Pulsafeeder 200-680C User Manual

INSTALLATION OPERATION MAINTENANCE INSTRUCTION
BULLETIN No. 680C
ENGINEERED PUMP OPERATIONS 2883 Brighton Henrietta TL Road P.O. Box 22909 Rochester, New York, 14692-22909 USA
Manufacturers of Quality Pumps, Fax (716) 424-5619 Controls and Systems http://www.pulsa.com
Telephone (716) 292-8000

Table of Contents

How it Works ........................................... 2
Installation Tips ......................................... 4
Hydracone Diaphragm
Figure 2
The HYDRACONE elastomer diaphragm Figure No. 2 isolates product pumped from the plunger and pump mechanism.
Start-Up Inspection ...................................... 6
Operation and Maintenance ............................... 9
Storage Instructions ..................................... 12
Trouble Shooting ....................................... 13
How it Works:
Figure 1
A standard foot mounted motor drives a wormshaft at constant speed. Through wormgear reduction and eccentric, a reciprocating power stroke is transferred to a plunger. The length of
stroke determines pump The forward movement of the capacity and can be adjusted plunger pressurizes the manually to provide pumping hydraulic fluid which expands range from 0-100% of rating. the elastomer HYDRACONE However, this plunger does diaphragm in direct relation to not pump chemicals, but an plunger travel. As diaphragm exceptionally stable oil having expands, chemical is forced
*
excellent lubricating qualities. from reagent head and out This makes a perfect discharge check valve. When pumping medium. plunger starts to return, the
plunger
A special property petroleum oil tradenamed "PULSAlube" is generally used as hydraulic fluid. Continual reference to "oil" as hydraulic medium implies its
general use rather than its use of necessity. Check with your representative or the factory if substitute oils must be used.
Several elastomers are offered including Viton and Hypalon which provide a
*
*
satisfactory chemical resistance for a wide variety of corrosive fluids.
hydraulic pressure is released and HYDRACONE returns to normal shape. This diaphragm return, which is not affected by inlet pressure conditions, draws in new chemical under high suction lift.
*Products of E.I. DuPont
Figure 1.
2
Any leakage past the plunger, Any excess pressure buildup Pressure Relief Valve however slight, is replaced by within the hydraulic chamber the make-up valve which or reagent head due to A separate process relief permits flow of replacement accidental valve closure or valve should be installed in oil from the oil reservoir. line stoppage is relieved the process piping to protect Replacement is automatic through the automatic piping and sensitive process because the oil loss allows hydraulic bypass valve. It equipment. the diaphragm to get out of blows off oil under excess phase with the plunger thus pressure ahead of the plunger Plastic Reagent Head creating a vacuum ahead of back into the oil reservoir thus 3/8" Dia. Piston Design the plunger during the suction terminating the pumping stroke of the pump. The action and protecting the make-up valves are factory pump mechanism. Hydraulic set. bypass valves are factory set
at full design pressure unless specified differently by purchaser.
Figure 2.
Figure 5.
Figure 3. Figure 4. Figure 6.
3
Installation Tips
Check The Shipment
A standard PULSA Series shipment includes the pump, PULSAlube oil, wrenches, instruction and parts list packet and replacement parts if ordered. Unpack carefully, check packing list and make sure all parts are received. Check voltage of electric motor against the service to be used.
NOTE: Most 680 models will
Discharge Pressure:
operate without bolting down. However, it is important to have a solid and level foundation so that a minimum of vibration is evident. Continual vibration can loosen gaskets and pipe connections.
All 680 models are designed for continuous service at the rated discharge pressure. To prevent liquid flow through, it is necessary that discharge pressure be at least 5 psi above suction pressure. When pumping downhill a
3. Check motor alignment back pressure valve should and reagent head and be placed in the discharge valve bolt tightness before line. operation. Follow bolt torque readings carefully.
Locating the 680C Pumps:
PULSA 680C pumps are designed to operated under indoor atmospheric conditions. It is desirable to provide a hood or covering for outdoor service. Alternate oil or external heating must be arranged if ambient temperatures will be below
o o
40 F (4.4 C). Fluid temperatures entering the pump must be 40 F (4.4 C) or
o o
greater. Check with factory if concerned with the suitability of the operating environment.
1. Check level of pump. Shim where necessary.
2. Securely bolt to foundation. Do not distort base.
Flooded Suction Desirable:
Installation will be simpler to operate if the liquid will flow to the pump by gravity. Wherever possible the pump should be located below the level of storage vessel.
4
Piping: shut off valves. This permits susceptible to dirt and other
easy installation of a contaminants and any Pipe size and length are calibration tube for calibration accumulation can cause critical to proper operation of of the pump at start up or any malfunction. Be sure to use a any metering pump. A future date. A tee in the pipeline strainer in the suction restricted discharge or starved discharge piping is a must on line between the suction shut suction condition spells a good installation because it off valve and the pump immediate failure to any permits ease of mounting a suction valve, 100 mesh metering pump installation. A pressure gauge to check screen is preferred. separate brochure entitled discharge pressure at the "Designing a Successful pump and setting the Flush Piping System: Metering Pump Installation" is hydraulic bypass valve during Whether new or old piping is provided to assist Engineers start up and future used, all lines should be responsible for piping system maintenance functions. To flushed with a clean liquid or design. Copies are available prevent strain on the pump air before connecting the upon request (Technical fittings use pipe straps and pump to carry out pipe scale Sheet 304). Inlet piping must braces. Do not allow the or other foreign material. be at least equal in size to weight of the piping to be Make sure flushing liquid is pump inlet connection. supported by a pipe union, the compatible with the chemical
valve fitting or other portion of to be pumped. Figure A shows the preferred the pump head or leaks will piping configuration for a occur. An air leak at a union Metal Reagent Head good metering pump or other fitting in the suction Models: installation. A good piping piping can severely affect installation metering accuracy and is The metal reagent head addresses present and future extremely difficult to detect. In assembly is provided in requirements of the metering assembly of piping, use pipe several alloys. Piping of system. Plan for shut off thread tape or a compound similar alloy should be valves and unions or flanges compatible with the product selected. Dissimilar materials installed on both suction and handled. If rigid piping is used can cause galvanic corrosion. discharge lines. This allows we suggest bolting the pump inspection of the check valves to its foundation. Do not backweld piping to the without draining long runs of valve housings without first pipe. Install a tee in the Use Strainers: removing the valve housings suction and discharge piping from the pump as excessive between the pump and the Pump check valves are heat can damage the reagent
head and other parts. Tie bars must be positioned on the valve housing before welding.
Plastic Reagent Head Models:
Care must be exercised when making connections on plastic reagent head models. Excessive tightening can distort or break the plastic materials. Tubing should be rated for the highest discharge pressure expected. DO NOT USE
METAL PIPING.
5

Start-Up

Final Inspection: Priming Process Head:
Inspection
Every 680C metering pump is tested for correct capacity at maximum pressure capability of the hydraulic bypass valve before shipment. The diaphragm cavity is fully primed and remains so for shipment. For shipping purposes the gear and hydraulic reservoir oil have been removed. Sufficient fresh PULSAlube oil is included with the shipment for refilling the gear and hydraulic reservoirs.
Warning
1. Do not run pump without
oil.
2. Do not remove main gear
box cover while pump is running.
3. Do not run pump with
coupling guard removed.
4. Do not put hands or fingers
in gear box or reservoir when pump is running.
Filling Gear and Oil Reservoirs:
Remove the pump cover and fill both reservoirs with PULSAlube oil to the top of the gear box partition. Do not overfill. PULSAlube oil is compounded to serve as both gear lubricant and hydraulic transfer fluid. Check with factory if substitute oils must be used.
The cover assembly incorporates a free acting diaphragm to allow breathing of the reservoir and at the same time seal the reservoir from the atmosphere. Be sure the diaphragm is properly positioned when replacing the cover so that it will seal on the gear box.
Because of the pump's small 1. Open the suction line and
size and light weight it discharge line shut off
sometimes receives severe valves.
handling during shipment. 2. If the piping system design
Though physical damage may and the storage tank are
not occur, it is always possible such that the product flows
for parts to move slightly in by gravity to the pump, no
adjustment. This situation priming is required. If
might occur with motor or however, the discharge line
pneumatic control alignment. is under pressure, air will
A quick visual check should be trapped in the process
be made to assure that motor head and it will be
and control shafts have not necessary to remove the
shifted severely out of discharge pressure to
alignment or damage could enable the pump to prime
occur from starting the motor. itself.
If unusual vibration should 3. If the pump must handle a
occur after start up realign the suction lift, it may be
motor and coupling. necessary to manually
prime the reagent head.
Start-up: Remove the discharge
valve by unscrewing the Since the hydraulic oil system two tie bar bolts and then is primed at the factory, lifting the valve out. Fill the priming the process system is head with process fluid, or all that should be necessary a compatible liquid then to produce flow. If the replace the valve in the hydraulic system has same position and retighten inadvertently been dumped the tie bar bolts. due to starting up with 4. The pump is now ready for restricted suction or discharge start-up. conditions, repriming 5. Start the pump and procedures under the increase the control setting maintenance section may to full stroke. have to be followed before 6. Make a brief check to pump calibration can begin. assure that the pump is
producing the approximate
flow desired at the full
stroke setting. Calibration
should not be attempted on
any model until it has run at
least one hour to assure
the pump hydraulic and
reagent head systems have
stabilized.
If the pump does not produce the approximate flow desired at the full stroke setting refer to the Trouble Shooting Section for possible causes and refer to Priming Procedure under the Operation and Maintenance Section.
6
To Adjust Flow Rate; Calibration: This is caused by
Figure B.
All pumps are tested on water and valve inefficiencies.
The 680C PULSA pumps are at room temperature with 7 Capacity at atmospheric provided with a micrometer foot flooded head at full rated pressure will be nearly that of knob adjustment for changing pressure. Any curves calculated displacement. As length of stroke while in supplied by Pulsafeeder the discharge pressure operation or idle. NOTE: The would be representative of increases there will be a external auto locking knob this test and can only be used corresponding decrease in must be fully disengaged prior as a guideline. capacity at a rate of to adjustment. When approximately 1% per 100 psi adjustment is complete the All pumps must be calibrated increase. lock will automatically engage under actual operating to prevent drifting of the conditions for the operator to stroke setting. Turn know the proper adjustment adjustment knob clockwise to for particular outputs. A increase flow and typical displacement chart is counterclockwise to decrease shown in Figure C. Note that flow. The adjustment knob is output is linear with respect to read directly in percent of micrometer settings but that stroke length. These increase in discharge indications can be converted pressure decreases output to volumetric or weight units slightly and describes the line by calibration conversion parallel to that at atmospheric charts. pressure.
compression of hydraulic oil
Figure B
7
Figures D and E show two PULSA pumps supplied with typical piping arrangements automatic controls, either for performing pump pneumatic or electronic, are calibration. It is desirable to accompanied by separate calibrate from the suction side instructions on output of the pump so the pump will adjustment and calibration. be operating under actual or comparable discharge conditions.
Check the capacity several times at three different stroke length settings and record them on linear graph paper. For all stable conditions, these points should describe a straight line.
8
Operation and Maintenance
The preceding instructions have assisted you in proper installation and start-up of your 680C pump. The following sections are arranged to assist in maintaining proper pump operation and trouble shooting any problems that might develop during start-up or thereafter.
Accurate records in the early stages of pump operation will reveal the type and amount of maintenance that will be required. A preventative maintenance program based on these records will insure trouble free operation. It is not possible in these instructions to forecast the life of such parts as the diaphragm, check valves and other parts in contact with the product you are handling. Corrosion rates and conditions of operation affect the useful life of these materials so an individual metering pump must be gauged according to particular service conditions.
HYDRACONE Diaphragm 5. Adjust the stroke length Inspection (capacity) to maximum.
6. Remove the reservoir The HYDRACONE cover assembly. diaphragm is an elastomeric 7. Remove the coupling material which stretches on guard. each displacement of the 8. Rotate the motor plunger. It can be damaged coupling until the pump by the following: piston is withdrawn to full
suction stroke (toward
1. Chemical attack. drive motor end).
2. Mechanical damage 9. Loosen the hydraulic
from trash or abrasives. bypass valve screw
3. High temperature located on top of the
(Maximum 180 F, 2.2 C). hydraulic pumphead to
4. Low temperature (below be sure all hydraulic
5. Suction pressure in relieved from behind the
Service conditions will properly dispose of oil determine life of the and product leakage that HYDRACONE and dictate the will occur when replacement schedule. disassembling head and
To Inspect HYDRACONE 11. Remove the inlet check Diaphragm valve to drain reagent
1. Remove all pressure extreme caution if
2. Lock out motor. and wear proper
3. Close the inlet and outlet protective clothing.
4. Break the union or bolts and rinse the head
o o
40 F, 4.4 C). pressure has been excess of 20 psig. diaphragm.
from the piping system. product is hazardous
shut-off valves. 12. Remove reagent head flanges on the piping. in water or a compatible
o o
10. Arrange to catch and
valving.
head and cavity. Use
liquid.
Figure 7. Figure 8. Figure 9.
9
13. Diaphragm can be 3. Connect inlet piping. removed from the 4. With discharge line 8. Add PULSAlube oil to reagent head by applying bypassed around front and rear oil air pressure to one of the process or to drain, start reservoirs to bring oil valve ports while motor and prime reagent level up to top of blocking the other. Be head. partition. sure diaphragm is 5. Set stroke length 9. After pump has run for directed away from adjustment to maximum several hours, again personnel so that it does stroke. check for any last traces not strike the body when 6. If not already lose, of air at the bypass valve. being expelled from the counting turns, loosen head. the hydraulic bypass Check Valve
14. Diaphragms which are valve located at the top
Figure 7, 8, 9 and 10
punctured or show of the hydraulic system evidence of tearing or to atmosphere and any Operating experience on abrasion at the sealing air present will vent back thousands of installations has edge should be into the gearbox oil indicated that many pump replaced. If diaphragm reservoir as the troubles have to do with check shows evidence of automatic make-up valve valves. Problems usually hardening so as to be fills the piston/diaphragm stem from (a) an non-flexible it should be chamber. Air bubbles accumulation of trash replaced. will be evident at the vent between the valve and seat,
hole, top center of pump (b) corrosion which damages
Repriming Hydraulic head in back of return seating surfaces, (c) erosion Systems on HYDRACONE spring. from high velocity flow, or (d) Models 7. When last traces of air normal physical damage after
have been expelled extended service.
1. Reassemble diaphragm retighten the bypass and reagent head, valve the same number When inspecting the valves, tightening all bolts of turns or to a desired separate the assembly and securely and evenly. setting using a pressure examine the components for
2. Reassemble valve gauge in the process wear, damage or housing, valves, seats line. Approximately a 1/2 accumulation of solids. A ball and seat gaskets and turn more after process valve seat should have a take care in inserting pressure setting has sharp 90 edge, free of any
o
gaskets that they are been reached will seat nicks or dents. Hold the ball properly placed. Tighten valve. The valve can be firmly on the seat and securely. set higher if desired but examine against a light. If
do not exceed MAX. light is visible between the two OPERATING then replace the seat and/or PRESSURE indicated on ball. the nameplate.
When reassembling after cleaning or replacement be sure to use new seals.
10
Hydraulic Make-up Valves To adjust the valve to a lower 3. Restricted flow to the
Figure 12
set pressure, turn counter- pump causing the make-
clockwise. up valve to operate. If an Hydraulic make-up valves are inlet strainer is plugged, designed to maintain the To check pressure setting it is or someone closes an correct volume of oil in the necessary to install a gauge in inlet valve thereby hydraulic system between the the discharge line between restricting flow of fluid to piston and the diaphragm. the pump and a shut off valve. the pump, the diaphragm No adjustment or attention is With the pump operating at is then unable to follow required, provided the oil is maximum stroke a gradual movement of the clean and free of moisture closing of the shut off valve plunger. The vacuums and chemical contamination. will cause the bypass valve to created between the Since the valve operates only reach its cracking pressure diaphragm and the occasionally and with very which will be observed on the plunger upset the makeĀ­little movement it is not gauge. When the bypass up valve allowing oil to considered a normal valve is set for maximum replace the vacuum replacement item in a service pump operating pressure condition. This excess schedule. If the valve is (shown on nameplate), oil will be displaced replaced because of cracking pressure is slightly through the hydraulic corrosion or fouling be sure above maximum operating bypass valve on the tape or sealant is used on the pressure so that it does not discharge stroke of the pipe threads to assure an air weep during normal pump plunger. Undersized tight seal. operation. Dead head (restrictive) piping must
dumping pressure can be be avoided (see "Piping" Hydraulic Bypass Valve considerably higher than page 5).
cracking pressure on some The bypass valve is an large piston, fast stroke rate Any unusual condition in the adjustable spring loaded models, so the internal system which prevents free valve. It is designed to protect bypass valve should not be movement of the diaphragm the pump against excessive considered a safety valve for will cause a recirculating hydraulic pressure. The valve protection of the process condition between the makeĀ­is factory set to the setting piping and instrumentation. A up valve and the hydraulic specified on the specification separate process relief valve bypass valve. Continuous oil data sheet or set to allow should be used for this recirculation against the operation at the maximum purpose. bypass valve will eventually pump pressure, indicated on cavitate the hydraulic prime the pump nameplate, without It is unusual for a hydraulic plus introduce unnecessary weeping. bypass valve to operate load conditions within the
during normal pump pump mechanism.
operation. The following
conditions will cause valve
operation:
1. Excessive pressure buildup in the process which the pump is injecting into.
2. A plugged discharge line or someone shutting off a valve in the discharge line while the pump is operating.
11

Lubricating Instructions month interval check the and then start up in

condition of the inlet and accordance with PULSAlube is a custom blend outlet check valves. These instructions in this oil with additives for lubrication items along with oil seal manual. and hydraulic transfer service. inspection should be part of a (For emergency routine service procedure. Long Term requirements, a list of acceptable commercial oils is Oil Capacity For storage longer than 12 available). The diaphragm on months in addition to the the cover of the gear box The standard 680C metering above, the following assembly generally protects pump requires approximately procedures should be the oil from contamination for one quart of PULSAlube oil to followed. extended periods of time. A fill both chambers and prime periodic six month check hydraulic pump head. 1. Every 12 months should be made for oil level PULSAlube oil is available in PULSAlube oil should be and possible contamination. one gallon cans, cartons of six drained from the gearbox
(6) one gallon cans, five and hydraulic reservoir. Under sustained conditions of gallon cans or 55 gallon The gearbox and high humidity or if water is drums. hydraulic reservoir present, the oil can become should be flushed with emulsified and take on a STORAGE INSTRUCTIONS kerosene or petroleum yellowish color. Change the Short Term base solvent, thoroughly oil immediately if this occurs dried out with a rag, and and examine the make-up Storage of PULSA Series then refilled with fresh valve and other parts for pump for up to 12 months PULSAlube oil. corrosion. A suction pump after shipment is considered 2. Every 12 months the similar to a grease gun is short term. Under this motor should be useful for removing oil from condition the recommended connected to a power chambers, or it may be storage procedures are as source and the pump drained from the ports at the follows: operated for a minimum side of each chamber. of one hour. It is not
1. The pump should be necessary to have liquid stored indoors at room in the reagent head temperature in a dry during this operation but environment. the suction and
2. The pump gearbox and discharge ports must be hydraulic reservoir is to open to atmosphere. be completely filled with PULSAlube oil within two After 12 months storage months after date of Pulsafeeder's warranty shipment. cannot cover such items as oil
3. The gearbox and seals, gaskets, piston cups hydraulic reservoir and other items which are should be inspected subject to deterioration with every 3-6 months. age. If the pump has been in Maintain the oil level and storage for longer than 12 assure that no water or months it is recommended condensation is present, that these items be replaced follow Procedure II, Step prior to going into service. A below. Material and labor to
4. It is recommended that recondition or replace this the stroke length of the class of item is the pump be adjusted to its purchaser's responsibility. midpoint and that the For a one year service
To establish a maintenance piston be manually warranty after extended record and routine procedure, cycled through 3-6 storage the refurbishment and check lubricant and drive cycles every 6 months. equipment inspection must be mechanism at three and six 5. Prior to start-up, perform done by a Pulsafeeder month intervals. At the first six a complete inspection serviceman.
12
Maintenance Parts Stock Ordering Parts Trouble Shooting
Pulsafeeder offers a KOPkit When ordering parts always Experience drawn from which uses a group of specify: thousands of installations has recommended spares carried shown that there are three in stock for replacement due 1. Pump model and serial outstanding areas which to normal wear. The Kit number (stamped on contribute to the bulk of covers such items as nameplate). operating problems. First and diaphragm, diaphragm 2. Part number (from parts foremost is installation gaskets if used, inlet and list), or KOPkit number. conditions - improper location discharge valve parts, a 3. Material of reagent head and supply, inadequate or complete set of valve gaskets construction (liquid end restrictive piping to and from and hydraulic pump head parts). pump; unsupported piping; gasket. The KOPkit part lack of strainer in suction number for your pump is Additional Pulsafeeder piping. indicated on the nameplate. Services A sufficient quantity of The second major area is PULSAlube oil should be on FIELD SERVICE - Including check valves. The check hand for periodic oil changes. pump repair or conversion to valve is the heart of any pump
different services is available and sees more severe service at nominal cost. than any other part of the
pump. Opening and closing FACTORY REPAIR - 40 to 140 times per minute, Complete pump the valve not only receives a reconditioning. mechanical hammering but
receives it under high velocity OPERATOR TRAINING corrosive, erosive and SEMINARS - Conducted by sometimes extreme experienced factory trained temperature conditions. service personnel at the Foreign particles, unlevel factory in Rochester, NY or in mounting, defective seals and the field. Field trips are improper torquing all too often available at nominal cost. aggravate even the simplest
application.
The third area is a simple lack
of a routine service policy.
Routine service will catch or
avoid simple operating
problems which can develop
into a crisis if left unattended.
The following is a brief trouble
shooting guide to help identify
and cure any operating
problems you might
experience.
13

Trouble Shooting Chart

Difficulty Probable Cause Remedy
Pump Does Not Start 1. Coupling disconnected Connect and align
2. Faulty power source Check power source
3. Blown fuse, circuit breaker Replace -- Locate overload
4. Broken wire Locate and repair
5. Wired improperly Check diagram
No Delivery 1. Motor not running Check power source. Check wiring diagram
2. Supply tank empty Fill with liquid
3. Lines clogged Clean and flush
4. Closed line valves Open pipeline valves
5. Ball check valves held open with solids Clean -- inspect
6. Vapor lock, cavitation Increase suction pressure
7. Prime lost Reprime, check for leak
8. Strainer clogged Remove and clean. Replace screen if necessary
9. Hydraulic system under-primed Refer to "Repriming Hydraulic System"
10. Check valves installed upside down See check valve illustrations
Low Delivery 1. Motor speed too low Check voltages, hertz, wiring, and terminal
connections. Check nameplate vs. specifications
2. Check valves worn or dirty Clean, replace if damaged
3. Bypass valve opening each stroke Refer to "Hydraulic Bypass Valve"
4. Calibration system error Evaluate and correct
5. Product viscosity too high Lower viscosity by increasing product temperature.
Increase pump size.
6. Product cavitating Increase suction pressure. Cool product as necessary
Delivery Gradually Drops 1. Stroke adjustment creeping Consult factory. Replace worn parts.
2. Check valve leakage Clean, replace if damaged
3. Leak in suction line Locate and correct
4. Fouled bypass or make-up valve Refer to "Operation and Maintenance"
5. Strainer fouled Clean or replace screen
6. Product change Check viscosity
7. Bypass leakage Correct for bypass valve leakage
Delivery Erratic 1. Leak in suction line Locate and correct
2. Product cavitating Increase suction pressure
3. Entrained air or gas in product Consult factory for suggested venting
4. Motor speed erratic Check voltage, hertz
5. Fouled check valves Clean, replace if necessary
14
Difficulty Probable Cause Remedy
Delivery Higher Than Rated 1. Suction pressure higher than Install back pressure valve or consult factory
discharge pressure for piping recommendations
2. Suction piping too small Increase pipe size -- Install PULSAtrol pulsation dampener at pump in suction line
3. Back pressure valvae set too low Increase setting
4. Back pressure valve leaks Repair, clean, or replace
Pump Loses Oil 1. Diaphragm ruptured Replace
2. Leaky oil seal Replace
3. Cover gasket leaks Replace or tighten
4. Pump head gasket leaks Replace -- tighten pump head bolts. Seal with permatex.
5. Gear box overfilled Remove excess oil
Air Continuously 1. Oil in reservoir low Refill to correct level Bleeds From 2. Hydraulic Bypass valve opening Refer to "Hydraulic Bypass Valve" Automated Air Bleed continuously Valve 3. Suction pressure too low Increase pressure
4. Breakdown of oil, temperature high Change oil type, consult factory
Noisy Gearing, Knocking 1. Discharge pressure too high Reduce pressure or discharge pipe size
2. Water hammer Install PULSAtrol
3. Worn bearings Replace
4. Worn gears Replace gears & check for improper hydraulic bypass valve setting
5. End play in worm shaft Consult factory
6. Eccentric or worm gear Tighten or replace assembly
7. Bypass valve set too high Readjust (see "Hydraulic Bypass Valve")
Piping Noisy
1. Pipe size too small Increase size of piping, install PULSAtrol
2. Pipe runs too long Install PULSAtrol in line
3. Surge chambers full of liquid Recharge with air or inert gas, replace diaphragm and recharge
4. No surge chambers used Install PULSAtrols -- pulsation dampeners
Motor Overheats
1. Pump overloaded Check operating conditions against pump design
2. Oil too viscous Consult factory
3. Low voltage Check power supply
4. Loose wire Trace and correct. Check no load amps
15
APPENDIX PULSAFEEDER ACCESSORIES
I. PULSATROL INSTALLATION, OPERATION AND REMOVAL INSTRUCTIONS
The PULSAtrol is a pneumatically charged diaphragm type chamber that continuously stores energy. Used on the inlet it will improve NPSH (Net Positive Suction Head available) characteristics of the suction piping
a
system. On the discharge line it will reduce dangerous peak pressures, eliminate shock waves and if of sufficient volume will reduce pulsating flow to almost linear.
INSTALLATION Figures 13 a and b On both discharge and suction lines it is desirable to mount the PULSAtrol as close to the pump connection as
possible. It can be mounted in any position, but vertical is preferred for ease of charging, draining and servicing. The air chamber is sealed and will not require replenishing regardless of position. A shut off valve should always be used between the piping system and PULSAtrol, also a drain valve should always be installed directly below the PULSAtrol. If the discharge line is open to atmospheric pressure then a back pressure valve should also be incorporated in the system near the PULSAtrol to assure proper operation.
16
OPERATION (Charging the PULSAtrol)
A. Discharge Installation The air side of the PULSAtrol must be precharged to approximately 50 percent of anticipated mean line
pressure before placing on stream. This will permit the diaphragm to move to a neutral position between the chambers when operating.
PROCEDURE Pre Charge Procedure for Discharge Installation
1. Calculate the precharge pressure Mean Line Pressure (PSIG)
+ Atmospheric Pressure Absolute Pressure (PSIA) x Precharge Percentage (80% Max.) Pressure Absolute
- Atmospheric Pressure Precharge Pressure (PSIG)
= Precharge Pressure
2. Isolate PULSAtrol from line.
3. Carefully drain off process fluid by opening a drain valve (see recommend piping arrangement).
4. Apply precharge pressure (additional liquid may drain as diaphragm moves).
5. Close drain valve.
6. Place PULSAtrol in stream.
B. Suction Installation (Flooded Suction) Charge the PULSAtrol with adequate pressure to overcome the static suction head. Start up the pump.
Depress the stem on the charge valve, but only during discharge strokes of the pump, until the gauge indicates pressure pulses. The diaphragm has not centered allowing the PULSAtrol to accumulate liquid while the pump is discharging. If too much air becomes released and the gauge will not indicate pressure pulses then recharge the PULSAtrol and repeat the procedure.
PROCEDURE
Pre Charge Procedure for Suction Installation
1. Isolate accumulator from line.
2. Carefully drain off process fluid by opening a drain valve (see recommended piping arrangement, attached).
3. Apply 5-10 psi precharge pressure (additional liquid may drain as diaphragm moves).
4. Close drain valve.
5. Bleed off all pressure on the PULSAtrol.
6. Open the valve to put PULSAtrol in stream.
7. Push in on the stem of the charging valve during the discharge stroke of the pump and release during the suction stroke.
8. Continue this for about 10 times and observe the compound gauge. As accumulator functions, the needle will go from pressure to vacuum.
C. Suction Installation (Suction Lift)
Consult your PULSA Series representative or the factory for details.
17
II. DIAPHRAGM BACK PRESSURE VALVES
Figure 14 Pulsafeeder diaphragm back pressure valves create a constant back pressure without chatter or cycling. A
TFE diaphragm, offering maximum chemical protection and service life, seals spring and bonnet from product. This diaphragm seals directly on a replaceable seat.
Be sure to install with fluid flow in direction of arrow on valve body. If arrow is missing from plastic valve body, install with flow exiting out center hole of valve body.
Figure 14
18

MAINTENANCE LOG

Pump Model Serial # Gear Ratio Maximum Flow Piston Diameter Maximum Pressure KOPKit All the above information can be obtained from the pump nameplate. Refer to the Pump Specification Data Sheet
for additional information.
Date Serviced By Maintenance Performed
19
CP 9/97 PRINTED IN USA
20
Loading...