on the enclosure.
Important Information
The unique DATEM software comes into operation as soon as power is applied and is designed to monitor a moving level or target with the transducer in a fixed position.
If, after any period of use, it should become necessary to move the transducer, for any reason, from its original operating position, switch off the Zenith, before proceeding, in order to prevent any undesirable updates to the DATEM trace. If after moving the transducer the reading is not as expected, please refer to Chapter 6 Troubleshooting.
Page 29
29

CHAPTER 3 HOW TO USE YOUR ZENITH 140

Operating the Controls

Display

The display provides information on the current mode of operation, and status of the remote communication. Whilst in the Run Mode it will display the current level reading and its units of measure, along with status messages with regards to the Transducer, Echo reception and Fail-Safe Mode. Additionally, it can be programmed to provide status messages on alarms, pumps etc. When in the Program mode the display is used to read information on the Menu System, Parameter Number and parameter details and values, which can be entered. During Test Mode, the display is used to monitor the simulated level. A bar graph is also provided which will provide a visual reading of the level, in percentage of span.
1. Displays the current mode of operation
2. Main 6-digit display:
Run Mode; current measurement displayed, dependent on mode and measurement units chosen, and value of hotkey selected. Program Mode; displays parameter number and values entered for parameters. Test Mode; displays simulated level.
1 2 3
4
0%
5
6
Run Mode Program Mode Test Mode 100%
REMOTE COMMUNICATOR OFF
XXXXXXXXXXXX
000.000
Page 30
ZENITH 140 UL INSTRUCTION MANUAL
30
3. Auxiliary Display, scrolling twelve-digit display.
Run Mode; displays measurement units, status messages on signal and transducer, details of Hot Key function selected. It can be also programmed to provide notification messages on alarms and pumps etc. For full details please refer to Display Parameters in the relevant parameter listing. Program Mode; displays menu and sub menu headings, parameter details and options.
4. Communicator status, this displays the status of remote PC
connection and velocity sensor operation.
5. Bar graph display, this gives visual indication of measurement in %
of span.
6. Level indicators:
Run Mode; indicates in which direction the level is moving. Program Mode: indicates at which level of the menu system you are
at.
There are two main operating modes for your Zenith 140, Run Mode and Program Mode. There is also a Test Mode, used for checking the set-up. All modes are now described.

Run Mode

This mode is used once the Zenith 140 has been set up in program mode. It is also the default mode that the unit reverts to when it resumes operation after a power failure.
When the Zenith 140 is switched on for the first time, it will display, in metres, the distance from the transducer face to the target. All relays by default are switched off.
After programming is complete, any relays that are set will operate when the level reaches the relevant setpoint, and the LED’s will change colour (unless specifically switched off).
Page 31
31

Program Mode

This mode is used to set up the Zenith 140 or change information already set. You must use either the built-in keypad (standard) or, alternatively the unit can be set up with a PC via the RS232 Serial Interface.
Entering a value for each of the parameters that are relevant to your application provides all the programming information.

How to Access Program Mode

To enter program mode on the Zenith 140, you simply enter the passcode, via the keypad, followed by the ENTER key. The default passcode is 1997, so you would press the following:
Important Information
There is a time-out period of 15 minutes when in program mode. After which time the run mode will resumed if you do not press any key.
ENTER
1
9 9 7
Page 32
ZENITH 140 UL INSTRUCTION MANUAL
32

Hot Keys

There are five hot keys on the keypad, which can be used to quickly access common parameters for viewing only, while in Run Mode. Pressing the hot key once will display the first parameter, then repeated pressing will display the others, then the Zenith reverts to Run Mode. In program mode, they have different functions, the functions are shown below.
HOT KEY
RUN MODE
PROGRAM MODE
Total pump running hours and individual pump running hours.
Not used with Zenith 140
Displays echo confidence, echo strength, height above loss limit (HALL), average noise, peak noise, and temperature
Not used with Zenith 140
Total number of pump starts, and individual pump starts.
Reset parameter to default setting
Instantaneous mA output
Not used with Zenith 140
Dependent on application. Displays distance, level, space, volume or rate of change of level.
Toggle relay setpoints between units of measure and % of span.
Reset for digital inputs
Takes you to the last parameter edited when you first enter program mode.
Shows details of function type, firmware revision and serial number
Enter decimal point.
mA
n
Page 33
33

Menu Keys

The menu keys have the following functions:
HOT KEY
FUNCTION
1) Arrow keys for moving left and right around the menu
system.
2) Used in test mode to simulate the level moving up and
down.
1) Used to confirm each action (e.g., select a menu option)
2) Used to confirm questions asked by the Zenith, such as
before restring factory defaults.
Used to navigate up a level in the menu system, and back to run mode.
Used to cancel a value entered in error

Numeric Keys

These keys are used for entering numerical information during programming.
CANCEL
ENTER
1
2
3 4 5
6
7
8 9 0
.
+
-
Page 34
ZENITH 140 UL INSTRUCTION MANUAL
34
There are two means of editing parameters, directly or using the menu system. Each is now described.

Using the Menu System

The menu system has been designed to make the changing of parameters very simple. There are two levels of menu: Main Menu and Sub Menu.
On the display, there is a line of text that displays the menu system. Pressing the arrow keys scrolls the display between the top-level menu items, (as the example shown below, starting at Quick Setup).
As you press the cursor keys to scroll left and right between these, you can press ENTER at any time, to select the desired menu heading, and take you to the sub-menu.
Each of these options, along with their sub-menus, are described later in this manual. When you move down into the sub-menu, you can scroll round using the arrow keys, press ENTER to go to the required section of parameters.
Once you have reached the relevant section, scroll through the parameters, and enter the necessary information. To enter the information, use the
numeric keys and then press ENTER, you will then see the message “Saved!”
If you press CANCEL, then the change you made will not be saved, and the message “Unchanged!!” will be displayed.
When you have finished, press CANCEL to go back to the previous level. When you have reached the top level, then the Zenith will ask for confirmation before allowing you to go back into run mode. This is done by pressing ENTER at the display prompt.
Quick Setup
Application
Relays
Pump
Advanced
Digital
Inputs
FS Backup
Tariff Guard
Display
mA
Output
Pump
Efficiency
Pump
Volume
Compensation
Stability
System
Test
Device Comm
Echo
Processing
Data Logs
Page 35
35

Directly Editing Parameters

If you already know the number of the parameter, that you wish to look at or edit, simply type the number in at any time while you are in the menu system. Thus, if you are in either the menu or sub-menu level by pressing a numeric key, you can enter the parameter number directly and jump straight there. You cannot type a parameter number whilst at parameter level, only at one of the two menu levels.
When you are at a parameter, the text line rotates automatically displaying the parameter name, number, the applicable units, and the maximum and minimum figure you can enter. The top line shows the value you are setting.
Once you have accessed a parameter, you can either just look at it, or change it.
Once a parameter has been changed, press ENTER and you will see the
message “Saved!”. If you press ‘CANCEL, then the change you made will not be saved, and the message “Unchanged!!” will be displayed.
You can jump straight to the last parameter you edited, by pressing ‘+/- when you first enter program mode.
Important Information
You can tell which part of the menu system you are in, as the up/down level indicators, (arrows) next to the bar graph will indicate as follows:
Top level menu: Down arrow on, to indicate you can move down.
Sub-menu: Up and Down arrows on, to indicate you can move up to the top
level, and down to parameter level.
Parameter Level: Up arrow on, to indicate you can move up to sub-menu
level.
Parameter Editing: No arrows on.
Page 36
ZENITH 140 UL INSTRUCTION MANUAL
36

Test Mode

Test mode is used to simulate the application and confirm that all parameters and relay setpoints have been entered as expected. During simulation, there is a choice of whether the relays will change state (hard
simulation) or not (soft simulation), but the LED’s will always change colour
as programmed, and the mA output will change in accordance to the chosen mode of operation. If you wish to test the logic of the system that the relays
are connected to then select hard simulation, but if you do not wish to change the relay state, then select a soft simulation.
There are two simulation modes, automatic and manual. Automatic simulation will move the level up and down between empty level or the pre­determined Start Level (P983) and Pump/Control relay switch points, if you wish to change the direction of the level movement e.g. to go beyond relay setpoints, this can be done by using the arrow keys. In manual simulation, using the arrow keys will allow you to move the level up and down as required.
To enter simulation, first go to program mode. Using the menu system, select menu item ‘Test’, then sub-menu item ‘Simulation’. Simply change the value of the parameter P980 to one of the following:
1= Manual soft simulation 2= Automatic soft simulation 3= Manual hard simulation 4= Automatic hard simulation
To return to program mode, press CANCEL and test mode will end. When in manual simulation, by default test mode will move the level by
0.328 feet steps. Altering the increment (P981) will change this value. In automatic mode, the rate at which the level moves up and down is set by
the increment (P981 in feet, and the rate (P982) in minutes, which can be changed to make the level move up and down faster. E.g., if increment (P981) is set for 0.328 feet and rate (P982) is set to 1 min then the level will increase or decrease at a rate of 0.328 ft/min. To make the simulated level move slower, decrease the value in increment (P981) or increase the value in rate (P982). To make the simulated level move faster, increase the value in increment (P981) or decrease the value in rate (P982).
Page 37
37

Using the Serial Interface

The RS232 serial interface is used to communicate between the Zenith and a PC using the optional Ultra PC and other associated Pulsar software packages, to obtain information such as data logging and view echo traces upload, download and save parameter files. In addition, it can also be used to control or obtain information using a standard PC or other computer base equipment. To do so, the settings for control are as follows: baud rate 19,200, 8 data bits, no parity, 1 stop bit.
The device should be connected as shown in Chapter 2 Zenith
140 Installation.
To use the device remotely, you need to log on to start, and log off when finished. When logged on, the Zenith will show ‘Remote ON’ on the display, and “Communicator OFF” when logged off.
All commands should be followed by a carriage return. When logged on, the unit will respond either OK (or a value) if the command is accepted, or NO if it is not.
To log on, send the command /ACCESS:pppp where pppp is the passcode (P922). To log off, send the command /ACCESS:OFF To read a parameter value, send the command /Pxxx where xxx is the parameter you wish to read, and the Zenith 140 will
respond with the parameter value. To set a parameter, send the command /Pxxx:yy where xxx is the parameter number, and yy is the value you wish to
set it to.
Page 38
ZENITH 140 UL INSTRUCTION MANUAL
38
Other commands you can use are:
/DISTANCE (shows current distance)
/LEVEL (shows current level)
/SPACE (shows current space)
/RATE (shows current rate)
/VOLUME (shows current volume)
/TEMP (shows current temperature)
/CURRENTOUT1 (show the mA output 1 value)
/CURRENTOUT2 (show the mA output 2 value)
/BACKUP1 (take backup of parameters to area 1)
/BACKUP2 (take backup of parameters to area 2)
/RESTORE1 (restore parameters from area 1)
/RESTORE2 (restore parameters from area 2)
Please consult Pulsar Measurement or contact your local Pulsar representative for further details and a full list of available commands.
Page 39
39

Parameter Defaults

When you first switch the Zenith 140 on, it will be reading the distance from the face of the transducer to the surface. It will be indicating in metres, as shown on the display. All relays are set OFF.
The date (P931) and time (P932) in the Zenith 140 were set at the factory, but may need checking, and amending if, for example the application is in a time zone other than GMT, see relevant parameter listing for full details.
In some applications, it is easier to empty the vessel, take a reading from the Zenith 140 for distance and then setup the empty level to this figure.
Once you are satisfied with the installation, and Zenith 140 is reading what you would expect in terms of distance from the face of the transducer to the material level, then you can proceed with programming, for the intended application. It is sensible to program all the required parameters at the same time. The system will be then set-up.
Note: The span is automatically calculated from the empty level, so the empty level should be entered first.
Factory Defaults
When first installing the Zenith, or subsequently moving or using the unit on a new application, before proceeding to program the unit for its intended application it is recommended that you ensure that all parameters are at their default values by completing a Factory Default P930, as described in the relevant unit type parameter guide.
Page 40
ZENITH 140 UL INSTRUCTION MANUAL
40

CHAPTER 4 QUICK SETUP GUIDE

This quick set-up guide shows you how to get up and running in a few minutes in just four easy steps after installing your Zenith 140.

Enter Program Mode

First you need to go from run mode into program mode. Assuming the passcode is the default 1997, then you should enter the following on the keypad:

Choose Quick Setup

Now you need to go into the quick setup. You will see on the menu the
words ‘Quick Setup’, which is the first item on the menu system. Try pressing
the two arrow keys to see some more menu options, but return to Quick Setup, and press
ENTER
1
9 9 7
ENTER
This takes you to the common applications parameter (P200).
ENTER
This takes you to the common
applications parameters, and you will see
some options appearing on the display.
Factory Defaults
If you have already setup a common application, then there will be a number shown other than 0, and you will see messages showing what the current setup is. If you want to reset this and start again, press 0 (which will reset all the quick setup parameters), otherwise pressing ENTER will allow you to edit the parameters that have been set.
Page 41
41

Choose Your Application

There are four categories of application, which are all described at the end of this chapter. They are level, pump down (sump control), pump up (reservoir control) or customised, all with the choice of alarms and a number of pumps, dependant on application.
If you want to set-up a basic level monitoring application, as described in the following example 1, then choose 1. You then need to decide the number of alarms required and their function and choose the appropriate options.
If you want to set-up a pump down (sump control) application, as described in the following example 2, then choose 2. You then need to decide the
number of pumps required the pump duty and any requirement for alarms and choose the appropriate options.
If you want to set-up a pump up (reservoir control) application, then choose
3. You then need to decide the number of pumps required the pump duty, and any requirement for alarms, and choose the appropriate options.
In certain cases, the Quick Setup Menu has been customised for customer specific applications, to choose one of these options press 4 and select the appropriate customised application and enter the details required as prompted.
Once you have chosen your application you will be asked a series of questions which are answered by choosing the appropriate option as detailed in the flow charts that follow. Once all the questions have been answered you will be prompted to provide further information, as detailed in the tables that follow, to complete the programming of the unit.
Page 42
ZENITH 140 UL INSTRUCTION MANUAL
42

Quick Setup

Quick Setup
For Each Alarm
1 = High Alarm 2 = Low alarm 3 = Hi Hi Alarm 4 = Lo Lo alarm 5 = Loss of Echo
1 = Level
2 = Pump Down
3 = Pump Up
How Many Pumps
1 = One Pump
2 = Two Pumps 3 = Three Pumps 4 = Four Pumps 5 = Five Pumps
For each Pump Relay
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3 4 = Set to Relay 4 5 = Set to Relay 5
How Many Alarms
0 = No Alarms 1 = One Alarm 2 = Two Alarms 3 = Three Alarms 4 = Four Alarms 5 = Five Alarms List will be truncated according to the number of Control relays selected
Pump Duty
1 = Fixed Duty Assis 2 = Fixed Duty Backup 3 = Alt Duty Assist 4 = Alt Duty Backup 5 = Duty Backup & Ass 6 = Ser Ratio Duty Ass 7 = Ser Ratio Duty B’up 8 = FOFO Alt Duty Ass 9 = Ser Ratio Stby 10 = 2 Pump Set
4 = Customised
Select the option
specific to your
application
For each Alarm
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3 4 = Set to Relay 4 5 = Set to Relay 5 6 = Set to Relay 6
Page 43
43

Set-up Your Application

Once you have chosen the application, you will see a ‘Wait…’ message while
the parameters are all calculated and stored. Next you will see the parameters needed to finalise your application, in turn, as shown below. If you know you do not need to change from the default, you can use the right arrow key to scroll through them, but if you want to view or change each one, just press ENTER.
PARAMETER
DEFAULT
DESCRIPTION
P101 Transducer
2 = dB6
Type of transducer being used.
P102 Material
1 = Liquid
Material in the vessel, either liquid or solid. If the solid lays flat, then it can be programmed as liquid.
P104 Measurement Units
4 = Feet
Select units to be used for programming measurement information.
P105 Empty Level
19.685 feet
Distance from the face of the transducer to the material at the bottom of the vessel.
P106 Span
18.701 feet
Distance from the empty level (0% full) to span (100% full).
For More Options Hit Enter
Now you will see a scrolling message that says, ‘For more Options Hit Enter’. If you press ENTER, you will then see more parameters, specific to the
application you have chosen, these are all factory pre-set. If you press any other key you will return to the Quick Setup menu, where you can press CANCEL to return to run mode.
Page 44
ZENITH 140 UL INSTRUCTION MANUAL
44
PARAMETER
DEFAULT
DESCRIPTION
P213 / P214 Relay 1 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P223 / P224 Relay 2 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P233 / P234 Relay 3 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P243 / P244 Relay 4 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P253 / P254 Relay 5 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P263 / P264 Relay 5 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P830 mA Out Range
2 = 4 to 20mA
Determines the mA output range. 0 = Off, 1 = 0 to 20mA, 2 = 4 to 20mA, 3 = 20 to 0mA, 4 = 20 to 4mA.
P870 Fill Damping
32.80 feet/min
Rate of maximum fill rate (set above the actual fill rate of the vessel).
P871 Empty Damping
32.80 feet/min
Rate of maximum empty rate (set above the actual rate of the vessel).
Page 45
45
Alarm relays, via the Quick Setup menu are entered as a % of span and are as follows:
APPLICATION
NO. OF
PUMPS
PUMP NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Down
One
Pump 1
50%
20%
Pump Down
Two
Pump 1 Pump 2
50% 70%
20% 20%
Pump Down
Three
Pump 1 Pump 2 Pump 3
50% 60% 70%
20% 20% 20%
Pump Down
Four
Pump 1 Pump 2 Pump 3 Pump 4
40% 50% 60% 70%
20% 20% 20% 20%
Pump Down
Five
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5
40% 50% 60% 70% 75%
20% 20% 20% 20% 20%
Pump Down
Six
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 Pump 6
40% 50% 60% 70% 75% 80%
20% 20% 20% 20% 20% 20%
Page 46
ZENITH 140 UL INSTRUCTION MANUAL
46
APPLICATION
NO. OF PUMPS
PUMP NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Up
One
Pump 1
50%
80%
Pump Up
Two
Pump 1 Pump 2
50% 30%
80% 80%
Pump Up
Three
Pump 1 Pump 2 Pump 3
50% 40% 30%
80% 20% 80%
Pump Up
Four
Pump 1 Pump 2 Pump 3 Pump 4
60% 50% 40% 30%
80% 80% 80% 80%
Pump Up
Five
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5
60% 50% 40% 30% 25%
80% 80% 80% 80% 80%
Pump Up
Six
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 Pump 6
60% 50% 40% 30% 25% 20%
80% 80% 80% 80% 80% 80%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%
Page 47
47

Example 1 Level Monitoring with Alarms

A vessel, containing liquid that has a variation in level that is to be monitored, with a high-level alarm set on Relay 1 and low-level alarm set on Relay 2.
In this example, when the level rises to 8.5 feet, relay 1 will come on until the level drops to 8 feet when it will turn off. If the level drops to 1 feet, then relay 2 will come on until it rises 1.5 feet when it will turn off.
The display will show the level in the tank.
The mA output will be representative of level where 4mA = empty level (0%) and 20mA = 10 feet (100%).
Empty Distance (P105), 11 feet
100%. Span (P106), 10 feet
85%. High alarm on (P213), 8.5 feet
80%. High alarm off (P214), 8 feet
0%, Empty level
10%. Low alarm on (P223), 1 feet
15%, Low alarm off (P224), 1.5 feet
Page 48
ZENITH 140 UL INSTRUCTION MANUAL
48
To program the Zenith 140 for Example 1 Level Monitoring with Alarms by using the Quick Setup menu proceed as follows. If required to access Program Mode, key in the passcode 1997 and press ENTER
At the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Volume
1 = Level App.
No. of alarms
2 = 2 Alarms
Type alarm 1
1 = High
Alarm no.1
1 = Set to relay 1
Type alarm 2
2 = Low
Alarm no.2
2 = Set relay 2
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measurement units (P104)
4 = Feet
Empty Level (P105)
11 feet
Span (P106)
10 feet
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Zenith 140 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
Page 49
49

Example 2 Sump Control (pump down)

A sump is typically used to temporarily hold water or effluent, and when the level reaches a specific point, the sump is pumped down, with the fluid being transferred to another process.
In this example, there are two pumps, which will be set to alternate duty assist, so they come on alternately. Pump 1 is to be set to relay 1, pump 2 to relay 2, and the high-level alarm to relay 3.
This will operate as follows. During normal operation, pump 1 will come on at 3 feet and pump down to 2 feet. The setpoints are then shifted to pump 2, which will come on first next time. During peak periods, when pump 1 cannot cope, pump 1 will come on at 3 feet, pump 2 will come on at 5 feet, and pump down to 2 feet. The setpoints are then shifted to pump 2, which will come on first next time.
If neither pump can cope, and the level rises to 8.5 feet, then the alarm relay (relay 3) will come on and go off when the level falls to 8 feet. This will indicate insufficient capacity of the pumps. The display will show the level in
Empty Distance (P105), 11 feet
100%. Span (P106), 10 feet
85%. High alarm on (P233), 8.5 feet
80%. High alarm off (P234), 8 feet
0%, Empty level
20%. Pump 1+2 off (P214, 224), 2 feet
30%. Pump 1 on (P213), 3 feet
50%. Pump 2 on (P223), 5 feet
Page 50
ZENITH 140 UL INSTRUCTION MANUAL
50
the sump and the mA output will be representative of level where 4mA = empty level (0%) and 20mA = 10 feet (100%).
To program the Zenith 140 for Example 2 Sump control (pump down) by using the Quick Setup menu proceed as follows. If required to access Program Mode, key in the passcode 1997 and press ENTER
At the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump Up or Down
2 = Pump Down
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 1
Pump No. 2
2 = Set to relay 2
Type Alarm 1
1 = High Alarm
Alarm No. 1
5 = Set to relay 5
Xducer (P101)
2 = dB6
Measurement units (P104)
4 = Feet
Empty Level (P105)
11 feet
Span (P106)
10 feet
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Zenith 140 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
Page 51
51

Example 2 Sump Control (pump up)

A reservoir is typically used to temporarily hold liquid, and when the level reaches a specific low point, the reservoir is pumped up.
In this example, there are two pumps, which will be set to alternate duty assist, so they come on alternately. Pump 1 is to be set to relay 1, pump 2 to relay 2, and the high-level alarm to relay 3.
This will operate as follows. During normal operation, pump 1 will come on at 3 feet and pump down to 2 feet. The setpoints are then shifted to pump 2, which will come on first next time. During peak periods, when pump 1 cannot cope, pump 1 will come on at 3 feet, pump 2 will come on at 5 feet, and pump down to 2 feet. The setpoints are then shifted to pump 2, which will come on first next time.
If neither pump can cope, and the level rises to 8.5 feet, then the alarm relay (relay 3) will come on and go off when the level falls to 8 feet. This will indicate insufficient capacity of the pumps. The display will show the level in the sump and the mA output will be representative of level where 4mA = empty level (0%) and 20mA = 10 feet (100%).
Empty Distance (P105), 11 feet
100%. Span (P106), 10 feet
15%. low alarm off (P234), 1.5 feet
80%. Pump 1+2 off (P214, 224), 8 feet
0%, Empty level
10%. low alarm on (P233), 1 feet
70%. Pump 1 on (P213), 7 feet
50%. Pump 2 on (P223), 5 feet
Page 52
ZENITH 140 UL INSTRUCTION MANUAL
52
To program the Zenith 140 for Example 3 Reservoir Control (pump up) by using the Quick Setup menu proceed as follows. If required access the Program Mode, Key in the passcode 1997 and press ENTER
Using the ‘right arrow key, go to Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump Up or Down
2 = Pump Down
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 1
Pump No. 2
2 = Set to relay 2
No. of alarms
1 = 1 Alarm
Type Alarm 1
2 = Low
Alarm No. 1
5 = Set to relay 3
Xducer (P101)
2 = dB6
Measurement units (P104)
4 = Feet
Empty Level (P105)
11 feet
Span (P106)
10 feet
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Zenith 140 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed, as necessary.
Page 53
53

CHAPTER 5 PARAMETER GUIDE

This chapter describes all the parameters in your Zenith 140, as they appear in the menu system.

Menu System

Shown below is a set of charts to show you how all the various functions and features can be found using the menu system.
For further details and a full description of all parameters refer to the Parameter Listings and Descriptions section of this chapter.

Top Level Menu

Quick Setup
Application
Relays
Pump
Advanced
Digital
Inputs
FS Backup
Tariff Guard
Display
mA
Output
Pump
Efficiency
Pump
Volume
Compensation
Stability
System
Test
Device Comm
Echo
Processing
Data Logs
Important Notice
FS Backup is only available in units with firmware version 7.4.3 and higher.
Page 54
ZENITH 140 UL INSTRUCTION MANUAL
54
Application Menu
Operation
Distances
mA Input
P100
Mode
P101
Transducer
P119
mA Status
P104
Measurement
Units
P102
Material
P105
Empty Level
P106 Span
P107
Near Blanking
P108
Far Blanking
P120
Low mA In
P121
High mA In
P122
Low Level In
P123
High Level In
P124
Low mA Trim
P125
High mA Trim
Page 55
55

Relays Menu

Relay 1
P210 Type
P211
Function
P212
Alarm ID
or
Pump
Group
P214 Set 2
P213 Set 1
P215
Set 3
As
Required
P216
Allocat.
P217
Closures
P218
Fail Safe
P219
R1
Max.Rate
If
P210=2
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
P220 Type
P230 Type
P240 Type
P250 Type
P260 Type
P221
Function
P231
Function
P241
Function
P251
Function
P261
Function
P222
Alarm ID
or
Pump
Group
P232
Alarm ID
or
Pump
Group
P242
Alarm ID
or
Pump
Group
P252
Alarm ID
or
Pump
Group
P262
Alarm ID
or
Pump
Group
P223 Set 1
P233 Set 1
P243 Set 1
P253 Set 1
P263 Set 1
P224 Set 2
P234 Set 2
P244 Set 2
P254 Set 2
P264 Set 2
P225
Set 3
As
Required
P235
Set 3
As
Required
P245
Set 3
As
Required
P255
Set 3
As
Required
P265
Set 3
As
Required
P226
Allocat.
P236
Allocat.
P246
Allocat.
P256
Allocat.
P266
Allocat.
P227
Closures
P237
Closures
P247
Closures
P257
Closures
P267
Closures
P228
Fail Safe
P238
Fail Safe
P248
Fail Safe
P258
Fail Safe
P268
Fail Safe
P249
R4
Max.Rate
If
P240=2
P259
R5
Max.Rate
If
P250=2
P269
R6
Max.Rate
If
P260=2
P229
R2
Max.Rate
If
P220=2
P239
R3
Max.Rate
If
P230=2
Page 56
ZENITH 140 UL INSTRUCTION MANUAL
56

Pump “Advanced” Menu

Run On
Starting
Stopping
Exercise
Wall Cling
Storm
P349
Prime
Level
P352
Start
Delay
P348
Stop Delay
P354
Exercise
Enable
P360
Wall Cling
P370
Pump
Disable
P350
Run
Interval
P351
Run
Duration
P353
Power
Delay
P355
Idle Time
P356
Exercise
Time
P357
Minimum
Head
P371
Disable
Time
Page 57
57

Digital Inputs Menu

Common
Par
Digital
Input 1
P300
Maximum
Attempts
P301
Switch
Mode
P302
Override
Delay
P303
Minimum
Override
P304
Input Delay
P305
Input Filter
P306
Override
Level
P372 Type
P373
Function
P374
Assign.
Input 2 – P375, Input 3 – P378 Input 4 – P381, Input 5 – P384
Input 6 – P387
Digital Input 2
to
Digital Input 6
Input 2 – P376, Input 3 – P379 Input 4 – P382, Input 5 – P385
Input 6 – P388
Input 2 – P377, Input 3 – P380 Input 4 – P383, Input 5 – P386
Input 6 – P389
Digital
Input 7
P390 Type
P391
Function
P392
Assign.
Page 58
ZENITH 140 UL INSTRUCTION MANUAL
58

Float Switch Menu

Common
Par
Digital
Input 1
P330
Mode
P331
Input Filter
P332
Pump Run
Time
P333 Type
P334
Function
P335
Forced
Level
Input 2 – P336, Input 3 – P339 Input 4 – P342, Input 5 – P345
(Type)
Digital Input 2
to
Digital Input 5
Input 2 – P337, Input 3 – P340 Input 4 – P343, Input 5 – P346
(Function)
Input 2 – P338, Input 3 – P341 Input 4 – P344, Input 5 – P347
(Forced Level)
Digital
Input 6
P363 Type
P364
Function
P365
Forced
Level
Page 59
59

Tariff Guard Menu

Set Up
Peak Time
1
Peak Time 2
to
Peak Time 9
PT2 – P406, PT3 – P412, PT4 – P418, PT5 – P424,
PT6 – P430, PT7 - P436,
PT8 – P443, PT9 – P448,
Peak Time
10
PT2 – P407, PT3 – P413, PT4 – P419, PT5 – P425, PT6 – P431, PT7 - P437, PT8 – P444, PT9 – P449,
PT2 – P408, PT3 – P414, PT4 – P420, PT5 – P426, PT6 – P432, PT7 - P438, PT8 – P445, PT9 – P450,
PT2 – P409, PT3 – P415,
PT4 – P421, PT5 – P427, PT6 – P433, PT7 - P439, PT8 – P446, PT9 – P451,
PT2 – P410, PT3 – P416, PT4 – P422, PT5 – P428, PT6 – P434, PT7 - P440, PT8 – P447, PT9 – P452,
PT2 – P411, PT3 – P417, PT4 – P423, PT5 – P429, PT6 – P435, PT7 - P441,
PT8 – P448, PT9 – P453,
P393
Enable
P394
Lead Time
P395
Lag Time
P396
Minimum
Pump Time
P398
Overflow
Level
P400
PT1 Day
P401
PT1 Week
P402
PT1
Start Peak
(Date)
P403
PT1
End Peak
(Date)
P404
PT1
Start
(Time)
P404
PT1
End
(Time)
P454
PT1 Day
P455
PT1 Week
P456
PT1
Start Peak
(Date)
P457
PT1
End Peak
(Date)
P458
PT1
Start
(Time)
P459
PT1
End
(Time)
Page 60
ZENITH 140 UL INSTRUCTION MANUAL
60

Data Logs Menu

Tot. Audit
Temperature
Pump 1
Pump 2 to 5
Pump 6
P521, P531 P541, P551
Pump Hours
P522, P532 P542, P552
Pump Starts
P523, P533 P543, P553
Pump Starts
per
Hour
P524, P534 P544, P554
Pump Run On
P460
Vol. Date 1
P461
Volume 1
P462, 464,
466, 468, 470,
472, 474, 476
Total Dates
2 to 9
P463, 465,
467, 469, 471,
473, 475, 477
Totals
2 to 9
P478
Vol. Date 10
P580
Min. Temp
P478
Volume 10
P581
Min. Temp.
Date
P582
Min. Temp.
Time
P583
Max. Temp.
P584
Max. Temp.
Date
P585
Max. Temp.
Time
P586
Current
Temperature
P511
Pump 1
Hours
P512
Pump 1
Starts
P513
Pump 1
Starts
per
Hour
P514
Pump 1
Run On
P561
Pump 6
Hours
P562
Pump 6
Starts
P563
Pump 6
Starts
per
Hour
P564
Pump 6
Run On
P515
Pump 1
Draw
P516
Pump 1
Effic.
P525, P535 P545, P555
Pump Draw
P526, P536 P546, P556
Pump Effic.
P565
Pump 6
Draw
P566
Pump 6
Effic.
Page 61
61

Pumped Volume Menu

Set Up
P205
Pump Vol.
Enabled
P206
Settle Time
P207
Inflow
Method
Conversion
P600
Vessel Shape
P601
As Required
Vol. Dimension 1
P602
As Required
Vol. Dimension 2
P603
As Required
Vol. Dimension 3
P604
Calculated
Volume
P605
Volume Units
P606
Correct. Factor
P607
Max. Volume
P612, 614, 616, 618,
620, 622, 624, 626, 628, 630, 632, 634, 636, 638, 640, 642, 644, 646, 648, 650, 652, 654, 656, 658, 660, 662, 664, 666,
668, 670
Level Bkpts. 2 to 31
Breakpoints
P610
Level Bkpt. 1
P611
Vol. Bkpt. 1
P613, 615, 617, 619,
621, 623, 625, 627, 629, 631, 633, 635, 637, 639, 641, 643, 645, 647, 649, 651, 653, 655, 657, 659, 661, 663, 665, 667,
669, 671
Vol. Bkpts. 2 to 31
P672
Level Bkpt. 32
P673
Vol. Bkpt. 32
Tables
P696
Reset
Bkpts.
P697
Number
Bkpts. Set
Page 62
ZENITH 140 UL INSTRUCTION MANUAL
62

Efficiency Menu

Set Up
P187
Pump Effic.
P188
Calib. Delay
P189
Cal. Duration
P190
Persist Cnt.
P191
Demote
Pumps
P192
Demote
Flags
P193
Calib. Pumps
Page 63
63

Display Menu

Options
Fail Safe
Auxiliary
Bargraph
P802
Display
Offset
P801
Decimal
Places
P804
Display
Conversion
P805
Display
Source
P808
Fail Mode
P809
Fail Time
P810
Units
P811
Alarms
P812
Pumps
P813
Control
P814
Misc.
P815
Auxiliary
Source
P816
Totaliser
(R)
P817
Auxiliary
Offset
Totaliser
P829
Bargraph
P820
Totaliser
P821
Totaliser (R)
P822
Totaliser
Decimal
P823
Totaliser
Multiplier
P800
Display
Units
Page 64
ZENITH 140 UL INSTRUCTION MANUAL
64

mA Output Menu

Compensation Menu

Offset
Temperature
Velocity
P851
Measurement
Offset
P852
Temperature
Source
P854
Fixed
Temperature
P860
Sound
Velocity
P854
Fixed
Temperature
Range
Operation
Setpoint
Limits
Trim
Fail Safe
Allocation
P830
mA Out
Range
P831
mA Out
Mode
P834
Low
Value
P836
Low
Limit
P835
High
Value
P838
Low
mA
Trim
P840
Fail
Mode
P841
Allocation
P837
High
Limit
P839 High
mA
Trim
P854
Fixed
Temperature
P853
Allocation
Page 65
65

Stability Menu

Echo Processing Menu

Damping
Indicator
Rate
Filters
P870
Fill
Damping
P871
Empty
Damping
P872
Fill
Indicator
P873
Empty
Indicator
P874
Rate Update
P875
Rate Time
P876
Rate Distance
P877
Rate Value
P878
Lower Cutoff
P880
Gate Mode
P881
Fixed Distance
P882
Process Filter
P884
Peak Percent
Xdr. 1 Status
Xdr. 2 Status
P900
Xdr. 1 Status
P901
Echo
Confidence 1
P902
Echo Strength 1
P903
Average Noise 1
P904
Peak Noise 1
P905
Sensitivity 1
P906
Side Clearance 1
P910
Xdr. 2 Status
P916
Side Clearance 2
P915
Sensitivity 2
P914
Peak Noise 2
P913
Average Noise 2
P912
Echo Strength 2
P911
Echo
Confidence 2
Page 66
ZENITH 140 UL INSTRUCTION MANUAL
66

System Menu

Passcode
Backup
System
Info
Date
&
Time
LED
Colour
Daylight
Saving
P921
Enable Code
P925
Parameter
Backup
P926
Software
Revision
P931
Date
P935
Off
Colour
P970
DST
Enable
P922
Passcode
P927
Hardware
Revision
P928
Serial
Number
P929
Site
Ident.
P930
Factory
Default
P931 Time
P932
Date
Format
P936
Alarm
Colour
P937
Pump
Colour
P938
Control
Colour
P939
Misc.
Colour
P971
DST
Difference
P972
DST
Start Time
P973
Start Day
P974
Start Week
P975
Start
Month
P976
DST
End Time
P977
End Day
P978
End Week
P979
End Month
Page 67
67

Device Comm Menu

RS485 Setup
(Optional)
If Comms.
Type is
Modbus
P130
Device
Mode
P131
Protocol
P132
Device
Addr.
P133
Device
Baud
RS232
Setup
P61
Comms Baud
Remote
Alarm
P144
Call Type
P145
Tel. No. 1
P146
Tel. No. 2
P147
Tel. No. 3
P134
Parity
P135
Stop Bit
P136
Data
Format
P137
Delay in
milli sec.
If Comms.
Type is
Profibus
P132
Device
Addr.
P143
Addr. Lock
P148
Timed Out
P149
Retry No.
Page 68
ZENITH 140 UL INSTRUCTION MANUAL
68

Test Menu

Simulation
Hardware
P980
Simulate
P981
Increment
P982 Rate
P983
Start Level
P984
Incremental
Change
P990
Self Test
P991
Hardware Test
P992
mA Out Test
P993
mA In Test
P994
Transducer Test
P995
Keys Test
P996
Relay Test
Page 69
69
Application Parameters Operation

P100 Mode of Operation

This parameter sets the mode of operation, when in run mode, and can be set to one of the following:
OPTION
DESCRIPTION
1 = Distance (Default)
Display shows the distance from the transducer face to the surface of the material measured.
2 = Level
Shows how full a vessel is.
3 = Space
Shows how empty a vessel is.
4 = Average Level
Display shows the average level of two points of measurement.
5 - Differential
Display shows the Differential level between 2 points of measure.

P101 Xducer (Transducer)

This parameter should be set to the transducer being used with the unit, and can be set to one of the following:
OPTION
DESCRIPTION
0 = Auxiliary
Use a mA input
1 = dB3
Transducer is a dB3. Range = 0.41 to 9.843 feet
2 = dB6 (default)
Transducer is a dB6. Range = 0.984 to 19.685 feet
3 = dB10
Transducer is a dB10. Range = 0.984 to 32.808
4 = dB15
Transducer is a dB15. Range =1.640 to 49.213 feet
5 = dB25
Transducer is a dB25. Range = 1.969 to 82.021 feet
6 = dB40
Transducer is a dB40. Range = 3.937 to 131.234 feet
7 = dBS6
Transducer is a dBS6. Range = 0.656 to 19.685 feet
8 = dBMach3
Transducer is a dBMach3. Range 0 to 7.956 feet
*11 = dBR16
Transducer is a mmWave radar. Range 0.25 to 52.49 feet
*12 = dBR8
Transducer is a mmWave radar. Range 0.25 to 26.25 feet
Important Notice
*Please consult your local Pulsar distributor for the versions of firmware that the mmWAVE radars are available in.
Page 70
ZENITH 140 UL INSTRUCTION MANUAL
70

P102 Material

This parameter should be set to the type of material being monitored.
OPTION
DESCRIPTION
1 = Liquid (Default)
Used for liquids and flat solid materials.
2 = Solid
Used for sold material that is heaped or at an angle.
3 = Closed Tank
Use for applications within a closed tank or where a secondary echo response may become focused to create a larger echo than the first.

P103 Input 2

The 4-20 mA input can be used to replace the transducer for applications where an ultrasonic transducer cannot be used.
Use this parameter to set the second input device when using in Average or Differential Mode, and P101 Transducer = 0 (Auxiliary Input).
OPTION
DESCRIPTION
0 = None (Default)
Use the optional mA input (Please consult Pulsar for availability).
1 = dB3
Transducer is a dB3. Range = 0.41 to 9.843 feet
2 = dB6
Transducer is a dB6. Range = 0.984 to 19.685 feet
3 = dB10
Transducer is a dB10. Range = 0.984 to 32.808
4 = dB15
Transducer is a dB15. Range =1.640 to 49.213 feet
5 = dB25
Transducer is a dB25. Range = 1.969 to 82.021 feet
6 = dB40
Transducer is a dB40. Range = 3.937 to 131.234 feet
7 = dBS6
Transducer is a dBS6. Range = 0.656 to 19.685 feet
8 = dBMach3
Transducer is a dBMach3. Range 0 to 7.956 feet
*11 = dBR16
Transducer is a mmWave radar. Range 0.25 to 52.49 feet
*12 = dBR8
Transducer is a mmWave radar. Range 0.25 to 26.25 feet
*The signal emanates from the curved face of the Radar, but for the purposes of measurement it is taken from the drip shield.
Page 71
71

Dimensions

P104 Measurement Units

This parameter sets the units you want to use for programming and display.
OPTION
DESCRIPTION
1 = metres
All units of measurement are Metres
2 = cm
All units of measurement are Centimetres
3 = mm
All units of measurement are Millimetres
4 = feet (Default)
All units of measurement are Feet
5 = inches
All units of measurement are Inches

P105 Empty Level

This parameter is to be set to the maximum distance from the face of the transducer to the empty point, in P104 Measurement Units. Note this value affects span as well, (see the following important information notices), so should be set before span.

P106 Span

This parameter should be set to the maximum distance from the Empty Level (P105) to the maximum material level. It is automatically set to be
equal to the Empty Level (P105) less the Near Blanking distance (P107) when you set the empty level.
Important Notice
When changing the Empty Distance (P105) you can also recalculate the values for the Span so that it equals the empty distance (P105) minus Near Blanking (P107) and the Relay Setpoints, so that they remain at the same percentage values of the empty distance as they were before you changed the empty distance (P105). You will be asked the question
“Recalculate Span?” if you choose yes (enter 1), then the span will be
recalculated. Any other answer will leave the span at its original value.
You will then be asked if you want to “Recalculate Setpoints?”, if you
choose yes (enter 1), then all Relay Setpoints will be recalculated as a percentage of the new empty distance. Any other answer will leave the setpoints at their original values.
Important Notice

When using the dB Mach 3 the empty distance is measured from the end of the horn to the empty point in P104 Measurement Units.

Page 72
ZENITH 140 UL INSTRUCTION MANUAL
72

P107 Span

This parameter is the distance from the face of the transducer that is not measurable and is pre-set to the minimum value dependant on the Transducer (P101) selected. It should not be set to less than this figure, but can be increased, typically to ignore close in obstructions.
TRANSDUCER
NEAR BLANKING DISTANCE
P101 = dBMach3
Default blanking distance = 0.00 feet
P101 = dB3
Default blanking distance = 0.410 feet
P101 = dB6
Default blanking distance = 0.984 feet
P101 = dB10
Default blanking distance = 0.984 feet
P101 = dB15
Default blanking distance = 1.640 feet
P101 = dB25
Default blanking distance = 1.969 feet
P101 = dB40
Default blanking distance = 3.937 feet
P101 = dBS6
Default blanking distance = 0.656 feet
P101 = dBR16
Default blanking distance = *0.252 feet
P101 = dBR8
Default blanking distance = *0.252 feet
*The signal emanates from the curved face of the radar, but for the purposes of measurement it is taken from the drip shield.

P108 Far Blanking Distance

This is the distance (as a percentage of the empty level P105) beyond the empty point that the unit will be able to measure, and by default is pre-set to 20% of the empty level.
If the surface being monitored can be extended beyond the empty level (P105) then the far blanking distance can be increased to a max. of 100% of the empty level, provided it does not exceed the max range of the transducer being used. This parameter is always entered as a % of the empty level.
Page 73
73

mA Input

The 4-20 mA (Auxiliary) input is available as an option (Consult Pulsar for details of availability), and can be used to replace the transducer for applications where an ultrasonic transducer cannot be used.

P119 mA Status

If P101 (Xducer) = 1 (Auxiliary)
This indicates the status of the Auxiliary input if selected
OPTION
DESCRIPTION
1 = mA OK (Default)
mA Input present and functioning correctly
1 = mA Open
No input (device) is being detected
2 = mA Short
Input is indicating a fault condition

P120 Low mA in

This parameter sets the current input figure that is used to represent empty when using the optional current input, instead of an ultrasonic transducer.
Default = 4ma

P121 High mA in

This parameter sets the current input figure that is used to represent span when using the optional current input, instead of an ultrasonic transducer.
Default= 20mA

P122 Low Level in.

This parameter sets the distance to empty point when using the optional current input, (Aux. input) instead of an ultrasonic transducer.
Default = 0.00 feet

P123 High Level in

This parameter sets the distance that is full (span) when using the optional current input, (Aux. input) instead of an ultrasonic transducer.
Default = 19.685 feet

P124 Low mA Trim

This parameter allows you to “calibrate” the Zenith to the Low mA Input from the device being used. If the expected low value, from the device connected to the mA Input, is not displayed, then you can trim it using this parameter.
Page 74
ZENITH 140 UL INSTRUCTION MANUAL
74

P125 High mA Trim

This parameter allows you to “calibrate” the Zenith to the High mA Input from the device being used. If the expected high value, from the device connected to the mA Input, is not displayed, then you can trim it using this parameter.
Important Notice
When using the auxiliary input, all settings relating to measurement should be entered in relation to level i.e., zero (empty) to 100% (full) and not distance. This also means that the device you are connecting should provide an input that will change with level.
Page 75
75

Relay Parameters

All relay related parameters are prefixed with a 2**. The second digit of the three-figure parameter number denotes the relay
number as follows:
21* parameters for Relay 1
22* parameters for Relay 2
23* parameters for Relay 3
24* parameters for Relay 4
25* parameters for Relay 5
26* parameters for Relay 6
The third digit selects specific parameter for the setting of the relays, which can be selected individually and results in the following parameter numbers for each relay:
Relay 1 210 to 219
Relay 2 220 to 229
Relay 3 230 to 239
Relay 4 240 to 249
Relay 5 250 to 259
Relay 6 260 to 269
Page 76
ZENITH 140 UL INSTRUCTION MANUAL
76

P210, 220, 230, 240, 250, 260 - Relay Type

This parameter defines what type each relay should be, see the table below for available options:
OPTION
DESCRIPTION
0 = Not in use (Default)
Relay is not in use or programmed and the LED will always be off.
1 = Alarm
Relay is programmed as an alarm relay, which will de- energise ON, and energise OFF. This will ensure an alarm is raised if the power fails to the unit.
2 = Pump
Relay is programmed as a pump relay, which will energise ON, and de-energise OFF.
3 = Control
Relay is programmed as a control relay, which will energise ON, and de-energise OFF.
4 = Miscellaneous
Relay is programmed as a miscellaneous relay, which will energise ON, and de-energise OFF.
5 = Pump by time
Relay is programmed as a pump relay, which will energise at its ON level setpoint, and de-energise at its
OFF level setpoint or after a predetermined time period, whichever occurs first.
Page 77
77

Alarms

P210, 220, 230, 240, 250, 260 = 1 (Alarm) The second parameter for each relay determines the function of the alarm.

P211, 221, 231, 241, 251, 261 – Relay Function

OPTION
DESCRIPTION
0 = Off (Default)
Relay will not operate.
1 = Level
Alarm is based on the level in the vessel, and the type of level alarm (P212, 222, 232, 232, 242, 252, 262) and two setpoints must be set (P223, 223, 233 & 214, 224, 234, 244, 254, 264). Setpoints are entered in display units or % of span as referenced to empty level.
2 = Rate of Change
Alarm is based on the rate of change of level in the vessel, and the type of rate of change alarm (212, 222, 232, 242, 252,
262), and two setpoints must be set (213 & 223, 214 & 224, 234 & 234, 243 & 244, 253 & 254, 263 & 264). Setpoints are entered in Display Units per minute or % of span per minute and a negative value should be entered for a Rate Alarm on a de-creasing level, and a positive value for an increasing level.
3 = Temperature
Alarm is based on the temperature, and the type of temperature alarm (P212, 222, 232, 242, 252, 262) and two setpoints must be set (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264). The temperature used depends on the temperature source selected (P852). Setpoints are entered in oC.
4 = Loss of Echo
Alarm is raised if the Failsafe Timer (P809) expires. No setpoints required.
5 = Loss of Clock
Alarm is raised if the expires. No setpoints required.
6 = Pump Efficiency
When Pump Efficiency is enabled, Alarm is based on the Efficiency of the pump which is allocated to the relay I.D. (P212, 222, 232, 242, 252, 262) and two setpoints must be set (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254,
264). Setpoints are entered in %.
7 = Device Fail
Alarm is raised if a device, connected to the relay assigned in alarm ID (P212, 222, 232, 242, 252, 262), fails. E.g. pump is put out of service. No setpoints are required.
8 = Device Alarm
Alarm is raised if a fail signal is detected on the digital input as assigned in alarm ID (P212, 222, 232, 242, 252, 262) No setpoints are required.
Page 78
ZENITH 140 UL INSTRUCTION MANUAL
78
OPTION
DESCRIPTION
15 = Tariff Alarm (Available in firmware v7.5.1 and greater
Alarm is raised when the unit enters Tariff Guard mode. Tariff Guard enable (P393) must be set to ‘1’ for this option to be selectable. No setpoints are required
To set figures in % press the hot key to show and enter %
figure relative to empty level.
Important Notice
The Loss of Echo, and Loss of Clock will also be shown on the display as “Lost Echo”, and “Lost Clock” respectively.
Page 79
79
The third parameter for each relay determines the Alarm ID for the relay you wish to set.

P212, 222, 232, 242, 252, 262 – Relay Alarm ID

When P211, 221, 231, 241, 251, 261 = 4 (Loss of Echo) or 5 (Loss of Clock). This parameter has no function and will not be displayed. P211, 221, 231, 241, 251, 261 = 1 (Level), 2 = Rate of Change or 3 (Temp)
This parameter defines which alarm type, or identification, the relay should respond to, as follows:
OPTION
DESCRIPTION
SETPOINTS
1 = General (Default)
Relay goes “ON” when the
value reaches the ON
setpoint and goes “OFF”
when the value reaches the OFF setpoint.
P213, 223, 233, 243, 253, 263 is ON Setpoint; P214, 224, 234, 244, 254, 264 is OFF Setpoint
2 = High
Relay goes “ON” when the
value rises to the ON
setpoint and goes “OFF”
when the value lowers to the OFF setpoint.
ON>OFF Relay Setpoints P213, 223, 233, 243, 253, 263 and P214, 224, 234, 244, 254, 264. Setpoints can be set in any order as
the unit ‘knows’ that you
are setting a high-level alarm.
3 = HiHi
Same as 2 = High, but different identifier
4 = Low
Relay goes “ON” when the
value lowers to the ON
setpoint and goes “OFF”
when the value rises to the OFF setpoint.
ON<OFF Relay Setpoints P213, 223, 233, 243, 253, 263 and P214, 224, 234, 244, 254, 264. Setpoints can be set in any
order as the unit ‘knows’
that you are setting a low­level alarm.
Page 80
ZENITH 140 UL INSTRUCTION MANUAL
80
OPTION
DESCRIPTION
SETPOINTS
5 = LoLo
Same as 4 = Lo, but different identifier
6 = In bounds
Relay goes “ON” if value
is inside the zone between the two setpoints.
Relay Setpoints, P213, 223, 233, 243, 253, 263 and P214, 224, 234, 244, 254, 264 can be set in any order
as the unit ‘knows’ that you
are setting an inbounds alarm.
7 = Out of bounds
Relay goes “ON” if value
is outside the zone between the two setpoints.
Relay Setpoints P213, 223, 233, 243, 253, 263 and P214, 224, 234, 244, 254, 264 can be set in any order
as the unit ‘knows’ that you
are setting an out of bounds alarm.
When P211, 221, 231, 241, 251 = 4 (L0ss of Echo) or 5 (Loss of Clock)
This parameter has no function and will not be displayed.
When P211, 221, 231, 241, 251, 261 = 6 Pump Efficiency
This parameter assigns the alarm to the appropriate pump relay as detailed below.
OPTION
DESCRIPTION
0 = Off (Default)
Relay will not operate
1 = Relay 1
Alarm is assigned to pump on Relay 1
2 = Relay 2
Alarm is assigned to pump on Relay 2
3 = Relay 3
Alarm is assigned to pump on Relay 3
4 = Relay 4
Alarm is assigned to pump on Relay 4
5 = Relay 5
Alarm is assigned to pump on Relay 5
7 = All
Alarm is assigned to relays designated as pump
The fourth parameter and the fifth parameter for each relay set the Alarm ON” and “OFF” points. For a high alarm, the “ON” is set higher than OFF”. For low alarm, then “ON” is set lower than OFF”. See the appropriate alarm ID, table (P212, 222, 232, 242, 252, 262) for further information.
Page 81
81

P212, 222, 232, 242, 252, 262 Relay Alarm ID

When P211, 221, 231, 241, 251, 261 = 7 (Device Fail)
This parameter defines which failed device relay, the alarm should respond to, as follows.
OPTION
DESCRIPTION
SETPOINTS
1 = Fail Relay 1 (Default)
Relay goes “ON” when a device failure is detected on relay 1.
None
2 = Fail Relay 2
Relay goes “ON” when a device failure is detected on relay 2.
None
3 = Fail Relay 3
Relay goes “ON” when a device failure is detected on relay 3.
None
4 = Fail Relay 4
Relay goes “ON” when a device failure is detected on relay 4.
None
5 = Fail Relay 5
Relay goes “ON” when a device failure is detected on relay 5.
None
6 = Fail Relay 6
Relay goes “ON” when a device failure is detected on relay 6.
None
7 = Any 1 Fail
Relay goes “ON” when a device failure is detected on any 1 relay.
None
8 = Any 2 Fail
Relay goes “ON” when a device failure is detected on any 2 relays.
None
Page 82
ZENITH 140 UL INSTRUCTION MANUAL
82

P212, 222, 232, 242, 252, 262 Relay Alarm ID

When P211, 221, 231, 241, 251, 261 = 8 (Device Alarm)
This parameter defines which digital input, the alarm should respond to, as follows.
OPTION
DESCRIPTION
SETPOINTS
1 = Fail Input 1 (Default)
Relay goes “ON” when a device fail signal is detected on digital input 1.
None
2 = Fail Input 2
Relay goes “ON” when a device fail signal is detected on digital input 2.
None
3 = Fail Input 3
Relay goes “ON” when a device fail signal is detected on digital input 3.
None
4 = Fail Input 4
Relay goes “ON” when a device fail signal is detected on digital input 4.
None
5 = Fail Input 5
Relay goes “ON” when a device fail signal is detected on digital input 5.
None
6 = Fail Input 6
Relay goes “ON” when a device fail signal is detected on digital input 6.
None
7 = Fail Input 7
Relay goes “ON” when a device fail signal is detected on digital input 7.
None
Page 83
83
When P211, 221, 231, 241, 251, 261 = 1 (Level), 2 (Rate of Change) or 3 (Temperature) or 6 (Efficiency)

P213, P223, P233, 243, 253, 263 - Relay Setpoint 1

Determines the “ON” or “OFF” point for the alarm according to the ID selected.

P214, P224, P234, 244, 254, 264 - Relay Setpoint 2

Determines the “ON” or “OFF” point for the alarm according to the ID selected.
To set figures in % press the hotkey to show and enter % figure, relative to empty level.
When P211, 221, 231, 241, 251, 261 = 4 (Loss of Echo), 5 (Loss of Clock), 7 (Device Fail) or 8 (Device Alarm)
This parameter has no function and will not be displayed.
Important Notice
Setpoints are entered in values according to the function selected. Level - entered in Display Units or % of span as referenced to Empty Level.
Rate of Change - entered in Display Units per minute or % of span per minute.
For an alarm on an increasing level enter setpoints as a positive value, for an alarm on a decreasing level enter setpoints as a negative value. Temperature - entered in ºC.
See the appropriate alarm function, table (P211, 221, 231, 241, 251 and 261) for further information.
Page 84
ZENITH 140 UL INSTRUCTION MANUAL
84

Pumps

P210, 220, 230, 240, 250, 260= 2 (Pump)
When a relay is being used for a pump function, the second parameter determines the pump duty that will be used to determine the operating cycle.

P211, 221, 231, 241, 251, 261 – Relay Function

This parameter defines which pump duty the relay should respond to as follows:
PUMP DUTY
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Fixed duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints. (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264).
2 = Fixed duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints. (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264).
3 = Alternate duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints, (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264). but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
4 = Alternate duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints, (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264). but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
Page 85
85
PUMP DUTY
DESCRIPTION
5 = Duty backup and assist
First pump comes on, if it cannot cope, it goes off and next pump comes on (duty backup). This continues until the last pump comes on and if it cannot cope the first pump comes back on to assist the last pump (duty assist) if the level continues to rise all other pumps will come on (assist) in turn until the level decreases to the pump off points. Each pump has its own setpoints, (P213, 223, 233, 243, 253 & P214, 224, 234, 244, 254, 264).
6 = Service ratio duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264). And a service ratio setting. The third setpoint (P215, 225, 235, 245, 255, 265) is used to set the service ratio. Each time a pump is required to start then the pump with the least running hours (with respect to the service ratio) is started (i.e. the setpoints are re­assigned accordingly). For example, if two pumps A and B have the service ratio set to 2 and 1 respectively, then pump A will operate for twice as many hours as pump B.
Page 86
ZENITH 140 UL INSTRUCTION MANUAL
86
PUMP DUTY
DESCRIPTION
7 = Service ratio duty backup
The first pump switched on is the first pump to be switched off, regardless of the set points, so the setpoints are dynamically changed to enable this. If a pump fails to meet the demand (due to malfunction, intake blockage and so on), then it is stopped, and another pump shall take over. Each time a pump is required to start then the pump with the least running hours (with respect to the service ratio) is started (i.e. the setpoints are re-assigned accordingly). Each pump has its own setpoints (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264). The third setpoint (P215, 225, 235, 245, 255, 265) is used to set the service ratio. E.g., if two pumps A and B have the service ratio set to 2 and 1 respectively, then pump A will operate for twice as many hours as pump B.
8 = First On First Off Alternate duty assist
The first pump switched on is the first pump to be switched off, etc. regardless of the set points, so the setpoints are dynamically changed to enable this.
9 = Service Ratio Standby
When a service ratio duty is being used, on all other pumps in use, the standby pump can be started on a ratio basis only, when it will assume the setpoints of the next pump to start. The third setpoint (P215, 225, 235, 245, 255, 265) is used to set the service ratio.
10 = Two Pump Sets
There are four pumps. Two rotate their start-up sequence with each other. If the two pumps cannot keep up, the level rise to the setpoints of the other two pumps which take over and rotate their sequence with each other.
Important Notice
The pumps are started and stopped at the “ON” and “OFF” setpoints. To pump down (reduce level) then set “ON” higher than “OFF”. To pump up (increase level) then set “ON” lower than “OFF”.
Page 87
87
The third parameter for each relay determines the pump group. You can have two groups of pumps, and all similar duties within that group will operate together.

P212, 222, 232, 242, 252, 262 – Relay Pump Group

By default, all pump groups are set to 1, but if you want to have another group, then set this parameter to 2, for each pump relay that should operate together as part of a second group.
The fourth parameter and the fifth parameter for each relay set the pump ON” and “OFF” points, which are entered in Measurement units P104. For
pump down the “ON” is set higher than OFF”. For pump up then “ON” is
set lower than OFF”. See the appropriate pump duty, function table (P212, 222, 232, 242, 252, 262) for further information.

P213, 223, 233, 243, 253, 263 – Relay Setpoint 1

This parameter determines the ‘ON’ point of the pump.

P214, 224, 234, 244, 254, 264 – Relay Setpoint 2

This parameter determines the ‘OFF’ point of the pump.
The sixth parameter will determine the service ratio that will be used to switch the pump, when pump duty selected is a Service Ratio duty.
P210, 220, 230, 240, 250 = 6, 7 or 9 (Service ratio)

P215, 225, 235, 245, 255, 265 – Relay Setpoint 3

This parameter determines the Service Ratio in values of %. See the appropriate pump duty function, table (P211, 221, 231, 241, 251, 261), for further information.

P219, 229, 239, 249, 259, 269 – Relay Max Rate

This parameter will allow a pump to be switched at a pre-determined Rate of change of Level, irrespective of the “ON” level setpoint P213, 223, 233,
243, 253, 263. Once a pump relay has been switched “ON” by the pre­determined Rate of Change, it will remain energised until the level reaches the “OFF level setpoint P214, 224, 234, 244, 254, 264.
Max. Rate is entered in Measurement Units (P104) per minute and can be entered as either positive (increasing level) or negative (decreasing level) values.
Page 88
ZENITH 140 UL INSTRUCTION MANUAL
88

Control

P210, 220, 230, 240, 250, 260 = 3 (Control)
When a relay is being set as a control relay, the second parameter that will be displayed in the menu determines its function.
P211, P221, P231, 241, 251, 261 - Relay Function,
This function allows the relay to be assigned to specific control functions and mainly work in relation to time.
OPTIONS
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Time
Relay will energise ON” after the Cycle time that is set in Relay Setpoint 2 (P214, 224, 234). And turns “OFF”, de-
energises, after the On-Time Period that is set in Relay Setpoint 1 (P213, 223, 233, 243, 253)
2 = Storm
Relay will energise ON” when storm conditions are in effect and, de-energise OFF” when storm conditions cease. Two setpoints are required, Upper Storm “ON”, (P213, 223, 233, 243, 253, 263) and Lower Storm, “OFF” (P214, 224, 234, 244, 254, 264). This allows the relay to be used to activate a device as a result of high levels such as a storm condition e.g. opening a gate valve to divert storm overflow into a holding vessel.
3 = Aeration
Relay will energise ON” after each Cycle time as set in Relay Setpoint 2 (P214, 224, 234, 244, 254, 264). And turns OFF”, de-energises, after the set On Time Period as set in Relay Setpoint 1 (P213, 223, 233, 243,253, 263). This can be used to activate a device based upon elapsed time since All Pumps have been “OFF”, such as the introduction of fresh air to reduce gas concentration.
Page 89
89
OPTIONS
DESCRIPTION
4 = Flush Valve
Relay will energise “ON” when Flush condition is in effect and goes off when Flush condition is cleared. A relay being used for Flush Valve/Pump must be assigned to one of the main pumps in use. Flush relay Alarm ID (P212, 222, 232, 242, 252, 262) is used to enter the relay number, to which the assigned pump is connected. Flush Valve/Pump relay requires three setpoints. The first set point (P213, 223, 233, 243, 253, 263) determines the Flush Interval, which is the number of main pump cycles that should occur before the Flush Valve/Pump operates. The second setpoint (P214, 224, 234, 244, 254, 264), sets the number of Flush cycles the Flush Valve/Pump will operate for. This means that the Flush Valve will be operated for several main pump starts (Flush Cycles) after which the Flush Valve activity will cease until the Flush Interval comes around again. Setpoint three of the Flush Valve/Pump relay sets the Flush Duration, (P215, 225, 235, 245, 235, 236) this is the duration for Flush
5 = Step Time
Step Time Control allows relays to be used to control a device, such as a motorised valve or gate, in order to maintain the level within two predetermined points. Relays will energise ON” when Step Time condition is in effect and
de-energisesOFF” when Step Time goes off. One relay will be required to control an increase in level, (‘open’ the device)
and a second relay is required to control a decrease in level, (‘close’ the device). Alarm ID (P212, 222, 232, 242, 252, 262) is used to assign the relay to control either the open or close condition. Step Time Control relay requires three setpoints. The first set point (P213, 223, 233, 243, 253, 263) determines the level, at which the relay is to be activated, (N.B. level setpoint for open relay, increase the level, must be lower than the setpoint for the close relay, decrease the level). The relay will energise ON” after the Limit time that is set in Relay Setpoint 3 (P215, 225, 235, 245, 255, 265). And turns OFF”, de-energises, after the Drive Period that is set in Relay Setpoint 2 (P214, 224, 234, 244, 254, 264).
Page 90
ZENITH 140 UL INSTRUCTION MANUAL
90
OPTIONS
DESCRIPTION
6 = Differential Control
Relay will energise ON” when a differential condition is in effect and, de-energise OFF” when the differential conditions cease. Two setpoints are required, Differential
control “ON”, (P213, 223, 233, 243, 253, 263) and Differential control, “OFF” (P214, 224, 234, 244, 254, 264).
This allows the relay to be used to activate a device because of a differential level, between two points e.g. operate a rake on a screen.
The third parameter for each relay determines the assignment or condition of the relay, where required.

P212, P222, P232, P242, P252, 262 - Relay Alarm ID/Pump Group,

P211, 221, 231, 241, 251, 261 = 1, 2, 3 or 6
This parameter has no function and will not be displayed.
P211, 221, 231, 241, 251, 261 = 4 (Flush Valve)
If the relay is selected for Flush Valve/Pump, then this parameter is used to determine to which pump the Flush function is assigned. Enter the relay
number to which the assigned pump is connected. P211, 221, 231, 241, 251, 261 = 5 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign the relay to the 0 = Open condition (increase level) or 1 = Close condition (decrease level).
The fourth parameter, fifth parameter and sixth parameter are set to
determine the switch points, “ON” and “OFF” for the relay and where
required the order of start. See control function, table (P211, 221, 231) for further information.
P213, P223, P233, P243, P253 Relay Setpoint 1
P211, 221, 231, 241, 251, 261 =1 (Time)
This parameter determines the “Time Period” that the relay will remain “ON”. Relay Setpoints are entered in Minutes. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261)
for further information.
Page 91
91
P211, 221, 231, 241, 251, 261 =2 (Storm)
Relay Setpoint 1 is entered in values of Measurement Units (P104) See the appropriate relay function tables (P211, 221, 231, 241, 251, 261)
for further information.
P211, 221, 231, 241, 251, 261 =3 (Aeration)
Relay Setpoint 1 is entered in Minutes to set Cycle Time See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261)
for further information.
P211, 221, 231, 241, 251, 261 =4 (Flush Valve)
Relay Setpoint 1 is entered in Pump cycles to set Flush Interval. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261)
for further information.
P211, 221, 231, 241, 251, 261 =5 (Step Time)
Relay Setpoint 1 is entered in values of Measurement Units (P104) See the appropriate relay function tables (P211, 221, 231, 241, 251, 261)
for further information.
P211, 221, 231, 241, 251, 261 =6 (Differential)
Relay Setpoint 1 is entered in values of Measurement Units (P104) See the appropriate relay function tables (P211, 221, 231, 241, 251, 261)
for further information.

P214, P224, P234, P244, P254 Relay Setpoint 2

P211, 221, 231, 241, 251, 261 =1 (Time)
This parameter determines the “Cycle Time” for the operation of the relay. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261)
for further information.
P211, 221, 231, 241, 251, 261 =2 (Storm)
Relay Setpoints are entered in values of Measurement Units (P104) See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261)
for further information.
Page 92
ZENITH 140 UL INSTRUCTION MANUAL
92
P211, 221, 231, 241, 251, 261 =3 (Aeration)
Relay Setpoints are entered in Minutes to set Time Period that the relay will remain ON. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261) for further information.
P211, 221, 231, 241, 251, 261 =4 (Flush Valve)
Relay Setpoints are entered in cycles to set the number of Flush cycles. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261)
for further information.
P211, 221, 231, 241, 251, 261 =5 (Step Time)
Relay Setpoints are entered in Seconds to set Drive Period, the time that the relay will remain ON See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261) for further information.
P211, 221, 231, 241, 251, 261 =6 (Differential)
Relay Setpoints are entered in values of Measurement Units (P104). See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261)
for further information.

P215, P225, P235, P245, P255, 265 Relay Setpoint 3

P211, 221, 231, 241, 251, 261 = 4 (Flush Valve)
Enter desired Flush duration in seconds. See the appropriate relay Function tables (P211, 221, 231, 241, 251) for
further information.
P211, 221, 231, 241, 251, 261 = 5 (Step Time)
This parameter is used to determine the Limit Time between each Drive Period. Relay Setpoints are entered in Minutes, during which time the relay will remain OFF.
See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261) for further information.
Page 93
93

Miscellaneous

P210, 220, 230, 240, 250 = 4 (Miscellaneous)
When a relay is set to be a miscellaneous relay, the second parameter determines its function.

P211, 221, 231, 241, 251, 261 – Relay Function

This function allows the relay to work in relation to a clock or a specific event and will be set to activate in relation to Real Time.
OPTIONS
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Clock
Relay will energise ON at a specified time each day as set in Relay Setpoint 1 (P213, 223, 233, 243, 253, 263). And turns OFF, de-energises, after the specified “On Time” period as set in Relay Setpoint 2 (P214, 224, 234, 244, 254, 264)
2 = Totaliser
Relay will energise ON momentarily each time the specified flow has passed as set in Relay setpoint 1 (P213, 223, 233, 243, 253, 263), this parameter sets the multiplication factor which will be applied to the on­board totaliser (P820) to determine the switch point of the relay. E.g., if the totaliser is set to totalise in cubic metres and the relay is required to provide a closure every 10,000 litres Relay setpoint 1 would be set to 10. Relay setpoint 2 (P214, 224, 234, 244, 254, 264) can be used to select the time the relay will remain closed in seconds.
Important Notice
When using a Relay to control a device at a specified time of day ensure that the Time P932 is set correctly. And if required, enable Daylight Saving for the appropriate time difference P970 – P979.
Page 94
ZENITH 140 UL INSTRUCTION MANUAL
94
The third parameter has no function when miscellaneous relay is chosen and will not be displayed.
The fourth parameter, and fifth parameter, are set to determine the switch points, “ON” and “OFF” for the relay. See miscellaneous function table (P211, 221, 231, 241, 251, 261) for further information.
P211, 221, 231, 241, 251, 261 = 1 (Clock)

P213, 223, 233, 243, 253, 263 – Relay Setpoint 1

Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at which relay will energise. Default = 00:00 (HH:MM)

P214, 224, 234, 244, 254, 264 – Relay Setpoint 2

Relay Setpoints are entered in seconds to set the Time Period that the relay
will remain ‘ON’. Default = 0.00 mins.
P210, 220, 230= 2 (Totaliser)

P213, 223, 233, 243, 253, 263 – Relay Setpoint 1

Relay Setpoints are entered as a factor by which the on-board totaliser (P820) should be multiplied by to provide a relay closure. Default = 0.00

P214, 224, 234, 244, 254, 264 – Relay Setpoint 2

Relay Setpoints are entered in seconds to set the Time Period that the relay will remain ‘ON’. Default = 0.00 secs.

Pump by Time

When a relay is assigned to Pump by Time the pump will come on (energise) at its normal “ON” level setpoint, and de-energise at its OFF level setpoint or after a predetermined time period, whichever occurs first.
P210, 220, 230, 240, 250, 260 = 5 (Pump by Time) When a relay is being used for a pump by time function, the second
parameter determines the pump duty that will be used to determine the
operating cycle.
Page 95
95
P211, P221, P231, P241, P25, 2611 - Relay Function,
This parameter defines which pump duty the relay should respond to as follows.
PUMP DUTY
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Fixed duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints. (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264).
2 = Fixed duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints. (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264).
3 = Alternate duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints, (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264). but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
4= Alternate duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints, (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264) but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
Page 96
ZENITH 140 UL INSTRUCTION MANUAL
96
PUMP DUTY
DESCRIPTION
5= Duty backup and assist
First pump comes on, if it cannot cope, it goes off and next pump comes on (duty backup). This continues until the last pump comes on and if it cannot cope the first pump comes back on to assist the last pump (duty assist) if the level continues to rise all other pumps will come on (assist) in turn until the level decreases to the pump off points. Each pump has its own setpoints, (P213, 223, 233, 243, 253, 263 & P214, 224, 234, 244, 254, 264).
The third parameter for each relay determines the pump group. You can have two groups of pumps, and all similar duties within that group will operate together.
P212, P222, P232, P242, P252, 262 - Relay Pump Group
By default, all pump groups are set to 1, but if you want to have another group, then set this parameter to 2, for each pump relay that should operate together as part of a second group.
The fourth parameter, and the fifth parameter for each relay set the
pump ON” and “OFF” points, which are entered in Measurement units P104. For pump down the ON” is set higher than OFF”. For pump up then “ON” is set lower than OFF”. See the appropriate pump duty, function table (P212, 222, 232, 242, 252, 262) for further information.

P213, P223, P233, P243, P253, 263 - Relay Setpoint 1

This parameter determines the “ON” point of the pump.

P214, P224, P234, P244, P254, 264 - Relay Setpoint 2

This parameter determines the “OFF” point for the pump. When a relay is being used for a pump by time function, then the sixth
parameter will determine the maximum time the pump will be allowed to run before it is switched off and the next pump takes over.
Important Notice
The pumps are started and stopped at the “ON” and “OFF” setpoints. To pump down (reduce level) then set “ON” higher than “OFF”. To pump up (increase level) then set “ON” lower than “OFF”.
Page 97
97

P215, P225, P235, P245, P255, 265 - Relay Setpoint 3

This parameter determines the Maximum Time the pump will be allowed to run before being switched “OFF” and is entered in minutes.
The pump will switch off either at its “OFF” level Relay Setpoint 2 (P214, 224, 234, 244, 254) or its Maximum Run Time Relay Setpoint 3 (P215, 225, 235, 245, 255), whichever occurs first.

P219, P229, P239, P249, P259, 269 - Relay Max.Rate

This parameter will allow a pump or general control relay to be switched at a pre-determined Rate of change of Level, irrespective of the “ON” level setpoint P213, 223, 233, 243, 253, 263. Once a pump or general control relay
has been switched “ON” by the pre-determined Rate of Change, it will remain energised until the level reaches the “OFF” level setpoint P214, 224,
234, 244, 254, 264. Max. Rate is entered in Measurement Units (P104) per minute and can be
entered as either positive (increasing level) or negative (decreasing level) values.

Common Relay parameters

P216, 226, 236, 246, 256, 266 – Relay Allocation

This parameter determines which input the relay will act on. You can set it to the transducer (default), or the optional auxiliary (current) input, or an average of the two. In most cases, this will not need to be changed from the default.
OPTIONS
DESCRIPTION
1 = Xducer 1 (Default)
Relay acts on Xducer 1 calculated values
2 = Xducer 2
Relay acts on Xducer 2 calculated values
3 = Auxiliary (Optional)
Relay acts on optional current input levels
4 = Average of 1 & 2
Relay acts on the resulting average levels of two signal inputs.
5 = Differential of 1 & 2
Relay acts on the resulting differential level of two signal inputs
Page 98
ZENITH 140 UL INSTRUCTION MANUAL
98

P217, P227, P 237, P247, P257, 267 - Relay Closures

The Zenith will record how many times each relay is closed, this parameter displays the number of times the relay has activated since the relay has been in use. It can be reset with any value.

P218, P228, P238, P248, P258, 268 - Relay Fail Safe

Your Zenith has a general fail-safe parameter P808. However, this can be overridden so that each individual relay has its own independent failsafe mode. This parameter determines what the relay will do in the event of the Failsafe Time (P809) expiring.
OPTIONS
DESCRIPTION
0 = Default
Relay assumes system default mode P808
1 = Hold
Relay remains in its current state
2 = De-energise
Relay will De-energise
3 = Energise
Relay will energise
Page 99
99

Pump “Advanced” Parameters

The following parameters are used to set the “Advanced” Pump features.

Pump Run On

This feature is used to periodically allow the pumps to continue operating
below their normal “OFF” point, to discharge any sediment that may have
settled at the bottom of the vessel.

P349 Prime Level

Sets the required level to ensure pumps are fully primed after a pump run
on has occurred. Following a pump run on, any pump, whose “ON” point is below the Prime Level will be held “OFF” until the Prime Level has been
exceeded.

P350 Run Interval

Set required time period, in hours, at which pump run on should occur.

P351 Run Duration

This parameter sets the length of time, in seconds, that pumps will run on for, it should be noted that only one run on is allowed per Run Interval.

Starting

This feature is used to reduce the effects of power surges, caused by switching of pumps, in the following instances, (P352) Power surge (mains or hydraulic) that is generated when multiple pumps are started simultaneously, (P353) Power resumption following a power failure.

P352 Start Delay

Set the required time period, in seconds, that should elapse between pumps starting. Default = 10 seconds.

P353 Power Delay

Set the required time period, in seconds, that should elapse before pumps are allowed to start following a power failure. Default = 10 seconds.
Page 100
ZENITH 140 UL INSTRUCTION MANUAL
100

Stopping

If required, this feature will prevent pumps, with a common “OFF” point being switched off all at the same time pumps will be switched “OFF” in turn as determined by the delay set in P348 Stop Delay.

P348 Stop Delay

Set the required time period, in seconds, that should elapse between pumps stopping. Default = 0.0 seconds.

Pump Exercising

This feature is used to reduce idle pump corrosion and sediment build up. Pumps can run after a specified Idle Time (P355) for a determined period of Exercise time (P356), providing a Minimum head /level (P357) is present and all other pumps are switched off.

P354 Exercise Enable

This parameter determines if Pump Exercising is enabled or disabled.
OPTIONS
DESCRIPTION
0 = No (Default)
Pump exercising disabled
1 = Yes
Pump exercising enabled

P355 Idle Time

Sets the Idle Time to elapse before Pump Exercising is to be activated. Set the required time period in minutes. Default = 720 minutes.

P356 Exercise Time

Set the required Exercise Time in seconds. Default = 30 seconds

P357 Minimum Head

To prevent the dry running and the possibility of cavitation, of the pump, enter the minimum level (head) of material, in metres, that is to be present before permitting pump exercising to take place.
Loading...