Pulsar AWO 624 Installation Manual

INSTALLATION MANUAL
ENGLISH
Code: AWO 624
Name: DIN 4/90 enclosure 370x640x90mm
Metal enclosure for: Access Control Systems, IDS….
IM624 Edition: 2 from 31.08.2015
Supercedes edition: 1 from 10.09.2014
1. Application:
Due to its construction, the AWO624 enclosure can be used as an element integrating electrical systems, automation
systems, CCTV, Access Control Systems, IDS, etc. It is dedicated to equipment mounted on a DIN rail (TH35mm). The devices that can be mounted in the enclosure (depending on the configuration) are listed below:
1. Electric fuses of the „S” type
2. Transformers of the following series: TRP, TRZ, TOR
3. Power supplies of the following series:
PS-15xxxx, PS-40xxxx, PS-60xxxx, PS-100xxxx, PS-150xxxx, PS-200xxxx DINxxxx
4. Built-in buffer power supplies of the following series:
PSB-25xxxx, PSB-35xxxx, PSB-50xxxx, PSB-75xxxx, PSB-100xxxx, PSB-155xxxx
 PSBOC25xxxx, PSBOC35xxxx, PSBOC50xxxx, PSBOC75xxxx, PSBOC100xxxx, PSBOC155xxxx
ADOC55xxxx, ADOC155xxx
5. Buffer power supply modules of the following series:
MSRDxxxx
2. Product description
The enclosure is fitted with 4 DIN rails with a length of 330mm, which corresponds to 18 fields of the "S" fuse. Battery space for two 17Ah / 12V batteries. Tamper protection (opening of the housing) included. In the standard version, the housing is screwed with 2 screws from the front. The front of the housing is fitted with an opening for the lock which allows installation of a lock with the same code MR027 or with a different code MR008. The 8mm distance from the wall at the bottom makes the wires easier to connect to the devices mounted in the enclosure.
3. Mounting:
The enclosure is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and
required for a given country) for 230V/AC in and low-voltage installations.
The enclosure should be mounted in confined spaces with normal relative humidity (RH=90% maximum, no
condensation) and temperature range from -10°C up to +40°C.
4. Technical parameters
TECHNICAL PARAMETERS
Battery space
2 x 17Ah/12V
Tamper protection
1x – enclosure opening
TAMPER output load- max
500mA@50Vdc
Enclosure: IP
IP 20
Operation temperature
-10ºC÷40ºC
Relative humidity RH – max.
90 [%]
Internal dimensions
(W x H x D)
370 x 640 x 90
[-/+2] [mm]
Possibility to mount
additional equipment
Lock with the same code MR027
Lock with a different code MR008
2
Finish
Galvanized sheet, thickness: 1,0mm
Corrosion protection
Color: RAL 7035 (grey)
Application
Indoor/
Surface mounted
Net weight
~6.05 [kg]
Gross weight
~6.65 [kg]
Table 1.
Technical parameters of transformers that can be mounted in the housing:
CODE
NAME
C S U
I
U1 or U2 or U3
I1 or I2 or I3
F
t
AWT053
TRP 20/12/14
PC/ABS
UL94 V-0
IP30
20VA
230V/AC
0,12A
12V or 14V
1,6A or 1,4A
T 200mA/250V
130oC
AWT050
TRP 20/16/18
PC/ABS
UL94 V-0
IP30
20VA
230V/AC
0,12A
16V or 18V
1,2A or 1,0A
T 200mA/250V
130oC
AWT268
TRZ 20/16/18
PC/ABS
UL94 V-0
IP43
20VA
230V/AC
0,12A
16V or 18V
1,2A or 1,0A
T 200mA/250V
130oC
AWT150
TRP 40/16/18
PC/ABS
UL94 V-0
IP30
40VA
230V/AC
0,20A
16V or 18V
2,2A or 2,0A
T 315mA/250V
130oC
AWT500
TRP 50/16/18/20
PC/ABS
UL94 V-0
IP30
50VA
230V/AC
0,25A
16V or 18V or 20V
3,0A or 2,8A or 2,5A
T 500mA/250V
130oC
AWT524
TRP 50/17/24/30
PC/ABS
UL94 V-0
IP30
50VA
230V/AC
0,25A
17V or 24V or 30V
2,9A or 2,1A or 1,7A
T 500mA/250V
130oC
AWT800
TRP 80/16/18/20
PC/ABS
UL94 V-0
IP30
80VA
230V/AC
0,4A
16V or 18V or 20V
5,0A or 4,5A or 4,0A
T 630mA/250V
130oC
AWT824
TRP 80/17/24/30
PC/ABS
UL94 V-0
IP30
80VA
230V/AC
0,4A
17V or 24V or 30V
4,7A or 3,3A or 2,7A
T 630mA/250V
130oC
AWT468
TRZ 40/16/18
PC/ABS
UL94 V-0
IP43
40VA
230V/AC
0,20A
16V or 18V
2,2A or 2,0A
T 315mA/250V
130oC
AWT
5161820
TRZ 50/16/18/20
PC/ABS
UL94 V-0
IP43
50VA
230V/AC
0,25A
16V or 18V or 20V
3,0A or 2,8A or 2,5A
T 500mA/250V
130oC
AWT
5172430
TRZ 50/17/24/30
PC/ABS
UL94 V-0
IP43
50VA
230V/AC
0,25A
17V or 24V or 30V
2,9A or 2,1A or 1,7A
T 500mA/250V
130oC
AWT
8161820
TRZ 80/16/18/20
PC/ABS
UL94 V-0
IP43
80VA
230V/AC
0,4A
16V or 18V or 20V
5,0A or 4,5A or 4,0A
T 630mA/250V
130oC
AWT
8172430
TRZ 80/17/24/30
PC/ABS
UL94 V-0
IP43
80VA
230V/AC
0,4A
17V or 24V or 30V
4,7A or 3,3A or 2,7A
T 630mA/250V
130oC
AWT037
TOR 50/16/18/20
-
50VA
230V/AC
0,25A
16V or 18V or 20V
3,0A or 2,8A or 2,5A
T 500mA/250V
130OC
AWT049
TOR 50/17/24/30
-
50VA
230V/AC
0,25A
17V or 24V or 30V
2,9A or 2,1A or 1,7A
T 500mA/250V
130OC
AWT039
TOR 80/16/18/20
-
80VA
230V/AC
0,4A
16V or 18V or 20V
5,0A or 4,5A or 4,0A
T 630mA/250V
130OC
AWT048
TOR 80/17/24/30
-
80VA
230V/AC
0,4A
17V or 24V or 30V
4,7A or 3,3A or 2,7A
T 630mA/250V
130OC
C- Transformer enclosure S - Power U – Supply voltage I - Current draw at nominal load with 230V AC mains U1 or U2 or U3 – Secondary voltage I1 or I2 or I3 – Nominal output current F – F fuse in the transformer primary circuit t- 130oC non-resettable thermal fuse