Pulsar Measurement Pulsar Sludge Finder 2 Blanket Level Control Manual

SludgeFinder 2
Instruction Manual
2
PULSAR MEASUREMENT
3
SludgeFinder 2 (SIXTH EDITION REV 1)
February 2021 Part Number M-920-0-006-1P
COPYRIGHT
© Pulsar Measurement, 2009 -21. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form without the written permission of Pulsar Process Measurement Limited.
WARRANTY AND LIABILITY
Pulsar Measurement guarantee for a period of 2 years from the date of delivery that it will either exchange or repair any part of this product returned to Pulsar Process Measurement Limited if it is found to be defective in material or workmanship, subject to the defect not being due to unfair wear and tear, misuse, modification or alteration, accident, misapplication, or negligence. Note: For a VT10 or ST10 transducer the period of time is 1 year from date of
delivery. DISCLAIMER
Pulsar Measurement neither gives nor implies any process guarantee for this product and shall have no liability in respect of any loss, injury or damage whatsoever arising out of the application or use of any product or circuit described herein.
Every effort has been made to ensure accuracy of this documentation, but Pulsar Measurement cannot be held liable for any errors.
Pulsar Measurement operates a policy of constant development and improvement and reserves the right to amend technical details, as necessary.
The SludgeFinder 2 shown on the cover of this manual is used for illustrative purposes only and may not be representative of the actual SludgeFinder 2 supplied.
CONTACT
For technical support, please contact: Europe: supporteurope@pulsarmeasurement.com
Outside Europe: supportnorthamerica@pulsarmeasurement.com If you have any comments or suggestions about this product, please contact: Europe: europe@pulsarmeasurement.com
Outside Europe: northamerica@pulsarmeasurement.com Pulsar Measurement website: www.pulsarmeasurement.com
United States
11451 Belcher Road South Largo, FL 33773 888-473-9546
Canada
16456 Sixsmith Drive Long Sault, Ont. K0C 1P0 855-300-9151
United Kingdom
Cardinal Building, Enigma Commercial Centre
Sandy’s Road, Malvern
WR14 1JJ 00 44 (0)1684 891371
4
CONTENTS
Chapter 1: Start Here… ........................................................................................................... 8
About this Manual ............................................................................................................... 8
About the SludgeFinder 2................................................................................................. 9
Applications ......................................................................................................................... 10
Functional Description .................................................................................................... 11
Product Specification ....................................................................................................... 12
EU Certificate of Conformity ......................................................................................... 14
Chapter 2 Installation ........................................................................................................... 15
Unpacking ............................................................................................................................ 15
Power Supply Requirements......................................................................................... 15
Location ................................................................................................................................ 16
Dimensions .......................................................................................................................... 17
Wall Mount .......................................................................................................................... 17
VT10 (Sludge) Transducer .............................................................................................. 19
ST10 (Sludge) Transducer .............................................................................................. 20
Terminal connection details .......................................................................................... 21
Terminal Connections ...................................................................................................... 21
dB (Air) Transducer ........................................................................................................... 22
ATEX ....................................................................................................................................... 22
VT & ST (Sludge) Transducer........................................................................................ 24
Wall mount Enclosure ..................................................................................................... 25
Preparation for Operation ............................................................................................. 27
Maintenance ....................................................................................................................... 27
VT & ST (Sludge)Transducer Maintenance. ............................................................ 27
Transducer Installation Options .................................................................................. 30
Transceiver Mounting...................................................................................................... 37
Chapter 3 Pulsar Radio Telemetry System ................................................................... 40
Verifying Communications. ........................................................................................... 44
Radio Telemetry Features. ............................................................................................. 46
Pulsar Non-Integrated Point – Point Radio Telemetry. ...................................... 46
PULSAR MEASUREMENT
5
Receiver and Transmitter Dimensional Details. ..................................................... 47
Gateway and Node wiring details .............................................................................. 48
Analogue and Digital I/O ............................................................................................... 49
Installation Tips .................................................................................................................. 50
Bridge Integrator-Radio Schematic ........................................................................... 53
Specifications ...................................................................................................................... 54
How To Use Your SludgeFinder 2 ................................................................................... 55
Operating the Controls ................................................................................................... 55
Run Mode ............................................................................................................................. 56
Program Mode ................................................................................................................... 59
How to Access Program Mode .................................................................................... 59
Hot Keys ................................................................................................................................ 61
Menu Keys ........................................................................................................................... 62
Numeric Keys ...................................................................................................................... 63
Using the Menu System ................................................................................................. 64
Directly Editing Parameters ........................................................................................... 65
Test Mode ............................................................................................................................ 66
Using the Serial Interface ............................................................................................... 67
Parameter Defaults ........................................................................................................... 69
Chapter 4 Programming Guide ........................................................................................ 70
Measurements needed for Interface monitoring ................................................. 70
Example 1: Primary Settlement Sludge Interface monitoring ......................... 71
Example 2: Level Monitoring with High and Low Alarms on Point 2 ........... 73
Example 3: Using a Single Viper Transducer to Measure 2 Different
Interface Levels. ................................................................................................................. 76
Example 4: Setting the Unit to Alarm on Hi-Floc Levels .................................... 77
High Floc Alarm ................................................................................................................. 77
Chapter 6 Menu System and Parameter Guide ......................................................... 79
Top Level Menu ................................................................................................................. 79
Application Menu .............................................................................................................. 79
SLUDGEFINDER 2 INSTRUCTION MANUAL
6
Relays Menu ........................................................................................................................ 81
Floc Alarm Menu ............................................................................................................... 82
Data Logs Menu ................................................................................................................ 83
Display Menu ...................................................................................................................... 84
mA Output Menu .............................................................................................................. 85
Compensation Menu ....................................................................................................... 86
Stability Menu .................................................................................................................... 86
Echo Processing Menu .................................................................................................... 87
System Menu ...................................................................................................................... 88
Device Comm Menu ........................................................................................................ 90
Test Menu ............................................................................................................................ 91
Chapter 7 Parameter Listing and Description ............................................................ 92
Application Parameters................................................................................................... 92
Global ..................................................................................................................................... 95
Relay Parameters ............................................................................................................... 96
Alarms .................................................................................................................................... 98
Control ................................................................................................................................. 101
Miscellaneous ................................................................................................................... 103
Common Parameters ..................................................................................................... 104
Floc Alarm Parameters .................................................................................................. 105
Service Interval Alarm Parameters............................................................................ 106
Data Log Parameters ..................................................................................................... 106
Display Parameters ......................................................................................................... 107
Failsafe ................................................................................................................................. 108
mA Out 1 / mA Out 2 Parameters ............................................................................ 109
Setpoint ............................................................................................................................... 110
Compensation Parameters .......................................................................................... 112
Offset.................................................................................................................................... 112
Temperature ...................................................................................................................... 112
Stability Parameters ....................................................................................................... 113
Damping ............................................................................................................................. 113
PULSAR MEASUREMENT
7
Filters .................................................................................................................................... 113
Echo Processing Parameters ....................................................................................... 114
Transducer 1 Status ........................................................................................................ 114
Transducer 2 Status ........................................................................................................ 115
System Parameters ......................................................................................................... 116
Passcode ............................................................................................................................. 116
Backup ................................................................................................................................. 116
System Information ........................................................................................................ 117
Date & Time ...................................................................................................................... 118
LED Colour ......................................................................................................................... 118
Watchdog ........................................................................................................................... 119
Daylight Saving Time ..................................................................................................... 120
Device Comm. .................................................................................................................. 124
RS232 Set Up .................................................................................................................... 124
RS 485 Set Up ................................................................................................................... 124
Test Parameters ............................................................................................................... 125
Simulation .......................................................................................................................... 125
Hardware ............................................................................................................................ 126
Chapter 8 Troubleshooting .............................................................................................. 128
Chapter 9 Disposal .............................................................................................................. 129
Notes ........................................................................................................................................ 130
SLUDGEFINDER 2 INSTRUCTION MANUAL
8

CHAPTER 1: START HERE…

Congratulations on your purchase of a Pulsar Sludge Finder 2. This quality system has been developed over many years and represents the latest in high technology ultrasonic sludge monitoring.
It has been designed to give you years of trouble free performance, and a few minutes spent reading this operating manual will ensure that your installation is as simple as possible

About this Manual

It is important that this manual is referred to for correct installation and operation. There are various parts of the manual that offer additional help
or information as shown.
Tips
TIP : Look f or thi s icon t h rougho u t y o ur Pul s a r Mea s ureme n t manual to fin d helpfu l infor m ation a nd an s w ers to f reque n tly as k ed ques t ions.
Additional Information
References
See Also
References to other parts of the manual.
Additional Information
At various parts of the manual, you will find sections like this that explain specific things in more detail.
PULSAR MEASUREMENT
9

About the SludgeFinder 2

The single Sludge Finder 2 unit provides dual point level sensing in liquids and/or air. It is easily installed, with conduit entry on the unit via 5 x 20mm Knockouts and 1 x 16mm knockout.
Outstanding stability, accuracy, and repeatability. Sophisticated algorithms for echo extraction utilizing powerful Digital Signal Processing (DSP) microprocessors.
The system has superior performance based on current leading-edge technology and modern design procedures.
Two independent transducer channels with the option of combining submersible and air transducers.
Two fully adjustable 4-20 mA outputs, six fully programmable SPDT status relays.
RS232 and RS485 communications ports for multiple unit installations. Radio communications for remote 4-20mA Indication (optional).
All these features and more plus the ease of programming, make this instrument the number one choice for interface level measurement in liquids.
SLUDGEFINDER 2 INSTRUCTION MANUAL
10

Applications

The Sludge Finder 2 is designed to monitor the levels of materials in various processes and to regulate the control loops, start and stop motors, and initiate events based on measured process conditions.
Some applications for the units are listed below:
Water & Wastewater Treatment Clarifiers
Water & Wastewater Gravity & DAF Thickeners
Raw Water Clarifiers
Sumps, lagoons, settling ponds.
Industrial Process Thickeners
Salt Brine Tanks
Material Inventory Tanks
Process Thickeners
Dewatering/Hydro Bins
Pyrite Holding/Transfer Tanks
FGD Thickeners
Surge & Settling Tanks
Oil/Water separators
SBR Tanks
PULSAR MEASUREMENT
11

Functional Description

Sludge Finder 2 sends a transmit pulse to the transducer, which then emits a high frequency ultrasonic sound wave perpendicular to the transducer face, the returned echo is received by the Sludge Finder 2. The time taken to receive the echo is measured and the distance from the transducer face to the sludge interface is calculated.
The relays can be programmed to activate alarms, pump starters, or other control equipment. There is an isolated 4-20 mA output for each of two transducer channels that can be connected to a recorder or PLC to monitor the sludge interface independently from that shown on the display. Finally, there is an RS232 port, so that the Sludge Finder 2 can be operated remotely by a PC or other equipment to download/upload parameters or view real time echo traces.
Sludge Finder 2 can be programmed either by the built-in keypad, or by PC via the RS 232 Serial Interface. All parameters are stored in non-volatile memory, so are retained in the event of power interruption. A second backup copy of all parameters can also be retained in the Sludge Finder 2 memory, in case an alternative set of parameters needs to be stored.
Six user definable control relays with individual setpoints and intelligent performance logging software features ensure maximum control versatility.
The Pulsar Sludge Finder 2 ultrasonic sludge detector has been designed to provide maintenance-free fit and forget performance.
SLUDGEFINDER 2 INSTRUCTION MANUAL
12

Product Specification

PHYSICAL
Wall Mount outside Dimensions
235 x 184 x 120mm (9.25 x 7.24 x 4.72)
Weight
Nominal 1 kg (2.2lbs)
Enclosure Material/Description
Polycarbonate, flame resistant to UL94-5V
Cable entry detail
10 cable entry knockouts, 1 x M16 underside, 5 x M20, 4 PG11 at rear.
Transducer Cable Extensions
3-conductor 20AWG screened
dB series (Air) Maximum Separation
3,280 ft (1,000m)
ENVIRONMENTAL
IP Rating (Fascia)
IP65, IP20 when open
Altitude
2000m maximum
Max. & min. temperature (electronics)
-20 ºC to +50 ºC (-4ºF to 122ºF)
Flammable atmosphere approval
Safe area: compatible with approved dB transducers (see transducer spec' sheet)
CE approval
See EU Declaration of Conformity
PERFORMANCE (WITH SLUDGE)
Accuracy
0.25% of the measured range or 1.181" (30 mm) (whichever is greater)
Resolution
0.25% of the measured range or 0.394" (10 mm) (whichever is greater)
Max. Range
32.808ft (10m)
Min. Range
0.984ft (0.3m)
Rate Response
Fully adjustable
OUTPUTS
Analogue Output
2 off Isolated (to 150V floating) output of 4-20 mA or 0-20 mA into 1k (user programmable and adjustable) 0.1% resolution.
Digital Output
Half Duplex RS232
Volt free contacts, number, and rating
6 form "C" (SPDT) rated at 5A at 115V AC
Display
192 x 128 pixel illuminated graphical display Fully programmable display options Integral keypad with menu navigation keys
Radio Modem (optional)
4 – 20mA using wireless exempt frequencies Maximum range 1640ft (500m) line of site
Communication bus (optional)
RS485 Modbus RTU/ASCII or Profibus DPV1 (slave device)
PULSAR MEASUREMENT
13
PROGRAMMING
On-board programming
By integral keypad
PC programming
Via RS232
Programming security
Via passcode (user selectable and adjustable)
Programmed data integrity
Via non-volatile RAM, plus backup
SUPPLY
Power Supply
Universal 100-240V ac 50-60 Hz, dc 22 - 28V 20W maximum power (typically 11W)
Fuse
2A Slow blow
VIPER TRANSDUCER
Sensor body dimensions
78 x 195mm (3.07 x 7.67in)
Sensor Weight
Nominal 1.5kg (3.3lbs)
Sensor body material
Valox 357. Wiper blade – Stainless steel
Transducer cable extensions
2 twisted pair 0.5mm2 with overall screen
Maximum separation
200 m (656ft)
Max and min temperature (electronics)
-20 ºC to +50 ºC (-4ºF to 122ºF)
IP Rating
IP68
Accuracy
0.25% of the measured range or 1.81in (30 mm) (whichever is greater)
Resolution
0.25% of the measured range or 10 mm (whichever is greater)
Max. range
10m (32.8ft)
Min. range
0.3m (0.98ft)
Min sludge density
0.5% concentration
Pulsar Measurement operates a policy of constant development and improvement and reserve the right to amend technical details, as necessary.
SLUDGEFINDER 2 INSTRUCTION MANUAL
14

EU Certificate of Conformity

PULSAR MEASUREMENT
15

CHAPTER 2 INSTALLATION

Unpacking

Power Supply Requirements

Sludge Finder 2 can operate from AC supply or from a DC battery. The AC is supplied via a universal 100-200VAC transformer. The DC is 22-28V. In all cases the Sludge Finder 2 will typically consume 11W of power, with a maximum of 20W.
Important Information
All shipping cartons should be opened carefully. When using a box cutter, do not plunge the blade deeply into the box, as it could potentially cut or scratch equipment components. Carefully remove equipment from each carton, checking it against the packing list before discarding any packing material. If there is any shortage or obvious shipping damage to the equipment, report it immediately to Pulsar Process Measurement Limited.
SLUDGEFINDER 2 INSTRUCTION MANUAL
16

Location

The SludgeFinder 2 must be mounted in a non-hazardous (safe) area, and the transducer fitted in the hazardous area.
When choosing a location to mount the enclosure, bear in mind the following:
Ensure that the SludgeFinder 2 is installed in a “Safe”, non-
hazardous area.
For a clear view of the LCD display, it is recommended that it is
mounted at eye level.
The mounting surface is to be vibration free.
The ambient temperature is between -20°C and 50°C.
There should be no high voltage cables or inverters nearby,
Important Information
All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation.
PULSAR MEASUREMENT
17

Dimensions

Wall Mount

The dimensions of the wall fixing holes are as shown below:
The Sludge Finder 2 should be mounted by drilling three holes suitable for size 8 screws (length to suit your application) and fixing the top screw in place. Hang the unit on this and fix the two remaining screws by removing the terminals access cover to access the pre-drilled holes.
SLUDGEFINDER 2 INSTRUCTION MANUAL
18
The full dimensions of the enclosure are as shown below:
PULSAR MEASUREMENT
19

Cable entry

There are 6 cable gland knockouts on the base of the Sludge Finder 2 (5 x M20, 1 x M16) and 4 on the rear (4 x PG11). Select which ones you wish to take out, and remove them by using a circular cutter, such as a tank cutter. Take care not to damage the circuit board inside whilst undertaking this. Do not use a hammer, as this may cause damage to the enclosure.
It is recommended that you use suitable cable glands to ensure that the ingress rating is maintained.

VT10 (Sludge) Transducer

Important Information
Please note that the VT10 has a 1 year warranty period from the date of delivery from Pulsar, if an issue arises with the item please contact your local Pulsar distributor and return it to Pulsar within its warranty period.
SLUDGEFINDER 2 INSTRUCTION MANUAL
20

ST10 (Sludge) Transducer

1.5” BSP BOTTOM
41 mm
1” BSP
78 mm
25 mm
65 mm
Important Information
Please note that the ST10 has a 1 year warranty period from the date of delivery from Pulsar, if an issue arises with the item please contact your local Pulsar distributor and return it to Pulsar within its warranty period.
PULSAR MEASUREMENT
21

Terminal connection details

The normal strip is as detailed below. There is also a wiring diagram inside the terminal access cover.

Terminal Connections

Power

Sludge Finder 2 can operate from mains AC and automatically from DC or battery backup in the event of power failure or can be operated permanently from DC or batteries.
Wire the transducer to the Sludge Finder 2’s transducer terminals as follows:
VT & ST Sludge Transducers

Transducer 1

TERMINAL CONNECTION DETAILS
*Orange:
Motor
Red:
Power
White: Signal
Black:
0 Volts
Green:
Screen
Terminal No.
37
38
39
40
40

Transducer 2

TERMINAL CONNECTION DETAILS
*Orange:
Motor
Red:
Power
White: Signal
Black:
0 Volts
Green:
Screen
Terminal No.
41
42
43
44
44
*There is no motor connection for the ST10, please connect the other cables for the ST10 as outlined in the tables above.
SLUDGEFINDER 2 INSTRUCTION MANUAL
22

dB (Air) Transducer

Transducer 1

TERMINAL CONNECTION DETAILS
Not
required
Red:
Power
White: Signal
Black:
0 Volts
Green:
Screen
Terminal No.
N/A
38
39
40
40

Transducer 2

TERMINAL CONNECTION DETAILS
Not
required
Red:
Power
White: Signal
Black:
0 Volts
Green:
Screen
Terminal No.
N/A
42
43
44
44
When installing a transducer in a hazardous area use an approved transducer, from the Pulsar dB range, suitable for the proposed application.

ATEX

For EEx m (Zone 1) applications a transducer certified to Sira 02ATEX5104X is used, and must be supplied via a 4000A breaking fuse,
which is fitted as standard to the Sludge Finder 2 controller. For EEx ia (Zone 0) a transducer certified to Sira 02ATEX2103X is used,
which must be connected to the Sludge Finder 2 via an external Zener barrier.
See transducer label for certification details.
Important Information
Please note that if the output of the ultrasonic transducers used with the Sludge Finder 2 are capable of emitting sound pressure levels in excess of 85dBA (above a reference sound pressure level of 20µPA), then the Sludge Finder 2 must be located remote from the transducer such that a sound pressure level of 85dBA is not exceeded when standing at the Sludge Finder 2 in the operator’s position.
PULSAR MEASUREMENT
23

Relay Outputs

The six relays can be programmed for a variety of alarms or process control functions. The relay contacts are all rated at 5A at 115V AC. All connections should be such that the short circuit capacity of the circuits to which they are connected, is limited by fuses rated such that they do not exceed the relay rating.

Current Output

This is an isolated (floating) mA output (to 150 V), of 4 - 20mA or 0 - 20mA, and the load should not exceed 500 .

RS2323 Serial Interface

If required, you can connect to the serial interface to operate your Sludge Finder 2 remotely.
Important Information
Never operate the Sludge Finder 2 with terminal access exposed. An external switch or circuit breaker should be installed near to the Sludge
Finder 2 to allow the supply to be removed during installation and maintenance. In installations where the relay contacts have mains power connected, there should be a means of isolating them from the Sludge Finder 2.
Interconnecting cables must be adequately insulated for IEC 664 Category II installations. Strip back 30 mm of the outer insulation of the cable. Strip 5 mm of insulation from the end of each conductor. Twist all exposed strands of the conductor together. Insert the stripped conductor into the terminal block as far as it will go and tighten the terminal block screw. Ensure that all strands are firmly clamped in the terminal block and that there is no excess bare conductor showing, and no stray strands.
Important Information
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
SLUDGEFINDER 2 INSTRUCTION MANUAL
24

VT & ST (Sludge) Transducer

Locating the Sludge Transducer

Position the transducer at a height within the tank such that it is fully
submerged at all times that measurements are required, typically the face of the transducer should be 150mm below the normal water level.
Liquid temperature compensation will only function correctly if the transducer is submerged at this level or below.
Ensure an unobstructed path between the transducer and the bottom of
the tank. N.B. Rotating sub-surface rakes and scrapers, that pass beneath the transducer, do not interfere with normal operation.
Select a location that minimizes the presence of gas bubbles, high flow
and heavy solid concentration dynamics in the process liquid near or the transducer.
Typical installation in a round clarifier or thickener is 1/3 to 2/3 the
distance from the sidewall to the centre of the tank with transducer mounted from the walkway safety railing.
Typical installation in a rectangular clarifier or thickener is along the
length of the clarifier in the third of the tank nearest the sludge discharge sump.

Installing the Transducer

The transducer housing is designed to accept a 1-inch BSP female
threaded coupler for pipe or conduit. Feed the integral transducer cable through the mounting pipe and tighten by hand until snug. CAUTION: extreme over-tightening may crack the transducer housing.
Position the transducer such that it is 150mm below the water surface
and the mounting pipe is perpendicular to the water surface. Secure the mounting pipe in place with clamps to ensure that it is rigid.
Flexible arm transducers assemblies are available and are required where
there is surface skimming equipment that passes the location of the transducer. Rotate the transducer mounting pipe so that the integral transducer shield contacts the skimmer arm squarely. Ensure that the transducer moves freely away from the passing skimmer equipment.
Optional transducer mounting brackets are available to extend the
mounting pipe away from its connection point at the handrail to provide clearance from obstructions.
PULSAR MEASUREMENT
25
If desired, the transducer cable may be extended up to 200m. Install
transducer cables in grounded metal conduit. Do not run-in cable trays or duct banks with variable frequency drives or other high voltage sources.
Air (dB) transducers should be installed and connected in accordance
with the installation instructions contained in the dB Transducer User Guide.

Wall mount Enclosure

Locating the Sludge Finder 2 unit

The unit may be located inside a building or it may be field-mounted.
Locate the unit so that the maximum cable length to any transducer
does not exceed 200m.
Avoid locating the processor near variable frequency drives or other
high voltage equipment or cables.
Ensure that the Sludge Finder 2 controller is installed in a “Safe”, non-
hazardous, area.
For a clear view of the LCD display it is recommended that it is mounted
at eye level.
Ensure the mounting surface is vibration-free and the ambient
temperature is between -20ºC and 50ºC.

Installing the controller

Mount the unit at a convenient height for viewing the control panel and
displays. Allow sufficient clearance around the unit for the door to swing fully open for instrument service.
Secure to a wall or panel using the mounting holes. Alternatively, attach
to a local handrail using the optional Integrator Mounting Assembly.
SLUDGEFINDER 2 INSTRUCTION MANUAL
26
PULSAR MEASUREMENT
27

Preparation for Operation

Before switching on, check the following:
The Sludge Finder 2 is mounted correctly and is in a ‘safe’ area. The power supply is correctly installed. The relays are connected correctly.

Maintenance

There are no user serviceable parts inside Sludge Finder 2, except the mains fuse. If you experience any problems with the unit, then please contact Pulsar Measurement for advice.
To clean the equipment, wipe with a damp cloth. Do not use any solvents on the enclosure.

VT & ST (Sludge)Transducer Maintenance.

Procedure for the Removal of Transducers

From time to time, it may be necessary to remove the transducer for cleaning or maintenance purposes, the following procedure is to ensure that this is done carefully with regard for the health and safety of the operator involved, and without damage to the transducer.
The transducer mounting bracket (option 1) is designed such that the transducer can be removed without any parts being available to fall into the application. Before attempting to remove the transducer for cleaning or maintenance, the power to the unit should be disconnected.
The correct PPE should be worn to ensure you do not come into direct contact with the wetted parts of the Sludge Finder 2 system, if in doubt contact your site Health and Safety Officer. To remove the transducer, loosen the retaining bolts on the end of the mounting brackets as shown in fig.1 and lift the transducer conduit assembly onto the walkway. The conduit is attached to the mounting assembly plate by means of a security chain so that it cannot be dropped and lost into the application.
The transducer can then be safely inspected for damage or material fouling and can be carefully cleaned with a damp cloth to remove any foreign debris. Care should be taken not to move the wiper by hand as any movement not under the power of the motor may damage the unit.
SLUDGEFINDER 2 INSTRUCTION MANUAL
28
IMPORTANT WARRANTY NOTICE:
THE ONE YEAR TRANSDUCER WARRANTY IS VOID IF THE WIPER BLADE IS ROTATED BY HAND. THIS IS DETRIMENTAL TO THE MOTOR GEAR DRIVE AND WILL DAMAGE THE UNIT.
PULSAR MEASUREMENT
29
The wiper arm on the VT10 will move twice every 20 mins as a default setting, if the face of the transducer is dirty and you are unsure as to whether or not the wiper is cleaning then place the transducer such that the wiper movement will not foul on anything and use the appropriate function key ( ) to force a wipe (see note below).
If it is necessary to replace the transducer, the following procedure should be followed.
Disconnect the transducer wiring from the electronics as shown on page 15 and remove the transducer cable from the electronics enclosure.
The transducer is mounted onto the end of the conduit via its process fitting, this should be carefully unscrewed in an anticlockwise direction. Make sure the transducer is not dropped or knocked as this can damage the unit.
When replacing the transducer care must be taken not to over tighten the unit as this can result in the transducer ‘ringing’. Hand tight is sufficient.
When the transducer is replaced into the application and the power re­applied the unit will re-initialise and after a short period of time depending on the process conditions show the correct blanket reading.
Important Information
The function key will only initiate a wiper sweep on a VT transducer related to the currently viewed point and will only operate in run mode on the “Main” display. The function key will not initiate a wiper sweep if the dual point view is displayed.
SLUDGEFINDER 2 INSTRUCTION MANUAL
30

Transducer Installation Options

1. Stainless steel mounting plate.
PULSAR MEASUREMENT
31
The mounting system shown above including the conduit is made from stainless steel.
The mounting plate is attached to the (normally galvanised) handrail via two hot dipped galvanised U-bolts, the U-bolts are then separated from the mounting plate via robust cast plastic spacers.
This system ensures that there are no problems with dissimilar metal reactions, and the entire mounting system should not suffer from oxidisation/corrosion issues which can cause problems when performing maintenance.
The above system is also available with an optional 2.3m length of Stainless
¾” conduit, with other lengths being available on request. The conduit can
be secured to the mounting bracket or the chain can be supplied welded to the conduit for the customer to attached at a suitable point.
SLUDGEFINDER 2 INSTRUCTION MANUAL
32

Mounting Plate Dimensions

PULSAR MEASUREMENT
33

Mounting Bracket (exploded view)

Note: the two arms holding the hinged conduit retainers are welded to the mounting plate.
SLUDGEFINDER 2 INSTRUCTION MANUAL
34
Part Numbers
Stainless transducer mounting bracket assembly complete with security chain and 2.5m ¾" stainless conduit.
Part Number 9200A0007
Stainless transducer mounting bracket assembly without chain or conduit.
Part Number 9200A0008
Flexible Arm Assembly
Part Number 9200A0001
PULSAR MEASUREMENT
35
2. Budget Mounting Option.
This mounting system has galvanised parts and is designed to be a budget option for transducer mounting.
In the picture shown above the security chain and flexible arm assembly are optional.
SLUDGEFINDER 2 INSTRUCTION MANUAL
36

Mounting option 2, arm assembly

Part Numbers
Budget galvanised transducer mounting bracket complete with
security chain and 2.5m ¾" galvanized conduit.
Part Number 9200A0009
Budget galvanised transducer mounting bracket.
Part Number 9200A0010
Flexible Arm Assembly
Part Number 9200A0001
PULSAR MEASUREMENT
37

Transceiver Mounting

The Sludge Finder 2 transceiver is mounted in an IP65 rated enclosure.
These enclosures are often situated out in the open on the walkways or bridges of settlement tanks and are therefore very exposed to the elements.
We offer a metal enclosure like the one below to ensure that, if required, the unit is not mounted in direct sunlight and is sheltered from any potential exposure to water ingress via precipitation or the application itself.
A steel enclosure with optional mounting plate and brackets is recommended as a suitable enclosure.
Dimensions: W x H x D: 400 mm x 400 mm x 200 mm are adequate. Requirements: General protection of electrical and other equipment against
impact and the ingress of dust and liquids.
Example Spec
• Overall sheet steel construction.
• Epoxy powder coated to RAL7032.
• Earth points on enclosure body & door.
• IP55 protection as standard.
• Polyurethane gasket.
Note: Enclosure mounting equipment supplied and fitted by others to suit local site conditions.
SLUDGEFINDER 2 INSTRUCTION MANUAL
38

Cabinet Mounting

If the Sludge Finder 2 transceiver is mounted into the steel cabinet, Pulsar can offer the necessary metalwork to affix the cabinet to a bridge or walkway as seen below. This includes 2 x slotted galvanised steel rails and 4 x U-bolt fittings (customer specified diameter).
Any other required fittings in addition to the above must be purchased separately by the installer.
PULSAR MEASUREMENT
39
Part Numbers for Cabinet Assembly.
Sludge Finder 2 integrator enclosure complete with chassis plate and mounting bracket.
Part Number 9200A0004
Sludge Finder 2 integrator enclosure complete with 5 x cable glands installed, integrator fixed to the internally mounted chassis plate and mounting brackets.
Part Number 9200A0005
Handrail installation kit for Sludge Finder 2 enclosure. Includes 2 x 2m mounting rails and 4 x U-bolts (diameter to be customer specified)
Part Number 9200A0006
SLUDGEFINDER 2 INSTRUCTION MANUAL
40

CHAPTER 3 PULSAR RADIO TELEMETRY SYSTEM

Some Pulsar units may be fitted with an optional Radio Telemetry System. This system cannot be retro fitted and must be purchased at the time of ordering.
The system consists of a small transmitter board or ‘Node’ that is integrated into the SF2 housing and a receiver or ‘Gateway’ that is placed in a suitable
location. The transmitter is pre-wired into the analogue output terminals and three of the digital outputs as shown below.

TRANSMITTER (node) WIRING

The transmitter unit has two analogue outputs and two digital outputs. Channel 1 is mA OUT 1. Channel 2 is mA OUT 2. Relay 4 is DIG OUT 1. Relays 5 and 6 are DIG OUT 2 The mA output will be set by the user in the Application section of the
parameters to reflect the operational 4-20 mA output span of the instrument. The Relays should be programmed as follows. Relay 5 should be set to be a Loss of Echo alarm, Relay 6 should be set to be
a Wiper fail. These outputs are wired in series to DIG 2 and are used to give a Failure Output. Relay 4 can be programmed as a customer preference for Hi or Lo alarm output.
PULSAR MEASUREMENT
41

RECEIVER (gateway) DX80

The Receiver unit is shown below.
The Receiver unit needs to be supplied with 10-30vdc.
SLUDGEFINDER 2 INSTRUCTION MANUAL
42
The Power Supply and output terminals are shown below.
The Power can be connected to either of the PWR and GND terminals.
10-30VDC
The Digital Output for Relay 4 (Hi or Lo level) is connected to DO1
The Digital Output for Relays 5 & 6 (Wiper Fail and LOE) is connected to DO2
The Analogue Output for Channel 1 is connected to AO1
The Analogue Output for Channel 2 is connected to AO2
PULSAR MEASUREMENT
43
The systems supplied by Pulsar are ‘paired’ and care should be taken to
ensure the right Receiver is installed with the appropriate Transmitter if more than one system is in operation on the same site.
The receiver unit should be pre-set to 11 or greater, the transmitters are set to 1 or greater, so for a transmitter address of, for example, 4 the receiver will be 14 and so on. These are pre-set as the transmitter rotary dial are difficult to access.

Receiver Specifications

Max distance between Transmitter & Receiver with a clear line of sight is 3km.
Frequency. 2.4 GHz Enclosure. Polycarbonate IP67, NEMA 6. Power. 10-30vdc consumption less than 1.4W at 24VDC Temp. (electronics) -20 to +80 C
The left dial represents the units of the device.
The right dial represents the tens of the device.
SLUDGEFINDER 2 INSTRUCTION MANUAL
44

Verifying Communications.

After powering up, verify the device is communicating properly.
When testing the Gateway and Node, ensure all radios and antenna are at least two metres apart or communications may fail.
PULSAR MEASUREMENT
45

Enclosure Dimensions

SLUDGEFINDER 2 INSTRUCTION MANUAL
46

Radio Telemetry Features.

Up to 48 repeaters can be used by upgrading to a ‘MULTIHOP’ receiver
vastly increasing the distance between transmitter and receiver.
Transmissions are always secure due to ‘Frequency Hopping’
technology.
Unlimited pairs can be used in the same location.
Light, strong, compact, and easily fitted enclosure.
Other options are available on request such as RS485 comms and Solar
Powered capability.
3km distance between Transmitter and Receiver, with clear line of sight.

Pulsar Non-Integrated Point – Point Radio Telemetry.

Pulsar also offer a non-integrated Radio Telemetry System that is available to be retro fitted.
The unit offers 2 x 4-20 Analogue Output and 4 x Digital Output re­transmission over 3km line of sight.
PULSAR MEASUREMENT
47

Receiver and Transmitter Dimensional Details.

SLUDGEFINDER 2 INSTRUCTION MANUAL
48

Gateway and Node wiring details

Applying power to the DX70 Radio Devices.

Connect power to the Gateway and Node by connecting 10-30VDC directly to the terminal block as shown below.
1 = 10-30VDC
2 = Ground
PULSAR MEASUREMENT
49

Analogue and Digital I/O

The Pulsar units will be supplied already ‘bound’ and correctly addressed this
means they will only talk to each other and cannot be externally interrogated.
When power is applied the units will show a solid green led and a flashing yellow led that will indicate they are communicating and all is normal, as shown below the speed of the flashing yellow led indicates the strength of the signal between the devices.
TERMINATION
NODE
GATEWAY
TERMINATION
AI1
Analogue Input 1
Analogue Output 1
AO1
AI2
Analogue Input 2
Analogue Output 2
AO2
DI1
Digital Input 1
Digital Output 1
DO1
DI2
Digital Input 2
Digital Output 2
DO2
DI3
Digital Input 3
Digital Output 3
DO3
DI4
Digital Input 4
Digital Output 4
DO4
AI1
Analogue Input 1
Analogue Output 1
AO1
AI2
Analogue Input 2
Analogue Output 2
AO2
SLUDGEFINDER 2 INSTRUCTION MANUAL
50

Installation Tips

It is important to create a clear communication path. Wireless comms can be hindered by radio interference and obstructions in
the path between the radio and receiver. To achieve the best performance carefully consider the installation locations for the Gateways and Nodes, select locations without obstructions in the pathway between them.
Increase the height of the Antenna. Position the antenna vertically for optimal RF communication, if necessary,
change the height of the radio or antenna to improve reception. For outdoor applications mounting the antenna on top of a pole or building may help to achieve line of sight radio link.
Line of sight
No line of sight
Gateway
Node
PULSAR MEASUREMENT
51

Be Aware of Seasonal Changes.

Seasonal changes may affect signal strength, leaves on trees that were absent during a site survey can become a problem later in the year.
Gateway
Gateway
Node
Node
A good signal strength in winter does not always mean you will get the same signal strength the rest of the year.
During spring and summer, leaves may block more of the radio signal.
SLUDGEFINDER 2 INSTRUCTION MANUAL
52

Further Antenna Installation Information.

It is very important that the Radio Antenna is installed correctly for the Radio Communication to be reliable under all conditions.
Pulsar only supply External Antenna; these Antenna are weatherproof if installed correctly.
Pulsar also supply 4m extensions for both the receiver and transmitter end to ensure there is sufficient flexibility for Antenna positioning.
The Antenna always need a CLEAR LINE OF SIGHT to each other to maintain reliable communication, care should be taken if either the transmitter or receiver end is installed on moving machinery. Or, the installation takes place in winter and foliage growth during the summer months could block signal.
Radio signal does not penetrate metalwork or water so special care should be taken avoiding these objects within line of sight.
The 4m length of cable at each end should not be tightly coiled, care should be taken during the installation to ensure, if possible, the extension cable is run in such a way as to make extensive or tight coiling of the remainder unnecessary.
PULSAR MEASUREMENT
53

Bridge Integrator-Radio Schematic

The Integrator on the Bridge should be protected from the elements inside an enclosure, the Antenna extension cable should be installed through a cable gland in the base of the enclosure and out to a suitable position so that the Antenna is above the enclosure.
If the installation position at either end is thought to be susceptible to a lightning strike then a surge suppressor can be installed in place of the cable gland, this installation would require an additional small extension cable from the integrator to the surge suppressor which is a bulkhead fitting. Please contact Pulsar for details.
SLUDGEFINDER 2 INSTRUCTION MANUAL
54

Specifications

Radio Range
2.4 GHz up to 3km.
Radio Transmit Power
18dn conducted, less than or equal to 20dbm EIRP.
Radio Compliance
FCC ID UE300DX80-2400 This device complies with FCC Part 15 Subpart C 15.247 ETSI/EN In accordance with EN 300 328: V1.7.1 (2006-
05). IC 7044A-DX8024
dB series (Air) Maximum Separation
3,280 ft (1,000m)
Spread Spectrum Technology
FSSS (Frequency Hopping Spread Spectrum)
Link Time Out
Adjustable
Power
+10 to 30VDC Consumption less than 1.4W (60ma) at 24vdc
Housing
Polycarbonate housing, nitrile rubber button covers. Mounting M5, Weight 0.26kg
Antenna Connection
External reverse polarity SMA 50 Ohms, max tightening torque 0.45Nm
Interface
Red/Green Power LED, Red/Yellow Signal LED
Wiring Access
½” NPT
Inputs
Discrete I/P OFF condition, PNP Less than 5V, NPN Greater than 2V or Open. Analogue I/P Rating 24ma, Impedance 100 ohms, Sample Rate 1 second or 1%, Resolution 12bit
Outputs
OFF State Leakage Less than 10 micro amps, Max End to End Latency 300 milliseconds. Analogue Outputs. Update Rate 125ms Accuracy 0.1%, Resolution 12bit
Environmental
Rating IEC IP67, NEMA 6. Operating temp -40 to 85ºC. Operating Humidity 95%. Radiated Immunity 10v/m, 80-2700MHz (EN61000-6-2)
Shock and Vibration
IEC 68-2-6 and IEC68-2-7, Shock 30g 11ms half sine wave, 18 shocks, Vibration 0.5mm p-p 10 to 60 Hz.
PULSAR MEASUREMENT
55

HOW TO USE YOUR SLUDGEFINDER 2

Operating the Controls

Display

The graphical display provides four levels of runtime information and a sophisticated, progressive menu system in program mode.
While in Run Mode, the ‘Main’ screen displays the current level reading and its units of measure, with a graphical representation of level for point 1 and/or point 2 along with status information with regards to the Transducer, Echo reception, Wiper status and Fail Safe Mode via the hotkeys. To scroll between run mode screens, use the left and right arrow keys (see diagrams below). To switch between points, use the up and down arrow keys.
The ‘Echo’ screen shows the live echo trace of point 1, point 2 or both on the same screen, with various viewing options described later in this chapter.
The ‘Range’ screen gives details of the empty level, span and blanking for
point 1 or point 2. The ‘Relays’ screen gives live information on relay type and current state, a
graphical representation of on and off setpoints and the current level for point 1 or point 2.
When in Program mode, the display is used to read information on the menu system, parameter details and the values that can be entered.
During Test Mode the display is used to monitor the simulated level with a
screen like the ‘Main’ screen in Run Mode. The current test mode
(auto/manual hard/soft) will also be shown at the bottom of the screen. There are two main operating modes for your Sludge Finder 2, Run Mode
and Program Mode. There is also a Test Mode, used for checking the set­up. All modes are now described.
SLUDGEFINDER 2 INSTRUCTION MANUAL
56

Run Mode

This mode is used once the Sludge Finder 2 has been set up in program mode. It is also the default mode that the unit reverts to when it resumes operation after a power failure.
When Sludge Finder 2 is switched on for the first time, it will display, in metres, a level measurement relating to the default tank dimensions. All relays by default are switched off.
After programming is complete, any relays that are set will operate when the
level reaches the relevant setpoint, and the LED’s will change colour (unless
specifically switched off).

Main

This group of screens provides information on Point 1, Point 2 or an overview of both Points. Use the up and down arrows to scroll between points 1, 2 or both. Below is an example of point 1, this is the screen that will be displayed when the Sludge Finder 2 is switched on for the first time.
Error messages, such as “Wiper Fault”, “Status = LOE” or “Status = Failed” will be displayed on this screen, relating to the point of measure currently being viewed, when a fault condition occurs.
Tank overview showing a graphical representation of the sludge level in percentage of span.
Sludge level in percentage of
Current sludge interface level in measurement units
Clock
Display modes - current mode is highlighted.
PULSAR MEASUREMENT
57

Echo

The echo screen displays the echo data. Below is an annotated example of a typical secondary settlement tank sludge interface.

Range

This screen gives details of the current interface level and the range settings held in the Sludge Finder 2.
P107 = Near Blanking Distance P106 = Span P105 = Empty Distance
Sludge Interface measurement
Gate
Tank Bottom
Distance in measurement units
Wiper Status
Transducer Status
Echo Strength in dB
Sludge Interface indicator
SLUDGEFINDER 2 INSTRUCTION MANUAL
58

Relays

The relays screen indicates the current state of all relay outputs and gives a visual representation of the current interface level and the on and off
setpoints of the individual relays. The level icons, e.g., ” (point 1), represent the level reading of the transducer that the corresponding relay is assigned to (see table below). Relays that do not relate to level will be displayed without the graphical representation of level setpoints but will still show the relay number and status.
All icons show the measurement from the vertical centre of the icon.
LEVEL ICON
DESCRIPTION
Point 1 Level, shown on left hand side of relay diagram.
Point 2 Level, shown on right hand side of relay diagram.
Average level, shown on left hand side of relay diagram.
Sum of levels, shown on left hand side of relay diagram.
Differential level, shown on left hand side of diagram.
Solid region within here, relay is always ACTIVE (ON).
Region between solid area and line signifies relay can be ACTIVE if triggered or INACTIVE if not triggered.
Light region within here, relay
is always INACTIVE (OFF).
Current Level Icon
Relay ON setpoint.
Relay OFF setpoint.
A = Alarm C = Control M = Misc. N = Not set
The numbers represent the relay number.
Relay Status
Current point and value in P104, measurement units shown in P100, mode of operation.
Tank view of the level of the current point of measure.
PULSAR MEASUREMENT
59

Program Mode

This mode is used to set up the Sludge Finder 2 or change information already set. You must use the built-in keypad to access program mode. Alternatively, the unit can be set up with a PC via the RS 232 Serial Interface.
Entering a value for each of the parameters that are relevant to your application provides all of the programming information.

How to Access Program Mode

With Sludge Finder 2, to enter program mode, you simply enter the passcode, via the keypad, followed by the ENTER key. The default passcode is 1997, so you would press the following:

Screenshots of program mode

Important Information
There is a time-out period of 15 minutes when in program mode. After which time the run mode will resumed if you do not press any key.
ENTER
1
9 9 7
Main Menu
Sub Menu
SLUDGEFINDER 2 INSTRUCTION MANUAL
60

Information screen

The information screen can be used to view system details such as Software revision, serial number etc. but can also be used to view a summary of the application settings. To access the information screen, press the button when the Sludge Finder 2 is in run mode. There are 4 pages within the information screen, preceded by the pulsar logo, showing the current page number at the bottom centre of the information screen. The screens will automatically scroll but can also use the left and right arrow keys to toggle between pages an example of page 1 is shown below:
PAGE
DESCRIPTION
1
General information on the system. See example above
2
Information on communications set up: RS232 and RS485 (if available)
3
Information on application set up, such as; transducer type, mode, empty level etc.
4
Information on mA output setup such as; allocation etc.
Sub menu heading
Parameter list
Current value
Units (none in this case)
System : SludgeFinder
Version : 2.2 Boot : Loader 1.2 Date : 12/03/21 Time : 16:45
Customer : Pulsar
Serial : 12345
Site ID : 12345
1/4
PULSAR MEASUREMENT
61

Hot Keys

There are five hot keys on the keypad that can be used to quickly access common parameters for viewing only, while in Run Mode. Pressing the hot key once will initiate or toggle the function assigned to that key, then the Sludge Finder 2 reverts to the Run Mode display, if applicable. In program mode, they have different functions. Information displayed by the function
keys in the “Main” screen will timeout and disappear after 20secs. The
functions are shown below:
HOT KEY
RUN MODE
PROGRAM MODE
Toggle status, echo strength, wiper status and temperature display in the “Main” screen.
Toggle the Gate display in the “Echo” screen.
Clear the current value
Toggle distance, level, and space display in “Main” screen. Toggle the DATEM trace in “Echo” screen.
Not used with Sludge Finder 2
Toggle mA output display in the ‘Main’ screen
Toggle the the Raw echo in the “Echo” screen
Reset parameter to default setting
Not used with Sludge Finder 2
Not used with Sludge Finder 2
Initiates a wiper sweep on the sludge transducer face (VT transducers on single point main display only).
Not used with SludgeFinder 2
Not used with SludgeFinder 2
Toggle negative values
Displays the information screen, timeout 20 seconds.
Enter decimal point.
F1
F2
F3
F4
F5
SLUDGEFINDER 2 INSTRUCTION MANUAL
62

Menu Keys

The menu keys have the following functions:
HOT KEY
FUNCTION
1) Arrow keys for moving left and right around the menu
system and used as a backspace when editing the value of a parameter.
2) Used for changing display modes in Run Mode.
3) Used in test mode to simulate the level moving up and
down (Right = up, Left = down)
1) Used to for moving up and down through the menu
system)
2) Used for changing displayed point of measurement in Run
Mode.
1) Used to confirm each action (for example, select a menu
option or accept a parameter number or value).
2) Used to confirm questions asked by your Sludge Finder 2
such as before restoring factory defaults.
When in ‘program mode’ used to navigate back a level in the
menu system or back to run mode. Cancel a value entered in error. When in ‘run mode’ used to re-initialise the SF2 echo trace if the unit is thought to be reading the incorrect value. This function should only be used by experienced users, see Service Manual for further details.
CANCEL
ENTER
PULSAR MEASUREMENT
63

Numeric Keys

These keys are used for entering numerical information during programming.
1
2
3 4 5
6
7
8
9
0
.
+
-
SLUDGEFINDER 2 INSTRUCTION MANUAL
64
There are two means of editing parameters, directly or using the menu system. Each is now described.

Using the Menu System

The menu system has been designed to make the changing of parameters very simple. There are two levels of menu: Main Menu and Sub Menu.
At the top of the display there is a line of text that displays the main menu items. Pressing the left/right arrow keys scrolls the display between the top­level menu items, (as the example shown below, starting at Application).
*This is only available in units with firmware version 1.1.0 or greater
As you press the cursor keys to scroll left and right between these, you can press ENTER, or the down arrow, at any time, to expand the sub-menu.
Each menu options, along with their sub-menus, is described later in this manual. When you move down into the sub-menu, you can scroll up and down using the arrow keys and then press ENTER to go to the required parameter lists. If there are more menu options or parameters than can be viewed on the display in one go, then a scroll bar will appear on the right hand side of the menu/parameter box. The position of the solid bar within the scroll bar provides a visual aid as to your position in the current menu.
Parameter List
Highlighted parameter
Scroll bar
Scroll bar position
Application
*Floc Alarm
Compensation
Data Logs
Stability
Display
Echo Process
Relays
mA Output
System
Device Comm
Test
PULSAR MEASUREMENT
65
Once you have reached the relevant section, scroll down the parameter list to highlight the parameter you wish to edit, and press ENTER to access the parameter options. When you are at parameter level, the options for that parameter will be displayed on the screen. If the parameter has pre-set options then scroll up or down, with the up/down arrow keys, or press the designated number key (displayed on the left hand side) to highlight the option, then press ENTER to save. If the parameter requires you to enter a value within a particular range, the range options will be displayed with a box to enter the value. Use the numeric keypad to enter the required value following the onscreen prompts and press ENTER to save.
When you have finished, press CANCEL to go back to the previous menu level. When you have reached the top level, press the CANCEL button again, the Sludge Finder 2 will ask for confirmation before allowing you return to run mode. This is done by pressing ENTER at the display prompt.

Directly Editing Parameters

If you already know the number of the parameter, that you wish to look at or edit, simply type the number in at any time while you are in the menu system. Thus, if you are in either the menu or sub-menu level by pressing a numeric key, you can enter the parameter number directly and jump straight there. You cannot type a parameter number whilst at parameter level, only at one of the two menu levels.
When you are at a parameter, the text line rotates automatically displaying the parameter name, number, the applicable units, and the maximum and minimum figure you can enter. The top line shows the value you are setting.
Once you have accessed a parameter, you can either just look at it, or change it.
Once a parameter has been changed, press ENTER and you will see the parameter value changed in the parameter list. If you press CANCEL then you will be returned to the parameter list with no change to the values.
SLUDGEFINDER 2 INSTRUCTION MANUAL
66

Test Mode

Test mode is used to simulate the application and confirm that all parameters and relay setpoints have been entered as expected. During simulation, there is a choice of whether the relays will change state (hard simulation) or not (soft simulation), but the LED’s will always change colour as programmed, and the mA outputs will change in accordance with the chosen mode of operation. If you wish to test the logic of the system that the relays are connected to then select hard simulation, but if you don’t wish to change the relay state, then select a soft simulation.
There are two modes of simulation for each point of measurement, automatic and manual. Automatic simulation will move the level up and down between empty level or the pre-determined Start Level (P983) and the span, if you wish to change the direction of the level movement, this can be done by using the left/right arrow keys. In manual simulation, using the up/down arrow keys will allow you to move the level up and down as required.
To enter simulation, first go to program mode. Using the menu system, select menu item ‘Test’, then sub-menu item ‘Simulation’. Select the point of measure you wish to simulate and press enter to access the simulation options. You can change the value of the parameter to one of the following:
1= Manual soft simulation 2= Automatic soft simulation 3= Manual hard simulation 4= Automatic hard simulation
When in test mode, the display will show the graphical level indicator with the current mode of operation value in measurement units. Also shown will be the relay setpoint indicators, for each relay, with an arrow showing the current level relevant to that relay allocation e.g. if you are simulating point 1 then the level indicator will move up and down along with the arrows next to any relay allocated to point 1. If a relay is allocated to sum, average or differential, then the Sludge Finder 2 will span the relay diagram to the sum, average or differential of point 1 and 2. The level of point 2 (or point 1 if simulating point 2) will always remain at 0.
To return to program mode, press CANCEL and test mode will end.
PULSAR MEASUREMENT
67
When in manual simulation, by default test mode will move the level by
0.1m steps. Altering the increment (P981) will change this value. In automatic mode, the rate at which the level moves up and down is set by
the increment (P981 in metres, the rate (P982) in minutes, which can be changed to make the level move up and down faster. E.g., if increment (P981) is set for 0.1m and rate (P982) is set to 1 min then the level will increase or decrease at a rate of 0.1m/min. To make the simulated level move slower, decrease the value in increment (P981) or increase the value in rate (P982). To make the simulated level move faster, increase the value in increment (P981) or decrease the value in rate (P982).

Using the Serial Interface

The RS232 serial interface is used to communicate between the Sludge Finder 2 and a PC using the optional Sludge Finder PC software and other associated Pulsar software packages. To obtain information such as data logging and view echo traces, upload, download and save parameter files. In addition it can also be used to control or obtain information using a standard PC or other computer base equipment. To do so, the default settings for communications port are as follows: baud rate 19,200, 8 data bits, no parity, 1 stop bit.
The device should be connected as shown in Chapter 2 Installation. To use the device remotely, you need to log on to start, and log off when
finished. When logged on, Sludge Finder 2 will show “Remote” on the display in place of the clock. When logged off, the display will return to normal (clock will be displayed).
All commands should be followed by a carriage return. The unit will respond either OK or a value if the command is accepted, or
NO if the command is not recognised or is not available. To log on, send the command
/ACCESS:pppp where pppp is the passcode (P922). To log off, send the command /ACCESS:OFF To set a parameter, send the command /Pxxx:yy where xxx is the parameter number, and yy is the value you wish to
set it to.
SLUDGEFINDER 2 INSTRUCTION MANUAL
68
Other commands you can use are:
/DISTANCE 1 (shows current distance of point 1)
/DISTANCE 2 (shows current distance of point 2)
/LEVEL 1 (shows current level of point 1l)
/LEVEL (shows current level of point 2)
/TEMP1 (shows current temperature of point 1)
/TEMP2 (shows current temperature of point 2)
/CURRENTOUT1 (shows the mA output value for mA output 1)
/CURRENTOUT2 (shows the mA output value for mA output 2)
Please consult Pulsar Measurement or contact your local Pulsar representative for further details and a full list of available commands.
PULSAR MEASUREMENT
69

Parameter Defaults

When you first switch Sludge Finder 2 on, it will be reading the distance from the face of the transducer to the interface. It will be indicating in metres, as shown on the display and all relays are set OFF.
The date (P931) and time (P932) in Sludge Finder 2 were set at the factory, but may need checking, and amending if, for example the application is in a time zone other than GMT, see relevant unit Parameter listing for full details.
Once you are satisfied with the installation, and Sludge Finder 2 is reading what you would expect in terms of distance from the face of the transducer to the material level, then you can proceed with programming for the intended application. It is sensible to program all of the required parameters at the same time. The system will then be fully set-up.
Once you are satisfied with the installation, and the SludgeFinder 2 is reading what you would expect in terms of distance from the face of the transducer to the material level, then you can proceed with programming, for the intended application. It is sensible to program all of the required parameters at the same time. The system will be then set-up.
Note: The span is automatically calculated from the empty level, so the empty level should be entered first.
Factory Defaults
When first installing the Sludge Finder 2, or subsequently moving or using the unit on a new application, before proceeding to program the unit for its intended application it is recommended that you ensure that all parameters are at their default values by completing a Factory Defaults P930, as described in the parameter guide.
SLUDGEFINDER 2 INSTRUCTION MANUAL
70

CHAPTER 4 PROGRAMMING GUIDE

Measurements needed for Interface monitoring

Mea s ured ta n k dep th a nd Tra n s ducer d epth a r e refe r enced f r om th e sam e point – Top wa t er lev el.
P115 Tank Depth
P116 Transducer
Depth
P107 Near Blanking
P107 Span
PULSAR MEASUREMENT
71

Example 1: Primary Settlement Sludge Interface monitoring

Tank Depth (P115) 2.8m
Span (P106) 2.3m
High alarm off (P214) 1.85m
Transducer Depth (P116) 0.2m
Interface level
High Alarm on (P213) 1.95m
Empty level
Near Blanking (P107) 0.3m
In this example, when the sludge interface level rises to 1.95 m, relay 1 will come on until the level drops to 1.85 m when it will turn off.
The display for point 1 will show the sludge interface level in the tank. The mA output will be representative of sludge interface level where 4mA =
empty level (0%) and 20mA = 2.3m (100%). To program the unit for Example 1 Primary Settlement Sludge Interface
Monitoring, proceed as follows. If required access the Program Mode. Key in the passcode 1997 and press ENTER.
SLUDGEFINDER 2 INSTRUCTION MANUAL
72
Use the arrow keys to scroll to the following menus and parameters and press ENTER to access them. Select the relevant option using the up and down arrows or type in the required value using the keypad and press ENTER to accept.
All other parameters should remain at default values.
If combining the sludge interface monitoring with a tank liquid level monitor then proceed to Example 1b Level Monitoring with Alarms on Point 2 otherwise, programming is now complete and the unit can be returned to the run mode, press CANCEL until Run Mode? Is displayed on the LCD press ENTER, and the Sludge Finder 2 will return to the Run Mode.
MENU
SUB MENU
PARAMETER
VALUE/OPTION
Application
Point 1
Global
Mode P100 Xducer P101 Material P102 Tank Depth P115 Xducer Depth P116 Span P106 Meast Units P104
2 = Level 7 = VT10 2 = Primary
2.8 (metres)
0.2 (metres)
2.3 (metres) 1 = metres
Application
Relay 1
Type P210 Function P211 Ident P212 Setpoint 1 P213 Setpoint 2 P214 Allocation P216
1 = Alarm 1 = Level 2 = High
1.95 (metres)
1.85 (metres) 1 = Xducer 1
PULSAR MEASUREMENT
73

Setting Up Point 2 with as an Ultrasonic Point of Measurement

If it is required that point two is to be set up as an ultrasonic transducer to measure level in air, follow the procedure as per the example below.

Example 2: Level Monitoring with High and Low Alarms on Point 2

A vessel, containing a liquid that has a variation in level that is to be monitored, with a high level alarm set on Relay 1, and low level alarm set on Relay 2. The following method uses an air transducer from the dB range, example shown is a dB6 on channel 2.
In this example, when the level rises to 2.38 m, relay 2 will come on until the level drops to 2.24 m when it will turn off. If the level drops to 0.28 m, then relay 3 will come on until it rises 0.42 m when it will turn off.
The display for point 2 will show the level in the tank. The mA output will be representative of level where 4mA = empty level (0%)
and 20mA = 2.8m (100%).
Empty Distance (P1105), 3.5m
100%. Span (P1106), 2.8m
85%. High alarm on (P223), 8.5 2.38m
80%. High alarm off (P224), 2.24m
0%, Empty level
10%. Low alarm on (P233), 0.28m
15%, Low alarm off (P234), 0.42m
SLUDGEFINDER 2 INSTRUCTION MANUAL
74
To program the unit for Example 2 Level Monitoring with alarms, proceed as follows.
If required access the Program Mode Key in the passcode 1997 and press ENTER Use the arrow keys to scroll to the following menus and parameters and
press ENTER to access them. Select the relevant option using the up and down arrows or type in the required value using the keypad and press ENTER to accept.
All other parameters should remain at default values. Programming is now complete, and the unit can be returned to the run
mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Sludge Finder 2 will return to the Run Mode.
MENU
SUB MENU
PARAMETER
VALUE/OPTION
Application
Point 2
Mode P1100 Xducer P1101 Material P1102 Empty Level P1105 Span P1106
2 = Level 2 = dB6 1 = Liquid
3.5 (metres)
2.8 (metres)
Relays
Relay 2
Type P220 Function P221 Ident P222 Setpoint 1 P223 Setpoint 2 P224 Allocation P226
1 = Alarm 1 = Level 2 = High
2.38 (metres)
2.24 (metres) 2 = Xducer 2
Relay 3
Type P230 Function P231 Ident P232 Setpoint 1 P233 Setpoint 2 P234 Allocation P236
1 = Alarm 1 = Level 2 = High
2.38 (metres)
2.24 (metres) 2 = Xducer 2
mA Output
mA Out 2
Allocation P899
2 = Xducer 2
PULSAR MEASUREMENT
75

Example Echo Screen for Ultrasonic Transducer

Status Indicator
Empty Distance
Indicator
SLUDGEFINDER 2 INSTRUCTION MANUAL
76

Example 3: Using a Single Viper Transducer to Measure 2 Different Interface Levels.

The Pulsar SF2 Integrator can be used to monitor both the Rag or FLOC levels and the Settled Sludge or RAS levels simultaneously using only one Viper Transducer.
This feature gives the user the ability to monitor and control the RAS level application by monitoring the settled sludge, but also prevent damaging FLOC spillage to the local water course by monitoring the less dense Rag levels.
To achieve this, we utilise Point number 2 in addition to Point number 1. Both points will display the same profile, but different service parameters can be applied thus setting Point 1 to monitor the RAS layer and Point 2 the FLOC layer.
It is required to set Point 2 Allocation in the Application menu (P1103) To 0 = Transducer 1.
The above profiles show the unit differentiating between the two echoes. In this instance point one is set to pick the largest echo and point two is set to pick the first echo (see SF2 Service Manual for details).
Each 4-20ma can be independently set to track both interfaces. All relays can be independently set to give control or alarms on both points.
PULSAR MEASUREMENT
77

Example 4: Setting the Unit to Alarm on Hi-Floc Levels

High Floc Alarm

The unit is now able to pick up on high level of floc readings, to do this it reacts to the raw echo trace rather than the processed echo. You are then able to set an alarm that is only reacting to the raw floc levels which will activate if the % of intrusion (P163) is reached between the distances set (in measurement units) in P160 Start distance and P161 End Distance. So if the reading is low and sat near the bottom of the tank the processed echo is low but the raw echo can be high.
The unit will pick up hi levels of floc near the surface which it can only do by looking at the raw trace. The alarm On Delay P164 and Off Delay P165 can be set to prevent passing ‘clouds’ of material in flight from nuisance alarming.
With the introduction of the High Floc Alarm feature, several different parameters and features now need to be included into the manual. Below are the illustrations, parameters and their descriptions which require adding to the new release of manuals due to be compiled indicating how to program a high floc alarm.

Top Level Menu

*This is only available in units with firmware version 1.1.0 or greater.
Compensation
mA Output
Display
Stability
Device Comm
System
Echo Process
Test
Relays
Application
Floc Alarm*
Data Logs
SLUDGEFINDER 2 INSTRUCTION MANUAL
78

Setting up a High Floc alarm:

Note: When setting a High Floc Alarm, it is necessary to access two menu systems the RELAYS menu to set up the relay and the FLOC ALARM menu to set the alarm parameters.
Enter program mode by keying in 1997 and pressing ENTER. Once in program mode you will need to program both a High Floc alarm relay and set up the parameters in the new Floc alarm menu option. Assigning an alarm relay to this new feature to alert you of a high floc presence, also allows you to view on the units trace screen the area box monitored by the Floc alarm parameters. How to set this alarm relay feature is explained in Relay parameters. The parameters required to setup a High Floc alarm are detailed in the Chapter 6 Menu system and parameter guide - Floc Alarm section.
The ‘Intrusion Window’ appears in the top let hand side of the echo profile display when the ‘Gate’ hot key is pressed.
The ‘Raw E c ho’ ( F 3 ) shoul d also b e pres s ed to s e e if t h e Raw E cho prof i le is i n the d isplay i s intr u d ing in to the window .
PULSAR MEASUREMENT
79

CHAPTER 6 MENU SYSTEM AND PARAMETER GUIDE

This section outlines all parameters available in the Sludge Finder 2, as they appear in the menu system.
Shown below is a set of charts to show you how all the various parts can be found using the menu system.
For further details and a full description of all parameters refer to Chapter 7
Parameter Listings and Descriptions.

Top Level Menu

Compensation
mA Output
Display
Stability
Device Comm
System
Echo Process
Test
Relays
Application
Floc Alarm*
Data Logs
SLUDGEFINDER 2 INSTRUCTION MANUAL
80
Application Menu
Global
P104 Measurement Units
Point 1
Point 2
Global
* only available with VT transducers
+
only available with dB transducers
Point 1
P100 Mode
P101 Transducer
P115* Tank Depth
P116* Transducer Depth
P105+ Empty Level
P106 Span
P107 Near Blanking
P108+ Far Blanking
P102 Material
Point 2
P1100 Mode
P1101 Transducer
P1115* Tank Depth
P1116* Transducer Depth
P1105+ Empty Level
P1106 Span
P1107 Near Blanking
P1108+ Far Blanking
P1102 Material
PULSAR MEASUREMENT
81

Relays Menu

Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
* is the number of the relay from 1 to 6
P2*0 Relay Type
P2*1 Relay Function
P2*2 Relay Ident.
P2*3 Relay Setpoint 1
P2*4 Relay Setpoint 2
P2*6 Relay Allocation
Relay *
P2*7 Relay Closures
P2*8 Failsafe Mode
SLUDGEFINDER 2 INSTRUCTION MANUAL
82

Floc Alarm Menu

Point 2
Point 1
P161 End Distance
P160 Start Distance
P162 Level
P163 % of Intrusion
P164 On Delay
P165 Off Delay
Point 1
P1161 End Distance
P1160 Start Distance
P1162 Level
P1163 % of Intrusion
P1164 On Delay
P1165 Off Delay
Point 2
PULSAR MEASUREMENT
83

Data Logs Menu

Point 1
Point 2
Point 1
P580 Min. Temperature
P581 Min. Temp. Date
P582 Min. Temp. Time
P583 Max. Temperature
P584 Max. Temp. Date
P585 Max. Temp. Time
P586 Current Temp.
Point 2
P1580 Min. Temperature
P1581 Min. Temp. Date
P1582 Min. Temp. Time
P1583 Max. Temperature
P1584 Max. Temp. Date
P1585 Max. Temp. Time
P1586 Current Temp.
SLUDGEFINDER 2 INSTRUCTION MANUAL
84

Display Menu

Point 1
Point 2
Point 1
P802 Display Offset
P804 Display Conversion
P808 Failsafe Mode
P809 Failsafe Time
P801 Decimal Places
P800 Display Units
Point 2
P1802 Display Offset
P1804 Display Conv.
P1808 Failsafe Mode
P1809 Failsafe Time
P1801 Decimal Places
P1800 Display Units
PULSAR MEASUREMENT
85

mA Output Menu

mA Out 1
mA Out 2
mA Out 1
P831 mA Mode
P841 mA Allocation
P830 mA Range
P840 mA Fail Mode
P834 mA Low Level
P835 mA High Level
P836 mA Low Limit
P837 mA High Limit
P838 mA Low Trim
P839 mA High Trim
mA Out 2
P891 mA Mode
P899 mA Allocation
P890 mA Range
P898 mA Fail Mode
P892 mA Low Level
P893 mA High Level
P894 mA Low Limit
P895 mA High Limit
P896 mA Low Trim
P897 mA High Trim
SLUDGEFINDER 2 INSTRUCTION MANUAL
86

Compensation Menu

Stability Menu

Point 1
Point 2
Point 1
P851 Measnt. Offset
P852 Temp. Source
P854 Fixed Temp.
P860 Sound Velocity
Point 2
P1851 Measnt. Offset
P1852 Temp. Source
P1854 Fixed Temp.
P1860 Sound Velocity
Point 1
Point 2
* dB transducers only
Point 1
P870 Fill Damping
P871 Empty Damping
P881 Fixed Distance
P882* Process Filter
P883 Gate Expand
Point 2
P1870 Fill Damping
P1871 Empty Damping
P1881 Fixed Distance
P1882* Process Filter
P1883 Gate Expand
PULSAR MEASUREMENT
87

Echo Processing Menu

Point 1
Point 2
* dB transducers only
Point 1
P900 Transducer Status
P901 Echo Confidence
P902 Echo Strength
P903 Average Noise
P904 Peak Noise
P905* Sensitivity
P906* Side Clearance
Point 2
P910 Transducer Status
P911 Echo Confidence
P912 Echo Strength
P913 Average Noise
P914 Peak Noise
P915* Sensitivity
P916* Side Clearance
SLUDGEFINDER 2 INSTRUCTION MANUAL
88

System Menu

Passcode
P921 Enable Code
P922 Passcode
Backup
P925 Parameter Backup
System Info
P926 Software Revision
P927 Hardware Revision
P928 Serial Number
P929 Site Identification
P930 Factory Defaults
Date & Time
P931 Date
P932 Time
P933 Date Format
LED Colour
P935 Off Colour
P936 Alarm Colour
P938 Control Colour
P939 Misc. Colour
Passcode
Daylight Save
Backup
System Info
Date & Time
LED Colour
Watchdog
PULSAR MEASUREMENT
89
Daylight Save
P970 DST Enable
P971 Difference
P972 Start Time
P973 Start Day
P974 Start Week
P975 Start Month
P976 End Time
P977 End Day
P978 End Week
P979 End Month
Watchdog
P940 Number of Starts
P941 Start Date
P942 Start Time
P943 Start Date 1
P944 Start Time 1
P945 Start Date 2
P946 Start Time 2
P947 Start Date 3
P948 Start Time 3
P949 Start Date 4
P950 Start Time 4
P951 Start Date 5
P952 Start Time 5
P953 Start Date 6
P954 Start Time 6
P955 Start Date 7
P956 Start Time 7
P957 Start Date 8
P958 Start Time 8
P959 Start Date 9
P960 Start Time 9
SLUDGEFINDER 2 INSTRUCTION MANUAL
90

Device Comm Menu

RS232 Setup
Modbus
Profibus
Comm. option dependent
RS232 Setup
P061 Comms Baudrate
Optional
Profibus
P132 Device Address
P143 Address Locked
Optional
Modbus
P130 Device Mode
P131 Protocol
P132 Device Address
P133 Device Baud rate
P134 Parity
P135 Stop Bits
P136 Data Format
P137 Delay in ms
PULSAR MEASUREMENT
91

Test Menu

Simulate Pt 1
Hardware
Simulate Pt 2
Setup
Simulate Pt 1
P980 Simulate
Simulate Pt 2
P1980 Simulate
Setup
P981 Increment
P982 Rate
P983 Start Level
Hardware
P990 Self Test
P991 Hardware Test
P992 mA Output Test
P994 Transducer Test
P995 Keypad Test
P996 Relay Test
SLUDGEFINDER 2 INSTRUCTION MANUAL
92

CHAPTER 7 PARAMETER LISTING AND DESCRIPTION

Application Parameters

Point 1 / Point 2

P1-100, P2-1100 Mode of Operation

This parameter sets the mode of operation, when in run mode, and can be set to one of the following:
OPTION
DESCRIPTION
1 = Distance (Default)
Display shows the distance from the transducer face to the surface of the material measured.
2 = Level
Shows how full a vessel is.
3 = Space
Shows how empty a vessel is.
4* = Average Level P1 & P2
Display shows the average level of point 1 & point 2
5* = Differential P1 & P2
Display shows the differential between point 1 & point 2
*If transducer 2 is enabled

P1-101, P2-1101 Xducer (Transducer)

This parameter should be set to the transducer being used with the unit, and can be set to one of the following:
OPTION
DESCRIPTION
0 = None
For point 2 only. Disables point 2 (Default)
1 = dB3
Transducer is a dB3. Range = 0.125 to 3 metres
2 = dB6
Transducer is a dB6. Range = 0.3 to 6 metres
3 = dB10
Transducer is a dB10. Range = 0.3 to 10 metres
4 = dB15
Transducer is a dB15. Range = 0.5 to 15 metres
5 = dB25
Transducer is a dB25. Range = 0.6 to 25 metres
6 = dB40
Transducer is a dB40. Range = 1.2 to 40 metres
7 = VT10 (Default)
Transducer is a VT10. Range = 0.3 to 10 metres
*8 = ST10
Transducer is a ST10. Range = 0.3 to 10 metres
*This option is only available in firmware versions 2.2.0 and greater
PULSAR MEASUREMENT
93

P1-102, P2-102 Material

This parameter should be set to the type of site being monitored for Sludge or the material being monitored with air transducers. The options are:
VT/ST Transducer
OPTION
DESCRIPTION
1 = Industrial
Use for the majority of non-sludge sites
2 = Primary (Default)
Use for primary settlement tanks
3 = Secondary
Use for secondary settlement tanks
4 = SBR
Use for SBR (Sequencing Batch Reactor) tanks
dB Transducers
OPTION
DESCRIPTION
1 = Industrial
Use for the majority of non-sludge sites
2 = Primary (Default)
Use for primary settlement tanks

P1-P105, P2-P1105 Empty Level (dB transducers only)

This parameter is to be set to the maximum distance from the face of a dB transducer to the empty point (bottom of tank), in P104 Measurement Units. This value also affects span, (see important information below), so should be set before span. With sludge transducers, the empty level is automatically calculated from P115 Tank Depth and P116 Transducer Depth.

P1-P106, P2-P1106 Span

This parameter should be set to the maximum distance from the Tank Depth (P115/P1115) or Empty Level (P105/P1105) to the maximum material level. It is automatically set to be equal to the Tank Depth (P115/P1115) or Empty Level (P105/P1105) less the Near Blanking distance (P107/P1107) when you set the tank depth or empty level.
SLUDGEFINDER 2 INSTRUCTION MANUAL
94

P1-107, P2-1107 Near Blanking

This parameter is the distance from the face of the transducer that is not measurable and is pre-set to the minimum value dependant on the Transducer (P101) selected. It should not be set to less than this figure, but can be increased, typically to ignore close in obstructions.
TRANSDUCER
NEAR BLANKING DISTANCE
P101/P1101 = dB3
Default blanking distance = 0.125 metres
P101/P1101 = dB6
Default blanking distance = 0.30 metres
P101/P1101 = dB10
Default blanking distance = 0.30 metres
P101/P1101 = dB15
Default blanking distance = 0.50 metres
P101/P1101 = dB25
Default blanking distance = 0.60 metres
P101/P1101 = dB40
Default blanking distance = 1.20 metres
P101/P1101 = VT10
Default blanking distance = 0.30 metres
*P101/P1101 = ST10
Default blanking distance = 0.30 metres
*This option is only available in firmware versions 2.2.0 and greater.

P1-108, P2-1108 Far Blanking Distance

This is the distance (as a percentage of empty level P105) beyond the empty point that the unit will be able to measure, and by default is pre-set to 20% of the empty level.
If the surface being monitored can extend beyond the Empty Level (P105) then the far blanking distance can be increased to a maximum of 100% of empty level.
This parameter is always entered as a % of empty level.
Important Notice
When changing the Tank Depth (P115) or Empty Distance (P105) you can also recalculate the values for the Span and the Relay Setpoints to take in to account the near blanking (P107) and transducer depth (P116) where applicable, so that they remain at the same percentage values of the empty distance as they were
before they were changed. The question “Recalculate Span?” will be asked, if you
choose yes (enter), then the span will be recalculated, any other answer will leave the span at its original value. You will then be asked if you want to “Recalculate
Setpoints?”, if you choose yes (enter), then all Relay Setpoints will be
recalculated as a percentage of the new empty distance, any other answer will leave the setpoints at their original values.
PULSAR MEASUREMENT
95

P1-115, P2-P1115 Tank Depth

This is the distance from the top of the tank (or the surface of the liquid when full) to the bottom of the tank in P104 Measurement Units. This parameter will only become available when a sludge transducer (prefixed ‘VT’) is selected in P101 Transducer Type.

P1-116, P2-P1116 Transducer Depth

This is the distance from the top of the tank (or the surface of the liquid when full) to the face of the sludge transducer in P104 Measurement Units. This parameter will only become available when a sludge transducer (prefixed ‘VT’) is selected in P101 Transducer Type.

Global

P104 Measurement Units

This parameter sets the units you want to use for programming and display.
OPTION
DESCRIPTION
1 = metres (Default)
All units of measurement are Metres
2 = cm
All units of measurement are Centimetres
3 = mm
All units of measurement are Millimetres
4 = feet
All units of measurement are Feet
5 = inches
All units of measurement are Inches
SLUDGEFINDER 2 INSTRUCTION MANUAL
96

Relay Parameters

All relay related parameters are prefixed with a 2**. The second digit of the three-figure parameter number denotes the relay
number as follows:
21* parameters for Relay 1 22* parameters for Relay 2 23* parameters for Relay 3 24* parameters for Relay 4 25* parameters for Relay 5 26* parameters for Relay 6
The third digit selects specific parameter for the setting of the relays, which can be selected individually and results in the following parameter numbers for each relay:
Relay 1 210 to 218
Relay 2 220 to 228
Relay 3 230 to 238
Relay 4 240 to 248 Relay 5 250 to 258 Relay 6 260 to 268
PULSAR MEASUREMENT
97

P210, 220, 230, 240, 250, 260 - Relay Type

This parameter defines what type each relay should be, see the table below for available options:
OPTION
DESCRIPTION
1 = Alarm
Relay is programmed as an alarm relay, which will de- energise ON, and energise OFF. This will ensure an alarm is raised if the power fails to the unit.
2 = Control
Relay is programmed as a control relay, which will energise ON, and de-energise OFF.
3 = Miscellaneous
Relay is programmed as a miscellaneous relay, which will energise ON, and de-energise OFF.
SLUDGEFINDER 2 INSTRUCTION MANUAL
98

Alarms

P210, 220, 230, 240, 250, 260 = 1 (Alarm) The second parameter for each relay determines the function of the alarm.

P211, 221, 231, 241, 251, 261 – Relay Function

*This is only available in units with firmware version 1.1.0 or greater. **This is only available in units with firmware version 1.1.1 or greater.
The third parameter for each relay determines the alarm ID for the relay you wish to set.

P212, P222, P232, P242, P252, P262 - Relay Alarm ID

When P211, 221, 231, 241, 251, 261 = 3 (Loss of Echo), 4 (Loss of Clock) or 5 (Wiper Fault)
This parameter has no function and will not be displayed.
OPTION
DESCRIPTION
0 = Off (Default)
Relay will not operate.
1 = Level
Alarm is based on the level in the vessel, and the type of level alarm (P212, 222, 232, 233, 243, 253) and two setpoints must be set (P223, 223, 233 & 214, 224, 234, 244, 254). Setpoints are entered in display units or % of span as referenced to empty level.
3 = Temperature
Alarm is based on the temperature, and the type of temperature alarm (P212, 222, 232, 242, 252) and two setpoints must be set (P213, 223, 233 & P214, 224, 234, 244,
254). The temperature used depends on the temperature source selected (P852). Setpoints are entered in oC.
4 = Loss of Echo
Alarm is raised if the Failsafe Timer (P809) expires. No setpoints required.
5 = Loss of Clock
Alarm is raised if the expires. No setpoints required.
*6 = High Floc Alarm
An alarm is raised if the floc level reaches the level of intrusion as set in % intrusion P1-163.
**7 = Service Alarm
An alarm is raised when the unit has reached its service interval (see service manual for details)
PULSAR MEASUREMENT
99
When P211, 221, 231, 241, 251, 261 = 1 (Level) or 2 (Temperature). This parameter has no function and will not be displayed. P211, 221, 231, 241, 251 = 1 (Level), 2 = Rate of Change or 3 (Temp)
This parameter defines which alarm type, or identification, the relay should respond to, as follows:
OPTION
DESCRIPTION
SETPOINTS
1 = General (Default)
Relay goes “ON” when the
value reaches the ON setpoint and goes “OFF” when the value reaches the OFF setpoint.
P213, 223, 233, 243, 253, 263 is ON Setpoint; P214, 224, 234, 244, 254, 264 is OFF Setpoint.
2 = High
Relay goes “ON” when the
value rises to the ON
setpoint and goes “OFF”
when the value lowers to the OFF setpoint.
ON> OFF Relay Setpoints P213, 223, 233, 243, 253, 263 and P214, 224, 234, 244, 254, 264. Setpoints can be set in any order as
the unit ‘knows’ that you
are setting a high level alarm.
3 = HiHi
Same as 2 = High, but different identifier
4 = Low
Relay goes “ON” when the
value lowers to the ON
setpoint and goes “OFF”
when the value rises to the OFF setpoint.
ON<OFF Relay Setpoints P213, 223, 233, 243, 253, 263 and P214, 224, 234, 244, 254, 264. Setpoints can be set in any order as the unit ‘knows’ that you are setting a low-level alarm.
5 = LoLo
Same as 4 = Lo, but different identifier
SLUDGEFINDER 2 INSTRUCTION MANUAL
100
OPTION
DESCRIPTION
SETPOINTS
6 = In bounds
Relay goes “ON” if value is
inside the zone between the two setpoints.
Relay Setpoints, P213, 223, 233, 243, 253 and P214, 224, 234, 244, 254 can be set in any order as
the unit ‘knows’ that you
are setting an inbounds alarm.
7 = Out of bounds
Relay goes “ON” if value is
outside the zone between the two setpoints.
Relay Setpoints P213, 223, 233, 243, 253 and P214, 224, 234, 244, 254 can be set in any order as
the unit ‘knows’ that you
are setting an out of bounds alarm.
ON” and “OFF” points. For a high alarm, the “ON” is set higher than OFF”. For low alarm then “ON” is set lower than OFF”. See the
appropriate alarm ID, table (P212, 222, 232, 242, 252, 262) for further information.
When P211, 221, 231, 241, 251, 261 = 3 (Loss of Echo), 4 (Loss of Clock) or 5 (Wiper Fault)
These parameters have no function and will not be displayed.
P211, 221, 231, 241, 251, 261 = 1 (Level) or 2 (Temperature)

P213, P223, P233, 243, 253, 263 - Relay Setpoint 1

Determines the “ON” or “OFF” point for the alarm according to the ID
selected.

P214, P224, P234, 244, 254, 264 - Relay Setpoint 2

Determines the “ON” or “OFF” point for the alarm according to the ID selected.
Loading...