Pulsar Measurement Quantum 2 Product Manual

Page 1
Quantum2
Instruction Manual
Page 2
2
Page 3
PULSAR MEASUREMENT
3
FLOWCERT LITE (FOURTH EDITION REV 1)
February 2021 Part Number M-142-Q-004-1P
COPYRIGHT
© Pulsar Measurement, 2012 -21. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form without the written permission of Pulsar Process Measurement Limited.
WARRANTY AND LIABILITY
Pulsar Measurement guarantee for a period of 2 years from the date of delivery that it will either exchange or repair any part of this product returned to Pulsar Process Measurement Limited if it is found to be defective in material or workmanship, subject to the defect not being due to unfair wear and tear, misuse, modification or alteration, accident, misapplication, or negligence.
DISCLAIMER
Pulsar Measurement neither gives nor implies any process guarantee for this product and shall have no liability in respect of any loss, injury or damage whatsoever arising out of the application or use of any product or circuit described herein.
Every effort has been made to ensure accuracy of this documentation, but Pulsar Measurement cannot be held liable for any errors.
Pulsar Measurement operates a policy of constant development and improvement and reserves the right to amend technical details, as necessary.
The Quantum2 shown on the cover of this manual is used for illustrative purposes only and may not be representative of the actual Quantum2 supplied.
CONTACT
For technical support, please contact: Europe: supporteurope@pulsarmeasurement.com
Outside Europe: supportnorthamerica@pulsarmeasurement.com If you have any comments or suggestions about this product, please contact: Europe: europe@pulsarmeasurement.com
Outside Europe: northamerica@pulsarmeasurement.com Pulsar Measurement website: www.pulsarmeasurement.com
United States
11451 Belcher Road South Largo, FL 33773 888-473-9546
Canada
16456 Sixsmith Drive Long Sault, Ont. K0C 1P0 855-300-9151
United Kingdom
Cardinal Building, Enigma Commercial Centre
Sandy’s Road, Malvern
WR14 1JJ 00 44 (0)1684 891371
Page 4
4
CONTENTS
Contents ....................................................................................................................................... 4
Chapter 1: Start Here… ........................................................................................................ 10
About this Manual ............................................................................................................ 10
About the Quantum2 ....................................................................................................... 11
Functional Description .................................................................................................... 11
Product Specification ....................................................................................................... 13
EU Certificate of Conformity ......................................................................................... 15
Chapter 2 Quantum2 Installation ..................................................................................... 16
Unpacking ............................................................................................................................ 16
Power Supply Requirements......................................................................................... 16
Location ................................................................................................................................ 17
Dimensions .......................................................................................................................... 18
Fascia Mount ....................................................................................................................... 18
Terminal connection details .......................................................................................... 20
Power ..................................................................................................................................... 21
Transducer(s) ....................................................................................................................... 21
ATEX ....................................................................................................................................... 21
Digital Inputs ....................................................................................................................... 24
Voltage selector and fuse location............................................................................. 24
Preparation for Operation ............................................................................................. 26
Maintenance ....................................................................................................................... 26
Chapter 3 How To Use Your Quantum2 ........................................................................ 27
Operating the Controls ................................................................................................... 27
Run Mode ............................................................................................................................. 28
Program Mode ................................................................................................................... 29
How to Access Program Mode .................................................................................... 29
Hot Keys ................................................................................................................................ 30
Menu Keys ........................................................................................................................... 31
Numeric Keys ...................................................................................................................... 31
Using the Menu System ................................................................................................. 32
Page 5
PULSAR MEASUREMENT
5
Directly Editing Parameters ......................................................................................... 33
Test Mode ............................................................................................................................ 34
Using the Serial Interface ............................................................................................... 35
Parameter Defaults ........................................................................................................... 37
Chapter 4 Quick Setup Guide ........................................................................................... 38
Enter Program Mode ....................................................................................................... 38
Choose Quick Setup ......................................................................................................... 38
Choose Your Application ............................................................................................... 39
Quick Setup ......................................................................................................................... 40
Set-up Your Application ................................................................................................. 41
Example 1 Level Control ................................................................................................. 45
Example 2 Sump Control (pump down) ................................................................... 47
Chapter 5 Parameter Guide ............................................................................................... 49
Menu System ...................................................................................................................... 49
Top Level Menu ................................................................................................................. 49
Application Menu .............................................................................................................. 50
Relays Menu ........................................................................................................................ 51
Pump Advanced Menu ................................................................................................... 52
Digital Inputs Menu.......................................................................................................... 53
Float Switch Backup ......................................................................................................... 54
Tariff Guard Menu ............................................................................................................. 55
Data Logs Menu ................................................................................................................ 56
Pumped Volume Menu ................................................................................................... 57
Efficiency Menu .................................................................................................................. 58
Display Menu ...................................................................................................................... 59
mA Output 1 Menu .......................................................................................................... 60
mA Output 2 Menu .......................................................................................................... 60
Compensation .................................................................................................................... 61
Stability Menu .................................................................................................................... 61
Echo Processing Menu .................................................................................................... 62
Page 6
QUANTUM2 INSTRUCTION MANUAL
6
System Menu ...................................................................................................................... 63
Device Comm Menu ........................................................................................................ 64
Test Menu ............................................................................................................................ 65
Chapter 6 Parameter Listing and Description ............................................................ 66
Application Parameters................................................................................................... 66
Operation ............................................................................................................................. 66
Dimensions .......................................................................................................................... 67
Relay Parameters ............................................................................................................... 69
Alarms .................................................................................................................................... 71
Pumps .................................................................................................................................... 82
Control ................................................................................................................................... 86
Miscellaneous ..................................................................................................................... 92
Pump by Time .................................................................................................................... 94
Common Relay parameters........................................................................................... 97
Pump Trips ........................................................................................................................... 98
Pump “Advanced” Parameters ..................................................................................... 99
Pump Run On ..................................................................................................................... 99
Starting .................................................................................................................................. 99
Stopping ............................................................................................................................. 100
Pump Exercising .............................................................................................................. 100
Wall Cling ........................................................................................................................... 101
Storm.................................................................................................................................... 101
Rate Method ..................................................................................................................... 102
Digital Inputs ..................................................................................................................... 103
Device Fail .......................................................................................................................... 105
Duty ...................................................................................................................................... 106
Override .............................................................................................................................. 109
Reset ..................................................................................................................................... 109
Digital Input Parameters .............................................................................................. 109
Digital Input ....................................................................................................................... 112
Page 7
PULSAR MEASUREMENT
7
Float Switch (FS) Backup .............................................................................................. 114
Common Par ..................................................................................................................... 114
Digital Input ....................................................................................................................... 115
Tariff Guard ........................................................................................................................ 116
Set Up .................................................................................................................................. 116
Peak Times ......................................................................................................................... 117
Data Log parameters ..................................................................................................... 119
Totaliser Audits ................................................................................................................ 119
Temperature ...................................................................................................................... 119
Pump Logs ......................................................................................................................... 120
Pumped Volume .............................................................................................................. 122
Set Up .................................................................................................................................. 122
Volume ................................................................................................................................ 123
Conversion ......................................................................................................................... 123
Breakpoints ........................................................................................................................ 128
Tables ................................................................................................................................... 129
Pump Efficiency ................................................................................................................ 130
Set Up .................................................................................................................................. 130
Display Parameters ......................................................................................................... 133
Options ................................................................................................................................ 133
Failsafe ................................................................................................................................. 135
Auxiliary ............................................................................................................................... 136
Totaliser ............................................................................................................................... 138
Bargraph ............................................................................................................................. 140
mA Output 1 Parameters ............................................................................................. 141
Range ................................................................................................................................... 141
Operation ........................................................................................................................... 142
Setpoint ............................................................................................................................... 142
mA1 Limits ......................................................................................................................... 143
mA1 Trim ............................................................................................................................ 143
Page 8
QUANTUM2 INSTRUCTION MANUAL
8
mA1 Failsafe ...................................................................................................................... 144
mA1 Allocation ................................................................................................................. 144
mA Output 2 Parameters ............................................................................................. 145
Range ................................................................................................................................... 145
Operation ........................................................................................................................... 146
Setpoint ............................................................................................................................... 146
mA2 Limits ......................................................................................................................... 147
mA2 Trim ............................................................................................................................ 147
mA2 Failsafe ...................................................................................................................... 148
mA2 Allocation ................................................................................................................. 148
Compensation Parameters .......................................................................................... 149
Offset.................................................................................................................................... 149
Temperature ...................................................................................................................... 149
OVF Persist ......................................................................................................................... 150
Velocity ................................................................................................................................ 150
Stability Parameters ....................................................................................................... 151
Damping ............................................................................................................................. 151
Indicator .............................................................................................................................. 151
Rate ....................................................................................................................................... 151
Filters .................................................................................................................................... 152
Echo Processing Parameters ....................................................................................... 153
Transducer 1 Status ........................................................................................................ 153
Transducer 2 Status ........................................................................................................ 154
DATEM Parameters......................................................................................................... 155
System Parameters ......................................................................................................... 156
Passcode ............................................................................................................................. 156
Backup ................................................................................................................................. 156
System Information ........................................................................................................ 156
Date & Time ...................................................................................................................... 158
LED Colour ......................................................................................................................... 158
Page 9
PULSAR MEASUREMENT
9
Watchdog ........................................................................................................................... 159
Daylight Saving Time ..................................................................................................... 160
Device Comm. .................................................................................................................. 164
RS232 Set Up .................................................................................................................... 164
RS 485 Set Up ................................................................................................................... 164
Remote Alarm ................................................................................................................... 165
Test Parameters ............................................................................................................... 167
Simulation .......................................................................................................................... 167
Hardware ............................................................................................................................ 168
Chapter 6 Troubleshooting .............................................................................................. 171
Chapter 7 Disposal .............................................................................................................. 172
Notes ........................................................................................................................................ 173
Page 10
QUANTUM2 INSTRUCTION MANUAL
10

CHAPTER 1: START HERE…

Congratulations on your purchase of a Pulsar Quantum2. This quality system has been developed over many years and represents the latest in high technology ultrasonic level measurement and control.
It has been designed to give you years of trouble-free performance, and a few minutes spent reading this operating manual will ensure that your installation is as simple as possible.

About this Manual

It is important that this manual is referred to for correct installation and operation. There are various parts of the manual that offer additional help
or information as shown.
Tips
TIP: Look f o r this icon t h r oughout y o u r Pulsar Me a s u r e ment manual to find help f u l informatio n a n d answers t o f r equentl y a s ked questio n s .
Additional Information
References
See Also
References to other parts of the manual.
Additional Information
At various parts of the manual, you will find sections like this that explain specific things in more detail.
Page 11
PULSAR MEASUREMENT
11

About the Quantum2

The Quantum2 is a state of the art pump management, and level controller, that provides advanced operating routines suitable for an extremely wide variety of applications. The system combines premium specification with high performance even in the most arduous applications where high turbulence and foam or froth is present.

Functional Description

The Quantum2 level and pump controller is a highly developed ultrasonic level measurement system which provides non-contacting sophisticated pump and level control routines suitable for an extremely wide variety of applications.
Easy calibration and maintenance free “fit and forget” performance mean
that you can install the Quantum2 pump controller rapidly and with confidence. Ten user-definable relays with adjustable, individual on and off points. Seven user-definable digital inputs, 2 x isolated mA output, RS 232 and intelligent performance logging software features provide the user with a superior pump management system and comprehensive level measurement information.
The Quantum2 operates on the principle of timing the echo received from a measured pulse of sound transmitted in air and utilises the unique DATEM software (Digital Adaptive Tracking of Echo Movement).
Page 12
QUANTUM2 INSTRUCTION MANUAL
12
This is an entirely new digital mapping technique developed especially for the Pulsar ultra range. It gives the system the edge when identifying the
“true target level” in the face of competing echoes from pipes, pumps, or
other obstructions. When coupled with the powerful, long range abilities of all the dB transducer range, including the new dBR16 mmWave radar, the Quantum2 level and pump controller has no equal.
The Quantum2 can measure from zero to 40m from the transducer to the surface being monitored, dependent on the transducer used.
The Quantum2 can show level, space, distance, average level and differential level on the display. The relays can be programmed to activate alarms, pump starters, or other control equipment. In addition, the digital inputs can be used to modify pump and control regimes in order to optimise performance. There are two isolated 4-20 mA outputs that can be connected to a chart recorder or PLC, to monitor level, space, distance, or pumping rate, independently from that shown on the display. There is an RS232 port, so that the Quantum2 can be operated remotely by a PC or other equipment.
The Quantum2 is programmed by the built-in keypad or by PC via the RS 232 Serial Interface (optional). All the parameters are stored in non-volatile memory, so are retained in the event of power interruption. A second backup copy of all parameters can also be retained in the Quantum2, in case a previous set of parameters needs to be restored.
Page 13
PULSAR MEASUREMENT
13

Product Specification

PHYSICAL
Fascia Mount Outside Dimensions
200 x 112 x 108 mm
Weight
Nominal 1.3kg
Enclosure Material/Description
Stainless steel with Polycarbonate UL94 –V0 front and bezel
Transducer Cable Extensions
2-core screened
Maximum Separation
1000m (3,280 ft), 500m (1,640 ft) for mmWave
ENVIRONMENTAL
IP Rating (Wall)
IP64
Max. & min. temperature (electronics)
-20 ºC to +50 ºC
Flammable atmosphere approval
Safe area: compatible with approved dB transducers (see transducer spec' sheet)
CE Approval
See EU Declaration of Conformity
PERFORMANCE
Accuracy
0.25% of the measured range or 6 mm (whichever is greater). mmWAVE ± 2mm.
Resolution
Dependant on application and sensor used, typically with standard ultrasonic transducer, 0.1% of the measured range or 2 mm (0.08") (whichever is greater).
Max. Range
Dependant on transducer (maximum 40m dB40)
Min. Range
Dependent upon application and transducer (minimum zero dB Mach3)
Rate Response
Fully adjustable
ECHO PROCESSING
Description
DATEM (Digital Adaptive Tracking of Echo Movement)
Page 14
QUANTUM2 INSTRUCTION MANUAL
14
OUTPUTS
Analogue I/O
2 off Isolated (floating) outputs (to 150V) of 4-20 mA or 0-20 mA into 500 (user programmable and adjustable) 0.1% resolution
Digital output
Full Duplex RS232
Volt free contacts, number, and rating
5 form “C” (SPDT) rated at 5A at 115V AC (Relays 1, 2,
3, 4,& 5) and 5 form "C" (SPDT) rated at 3A at 115V AC (Relays 6, 7, 8, 9 & 10)
Display
6 digits plus 12-character text, plus bar graph with direction indicators, remote communicator identifier, and program/run/test mode indicators
DIGITAL INPUTS
Min. Input voltage 4.5V DC
Max. Input Voltage 30VDC (Max Current 3mA per Input)
24VDC Input Supply maximum total current 24mA.
PROGRAMMING
On-board programming
By integral keypad
PC programming
Via RS232
Programming security
Via passcode (user selectable and adjustable)
Programmed data integrity
Via non-volatile RAM, plus backup
SUPPLY
Power Supply
115V AC + 5% / -10% 50/60 Hz, 230V AC + 5% / -10% 50/60 Hz, DC 18 - 36V 10W maximum power (typically 6W)
Fuses
100 mA at 170-240V AC (fitted as standard to wall units). 200 mA at 85-120V AC (fitted as standard to fascia units)
Pulsar Measurement operates a policy of constant development and improvement and reserve the right to amend technical details, as necessary.
Page 15
PULSAR MEASUREMENT
15

EU Certificate of Conformity

Page 16
QUANTUM2 INSTRUCTION MANUAL
16

CHAPTER 2 QUANTUM2 INSTALLATION

Unpacking

Power Supply Requirements

The Quantum2 can operate from AC supply or from a DC battery. The AC is either 115V+5%/-10% 50/60Hz or 230V +5%/-10% 50/60Hz, depending on the position of the selector switch. The DC is 18-36V. In all cases the Quantum2 will typically consume 6W of power, with a maximum of 10W.
Important Information
All shipping cartons should be opened carefully. When using a box cutter, do not plunge the blade deeply into the box, as it could potentially cut or scratch equipment components. Carefully remove equipment from each carton, checking it against the packing list before discarding any packing material. If there is any shortage or obvious shipping damage to the equipment, report it immediately to Pulsar Process Measurement Limited.
Page 17
PULSAR MEASUREMENT
17

Location

The Qunatum2 must be mounted in a non-hazardous (safe) area, and the transducer fitted in the hazardous area
When choosing a location to mount the enclosure, bear in mind the following:
Ensure that the Quantum
2
Lite is installed in a “Safe”, non-hazardous
area.
For a clear view of the LCD display, it is recommended that it is
mounted at eye level.
The mounting surface is to be vibration free.
The ambient temperature is between -20°C and 50°C.
There should be no high voltage cables or inverters nearby,
Important Information
All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation.
Page 18
QUANTUM2 INSTRUCTION MANUAL
18

Dimensions

Fascia Mount

The dimensions of the wall fixing holes are as shown below:
Page 19
PULSAR MEASUREMENT
19
The full dimensions of the fascia mount enclosure are as shown below:
200 mm
112mm
162 mm
20mm
72mm
15mm
16mm
Page 20
QUANTUM2 INSTRUCTION MANUAL
20

Terminal connection details

Page 21
PULSAR MEASUREMENT
21

Power

The Quantum2 can operate from mains AC and automatically from DC or battery backup in the event of power failure or can be operated permanently from DC or batteries.

Transducer(s)

The transducer should be installed, and connected, in accordance with the installation instructions contained in the Transducer User Guide.
Wire the transducer to the Quantum2’s transducer terminals, as follows:

Transducer 1

TERMINAL CONNECTION DETAILS
Red:
Power
White: Signal
Black:
0Volts
Green:
Screen
32
31
30
30

Transducer 2

TERMINAL CONNECTION DETAILS
Red:
Power
White:
Signal
Black:
0Volts
Green: Screen
35
34
33
33
When using 2-core screened extension cable, the Black and Green wires of the transducer should be connected to the screen of the extension cable
which in turn should be connected to the appropriate 0 volts’ terminal of the
Quantum2.

ATEX

For Zone 1 applications a transducer certified to Sira 02ATEX5104X is used, and must be supplied via a 4000A breaking fuse, which is fitted as standard to the Quantum2.
For Zone 0 a transducer certified to Sira 02ATEX2103X is used, which must be connected to the Quantum2 controller via an external Zener barrier.
Page 22
QUANTUM2 INSTRUCTION MANUAL
22
When using the Quantum2 in a single transducer mode, to measure space, level or distance, the transducer should be connected to Transducer 1 input terminals. In applications where it is required to measure Differential, then the upstream transducer should be connected to Transducer 1 input terminals and the downstream transducer to Transducer 2 input terminals. In cases where the Quantum2 is required to measure Average, transducers can be connected as required.

Relay Outputs

The ten user definable relays can be programmed for a variety of alarms, pump control, or other process functions. Relays 1, 2, 3 4 and 5 contacts are all rated at 5A at 240V AC, whilst Relay 5, 6, 7, 8, 9 and 10 contacts are rated at 3A at 240V AC. All connections should be such that the short circuit capacity of the circuits to which they are connected, is limited by fuses rated so that they do not exceed the relay rating.

Current Output

This is an isolated (floating) mA output (to 150 V), of 4 - 20mA or 0 - 20mA, and the load should not exceed 500 .

Temperature Input

The external temperature sensor allows more localised compensation of the measured distance due to changes in temperature.
There are 2 models Type A: -25°C to 50°C, and Type B: -25°C to 125°C
Page 23
PULSAR MEASUREMENT
23
The temperature sensor should be placed close to the point of the measurement.
The Temperature sensor connections are as follows:
DESCRIPTION
TEMPERATURE SENSOR
QUANTUM2
Power Supply
Terminal 1
Terminal 25
Return
Terminal 2
Terminal 24
Temp Source (P852), should be set to option 4 or 5 depending on the sensor range, set 4 for type A and 5 for type B (see above), the range is specified on the label of the sensor.
This feature is available as an option only, please consult Pulsar for further details.
92mm
182mm
100mm
M20 ENTRY
IP67 ABS HOUSING
316 STAINLESS STEEL
6mm
Page 24
QUANTUM2 INSTRUCTION MANUAL
24

Digital Inputs

Where the Quantum2 is required to provide power for a Device Input the appropriate Digital Input should be wired between the 24VDC supply terminal and the IN terminal. (TOTAL maximum current available, for all seven digital inputs, from the 24VDC supply is 24mA). When Device Inputs are self-powered, connection of the device should be made between the Common terminal and the IN terminal. (Min Input voltage 4.5VDC, and Maximum Input voltage 30VDC with a maximum current of 3mA).

RS2323 Serial Interface

If required, you can connect to the serial interface to operate your Quantum2 remotely.

Voltage selector and fuse location

The voltage selector switch and mains fuse, is located under the removable cover at the bottom of the unit, as illustrated below.
Page 25
PULSAR MEASUREMENT
25
DON’T FORGET
Make sure you move the voltage selector switch to the correct position for your power supply
Important Information
Before applying AC power (mains), make sure you have correctly selected the voltage selector switch. In the case of the Fascia mount model this is located under the removable cover at the bottom of the unit, as detailed in the preceding pages.
Please note that all Fascia units are set to 115 volts AC with a 200mA fuse fitted, and wall units are supplied set to 230 volts AC for safety reasons, and a 100mA fuse fitted as standard.
Never operate the Quantum2 with the terminals access cover removed.
An external switch or circuit breaker should be installed near to the Quantum2 to allow the supply to be removed during installation and maintenance. In addition, the relay contacts should also have a means of isolating them from the unit.
Interconnecting cables must be adequately insulated in accordance with local regulations. Strip back 30 mm of the outer insulation of the cable. Strip 5 mm of insulation from the end of each conductor. Twist all exposed strands of the conductor together. Insert the stripped conductor into the terminal block as far as it will go and tighten the terminal block screw. Ensure that all strands are firmly clamped in the terminal block and that there is no excess bare conductor showing, and no stray strands.
Important Information
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
Page 26
QUANTUM2 INSTRUCTION MANUAL
26

Preparation for Operation

Before switching on, check the following:
The Quantum
2
is mounted correctly and is in a ‘safe’ area.
The power supply is correctly installed. The voltage selector switch is in the correct position. The relays are connected correctly.

Maintenance

There are no user serviceable parts inside Quantum2, except the mains fuse. If you experience any problems with the unit, then please contact Pulsar Measurement for advice.
To clean the equipment, wipe with a damp cloth. Do not use any solvents on the enclosure.
Important Information
The unique DATEM software comes into operation as soon as power is applied and is designed to monitor a moving level or target with the transducer in a fixed position.
If, after any period of use, it should become necessary to move the transducer, for any reason, from its original operating position, switch off the Quantum2, before proceeding, in order to prevent any undesirable updates to the DATEM trace. If after moving the transducer the reading is not as expected, please refer to Chapter 6 Troubleshooting.
Page 27
PULSAR MEASUREMENT
27
CHAPTER 3 HOW TO USE YOUR QUANTUM
2

Operating the Controls

If you are already familiar with the setup of the Quantum2, go straight to the quick setup guide in Chapter 4.

Display

The display provides information on the current mode of operation, and status of the remote communication. Whilst in the Run Mode it will display the current level reading and its units of measure, along with status messages with regards to the Transducer, Echo reception and Fail Safe Mode. Additionally, it can be programmed to provide status messages on alarms, pumps etc. When in the Program mode the display is used to read information on the Menu System, Parameter Number and parameter details and values, which can be entered. During Test Mode, the display is used to monitor the simulated level. A bar graph is also provided which will provide a visual reading of the level, in percentage of span.
1. Displays the current mode of operation
2. Main 6-digit display:
Run Mode; current measurement displayed, dependent on mode and measurement units chosen, and value of hotkey selected. Program Mode; displays parameter number and values entered for parameters. Test Mode; displays simulated level.
1
2
3
4
0%
5
6
Run Mode Program Mode Test Mode 100%
REMOTE COMMUNICATOR OFF
XXXXXXXXXXXX
000.000
Page 28
QUANTUM2 INSTRUCTION MANUAL
28
3. Auxiliary Display, scrolling twelve-digit display.
Run Mode; displays measurement units, status messages on signal and transducer, details of Hot Key function selected. It can be also programmed to provide notification messages on alarms and pumps etc. For full details please refer to Display Parameters in the relevant parameter listing. Program Mode; displays menu and sub menu headings, parameter details and options.
4. Communicator status, this displays the status of remote PC
connection and velocity sensor operation.
5. Bar graph display, this gives visual indication of measurement in %
of span.
6. Level indicators:
Run Mode; indicates in which direction the level is moving. Program Mode; indicates at which level of the menu system you are
at.
There are two main operating modes for your Quantum2, Run Mode and Program Mode. There is also a Test Mode, used for checking the set-up. All modes are now described.

Run Mode

This mode is used once the Quantum2 has been set up in program mode. It is also the default mode that the unit reverts to when it resumes operation after a power failure.
When the Quantum2 is switched on for the first time, it will display, in metres, the distance from the transducer face to the target. All relays by default are switched off.
After programming is complete, any relays that are set will operate when the level reaches the relevant setpoint, and the LED’s will change colour (unless specifically switched off).
Page 29
PULSAR MEASUREMENT
29

Program Mode

This mode is used to set up the Quantum2 or change information already set. You must use either the built-in keypad (standard) or, alternatively the unit can be set up with a PC via the RS232 Serial Interface.
Entering a value for each of the parameters that are relevant to your application provides all the programming information.

How to Access Program Mode

To enter program mode on the Quantum2, you simply enter the passcode, via the keypad, followed by the ENTER key. The default passcode is 1997, so you would press the following:
Important Information
There is a time-out period of 15 minutes when in program mode. After which time the run mode will resumed if you do not press any key.
ENTER
1
9 9 7
Page 30
QUANTUM2 INSTRUCTION MANUAL
30

Hot Keys

There are five hot keys on the keypad, which can be used to quickly access common parameters for viewing only, while in Run Mode. Pressing the hot key once will display the first parameter, then repeated pressing will display the others, then the Quantum2 reverts to Run Mode. In program mode, they have different functions, the functions are shown below.
HOT KEY
RUN MODE
PROGRAM MODE
Total pump running hours, and individual pump running hours
Not used with Quantum
2
Displays echo confidence, echo strength, height above loss limit (HALL), average noise, peak noise and temperature
Not used with Quantum2
Total number of pump starts and individual pump starts.
Reset parameter to default setting
Instantaneous mA output
Not used with Quantum2
Dependent on application. Displays distance, level, space, volume or rate of change of level.
Toggle relay setpoints between units of measure and % of span.
Reset for digital Inputs
Takes you to the last parameter edited when you first enter program mode.
Shows details of function type, firmware revision and serial number
Enter decimal point.
mA
n
Page 31
PULSAR MEASUREMENT
31

Menu Keys

The menu keys have the following functions:
HOT KEY
FUNCTION
1) Arrow keys for moving left and right around the menu
system.
2) Used in test mode to simulate the level moving up and
down.
1) Used to confirm each action (e.g. select a menu option)
2) Used to confirm questions asked by the Quantum
2
, such as
before restring factory defaults.
Used to navigate up a level in the menu system, and back to run mode.
Used to cancel a value entered in error

Numeric Keys

These keys are used for entering numerical information during programming.
CANCEL
ENTER
1
2
3 4 5
6
7
8 9 0
.
+
-
Page 32
QUANTUM2 INSTRUCTION MANUAL
32
There are two means of editing parameters, directly or using the menu system. Each is now described.

Using the Menu System

The menu system has been designed to make the changing of parameters very simple. There are two levels of menu: Main Menu and Sub Menu.
On the display, there is a line of text that displays the menu system. Pressing the arrow keys scrolls the display between the top-level menu items, (as the example shown below, starting at Quick Setup).
As you press the cursor keys to scroll left and right between these, you can press ENTER at any time, to select the desired menu heading, and take you to the sub-menu.
Each of these options, along with their sub-menus, are described later in this manual. When you move down into the sub-menu, you can scroll round using the arrow keys, press ENTER to go to the required section of parameters.
Once you have reached the relevant section, scroll through the parameters, and enter the necessary information. To enter the information, use the
numeric keys and then press ENTER, you will then see the message “Saved!”
If you press CANCEL, then the change you made will not be saved, and the message “Unchanged!!” will be displayed.
When you have finished, press CANCEL to go back to the previous level. When you have reached the top level, then the Quantum2 will ask for confirmation before allowing you to go back into run mode. This is done by pressing ENTER at the display prompt.
Quick Setup
Application
Relays
Pump
Advanced
Digital Inputs
FS Backup
Compensation
Stability
System
Test
Device Comm
Echo
Processing
Tariff Guard
Data Logs
Pump
Volume
Pump
Efficiency
Display
mA
Output 1
mA
Output 2
Page 33
PULSAR MEASUREMENT
33

Directly Editing Parameters

If you already know the number of the parameter, that you wish to look at or edit, simply type the number in at any time while you are in the menu system. Thus, if you are in either the menu or sub-menu level by pressing a numeric key, you can enter the parameter number directly and jump straight there. You cannot type a parameter number whilst at parameter level, only at one of the two menu levels.
When you are at a parameter, the text line rotates automatically displaying the parameter name, number, the applicable units, and the maximum and minimum figure you can enter. The top line shows the value you are setting.
Once you have accessed a parameter, you can either just look at it, or change it.
Once a parameter has been changed, press ENTER and you will see the
message “Saved!”. If you press ‘CANCEL, then the change you made will not be saved, and the message “Unchanged!!” will be displayed.
You can jump straight to the last parameter you edited, by pressing ‘+/- when you first enter program mode.
Important Information
You can tell which part of the menu system you are in, as the up/down level indicators, (arrows) next to the bar graph will indicate as follows:
Top level menu: Down arrow on, to indicate you can move down.
Sub-menu: Up and Down arrows on, to indicate you can move up to the top
level, and down to parameter level.
Parameter Level: Up arrow on, to indicate you can move up to sub-menu
level.
Parameter Editing: No arrows on.
Page 34
QUANTUM2 INSTRUCTION MANUAL
34

Test Mode

Test mode is used to simulate the application and confirm that all parameters and relay setpoints have been entered as expected. During simulation, there is a choice of whether the relays will change state (hard simulation) or not (soft simulation), but the LED’s will always change colour as programmed, and the mA output will change in accordance to the chosen mode of operation. If you wish to test the logic of the system that the relays
are connected to then select hard simulation, but if you do not wish to change the relay state, then select a soft simulation.
There are two simulation modes, automatic and manual. Automatic simulation will move the level up and down between empty level or the pre­determined Start Level (P983) and Pump/Control relay switch points, if you wish to change the direction of the level movement e.g. to go beyond relay setpoints, this can be done by using the arrow keys. In manual simulation, using the arrow keys will allow you to move the level up and down as required.
To enter simulation, first go to program mode. Using the menu system, select menu item ‘Test’, then sub-menu item ‘Simulation’. Simply change the value of the parameter P980 to one of the following:
To return to program mode, press CANCEL and test mode will end. When in manual simulation, by default test mode will move the level by
0.1m steps. Altering the increment (P981) will change this value. In automatic mode, the rate at which the level moves up and down is set by
the increment (P981 in metres, and the rate (P982) in minutes, which can be changed to make the level move up and down faster. E.g. if increment (P981) is set for 0.1m and rate (P982) is set to 1 min then the level will increase or decrease at a rate of 0.1m/min. To make the simulated level move slower, decrease the value in increment (P981) or increase the value in rate (P982). To make the simulated level move faster, increase the value in increment (P981) or decrease the value in rate (P982).
Page 35
PULSAR MEASUREMENT
35

Using the Serial Interface

The RS232 serial interface is used to communicate between the Quantum2 Lite and a PC using the optional Ultra PC and other associated Pulsar software packages, to obtain information such as data logging and view echo traces upload, download and save parameter files. In addition, it can also be used to control or obtain information using a standard PC or other computer base equipment. To do so, the settings for control are as follows: baud rate 19,200, 8 data bits, no parity, 1 stop bit.
The device should be connected as shown in Chapter 2
Quantum2 Installation.
To use the device remotely, you need to log on to start, and log off when finished. When logged on, Quantum2 Lite will show ‘Remote ON’ on the display, and “Communicator OFF” when logged off.
All commands should be followed by a carriage return. When logged on, the unit will respond either OK (or a value) if the command is accepted, or NO if it is not.
To log on, send the command /ACCESS:pppp where pppp is the passcode (P922). To log off, send the command /ACCESS:OFF To read a parameter value, send the command /Pxxx where xxx is the parameter you wish to read, and the Quantum2 will
respond with the parameter value. To set a parameter, send the command /Pxxx:yy where xxx is the parameter number, and yy is the value you wish to
set it to.
Page 36
QUANTUM2 INSTRUCTION MANUAL
36
Other commands you can use are:
/DISTANCE (shows current distance)
/LEVEL (shows current level)
/SPACE (shows current space)
/RATE (shows current rate)
/VOLUME (shows current volume)
/TEMP (shows current temperature)
/CURRENTOUT1 (show the mA output 1 value)
/CURRENTOUT2 (show the mA output 2 value)
/BACKUP1 (take backup of parameters to area 1)
/BACKUP2 (take backup of parameters to area 2)
/RESTORE1 (restore parameters from area 1)
/RESTORE2 (restore parameters from area 2)
Please consult Pulsar Measurement or contact your local Pulsar representative for further details and a full list of available commands.
Page 37
PULSAR MEASUREMENT
37

Parameter Defaults

When you first switch the Quantum2 on, it will be reading the distance from the face of the transducer to the surface. It will be indicating in metres, as shown on the display. All relays are set OFF.
The date (P931) and time (P932) in the Quantum2 were set at the factory, but may need checking, and amending if, for example the application is in a time zone other than GMT, see relevant parameter listing for full details.
In some applications, it is easier to empty the vessel, take a reading from the Qunatum2 for distance and then setup the empty level to this figure.
Once you are satisfied with the installation, and Quantum2 is reading what you would expect in terms of distance from the face of the transducer to the material level, then you can proceed with programming, for the intended application. It is sensible to program all of the required parameters at the same time. The system will be then set-up.
Note: The span is automatically calculated from the empty level, so the empty level should be entered first.
Factory Defaults
When first installing the Qunatum2, or subsequently moving or using the unit on a new application, before proceeding to program the unit for its intended application it is recommended that you ensure that all parameters are at their default values by completing a Factory Default P930, as described in the relevant unit type parameter guide.
Page 38
QUANTUM2 INSTRUCTION MANUAL
38

CHAPTER 4 QUICK SETUP GUIDE

This quick set-up guide shows you how to get up and running within a few minutes of installing your Quantum2.

Enter Program Mode

First you need to go from run mode into program mode. Assuming the passcode is the default 1997, then you should enter the following on the keypad:

Choose Quick Setup

Now you need to go into the quick setup. You will see on the menu the
words ‘Quick Setup’, which is the first item on the menu system. Try pressing
the two arrow keys to see some more menu options, but return to Quick Setup, and press
ENTER
1
9 9 7
ENTER
ENTER
This takes you to the ‘Quick Setup Menu’.
This takes you to the common applications menu, and several options will appear on the display.
Important Notice
If you have already setup a common application, then there will be a number shown other than 0, and you will see messages showing what the current setup is. If you want to reset this and start again, press 0 (which will reset all the quick setup parameters), otherwise pressing ENTER will allow you to edit the parameters that have been set.
Page 39
PULSAR MEASUREMENT
39

Choose Your Application

There are four categories of application, which are all described at the end of this chapter. They are level, pump down (sump control), pump up (reservoir control) or customised, all with the choice of alarms and a number of pumps, dependant on application.
If you want to set-up a basic level monitoring application, as described in the following example 1, then choose 1. You then need to decide the number of alarms required and their function and choose the appropriate options.
If you want to set-up a pump down (sump control) application, as described in the following example 2, then choose 2. You then need to decide the
number of pumps required the pump duty and any requirement for alarms and choose the appropriate options.
If you want to set-up a pump up (reservoir control) application, then choose
3. You then need to decide the number of pumps required the pump duty, and any requirement for alarms, and choose the appropriate options.
In certain cases the Quick Setup Menu has been customised for particular customer specific applications, to choose one of these options press 4 and select the appropriate customised application and enter the details required as prompted.
Once you have chosen your application you will be asked a series of questions which are answered by choosing the appropriate option as detailed in the flow charts that follow. Once all the questions have been answered you will be prompted to provide further information, as detailed in the tables that follow, in order to complete the programming of the unit.
Page 40
QUANTUM2 INSTRUCTION MANUAL
40

Quick Setup

How Many Pumps
0 = No Pumps
1 = 1 Pump
2 = 2 Pumps 3 = 3 Pumps 4 = Four Pumps 5 = Five Pumps 6 = Six Pumps
Pump Duty
1= Fixed Duty Assist 2=Fixed Duty Backup 3=Alt Duty Assist
4=Akt Duty Backup
5=Duty Backup & Ass 6=Serv Ratio Duty Ass 7=Serv Ratio Duty Bup 8=FOFO Alt Duty Ass
Select the option
specific to your
application
Quick Setup
For Each Pump Relay
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3 4 = Set to Relay 4
5 = Set to Relay 5
6 = Set to Relay 6 7 = Set to Relay 7 8 = Set to Relay 8 9 = Set to Relay 9 0 = Set to Relay 10
How Many Alarms
0 = 0 Alarms 1 = One Alarm 2 = Two Alarms
3 = Three Alarms
4 = Four Alarms 5 = Five Alarms 6 = Six Alarms 7= Seven Alarms 8 = Eight Alarms 9 = Nine Alarms 10 = Ten Alarms List is truncated according to the no. of pumps selected.
For Each Alarm
1 = High Alarm 2 = Low Alarm 3 = Hi Hi Alarm 4 = Lo Lo Alarm 5 = Loss Of Echo
For Each Alarm
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3 4 = Set to Relay 4 5 = Set to Relay 5 6 = Set to Relay 6 7 = Set to Relay 7 8 = Set to Relay 8 9 = Set to Relay 0 0 = Set to Relay 10
1 = Level
4 = Customised
2 = Pump Down
3 = Pump Up
Page 41
PULSAR MEASUREMENT
41

Set-up Your Application

Once you have chosen the application, you will see a ‘Wait…’ message while
the parameters are all calculated and stored. Next you will see the parameters needed to finalise your application, in turn, as shown below. If you know you don’t need to change from the default, you can use the right arrow key to scroll through them, but if you want to view or change each one, just press ENTER.
PARAMETER
DEFAULT
DESCRIPTION
P101 Transducer
2 = dB6
Type of transducer being used.
P104 Measurement Units
1 = metres
Select units to be used for programming measurement information.
P105 Empty Level
6m
Distance from the face of the transducer to the material at the bottom of the vessel.
P106 Span
5.7m
Distance from the empty level (0% full) to span (100% full).
For More Options Hit Enter..
Now you will see a scrolling message that says, ‘For more Options Hit Enter’. If you press ENTER, you will then see more parameters, specific to the
application you have chosen, these are all factory pre-set. If you press any other key you will return to the Quick Setup menu, where you can press CANCEL to return to run mode.
Important Notice
The maximum number of relays that can be allocated, via the Quick Setup, for use
as ‘alarms’ or ‘pump’ is six, if you require to allocate additional relays to ‘alarms or ‘pump’ this can be achieved by accessing the Relay Menu and programming
additional relays as required.
Page 42
QUANTUM2 INSTRUCTION MANUAL
42
If you want to change any of the factory pre-set parameters, then you can do so, referring to the relevant page of Chapter 5, in this handbook for detailed information. The parameters concerned are shown below.
PARAMETER
DEFAULT
DESCRIPTION
P213 / P214 Relay 1 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P223 / P224 Relay 2 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P233 / P234 Relay 3 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P243 / P244 Relay 4 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P253 / P254 Relay 5 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P263 / P264 Relay 6 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P830 mA Out Range
2 = 4 to 20mA
Determines the mA output range. 0 = Off, 1 = 0 to 20mA, 2 = 4 to 20mA, 3 = 20 to 0mA, 4 = 20 to 4mA.
P870 Fill Damping
10m/min
Rate of maximum fill rate (set above the actual fill rate of the vessel).
P871 Empty Damping
10m/min
Rate of maximum empty rate (set above the actual rate of the vessel).
Page 43
PULSAR MEASUREMENT
43
The default values used for determining the relay setpoints, when setting Alarm relays, via the Quick Setup menu are entered as a % of span and are as follows:
APPLICATION
NO. OF PUMPS
PUMP NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Down
One
Pump 1
50%
20%
Pump Down
Two
Pump 1 Pump 2
50% 70%
20% 20%
Pump Down
Three
Pump 1 Pump 2 Pump 3
50% 60% 70%
20% 20% 20%
Pump Down
Four
Pump 1 Pump 2 Pump 3 Pump 4
40% 50% 60% 70%
20% 20% 20% 20%
Pump Down
Five
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5
40% 50% 60% 70% 75%
20% 20% 20% 20% 20%
Pump Down
Six
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 Pump 6
40% 50% 60% 70% 75% 80%
20% 20% 20% 20% 20% 20%
Page 44
QUANTUM2 INSTRUCTION MANUAL
44
APPLICATION
NO. OF PUMPS
PUMP NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Up
One
Pump 1
50%
80%
Pump Up
Two
Pump 1 Pump 2
50% 30%
80% 80%
Pump Up
Three
Pump 1 Pump 2 Pump 3
50% 40% 30%
80% 80% 80%
Pump Up
Four
Pump 1 Pump 2 Pump 3 Pump 4
60% 50% 40% 30%
80% 80% 80% 80%
Pump Up
Five
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5
60% 50% 40% 30% 25%
80% 80% 80% 80% 80%
Pump Up
Six
Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 Pump 6
60% 50% 40% 30% 25% 20%
80% 80% 80% 80% 80% 80%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%
Page 45
PULSAR MEASUREMENT
45

Example 1 Level Control

A vessel, containing liquid that has a variation in level that is to be monitored, with a high level alarm set on Relay 1 and low level alarm set on Relay 2.
In this example, when the level rises to 2.38 m, relay 1 will come on until the level drops to 2.24 m when it will turn off. If the level drops to 0.28 m, then relay 2 will come on until it rises 0.42 m when it will turn off.
The display will show the level in the tank.
The mA output will be representative of level where 4mA = empty level (0%) and 20mA = 2.8m (100%).
Empty Distance (P105), 3.5m
100%. Span (P106), 2.8m
85%. High alarm on (P213), 2.38m
80%. High alarm off (P214), 2.24m
0%, Empty level
10%. Low alarm on (P223), 0.28m
15%, Low alarm off (P224), 0.42m
Page 46
QUANTUM2 INSTRUCTION MANUAL
46
To program the Quantum2 for Example 1 Level Monitoring with Alarms by using the Quick Setup menu proceed as follows. If required to access Program Mode, key in the passcode 1997 and press ENTER
At the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump/Custom
1 = Level App.
No. of alarms
2 = 2 Alarms
Type alarm 2
2 = Low
Alarm no.2
2 = Set relay 2
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Quantum2 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application, they can
be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is
displayed, and entering new values to relay setpoints as required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
Page 47
PULSAR MEASUREMENT
47

Example 2 Sump Control (pump down)

A sump is typically used to temporarily hold water or effluent, and when the level reaches a specific point, the sump is pumped down, with the fluid being transferred to another process.
In this example, there are two pumps, which will be set to alternate duty assist, so they come on alternately. Pump 1 is to be set to Relay 1, Pump 2 to Relay 2, and the high-level alarm to Relay 5.
This will operate as follows. During normal operation, pump 1 will come on at 1.4 m, and pump down to 0.56 m. The setpoints are then shifted to pump 2, which will come on first next time.
During peak periods, when pump 1 cannot cope, pump 1 will come on at
1.4 m, pump 2 will come on at 1.96 m, and pump down to 0.56 m. The setpoints are then shifted to pump 2, which will come on first next time.
If neither pump can cope, and the level rises to 2.38 m, then the alarm relay (relay 5) will come on, and go off when the level falls to 2.24 m. This will indicate insufficient capacity of the pumps.
Empty Distance (P105), 3.5m
100%. Span (P106), 2.8m
85%. High alarm on (P253), 2.38m
80%. High alarm off (P254), 2.24m
0%, Empty level
20%. Pump 1+2 off (P214, 224), 0.56m
50%. Pump 1 on (P213), 1.4m
70%. Pump 2 on (P223), 1.96m
Page 48
QUANTUM2 INSTRUCTION MANUAL
48
The display will show the level in the sump and the mA output will be representative of level where 4mA = empty level (0%) and 20mA = 2.9m (100%).
To program the Quantum2 for Example 2 Sump control (pump down) by using the Quick Setup menu proceed as follows. If required to access Program Mode, key in the passcode 1997 and press ENTER
At the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump/Custom
2 = Pump Down
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 1
Pump No. 2
2 = Set to relay 2
Type Alarm 1
1 = High Alarm
Alarm No. 1
5 = Set to relay 5
Xducer (P101)
2 = dB6
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Quantum2 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application, they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed, and entering new values to relay setpoints as required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
Page 49
PULSAR MEASUREMENT
49

CHAPTER 5 PARAMETER GUIDE

This chapter describes all the parameters in your Quantum2, as they appear in the menu system.

Menu System

Shown below is a set of charts to show you how all the various functions and features can be found using the menu system.
For further details and a full description of all parameters refer to the Parameter Listings and Descriptions section of this chapter.

Top Level Menu

Quick Setup
Application
Relays
Pump
Advanced
Digital Inputs
FS Backup
Compensation
Stability
System
Test
Device Comm
Echo
Processing
Tariff Guard
Data Logs
Pump
Volume
Pump
Efficiency
Display
mA
Output 1
mA
Output 2
Page 50
QUANTUM2 INSTRUCTION MANUAL
50

Application Menu

Operation
Distances
P100
Mode
P101
Transducer
P104
Measurement
Units
P102
Material
P105
Empty Level
P106
Span
P107
Near Blanking
P108
Far Blanking
Page 51
PULSAR MEASUREMENT
51

Relays Menu

Relay
1
Relay
10
Pump
Trips
Relay 2 to Relay 9
Rly 2 – P220, Rly 3 – P230, Rly 4 – P240, Rly 5 – P250 Rly 6 – P260, Rly 7 – P270, Rly 8 – P280, Rly 9 – P290
Type
P210 Type
P570 Type
P211
Function
P213 Set 1
P212
Alarm ID
or
Pump Group
P214 Set 2
P215 Set 3
as
required
P216
Allocat.
P217
Closures
P218
Fail Safe
P219
R1
Max
Rate if
P210 = 2
Rly 2 – P221, Rly 3 – P231, Rly 4 – P241, Rly 5 – P251
Rly 6 – P261, Rly 7 – P271, Rly 8 – P281, Rly 9 – P291
Function
Rly 2 – P222, Rly 3 – P232, Rly 4 – P242, Rly 5 – P252 Rly 6 – P262, Rly 7 – P272, Rly 8 – P282, Rly 9 – P292
Alarm ID or Pump Group
Rly 2 – P223, Rly 3 – P233, Rly 4 – P243, Rly 5 – P253 Rly 6 – P263, Rly 7 – P273, Rly 8 – P283, Rly 9 – P293
Relay Setpoint 1
Rly 2 – P224, Rly 3 – P234, Rly 4 – P244, Rly 5 – P254
Rly 6 – P264, Rly 7 – P274, Rly 8 – P284, Rly 9 – P294
Relay Setpoint 2
Rly 2 – P225, Rly 3 – P235, Rly 4 – P245, Rly 5 – P255 Rly 6 – P265, Rly 7 – P275, Rly 8 – P285, Rly 9 – P295
Relay Setpoint 3 as required
Rly 2 – P226, Rly 3 – P236, Rly 4 – P246, Rly 5 – P256 Rly 6 – P266, Rly 7 – P276, Rly 8 – P286, Rly 9 – P296
Relay Allocation
Rly 2 – P227, Rly 3 – P237, Rly 4 – P247, Rly 5 – P257
Rly 6 – P267, Rly 7 – P277, Rly 8 – P287, Rly 9 – P297
Relay Closures
Rly 2 – P228, Rly 3 – P238, Rly 4 – P248, Rly 5 – P258 Rly 6 – P268, Rly 7 – P278, Rly 8 – P288, Rly 9 – P298
Fail Safe
Rly 2 – P229, Rly 3 – P239, Rly 4 – P249, Rly 5 – P259 Rly 6 – P269, Rly 7 – P279, Rly 8 – P289, Rly 9 – P299
Max Rate if P2*0 = 2
P571
Function
P572
Alarm ID
or
Pump
Group
P573 Set 1
P574
Set 2
P575
Set 3
as
required
P576
Allocat.
P577
Closures
P578
Fail Safe
P579
R1
Max
Rate if
P570 = 2
P307
Trip
Limit
P311
to
P318
Pump 2
to
Pump 9
Trips
P310
Pump 1
Trip
P309 Reset Pulse
P308
Reset
Int.
P319
Pump 10
Trip
Page 52
QUANTUM2 INSTRUCTION MANUAL
52

Pump Advanced Menu

Stopping
Wall Cling
P348
Stop Delay
P360
Wall Cling
Run On
P349
Prime
Level
P350
Run
Interval
P351
Run
Duration
Starting
P352
Start
Delay
P353
Power
Delay
Exercise
P354
Exercise
Enable
P355
Idle Time
P356
Exercise
Time
P357
Minimum
Head
Storm
P370
Pump
Disable
P371
Disable
Time
Rate
Method
P116 Rate
Calc.
P117 RMA
Delay
Page 53
PULSAR MEASUREMENT
53

Digital Inputs Menu

Common
Par
Digital
Input 1
P300
Maximum
Attempts
P301
Switch
Mode
P302
Override
Delay
P303
Minimum
Override
P304
Input Delay
P305
Input Filter
P306
Override
Level
P372
Type
P373
Function
P374
Assign.
Input 2 – P375, Input 3 – P378
Input 4 – P381, Input 5 – P384
Input 6 – P387
Type
Digital Input 2
to
Digital Input 6
Input 2 – P376, Input 3 – P379 Input 4 – P382, Input 5 – P385
Input 6 – P388
Function
Input 2 – P377, Input 3 – P380 Input 4 – P383, Input 5 – P386
Input 6 – P389
Assign.
Digital
Input 7
P390
Type
P391
Function
P392
Assign.
Page 54
QUANTUM2 INSTRUCTION MANUAL
54

Float Switch Backup

Common
Par
Digital
Input 1
P330
Mode
P331
Input Filter
P332
Pump Run
Time
P333
Type
P334
Function
P335
Forced
Level
Input 2 – P336, Input 3 – P339
Input 4 – P342, Input 5 – P345
(Type)
Digital Input 2
to
Digital Input 5
Input 2 – P337, Input 3 – P340 Input 4 – P343, Input 5 – P346
(Function)
Input 2 – P338, Input 3 – P341 Input 4 – P344, Input 5 – P347
(Forced Level)
Digital
Input 6
P363
Type
P364
Function
P365
Forced
Level
Page 55
PULSAR MEASUREMENT
55

Tariff Guard Menu

Set Up
Peak Time
1
Peak Time 2
to
Peak Time 9
PT2 – P406, PT3 – P412, PT4 – P418, PT5 – P424,
PT6 – P430, PT7 - P436,
PT8 – P443, PT9 – P448,
Peak Time
10
PT2 – P407, PT3 – P413, PT4 – P419, PT5 – P425,
PT6 – P431, PT7 - P437,
PT8 – P444, PT9 – P449,
PT2 – P408, PT3 – P414, PT4 – P420, PT5 – P426,
PT6 – P432, PT7 - P438,
PT8 – P445, PT9 – P450,
PT2 – P409, PT3 – P415,
PT4 – P421, PT5 – P427,
PT6 – P433, PT7 - P439,
PT8 – P446, PT9 – P451,
PT2 – P410, PT3 – P416, PT4 – P422, PT5 – P428,
PT6 – P434, PT7 - P440,
PT8 – P447, PT9 – P452,
PT2 – P411, PT3 – P417, PT4 – P423, PT5 – P429,
PT6 – P435, PT7 - P441,
PT8 – P448, PT9 – P453,
P393
Enable
P394
Lead Time
P395
Lag Time
P396
Minimum
Pump Time
P398
Overflow
Level
P400
PT1 Day
P401
PT1 Week
P402
PT1
Start Peak
(Date)
P403
PT1
End Peak
(Date)
P404
PT1
Start
(Time)
P405
PT1
End
(Time)
P454
PT1 Day
P455
PT1 Week
P456
PT1
Start Peak
(Date)
P457
PT1
End Peak
(Date)
P458
PT1
Start
(Time)
P459
PT1
End
(Time)
Page 56
QUANTUM2 INSTRUCTION MANUAL
56

Data Logs Menu

P511
Pump 1
Starts
Tot. Audit
Temperature
Pump 1
Pump 2 to 9
Pump 10
P516, P522
P528, P534 P540, P546
P552, P558
Pump Hours
P517, P523
P529, P535 P541, P547
P553, P559
Pump Starts
P518, P524
P530, P536 P542, P548
P554, P560
Pump Starts
per
Hour
P519, P525
P531, P537 P543, P549
P555, P561
Pump Run On
P460
Vol. Date 1
P461
Volume 1
P462, 464,
466, 468, 470,
472, 474, 476
Total Dates
2 to 9
P463, 465,
467, 469, 471,
473, 475, 477
Totals
2 to 9
P478
Vol. Date 10
P580
Min. Temp
P479
Volume 10
P581
Min. Temp.
Date
P582
Min. Temp.
Time
P583
Max. Temp.
P584
Max. Temp.
Date
P585
Max. Temp.
Time
P586
Current
Temperature
P510
Pump 1
Hours
P512
Pump 1
Starts
per
Hour
P513
Pump 1
Run On
P564
Pump 6
Hours
P565
Pump 6
Starts
P566
Pump 6
Starts
per
Hour
P567
Pump 6
Run On
P514
Pump 1
Draw
P515
Pump 1
Effic.
P520, P526
P532, P538
P544, P550
P556, P562
Pump Draw
P521, P527
P533, P539 P545, P551
P557, P563
Pump Effic.
P568
Pump 6
Draw
P569
Pump 6
Effic.
P480
Clear Logs
Page 57
PULSAR MEASUREMENT
57

Pumped Volume Menu

Set Up
P205
Pump Vol.
Enabled
P206
Settle Time
P207
Inflow
Method
Conversion
P600
Vessel Shape
P601
As Required
Vol. Dimension 1
P602
As Required
Vol. Dimension 2
P603
As Required
Vol. Dimension 3
P604
Calculated
Volume
P605
Volume Units
P606
Correct. Factor
P607
Max. Volume
P612, 614, 616, 618,
620, 622, 624, 626, 628, 630, 632, 634, 636, 638, 640, 642, 644, 646, 648, 650, 652, 654, 656, 658, 660, 662, 664, 666,
668, 670
Level Bkpts. 2 to 31
Breakpoints
P610
Level Bkpt. 1
P611
Vol. Bkpt. 1
P613, 615, 617, 619,
621, 623, 625, 627,
629, 631, 633, 635, 637, 639, 641, 643, 645, 647, 649, 651, 653, 655, 657, 659, 661, 663, 665, 667,
669, 671
Vol. Bkpts. 2 to 31
P672
Level Bkpt. 32
P673
Vol. Bkpt. 32
Tables
P696
Reset
Bkpts.
P697
Number
Bkpts. Set
Page 58
QUANTUM2 INSTRUCTION MANUAL
58

Efficiency Menu

Set Up
P187
Pump Effic.
P188
Calib. Delay
P189
Cal. Duration
P190
Persist Cnt.
P191
Demote
Pumps
P192
Demote
Flags
P193
Calib. Pumps
Page 59
PULSAR MEASUREMENT
59

Display Menu

Options
Fail Safe
Auxiliary
Bargraph
P802
Display
Offset
P801
Decimal
Places
P804
Display
Conversion
P805
Display
Source
P808
Fail Mode
P809
Fail Time
P810
Units
P811
Alarms
P812
Pumps
P813
Control
P814
Misc.
P815
Auxiliary
Source
P816
Totaliser
(R)
P817
Auxiliary
Offset
Totaliser
P829
Bargraph
P820
Totaliser
P821
Totaliser (R)
P822
Totaliser
Decimal
P823
Totaliser
Multiplier
P800
Display
Units
Page 60
QUANTUM2 INSTRUCTION MANUAL
60

mA Output 1 Menu

mA Output 2 Menu

Range
Operation
Setpoint
Limits
Trim
Fail Safe
Allocation
P830
mA Out
Range
P831
mA Out
Mode
P834
Low
Value
P836
Low
Limit
P835
High
Value
P838
Low
mA
Trim
P840
Fail
Mode
P841
Allocation
P837
High
Limit
P839 High
mA
Trim
Range
Operation
Setpoint
Limits
Trim
Fail Safe
Allocation
P890
mA2
Out
Range
P891
mA2 Out
Mode
P892
Low
Value
P894
Low
Limit
P893
High
Value
P896
Low
mA
Trim
P898
Fail
Mode
P899
Allocation
P895
High
Limit
P897 High
mA
Trim
Page 61
PULSAR MEASUREMENT
61

Compensation

Stability Menu

Offset
Temperature
Velocity
P851
Measurement
Offset
P852
Temperature
Source
P853
Allocation
P854
Fixed
Temperature
P860
Sound
Velocity
P861
Calibration
Distance 1
P862
Calibration
Distance 2
Damping
Indicator
Rate
Filters
P870
Fill
Damping
P871
Empty
Damping
P872
Fill
Indicator
P873
Empty
Indicator
P874
Rate Update
P875
Rate Time
P876
Rate Distance
P877
Rate Value
P878
Lower Cutoff
P880
Gate Mode
P881
Fixed Distance
P882
Process Filter
P884
Peak Percent
Page 62
QUANTUM2 INSTRUCTION MANUAL
62

Echo Processing Menu

Xdr. 1 Status
Xdr. 2 Status
P900
Xdr. 1 Status
P901
Echo
Confidence 1
P902
Echo Strength 1
P903
Average Noise 1
P904
Peak Noise 1
P905
Sensitivity 1
P906
Side Clearance 1
P910
Xdr. 2 Status
P916
Side Clearance 2
P915
Sensitivity 2
P914
Peak Noise 2
P913
Average Noise 2
P912
Echo Strength 2
P911
Echo
Confidence 2
Page 63
PULSAR MEASUREMENT
63

System Menu

Passcode
Backup
System
Info
Date
&
Time
LED
Colour
Daylight
Saving
P921
Enable Code
P925
Parameter
Backup
P926 Software Revision
P931
Date
P935
Off
Colour
P970
DST
Enable
P922
Passcode
P927
Hardware
Revision
P928
Serial
Number
P929
Site
Ident.
P930
Factory
Default
P932 Time
P933
Date
Format
P936
Alarm
Colour
P937
Pump
Colour
P938
Control
Colour
P939
Misc.
Colour
P971
DST
Difference
P972
DST
Start Time
P973
Start Day
P974
Start Week
P975
Start
Month
P976
DST
End Time
P977
End Day
P978
End Week
P979
End Month
Page 64
QUANTUM2 INSTRUCTION MANUAL
64

Device Comm Menu

RS485 Setup
(Optional)
If Comms.
Type is
Modbus
P130
Device
Mode
P131
Protocol
P132
Device
Addr.
P133
Device
Baud
RS232
Setup
P61
Comms Baud
Remote
Alarm
P144
Call Type
P145
Tel. No. 1
P146
Tel. No. 2
P147
Tel. No. 3
P134
Parity
P135
Stop Bit
P136
Data
Format
P137
Delay in
milli sec.
If Comms.
Type is
Profibus
P132
Device
Addr.
P143
Addr. Lock
Page 65
PULSAR MEASUREMENT
65

Test Menu

Simulation
Hardware
P980
Simulate
P981
Increment
P982
Rate
P983
Start Level
P984
Incremental
Change
P990
Self Test
P991
Hardware Test
P992
mA Out Test
P994
Transducer Test
P995
Keys Test
P996
Relay Test
Page 66
QUANTUM2 INSTRUCTION MANUAL
66

CHAPTER 6 PARAMETER LISTING AND DESCRIPTION

Application Parameters Operation

P100 Mode of Operation

This parameter sets the mode of operation, when in run mode, and can be set to one of the following:
OPTION
DESCRIPTION
1 = Distance (Default)
Display shows the distance from the transducer face to the surface of the material measured.
2 = Level
Shows how full a vessel is.
3 = Space
Shows how empty a vessel is.
4 = Average Level
Display shows the average level of 2 points of measurement
5 = Differential
Display shows the differential level between 2 points of measurement

P101 Xducer (Transducer)

This parameter should be set to the transducer being used with the unit, and can be set to one of the following:
OPTION
DESCRIPTION
1 = dB3 (Default)
Transducer is a dB3. Range = 0 to 3 metres
2 = dB6
Transducer is a dB6. Range = 0.3 to 6 metres
3 = dB10
Transducer is a dB10. Range = 0.3 to 10 metres
4 = dB15
Transducer is a dB15. Range = 0.5 to 15 metres
5 = dB25
Transducer is a dB25. Range = 0.6 to 25 metres
6 = dB40
Transducer is a dB40. Range = 1.2 to 40 metres
7 = dBS6
Transducer is a dBS6. Range = 0.2 to 6 metres
8 = dBMach3
Transducer is a dBMach3. Range 0.3 to 1.50 metres
*11 = dBR16
Transducer is a mmWAVE radar. Range = 0.077 to 16 metres
*12 = dBR8
Transducer is a mmWAVE radar. Range = 0.077 to 8 metres
Important Notice
*Please consult your local Pulsar distributor for the versions of firmware that the mmWAVE radars are available in.
Page 67
PULSAR MEASUREMENT
67

P102 Material

This parameter should be set to the type of material being monitored.
OPTION
DESCRIPTION
1 = Liquid (Default)
Used for liquids and flat solid materials.
2 = Solid
Used for sold material that is heaped or at an angle.
3 = Closed Tank
Use for applications within a closed tank or where a secondary echo response may become focused to create a larger echo than the first.

Dimensions

P104 Measurement Units

This parameter sets the units you want to use for programming and display.
OPTION
DESCRIPTION
1 = metres (Default)
All units of measurement are Metres
2 = cm
All units of measurement are Centimetres
3 = mm
All units of measurement are Millimetres
4 = feet
All units of measurement are Feet
5 = inches
All units of measurement are Inches

P105 Empty Level

This parameter is to be set to the maximum distance from the face of the transducer to the empty point, in P104 Measurement Units. Note this value affects span as well, (see the following important information notices), so should be set before span.
Important Notice
When changing the Empty Distance (P105) you can also recalculate the values for the Span so that it equals the empty distance (P105) minus Near Blanking (P107) and the Relay Setpoints, so that they remain at the same percentage values of the empty distance as they were before you changed the empty distance
(P105). You will be asked the question “Recalculate Span?” if you choose yes
(enter 1), then the span will be recalculated. Any other answer will leave the
span at its original value. You will then be asked if you want to “Recalculate
Setpoints?”, if you choose yes (enter 1), then all Relay Setpoints will be recalculated as a percentage of the new empty distance. Any other answer will leave the setpoints at their original values.
Page 68
QUANTUM2 INSTRUCTION MANUAL
68

P106 Span

This parameter should be set to the maximum distance from the Empty Level (P105) to the maximum material level. It is automatically set to be
equal to the Empty Level (P105) less the Near Blanking distance (P107) when you set the empty level.

P107 Span

This parameter is the distance from the face of the transducer that is not measurable and is pre-set to the minimum value dependant on the Transducer (P101) selected. It should not be set to less than this figure, but can be increased, typically to ignore close in obstructions.
TRANSDUCER
NEAR BLANKING DISTANCE
P101 = dBMach3
Default blanking distance = 0.00 metres
P101 = dB3
Default blanking distance = 0.125 metres
P101 = dB6
Default blanking distance = 0.30 metres
P101 = dB10
Default blanking distance = 0.30 metres
P101 = dB15
Default blanking distance = 0.50 metres
P101 = dB25
Default blanking distance = 0.60 metres
P101 = dB40
Default blanking distance = 1.20 metres
P101 = dBS6
Default blanking distance = 0.20 metres
P101 = dBR16
Default blanking distance = *0.077 metres
P101 = dBR8
Default blanking distance = *0.077 metres
*The signal emanates from the curved face of the radar, but for the purposes of measurement it is taken from the drip shield.

P108 Far Blanking Distance

This is the distance (as a percentage of the empty level P105) beyond the empty point that the unit will be able to measure, and by default is pre-set to 20% of the empty level.
If the surface being monitored can be extended beyond the empty level (P105) then the far blanking distance can be increased to a max. of 100% of the empty level, provided it does not exceed the max range of the transducer being used. This parameter is always entered as a % of the empty level.
Important Notice

When using the dB Mach 3 the empty distance is measured from the end of the horn to the empty point in P104 Measurement Units.

Page 69
PULSAR MEASUREMENT
69

Relay Parameters

All relay related parameters are prefixed with a 2**. The second digit of the three-figure parameter number denotes the relay
number as follows:
21* parameters for Relay 1 22* parameters for Relay 2 23* parameters for Relay 3 24* parameters for Relay 4 25* parameters for Relay 5 26* parameters for Relay 6 27* parameters for Relay 7 28* parameters for Relay 8 29* parameters for Relay 5 57* parameters for Relay 10
The third digit selects specific parameter for the setting of the relays, which can be selected individually and results in the following parameter numbers for each relay:
Relay 1 210 to 219
Relay 2 220 to 229
Relay 3 230 to 239
Relay 4 240 to 239
Relay 5 250 to 239
Relay 6 260 to 269
Relay 7 270 to 279
Relay 8 280 to 289
Relay 9 290 to 299
Relay 10 570 to 579
Page 70
QUANTUM2 INSTRUCTION MANUAL
70

P210, 220, 230, 240, 250 - Relay Type

This parameter defines what type each relay should be, see the table below for available options:
OPTION
DESCRIPTION
0 = Not in use (Default)
Relay is not in use or programmed and the LED will always be off.
1 = Alarm
Relay is programmed as an alarm relay, which will de- energise ON, and energise OFF. This will ensure an alarm is raised if the power fails to the unit.
2 = Pump
Relay is programmed as a pump relay, which will energise ON, and de-energise OFF.
3 = Control
Relay is programmed as a control relay, which will energise ON, and de-energise OFF.
4 = Miscellaneous
Relay is programmed as a miscellaneous relay, which will energise ON, and de-energise OFF.
5 = Pump by time
Relay is programmed as a pump relay, which will energise at its ON level setpoint, and de-energise at its
OFF level setpoint or after a predetermined time period, whichever occurs first.
Page 71
PULSAR MEASUREMENT
71

Alarms

P210, 220, 230, 240, 250 = 1 (Alarm) The second parameter for each relay determines the function of the alarm.

P211, 221, 231, 241, 251 – Relay Function

OPTION
DESCRIPTION
0 = Off (Default)
Relay will not operate.
1 = Level
Alarm is based on the level in the vessel, and the type of level alarm (P212, 222, 232, 242, 252) and two setpoints must be set (P2b3, 223, 233, 243, 253 & 214, 224, 234, 244,
254). Setpoints are entered in display units or % of span as referenced to empty level.
2 = Rate of Change
Alarm is based on the rate of change of level in the vessel, and the type of rate of change alarm (212, 222, 232, 242,
252), and two setpoints must be set (213, 223, 233, 243, 253 & 214, 224, 234, 244, 254). Setpoints are entered in Display Units per minute or % of span per minute and a negative value should be entered for a Rate Alarm on a de-creasing level, and a positive value for an increasing level.
3 = Temperature
Alarm is based on the temperature, and the type of temperature alarm (P212, 222, 232, 242, 252) and two setpoints must be set (P213, 223, 233, 243, 253 & P214, 224, 234, 244, 254). The temperature used depends on the temperature source selected (P852). Setpoints are entered in
o
C.
4 = Loss of Echo
Alarm is raised if the Failsafe Timer (P809) expires. No setpoints are required.
5 = Loss of Clock
Alarm is raised if the expires. No setpoints are required.
6 = Pump Efficiency
When Pump Efficiency is enabled, Alarm is based on the Efficiency of the pump which is allocated to the Relay I.D. (P212, 222, 232, 242, 252, 262, 272, 282, 292, 572) and two setpoints must be set (P213, 223, 233, 243, 253, 263, 273, 283, 293 & P214, 224, 234, 244, 254, 264, 274, 284, 294,
574). Setpoints are entered in %.
Page 72
QUANTUM2 INSTRUCTION MANUAL
72
OPTION
DESCRIPTION
7 = Device Fail
Alarm is raised if a device, connected to the relay assigned in Alarm ID (P212, 222, 232, 242, 252, 262, 272, 282, 292,
572), fails. E.g. pump is put out of service. No setpoints are required.
8 = Device Alarm
Alarm is raised if a fail signal is detected on the digital input as assigned in Alarm ID (P212, 222, 232, 242, 252, 262, 272, 282, 292, 572) No setpoints are required.
9 = OVF Alarm
Alarm is raised to indicate a “High” level or a potential Overflow” condition and four setpoints must be set,
Overflow Level (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573). Reset Level (P214, 224, 234, 254, 264, 274, 284, 294, 574). High Alarm Level (P215, 225, 235, 245, 255, 265, 275, 285, 295, 575). All level Setpoints are entered in Display Units or % of span as referenced to Empty Level *. Time to Overflow (P219, 229, 239, 249, 259, 269, 279, 289,
579). Setpoint entered in minutes.
10 = RMA Alarm
Alarm is based on the rate of change of level during a pumping cycle, and on the type of RMA alarm (P212, 222, 232, 242, 252, 262, 272, 282, 292, 572) and 3 setpoints must be set. Alarm Setpoint (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573) in rate measurement units. Persistence Time (P214, 224, 234, 254, 264, 274, 284, 294, 574) in seconds. Prime Head Level (P215, 225, 235, 245, 255, 265, 275, 285, 295, 575) in level display units, alarm will not activate below this level.
15 = Tariff Alarm (Only
available in units with firmware version 7.5.1 and above)
Alarm is raised when the unit enters Tariff Guard mode. Tariff Guard enable (P393) must be set to ‘1’ for this option to be selectable. No setpoints are required.
To set figures in %, press the hot key to show and enter % figure relative to empty level.
Important Notice
The Loss of Echo, and Loss of Clock will also be shown on the display as “Lost Echo”, and “Lost Clock” respectively.
Page 73
PULSAR MEASUREMENT
73
The third parameter for each relay determines the Alarm ID for the relay you wish to set.

P212, 222, 232, 242, 252 – Relay Alarm ID

When P211, 221, 231, 241, 251 =4 (Loss of Echo) or 5 (Loss of Clock) This parameter has no function and will not be displayed.
P211, 221, 231, 241, 251 = 1 (Level), 2 = Rate of Change or 3 (Temp) This parameter defines which alarm type, or identification, the relay should
respond to, as follows:
OPTION
DESCRIPTION
SETPOINTS
1 = General (Default)
Relay goes “ON” when the
value reaches the ON
setpoint and goes “OFF”
when the value reaches the OFF setpoint.
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 is ON Setpoint; P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 is OFF Setpoint
2 = High
Relay goes “ON” when the
value rises to the ON
setpoint and goes “OFF”
when the value lowers to the OFF setpoint.
ON>OFF Relay Setpoints P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 and P214, 224, 234, 244, 254, 264, 274, 284, 294,
574. Setpoints can be set in any order as the unit
‘knows’ that you are
setting a high-level alarm.
3 = HiHi
Same as 2 = High, but different identifier
4 = Low
Relay goes “ON” when the
value lowers to the ON
setpoint and goes “OFF”
when the value rises to the OFF setpoint.
ON<OFF Relay Setpoints P213, 223, 233,243, 253, 263, 273, 283, 293, 573 and P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 Setpoints can be set in any order as the unit
‘knows’ that you are
setting a low level alarm.
Page 74
QUANTUM2 INSTRUCTION MANUAL
74
OPTION
DESCRIPTION
SETPOINTS
5 = LoLo
Same as 4 = Lo, but different identifier
6 = In bounds
Relay goes “ON” if value is
inside the zone between the two setpoints.
Relay Setpoints, P213, 223, 233 and P214, 224, 234 can be set in any order as the unit ‘knows’ that you are setting an inbounds alarm.
7 = Out of bounds
Relay goes “ON” if value is
outside the zone between the two setpoints.
Relay Setpoints P213, 223, 233 and P214, 224, 234 can be set in any
order as the unit ‘knows’
that you are setting an out of bounds alarm.
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 4 (Loss of Echo), 5 (Loss of Clock) or 9 = OVF Alarm
This parameter has no function and will not be displayed.
Page 75
PULSAR MEASUREMENT
75
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 6 (Pump Efficiency)
This parameter assigns the alarm to the appropriate pump relay as detailed below.
OPTION
DESCRIPTION
0 = Off (Default)
Relay will not operate.
1 = Relay 1
Alarm is assigned to pump on Relay 1
2 = Relay 2
Alarm is assigned to pump on Relay 2
3 = Relay 3
Alarm is assigned to pump on Relay 3
4 = Relay 4
Alarm is assigned to pump on Relay 4
5 = Relay 5
Alarm is assigned to pump on Relay 5
6 = Relay 6
Alarm is assigned to pump on Relay 6
7 = Relay 7
Alarm is assigned to pump on Relay 7
8 = Relay 8
Alarm is assigned to pump on Relay 8
9 = Relay 9
Alarm is assigned to pump on Relay 9
10 = Relay 10
Alarm is assigned to pump on Relay 10
11 = All
Alarm is assigned to all relays designated as pump
Page 76
QUANTUM2 INSTRUCTION MANUAL
76
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 7 (Device Fail) This parameter defines which failed device relay, the alarm should respond
to, as follows.
OPTION
DESCRIPTION
SETPOINTS
1 = Fail Relay 1 (Default)
Relay goes “ON” when a device failure is detected on relay 1.
None
2 = Fail Relay 2
Relay goes “ON” when a device failure is detected on relay 2.
None
3 = Fail Relay 3
Relay goes “ON” when a device failure is detected on relay 3.
None
4 = Fail Relay 4
Relay goes “ON” when a device failure is detected on relay 4.
None
5 = Fail Relay 5
Relay goes “ON” when a device failure is detected on relay 5.
None
6 = Fail Relay 6
Relay goes “ON” when a device failure is detected on relay 6.
None
7 = Fail Relay 7
Relay goes “ON” when a device failure is detected on relay 7.
None
8 = Fail Relay 8
Relay goes “ON” when a device failure is detected on relay 8.
None
9 = Fail Relay 9
Relay goes “ON” when a device failure is detected on relay 9.
None
10 = Fail Relay 10
Relay goes “ON” when a device failure is detected on relay 10.
None
11 = Any 1 Fail
Relay goes “ON” when a device failure is detected on any 1 relay.
None
12 = Any 2 Fail
Relay goes “ON” when 2 device failures are detected on any 2 relays
None
Page 77
PULSAR MEASUREMENT
77
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 8 (Device Alarm)
This parameter defines which digital input, the alarm should respond to, as follows.
OPTION
DESCRIPTION
SETPOINTS
1 = Fail Input 1 (Default)
Relay goes “ON” when a fail signal is detected on digital input 1.
None
2 = Fail Input 2
Relay goes “ON” when a fail signal is detected on digital input 2.
None
3 = Fail Input 3
Relay goes “ON” when a fail signal is detected on digital input 3.
None
4 = Fail Input 4
Relay goes “ON” when a fail signal is detected on digital input 4.
None
5 = Fail Input 5
Relay goes “ON” when a fail signal is detected on digital input 5.
None
6 = Fail Input 6
Relay goes “ON” when a fail signal is detected on digital input 6.
None
7 = Fail Input 7
Relay goes “ON” when a fail signal is detected on digital input 7.
None
Page 78
QUANTUM2 INSTRUCTION MANUAL
78
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 10 (RMA Alarm).
This parameter defines which alarm type, or identification, the relay should respond to, as follows.
ALARM ID
DESCRIPTION
SETPOINTS
1 = Blockage (Default)
Relay goes “ON” when the pumping rate
is lower than the Alarm setpoint for longer than the Persistence Time provided the level is above the Prime
Head and goes “OFF” when the pumping
rate rises above the Alarm setpoint for longer than the Persistence Time.
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 is Alarm Setpoint; P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 is Persistence Time; P215, 225, 235, 245, 255, 265, 275, 285, 295, 575 is Prime Head.
2 = Burst
Relay goes “ON” when the pumping rate
is above than the Alarm setpoint for longer than the Persistence Time provided the level is above the Prime
Head and goes “OFF” when the pumping
rate lowers below the Alarm setpoint for longer than the Persistence Time
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 is Alarm Setpoint; P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 is Persistence Time; P215, 225, 235, 245, 255, 265, 275, 285, 295, 575 is Prime Head.
Page 79
PULSAR MEASUREMENT
79
The fourth parameter and the fifth parameter for each relay set the Alarm ON” and “OFF” points. For a high alarm the “ON” is set higher than OFF”. For low alarm then “ON” is set lower than OFF”. See the appropriate alarm ID, table (P212, 222, 232, 242, 252, 262, 272, 282 292 572) for further information.
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 1 (Level), 2 (Rate of Change), 3 (Temp.) or 6 (Efficiency)
P213, P223, P233, P243, P253, P263, P273, P283, P293, P573

P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 – Relay Setpoint 1

Determines the ON’ or ‘OFF’ point for the alarm according to the ID selected.

P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 – Relay Setpoint 2

Determines the ‘ON’ or ‘OFF’ point for the alarm according to the ID selected.
To set figures in % press the hotkey to show and enter % figure, relative to empty level.
Important Notice
Setpoints are entered in values according to the function selected. Level - entered in Display Units or % of span as referenced to Empty Level.
Rate of Change - entered in Display Units per minute or % of span per minute.
For an alarm on an increasing level enter setpoints as a positive value, for an alarm on a decreasing level enter setpoints as a negative value. Temperature - entered in ºC.
See the appropriate alarm function, table (P211, 221, 231, 241 and 251) for further information.
Page 80
QUANTUM2 INSTRUCTION MANUAL
80
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 4 (Loss of Echo), 5 (Loss of Clock), 7 (Device Fail) or 8 (Device Alarm)
These parameters have no function and will not be displayed.
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 9 (OVF Alarm)

P213, P223, P233, P243, P253, P263, P273, P283, P294, P573 - Relay Setpoint 1

This parameter determines the “Overflow Level”, this is the level at which an overflow would occur and is the level that the unit will calculate the time to overflow to.

P214, P224, P234, P244, P254, P264, P274, P284, P294, P574 - Relay Setpoint 2

This parameter determines the “Reset Level”, this level determines the point the level has to be below (of fall below) before an activated alarm can be considered to be deactivated, provided the time to overflow does not
exceed the “Time to Overflow” (P219, 229, 238, 249, 259, 269, 279, 289, 299,
579) and the level is below the Reset Level”, the alarm will turn “OFF”.

P215, P225, P235, P245, P255, P265, P275, P285, P295, P575 - Relay Setpoint 3

This parameter determines the level at which the “High Alarm” will be activated and should be set below or at the same level as the “Overflow
Level” (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573).
Relay setpoints 1, 2 and 3 are entered in values of Measurement Units (P104)

P219, P229, P239, P249, P259, P269, P279, P289, P299, P579 - OVF Time

This parameter determines the time, prior to a potential overflow occurrence, at which the alarm will activate if it is calculated that an overspill is likely to occur.
Page 81
PULSAR MEASUREMENT
81
When P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 =10 (RMA Alarm)

P213, P223, P233, P243, P253, P263, P273, P283, P294, P573 - Relay Setpoint 1

This parameter determines the RMA alarm ON/OFF point, this is the rate of change during pumping at which a potential burst or blockage condition
may occur (depending on Relay Alarm ID). Units are in rate measurement units and are dependent on P116 Rate Method.

P214, P224, P234, P244, P254, P264, P274, P284, P294, P574 - Relay Setpoint 2

This parameter determines the “Persistence Time”. This is the amount of
time the rate has to persist above/below the Alarm Setpoint (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573) before the alarm will change state. It
is used to prevent relay “chatter” if the rate is near the alarm setpoint. Units
are in Seconds.

P215, P225, P235, P245, P255, P265, P275, P285, P295, P575 - Relay Setpoint 3

This parameter determines the “Prime Head Level”. The RMA function will not raise an alarm below this level but will allow an alarm to turn off. Units are in Measurement Units (P104).
Page 82
QUANTUM2 INSTRUCTION MANUAL
82

Pumps

P210, 220, 230, 240, 250, 260, 270, 280, 290, 570 = 2 (Pump)
When a relay is being used for a pump function, the second parameter determines the pump duty that will be used to determine the operating cycle.

P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 – Relay Function

This parameter defines which pump duty the relay should respond to as follows:
PUMP DUTY
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Fixed duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints. (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294,
574).
2 = Fixed duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints. (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294, 574).
3 = Alternate duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints, (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294,
574). but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
4 = Alternate duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints, (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
Page 83
PULSAR MEASUREMENT
83
PUMP DUTY
DESCRIPTION
5 = Duty backup and assist
First pump comes on, if it cannot cope, it goes off and next pump comes on (duty backup). This continues until the last pump comes on and if it cannot cope the first pump comes back on to assist the last pump (duty assist) if the level continues to rise all other pumps will come on (assist) in turn until the level decreases to the pump off points. Each pump has its own setpoints, (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254,264, 274, 284, 294, 574).
6 = Service ratio duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). And a service ratio setting. The third setpoint (P215, 225, 235, 245, 255, 265, 275, 285, 295, 575) is used to set the service ratio. Each time a pump is required to start then the pump with the least running hours (with respect to the service ratio) is started (i.e. the setpoints are re-assigned accordingly). For example, if two pumps A and B have the service ratio set to 2 and 1 respectively, then pump A will operate for twice as many hours as pump B.
Page 84
QUANTUM2 INSTRUCTION MANUAL
84
PUMP DUTY
DESCRIPTION
8 = Service ratio duty backup
The first pump switched on is the first pump to be switched off, etc. regardless of the set points, so the setpoints are dynamically changed to enable this. If a pump fails to meet the demand (due to malfunction, intake blockage and so on), then it is stopped and another pump shall take over. Each time a pump is required to start then the pump with the least running hours (with respect to the service ratio) is started (i.e. the setpoints are re-assigned accordingly). Each pump has its own setpoints (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). The third setpoint (P215, 225, 235, 245,255, 265, 275, 285, 295, 575) is used to set the service ratio. For example, if two pumps A and B have the service ratio set to 2 and 1 respectively, then pump A will operate for twice as many hours as pump B.
8 = First On First Off Alternate duty assist
The first pump switched on is the first pump to be switched off, etc. regardless of the set points, so the setpoints are dynamically changed to enable this.
9 = Service Ratio Standby
When a service ratio duty is being used, on all other pumps in use, the standby pump can be started on a ratio basis only, when it will assume the setpoints of the next pump to start. The third setpoint (P215, 225, 235, 245, 255, 265, 275, 285, 295, 575) is used to set the service ratio.
10 = Two Pump Sets
There are four pumps. Two rotate their start-up sequence with each other. If the two pumps cannot keep up, the level rise to the setpoints of the other two pumps which take over and rotate their sequence with each other.
Page 85
PULSAR MEASUREMENT
85
The third parameter for each relay determines the pump group. You can have two groups of pumps, and all similar duties within that group will operate together.

P212, 222, 232, 242, 252, 262, 272, 282, 292, 572 – Relay Pump Group

By default, all pump groups are set to 1, but if you want to have another group, then set this parameter to 2, for each pump relay that should operate together as part of a second group.
The fourth parameter and the fifth parameter for each relay set the pump ON” and “OFF” points, which are entered in Measurement units P104. For
pump down the “ON” is set higher than OFF”. For pump up then “ON” is
set lower than OFF”. See the appropriate pump duty, function table (P212, 222, 232, 242, 252) for further information.

P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 – Relay Setpoint 1

This parameter determines the ‘ON’ point of the pump.

P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 – Relay Setpoint 2

This parameter determines the ‘OFF’ point of the pump.
The sixth parameter will determine the service ratio that will be used to switch the pump, when pump duty selected is a Service Ratio duty.

P215, 225, 235, 245, 255, 265, 275, 285, 295, 575 – Relay Setpoint 3

This parameter determines the Service Ratio in values of %. See the appropriate pump duty function, table (P211, 221, 231, 241, 251, 261,
271, 281, 291, 571), for further information.
Important Notice
The pumps are started and stopped at the “ON” and “OFF” setpoints. To pump down (reduce level) then set “ON” higher than “OFF”. To pump up (increase level) then set “ON” lower than “OFF”.
Page 86
QUANTUM2 INSTRUCTION MANUAL
86

P219, 229, 239, 249, 259, 269, 279, 289, 299, 579 – Relay Max Rate

This parameter will allow a pump to be switched at a pre-determined Rate of change of Level, irrespective of the “ON” level setpoint P213, 223, 233, 243, 253. Once a pump relay has been switched “ON” by the pre-determined Rate of Change, it will remain energised until the level reaches the “OFF
level setpoint P214, 224, 234, 244, 254, 264, 274, 284, 294, 574. Max. Rate is entered in Measurement Units (P104) per minute and can be
entered as either positive (increasing level) or negative (decreasing level) values.

Control

When P210, 220, 230, 240, 250, 260, 270, 280, 290, 570 = 3 (Control)
When a relay is being set up as a control relay, the second parameter that will be displayed in the menu determines its function.

P211, P221, P231, P241, P251, P261, P271, P281, P291, P571 - Relay Function

This function allows the relay to be assigned to specific control functions (other than pumps and alarms) several of these functions work in relation to time.
This can be used to activate devices based on elapsed time or running cycles, such as a timed rake control to keep a ram lubricated if idle for long periods, or flush valve operation.
OPTIONS
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Time
Relay will energise ON” after the Cycle time that is set in Relay Setpoint 2 (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). And turns “OFF”, de-energises, after the On Time Period that is set in Relay Setpoint 1 (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573)
2 = Storm
Relay will energise ON” when storm conditions are in effect and, de-energise OFF” when storm conditions
cease. Two setpoints are required, Upper Storm “ON”,
(P213, 223, 233, 243, 253, 263, 273, 283, 293, 573) and Lower Storm, “OFF” (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). This allows the relay to be used to activate a device as a result of high levels such as a storm condition e.g. opening a gate valve to divert storm overflow into a holding vessel.
Page 87
PULSAR MEASUREMENT
87
OPTIONS
DESCRIPTION
3 = Aeration
Relay will energise ON” after each Cycle time as set in Relay Setpoint 2 (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). And turns “OFF”, de-energises, after the set On Time Period as set in Relay Setpoint 1 (P213, 223, 233, 243,253, 263, 273, 283, 293, 573). This can be used to activate a device based upon elapsed time since All Pumps have been “OFF”, such as the introduction of fresh air to reduce gas concentration.
4 = Flush Valve
Relay will energise ON” when Flush condition is in effect and goes off when Flush condition is cleared. A relay being used for Flush Valve/Pump must be assigned to one of the main pumps in use. Flush relay Alarm ID (P212, 222, 232, 242, 252, 262, 272, 282, 292, 572) is used to enter the relay number, to which the assigned pump is connected. Flush Valve/Pump relay requires three setpoints. The first set point (P213, 223, 233, 243, 253, 263, 273, 283, 293,
573) determines the Flush Interval, which is the number of main pump cycles that should occur before the Flush Valve/Pump operates. The second setpoint (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574), sets the number of Flush cycles the Flush Valve/Pump will operate for. This means that the Flush Valve will be operated for a number of main pump starts (Flush Cycles) after which the Flush Valve activity will cease until the Flush Interval comes around again. Setpoint three of the Flush Valve/Pump relay sets the Flush Duration, (P215, 225, 235, 245, 255, 265, 275, 285, 295, 575) this is the duration for Flush Cycle, in seconds.
Page 88
QUANTUM2 INSTRUCTION MANUAL
88
OPTIONS
DESCRIPTION
5 = Step Time
Step Time Control allows relays to be used to control a device, such as a motorised valve or gate, in order to maintain the level within two predetermined points. Relays will energise ON” when Step Time condition is in effect and de-energises OFF” when Step Time goes off. One relay will be required to control an increase in level,
(‘open’ the device) and a second relay is required to control a decrease in level, (‘close’ the device). Alarm ID
(P212, 222, 232, 242, 252, 262, 272, 282, 292, 572) is used to assign the relay to control either the open or close condition. Step Time Control relay requires three setpoints. The first set point (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573) determines the level, at which the relay is to be activated, (N.B. level setpoint for open relay, increase the level, must be lower than the setpoint for the close relay, decrease the level). The relay will energise ON” after the Limit time that is set in Relay Setpoint 3 (P215, 225, 235, 245, 255, 265, 275, 285, 295, 575). And turns “OFF”, de-energises, after the Drive Period that is set in Relay Setpoint 2 (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574).
6 = Differential Control
Relay will energise ON” when a differential condition is in effect and, de-energise OFF” when the differential conditions cease. Two setpoints are required, Differential control “ON”, (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573) and Differential control, “OFF (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). This allows the relay to be used to activate a device as a result of a differential level, between two points e.g. operate a rake on a screen.
7 = Pump Reset
Relay will energise “ON” for the period of the Reset Pulse (P309) after expiry of the Reset Interval (P308), provided the level is above the Prime Level (P349), to reset the designated pump that has tripped. Alarm ID (P212, 222, 232, 242, 252, 262, 272, 282, 292, 572) is used to enter the relay number, to which the designated pump is connected.
Page 89
PULSAR MEASUREMENT
89
The third parameter for each relay determines the assignment or condition of the relay, where required.

P212, 222, 232, 242, 252, 262, 272, 282, 292, 572 – Relay Alarm ID/Pump Group

P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 1, 2, 3 or 6
This parameter has no function and will not be displayed.
P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 4 (Flush Valve)
If the relay is selected for Flush Valve/Pump, then this parameter is used to determine to which pump the Flush function is assigned. Enter the relay
number to which the assigned pump is connected.
P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 5 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign the relay to the 0 = Open condition (increase level) or 1 = Close condition (decrease level).
P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 7 (Reset)
If the relay is selected for Reset, then this parameter is used to determine to which pump the Reset function is assigned. Enter the relay number to which the assigned pump is connected.
The fourth parameter, fifth parameter and sixth parameter are set to
determine the switch points, “ON” and “OFF” for the relay and where
required the order of start. See control function, table (P211, 221, 231, 241, 251, 261, 271, 281, 291, 571) for further information.
P213, P223, P233, P243, P253, P263, P273, P283, P293, P573

Relay Setpoint 1

P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 =1 (Time)
This parameter determines the “Time Period ” that the relay will remain “ON”. Relay Setpoints are entered in Minutes.
See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261, 271, 281, 291, 571) for further information.
Page 90
QUANTUM2 INSTRUCTION MANUAL
90
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 = 2 (Storm)
Relay Setpoint 1 is entered in values of Measurement Units (P104). See the appropriate relay function tables (P211, 221, 231, 241, 251, 261, 271, 281,
291, 571) for further information.
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 = 3 (Aeration)
Relay Setpoint 1 is entered in Minutes to set Cycle Time. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261, 271, 281,
291, 571) for further information.
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 = 4 (Flush Valve).
Relay Setpoint 1 is entered in Pump cycles to set Flush Interval. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261, 271, 281,
291, 571) for further information.
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 =5 (Step Time)
Relay Setpoint 1 is entered in values of Measurement Units (P104). See the appropriate relay function tables (P211, 221, 231, 241, 251, 261, 271, 281,
291, 571) for further information.
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 =6 (Differential)
Relay Setpoint 1 is entered in values of Measurement Units (P104). See the appropriate relay function tables (P211, 221, 231, 241, 251, 261, 271, 281,
291, 571) for further information.
P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 = 7 (Reset)
This parameter has no function and will not be displayed.

Relay Setpoint 2

P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 = 1 (Time)
This parameter determines the “Cycle Time ” for the operation of the relay. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261,
271, 281, 291, 571) for further information.
P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 = 2 (Storm)
Relay Setpoints are entered in values of Measurement Units (P104). See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261, 271, 281,
291, 571) for further information. P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 = 3 (Aeration)
Page 91
PULSAR MEASUREMENT
91
Relay Setpoints are entered in Minutes to set Time Period that the relay will remain ON. See the appropriate relay Function tables (P211, 221, 231, 241,
251, 261, 271, 281, 291, 571) for further information.
P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 = 4 (Flush Valve)
Relay Setpoints are entered in cycles to set the number of Flush cycles. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261,
271, 281, 291, 571) for further information.
P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 = 5 (Step Time)
Relay Setpoints are entered in Seconds to set Drive Period, the time that the relay will remain ON. See the appropriate relay Function tables (P211, 221,
231, 241, 251, 261, 271, 281, 291, 571) for further information.
P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 =6 (Differential)
Relay Setpoints are entered in values of Measurement Units (P104). See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261, 271, 281,
291, 571) for further information.
P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 = 7 (Reset)
This parameter has no function and will not be displayed.
P215, P225, P235, P245, P255, P265, P275, P285, P295, P575

Relay Setpoint 3

P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 = 1, 2, 3, 6 or 7
This parameter has no function and will not be displayed.
P215, 225, 235, 245, 255, 265, 275, 285, 295, 575 = 4 (Flush Valve)
Enter desired Flush duration in seconds. See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261, 271, 281, 291, 571) for further information.
P215, 225, 235, 245, 255, 265, 275, 285, 295, 575 = 5 (Step Time)
This parameter is used to determine the Limit Time between each Drive Period. Relay Setpoints are entered in Minutes, during which time the relay will remain OFF.
See the appropriate relay Function tables (P211, 221, 231, 241, 251, 261, 271, 281, 291, 571) for further information.
Page 92
QUANTUM2 INSTRUCTION MANUAL
92

Miscellaneous

P210, 220, 230, 240, 250, 260, 270, 280, 290, 570 = 4 (Miscellaneous)
When a relay is set to be a miscellaneous relay, the second parameter determines its function.

P211, 221, 231, 241, 251, 261, 271, 281, 291, 571 – Relay Function

This function allows the relay to work in relation to a clock or a specific event and will be set to activate in relation to Real Time.
OPTIONS
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Clock
Relay will energise ON at a specified time each day as set in Relay Setpoint 1 (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573). And turns OFF, de-energises, after the specified On Time period as set in Relay Setpoint 2 (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574)
2 = Totaliser
Relay will energise ON momentarily each time the specified flow has passed as set in Relay setpoint 1 (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573), this parameter sets the multiplication factor which will be applied to the on board totaliser (P820) to determine the switch point of the relay. E.g. if the totaliser is set to totalise in cubic metres and the relay is required to provide a closure every 10,000 litres Relay setpoint 1 would be set to 10. Relay setpoint 2 (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574) can be used to select the time the relay will remain closed in seconds.
Important Notice
When using a Relay to control a device at a specified time of day ensure that the Time P932 is set correctly. And if required, enable Daylight Saving for the appropriate time difference P970 – P979.
Page 93
PULSAR MEASUREMENT
93
The third parameter has no function when miscellaneous relay is chosen and will not be displayed.
The fourth parameter, and fifth parameter, are set to determine the switch points, “ON” and “OFF” for the relay. See miscellaneous function table (P211, 221, 231, 241, 251, 261, 271, 281, 291, 571) for further information.
P210, 220, 230, 240, 250 = 1 (Clock)

P213, 223, 233, 243, 253,263, 273, 283, 293, 573 – Relay Setpoint 1

Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at which relay will energise. Default = 00:00 (HH:MM)

P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 – Relay Setpoint 2

Relay Setpoints are entered in seconds to set the time period that the relay
will remain ‘ON’. Default = 0.00 mins.
P210, 220, 230, 240, 250, 260, 270, 280, 290, 570 = 2 (Totaliser)

P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 – Relay Setpoint 1

Relay Setpoints are entered as a factor by which the on board totaliser (P820) should be multiplied by to provide a relay closure. Default = 0.00

P214, 224, 234, 244, 254, 264, 274, 284, 294, 574 – Relay Setpoint 2

Relay Setpoints are entered in seconds to set the time period that the relay will remain ‘ON’. Default = 0.00 secs.
Page 94
QUANTUM2 INSTRUCTION MANUAL
94

Pump by Time

When a relay is assigned to Pump by Time the pump will come on (energise) at its normal “ON” level setpoint, and de-energise at its OFF level setpoint or after a predetermined time period, whichever occurs first.
P210, 220, 230, 240, 250, 260, 270, 280, 290, 570 = 5 (Pump by Time) When a relay is being used for a pump by time function, the second
parameter determines the pump duty that will be used to determine the
operating cycle.

P211, P221, P231, P241, P251, P261, P271, P281, P291, P571 - Relay Function

This parameter defines which pump duty the relay should respond to as follows.
PUMP DUTY
DESCRIPTION
0 = Off (Default)
Relay is always de-energised
1 = Fixed duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints. (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294,
574).
2 = Fixed duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints. (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294, 574).
3 = Alternate duty assist
All pumps are used to assist each other (run at the same time) and each pump has its own setpoints, (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294,
574). but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
Page 95
PULSAR MEASUREMENT
95
PUMP DUTY
DESCRIPTION
4 = Alternate duty backup
If a pump fails to meet the demand (due to malfunction, intake blockage etc.), then it is stopped, and another pump shall take over. Each pump has its own setpoints, (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294, 574). but each time all pumps have stopped, then the setpoints are sequentially rotated between the pumps to ensure equal pump use.
5 = Duty backup and assist
First pump comes on, if it cannot cope, it goes off and next pump comes on (duty backup). This continues until the last pump comes on and if it cannot cope the first pump comes back on to assist the last pump (duty assist) if the level continues to rise all other pumps will come on (assist) in turn until the level decreases to the pump off points. Each pump has its own setpoints, (P213, 223, 233, 243, 253, 263, 273, 283, 293, 573 & P214, 224, 234, 244, 254, 264, 274, 284, 294,
574).
The third parameter for each relay determines the pump group. You can have two groups of pumps, and all similar duties within that group will operate together.
Important Notice
The pumps are started and stopped at the “ON” and “OFF” setpoints. To pump down (reduce level) then set “ON” higher than “OFF”. To pump up (increase level) then set “ON” lower than “OFF”.
Page 96
QUANTUM2 INSTRUCTION MANUAL
96
P212, P222, P232, P242, P252, P262, P272, P282, P292, P572

Relay Pump Group

By default, all pump groups are set to 1, but if you want to have another group, then set this parameter to 2, for each pump relay that should operate together as part of a second group.
The fourth parameter, and the fifth parameter for each relay set the
pump ON” and “OFF” points, which are entered in Measurement units P104. For pump down the “ON” is set higher than OFF”. For pump up then “ON” is set lower than OFF”. See the appropriate pump duty, function table (P212, 222, 232, 242, 252, 262) for further information.
P213, P223, P233, P243, P253, P263, P273, P283, P293, P573

Relay Setpoint 1

This parameter determines the “ON” point of the pump.
P214, P224, P234, P244, P254, P264, P274, P284, P294, P574

Relay Setpoint 2

This parameter determines the “OFF” point for the pump. When a relay is being used for a pump by time function, then the sixth
parameter will determine the maximum time the pump will be allowed to run before it is switched off and the next pump takes over.
P215, P225, P235, P245, P255 P265, P275, P285, P295, P575

Relay Setpoint 3

This parameter determines the Maximum Time the pump will be allowed to run before being switched “OFF” and is entered in minutes.
The pump will switch off either at its “OFF” level Relay Setpoint 2 (P214, 224, 234, 244, 254, 264, 274, 284, 294, 574) or its Maximum Run Time Relay Setpoint 3 (P215, 225, 235, 245, 255, 265, 275, 285, 295, 575),
whichever occurs first.
Page 97
PULSAR MEASUREMENT
97

Common Relay parameters

P216, 226, 236, 246, 256, 266, 276, 286, 296, 576 – Relay Allocation

This parameter determines which input the relay will act on. You can set it to the transducer (default), or the optional auxiliary (current) input, or an average of the two. In most cases, this will not need to be changed from the default.
OPTION
DESCRIPTION
1 = Xducer 1 (Default)
Relay acts on Xducer 1 calculated values
2 = Xducer 2
Relay acts on Xducer 2 calculated values
4 = Average of 1 & 2
Relay acts on the resulting average levels of two signal inputs.
5 = Differential of 1 & 2
Relay acts on the resulting differential level of two signal inputs.

P217, 227, 237, 247, 257, 267, 287, 297, 577 – Relay Closures

The Quantum2 will record how many times each relay is closed, this parameter displays the number of times the relay has activated since the relay has been in use. It can be reset with any value.

P218, 228, 238, 248, 258, 268, 278, 578 – Relay Fail Safe

The Quantum2 has a general fail-safe parameter P808. However, this can be overridden so that each individual relay has its own independent fail-safe mode.
This parameter determines what the relay will do in the event of the Failsafe
Time (P809) expiring.
OPTION
DESCRIPTION
0 = Default
Relay assumes system default mode set in P808
1 = Hold
Relay remains in its current state
2 = De-energise
Relay will De-energise
3 = Energise
Relay will energise
Page 98
QUANTUM2 INSTRUCTION MANUAL
98

Pump Trips

When using digital inputs to monitor pump running status and assign relays
to “Pump Reset” this function allows for a pre-programmed number of pump “fails” (P307 Trip limit) to be automatically reset before putting a
pump out of service.
A pump “fail” is defined as the change of state of the trip signal from normal condition to failed. At the point of failure both the consecutive trip counter and the 24-hour rolling counter will be advanced by an increment of 1. After
any such pump “fail” is observed the unit will initiate a “cooling” down
period (P308 Reset Interval) before initiating an automatic reset (Reset Pulse P309), provided the level in the sump is above the specified minimum level (Prime Level P349).
At this point, the pump has been reset and will operate as normal the next
time its ‘ON’ setpoint is reached. If the pump then successfully pumps to its ‘OFF’ setpoint, thereby completing a successful pump cycle, then the
consecutive trip counter will be reset and the 24-hour rolling counter preserved. When any Pump Trip counter exceeds the number of trips allowed (P307 Trip Limit) in any rolling 24-hour period, starting with the first increment of the Trip counter or the pump fails consecutively, exceeding the number of consecutive trips (Maximum Attempts P300) without completing a successful pump cycle, that pump will be put out of service and will not be rest until such time that the fail condition is removed.

P307 Trip Limit

This parameter sets the maximum number of pump “fails” allowed in any 24­hour rolling period.

P308 Reset Interval

This parameter sets the “cooling” off period prior to a Reset Pulse being
initiated.

P309 Reset Pulse

This parameter determines the duration of the Reset Pulse.

P310 Pump 1 Trip

This parameter is a “Read Only” parameter and displays the number of times that Pump 1 has “tripped” since the last successful Reset was performed.
Page 99
PULSAR MEASUREMENT
99

P311 Pump 2 Trip to P319 Pump Trip 10

These parameters are “Read Only” and display the same information as P310 Pump Trip 1 for Pump Trip 2 to 10.

Pump “Advanced” Parameters

The following parameters are used to set the “Advanced” Pump features.

Pump Run On

This feature is used to periodically allow the pumps to continue operating
below their normal “OFF” point, in order to discharge any sediment that may
have settled at the bottom of the vessel.

P349 Prime Level

Sets the required level to ensure pumps are fully primed after a pump run on has occurred. Following a pump run on, any pump, whose “ON” point is
below the Prime Level will be held “OFF” until the Prime Level has been
exceeded.

P350 Run Interval

Set required time period, in hours, at which pump run on should occur.

P351 Run Duration

This parameter sets the length of time, in seconds, that pumps will run on for, it should be noted that only one run on is allowed per Run Interval.

Starting

This feature is used to reduce the effects of power surges, caused by switching of pumps, in the following instances, (P352) Power surge (mains or hydraulic) that is generated when multiple pumps are started simultaneously, (P353) Power resumption following a power failure.

P352 Start Delay

Set the required time period, in seconds, that should elapse between pumps starting. Default = 10 seconds.

P353 Power Delay

Set the required time period, in seconds, that should elapse before pumps can start following a power failure. Default = 10 seconds.
Page 100
QUANTUM2 INSTRUCTION MANUAL
100

Stopping

If required, this feature will prevent pumps, with a common “OFF” point being switched off all at the same time pumps will be switched “OFF” in turn as determined by the delay set in P348 Stop Delay.

P348 Stop Delay

Set the required time period, in seconds, that should elapse between pumps stopping. Default = 0.0 seconds.

Pump Exercising

This feature is used to reduce idle pump corrosion and sediment build up. Pumps can run after a specified Idle Time (P355) for a determined period of Exercise time (P356), providing a Minimum head /level (P357) is present and all other pumps are switched off.

P354 Exercise Enable

This parameter determines if Pump Exercising is enabled or disabled.
OPTION
DESCRIPTION
0 = No (Default)
Pump exercising disabled
1 = Yes
Pump exercising is enabled

P355 Idle Time

Sets the Idle Time (in minutes) to elapse before Pump Exercising is to be activated. Default = 720 minutes

P356 Exercise Time

Set the required Exercise Time in seconds. Default = 30 seconds

P357 Minimum Head

To prevent the dry running and the possibility of cavitation, of the pump, enter the minimum level (head) of material, in measurement units (P104), that is to be present before permitting pump exercising to take place.
Loading...