Pulsar Measurement Flow Monitor Product Manual

Page 1
Flow Monitor
Instruction Manual
Page 2
2
Page 3
3
FLOW MONITOR (THIRD EDITION REV 1)
January 2021 Part Number M-560-A-002-5P
COPYRIGHT
© Pulsar Measurement, 2017 - 21. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form without the written permission of Pulsar Process Measurement Limited.
WARRANTY AND LIABILITY
Pulsar Process Measurement Limited guarantee for a period of 2 years from the date of delivery that it will either exchange or repair any part of this product returned to Pulsar Process Measurement Limited if it is found to be defective in material or workmanship, subject to the defect not being due to unfair wear and tear, misuse, modification or alteration, accident, misapplication, or negligence.
DISCLAIMER
Pulsar Measurement neither gives nor implies any process guarantee for this product and shall have no liability in respect of any loss, injury or damage whatsoever arising out of the application or use of any product or circuit described herein.
Every effort has been made to ensure accuracy of this documentation, but Pulsar Measurement cannot be held liable for any errors.
Pulsar Measurement operates a policy of constant development and improvement and reserves the right to amend technical details, as necessary.
The Flow Monitor shown on the cover of this manual is used for illustrative purposes only and may not be representative of the actual Flow Monitor supplied.
CONTACT
For technical support, please contact: Europe: supporteurope@pulsarmeasurement.com Outside Europe: supportnorthamerica@pulsarmeasurement.com If you have any comments or suggestions about this product, please contact: Europe: europe@pulsarmeasurement.com Outside Europe: northamerica@pulsarmeasurement.com Pulsar Measurement website: www.pulsarmeasurement.com
United States 11451 Belcher Road South Largo, FL 33773 888-473-9546
Canada 16456 Sixsmith Drive Long Sault, Ont. K0C 1P0 855-300-9151
United Kingdom Cardinal Building, Enigma Commercial Centre
Sandy’s Road, Malvern
WR14 1JJ 00 44 (0)1684 891371
Page 4
4
CONTENTS
Chapter 1: Start Here… ........................................................................................................... 7
About this Manual ............................................................................................................... 7
About the Flow Monitor .................................................................................................... 8
Product Specification .......................................................................................................... 9
EU Declaration of Conformity ...................................................................................... 10
Chapter 2 Installation ........................................................................................................... 11
Unpacking ............................................................................................................................ 11
Power Supply Requirements......................................................................................... 11
Location ................................................................................................................................ 11
Dimensions .......................................................................................................................... 12
Terminal Connection Detail .......................................................................................... 14
Terminal Connection Detail .......................................................................................... 15
AC and Fuse Location ...................................................................................................... 16
Preparation for Operation ............................................................................................. 16
Maintenance ....................................................................................................................... 16
Chapter 3 How To Use Your FlowMonitor ................................................................... 17
Operating the Controls ................................................................................................... 18
Hot Keys ................................................................................................................................ 19
Menu Keys ........................................................................................................................... 20
Numeric Keys ...................................................................................................................... 20
Run Mode ............................................................................................................................. 21
LED’s ....................................................................................................................................... 21
Program Mode ................................................................................................................... 22
How to Access Program Mode .................................................................................... 22
Directly Editing Parameters ........................................................................................... 23
Test Mode ............................................................................................................................ 24
Using the RS232 Serial Interface ................................................................................. 25
Parameter Defaults ........................................................................................................... 25
Chapter 4 Parameter Guide ............................................................................................... 26
Menu System Diagrams ................................................................................................. 26
Page 5
5
Application Menu .............................................................................................................. 27
Relays Menu ........................................................................................................................ 28
Display Menu ...................................................................................................................... 29
mA Output Menu .............................................................................................................. 30
Totaliser Menu ................................................................................................................... 30
System Menu ...................................................................................................................... 31
Test Menu ............................................................................................................................ 32
Application Parameters................................................................................................... 33
Operation ............................................................................................................................. 33
Device Comms.................................................................................................................... 35
Relay Parameters ............................................................................................................... 37
Relay Type ............................................................................................................................ 37
Alarms .................................................................................................................................... 38
Control ................................................................................................................................... 41
Totaliser ................................................................................................................................. 42
Common Parameters ....................................................................................................... 42
Display Parameters ........................................................................................................... 43
Options .................................................................................................................................. 43
Failsafe ................................................................................................................................... 44
Auxiliary ................................................................................................................................. 45
mA Output Parameters ................................................................................................... 46
Range ..................................................................................................................................... 46
Operation ............................................................................................................................. 46
Setpoint ................................................................................................................................. 47
Limits ...................................................................................................................................... 47
Trim ......................................................................................................................................... 48
Failsafe ................................................................................................................................... 48
Totaliser Parameters ........................................................................................................ 49
Setup ...................................................................................................................................... 49
Page 6
FLOWMONITOR INSTRUCTION MANUAL
6
Totalisers ............................................................................................................................... 50
Tot. Audit .............................................................................................................................. 50
System Parameters ........................................................................................................... 51
Passcode ............................................................................................................................... 51
System Information .......................................................................................................... 51
Date & Time ........................................................................................................................ 52
Daylight Saving Time ....................................................................................................... 52
Test Parameters ................................................................................................................. 56
Simulation ............................................................................................................................ 56
Hardware .............................................................................................................................. 57
Chapter 5 Troubleshooting ................................................................................................ 58
Chapter 6 Disposal ................................................................................................................ 59
Page 7
7

CHAPTER 1: START HERE…

Congratulations on your purchase of Pulsar’s Flow Monitor system. This quality system has been developed over many years and represents the latest in high technology ultrasonic level measurement and control.
It has been designed to give you years of trouble-free performance, and a few minutes spent reading this operating manual will ensure that your installation is as simple as possible.

About this Manual

It is important that this manual is referred to for correct installation and operation. There are various parts of the manual that offer additional help
or information as shown.
Tips
TIP : L ook f o r this i c o n throu g h out you r Pulsar M easure m e n t manu a l to fin d helpful informa t i on and a nswers t o frequ e n tly aske d questi o n s .
Additional Information
Additional Information
At various parts of the manual, you will find sections like this that explain specific things in more detail.
Page 8
FLOWMONITOR INSTRUCTION MANUAL
8

About the Flow Monitor

The Pulsar Flow Monitor has been designed to provide a simple interface to the Pulsar Flow Pulse Sensor.
Housed in an IP67 enclosure the product is ideally suited to applications where velocity monitoring, reporting or control is required.
The controller is very easy to use and may be quickly and simply setup via the on-board keypad and display.
The Flow Monitor is designed to provide you with highly reliable measurement in a robust and functional package that is easy to use and low in cost.
Page 9
9

Product Specification

PHYSICAL
Wall Mount
Outside dimensions
130 x 150 x 63.5 mm
Weight
Nominal 0.65 kg
Enclosure material/description
ABS base with Polycarbonate lid, flammability rating UL94HB
Cable entry detail
underside fitted with 3 x M20, nylon cable glands suitable for 6 – 12mm cable
ENVIRONMENTAL
IP Rating (Wall)
IP66/67
Max. & min. temperature (electronics)
-20 ºC to +50 ºC
CE Approval
See EU Declaration of Conformity
OUTPUTS
Analogue output
Isolated active output (passive output optional) of 4­20 mA or 0-20 mA into 1K (user programmable and adjustable) 0.1% resolution
Display
2 x 12 alpha numeric
Serial Port
RS232 for programming and data extraction
Volt free contacts, number, and rating
5 form "C" (SPDT) rated at 5A at 115V/240V AC
PROGRAMMING
On-board programming
By integral keypad
Programming security
Via passcode (user selectable and adjustable)
Programmed data integrity
Via non-volatile RAM
SUPPLY
Power Supply
85 – 264V ac 50/60 Hz, DC 22 - 28V 10W maximum power (typically 8W)
Mains Fuse
2A T” 20mm
DC Fuse
Self-resetting Type
Pulsar Measurement Limited operates a policy of constant development and improvement and reserve the right to amend technical details, as necessary.
Page 10
FLOWMONITOR INSTRUCTION MANUAL
10

EU Declaration of Conformity

Page 11
11

CHAPTER 2 INSTALLATION

Unpacking

Power Supply Requirements

The Flow Monitor can operate from AC supply or from a DC battery. The AC is 85 – 264V, 50/60Hz. The DC is 22 - 28V. In all cases the Flow Monitor will typically consume 8W of power, with a maximum of 10W.

Location

All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation.
The Flow Monitor must be mounted in a non-hazardous (safe) Area.
When choosing a location to mount the enclosure, bear in mind the following:
Easy access to the enclosure is maintained.
The mounting surface is vibration-free.
The ambient temperature is between -20ºC and 50ºC.
There should be no high voltage cables or inverters close by.
Important Notice
All shipping cartons should be opened carefully. When using a box cutter, do not plunge the blade deeply into the box, as it could potentially cut or scratch equipment components. Carefully remove equipment from each carton, checking it against the packing list before discarding any packing material. If there is any shortage or obvious shipping damage to the equipment, report it immediately to Pulsar Measurement.
Page 12
FLOWMONITOR INSTRUCTION MANUAL
12

Dimensions

The dimensions of the mounting holes are as shown below:
The Flow Monitor should be mounted by drilling four holes suitable for size 8 screws (length and type to suit your application) And fix all four screws by removing the top cover to access the pre-moulded mounting holes which are located in the base of the enclosure under the lid retaining screws.
Page 13
13
The full dimensions of the enclosure are as shown below.

Cable Entry

There are 3 x M20 cable glands, suitable for 6 – 12mm cables, fitted to the base of the Flow Monitor enclosure.
3 off M20
Glands
130mm (5.12)
63.5mm (2.5)
150mm (5.
91”)
13mm (0.51)
Important Notice
All cable glands should be tightened to the manufacturer’s specifications. The terminal compartment cover screws should be tightened to 0.5Nm Care should be taken not to over tighten the screws.
Page 14
FLOWMONITOR INSTRUCTION MANUAL
14

Terminal Connection Detail

TERMINAL NAME
FLOWMONITOR
TERMINAL
FLOWMPULSE
TERMINAL
0V (GND)
22
1
24V DC
23
2
*RS485 SCR
26
8
RS485 +
24
9
RS485 -
25
10
Cable Screen
3 or 6
Not Connected
*On older versions of the device, the RS485 screen is connected to terminal 21 (not shown on the above diagram).
FLOW MONITOR
FLOW PULSE
SCREEN NOT
CONNECTED
THIS END.
SCREEN
0V
GND
24V PWR
Page 15
15

Terminal Connection Detail

Power

The Flow Monitor can be powered from mains AC or from a DC source/battery and where a backup DC power source is connected it will automatically take over in the event of AC power failure; DC will automatically power the unit. When AC returns it will switch back.

FlowPulse Sensor

The FlowPulse sensor should be installed and connected, in accordance with the FlowPulse manual.
Wire the FlowPulse sensor to the Flow Monitor sensor terminals, as on the previous page.

Relay Outputs

The two relays can be programmed to a variety of alarm & control functions. The relay contacts are all rated at 2A at 240V AC. All connections should be such that the short circuit capacity of the circuit to which they are connected, is limited by fuses rated so that they do not exceed the relay rating.

Current Output

This is an isolated active mA output of 4 - 20mA or 0 - 20mA, with an option of a passive mA output. The load should not exceed 1K.

RS485 termination switch

By default, this is switched off, to enable RS485 termination both switches need to be switched to the ON position.
Important Notice
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
Page 16
FLOWMONITOR INSTRUCTION MANUAL
16

AC and Fuse Location

AC mains power fuse is located, on bottom board to the left and above of the power input terminals, as previously illustrated in the Terminal Connections Detail drawing.

Preparation for Operation

Before switching on, check the following:
The Flow Monitor is mounted correctly and is in a ‘safe’ area.
The power supply is correctly installed.
The relays are connected correctly.

Maintenance

There are no user serviceable parts inside your Flow Monitor, except the mains power fuse. If you experience any problems with the unit, then please contact your local Pulsar Measurement distributor for advice.
To clean the equipment, wipe with a damp cloth. Do not use any solvents on the enclosure.
Important Notice
If the equipment is installed or used in a manner not specified in this manual, then the protection provided by the equipment may be impaired.
Page 17
17

CHAPTER 3 HOW TO USE YOUR FLOWMONITOR

Your Flow Monitor can be programmed directly via the integral keypad.
Page 18
FLOWMONITOR INSTRUCTION MANUAL
18

Operating the Controls

Display

Whilst in the Run Mode it will display the current flow or velocity reading and its units of measurement, along with the mA output and status messages with regards to the communication status and Fail Safe Mode.
When in Program mode, the display is used to read information on the menu system, the parameter number and parameter details and values, which can be entered.
During Test Mode the display is used to monitor the simulated flow or velocity and mA output.
1) Main Display, 12-digit alpha numeric display:
Run Mode: current measurement displayed, dependent on measurement unit's chosen, and value of Hot Key function selected. Program Mode: displays parameter number and values entered for parameters. Test Mode: displays simulated flow or velocity.
2) Auxiliary Display, scrolling 12-digit alpha numeric display
Run Mode: displays units, totaliser or status messages on communications, detail of Hot Key function selected. Program Mode: displays Menu and Sub Menu headings, parameter details and options.
0.53 Litres/sec
1
2
Page 19
19

Hot Keys

There are five hot keys on the keypad, which can be used to quickly access common parameters for viewing only, while in Run Mode. Pressing the hot key once will display the first parameter, then repeated pressing will display the others, then the Flow Monitor reverts to Run Mode. In program mode, they have different functions, the functions are shown below.
HOT KEY
RUN MODE
PROGRAM MODE
System totaliser and resettable totaliser
Not used with the Flow Monitor
Confidence level and signal strength
Not used with FlowCERT
Not used with Flow Monitor
Reset parameter to default setting
Instantaneous mA output
Not used with Flow Monitor
Displays flow and velocity readings
Not used with Flow Monitor
Not used with Flow Monitor
Takes you to the last parameter edited when you first enter program mode.
Shows details of function type, firmware revision and serial number
Enter decimal point.
mA
n
Page 20
FLOWMONITOR INSTRUCTION MANUAL
20

Menu Keys

The menu keys have the following functions:
Hot Key
function
1) Arrow keys for moving left and right around the menu
system.
2) Used in test mode to simulate the level moving up and
down.
Used to confirm each action (e.g. select a menu option or answer a question asked by the Flow Monitor) or when entering a parameter value.
Used to navigate up a level in the menu system, and back to run mode.
Used to cancel a value entered in error.

Numeric Keys

These keys are used for entering numerical information during programming.
CANCEL
ENTER
1
2
3 4 5
6
7
8 9 0
.
+
-
Page 21
21
There are two main operating modes for your Flow Monitor, Run Mode and Program Mode. There is also a Test Mode, used for checking the set-up. All modes are now described.

Run Mode

This mode is used once the Flow Monitor has been set up in program mode. It is also the default mode that the unit reverts to when it resumes operation after a power failure.
When the Flow Monitor is switched on for the first time, it will attempt to initiate the FlowPulse sensor and will display a message similar to “Update….” and follow by parameter number. All relays by default are switched off and once the FlowPulse is initialised, the display will show the current flow or velocity and the measurement unit.
After programming is complete, any relays that are set will operate when the measurement reaches the relevant setpoint.

LED’s

There are two LED’s that can be seen through the lid of the Flow Monitor enclosure, which will indicate the operational status of the relays whilst in
RUN mode, as follows:
LED 1
LED 2
RUN MODE
Off
Off
Relays are in their OFF state
Constant On
Off
Relay 1 is in its ON state
Off
Constant On
Relay 2 is in its OFF state
Flash
Off
No sensor is detected
Off
Flash
System error (clock or EEPROM error)
Important Notice
If the FlowPulse sensor is not detected, the Flow Monitor will automatically retry to connect to it.
Page 22
FLOWMONITOR INSTRUCTION MANUAL
22

Program Mode

This mode is used to set up the Flow Monitor or change information already set. You must use either the on-board keypad (standard) or alternatively the unit can be set up with a Handheld Calibrator (optional), which must be connected to the Flow Monitor via the RS 232 Serial Interface.
Entering a value for each of the parameters that are relevant to your application provides all the programming information.

How to Access Program Mode

To enter program mode, you simply enter the passcode, via the keypad, followed by the ENTER key. The default passcode is 1997, so you would press the following:
There are two means of editing parameters, directly or using the menu system. Each is now described.

Using the Menu System

The menu system has been designed to make the changing of parameters very simple. There are two levels of menu: Main Menu and Sub Menu.
On the display there is a line of text that shows the menu system. Pressing the arrow keys scrolls the display between the top-level menu items, (as shown below, starting at Quick Setup).
ENTER
1
9 9 7
Important Notice
There is a time-out period of 15 minutes when in program mode, after which time run mode will be resumed if you do not press any keys.
Application
Relays
Display
System
Test
mA Output
Totaliser
Page 23
23
As you press the cursor keys to scroll left and right between these, you can press ENTER at any time to select it and take you to the sub-menu. Each of these options, along with their sub-menus is described in Chapter 5, Parameter Guide. When you move down into the sub-menu, you can scroll round using the arrow keys, press ENTER to go to the required section of parameters.
Once you have reached the relevant section, scroll through the parameters, and enter the necessary information. To enter the information, use the numeric keys and press ENTER and you will see the message “Saved!”. If you press CANCEL, then no change will be made, and the message Unchanged!!” will be displayed.
When you have finished, press CANCEL to go back to the previous level. When you have reached the top level, then the Flow Monitor will ask for confirmation before allowing you to go back into run mode. This is done by pressing ENTER at the display prompt.

Directly Editing Parameters

If you already know the number of the parameter, that you wish to look at or edit, simply type the number in at any time while you are in the menu system. Thus, if you are in either the menu or sub-menu level by pressing a numeric key, you can enter the parameter number directly and jump straight there. You cannot type a parameter number whilst at parameter level, only at one of the two menu levels.
When you are at a parameter, the text line rotates automatically displaying the parameter name, number, the applicable units and the maximum and minimum figure you can enter. The top line shows the value you are setting.
Once you have accessed a parameter, you can either just look at it, or change it.
Once a parameter has been changed, press ENTER and you will see the
message “Saved!”. If you press CANCEL, then no change will be made, and the message “Unchanged!!” will be displayed.
TIP: You can jump straight to the last parameter you edited, by pressing the +/- key when you first enter program mode.
Page 24
FLOWMONITOR INSTRUCTION MANUAL
24

Test Mode

Test mode is used to simulate the application and confirm that all parameters and relay setpoints have been entered as expected. During simulation, there is a choice of whether the relays will change state (hard
simulation) or not (soft simulation), but the LED’s will always change state to
indicate that the relay setpoints have been activated, and the mA output will change. If you wish to test the logic of the system that the relays are
connected to then select hard simulation, but if you do not want to change the relay state, then select a soft simulation.
There are two simulation modes, automatic and manual. Automatic simulation will move the velocity up and down between minimum velocity and maximum velocity, whereas manual simulation will allow you to move the velocity up and down using the arrow keys.
To enter simulation, first go to program mode. Then, using the menu system, select menu item ‘Test’ then sub-menu item ‘Simulation’. Simply change the value of the parameter P980 to one of the following:
1 = Manual soft simulation 2 = Automatic soft simulation 3 = Manual hard simulation 4 = Automatic hard simulation
To return to program mode, press CANCEL and test mode will end. When in manual simulation, by default test mode will move the flow or
velocity by 0.25 steps. Altering the increment (P981) will change this value. In automatic mode, the rate at which the velocity moves up and down is set
by the increment (P981), and the rate (P982) in minutes, which can be changed to make the flow or velocity move up and down faster. E.g. if increment (P981) is set for 0.25 and rate (P982) is set to 1 min then the flow or velocity will increase or decrease at a rate of 0.25/min. To make the simulated flow or velocity move slower, decrease the value in increment (P981) or increase the value in rate (P982). To make the simulated flow or velocity move faster, increase the value in increment (P981) or decrease the value in rate (P982).
Page 25
25

Using the RS232 Serial Interface

The RS232 serial interface is used to program the Flow Monitor and obtain information using a PC or other computer equipment. To do so, the settings for control are as follows: baud rate 19200, 8 data bits, no parity, 1 stop.
The device should be connected to the RS232 Interface via the RJ11 connector as shown in Chapter 2 Installation.

Parameter Defaults

Factory Defaults

The date (P931) and time (P932) in the Flow Monitor were set at the factory, but may need checking or amending if, for example the application is in a time zone other than GMT, see Chapter 5 Parameter Guide for full details.
Once you are satisfied with the installation, you can proceed with programming for the intended application. It is sensible to program all of the required parameters at the same time. The system will be then set-up.
Important Notice
When first installing the Flow Monitor, or subsequently moving or using the unit on a new application, before proceeding to program the unit for its intended application it is recommended that you ensure that all parameters are at their default values by completing a Factory Default (P930).
Page 26
FLOWMONITOR INSTRUCTION MANUAL
26

CHAPTER 4 PARAMETER GUIDE

This chapter describes all of the parameters in your Flow Monitor, in the order they appear in the menu system.

Menu System Diagrams

Shown below is a set of charts to show you how all the various parts can be found using the menu system.

Top Level Menu

Application
Relays
Display
System
Test
mA Output
Totaliser
Page 27
27

Application Menu

P102
Mag Thresh
P105
Averaging
P108
Cal factor
P110
Pipe ID
P111
Noise Adapt
P113
Step Resp
P104
Damping
P115
Step Thresh
P141
Protocol
P143
Device Baud
P144
Parity
P145
Stop Bits
P146
Format
P147
Tx Delay
P148
Poll Int.
P142
Device Addr.
Operation
Device
Comms
P120
Min Cut Off
P121
Step Limit
P128
TrackThrAdd
P134
Density
Page 28
FLOWMONITOR INSTRUCTION MANUAL
28

Relays Menu

Relay 1
Relay 2
P210
R1 Type
P220
R2 Type
P211
R1 Function
P212
R1 I/D
P213
R1 Setpoint 1
P214
R1 Setpoint 2
P217
R1 Closures
P218
R1 Failsafe
P221
R2 Function
P222
R2 I/D
P223
R2 Setpoint 1
P224
R2 Setpoint 2
P227
R2 Closures
P228
R2 Failsafe
Page 29
29

Display Menu

Options
P800
Display Source
Failsafe
P808
Fail Mode
P809
Fail Time
P801
Dec.Places
P803
Volume Unit
P802
Meas.Unit
P804
Time Unit
P805
Display Offset
P806
Displ Converter
Auxiliary
P815
Aux Source
Page 30
FLOWMONITOR INSTRUCTION MANUAL
30

mA Output Menu

Totaliser Menu

Setup
P822
Tot Enable
Totaliser
P820
System Tot
Tot.Audit
P460
Tot.Date 1
P823
Tot.Decimal
P824
Tot.Mult
P825
Tot.LogTime
P821
Reset Tot.
P461
Totaliser 1
P478
Tot.Date 10
P479
Totaliser 10
P480
Clear Logs?
Range
P830
mA Range
Fail Safe
P840
Fail Mode
Setpoints
P834
Low Value
P835
High Value
Limits
P836
Low Limit
P837
High Limit
Trim
P838
Low Trim
P839
High Trim
Operation
P831
mA Mode
Page 31
31

System Menu

P926
Software Rev
P927
Hardware Rev
P931 Date
P932 Time
P970
DST Enable
P971
DST Difference
Pass Code
P921
Enable Code
P922
Passcode
Sys. Info
Date & Time
Daylight Save
P928
Serial No.
P929
Site Ident
P930
Factory Def.
P933
Date Format
P972
DST Start Time
P973
Start Day
P974
Start Week
P975
Start Month
P976
DST End Time
P977
End Day
P978
End Week
P979
End Month
Page 32
FLOWMONITOR INSTRUCTION MANUAL
32

Test Menu

Simulation
P980
Simulate
P981
Increment
P982 Rate
Hardware
P991
Hard Test
P992
mA Out Test
P993
Relay Test
P983
Test Max
P984
Test Min
Page 33
33
Parameter Listing
This section describes all of the parameters. Any parameter can be reset to
its default, by pressing the hot key, whilst in program mode.

Application Parameters

Operation

P102 Mag Threshold

This parameter sets the sensitivity of FlowPulse sensor. The Mag Threshold value sets the required level of signal above the minimum signal before the FlowPulse decides it is seeing flow. The default is set at 1600 which means that the FlowPulse must see a signal strength of at least 16 above the minimum signal before it decides there is flow. Default = 1600

P104 Damping

This parameter sets the damping of the FlowPulse unit. The value of the damping sets the amount of flow readings it uses to create an average flow. The default is set to 24, meaning the average of 24 readings will be used as the flow value. Default = 24

P105 Averaging

This is the number of averaging to perform on the reading – this is independent of the damping process.
Reducing this will increase flow sampling rate at the expense of measurement stability. Default = 6

P108 Cal Factor

This parameter sets the calibration factor for the FlowPulse unit in percentage. The FlowPulse is designed to give a repeatable flow value. However, if the value being read by the FlowPulse does not meet the flow value that is expected the Cal Factor can be used to modify the output. Default = 100%
Page 34
FLOWMONITOR INSTRUCTION MANUAL
34

P110 Pipe Diameter

This parameter sets the internal pipe diameter of the pipe that the FlowPulse is connected to. Default = 0.1 metre

P111 Noise Adapt Threshold

This parameter defines the difference between the minimum value of the trace and the normal floor before a trace is considered to have a raised noise floor due to noise.
Default = 800

P113 Step Response

The step response allows Flow Pulse to temporarily bypass damping and track any sudden change in flow commonly encountered during the beginning and end of a pumping cycles.
OPTION
DESCRIPTION
0 = Off
No Effect
1 = On (Default)
Step Response is enabled

P115 StepResThres

The Step Response Threshold is the change in flow required for the normal damping to be bypassed. The range of the step response threshold is: Min = 22, Max = 426 Default = 60
426 relates to the ‘Flow High’ value. The higher the step response threshold, the larger the jump in flow needs to
be before damping is skipped.

P120 Minimum Flow Cut-off

This parameter multiplies the units of flow by 23 on the horizontal axis of the flow trace. E.g. if the parameter is set to 2300, then the corresponding flow index would be 100. The Flow Pulse via the Flow Monitor will not report any flow unless the flow indicator exceeds 100 on the flow index. Default = 740
Page 35
35

P121 Step Limit

This parameter sets the limit on any sudden change in the flow reading between measurements, even while damping is being bypassed by step response.

P128 TrackThrAdd

This is only activated when noise floor is raised, such that the noise floor is more than P111 away from the normal floor without flow. This causes the flow to be tracked at a lower flow index so that compensation can be applied. Min = 20, Max = 2000 Default = 400

P134 Particle Density

This parameter is used to set the type of material being measured in the pipe that the FlowPulse is attached to.
OPTION
DESCRIPTION
0 = Very Low
Material has very low particle density
1 = Low
Material has low particle density
2 = Medium (Default)
Material has medium particle density
3 = High
Material has high particle density
4 = Very High
Material has very high particle density

Device Comms

P141 Protocol

This parameter determines the communication protocol that the processor uses to initialise the FlowPulse sensor.
OPTION
DESCRIPTION
0 = Modbus RTU (Default)
Modbus RTU with hexadecimal data
1 = Modbus ASCII
Modbus ASCII with ASCII data
Page 36
FLOWMONITOR INSTRUCTION MANUAL
36

P146 Extended Format

This parameter determines the data format that the processor uses to communicate with the FlowPulse sensor.
OPTION
DESCRIPTION
0 = Unsigned Integer (Default)
Unsigned Integer data
1 = Signed Integer
Signed Integer data
2 = Float Motorola Format
Motorola floating point format
3 = Float IEEE Format
IEEE 754 floating point format

P147 Tx Delay

This parameter determines the transmission delay that the processor uses to communicate with the FlowPulse sensor.
Default = 5ms

P148 Poll Interval

This parameter determines the polling interval that the processor uses to exchange data with the FlowPulse sensor.
Default = 1.5 seconds
Page 37
37

Relay Parameters

All relay related parameters are prefixed with a 2**. The second digit of the three figure parameter number denotes the relay
number as follows: 21* parameters for Relay 1
22* parameters for Relay 2
The third digit selects specific parameters for the setting up of the relays, which can be selected individually and results in the following parameter numbers for each relay.
Relay 1 210 to 218
Relay 2 220 to 228

Relay Type

P210, P220 - Relay Type

This parameter defines what type each relay should be, see the table below or available options.
OPTION
DESCRIPTION
0 = Not In Use (Default)
Relay not in use programmed.
1 = Alarm
Relay is programmed as an alarm relay, which will de-energise ON, and energise OFF. This will ensure an alarm is raised if the power fails to the unit.
2 = Control
Relay is programmed as a control relay, which will energise ON, and de-energise OFF.
3 = Totaliser
Relay is programmed as a totaliser relay, which will energise ON, and de-energise OFF as pulsing relay
Page 38
FLOWMONITOR INSTRUCTION MANUAL
38

Alarms

P210, P220 =1 (Alarm)

The second parameter for each relay determines the function of the alarm.

P211, P221 - Relay Function

This parameter defines what function the alarm will respond to as follows.
OPTION
DESCRIPTION
0 = Off (Default)
Relay will not operate.
1 = Flow
Alarm is based on the flow rate and the type of flow alarm (P212, 222) and two setpoints must be set (P213, 223 & P214, 224). Setpoints are entered in Display Units
2 = Velocity
Alarm is based on the velocity, and the type of velocity alarm (P212, 222) and two setpoints must be set (P213, 223 & P214, 224).
3 = Loss of Echo
Alarm is raised if the Failsafe Timer (P809) expires. No setpoints are required.
4 = Loss of Clock
Alarm is raised if the real time clock fails. No setpoints are required.
Note that the loss of echo and loss of clock will also be shown on the display as “NO SENSOR” and “LOST CLOCK” respectively.
The third parameter for each relay determines the alarm ID for the relay you wish to set.

P212, 222 - Relay Alarm ID

When P211, P221 = 3 (Loss of Echo) or 4 (Loss of Clock)
This parameter has no function and will not be displayed
When P211, P221 = 1 or 2
This parameter defines which alarm type, the relay should respond to, as follows:
Page 39
39
OPTION
DESCRIPTION
SETPOINTS
1 = General (Default)
Relay goes “ON” when the
value reaches the ON
setpoint and goes “OFF”
when the value reaches the OFF setpoint.
P213, 223 is ON Setpoint. P214, 224 is OFF Setpoint
2 = High
Relay goes “ON” when the
value rises to the ON
setpoint and goes “OFF”
when the value lowers to the OFF setpoint.
ON > OFF Relay Setpoints P213, 223
and P214, 224 Setpoints, can be set in any order as
the unit ‘knows’ that you
are setting a high-level alarm.
3 = Hi-Hi
Same as 2 = High, but different identifier.
4 = Low
Relay goes “ON” when the
value lowers to the ON setpoint and goes “OFF” when the value rises to the OFF setpoint.
ON < OFF Relay Setpoints P213, 223 and P214, 224. Setpoints, can be set in any order as the unit
‘knows’ that you are
setting a low level alarm.
5 = LoLo
Same as 4 = Low, but different identifier.
6 = In bounds
Relay goes “ON” if value is
inside the zone between the two setpoints.
Relay Setpoints, P213, 223 and P214, 224 can be set in any order as the unit
‘knows’ that you are
setting an inbounds alarm.
7 = Out of bounds
Relay goes “ON” if value is outside the zone between the two setpoints.
Relay Setpoints P213, 223 and P214, 224 can be set in any order as the unit
‘knows’ that you are
setting an out of bounds alarm.
Page 40
FLOWMONITOR INSTRUCTION MANUAL
40
The fourth parameter and the fifth parameter for each relay set the Alarm ON” and “OFF” points. For a high alarm, the “ON” is set higher than “OFF”. For low alarm then “ON” is set lower than “OFF”. See the appropriate alarm
ID, table (P212, 222) for further information. When P211, P221 = 3 (Loss of Echo) or 4 (Loss of Clock)
This parameter has no function and will not be displayed.
When P211, P221 = 1 or 2

P213, P223 - Relay Setpoint 1

Determines the “ON” or “OFF” point for the alarm according to the ID selected.

P214, P224 - Relay Setpoint 2

Determines the “ON” or “OFF” point for the alarm according to the ID selected.
Important Notice
Setpoints are entered in values according to the function selected. Flow/Velocity - entered in Display Units. See the appropriate alarm function, table (P211, 221, 231) for further
information.
Page 41
41

Control

P210, P220 = 2 (Control)

When a relay is being set up as a control relay, the second parameter that will be displayed in the menu determines its function.

P211, P221 - Relay Function,

This function is used, where it is required to energise the relay to switch a device, such as a pump, ON and de-energise the relay to switch the device
OFF.
OPTION
DESCRIPTION
0 = Off
Relay is always de-energised
1 = Flow
Relay will energise ON” as set in Relay
Setpoint 1 (P213, 223). And turns “OFF”, de­energises, as set in Relay Setpoint 2 (P214,
224).
2 = Velocity
Relay will energise ON” as set in Relay
Setpoint 1 (P213, 223). And turns “OFF”, de­energises, as set in Relay Setpoint 2 (P214,
224).
The fourth parameter, and fifth parameter, are set to determine the switch
points, “ON” and “OFF” for the relay. See control function, table (P211, 221,
231) for further information.

P213, P223 - Relay Setpoint 1

This parameter determines the “ON” point for the control relay. Relay Setpoints are entered in values of Measurement Units (P802).

P214, P224 - Relay Setpoint 2

This parameter determines the “OFF” point for the control relay. Relay Setpoints are entered in values of Measurement Units (P802).
Important Notice
A control relay is started and stopped at the “ON” and “OFF” setpoints. To control down (reduce level) then set “ON” higher than “OFF”. To control up (increase level) then set “ON” lower than “OFF”. For relay 1 “ON” is P213, “OFF” is P214 and for relay 2 “ON” is P223, “OFF” is P224s
Page 42
FLOWMONITOR INSTRUCTION MANUAL
42

Totaliser

P210, P220 = 3 (Totaliser)

When a relay is set up as a totaliser relay, the second and third parameters that will be displayed in the menu determine the frequency and duration of the relay pulse.

P213, P223 - Relay Setpoint 1

The factor by which the on board totaliser (P820) should be multiplied by to provide a relay closure, giving the frequency of the pulse. Default = 0.00

P214, P224 - Relay Setpoint 2

The time in seconds to set the duration of the relay pulse. Default = 0.00 secs.

Common Parameters

P217, P227 - Relay Closures

This parameter displays the number of times the relay has activated since the relay has been in use. It can be reset with any value.

P218, P228 - Relay Fail Safe

The unit has a general fail-safe parameter P808. However, this can be overridden so that each individual relay has its own independent fail safe mode.
This parameter determines what the relay will do in the event of the Failsafe
Time (P809) expiring.
OPTION
DESCRIPTION
0 = Default
Relay assumes system default mode P808
1 = Hold
Relay remains in its current state
2 = De-energise
Relay will De-energise
3 = Energise
Relay will Energise
Page 43
43

Display Parameters

Options

P800 Display Source

This parameter determines whether the Flow Monitor uses the Flow or the Velocity.
OPTION
DESCRIPTION
1 = Flow (Default)
Display shows flow readings
2 = Velocity
Display shows velocity readings

P801 Decimal Places

This parameter determines the number of decimal places on the reading during run mode. Minimum = 0 (No decimal places), Maximum 3 = (3 decimal Places). Default = 2 (2 decimal Places)

P802 Measurement Unit

This parameter determines the measurement units showed on the reading during run mode.
OPTION
DESCRIPTION
1 = metres (Default)
Measurement in metres
2 = cm
Measurement in centimetres
3 = mm
Measurement in millimetres
4 = feet
Measurement in feet
5 = inch
Measurement in inches
Page 44
FLOWMONITOR INSTRUCTION MANUAL
44

P803 Volume Unit

The value of this parameter determines volume unit of flow readings.
OPTION
DESCRIPTION
1 = litres (Default)
Display volume in litres
2 = cubic metre
Display volume in cubic metres
3 = cubic feet
Display volume in cubic feet
4 = UK gallons
Display volume in UK gallons
5 = US gallons
Display volume in US gallons
6 = MUSG
Display volume in million US gallons

P804 Time Unit

The value of this parameter determines the time unit of flow and velocity readings.

P805 Display Offset

The reading is added by the value of this parameter before being displayed.
Default = 0

P806 Display Conversion

The reading is multiplied by the value of this parameter before being displayed.
Default = 1.0

Failsafe

P808 Fail-safe Mode

By default, if a fail-safe condition occurs, then the display and the output are held at their last known values until a valid reading is obtained. If required, you can change this so that the unit goes to high (max flow/velocity, P683), or low (min flow/velocity, P682) as follows:
Important Notice
In the event of a fail-safe condition occurring, the display and Output can be configured to fail to a condition which is independent of each other. To set independent Output Failsafe see P840.
Page 45
45

P809 Fail-safe Time

In the event of a fail-safe condition the failsafe timer determines the time before fail-safe mode is activated. Default = 2min
If the timer activates, the unit goes into fail-safe as determined by P808 (Display) and P840 (Output). When this happens, you will see the message Failed Safe!” on the display, along with a message explaining why (lost comm. or comm. error, for example).
When a valid measurement is obtained then the display and output will be restored, and the timer is reset.

Auxiliary

P815 Aux Source

Determine the display on the secondary line of screen
OPTION
DESCRIPTION
0 = Units (Default)
Display the units of the main display
1 = Flow
Display flow readings
2 = Velocity
Display velocity readings
3 = Totaliser
Display resettable totaliser
Page 46
FLOWMONITOR INSTRUCTION MANUAL
46

mA Output Parameters

Range

P830 Output Range

This parameter determines the range of the mA output, from the following.
OPTION
DESCRIPTION
0 = Off
Output disabled
1 = 0 to 20mA
Output directly proportional to the output mode (P831), so if the reading is 0% the output is 0 mA. If the reading is 100% the output is 20 mA.
2 = 4 to 20mA (Default)
output directly proportional to the output mode (P831), so if the reading is 0% the output is 4 mA. If the reading is 100% the output is 20 mA.
3 = 20 to 0mA
output inversely proportional to the output mode (P831), so if the reading is 0% the output is 20 mA. If the reading is 100% the output is 0 mA.
4 = 20 to 4mA
output inversely proportional to the output mode (P831), so if the reading is 0% the output is 20 mA. If the reading is 100% the output is 4 mA

Operation

P831 Output Mode

This parameter determines the output mode of the mA output, from the following.
OPTION
DESCRIPTION
0 = Default (Default)
mA output follows P800 (Display Source)
1 = Flow
mA output according to flow reading
2 = Velocity
mA output according to velocity reading
Page 47
47

Setpoint

By default, the mA Output will represent the 0% (0 or 4mA dependant on (P830) Output Range) and 100% of the operational span (20mA), but you may wish to have the output represent a section of the operational span. For example, the application has an operational span of 6 m/s but output is to represent 0m/s (0 or 4mA dependant on (P830) Output Range) to a level of 5 m/s (20mA). If so P834 (Low Setpoint) should be set to 0.00 m/s and P835 (High Setpoint) should be set to 5 m/s.

P834 Output Low Level

This parameter sets the measurement value at which the low mA output will occur (0 or 4mA dependant on (P830) Output Range)
Default = 0 l/s

P835 Output High Level

This parameter sets the measurement value at which the high mA output will occur (20mA).
Default = 6000 l/s

Limits

P836 Output Low Limit

This parameter sets the lowest level that the mA output will drop to, the default is 0mA, but you can override this if the device you connect to cannot for example accept less than 2mA, yet you want to use the 0-20mA range.
Default = 0.00mA

P837 Output High Limit

This parameter sets the highest level that the mA output will rise to, the default is 20 mA, but you can override this if the device you connect to cannot for example accept more than 18 mA, yet you want to use the 0-20 mA range. Default = 20.00mA
Page 48
FLOWMONITOR INSTRUCTION MANUAL
48

Trim

P838 Output Low Trim

If the device you are connected to is not calibrated, and not showing the correct low value (reading), then you can trim it using this parameter. You can either type in the offset directly or use the arrow keys to move the output up and down until you get the expected result (reading) on the device that is connected.

P839 Output High Trim

If the device you are connected to is not calibrated, and not showing the correct high value (reading), then you can trim it using this parameter. You can either type in the offset directly or use the arrow keys to move the output up and down until you get the expected result (reading) on the device that is connected.

Failsafe

P840 Output Fail-safe Mode

This parameter determines what happens to the output in the event of the unit going into fail-safe mode. The default is to do the same as the system fail-safe (P808), but this can be overridden to force the output to an independent fail-safe mode as follows:
OPTION
DESCRIPTION
0 =Default
Output will fail as per P808
1 = Hold
Output will retain its last known value
2 = Low
Output will fail to its low condition.
3 = High
Output will fail to its high condition (20mA maximum)
4 = Very Low
Output will fall to its lowest or fault condition of 2mA for 4-20 range or 0mA for 0-20 range.
5 = Very High
Output will fail to its highest or fault condition of greater than 20mA (22mA maximum)
Page 49
49
Totaliser Parameters Setup

P822 Totaliser Enable

This parameter determines if the totaliser is enabled or not, options are:
OPTION
DESCRIPTION
0 = No (Default)
Totaliser is disabled
1 = Yes
Totaliser in enabled

P823 Totaliser Decimal

This parameter determines the number of decimal places in the totaliser
during run mode. It can be set between 1 and 3. Default = 2

P824 Totaliser Multiplier

Use this parameter if the totaliser increments by to large or small amount, enter the factor by which the actual flow rate is multiplied by before incrementing the totaliser. E.g. if flowrate is being calculated and displayed in litres/second and it is desired to increment the totaliser in cubic metres select 7 = *1000. When viewing, the totaliser display will state, “Units are: L*1000”, and the totaliser will be incremented every 1000 litres
OPTION
DESCRIPTION
1 = 1/1000
Totaliser will increment every 1/1000th units of flow
2 = 1/100
Totaliser will increment every 1/100th units of flow
3 = 1/10
Totaliser will increment every 1/10th units of flow
4 = *1 (Default)
Totaliser will increment every 1 units of flow
5 = *10
Totaliser will increment every 10 units of flow
6 = *100
Totaliser will increment every 100 units of flow
7 = *1,000
Totaliser will increment every 1000 units of flow
8 = *10,000
Totaliser will increment every 10,000 units of flow
9 = *100,000
Totaliser will increment every 100,000 units of flow
10 = *1,000,000
Totaliser will increment every 1,000,000 units of flow
11 = 1/10,000
Totaliser will increment every 1,000,000 units of flow
12 = 1/100,000
Totaliser will increment every 1/100,000 units of flow
13 = 1/1,000,000
Totaliser will increment every 1/1,000,000 units of flow
Page 50
FLOWMONITOR INSTRUCTION MANUAL
50

P825 Totaliser Log Time

This parameter sets the time at which the totalisers are stored in non-volatile memories.
Default = 00:00

Totalisers

P820 System Totaliser

Displays the current value of the, non-resettable totaliser. During run mode
this totaliser can be viewed via the “Totaliser” hot key. Unlike the resettable
totaliser this totaliser cannot be reset whilst in run mode, it can however be reset whilst in program mode by accessing P820 Totaliser and entering zero.

P821 Resettable Totaliser

Displays the current value of the, resettable totaliser. This totaliser can be allocated to appear, during run mode, on the auxiliary display line (P815) or alternatively via the “Totaliser” hot key.

Tot. Audit

P460 to P479 Totaliser Audits

Parameters P460-P479 show the date and total flow for the last ten days, the first on the list are the most recent and last ones are the oldest. When all ten total audits are full the oldest is pushed out and all totals increment
through to allow the new days total to be registered in the first day’s total
audit parameter allocation.

P480 Clear Logs

This parameter enables all of the Total Audits (P460 - P479) to be cleared to factory default values.
Page 51
51

System Parameters

Passcode

P921 Enable Code

Enables the passcode (P922), which means the passcode must be entered to go into program mode. If disabled (set to 0), then no passcode is required, and ENTER is used to enter program mode. Default = 1 (Enabled)

P922 Passcode

This is the passcode that must be used to enter program mode. The default is 1997, but this can be changed to another value from 0 to 9999.

System Information

The following three parameters do not affect how the unit performs, but details contained within them may be required, by Pulsar, when making technical enquiries.

P926 Software Revision

This parameter will show the current software revision

P927 Hardware Revision

This parameter will show details of the current hardware revision

P928 Serial Number

This parameter will show the serial number of the unit.

P929 Site Identification

This parameter allows you to give each unit an individual reference number, for identification purposes. You can set any number between 1 and 99999.

P930 Factory Defaults

This parameter resets all parameter values to the original Factory Set values that were installed when the unit was tested before despatch to you.
To reset parameters, enter 1 (Yes), and press ENTER, then you will see a message “Entr if sure”, you should press ENTER again. If you press any other key at this point, the parameters will not be reset, and you will see a message confirming this.
Once you have done this, program the unit, to the desired application.
Page 52
FLOWMONITOR INSTRUCTION MANUAL
52

Date & Time

P931 Date

This parameter shows the current date, in the format as set by P933 (Date Format) and can be reset if required.

P932 Time

This parameter shows the current time and can be reset if required, in the format HH: MM (24-hour format). This is set initially at the factory for UK time.

P933 Date Format

This parameter allows you to alter the format that the date is displayed to your choice of DD: MM: YY, MM: DD: YY or YY: MM: DD. The default is DD: MM: YY.

Daylight Saving Time

P970 DST Enable

When Enabled (set to 1) the internal clock will be automatically adjusted to compensate for the difference between standard time and Daylight Saving Time.
OPTION
DESCRIPTION
0 = No
DST is disabled
1 = Yes (Default)
DST in enabled

P971 DST Difference

This parameter sets the time difference between standard time and Daylight Saving Time. The time difference is entered in HH: MM.
Default = 01:00

P972 DST Start Time

This parameter is used to set the time of day at which Daylight Saving Time will start, the time is entered in the format HH: MM (24-hour format).
Default = 02:00
Page 53
53

P973 Start Day

Use this parameter to enter the day of the week (P974) that Daylight Saving Time is to start.
OPTION
DESCRIPTION
2 = Monday
DST will start on a Monday
3 = Tuesday
DST will start on a Tuesday
4 = Wednesday
DST will start on a Wednesday
5 = Thursday
DST will start on a Thursday
6 = Friday
DST will start on a Friday
7 = Saturday
DST will start on a Saturday
8 = Sunday (Default)
DST will start on a Sunday

P974 Start Week

This parameter will determine the week of the month (P975) in which Daylight Saving Time is to start.
OPTION
DESCRIPTION
1 = Week 1
DST will start on day (P973) in the first week (P974) of the month (P975).
2 = Week 2
DST will start on day (P973) in the second week (P974) of the month (P975).
3 = Week 3
DST will start on day (P973) in the third week (P974) of the month (P975).
4 = Week 4
DST will start on day (P973) in the fourth week (P974) of the month (P975).
5 = Last (Default)
DST will start on day (P973) in the last week (P974) of the month (P975).
Page 54
FLOWMONITOR INSTRUCTION MANUAL
54

P975 Start Month

This parameter is used to select the month in which Daylight Saving Time is to start.
OPTION
DESCRIPTION
1 = January
DST will start during the month of January
2 = February
DST will start during the month of February
3 = March (Default)
DST will start during the month of March
4 = April
DST will start during the month of April
5 = May
DST will start during the month of May
6 = June
DST will start during the month of June
7 = July
DST will start during the month of July
8 = August
DST will start during the month of August
9 = September
DST will start during the month of September
10 = October
DST will start during the month of October
11 = November
DST will start during the month of November
12 = December
DST will start during the month of December

P976 DST End Time

This parameter is used to set the time of day at which Daylight Saving Time will end, the time is entered in the format HH: MM (24-hour format).
Default = 02:00

P977 End Day

Use this parameter to enter the day of the week (P978) that Daylight Saving Time is to end.
OPTION
DESCRIPTION
2 = Monday
DST will start on a Monday
3 = Tuesday
DST will start on a Tuesday
4 = Wednesday
DST will start on a Wednesday
5 = Thursday
DST will start on a Thursday
6 = Friday
DST will start on a Friday
7 = Saturday
DST will start on a Saturday
8 = Sunday (Default)
DST will start on a Sunday
Page 55
55

P978 End Week

This parameter will determine the week of the month (P975) in which Daylight Saving Time is to end.
OPTION
DESCRIPTION
1 = Week 1
DST will end on day (P973) in the first week (P974) of the month (P975).
2 = Week 2
DST will end on day (P973) in the second week (P974) of the month (P975).
3 = Week 3
DST will end on day (P973) in the third week (P974) of the month (P975).
4 = Week 4
DST will end on day (P973) in the fourth week (P974) of the month (P975).
5 = Last (Default)
DST will end on day (P973) in the last week (P974) of the month (P975).

P979 End Month

This parameter is used to select the month in which Daylight Saving Time is to end.
OPTION
DESCRIPTION
1 = January
DST will start during the month of January
2 = February
DST will start during the month of February
3 = March
DST will start during the month of March
4 = April
DST will start during the month of April
5 = May
DST will start during the month of May
6 = June
DST will start during the month of June
7 = July
DST will start during the month of July
8 = August
DST will start during the month of August
9 = September
DST will start during the month of September
10 = October (Default)
DST will start during the month of October
11 = November
DST will start during the month of November
12 = December
DST will start during the month of December
Page 56
FLOWMONITOR INSTRUCTION MANUAL
56
Test Parameters Simulation

P980 Simulate

Test mode is used to simulate the application and confirm that all parameters and relay setpoints have been entered as expected. During simulation, there is a choice of whether the relays will change state (hard simulation) or not (soft simulation), but the LED’s will always switch according to how the relays have been programmed, and the output will change accordingly. If you want to test the logic of the system that the
relays are connected to then select a hard simulation, but if you don’t want
to change the relay state, then select a soft simulation. There are two simulation modes, automatic and manual. Automatic
simulation will move the velocity up and down between minimum and maximum velocity and activate the relay and/or corresponding LED at the programmed setpoints, if you wish to change the direction of the velocity movement at any time this can be done by using the arrow keys. In manual simulation, using the arrow keys will allow you to move the velocity up and down as required. The choices for you to enter are as follows.
1. Manual soft simulation
2. Automatic soft simulation
3. Manual hard simulation
4. Automatic hard simulation
To return to program mode, press CANCEL and test mode will end.

P981 Increment

By default, simulation mode will move by 0.25 steps in manual simulation and by 0.25/min in automatic simulation. Altering the increment can change this value.

P982 Rate

In automatic mode, the rate at which the measurement will move up and down is determined by the Increment (P981) and the time, Rate (P982) which can be changed as required. To increase the rate at which the measurement moves increase the Increment (P981) or decrease the Rate
(P982). To decrease the rate at which the measurement moves decrease the Increment (P981) or increase the Rate (P982).
Page 57
57

P983 Test Max

This parameter determines the maximum of the simulated measurement values.
Default = 1000

P984 Test Min

This parameter determines the minimum of the simulated measurement values.
Default = 0

Hardware

P991 Hard Test

When this parameter is selected, the unit will test the following in turn:
LED’s. Watch them change colour as shown on the display and
press ENTER if they operate as shown.
Relays. Press a numeric key, corresponding to the number of the
relay you wish to test, and the relay will change state each time the key is pressed. If you press any other key, other than a valid relay number, then the test will end.
Segments. All the segments on the LCD are lit up so you can see if
they all work. Press ENTER to end the test.
Keys. You should press each key to confirm it works, with a counter
showing how many more keys remain un-pressed. Be sure to press the CANCEL key last as this will show if all keys were pressed or not. If they were not, then an error message is displayed.

P992 Output Test

This parameter will allow you to force a specified current on to the output to test any equipment that it is connected to. The figure you enter will be generated by the output.

P993 Relay Test

Press a numeric key corresponding to the number of the relay you wish to test, and the relay will change state each time the key is pressed. If you press any other key, other than a valid relay number, then the test will end.
Page 58
FLOWMONITOR INSTRUCTION MANUAL
58

CHAPTER 5 TROUBLESHOOTING

This section describes many common symptoms, with suggestions as to what to do. If the issue persists, please contact your local Pulsar distributor.
SYMPTOM
WHAT TO DO
“No Sensor” message displayed.
Check power supply. Check wiring to FlowPulse sensor.
“P102 Fail” message is displayed
Check that the correct Device Address (Modbus ID) for the FlowPulse has been entered into P142 of the Flow Monitor. This can be checked by connecting the FlowPulse to FlowPulse PC to check the ID set on the sensor.
Current velocity reads zero, but you know there is flow movement.
Ensure FlowPulse sensor is mounted correctly and in accordance with chapter 2.
LED’s change colour at relevant
relay switch points but relays do not change state.
Check supply to unit and ensure voltage selector set to correct position.
Page 59
59

CHAPTER 6 DISPOSAL

Incorrect disposal can cause adverse effects to the environment. Dispose of the device components and packaging material in accordance
with regional environmental regulations including regulations for electrical \ electronic products.
Transducers
Remove power, disconnect the Transducer, cut off the electrical cable and dispose of cable and Transducer in accordance with regional environmental regulations for electrical \ electronic products.
Controllers
Remove power, disconnect the Controller and remove battery (if fitted). Dispose of Controller in accordance with regional environmental regulations for electrical \ electronic products.
Dispose of batteries in accordance with regional environmental regulations for batteries.
EU WEEE Directive Logo
This symbol indicates the requirements of Directive 2012/19/EU regarding the treatment and disposal of waste from electric and electronic equipment.
Page 60
FLOWMONITOR INSTRUCTION MANUAL
60
www.pulsarmeasurement.com
S U P P O R T @ P U L S A R M E A S U R E M E N T . C O M
Copyright © 2020 Pulsar Measurement Ltd. Registered Address: 1 Chamberlain Square CS, Birmingham B3 3AX Registered No.: 3345604 England & Wales Rev 1.0
Loading...