Pulsar Measurement Pulsar Ultra 4 Product Manual

Ultra 4
Instruction Manual
2
3
ULTRA 4 (SECOND EDITION REV 3)
August 2021 Part Number M-174-1-002-3P
COPYRIGHT
© Pulsar Measurement, 2020 -21. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form without the written permission of Pulsar Measurement.
WARRANTY AND LIABILITY
Pulsar Measurement guarantee for a period of 2 years from the date of delivery that it will either exchange or repair any part of this product returned to Pulsar Measurement if it is found to be defective in material or workmanship, subject to the defect not being due to unfair wear and tear, misuse, modification or alteration, accident, misapplication, or negligence.
DISCLAIMER
Pulsar Measurement neither gives nor implies any process guarantee for this product and shall have no liability in respect of any loss, injury or damage whatsoever arising out of the application or use of any product or circuit described herein.
Every effort has been made to ensure accuracy of this documentation, but Pulsar Measurement cannot be held liable for any errors.
Pulsar Measurement operates a policy of constant development and improvement and reserves the right to amend technical details, as necessary.
The Ultra 4 shown on the cover of this manual is used for illustrative purposes only and may not be representative of the actual Ultra 4 supplied.
CONTACT
For technical support, please contact: Europe: supporteurope@pulsarmeasurement.com
Outside Europe: supportnorthamerica@pulsarmeasurement.com If you have any comments or suggestions about this product, please contact: Europe: europe@pulsarmeasurement.com
Outside Europe: northamerica@pulsarmeasurement.com Pulsar Measurement website: www.pulsarmeasurement.com
United States
11451 Belcher Road South Largo, FL 33773 888-473-9546
Canada
16456 Sixsmith Drive Long Sault, Ont. K0C 1P0 855-300-9151
United Kingdom
Cardinal Building, Enigma Commercial Centre
Sandy’s Road, Malvern
WR14 1JJ 00 44 (0)1684 891371
4
CONTENTS
Chapter 1: Start Here… ........................................................................................................... 9
About this Manual ............................................................................................................... 9
About the Ultra 4............................................................................................................... 10
Functional Description .................................................................................................... 11
How to use this Manual .................................................................................................. 12
Product Specification ....................................................................................................... 13
EU Certificate of Conformity ......................................................................................... 15
Chapter 2 Ultra 4 Installation ............................................................................................ 16
Unpacking ............................................................................................................................ 16
Power Supply Requirements......................................................................................... 16
Location ................................................................................................................................ 16
Typical system wiring....................................................................................................... 18
Dimensions .......................................................................................................................... 19
Wall Mount .......................................................................................................................... 19
Fascia Mount ....................................................................................................................... 21
Terminal connection details .......................................................................................... 23
Interface Connections ..................................................................................................... 24
Terminal Connections ...................................................................................................... 24
Fuse Location ...................................................................................................................... 26
Preparation for Operation ............................................................................................. 27
Maintenance ....................................................................................................................... 27
Chapter 3 How To Use Your Ultra 4 ............................................................................... 28
Operating the Controls ................................................................................................... 28
Run Mode ............................................................................................................................. 29
How to Access Program Mode .................................................................................... 38
Menu Keys ........................................................................................................................... 39
Hot Keys ................................................................................................................................ 40
Numeric Keys ...................................................................................................................... 40
Using the Menu System ................................................................................................. 41
Directly Editing Parameters ........................................................................................... 42
Test Mode ............................................................................................................................ 43
5
Using the Serial Interface ............................................................................................... 44
Parameter Defaults ........................................................................................................... 46
Chapter 4 Ultra Wizard ........................................................................................................ 47
Enter Program Mode ....................................................................................................... 47
Choose Ultra Wizard ........................................................................................................ 47
Ultra 4 - Level / Volume ................................................................................................. 48
Ultra 4 - Pump control .................................................................................................... 48
Ultra 4 - Flow ...................................................................................................................... 49
Chapter 5 Level / Volume ................................................................................................... 51
Quick Setup ......................................................................................................................... 53
Example 1 Level Monitoring with Alarms ................................................................ 57
Example 2 Level Monitoring and Control (up or down) .................................... 59
Example 3 Volume Application .................................................................................... 61
Chapter 6 Pump ..................................................................................................................... 64
Quick Setup Menu ............................................................................................................ 66
Example 4 Level Monitoring with Alarms ................................................................ 69
Example 5 Sump Control (pump down) ................................................................... 71
Example 6 Reservoir Control (pump up) .................................................................. 73
Chapter 7 Flow ........................................................................................................................ 75
Exponential Devices ......................................................................................................... 82
Calculations ......................................................................................................................... 85
BS3680 Flumes (P700 = 2) ............................................................................................. 89
Rectangular Flume Calculations .................................................................................. 90
U-Throated Flume Calculations ................................................................................... 91
Example 2 BS3680 U-Throated Flume ...................................................................... 92
BS3680 Weirs (P700 = 3) ................................................................................................ 94
Rectangular Weir Calculations ..................................................................................... 94
V-Notch Weir Calculations ............................................................................................ 95
BS3680 Rectangular Broad Crested Weir ................................................................ 98
Rectangular Broad Crested Weir Calculations ....................................................... 99
ULTRA 4 INSTRUCTION MANUAL
6
Special Devices ................................................................................................................. 100
Palmer Bowlus and H-Flume Calculations ............................................................ 101
V-Notch Angle Weir (Non-BS 3680) Calculations .............................................. 102
Universal Calculations (P700=6) ................................................................................ 102
Chapter 8 Parameter Guide ............................................................................................. 103
Menu System .................................................................................................................... 103
Top Level Menu ............................................................................................................... 103
Application Menu ............................................................................................................ 104
Relays Menu ...................................................................................................................... 105
Data Logs Menu .............................................................................................................. 106
Volume: Available when Ultra Wizard = Volume .............................................. 107
OCM: Available when Ultra Wizard = Flow ......................................................... 108
Display Menu .................................................................................................................... 109
mA Output Menu ............................................................................................................ 110
Compensation Menu ..................................................................................................... 110
Stability Menu .................................................................................................................. 111
Echo Processing Menu .................................................................................................. 112
System Menu .................................................................................................................... 113
Device Comm Menu ...................................................................................................... 114
Test Menu .......................................................................................................................... 115
Application Parameters................................................................................................. 116
Operation ........................................................................................................................... 116
Dimensions ........................................................................................................................ 117
Relay Parameters ............................................................................................................. 120
Alarms .................................................................................................................................. 121
General Control ................................................................................................................ 125
Pumps .................................................................................................................................. 126
Control ................................................................................................................................. 129
Miscellaneous ................................................................................................................... 131
Common Parameters ..................................................................................................... 133
Data Log parameters ..................................................................................................... 133
7
Volume ................................................................................................................................ 138
When Ultra Wizard = 1 Level/Volume .................................................................... 138
Conversion ......................................................................................................................... 138
Breakpoints ........................................................................................................................ 143
Tables ................................................................................................................................... 144
OCM Parameters ............................................................................................................. 145
Dimensions ........................................................................................................................ 149
Calculations ....................................................................................................................... 153
Breakpoints ........................................................................................................................ 154
Tables ................................................................................................................................... 154
Average Flow .................................................................................................................... 154
Display Parameters ......................................................................................................... 155
Options ................................................................................................................................ 155
Failsafe ................................................................................................................................. 156
Auxiliary ............................................................................................................................... 157
Totaliser ............................................................................................................................... 158
mA Output Parameters ................................................................................................. 160
Range ................................................................................................................................... 160
Operation ........................................................................................................................... 161
Setpoint ............................................................................................................................... 161
mA Limits ............................................................................................................................ 162
mA Trim .............................................................................................................................. 163
mA Failsafe ......................................................................................................................... 165
Compensation Parameters .......................................................................................... 165
Offset.................................................................................................................................... 165
Temperature ...................................................................................................................... 165
Velocity ................................................................................................................................ 166
Stability Parameters ....................................................................................................... 167
Damping ............................................................................................................................. 167
Rate ....................................................................................................................................... 167
ULTRA 4 INSTRUCTION MANUAL
8
Filters .................................................................................................................................... 168
Echo Processing Parameters ....................................................................................... 169
Transducer Status ............................................................................................................ 169
System Parameters ......................................................................................................... 170
Passcode ............................................................................................................................. 170
Backup ................................................................................................................................. 170
Params SD .................................................................................................................... 171
System Information ........................................................................................................ 171
Date & Time ...................................................................................................................... 172
Watchdog ........................................................................................................................... 172
Daylight Saving Time ..................................................................................................... 173
Service Alarm .................................................................................................................... 176
Language ............................................................................................................................ 177
Device Comm. .................................................................................................................. 178
RS232 Set Up .................................................................................................................... 178
Modbus ............................................................................................................................... 178
Profibus ............................................................................................................................... 180
HART .................................................................................................................................... 181
Test Parameters ............................................................................................................... 183
Simulation .......................................................................................................................... 183
Hardware ............................................................................................................................ 184
Chapter 9 SD Card Logger ............................................................................................... 186
About the Micro SD card logger ............................................................................... 186
Types of Files .................................................................................................................... 186
Setting up the unit to log ............................................................................................ 187
Chapter 10 Troubleshooting ........................................................................................... 188
Chapter 11 Disposal ............................................................................................................ 189
9

CHAPTER 1: START HERE…

Congratulations on your purchase of a Pulsar Ultra 4. This quality system has been developed over many years and represents the latest in high technology level measurement and control.
It has been designed to give you years of trouble-free performance, and a few minutes spent reading this operating manual will ensure that your installation is as simple as possible.

About this Manual

It is important that this manual is referred to for correct installation and operation. There are various parts of the manual that offer additional help
or information as shown.
Tips
TIP : L ook f o r this i c o n throu gh o u t your P u lsar Me a surement manua l to fin d helpful i nformat i o n and a n s wers t o f requen t l y asked q uestion s .
Additional Information
Additional Information
At various parts of the manual, you will find sections like this that explain specific things in more detail.
ULTRA 4 INSTRUCTION MANUAL
10

About the Ultra 4

Ultra 4 is a brand-new concept in ultrasonic level measurement. Within its memory are all the functions and settings of three different and separate ultrasonic devices.
The Ultra 4 does not offer a multiple range of functions blended together which leads to complicated calibration and a compromise to the specification. The Ultra 4 is the first ever system to offer the ability to dedicate the functionality of the unit to any of three specific duties i.e., level or volume measurement, pump control, or flow measurement. Diagnostic trace information and measurement trending can be viewed directly on the display of the unit itself and automatically logged to SD card. The benefits are many but most importantly the unit provides:
1. A most versatile system which can be configured quickly, to offer
one of three separate functions within a matter of seconds. Ideal for simplicity of purchase and off the shelf spares.
2. Ability to log vast amounts of data using the integral Micro SD
card slot, and at a minimum of 1-minute intervals.
3. A totally dedicated device with the ability to perform all aspects of
the task required i.e., no compromise in specification.
4. Easy to set up using Pulsars unique “Quick Set Up” Menu. To
calibrate the unit, first set the Ultra Wizard for the desired task, then refer to the relevant chapter in this manual that relates to your application:
Chapter 5 for Level or Volume, Chapter 6 for Pump Control Chapter 7 for Flow
11

Functional Description

Ultra 4 sends a transmit pulse to the transducer, which emits an ultrasonic pulse or radar signal (dependent on transducer) perpendicular to the transducer face, and the returned echo is sent back to the Ultra 4. The time taken to receive the echo is measured and the distance from the transducer face to the surface being monitored is calculated.
Ultra 4 can measure from zero to 40m from the face of the transducer to the surface being monitored, dependent on the application chosen and transducer used.
The relays can be programmed to activate alarms, pump starters, or other control equipment. There is an isolated 4-20 mA output that can be connected to a recorder or PLC, to monitor, depending on application chosen, level, space, distance, OCM head, OCM flow or volume, independently from that shown on the display. There is an RS232 port, so that the Ultra 4 can be operated remotely by a PC or other equipment.
Ultra 4 can be programmed either by the built-in keypad (standard on all wall and fascia units), via the SD card slot or by PC via the RJ11 Serial Interface. All parameters are stored in a non-volatile memory, so are retained in the event of power interruption. A second backup copy of all parameters can also be retained in the Ultra 4 memory, in case an alternative set of parameters needs to be stored.
Four user definable relays with individual setpoints and intelligent performance logging software features ensure maximum control versatility.
The system utilises the unique DATEM software (Digital Adaptive Tracking of Echo Movement). This is a proven digital mapping technique developed especially for the Pulsar Ultra range, which gives the system unequalled
ability when identifying the “true target level” in the face of competing
echoes from pipes, pumps, or other obstructions. Coupled with the powerful, long-range abilities of the ‘all new’ dB transducer range, the Ultra 4 lives up to its reputation as the most reliable ultrasonic level measurement system available.
The Pulsar Ultra 4 ultrasonic level controllers have been designed to provide maintenance-free fit and forget performance.
ULTRA 4 INSTRUCTION MANUAL
12

How to use this Manual

1. Read the installation and operating instructions contained in,
Chapters 2 and 3, carefully, they are applicable in every use of this
product.
2. Decide which “task” you wish your Ultra 4 to perform for you and
then configure the unit using “Ultra Wizard” as described in Chapter 4.
3. Move directly to the appropriate chapter of this manual, as listed
below, for details on how to program Ultra 4 using the “Quick Set Up” Menu.
4. Alternatively, if you are familiar with Pulsar products or you wish to
directly program your unit, please refer to Chapter 8 Parameter
descriptions.
CHAPTER
DUTY / TASK
Chapter 5 Level/Volume
Measurement of Level or Volume
Chapter 6 Pump
Control of Pumps
Chapter 7 Flow
Measurement of Open Channel Flow
13

Product Specification

PHYSICAL
Wall Mount outside Dimensions
150 x 130 x 64mm (5.9 x 5.1 x 2.5”)
Weight
Nominal 700g
Enclosure Material/Description
Polycarbonate flame resistant to UL94-5V
Cable entry detail
3 x M20 cable glands, for cable dia. 5 to 13mm (0.2” to
0.5”)
Fascia Mount outside dimensions
160 x 180 x 64mm (6.3 x 7.1 x 2.5”)
Weight
1.3kg
Enclosure material/description
Polycarbonate flame resistant to UL94-5V
Transducer Cable Extensions
2-core screened (minimum)
Maximum Separation
1000m (3,280 ft), 500m (1,640 ft) for mmWave
ENVIRONMENTAL
IP Rating (Wall)
IP67 / NEMA 4X
IP Rating (Fascia)
IP64
Max. & min. temperature (electronics)
-20°C to +45°C (-4°F to +113°F)
Flammable atmosphere approval
Safe area: compatible with approved transducers and sensors. (see spec. sheets)
CE Approval
See EU Declaration of Conformity
UL Approval
UL61010-1
PERFORMANCE
Accuracy
0.25% of the measured range or 6 mm (whichever is greater). ± 2mm for mmWAVE RADAR
Resolution
0.1% of the measured range or 2 mm (whichever is greater)
Max. Range
Dependant on transducer (maximum 40m dB40)
Min. Range
Dependent upon application and transducer (minimum zero dB Mach3)
Rate Response
Fully adjustable
ECHO PROCESSING
Description
DATEM (Digital Adaptive Tracking of Echo Movement)
Technology
Ultrasonic and MCW Radar
ULTRA 4 INSTRUCTION MANUAL
14
OUTPUTS
Analogue I/O
Isolated (floating) output (to 150V) of 4-20 mA or 0-20 mA into 1K (user programmable and adjustable)
Digital output
Full Duplex RS232
Volt free contacts, number, and rating
3 x SPCO isolated relays, rated at 5A at 250V AC and 1 solid state SPNO isolated relay, rated 30V at 100mA (to suit pulse counter applications).
Display
Monochrome graphical dot-matrix, 160 x 240 pixels. Fully programmable display options with integral keypad and menu navigation keys.
PROGRAMMING
On-board programming
By integral keypad
PC programming
Via RJ11 port on unit, or via Micro SD
Programming security
Via passcode (user selectable and adjustable)
Programmed data integrity
Via non-volatile RAM, plus backup
Data logging and removable storage
Via micro-SD card slot and internal 10-day totaliser logs (flow only).
SD card memory (included)
16GB
SUPPLY
Power Supply
115VAC +5% / -10% 50/60 Hz, 230VAC + 5% / -10% 50/60 Hz, dc 18 - 30V 10W maximum power (typically 6W)
Fuse, mains
100mA at 230V AC (fitted as standard to wall units) 200mA at 115V AC (fitted as standard to fascia units)
Fuse, transducer
100mA barrier type, 4000A breaking
COMMUNICATIONS (OPTIONAL
Modbus RTU/ASCII
Isolated RS485
Profibus DPV1
Isolated RS485
HART 7
Isolated 4-20mA
DNP3/WITS
Gateway interface (pending)
Pulsar Measurement operates a policy of constant development and improvement and reserve the right to amend technical details, as necessary.
15

EU Certificate of Conformity

ULTRA 4 INSTRUCTION MANUAL
16

CHAPTER 2 ULTRA 4 INSTALLATION

Unpacking

Power Supply Requirements

Ultra 4 can operate from AC supply or from a DC supply or battery. The rated AC range is between 100V and 240V 50/60Hz. The DC range is 10 – 28V. In both cases the Ultra 4 will typically consume 6W of power, with a maximum of 10W.

Location

When choosing a location to mount the enclosure, please bear in mind the following:
Ensure that the Ultra 4 is installed in a “Safe”, non-hazardous, area.
For a clear view of the display, it is recommended that it is mounted
at eye level.
The mounting surface is vibration-free.
The ambient temperature is between -20ºC and 45ºC (-4
o
F and
113oF).
When installing the fascia, remember the temperature within an
equipment cabinet may be higher than the outside ambient, depending on the heat generated within and ventilation provided.
There should be no high voltage cables or inverters close by.
There should not be any heat-generating components nearby.
Important Information
All shipping cartons should be opened carefully. When using a box cutter, do not plunge the blade deeply into the box, as it could potentially cut or scratch equipment components. Carefully remove equipment from each carton, checking it against the packing list before discarding any packing material. If there is any shortage or obvious shipping damage to the equipment, report it immediately to your local Pulsar distributor.
17
All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation.
When forming part of a system used in a hazardous area, the Ultra 4 must be mounted in a non-hazardous (safe) area, and the transducer / sensor fitted in the hazardous area.
Appropriate safety precautions must be taken (IECEx / ATEX / FM). Exia (I.S.) installations require a safety barrier and protective earth. Exmb installations require protected cable runs and adequate fusing.
Refer to local regulations and standards for specific requirements.
Important Information
All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation.
LEVEL SENSOR
ULTRA 4 INSTRUCTION MANUAL
18

Typical system wiring

19

Dimensions

Wall Mount

The dimensions of the wall fixing holes are as shown below:
Ultra 4 (wall-mount) should be mounted by drilling four holes suitable for size 8 self-tapping screws (length to suit your application).
Where machine screws are required, M3.5 is the best size to use.
ULTRA 4 INSTRUCTION MANUAL
20
The full dimensions of the wall-mount enclosure are shown below:

Cable Entry

Three M20 cable glands are supplied fitted. They accept cables between 5.0
and 13.0mm (0.2” to 0.5”) overall diameter. The gland cable nuts require a
24mm A/F spanner; tighten to a torque of 2Nm.
63.5mm (2.5”)
Fixing screws, thread d.43mm
(0.16”) max
head
d. 7.6mm
(0.300”) max
130mm (5.12”)
13mm (0.51”)
150mm (5.
91”)
3 off M20 glands
21

Fascia Mount

The Fascia mount Ultra 4 should be installed by cutting a rectangular hole and four fixing holes in the panel as detailed below.
Observe minimum clearances to the cabinet and other equipment as shown.
ULTRA 4 INSTRUCTION MANUAL
22
The full dimensions of the fascia enclosure are shown below:
There is a sealing gasket that sits under the flange; check that this is installed and is a flat fit against the panel. The mounting nuts are M3, requiring a
5.5mm A/F socket. They should be tightened to a torque of 0.5Nm.
30mm (1.18”)
33mm (1.30”)
160mm (6.30”)
180mm (
7.07”)
23

Terminal connection details

Wall Mount

The terminal strip is as detailed below:

Fascia Mount

The terminal details are as illustrated below:
ULTRA 4 INSTRUCTION MANUAL
24

Interface Connections

The SD card slot labelled ‘SD’, and the RJ11 socket labelled ‘PC’ are situated
on the LCD display board as detailed below:

Terminal Connections

Power

Ultra 4 can operate from mains AC and automatically from DC or battery backup in the event of a power failure or can be operated permanently from DC or batteries.

Transducer/sensor

The transducer should be installed, and connected, in accordance with the installation instructions contained in the Transducer User Guide.
The entire range of, standard dB transducers and mmWave dBR sensors are certified for use in hazardous areas. See the product label for certification details. Wire the transducer to the Ultra 4’s transducer terminals, as follows:
TERMINAL CONNECTION DETAILS
Black:
0Volts
White: Signal
Red:
Power
Green: Screen
15
16
17
18
When using 2-core screened extension cable, the Black and Green wires of the transducer should be connected to the screen of the extension cable
which in turn should be connected to the appropriate 0 volts’ terminal of the
Ultra 4.
LCD Board
Micro SD Slot
Keypad connector
RJ11 connector
25

Relay Outputs

All four of the relays can be programmed for a variety of alarms, pump control, or other process functions. Three relays have contacts rated at 5A at 240V AC. The fourth is a low power solid state SPNO isolated relay, intended to be suitable for pulse counter functions.
All connections should be fused or protected such that the short circuit capacity of the circuits to which they are connected is limited so that they do not exceed the relay rating.

Current Output

This is an isolated (floating) mA output (to 150 V), of 4 - 20mA or 0 - 20mA, and the load should not exceed 500 .

RS2323 Serial Interface

If required, you can connect to the serial interface to operate your Ultra 4 remotely.

Wire/cable ratings & sizes (Copper conductors)

CONNECTOR
RATING
WIRE SIZE (MIN)
WIRE SIZE (MAX)
Power, AC
120V / 240V 2A min
0.5mm2/20 AWG
2.5mm2 / 12 AWG
Power, DC
30V 2A min.
0.5mm2/20 AWG
Relays 1-3
For max. rated 5A rms use 1mm2 / 18AWG min.
Depends on load.
Relay 4, SSR
30V 0A2 min.
0.2mm2/30 AWG
Transducer
30V 0A2 min. Pulsar cable is 0.5mm2 / 20AWG.
0.2mm2 / 30AWG.
mA out
30V 0A2 min
Depends on distance.
Comms.
150V 0A2 min.
0.2mm2 / 30AWG
Gateway RS232
30V 0A2 min
0.2mm2 / 30AWG
1.5mm2 / 12 AWG
ULTRA 4 INSTRUCTION MANUAL
26

Fuse Location

The mains fuse is located inside the terminal compartment, under the removable protective cover, as shown below:
DON’T FORGET
Before powering up the unit, ensure the protective terminal cover is in place.
E N L
1
2
3
COM
NC
NO
4
5
6
FUSE
20mm
1A T
MAINS FUSE MAINS
Protective
cover
Important Information
Please note that all units are supplied for safety reasons with a 20mm 1AT fuse fitted as standard. Never operate the Ultra 4 with the protective cover removed.
An external switch or circuit breaker should be installed near to the Ultra 4 to allow the supply to be removed during installation and maintenance. In addition, the relay contacts should also have a means of isolating them from the Ultra 4.
Interconnecting cables must be adequately insulated in accordance with local regulations. Strip back 30 mm of the outer insulation of the cable. Strip 5 mm of insulation from the end of each conductor. Twist all exposed strands of the conductor together. Insert the stripped conductor into the terminal block as far as it will go and tighten the terminal block screw. Ensure that all strands are firmly clamped in the terminal block and that there is no excess bare conductor showing, and no stray strands.
Important Information
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
27

Preparation for Operation

Before switching on, check the following:
The Ultra 4 is mounted correctly and is in a ‘safe’ area. The power supply is correctly installed. If powered by AC the protective cover is fitted. The relays are connected correctly. Any controlled equipment, e.g., motors, servos & valves, are not able to
injure people or damage property.

Maintenance

There are no user serviceable parts inside Ultra 4, except the mains fuse. If you experience any problems with the unit, then please contact Pulsar Measurement for advice.
To clean the equipment, wipe with a damp cloth. Do not use any solvents on the enclosure.
Important Information
The unique DATEM software comes into operation as soon as power is applied and is designed to monitor a moving level or target with the transducer in a fixed position.
If, after any period of use, it should become necessary to move the transducer, for any reason, from its original operating position, switch off the Ultra 4, before proceeding, to prevent any undesirable updates to the DATEM trace. If after moving the transducer the reading is not as expected, please refer to Chapter 10 Troubleshooting.
ULTRA 4 INSTRUCTION MANUAL
28

CHAPTER 3 HOW TO USE YOUR ULTRA 4

Operating the Controls

There are two main operating modes for your Ultra 4, Run Mode and Program Mode. There is also a Test Mode, used for checking the set-up.

Display

The graphical display provides different levels of runtime information on the current mode of operation, and status of the remote communication. Whilst in the Run Mode the ‘Main’ screen displays the current reading or measurement and its units of measure, along with status messages with regards to the Transducer, Echo reception and Fail-Safe Mode and relay activity. Additionally, it can be programmed to display up to 5 auxiliary variables and provide status messages on alarms, pumps etc. To scroll between run mode screens (Echo, Settings, Trend, Info and Big), use the left and right arrow keys.
The ‘Echo’ screen shows the live echo trace of the point of measurement set
up, with various viewing options available. For further information of the
options available please refer to the ‘Hot keys’ section later in this chapter. The ‘Settings’ screen shows details of the empty level, span and blanking
distance for the measurement point set up. And if relays have been programmed, a graphical representation of the ON and OFF setpoints of the relay(s) are shown.
The ‘Trend’ screen shows live measurement information depending on what is selected within the ‘Trend Setup’ parameters P260-274. Pressing the up
and down arrow keys allows you to toggle between current and historical trending. Pressing the up and down arrow keys will toggle between the
different trend logs being monitored as set up in ‘Trend Setup’. The ‘Info’ screen is split into multiple pages. These give information such as
the current time and date, details of the unit, if there is a SD card inserted and what it is logging, amongst other information. Pressing the up and down arrows allows you to move between the info pages.
The ‘Big screen allows you to view the current measurement and measurement unit displayed on the Main screen in a larger, clearer font.
29
When in Program mode the display is used to read information using a sophisticated progressive menu system, where parameter numbers can be entered, their details viewed, and values changed to suit the application. During Test Mode, the display is used to monitor the simulated level. A bar graph is also provided which will provide a visual reading of the level, in percentage of span.

Run Mode

This mode is used once the Ultra 4 has been set up in program mode. It is also the default mode that the unit reverts to when it resumes operation after a power failure. When the Ultra 4 is switched on for the first time, it will display, in metres, the distance from the transducer face to the target. All relays by default are switched off.
After programming is complete, any relays that are set will operate when the level reaches the relevant setpoint, and the small square box will become solid. The letter in the box indicates the relay type.
ULTRA 4 INSTRUCTION MANUAL
30

Main Display

This screen provides information on the measurement point set up. Use the left and right arrow keys to scroll between screens
Pressing the up/down arrow keys will allow you to view the default information displays (non-programmable). The display returns to the default
screen after 30 seconds. Pressing the ‘up’ key you can scroll through the
following information:
1. Status, Strength, Confidence & Temperature
2. Distance, Level, Space & Temperature
3. Current mA output.
There is an SD card icon next to the clock; steady icon means the card is available, flashing is safe to eject, and not visible if there is no card present.
52%
Auxiliary display information
Graphical overview of level in application
Current level in percentage of span
Relay status
Clock
Current level in measurement units
Display Modes – current mode is highlighted.
metres
1.16
12:53
Echo Settings Trend Info
Main
Indicates an SD card is inserted.
31

Echo Display

The Echo screen displays the instantaneous echo data captured from the transducer and presents it in the format shown in the illustration below.
Pressing the hotkeys on the keypad can display other trace information:
F1 = Toggles Normalised trace.
F2 = Toggles Loss limit line.
F3 = Toggles Gate.
The text at the top right of the display indicates which of these display modes is on or off. Normal text for off, invers text for on (example shown in the below diagram).
Below is an example of a typical level measurement application:
Status: OK
metres
100
2.5
3.0
2.0
1.5
1.0
0.5
3.5
0.0
40
60
80
20
0
(dB) dB6: 1.16m
Echo
strength in dB
Current measurement
F1-Norm
F3-Gate
F2-Loss
Distance in measurement units
Echo Gate
12:53:1
Main Settings Trend Info
Echo
Empty Distance marker
ULTRA 4 INSTRUCTION MANUAL
32

Settings Display

The Settings screen displays the transducer settings and has a bar-graph showing the measured value or as a percentage of maximum. To the left of the display:
P105 = Empty Level
P106 = Span
P107 = Near Blanking.
Also, on this screen are indicators of any relays currently setup. The level icons represent the level reading of the transducer. Relays that do not relate to the level (Miscellaneous) will be displayed without the graphical representation of setpoints but will however show the relay number and status. Below is an example of information on the Settings screen:
Relay OFF setpoint
Solid region indicates the relay is always ACTIVE
(ON)
Light region indicates the relay is always INACTIVE (OFF)
Relay ON setpoint
A1
on
Current level icon
Region between solid area and line signifies a relay can be ACTIVE if triggered, or INACTIVE if not triggered.
Relay Status
A = Alarm G = General Control C = Control P = Pump M = Misc.
N = Not set.
Numbers represent the relay number.
Current value in measurement units
N4
on
on
on
off
A1
P2
C3
1.16m
Status: OK
12:53:1
Main Echo Settings Trend Info
Settings
P107=0.300m
P106=2.000m
P105=2.300m
Xdr Settings
Relay Settings
33

Trend Display

The Trend screen shows live and historical data for selectable measurements. You can toggle a display of up to 15 selectable measurements used in an application setup, which are then automatically updated every sample taken. The frequency of the trend sample taken varies in the user definable parameter P129 - Sample interval. Pressing the Up and Down buttons selects the different trending measurements (up to 15).
The LCD shows up to 210 points, and once the screen is full it scrolls left as each new sample is added. F1 and F2 symbols will appear on the screen indicating that you can scroll back to view the historical data and return to current measurements.
The files that the data is saved to is in the form of LyymmddA.CSV. L – log file and yymmdd = year, month, and a = letter starting at ‘A’ in case more than one file is created. A new log file will be generated each day for that month.
27/05/19
Date
Value range in measurement units
Trending line
Time interval
Trend identifier F1 = Current F2 = Historical
Current Trending measuring point selected.
13:20:00
13:10:00
13:00:00
12:50:00
Level = 1.16m
1.5
0.6
0.9
1.2
0.3
0
12:53:1
Main Echo Settings Info
Trend
F1
27/05/19
27/05/19
27/05/19
ULTRA 4 INSTRUCTION MANUAL
34
Info Display
The Info screen allows you to view the system details and a summary of the current application system setup.
There are 11 pages in total that can be scrolled through to view different forms of information. Using the up and down arrows you can easily manoeuvre through the different pages. The page number is located at the top right of the display.
Page 1 System Information
This shows the general information about the controller, details of this information are shown in the illustration above.
Page 2 SD Card information
This shows information and status about the SD card (if inserted):
Status of the card:
Scanning: The unit has detected a card is present and is checking it. No Card: The unit has not detected a card is present. Card Full: There is no storage room left on the SD card. Ready: The card is available to have data written on it. Bad card: A problem has been detected and the card is unusable. Ejected: The [.] has been pressed and the SD card has not been ejected. If
the [.] button is pressed accidentally the card becomes available again in 5 minutes.
Card size inserted into the unit.
Free space on the card.
Used space on the card.
File system type of the SD card.
12:53:1
Main Echo Settings Trend
Info
Model Ultra IV System Level/Volume Customer Pulsar Version 1.0 Serial No. 000001 Site ID 000001 Day Thursday
Date 27/05/19
Time 12:53:11
35

Page 3 – Data logging Information

This shows up to date logging information of all measurement information. It also shows the sample interval that is currently set.

Page 4 – Trace logging Information

Trace logging is enabled by default, it can be disabled in program mode, if not required. Echo traces are logged to the SD card, where the file and
format are TyymmddA and TyymmddA.DAT. Where ‘T’ indicates a trace
file/folder, yymmdd are the year, month, and day the file and folder were
created, and ‘A’ is a letter, starting with ‘A’ in case more than one file is
created in a day. A new log file will be generated each day for that month. The .DAT suffix indicates that the files have been saved in such a way that they can be viewed using PC Suite (Ultra PC).
The display shows whether the trace logging is enabled. The normal interval is how often a trace is written/saved to the SD card, the fault interval is how often a trace is written/saved to the SD card when a fault occurs. The rest of the display shows settings for fault conditions, some of which are referenced to user-set limits.

Page 5 – Pump Diagnostics

This page is always visible, but it is only populated when pumps are programmed into the unit. The screen shows the following:
Duty – The pump duty set for each pump e.g., ADB.
SP1, SP2 & SP3 - The three setpoints associated with pumps.
Closures – This is the number of closures for each relay.
Status – Pump status, on or off. Off is shown in normal text where as
On is in inverse text.
Run – Total run times (in hours) since the relay was configured.
Current level.

Page 6 – Event Log

This screen shows the date and time of the occurrence of various events, which are also written/saved to the SD card. The latest 9 events are displayed on the screen.
The event log file and formats are EyymmddA.CSV, where ‘E’ is for event, yymmdd are the year, month, and the day on which the file was created.
And ‘A’ is a letter starting at A in case there is more than one file started on
the same day. A new log file will be generated each day for that month.
ULTRA 4 INSTRUCTION MANUAL
36

Page 7 – RS232 settings and Comms settings

Information regarding the RS232 and comms settings are shown on this screen. The RS232 baud rate, number of bits, parity and number of stop bits for the RJ11 serial port is displayed. If the Ultra 4 has optional comms protocols enabled, the screen will show the device address and any associated bus parameters.

Page 8 – Point Settings

This page shows the settings for the measurement point:
Transducer type.
Mode, e.g., Volume.
Material (liquid, solids, or closed tank).
Empty level.
Span.
Fail Mode.

Page 9 – mA Out Settings

This page shows the information portraying the mA out:
Range – Maximum range of the output.
Mode – Measurement represented by the output.
Low – Measured value indicated by the Low limit.
High – Measured value indicated by the High Limit.
Fail Mode – Output of current during a failed safe mode.
Low Limit – Minimum output current.
High Limit – Maximum output current.

Page 10 – 10-day totaliser log

Displays date and flow totaliser information for the last ten days, the
first on the list is the most recent and the last one is the oldest. When all 10 totaliser logs are full the oldest is pushed out and all totals increment through to allow the new days to be registered.

Page 11 – Echo information

Displays current information relating to H.A.L.L (Height Above Loss
Limit), Average noise, Peak Noise and Echo strength.
37

Big Display

The Big display shows the current measurement and measurement units being displayed on the Main screen, but in a much larger font for ease of reading.
Pressing the F2 button will invert the screen, so that the screen has a black background with large white letters and numbers on the screen.
Note: The Big screen display will only show one auxiliary display option, the screen will alternate from the display above to a display like the one shown below (depending on the aux option chosen will depend on the information shown).
12:53:1
Echo Settings Trend Info
Big
1.16
metres
12:53:1
Echo Settings Trend Info
Big
Tot R:
123456789.10
OK
m
3
Auxiliary display information
Transducer status
ULTRA 4 INSTRUCTION MANUAL
38
Program Mode This mode is used to set up the Ultra 4 or change information already set, by
using the built-in keypad Alternatively, the unit can be set up with a PC via the RS 232 Serial Interface.
Entering a value for each of the parameters that are relevant to your application defines all the programming information.

How to Access Program Mode

To enter program mode, you simply enter the passcode, via the keypad, followed by the ENTER key. The default passcode is 1997, so you would press the following:
ENTER
1
9 9 7
Pass Code * * * *
This will appear on the display of the unit, before pressing Enter.
Important Information
There is a time-out period of 30 minutes when in program mode, after which time run mode will be resumed if you do not press any keys.
39

Menu Keys

The menu keys have the following functions:
HOT KEY
RUN MODE
PROGRAM MODE
Used to scroll between the displays on the main display
1. Displays Status, echo strength, echo
confidence and temperature.
2. Displays Distance, Level, Space,
Temperature and Head (when Ultra Wizard = Flow).
3. Displays echo confidence, H.A.L.L,
average noise, peak noise.
4. Displays instantaneous mA output.
If enabled, Daily, system and resettable totalisers are displayed.
5. Moves through different trending
points setup on the Trend screen.
6. Moves through the different Info
screens on the Info display.
Arrow keys for moving up and down the menu system. Also used in simulation mode to move the level up and down.
Not used with Ultra 4.
Used to confirm each action (for example select a menu option) or when entering a parameter number or value. Also used to confirm questions asked by your Ultra 4 such as before restoring factory defaults.
Not used with Ultra 4.
Used to navigate up a level in the menu system, and back to run mode. Used to cancel a value entered in error.
ENTER
CANCEL
ULTRA 4 INSTRUCTION MANUAL
40

Hot Keys

The hot keys have the following functions:
HOT KEY
RUN MODE
PROGRAM MODE
Used to reset to the resettable totaliser on main screen. Used to display Normalised trace on the Echo screen. Switches trending so the historical trends on Trend screen can be viewed.
Clears the current value entered in a parameter.
Used to display the Loss limit line in the Trace screen. Switches trending to view the current trends on the Trend screen. And also invert the screen on the big screen.
Changes Relay setpoints from measurement units to a percentage value.
Used to display the Gate on the echo screen.
Reset parameter to default setting.
Press this to eject the Micro SD
card safely. If ‘.’ Is pressed but
the card is not removed it becomes active again after 5 minutes.
Used for decimal parameter values.
Not used with Ultra 4.
Toggle between positive and negative values.

Numeric Keys

These keys are used for entering numerical information during programming.
1 2 3
4 5 6 0 7 8 9
+/-
F1
F2
F3
41
There are two means of editing parameters in the Ultra 4, using the menu system or directly accessing them. Each means of parameter editing is now explained.

Using the Menu System

The menu system has been designed to make the changing of parameters very simple. There are two levels of menu: Main Menu and Sub Menu.
At the top of the display, there is a line of text that displays the main menu system. Pressing the left and right arrow keys scrolls the display between the top-level menu items, (as shown below).
*This option becomes available when Ultra Wizard = Level/Volume. +This option becomes available when Ultra Wizard = Flow. As you press the cursor keys to scroll left and right between these, you can
press ENTER or the down arrow at any time, to expand the sub menu. Each of these options, along with their sub-menus, are described later in this manual. When you move down into the sub-menu, you can scroll around using the arrow keys, press ENTER to go to the required section of parameters.
A scroll bar is shown where more options are available.
mA Out
Echo Process
Stability
Compensation
Device Comm
Test
System
*Volume
Display
+OCM
Data Logs
Relays
Application
Ultra Wizard
Quick Setup
ULTRA 4 INSTRUCTION MANUAL
42
Once you have reached the relevant section, scroll through the parameters, and enter the necessary information. To enter the information, use the
numeric keys and then press ENTER, you will then see the message “Saved!”
If you press CANCEL, then the change you made will not be saved, and you will exit from the parameter to the menu options.
When you have finished, press CANCEL to go back to the previous level. When you have reached the top level, then the Ultra 4 will ask for confirmation before allowing you to go back into run mode. This is done by pressing ENTER at the display prompt ‘Run Mode?’

Directly Editing Parameters

If you already know the number of the parameter, that you wish to look at or edit, simply type the number in at any time while you are in the menu system. Thus, if you are in either the menu or sub-menu level by pressing a numeric key, you can enter the parameter number directly and jump straight there. You cannot type a parameter number whilst at parameter level, only at one of the two menu levels.
When you are at a parameter, the text line rotates automatically displaying the parameter name, number, the applicable units, and the maximum and minimum figure you can enter. The top line shows the value you are setting.
Once you have accessed a parameter, you can either just look at it, or change it.
Once a parameter has been changed, press ENTER and you will see the
message “Saved!”. If you press ‘CANCEL, then the change you made will not be saved, and the message “Unchanged!!” will be displayed.
43

Test Mode

Test mode is used to simulate the application and confirm that all parameters and relay setpoints have been entered as expected. During simulation, there is a choice of whether the relays will change state (hard simulation) or not (soft simulation), but the relay boxes will always change colour as programmed (solid black fill or white fill), and the mA output will change in accordance with the chosen mode of operation. If you wish to test the logic of the system to which the relays are connected, select hard
simulation, but if you don’t wish to change the relay state, then select a soft simulation.
There are two simulation modes, automatic and manual. Automatic simulation will move the level up and down between empty level or the pre­determined Start Level (P983) and Pump/Control relay switch points, if you wish to change the direction of the level movement e.g. to go beyond relay setpoints, this can be done by using the arrow keys. In manual simulation, using the arrow keys will allow you to move the level up and down as required.
To enter simulation, first go to program mode. Using the menu system, select menu item ‘Test’, then sub-menu item ‘Simulation’. Simply change the value of the parameter P980 to one of the following:
1= Manual soft simulation 2= Automatic soft simulation 3= Manual hard simulation 4= Automatic hard simulation
To return to program mode press CANCEL, and test mode will end. When in manual simulation, by default test mode will move the level by
0.1m steps. Altering the increment (P981) will change this value. In automatic mode, the rate at which the level moves up and down is set by
the increment (P981) in metres, the rate (P982) in minutes, which can be changed to make the level move up and down faster. E.g., if increment (P981) is set for 0.1m and rate (P982) is set to 1 min then the level will increase or decrease at a rate of 0.1m/min. To make the simulated level move slower, decrease the value in increment (P981) or increase the value in rate (P982). To make the simulated level move faster, increase the value in increment (P981) or decrease the value in rate (P982).
ULTRA 4 INSTRUCTION MANUAL
44

Using the Serial Interface

The RS232 serial interface is used to communicate between the Ultra 4 and a PC using the optional Ultra PC and other associated Pulsar software packages, to obtain information such as data logging and view echo traces upload, download and save parameter files. In addition, it can also be used to control or obtain information using a standard PC or other computer base equipment. To do so, the settings for control are as follows: baud rate 19,200, 8 data bits, no parity, 1 stop bit.
The device should be connected as shown in Chapter 2 Ultra 4 Installation. To use the device remotely, you need to log on to start, and log off when
finished. When logged on, Ultra 4 will show ‘Remote ON’ on the display, and “Communicator OFF” when logged off.
All commands should be followed by a carriage return. When logged on, the unit will respond either OK (or a value) if the command is accepted, or NO if it is not.
To log on, send the command /ACCESS:pppp where pppp is the passcode (P922). To log off, send the command /ACCESS:OFF To read a parameter value, send the command /Pxxx where xxx is the parameter you wish to read, and the Ultra 4 will
respond with the parameter value. To set a parameter, send the command /Pxxx:yy where xxx is the parameter number, and yy is the value you wish to
set it to.
45
Other commands you can use are:
/DISTANCE (shows current distance)
/LEVEL (shows current level)
/SPACE (shows current space)
/RATE (shows current rate)
/VOLUME (shows current volume)
/TEMP (shows current temperature)
/CURRENTOUT1 (show the mA output 1 value)
/CURRENTOUT2 (show the mA output 2 value)
/BACKUP1 (take backup of parameters to area 1)
/BACKUP2 (take backup of parameters to area 2)
/RESTORE1 (restore parameters from area 1)
/RESTORE2 (restore parameters from area 2)
Please consult Pulsar Measurement or contact your local Pulsar representative for further details and a full list of available commands.
ULTRA 4 INSTRUCTION MANUAL
46

Parameter Defaults

When you first switch the Ultra 4 on, it will be reading the distance from the face of the transducer to the surface. It will be indicating in metres, as shown on the display. All relays are set OFF.
The date (P931) and time (P932) in the Ultra 4 were set at the factory, but may need checking, and amending if, for example the application is in a time zone other than GMT, see relevant parameter listing for full details.
In some applications, it is easier to empty the vessel, take a reading from the Ultra 4 for distance and then setup the empty level to this figure.
Once you are satisfied with the installation, and Ultra 4 is reading what you would expect in terms of distance from the face of the transducer to the material level, then you can proceed with programming, for the intended application. It is sensible to program all the required parameters at the same time. The system will be then set-up.
The span is automatically calculated from the empty level, so the empty level should be entered first.
Factory Defaults
When first installing the Ultra 4, or subsequently moving or using the unit on a new application, before proceeding to program the unit for its intended application it is recommended that you ensure that all parameters are at their default values by completing a Factory Default P930, as described in the relevant unit type parameter guide.
47

CHAPTER 4 ULTRA WIZARD

The Ultra Wizard menu allows you to turn Ultra 4 into anyone of three dedicated ultrasonic devices to exactly suit the requirements of your application.

Enter Program Mode

First you need to go from run mode into program mode. Assuming the passcode is the default 1997, then you should enter the following on the keypad:

Choose Ultra Wizard

Now you need to go into the quick setup. You will see on the menu the
words ‘Quick Setup’, which is the first item on the menu system. Try pressing
the two arrow keys to see some more menu options, but return to Quick Setup, and press
1 = Level or Volume measurement (Level/Vol) 2 = Pump Control (Pump) 3 = Open Channel Flow measurement (Flow)
Once you have selected the application of your choice the Ultra 4 will be configured to the system type specific to that task. And you can continue to set up the controller with ease.
ENTER
1
9 9 7
ULTRA 4 INSTRUCTION MANUAL
48

Ultra 4 - Level / Volume

If you require to set up a level or volume application, with or without a choice of control functions, use the arrow keys to highlight Level/Volume or
press “1” followed by “ENTER” the message “Saved” followed by “Loading ***” will be displayed and your Ultra 4 will be configured to allow the setup
for level/volume applications. Confirmation that configuration has been completed will be the unit returning to the Ultra Wizard selection and the setup you have chosen will be displayed. You can now continue in the unit advancing to the relevant “Quick Setup” menu.
For full details on how to programme the Ultra 4 for level/volume, using the Quick Setup Menu, please proceed to Chapter 5 Level/Volume. For a full description of all features and parameters please refer to Chapter 8 Parameter Listing and Description.
Programming the controller for level/volume, provides the ability to convert level measurement to enable the contents of a vessel to be displayed in volume, along with control functions, for a complete range of vessel shapes. Also available within the unit is a customised 32-point calibration routine which also permits the calculation of volume in non - standard vessels.
The Ultra 4 can measure from zero to 40 m from the face of the transducer to the surface being monitored, dependent on the transducer used. Details of level, space, distance, and units of volume can be shown on the display. The four user-definable relays with individual setpoints can be programmed to activate devices such as pumps or other control equipment.
The 4-20 mA output is fully programmable to provide an output relative to level, space, distance or volume of the application being measured.

Ultra 4 - Pump control

Programming the controller for pump control, provides a complete range of pump “duties” readily available to the user.
The Ultra 4 can measure from zero to 40m from the face of the transducer to the surface being monitored, dependent on the transducer used. Details of level, space or distance can be shown on the display. The four user definable relays with individual setpoints can be programmed to activate alarms, pump starters, or other control equipment.
The 4-20 mA output is fully programmable to provide an output relative to level, space, or distance. If you require to set up a pump application, then
49
use the arrow keys to highlight Pump or press “2” followed by “ENTER” the message “Saved” followed by “Loading ***” will be displayed and your Ultra
4 will be configured to allow the setup for pump applications. Confirmation that configuration has been completed will be the unit
returning to the Ultra Wizard selection and the setup you have chosen will be displayed. You can now continue in the unit advancing to the relevant “Quick Setup” menu.
For full details on how to programme the Ultra 4 for Pump control, using the Quick Setup Menu, please proceed to Chapter 6 Pump. For a full description of all features and parameters please refer to Chapter 8 Parameter Listing and Description.

Ultra 4 - Flow

If you require to set up a flow application, then use the arrow keys to
highlight Flow or press “3” followed by “ENTER” the message “Saved” followed by “Loading ***” will be displayed and your Ultra 4 will be
configured to allow the setup for flow applications. Confirmation that configuration has been completed will be the unit returning to the Ultra Wizard selection and the setup you have chosen will be displayed. You can now continue in the unit advancing to the relevant “Quick Setup” menu.
For full details on how to programme the Ultra 4 for flow, using the Quick Setup Menu, please proceed to Chapter 7 Flow. For a full description of all features and parameters please refer to Chapter 8 Parameter Listing and Description.
Programming the controller for Open Channel Flow Measurement (OCM) provides comprehensive flow monitoring with data logging and control functions for a complete range of flumes, weirs and channels. Flow calculations to the British Standard BS3680 are available within the firmware together with calculations for a wide variety of other primary elements. Also available within the unit is a customised 32-point calibration routine which also permits the flow measurement of non - standard flumes and weirs.
ULTRA 4 INSTRUCTION MANUAL
50
The Ultra 4 can measure from zero to 16m from the transducer to the surface being monitored, dependent on the transducer used. Details of level, space, distance, head, or flow can be show on the display along with a totaliser if desired. The four user-definable relays with individual setpoints can be programmed to activate devices such as pumps, samplers, remote totalisers, or other control equipment.
The 4-20 mA output is fully programmable to provide an output relative to level, space, distance, head, average flow, or flow.
51

CHAPTER 5 LEVEL / VOLUME

This quick set-up guide shows you how to get up and running within a few minutes of installing your Ultra 4. As outlined in Chapter 4 Ultra Wizard of this manual the unit type can set up to monitor Level/Volume, Pump control or Flow. The following steps show you the quick setup for each system type.

System type selection

Before proceeding ensure that the Ultra Wizard = 1 Level/Volume, 2 = Pump or 3 = Flow. For further details, see Chapter 4 Ultra Wizard of this
manual.

Enter Program Mode

First you need to go from run mode into program mode. Assuming the passcode is the default 1997, then you should enter this.

Choose Quick Setup

Now you need to go into the quick setup. You will see on the display the
words ‘Ultra Wizard’, press the ‘right hand’ arrow key and this will take you to the ‘Quick Setup’ menu option. Try pressing either of the two arrow keys
to see some more menu options, but return to Quick Setup, and press
ENTER
1
9 9 7
ENTER
This takes you to the ‘Quick Setup Menu.’
ENTER
This takes you to the common applications menu, and several options will appear on the display.
This will appear on the display of the unit, before pressing Enter.
Pass Code * * * *
ULTRA 4 INSTRUCTION MANUAL
52

Level or Volume Application

When Ultra Wizard = 1, Level/Volume there are two categories of application, which are all described later in this chapter. They are level or volume, both with the choice of control functions and alarms.
If you want to set-up a basic level monitoring application, as described in example 1, then choose option 1.
If you want to set-up a level monitoring application with control relays, as described in example 2, then choose 1 and choose either control down (option 1) or control up (option 2).
If you want to set-up a volume application, as described in the following example 3, then choose option 2.
Once you have chosen your application you will be able to choose a series of parameters with the options detailed in Chapter 7 to setup your application. Once all the parameters have been set in the quick setup you can return to run mode, or alternatively if you have more advanced parameters to setup, you can access these through the menu system, to complete the programming of the unit.
53

Quick Setup

Xducer (P101)
0 = None 1 = dB3
2 = dB6 (default)
3 = dB10 4 = dB15 5 = dB25 6 = dB40 7 = dBS6 8 = dBMach3
9 = dBR16
10 = dBR8
Material (P102)
1 = Liquid 2 = Solid
3 = Closed Tank
Measurement
units (P104)
1 = metres (default)
2 = Centimetres
3 = Millimetres
4 = Feet
5 = Inches
Empty Level
(P105)
Span (P106)
No. of Controls
0 = 0 Control 1 = 1 Control 2 = 2 Controls 3 = 3 Controls
4 = 4 Controls
0 = No Control
1 = Control
2 = Control Up
Quick Setup
1 = Level
2 = Volume
For each
Control Relay
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3
4 = Set to Relay 4
Alarm No. *
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3
4 = Set to Relay 4
Alarm ID (P2*2)
1 = High 2 = Low 3 = Hi-Hi 4 = Lo-Lo
5 = Loss of Echo
No. of Alarms
0 = 0 Alarms 1 = 1 Alarm
2 = 2 Alarms 3 = 3 Alarms
4 = 4 Alarms
ULTRA 4 INSTRUCTION MANUAL
54
Saving Parameters…. Please wait
If you have selected a Volume Application, you will now be prompted to enter details required for the calculation of your volume application.
PARAMETER
DEFAULT
DESCRIPTION
P600 Vessel Shape
0 = Cylinder Flat Base
Shape of vessel being monitored. Select from the options below:
0 = Cyl. Flat Base (default)
1 = Rect. Flat Base 2 = Cone Base 3 = Pyram. Base 4 = Parab. Base 5 = Half Sphere 6 = Cyl. Sloped 7 = Rect. Sloped 8 = Cyl. Flat 9 = Cyl. Parabolic 10 = Sphere 11 = Uni. Linear
P601–P603 Vessel Dimensions
Dependent on vessel shape selected
Enter vessel dimensions as required.
P605 Volume units
3 = Cubic metres
Selects volume units required from the list below: 1 = Tons 2 = Tonnes 3 = Cubic metres (default) 4 = Litres 5 = UK Gallons 6 = US Gallons 7 = Cubic Feet 8 = Barrels 9 = Lbs (pounds)
P607 Max Volume
Read Only
Displays the calculated Volume in P605 units.
55
For More Options Hit Enter...
PARAMETER
DEFAULT
DESCRIPTION
P213 / P214 Relay 1 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P223 / P224 Relay 2 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P233 / P234 Relay 3 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P830 mA Out Range
2 = 4 to 20mA
Determines the mA output range. 0 = Off
1 = 0 to 20mA 2 = 4 to 20mA 3 = 20 to 0mA 4 = 20 to 4mA.
P870 Fill Damping
10m/min
Rate of maximum fill rate (set above the actual fill rate of the vessel).
P871 Empty Damping
10m/min
Rate of maximum empty rate (set above the actual rate of the vessel).
ULTRA 4 INSTRUCTION MANUAL
56

Relay Setpoints Table

The default values used for determining the relay setpoints, when setting Alarms and Control relays, via the Quick Setup menu are entered as a % of
span and are as follows:
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Control Down
One
Control 1
80%
20%
Control Down
Two
Control 1 Control 2
80% 70%
20% 20%
Control Down
Three
Control 1 Control 2 Control 3
80% 70% 60%
20% 20% 20%
Control Down
Four
Control 1 Control 2 Control 3 Control 4
80% 70% 60% 50%
20% 20% 20% 20%
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Control Up
One
Control 1
20%
20%
Control Up
Two
Control 1 Control 2
20% 30%
20% 20%
Control Up
Three
Control 1 Control 2 Control 3
20% 30% 40%
20% 20% 20%
Control Up
Four
Control 1 Control 2 Control 3 Control 4
20% 30% 40% 50%
20% 20% 20% 20%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%
57

Example 1 Level Monitoring with Alarms

A vessel, containing liquid that has a variation in level that is to be monitored, with a high-level alarm set on Relay 1 and low-level alarm set on Relay 2.
In this example, when the level rises to 2.38m (7.8 ft), relay 1 will come on until the level drops to 2.24m (7.34 ft) when it will turn off. If the level drops to 0.28m (0.92 ft), then relay 2 will come on until it rises 0.42m (1.37 ft) when it will turn off.
The display will show the level in the tank.
The mA output will be representative of level where 4mA = empty level (0%) and 20mA = 2.8m (9.18 ft) (100%).
Empty Distance (P105), 3.5m (11.48 ft)
100%. Span (P106), 2.8m (9.18 ft)
85%. High alarm on (P213), 2.38m (7.8 ft)
80%. High alarm off (P214), 2.24m (7.34 ft)
0%, Empty level
10%. Low alarm on (P223), 0.28m (0.92 ft)
15%, Low alarm off (P224), 0.42m (1.37 ft)
ULTRA 4 INSTRUCTION MANUAL
58
To program the unit for Example 1 using the Quick Setup menu, proceed as follows.
If required access Program Mode, by keying in the passcode 1997 and press ENTER.
Using the ‘right’ arrow key, go to the Quick Setup menu and press ENTER. And as prompted, by the questions, select the relevant option and press
ENTER.
QUESTION
OPTION
Level/Volume
1 = Level App.
No. of alarms
2 = 2 Alarms
Type alarm 1
1 = High
Alarm no.1
1 = Set to relay 1
Type alarm 2
2 = Low
Alarm no.2
2 = Set relay 2
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Ultra 4 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
59

Example 2 Level Monitoring and Control (up or down)

A vessel, containing a liquid that has a variation in level that is to be monitored, and when the level reaches a specific point, the vessel is pumped down, with the fluid being transferred to another process. The pump will be assigned to Relay 1 a High Alarm to Relay 2 and Low Alarm to Relay 3.
In this example, there is a control relay (relay 1), which will come on if the level rises to 2.24m (7.80 ft) and go off when the level drops to 0.56m (1.83 ft) (control down). If the level rises to 2.38m (7.80 ft), then the high-level alarm (relay 2) will come on until the level drops to 2.24m (7.34 ft). If the level falls to 0.28m (0.918 ft), then the low-level alarm (relay 3) will come on until the level rises to 0.42m (1.37 ft).
Alternatively, if it is a control up application, then the on and off points for the control relay are reversed, so the control device comes on when the level is at 0.56m (1.83 ft) and goes off when it rises to 2.24m (7.34 ft). The display will show the level in the tank and the mA output will be representative of level where 4mA = empty level (0%) and 20mA = 2.8m (9.18 ft) (100%).
Empty Distance (P105), 3.5m (11.4 ft)
100%. Span (P106), 2.8m (9.18 ft)
85%. High alarm on (P213), 2.38m (7.8 ft)
80%. High alarm off (P214), 2.24m (7.34 ft)
0%, Empty level
10%. Low alarm on (P233), 0.28m (0.918 ft)
15%, Low alarm off (P234), 0.42m (1.37 ft)
80%. Control (down) on (P213), 2.24m (7.34 ft)
20%. Control (down) off (P214), 0.56m (1.83 ft)
ULTRA 4 INSTRUCTION MANUAL
60
To program the unit for Example 2 using the Quick Setup menu, proceed as follows.
If required access Program Mode, by keying in the passcode 1997 and pressing ENTER.
Using the ‘right’ arrow key, go to the Quick Setup menu press ENTER. And as prompted, by the questions, select the relevant option and press ENTER
QUESTION
OPTION
Level/Volume
1 = Level App.
Control
1 = Control down
No. of controls
1 = 1 Relay
Control no.1
1 = Set to relay 1
No. of alarms
2 = 2 Alarms
Type alarm 1
1 = High
Alarm no.1
1 = Set to relay 2
Type alarm 2
2 = Low
Alarm no.2
The unit knows that only Relay 3 is available and so will automatically set Alarm 2 to Relay 3.
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Ultra 4 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application, they can be modified to suit by pressing ENTER when, “For More Options
Hit Enter”, is displayed and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed, as necessary.
61

Example 3 Volume Application

A cylindrical tank with a diameter of 2m and a flat base that is typically used to temporarily hold liquid, and you wish to know the volume of liquid. You also require a high and low alarm and when the level reaches a specific point, the vessel is pumped down, with the fluid being transferred to another process.
In this example, there is a pump (relay 1), which will come on if the level rises to 2.24m (7.39 ft) and go off when the level drops to 0.56m (1.83 ft). (Control down). If the level rises to 2.38m (7.8 ft), then the high-level alarm (relay 2) will come on until the level drops to 2.24m (7.39 ft). If the level falls to 0.28m (0.91 ft), then the low-level alarm (relay 3) will come on until the level rises to 0.42m (1.37 ft).
The display will show the volume of fluid in the tank and the mA output will be representative of Volume where 4mA = empty (0%) and 20mA = Max Volume (100%).
Empty Distance (P105), 3.5m (11.48 ft)
100%. Span (P106), 2.8m (9.18 ft)
85%. High alarm on (P213), 2.38m (7.8 ft)
80%. High alarm off (P214), 2.24m (7.39 ft)
0%, Empty level
10%. Low alarm on (P233), 0.28m 0.91 ft)
15%, Low alarm off (P234), 0.42m (1.37 ft)
80%. Control (down) on (P213), 2.24m (7.39 ft)
20%. Control (down) off (P214), 0.56m (1.83 ft)
ULTRA 4 INSTRUCTION MANUAL
62
To program the unit for Example 3 using the Quick Setup menu, proceed as follows. If required access Program Mode, by keying in the passcode 1997 and press ENTER. Using the ‘right’ arrow key, go to the Quick Setup menu and press ENTER. And as prompted, by the questions, select the relevant option and press ENTER.
This example is for a cylindrical flat-bottomed vessel. See P600 Vessel Shape in the following Parameter Guide, for a description of all the other vessel shapes you could select, and dimensions required. Programming is now complete, and the unit can be returned to the run mode. To do this, press CANCEL until Run Mode? is displayed on the screen. Press ENTER, and the Ultra 4 will now return to Run Mode
QUESTION
OPTION
Level/Volume
1 = Level App.
Control
1 = Control down
No. of controls
1 = 1 Relay
Control no.1
1 = Set to relay 1
No. of alarms
2 = 2 Alarms
Type alarm 1
1 = High
Alarm no.1
1 = Set to relay 2
Type alarm 2
2 = Low
Alarm no.2
The unit knows that only Relay 3 is available and so will automatically set Alarm 2 to Relay 3.
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Vessel shape (P600)
0 = Cylindrical flat base
Vessel dimensions
Enter vessel dimensions as requested (depends on vessel shape chosen)
Volume units
Select as required
Max Volume (Read only)
Displays the Max volume as calculated by the Ultra 4. This is a read only parameter.
63
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed, as necessary.
ULTRA 4 INSTRUCTION MANUAL
64

CHAPTER 6 PUMP

When Ultra Wizard = 2 Pump
This quick set-up guide shows you how to get up and running within a few minutes of installing your Ultra 4.
Before proceeding ensure that the Ultra Wizard = 2 Pump (Vantage 3). For further details, see Chapter 4 Ultra Wizard.

Enter Program Mode

First you need to go from run mode into program mode. Assuming the passcode is the default 1997, then you should enter this.

Choose Quick Setup

Now you need to go into the quick setup. You will see on the display the
words ‘Ultra Wizard’, press the ‘right hand’ arrow key and this will take you to the ‘Quick Setup’ menu option. Try pressing either of the two arrow keys
to see some more menu options, but return to Quick Setup, and press
ENTER
1
9 9 7
ENTER
This takes you to the ‘Quick Setup Menu.’
ENTER
This takes you to the common applications menu, and several options will appear on the display.
This will appear on the display of the unit, before pressing Enter.
Pass Code * * * *
65
Pump Application
When Ultra Wizard = 2, Pump there are two categories of application, which are all described later in this manual. They are pump down (sump control) or pump up (reservoir control) all with the choice of alarms.
If you want to set-up a basic level monitoring application, as described in example 4, then choose option 1.
If you want to set-up a pump down (sump control) application, as described in example 5 then choose option 2.
If you want to set-up a pump up (reservoir control) application, as described in the following example 6 then choose option 3.
Once you have chosen your application you will be asked a series of questions which are answered by choosing the appropriate option as detailed in the flow chart on the following page. Once all the parameters have been set in the quick setup you can return to run mode, or alternatively if you have more advanced parameters to setup you can access these through the menu system, to complete the programming of the unit.
ULTRA 4 INSTRUCTION MANUAL
66

Quick Setup Menu

No. of Alarms
0 = 0 Alarms 1 = 1 Alarm
2 = 2 Alarms 3 = 3 Alarms
4 = 4 Alarms
Alarm ID (P2*2)
1 = High 2 = Low 3 = Hi-Hi 4 = Lo-Lo
5 = Loss Of Echo
Quick Setup
No. of Pumps
0 = 1 Pump 1 = 2 Pumps 2 = 3 Pumps
3 = 4 Pumps
Pump Duty
1 = Fixed DutyAss 2 = Fixed DutyBkp 3 = Alt DutyAss 4 = Alt DutyBkp 5 = Duty BkpAss 6 = Service DtyAss 7 = Service DtyBkp
8 = FOFO AltDtyAss 9 = ServRatio Stby
0 = Level
1 = Pump Down
2 = Pump Up
Pump No. *
1 = Set to Relay 1
2 = Set to Relay 2 3 = Set to Relay 3
4 = Set to Relay 4
Alarm No. *
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3
4 = Set to Relay 4
Xducer (P101)
0 = None 1 = dB3
2 = dB6 (default)
3 = dB10 4 = dB15 5 = dB25 6 = dB40 7 = dBS6 8 = dBMach3 9 = dBR16
10 = dBR8
Material (P102)
1 = Liquid 2 = Solid
3 = Closed Tank
Measurement units
(P104)
1 = metres (default)
2 = Centimetres
3 = Millimetres
4 = Feet
5 = Inches
Empty Level
(P105)
Span (P106)
67
Saving Parameters…. Please wait
PARAMETER
DEFAULT
DESCRIPTION
P213 / P214 Relay 1 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P223 / P224 Relay 2 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P233 / P234 Relay 3 ON/OFF
setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P233 / P234 Relay 3 ON/OFF setpoints
Factory preset as a % to appropriate level according to the span already entered. See tables below
Either Alarm or Level control. Depends on application.
P830 mA Out Range
2 = 4 to 20mA
Determines the mA output range. 0 = Off
1 = 0 to 20mA
2 = 4 to 20mA
3 = 20 to 0mA 4 = 20 to 4mA.
P870 Fill damping
10m/min
Rate of maximum fill rate (set above the actual fill rate of the vessel).
P871 Empty damping
10m/min
Rate of maximum empty rate (set above the actual empty rate of the vessel).
ULTRA 4 INSTRUCTION MANUAL
68

Relay Setpoints Table

The default values used for determining the relay setpoints, when setting Alarms and Control relays, via the Quick Setup menu are entered as a % of
span and are as follows:
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Down
One
Pump 1
50%
20%
Pump Down
Two
Pump 1 Pump 2
50% 70%
20% 20%
Pump Down
Three
Pump 1 Pump 2 Pump 3
50% 60% 70%
20% 20% 20%
Pump Down
Four
Pump 1 Pump 2 Pump 3 Pump 4
40% 50% 60% 70%
20% 20% 20% 20%
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Control Up
One
Control 1
50%
20%
Control Up
Two
Control 1 Control 2
50% 30%
20% 20%
Control Up
Three
Control 1 Control 2 Control 3
50% 40% 30%
20% 20% 20%
Control Up
Four
Control 1 Control 2 Control 3 Control 4
60% 50% 40% 30%
20% 20% 20% 20%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%
69

Example 4 Level Monitoring with Alarms

A vessel, containing liquid that has a variation in level that is to be monitored, with a high-level alarm set on Relay 1 and low-level alarm set on Relay 2.
In this example, when the level rises to 2.38m (7.80 ft), relay 1 will come on until the level drops to 2.24m (7.34 ft) when it will turn off. If the level drops to 0.28m (0.91 ft), then relay 2 will come on until it rises 0.42m (1.37 ft) when it will turn off.
The display will show the level in the tank. The mA output will be representative of level where 4mA = empty level (0%)
and 20mA = 2.8m (9.18 ft) (100%).
Empty Distance (P105), 3.5m (11.48 ft)
100%. Span (P106), 2.8m (9.18 ft)
85%. High alarm on (P213), 2.38m (7.8 ft)
80%. High alarm off (P214), 2.24m (7.34 ft)
0%, Empty level
10%. Low alarm on (P223), 0.28m (7.8 ft)
15%, Low alarm off (P224), 0.42m (7.8 ft)
ULTRA 4 INSTRUCTION MANUAL
70
To program the Ultra 4 for Example 4 Level Monitoring with Alarms by using the Quick Setup menu proceed as follows. If required to access Program Mode, key in the passcode 1997 and press ENTER
At the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump up or down
1 = Level App.
No. of alarms
2 = 2 Alarms
Type alarm 1
1 = High
Alarm no.1
1 = Set to relay 1
Type alarm 2
2 = Low
Alarm no.2
2 = Set relay 2
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Ultra 4 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application, they can be modified to suit by pressing ENTER when, “For More Options
Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
71

Example 5 Sump Control (pump down)

A sump is typically used to temporarily hold water or effluent, and when the level reaches a specific point, the sump is pumped down, with the fluid being transferred to another process.
A sump is typically used to temporarily hold water or effluent, and when the level reaches a specific point, the sump is then pumped down, with the fluid being transferred to another process. In this example, there are two pumps, which will be set to alternate duty assist, so they come on alternately. Pump 1 is to be set to relay 1, pump 2 to relay 2, and the high-level alarm to relay 3.
This will operate as follows. During normal operation, pump 1 will come on at 1.4m (4.59 ft) and pump down to 0.56m (1.83 ft). The setpoints are then shifted to pump 2, which will come on first next time the pumps are called to run. During peak periods, when pump 1 cannot cope, pump 1 will come on at 1.4m (4.59 ft), pump 2 will come on at 1.96m (6.43 ft) and pump down to 0.56m (1.83 ft). The setpoints are then shifted to pump 2, which will come on first next time.
Empty Distance (P105), 3.5m (11.48 ft)
100%. Span (P106), 2.8m (9.18 ft)
85%. High alarm on (P233), 2.38m (7.80 ft)
80%. High alarm off (P234), 2.24m (7.34 ft)
0%, Empty level
20%. Pump 1+2 off (P214, 224), 0.56m (1.83 ft)
70%. Pump 2 on (P213, 1.96m (6.43 ft)
50%. Pump 2 on (P223), 1.4m (4.59 ft)
ULTRA 4 INSTRUCTION MANUAL
72
If neither pump can cope, and the level rises to 2.38m (7.8 ft), then the alarm relay (relay 3) will come on and go off when the level falls to 2.24m (7.34 ft). This will indicate insufficient capacity of the pumps. The display will show the level in the sump and the mA output will be representative of level where 4mA = empty level (0%) and 20mA = 2.8m (9.18 ft) (100%).
To program the Ultra 4 for Example 5 Sump control (pump down) by using the Quick Setup menu proceed as follows. If required to access Program Mode, key in the passcode 1997 and press ENTER
At the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump Up or Down
2 = Pump Down
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 1
Pump No. 2
2 = Set to relay 2
Type Alarm 1
1 = High Alarm
Alarm No. 1
The unit knows that only Relays 3 & 4 are available and will only display these for use.
Xducer (P101)
2 = dB6
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Ultra 4 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application, they can
be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is
displayed, and entering new values to relay setpoints as required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
73

Example 6 Reservoir Control (pump up)

A reservoir is typically used to temporarily hold liquid, and when the level reaches a specific low point, the reservoir is pumped up.
In this example, there are two pumps, which will be set to alternate duty assist, so they come on alternately. Pump 1 is to be set to relay 2, pump 2 to relay 3, and the low-level alarm to relay 1. This will operate as follows: During normal operation, pump 1 will come on at 1.4m (4.59 ft) and pump up to 2.24m (7.34 ft). The setpoints are then shifted to pump 2, which will come on first next time.
During peak periods, when pump 1 cannot cope, pump 1 will come on at
1.4m (4.59 ft) and pump 2 will come on at 0.84m (2.75 ft) and pump up to
2.24m (7.34 ft). The setpoints are then shifted to pump 2, which will come on first next time. If both pumps cannot cope, and the level drops to
0.28m (0.91 ft), then the alarm relay (relay 1) will come on and go off when the level rises to 0.42m (1.37 ft). This will indicate insufficient capacity of the pumps. The display will show the level in the sump and the mA output will
50%. Pump 2 on (P233), 1.4m (4.59 ft) 0% - Empty level
80%. Pump 1&2 off (P224, P234)
2.24m (7.34 ft)
10% - Low alarm on (P213), 0.28m (0.91 ft)
Empty distance (P105), 3.5m (11.48 ft) 30%. Pump 1 on (P223), 0.84m (2.75 ft)
100%. Span (P106), 2.8m (9.18 ft)
15%. Low alarm off (214), 0.42m (1.37 ft)
ULTRA 4 INSTRUCTION MANUAL
74
be representative of level where 4mA = empty level (0%) and 20mA = 2.8m (9.18 ft) (100%). To program the Ultra 4 for Example 6 Reservoir Control (pump up) by using the Quick Setup menu proceed as follows. If required access the Program Mode and key in the passcode 1997 and press ENTER
Using the ‘right arrow key, go to Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and ENTER.
QUESTION
OPTION
Level/Pump Up or Down
2 = Pump Up
No. of Pumps
2 = 2 Pumps
Pump Duty
3 =Alt Duty Assist
Pump No. 1
1 = Set to relay 2
Pump No. 2
2 = Set to relay 3
No. of alarms
1 = 1 alarm
Type Alarm 1
2 = Low Alarm
Alarm No. 1
The unit knows that only relay 1 is available and so will automatically set alarm 1 to Relay 1
Xducer (P101)
2 = dB6
Measurement units (P104)
1 = Metres
Empty Level (P105)
3.5m
Span (P106)
2.8m
Programming is now complete, and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Ultra 4 will return to the Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options
Hit Enter”, is displayed, and entering new values to relay setpoints as required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
75

CHAPTER 7 FLOW

When Ultra Wizard = 3 Flow
This quick set-up guide shows you how to get up and running within a few minutes of installing your Flow 3.
Before proceeding ensure that the Ultra Wizard = 3 Flow (Flow 3). For further details, see Chapter 4 Ultra Wizard.

Enter Program Mode

First you need to go from run mode into program mode. Assuming the passcode is the default 1997, then you should enter this.

Choose Quick Setup

Now you need to go into the quick setup. You will see on the display the
words ‘Ultra Wizard’, press the ‘right hand’ arrow key and this will take you to the ‘Quick Setup’ menu option. Try pressing either of the two arrow keys
to see some more menu options, but return to Quick Setup, and press
ENTER
1
9 9 7
ENTER
This takes you to the ‘Quick Setup Menu.’
ENTER
This takes you to the common applications menu, and several options will appear on the display.
This will appear on the display of the unit, before pressing Enter.
Pass Code * * * *
ULTRA 4 INSTRUCTION MANUAL
76

Choose Your Application

There are five categories of Primary Measuring Device, which are all described in this chapter. They are exponential, BS3860 flumes, BS3860 weirs, special and universal. Calculations for flow can be performed using absolute or ratiometric calculations. The answer will be the same, the choice of calculation method being limited to the amount of information available, with regards to the primary measuring device. For ratiometric calculation it is normally sufficient to know the maximum flow at maximum head for the device in question. All types of primary measuring devices can be set up with a choice of alarms.
If you want to set-up a basic exponential device, as described in the following example 1, then choose 1. You then need to select the primary
measuring device for your application from the following available options: suppressed rectangular weir, Cipolletti (trapezoidal) weir, Venturi flume, Parshall flume, Leopold Lagco flume, V notch weir or other, for
any other type of exponential device. To set-up an application for a BS3680 flume, as described in the following
example 2, then choose 2. You then need to select the primary measuring device for your application from the following available options: rectangular flume with or without hump, U-throated flume with or without hump.
To set-up an application for a BS3680 weir, as described in the following example 3, then choose 3. You then need to select the primary measuring device for your application from the following available options: rectangular weir, V notch full 90o (90degrees), V notch half 90o (53 degree 8 minutes) or a V notch quarter 90o (28 degree 4 minutes).
To set-up an application for a device contained in special, choose 5. You then need to select the primary measuring device for your application from the following available options: Palmer Bowlus flume, H-flume or a V notch, other than BS3680.
77
For devices, which do not match any of the above devices the application can be setup using a universal flow calculation, to select this option choose 6. You then need to select the primary measuring device for your application from the following available options: linear flow or curved flow. Once you have chosen your application you will be asked a series of questions which are answered by choosing the appropriate option as detailed in the flow chart below. Once all the questions have been answered you will be prompted to provide further information, as detailed in the tables below, to complete the programming of the unit.
ULTRA 4 INSTRUCTION MANUAL
78

Quick Setup Menu

Empty Level (P105)
Xducer (P101)
0 = None
1 = dB3
2 = dB6 3 = dB10 4 = dB15 5 = Not Available 6 = Not Available 7 = dBS6
8 = dBMach3 (default)
9 = dBR16 10 = dBR8
Volume units (P706)
1 = Litres (default)
2 = Cubic Metres
3 = Cubic Feet 4 = UK Gallons 5 = US Gallons 6 = Mil. USG 7 = Custom Units
Measurement units
(P104)
1 = metres (default)
2 = Centimetres 3 = Millimetres 4 = Feet
5 = Inches
Time units (P707)
1 = Per Second (default)
2 = Per Minute 3 = Per Hour 4 = Per Day
Alarm ID (P2*2)
1 = High 2 = Low 3 = Hi-Hi 4 = Lo-Lo 5 = Loss Of Echo
Alarm No. *
1 = Set to Relay 1 2 = Set to Relay 2 3 = Set to Relay 3 4 = Set to Relay 4
No. of Alarms
0 = 0 Alarms 1 = 1 Alarm
2 = 2 Alarms
3 = 3 Alarms
4 = 4 Alarms
Calculation (P702)
1 = Absolute 2 = Ratiometric
BS3680 Weir
1 = Rectangular 2 = V-Notch 90
°
3 = V-Notch 53
°
4 = V-Notch 28° 5 = Broad Crested
Exponent
1 = Supp. Rect. 2 = Trapezoidal 3 = Venturi 4 = Parshall 5 = Leopold 6 = V-Notch 7 = Other 8 = Rect. Contracted
BS3680 Flume
1 = Rectangular 2 = Rect. Hump 3 = U-Throat
4 = U-Throat Hump
Special
1 = Palmer Bowlus 2 = H - Flume 3 = V-Notch Angle
Universal
1 = Linear Flow 2 = Curved Flow
Quick Setup
PMD Type (P700)
0 = Off (No Calculation) 1 = Exponent 2 = 3680 Flume 3 = 3680 Weir 4 = Not Available 5 = Special
6 = Universal
79
Quick Setup Flow Continued:
PARAMETER
DEFAULT
DESCRIPTION
P703 Minimum Head
0.000m
Distance from empty point (P105) to zero flow.
P704 Max Head
2.425m
Distance from zero flow to max flow. It should be noted that any change to P704 updates P106 Span, and vice versa.
P824 Totaliser Enable
1 = On
Enables the flow totaliser, P820, options are 0=Off, 1=On. Note this totaliser can be viewed during run mode by pressing the down arrow key. It can be reset but only whilst in program mode.
P823 Totaliser multiplier
7 = *1
Sets the factor by which the calculated volume will be divided or multiplied by before being displayed. 1= /1,000,000 2 = /1,00,000 3 = /10,000 4 = /1,000 5 = /100 6 = /10
7 = *1 8 = *10 9 = *100 10 = *1,000 11 = *10,000 12 = *100,000 13 = *1,000,000
ULTRA 4 INSTRUCTION MANUAL
80
The remaining parameters required to finalise the setup of your application will follow on immediately from the above. These parameters relate to details required to carry out the calculation for flow and will be dependent on the Primary Measuring Device chosen and the method of calculation chosen, please enter values for the parameters concerned as requested.
PARAMETER
DEFAULT
DESCRIPTION
P705 Max flow
0.00
When requested enter the known maximum flow rate, in units of volume (P706) and Time (P707) which occurs at maximum head (P704)
P710 Dimension A
0
When requested, enter, in measurement units (P104) the required dimension.
P711 Dimension B
0
When requested, enter, in measurement units (P104) the required dimension.
P712 Dimension C
0
When requested, enter, in measurement units (P104) the required dimension.
P713 Dimension D
0
When requested, enter, in measurement units (P104) the required dimension.
P717 Exponent
Dependent on chosen PMD
Where available the unit will automatically enter the default exponent value for the PMD chosen, but this can be changed if required. When P700 = 7 (Other), enter the exponent value as defined by the manufacturer of the PMD.
P718 K Factor
Enter the ‘K’ factor for the PMD.
Obtained from the manufacturer’s specifications
P843 Aux Line 2
0 = None
Allows another variable to be shown in an auxiliary display line, such as the resettable totaliser.
Saving Parameters…. Please Wait
Important Notice
To view auxiliary information on the Big Screen in run mode, please program aux line 1 to view this information.
81
For More Options Hit Enter
PARAMETER
DEFAULT
DESCRIPTION
P213 / P214 Relay 1 ON/OFF setpoints
Depends on application
Either Alarm or Level control. Depends on application.
P223 / P224 Relay 2 ON/OFF setpoints
Depends on application
Either Alarm or Level control. Depends on application.
P233 / P234 Relay 3 ON/OFF setpoints
Depends on application
Either Alarm or Level control. Depends on application.
P234 / P244 Relay 4 ON/OFF setpoints
Depends on application
Either Alarm or Level control. Depends on application.
P708 Flow Decimal
2
Sets the number of decimal points required in the flow rate display.
P709 Flow cut off
5%
Enter, as a percentage maximum flow. The minimum flow rate to be added to the totaliser.
P830 mA Out range
2 = 4 -20mA
What the mA output uses for the range. 0= Off, 1= 0 to 20 mA, 2= 4 to 20 mA (Default), 3= 20 to 0 mA, 4= 20 to 4 mA.
P870 Fill Damping
10m/min
Rate of maximum fill rate (set above the actual fill rate of the vessel)
P871 Empty Damping
10m/min
Rate of maximum empty rate (set above the actual empty rate of the vessel)

Relay Setpoints Table

The default values used for determining the relay setpoints, when setting Alarm relays, via the Quick Setup menu are entered as a % of span and are
as follows.
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%
ULTRA 4 INSTRUCTION MANUAL
82

Exponential Devices

If the primary measuring device is a simple exponential device, then an exponent value is required. The Ultra 4 will automatically enter the exponent value for the device chosen as detailed in the table below.
EXPONENT TYPE
PMD SHAPE EXAMPLE
EXPONENT (P717)
Suppressed Rectangular Weir (Without end contractions)
1.50, automatically set by the unit.
Cipolletti (Trapezoidal) Weir
1.50, automatically set by the unit.
Venturi Flume
1.50, automatically set by the unit.
Parshall Flume
Automatically calculated according to the throat size.
Leopold Lagco Flume
1.55
V-Notch Weir
2.50
Other
As per manufacturer
Value to be set as required.
Contracted Rectangular Weir (With end contractions)
1.50
83

Point of Measurement

The transducer must be above the maximum head P704 by at least the near blanking distance P107.
For Suppressed/Contracted Rectangular, Trapezoidal and V-notch, weirs, the head is measured upstream at a minimum distance of 3 times maximum head from the weir plate to ensure the surface of the liquid is not affected by turbulence or drawdown. (See DRWG. 1)
In the case of a Venturi flume the point of measurement should be 150 mm upstream from the beginning of the converging section and for a Parshall flume 2/3 the length of the converging section upstream of the throat section. (See DRWG 2 and 3).
3 x Hmax minimum
FLOW (q)
DRWG. 1
DRWG. 2
DRWG. 3
FLOW (q)
FLOW (q)
VENTURI FLUME
PARSHALL FLUME
ULTRA 4 INSTRUCTION MANUAL
84
For a Leopold Lagco flume the head is measured at a point upstream of the beginning of the converging section as detailed in the table below. (See DRWG 4).
FLUME SIZE
POINT OF MEASUREMENT
mm
inches
mm
inches
100 - 305
4 – 12 25
1.0
380
15 32
1.3
455
18 38
1.5
530
21 44
1.8
610
24 51
2.1
760
30 64
2.5
915
36 76
3.0
1065
42 89
3.5
1220
48 102
4.0
1370
54 114
4.5
1520
60 127
5.0
1675
66 140
5.5
1830
72 152
6.0
When any Other device is chosen, please consult the manufacturer of the device for details of where the point of measurement should be located but ensure that it is chosen such that the surface of the liquid is not affected by turbulence or drawdown.
FLOW (q)
THROAT
DIVERGING
CONVERGING
TRANSDUCER MOUNTED MIN. BLANKING DISTANCE (P107) ABOVE MAX. HEAD
POINT OF MEASUREMENT
DRWG. 4
85

Calculations

Absolute

If the flow calculation is to be absolute P702 = 1 the flow will be calculated using the formula (s) as follows:
EXPONENT TYPE
FORMULA
EXPONENT
K FACTOR
Suppressed Rectangular Weir (Without end contractions)
Q = KLh* Where: Q=Flow K=K Factor L=Crest length of weir h=head *=exponent
1.50 Automatically selected by the Ultra 4
Automatically calculated, dependent on measurement, flow and time units chosen.
Cipolletti (Trapezoidal Weir)
Q = KLh* Where: Q=Flow K=K Factor L=Crest length of weir h=head *=exponent
1.50 Automatically selected by the Ultra 4
Automatically calculated, dependent on measurement, flow and time units chosen
Venturi Flume
Q=Kh* Where: Q=Flow K=K Factor h=head *=exponent
1.50 Automatically selected by the Ultra 4
Enter value of K Factor (P718) as required
Parshall Flume
Q=Kh* Where: Q=Flow K=K Factor h=head *=exponent
Automatically calculated, dependent on throat size (P719)
Automatically calculated, dependent on measurement, flow and time units chosen
Leopold Lagco Flume
Q=KD
0.0953hx
Where: Q =Flow K=K factor D=pipe
diameter h=head *=exponent
1.55 Automatically selected by the Ultra 4
Automatically calculated, dependent on measurement, flow and time units chosen
ULTRA 4 INSTRUCTION MANUAL
86
EXPONENT TYPE
FORMULA
EXPONENT
K FACTOR
V-Notch Weir
Q=Kh
x
Where: Q =Flow K=K factor h=head *=exponent
2.50 Automatically selected by the Ultra 4
Automatically calculated, dependent on measurement flow and time units chosen.
Other
Q=Kh*
Enter value as required
Enter value as required
Contracted Rectangular Weir (With end contractions)
Q=K(L-0.2*h)h
x
Where: Q =Flow K=K factor L=crest length of weir
h=head
x
=exponent
1.50 Automatically
selected by the Ultra 4
Automatically calculated, dependent on measurement flow and time units chosen.

Ratiometric

If the flow calculation is to be ratiometric P702 = 2 the flow will be calculated using the formula: q = q
cal
(h/h
cal
)x
Where:
q = flowrate
q
cal
= flowrate at maximum head (705)
h = head
h
cal
= maximum head (P704)
x = exponent (determined as in absolute calculation above)
87

Example 1 ‘V’ Notch Weir

In this example, it is required to calculate the flow through a Simple Exponential Device, which on this occasion is a V-Notch Weir. Ratiometric calculation will be used, to use the customers declared maximum flow, there is no requirement for alarms and the flow rate is to be displayed in litres/second. The totaliser is to record the flow in cubic metres but is not to be displayed during RUN.
The distance from the end of the transducer horn (dB Mach 3) to zero flow (P105) is 1 metre and max head (P704) is 0.4 metres, maximum flow (P705) is known to be 96.5 litres/second.
ULTRA 4 INSTRUCTION MANUAL
88
To program the Ultra 4 for Example 1 V-Notch Weir by using the Quick Setup menu proceed as follows. If required access the Program Mode, key in the passcode 1997 and press ENTER
Using the ‘right’ arrow key, go to the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and press ENTER.
Programming is now complete, and the unit can now be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Ultra 4 will return to Run Mode.
QUESTION
OPTION
PMD Type
1 = Exponent
Exponent
6 = V-Notch
Calculation
2 = Ratiometric
No. of alarms
0 = No alarms
Xducer
1 = dB Mach3
Volume units
1 = Litres
Time units
1 = Per second
Measurement units
1 = metres
Empty Level
1.00 metres
Minimum head
0.00 metres
Maximum head
0.40 metres
Totaliser enable
1 = On
Totaliser (R)
0 = No
Totaliser multiplier
7 = *1
Max flow
96.5
Aux Line
0 = None
89

BS3680 Flumes (P700 = 2)

Point of Measurement

The transducer must be above the maximum head P704 by at least the near blanking distance P107.
For a Rectangular and U-throated flume, the head is measured at 3 to 4
times the maximum head upstream from the beginning of the converging section, to ensure the surface of the liquid is not affected by turbulence.
(See DRWG 6)
3-4 x hmax
DRWG. 6
THROAT LENGTH
DIM C (P712)
DIM A (P710)
APPROACH WIDTH
DIM B (P711)
THROAT WIDTH/DIA.
FLOW (q)
BS3680 FLUME
ULTRA 4 INSTRUCTION MANUAL
90

Rectangular Flume Calculations

Absolute

If the flow calculation is to be absolute P702 = 1 the flow will be calculated using the formula: q = (2/3)
1.5gn0.5
CsCvCdbh
1.5
Where:
q = flowrate gn = gravitational acceleration (nominal value = 980.66 cm/s2)
Cs = shape coefficient (value = 1) Cv = velocity coefficient calculated by Ultra 4 (P721) Cd = discharge coefficient calculated by Ultra 4 (P722) b = throat width P711
h = head

Ratiometric

If the flow calculation is to be ratiometric P702 = 2 the flow will be calculated using the formula: q= q
cal(Cv/Cvcal
)(Cd/C
dcal
)(h/h
cal
)
1.5
Where:
q = flowrate
q
cal
= flowrate at maximum head P705
Cv = velocity coefficient calculated by Ultra 4 (P721)
C
vcal
= velocity coefficient at maximum head
Cd = discharge coefficient calculated by Ultra 4 (P722) C
dcal
= discharge coefficient at maximum head
h = head
h
cal
= maximum head P704
91

U-Throated Flume Calculations

Absolute

If the flow calculation is to be absolute P702 = 1 the flow will be calculated using the formula: q = (2/3)
1.5
g
n
0.5
CuCvCdbh
1.5
Where:
q = flowrate gn = gravitational acceleration, (nominal value = 980.66 cm/s2) h = head
Cu= shape coefficient calculated by Ultra 4 (P724) Cv = velocity coefficient calculated by Ultra 4 (P721) Cd = discharge coefficient calculated by Ultra 4 (P722) b = throat width P711

Ratiometric

If the flow calculation is to be ratiometric P702 = 2 the flow will be calculated using the formula:
q= q
cal(Cv/Cvcal
)(Cd/C
dcal
)(Cu/C
ucal
)(h/h
cal
)
1.5
Where:
q = flowrate
q
cal
= flowrate at maximum head P705
Cv = velocity coefficient calculated by Ultra 4 (P721)
Cv
cal
= velocity coefficient at maximum head
Cd = discharge coefficient calculated by Ultra 4 (P722) Cd
cal
= discharge coefficient at maximum head
Cu = shape coefficient P724 Cu
cal
= shape coefficient at maximum head
h = head h
cal
= maximum head P704
ULTRA 4 INSTRUCTION MANUAL
92

Example 2 BS3680 U-Throated Flume

In this example, it is required to calculate to BS3680 the flow through a U­Throated Flume without any hump. Absolute calculation will be used, and there is a requirement for an alarm to indicate a low flow condition which will be set to relay 1. The flow rate is to be displayed in cubic meters/hour and the totaliser is also to record the flow in cubic metres, the resettable totaliser is to be displayed during RUN.
The distance from the end of the transducer horn (dB Mach 3) to zero flow (P105) is 1 metre and max head (P704) is 0.4 metres, maximum flow (P705) which will be calculated by the Ultra 4 as 725.171 cubic metres/hour.
The dimensions of the flume are as follows:
Approach Channel diameter (Dim “A”) P710 = 0.7 m (2.29 ft) Throat diameter (Dim “B”) P711 = 0.5 m (1.64 ft) Throat length (Dim “C”) P712 = 1.0m (3.28 ft)
To program the Ultra 4 for Example 2 BS3680 U-Throated Flume by using the Quick Setup menu proceed as follows.
93
To program the Ultra 4 for Example 2 BS3680 U-Throated Flume by using the Quick Setup menu proceed as follows. If required access the Program Mode, key in the passcode 1997 and press ENTER. Using the ‘right’ arrow key, go to the Quick Setup menu press ENTER and as prompted, select the relevant option and press ENTER.
QUESTION
OPTION
PMD Type
2 = 3680 Flume
3680 Flumes
3 = U-Throat
Calculation
1 = Absolute
No. of alarms
1 = 1 Alarm
Type alarm 1
2 = Low
Alarm No.1
1 = Set to relay 1
Transducer
8 = dB Mach3
Volume units
2 = Cubic metres
Time Units
4 = Per hour
Measurement units
1 = Metres
Empty level
1.00m
Minimum head
0.00m
Maximum head
0.40m
Totaliser enabled
1 = On
Totaliser multiplier
7 = *1
Approach dia. (Dim A)
0.70m
Throat dia. (Dim B)
0.50m
Throat length (Dim C)
1.00m
Aux Line 2
13 = Tot R
Programming is now complete, and the unit can now be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Ultra 4 will return to Run Mode.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
ULTRA 4 INSTRUCTION MANUAL
94

BS3680 Weirs (P700 = 3)

Point of Measurement

The transducer must be above the maximum head P704 by at least the near blanking distance P107.
For a Rectangular and V-notch weir, the head is measured at a point 4 to 5 times the maximum head upstream from the weir plate, to ensure the surface of the liquid is not affected by turbulence or drawdown. (See DRWG
7)

Rectangular Weir Calculations

Absolute

If the flow calculation is to be absolute P702 = 1 the flow will be calculated using the formula: q = Ce 2/3(2gn)
0.5
beh
e
1.5
Where: q = flowrate Ce = discharge coefficient calculated by Ultra 4 (P723)
gn = gravitational acceleration (nominal value = 980.66 cm/s2) be =effective approach width where b is approach width (Dim “A”) P710 he = effective head
4-5 x hmax minimum
DRWG. 7
BS3680 WEIR
95

Ratiometric

If the flow calculation is to be ratiometric P702 = 2 the flow will be calculated using the formula: q= q
calCe/Cecal(he/hecal
)
1.5
Where: q = flowrate
q
cal
= flowrate at maximum head P705
Ce = discharge coefficient calculated by Ultra 4 (P723)
Ce
cal
= discharge coefficient at maximum head he = effective head he
cal
= effective head at maximum head

V-Notch Weir Calculations

Absolute

If the flow calculation is to be absolute P702 = 1 the flow will be calculated using the formula: q = Ce8/15tan(theta/2) (2gn)
0.5h2.5
Where:
q = flowrate Ce = discharge coefficient calculated by the Ultra 4 (P723) theta = V-notch angle gn = gravitational acceleration (nominal value = 980.66 cm/s2) h = head
The Ultra 4 pre-sets the angle (theta) on selection of the chosen device this angle is 90° for a BS 3680 full 90°V notch weir, 53° 8 minutes in the case of the BS3680 half 90°V notch weir and 28° 4 minutes in the case of the BS3680 quarter 90°V notch.

Ratiometric

If the flow calculation is to be ratiometric P702 = 2 the flow will be calculated using the formula: q = q
calCe
(h)/Ce(h
cal
)(h/h
cal
)
2.5
Where:
q = flowrate
q
cal
= flowrate at maximum head P705
Ce(h) = discharge coefficient for head Ce(h
cal
) = discharge coefficient for maximum head
h = head
h
cal
= maximum head P704
ULTRA 4 INSTRUCTION MANUAL
96

Example 3 BS3680 Rectangular Weir

In this example, it is required to calculate to the flow through a BS3680 Rectangular weir. Absolute calculation will be used, and there is a requirement for an alarm to indicate a high flow condition to be set to relay
3. The flow rate is required to be displayed in litres/minute and the totaliser is to record the flow in cubic metres, the resettable totaliser is to be displayed during RUN.
The distance from the end of the transducer horn to zero flow (P105) is 1 metre and max head (P704) is 0.4 metres, maximum flow (P705).
Approach width (Dim “A”) P710 = 0.5 m (1.64 ft) Crest width (Dim “B”) P711 = 0.3 m (0.98 ft) Crest Height (Dim “C”) P712 = 0.3 m (0.98 ft)
97
To program the Ultra 4 for Example 3 BS3680 Weir by using the Quick Setup menu proceed as follows. If required access the Program Mode, key in the passcode 1997 and press ENTER.
Using the ‘right’ arrow key, go to the Quick Setup menu press ENTER and as prompted, by the questions, select the relevant option and press ENTER.
QUESTION
OPTION
PMD Type
3 = 3680 Weir
3680 Weir
1 = Rectangular
Calculation
1 = Absolute
No. of alarms
1 = 1 Alarm
Type alarm 1
1 = High
Alarm No.1
1 = Set to relay 3
Transducer
8 = dB Mach3
Volume units
1 = Litres
Time Units
2 = Minute
Measurement units
1 = Metres
Empty level
1.00m
Minimum head
0.00m
Maximum head
0.40m
Totaliser enabled
1 = On
Totaliser multiplier
7 = 1000
Approach dia. (Dim A)
0.50m
Throat dia. (Dim B)
0.30m
Throat length (Dim C)
0.30m
Aux Line 2
13 = TotR
ULTRA 4 INSTRUCTION MANUAL
98
Programming is now complete, and the unit can now be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press ENTER, and the Ultra 4 will return to Run Mode.

BS3680 Rectangular Broad Crested Weir

Point of Measurement

The transducer must be above the maximum head P704 by at least the near blanking distance P107.
The head is measured at a point 3 to 4 times the maximum head upstream from the weir crest, to ensure the surface of the liquid is not affected by turbulence or drawdown.
Important Notice
If relay setpoints do not meet the exact requirements of the application,
they can be modified to suit by pressing ENTER when, “For More Options Hit Enter”, is displayed, and entering new values to relay setpoints as
required. Alternatively, the relevant relay setpoint can be accessed either by the main menu system or directly via parameter number and changed as necessary.
99

Rectangular Broad Crested Weir Calculations

Calculations Absolute

If the flow calculation is to be absolute P702 = 1 the flow will be calculated using the formula: q = (2/3)

1.5
Ceb(gh3)
0.5
Where:
q = flowrate Ce = discharge coefficient calculated by Ultra 4 P723 b = approach width P710 g = gravitational acceleration (nominal value = 980.66 cm/s2) h = head

Ratiometric

If the flow calculation is to be ratiometric P702 = 2 the flow will be calculated using the formula: q= q
calCe/Cecal(he/hecal
)
1.5
Where: q = flowrate
q
cal
= flowrate at maximum head P705
Ce = discharge coefficient calculated by Ultra 4 P723
Ce
cal
= discharge coefficient at maximum head he = effective head he
cal
= effective head at maximum head
ULTRA 4 INSTRUCTION MANUAL
100

Special Devices

Point of Measurement

The transducer must be above the maximum head P704 by at least the near blanking distance P107.
In the case of a Palmer Bowlus flume the point of head measurement should be half the value of Dim “A” P710 upstream of the device.
For a H-Flume the head measurement is taken at a point downstream from the flume entrance as detailed in the table below:
Loading...