A standard foot mounted
motor drives a wormshaft at
constant speed. Through
wormgear reduction and
eccentric, a reciprocating
power stroke is transferred to
a plunger. The length of
stroke determines pumpThe forward movement of the
capacity and can be adjustedplunger pressurizes the
manually to provide pumpinghydraulic fluid which expands
range from 0-100% of rating. the elastomer HYDRACONE
However, this plunger doesdiaphragm in direct relation to
not pump chemicals, but anplunger travel. As diaphragm
exceptionally stable oil havingexpands, chemical is forced
*
excellent lubricating qualities. from reagent head and out
This makes a perfectdischarge check valve. When
pumping medium.plunger starts to return, the
plunger
A special property petroleum oil
tradenamed "PULSAlube" is generally
used as hydraulic fluid. Continual
reference to "oil" as hydraulic medium
implies its
general use rather than its use of
necessity. Check with your
representative or the factory if
substitute oils must be used.
Several elastomers are
offered including Viton and
Hypalon which provide a
*
*
satisfactory chemical
resistance for a wide variety of
corrosive fluids.
hydraulic pressure is released
and HYDRACONE returns to
normal shape. This
diaphragm return, which is not
affected by inlet pressure
conditions, draws in new
chemical under high suction
lift.
*Products of E.I. DuPont
Figure 1.
2
Any leakage past the plunger,Any excess pressure buildupPressure Relief Valve
however slight, is replaced bywithin the hydraulic chamber
the make-up valve whichor reagent head due toA separate process relief
permits flow of replacementaccidental valve closure orvalve should be installed in
oil from the oil reservoir. line stoppage is relievedthe process piping to protect
Replacement is automaticthrough the automaticpiping and sensitive process
because the oil loss allowshydraulic bypass valve. Itequipment.
the diaphragm to get out ofblows off oil under excess
phase with the plunger thuspressure ahead of the plungerPlastic Reagent Head
creating a vacuum ahead ofback into the oil reservoir thus3/8" Dia. Piston Design
the plunger during the suctionterminating the pumping
stroke of the pump. Theaction and protecting the
make-up valves are factorypump mechanism. Hydraulic
set.bypass valves are factory set
at full design pressure unless
specified differently by
purchaser.
Figure 2.
Figure 5.
Figure 3.Figure 4.Figure 6.
3
Installation Tips
Check The Shipment
A standard PULSA Series
shipment includes the pump,
PULSAlube oil, wrenches,
instruction and parts list
packet and replacement parts
if ordered. Unpack carefully,
check packing list and make
sure all parts are received.
Check voltage of electric
motor against the service to
be used.
NOTE: Most 680 models will
Discharge Pressure:
operate without bolting down.
However, it is important to
have a solid and level
foundation so that a minimum
of vibration is evident.
Continual vibration can
loosen gaskets and pipe
connections.
All 680 models are designed
for continuous service at the
rated discharge pressure. To
prevent liquid flow through, it
is necessary that discharge
pressure be at least 5 psi
above suction pressure.
When pumping downhill a
3. Check motor alignmentback pressure valve should
and reagent head andbe placed in the discharge
valve bolt tightness beforeline.
operation. Follow bolt
torque readings carefully.
Locating the 680C Pumps:
PULSA 680C pumps are
designed to operated under
indoor atmospheric
conditions. It is desirable to
provide a hood or covering for
outdoor service. Alternate oil
or external heating must be
arranged if ambient
temperatures will be below
oo
40 F (4.4 C). Fluid
temperatures entering the
pump must be 40 F (4.4 C) or
oo
greater. Check with factory if
concerned with the suitability
of the operating environment.
1. Check level of pump. Shim
where necessary.
2. Securely bolt to foundation.
Do not distort base.
Flooded Suction Desirable:
Installation will be simpler to
operate if the liquid will flow to
the pump by gravity.
Wherever possible the pump
should be located below the
level of storage vessel.
4
Piping: shut off valves. This permits susceptible to dirt and other
easy installation of a contaminants and any
Pipe size and length are calibration tube for calibration accumulation can cause
critical to proper operation of of the pump at start up or any malfunction. Be sure to use a
any metering pump. A future date. A tee in the pipeline strainer in the suction
restricted discharge or starved discharge piping is a must on line between the suction shut
suction condition spells a good installation because it off valve and the pump
immediate failure to any permits ease of mounting a suction valve, 100 mesh
metering pump installation. A pressure gauge to check screen is preferred.
separate brochure entitled discharge pressure at the
"Designing a Successful pump and setting the Flush Piping System:
Metering Pump Installation" is hydraulic bypass valve during Whether new or old piping is
provided to assist Engineers start up and future used, all lines should be
responsible for piping system maintenance functions. To flushed with a clean liquid or
design. Copies are available prevent strain on the pump air before connecting the
upon request (Technical fittings use pipe straps and pump to carry out pipe scale
Sheet 304). Inlet piping must braces. Do not allow the or other foreign material.
be at least equal in size to weight of the piping to be Make sure flushing liquid is
pump inlet connection. supported by a pipe union, the compatible with the chemical
valve fitting or other portion of to be pumped.
Figure A shows the preferred the pump head or leaks will
piping configuration for a occur. An air leak at a union Metal Reagent Head
good metering pump or other fitting in the suction Models:
installation. A good piping piping can severely affect
installation metering accuracy and is The metal reagent head
addresses present and future extremely difficult to detect. In assembly is provided in
requirements of the metering assembly of piping, use pipe several alloys. Piping of
system. Plan for shut off thread tape or a compound similar alloy should be
valves and unions or flanges compatible with the product selected. Dissimilar materials
installed on both suction and handled. If rigid piping is used can cause galvanic corrosion.
discharge lines. This allows we suggest bolting the pump
inspection of the check valves to its foundation. Do not backweld piping to the
without draining long runs of valve housings without first
pipe. Install a tee in the Use Strainers: removing the valve housings
suction and discharge piping from the pump as excessive
between the pump and the Pump check valves are heat can damage the reagent
head and other parts. Tie
bars must be positioned on
the valve housing before
welding.
Plastic Reagent Head
Models:
Care must be exercised when
making connections on plastic
reagent head models.
Excessive tightening can
distort or break the plastic
materials. Tubing should be
rated for the highest discharge
pressure expected. DO NOT USE
METAL PIPING.
5
Start-Up
Final Inspection:Priming Process Head:
Inspection
Every 680C metering pump is
tested for correct capacity at
maximum pressure capability
of the hydraulic bypass valve
before shipment. The
diaphragm cavity is fully
primed and remains so for
shipment. For shipping
purposes the gear and
hydraulic reservoir oil have
been removed. Sufficient
fresh PULSAlube oil is
included with the shipment for
refilling the gear and hydraulic
reservoirs.
Warning
1. Do not run pump without
oil.
2. Do not remove main gear
box cover while pump is
running.
3. Do not run pump with
coupling guard removed.
4. Do not put hands or fingers
in gear box or reservoir
when pump is running.
Filling Gear and Oil
Reservoirs:
Remove the pump cover and
fill both reservoirs with
PULSAlube oil to the top of
the gear box partition. Do not
overfill. PULSAlube oil is
compounded to serve as both
gear lubricant and hydraulic
transfer fluid. Check with
factory if substitute oils must
be used.
The cover assembly
incorporates a free acting
diaphragm to allow breathing
of the reservoir and at the
same time seal the reservoir
from the atmosphere. Be
sure the diaphragm is
properly positioned when
replacing the cover so that it
will seal on the gear box.
Because of the pump's small1. Open the suction line and
size and light weight itdischarge line shut off
sometimes receives severevalves.
handling during shipment. 2. If the piping system design
Though physical damage mayand the storage tank are
not occur, it is always possiblesuch that the product flows
for parts to move slightly inby gravity to the pump, no
adjustment. This situationpriming is required. If
might occur with motor orhowever, the discharge line
pneumatic control alignment. is under pressure, air will
A quick visual check shouldbe trapped in the process
be made to assure that motorhead and it will be
and control shafts have notnecessary to remove the
shifted severely out ofdischarge pressure to
alignment or damage couldenable the pump to prime
occur from starting the motor. itself.
If unusual vibration should3. If the pump must handle a
occur after start up realign thesuction lift, it may be
motor and coupling.necessary to manually
prime the reagent head.
Start-up:Remove the discharge
valve by unscrewing the
Since the hydraulic oil systemtwo tie bar bolts and then
is primed at the factory,lifting the valve out. Fill the
priming the process system ishead with process fluid, or
all that should be necessarya compatible liquid then
to produce flow. If thereplace the valve in the
hydraulic system hassame position and retighten
inadvertently been dumpedthe tie bar bolts.
due to starting up with4. The pump is now ready for
restricted suction or dischargestart-up.
conditions, repriming5. Start the pump and
procedures under theincrease the control setting
maintenance section mayto full stroke.
have to be followed before6. Make a brief check to
pump calibration can begin.assure that the pump is
producing the approximate
flow desired at the full
stroke setting. Calibration
should not be attempted on
any model until it has run at
least one hour to assure
the pump hydraulic and
reagent head systems have
stabilized.
If the pump does not produce
the approximate flow desired
at the full stroke setting refer
to the Trouble Shooting
Section for possible causes
and refer to Priming
Procedure under the
Operation and
Maintenance Section.
6
To Adjust Flow Rate;Calibration:This is caused by
Figure B.
All pumps are tested on waterand valve inefficiencies.
The 680C PULSA pumps areat room temperature with 7Capacity at atmospheric
provided with a micrometerfoot flooded head at full ratedpressure will be nearly that of
knob adjustment for changingpressure. Any curvescalculated displacement. As
length of stroke while insupplied by Pulsafeederthe discharge pressure
operation or idle. NOTE: Thewould be representative ofincreases there will be a
external auto locking knobthis test and can only be usedcorresponding decrease in
must be fully disengaged prioras a guideline.capacity at a rate of
to adjustment. Whenapproximately 1% per 100 psi
adjustment is complete theAll pumps must be calibratedincrease.
lock will automatically engageunder actual operating
to prevent drifting of theconditions for the operator to
stroke setting. Turnknow the proper adjustment
adjustment knob clockwise tofor particular outputs. A
increase flow andtypical displacement chart is
counterclockwise to decreaseshown in Figure C. Note that
flow. The adjustment knob isoutput is linear with respect to
read directly in percent ofmicrometer settings but that
stroke length. Theseincrease in discharge
indications can be convertedpressure decreases output
to volumetric or weight unitsslightly and describes the line
by calibration conversionparallel to that at atmospheric
charts. pressure.
compression of hydraulic oil
Figure B
7
Figures D and E show twoPULSA pumps supplied with
typical piping arrangementsautomatic controls, either
for performing pumppneumatic or electronic, are
calibration. It is desirable toaccompanied by separate
calibrate from the suction sideinstructions on output
of the pump so the pump willadjustment and calibration.
be operating under actual or
comparable discharge
conditions.
Check the capacity several
times at three different stroke
length settings and record
them on linear graph paper.
For all stable conditions,
these points should describe
a straight line.
8
Operation and
Maintenance
The preceding instructions
have assisted you in proper
installation and start-up of
your 680C pump. The
following sections are
arranged to assist in
maintaining proper pump
operation and trouble
shooting any problems that
might develop during start-up
or thereafter.
Accurate records in the early
stages of pump operation will
reveal the type and amount of
maintenance that will be
required. A preventative
maintenance program based
on these records will insure
trouble free operation. It is
not possible in these
instructions to forecast the life
of such parts as the
diaphragm, check valves and
other parts in contact with the
product you are handling.
Corrosion rates and
conditions of operation affect
the useful life of these
materials so an individual
metering pump must be
gauged according to
particular service conditions.
HYDRACONE Diaphragm5.Adjust the stroke length
Inspection(capacity) to maximum.
6.Remove the reservoir
The HYDRACONEcover assembly.
diaphragm is an elastomeric7.Remove the coupling
material which stretches onguard.
each displacement of the8.Rotate the motor
plunger. It can be damagedcoupling until the pump
by the following:piston is withdrawn to full
suction stroke (toward
1.Chemical attack.drive motor end).
2.Mechanical damage9.Loosen the hydraulic
from trash or abrasives.bypass valve screw
3.High temperaturelocated on top of the
(Maximum 180 F, 2.2 C).hydraulic pumphead to
4.Low temperature (belowbe sure all hydraulic
5.Suction pressure inrelieved from behind the
Service conditions willproperly dispose of oil
determine life of theand product leakage that
HYDRACONE and dictate thewill occur when
replacement schedule.disassembling head and
To Inspect HYDRACONE11. Remove the inlet check
Diaphragm valve to drain reagent
1.Remove all pressure extreme caution if
2.Lock out motor.and wear proper
3.Close the inlet and outletprotective clothing.
4.Break the union orbolts and rinse the head
oo
40 F, 4.4 C).pressure has been
excess of 20 psig.diaphragm.
from the piping system.product is hazardous
shut-off valves.12. Remove reagent head
flanges on the piping.in water or a compatible
oo
10. Arrange to catch and
valving.
head and cavity. Use
liquid.
Figure 7. Figure 8.Figure 9.
9
13. Diaphragm can be3.Connect inlet piping.
removed from the4.With discharge line8.Add PULSAlube oil to
reagent head by applyingbypassed aroundfront and rear oil
air pressure to one of theprocess or to drain, startreservoirs to bring oil
valve ports whilemotor and prime reagentlevel up to top of
blocking the other. Behead.partition.
sure diaphragm is5.Set stroke length9.After pump has run for
directed away fromadjustment to maximumseveral hours, again
personnel so that it doesstroke.check for any last traces
not strike the body when6.If not already lose,of air at the bypass valve.
being expelled from thecounting turns, loosen
head.the hydraulic bypassCheck Valve
14. Diaphragms which arevalve located at the top
Figure 7, 8, 9 and 10
punctured or showof the hydraulic system
evidence of tearing orto atmosphere and anyOperating experience on
abrasion at the sealingair present will vent backthousands of installations has
edge should beinto the gearbox oilindicated that many pump
replaced. If diaphragmreservoir as thetroubles have to do with check
shows evidence ofautomatic make-up valvevalves. Problems usually
hardening so as to befills the piston/diaphragmstem from (a) an
non-flexible it should bechamber. Air bubblesaccumulation of trash
replaced.will be evident at the ventbetween the valve and seat,
hole, top center of pump(b) corrosion which damages
Repriming Hydraulichead in back of returnseating surfaces, (c) erosion
Systems on HYDRACONEspring.from high velocity flow, or (d)
Models7.When last traces of airnormal physical damage after
have been expelledextended service.
1.Reassemble diaphragmretighten the bypass
and reagent head,valve the same numberWhen inspecting the valves,
tightening all boltsof turns or to a desiredseparate the assembly and
securely and evenly.setting using a pressureexamine the components for
2.Reassemble valvegauge in the processwear, damage or
housing, valves, seatsline. Approximately a 1/2accumulation of solids. A ball
and seat gaskets andturn more after processvalve seat should have a
take care in insertingpressure setting hassharp 90 edge, free of any
o
gaskets that they arebeen reached will seatnicks or dents. Hold the ball
properly placed. Tightenvalve. The valve can befirmly on the seat and
securely.set higher if desired butexamine against a light. If
do not exceed MAX.light is visible between the two
OPERATINGthen replace the seat and/or
PRESSURE indicated onball.
the nameplate.
When reassembling after
cleaning or replacement be
sure to use new seals.
10
Hydraulic Make-up ValvesTo adjust the valve to a lower3.Restricted flow to the
Figure 12
set pressure, turn counter-pump causing the make-
clockwise. up valve to operate. If an
Hydraulic make-up valves areinlet strainer is plugged,
designed to maintain theTo check pressure setting it isor someone closes an
correct volume of oil in thenecessary to install a gauge ininlet valve thereby
hydraulic system between thethe discharge line betweenrestricting flow of fluid to
piston and the diaphragm. the pump and a shut off valve. the pump, the diaphragm
No adjustment or attention isWith the pump operating atis then unable to follow
required, provided the oil ismaximum stroke a gradualmovement of the
clean and free of moistureclosing of the shut off valveplunger. The vacuums
and chemical contamination. will cause the bypass valve tocreated between the
Since the valve operates onlyreach its cracking pressurediaphragm and the
occasionally and with verywhich will be observed on theplunger upset the makeĀlittle movement it is notgauge. When the bypassup valve allowing oil to
considered a normalvalve is set for maximumreplace the vacuum
replacement item in a servicepump operating pressurecondition. This excess
schedule. If the valve is(shown on nameplate),oil will be displaced
replaced because ofcracking pressure is slightlythrough the hydraulic
corrosion or fouling be sureabove maximum operatingbypass valve on the
tape or sealant is used on thepressure so that it does notdischarge stroke of the
pipe threads to assure an airweep during normal pumpplunger. Undersized
tight seal.operation. Dead head(restrictive) piping must
dumping pressure can bebe avoided (see "Piping"
Hydraulic Bypass Valveconsiderably higher thanpage 5).
cracking pressure on some
The bypass valve is anlarge piston, fast stroke rateAny unusual condition in the
adjustable spring loadedmodels, so the internalsystem which prevents free
valve. It is designed to protectbypass valve should not bemovement of the diaphragm
the pump against excessiveconsidered a safety valve forwill cause a recirculating
hydraulic pressure. The valveprotection of the processcondition between the makeĀis factory set to the settingpiping and instrumentation. Aup valve and the hydraulic
specified on the specificationseparate process relief valvebypass valve. Continuous oil
data sheet or set to allowshould be used for thisrecirculation against the
operation at the maximumpurpose. bypass valve will eventually
pump pressure, indicated oncavitate the hydraulic prime
the pump nameplate, withoutIt is unusual for a hydraulicplus introduce unnecessary
weeping.bypass valve to operateload conditions within the
during normal pumppump mechanism.
operation. The following
conditions will cause valve
operation:
1.Excessive pressure
buildup in the process
which the pump is
injecting into.
2.A plugged discharge line
or someone shutting off
a valve in the discharge
line while the pump is
operating.
11
Lubricating Instructionsmonth interval check theand then start up in
condition of the inlet andaccordance with
PULSAlube is a custom blendoutlet check valves. Theseinstructions in this
oil with additives for lubricationitems along with oil sealmanual.
and hydraulic transfer service. inspection should be part of a
(For emergencyroutine service procedure.Long Term
requirements, a list of
acceptable commercial oils isOil CapacityFor storage longer than 12
available). The diaphragm onmonths in addition to the
the cover of the gear boxThe standard 680C meteringabove, the following
assembly generally protectspump requires approximatelyprocedures should be
the oil from contamination forone quart of PULSAlube oil tofollowed.
extended periods of time. Afill both chambers and prime
periodic six month checkhydraulic pump head. 1.Every 12 months
should be made for oil levelPULSAlube oil is available inPULSAlube oil should be
and possible contamination.one gallon cans, cartons of sixdrained from the gearbox
(6) one gallon cans, fiveand hydraulic reservoir.
Under sustained conditions ofgallon cans or 55 gallonThe gearbox and
high humidity or if water isdrums.hydraulic reservoir
present, the oil can becomeshould be flushed with
emulsified and take on aSTORAGE INSTRUCTIONSkerosene or petroleum
yellowish color. Change theShort Termbase solvent, thoroughly
oil immediately if this occursdried out with a rag, and
and examine the make-upStorage of PULSA Seriesthen refilled with fresh
valve and other parts forpump for up to 12 monthsPULSAlube oil.
corrosion. A suction pumpafter shipment is considered2.Every 12 months the
similar to a grease gun isshort term. Under thismotor should be
useful for removing oil fromcondition the recommendedconnected to a power
chambers, or it may bestorage procedures are assource and the pump
drained from the ports at thefollows:operated for a minimum
side of each chamber.of one hour. It is not
1.The pump should benecessary to have liquid
stored indoors at roomin the reagent head
temperature in a dryduring this operation but
environment.the suction and
2.The pump gearbox anddischarge ports must be
hydraulic reservoir is toopen to atmosphere.
be completely filled with
PULSAlube oil within twoAfter 12 months storage
months after date ofPulsafeeder's warranty
shipment.cannot cover such items as oil
3.The gearbox andseals, gaskets, piston cups
hydraulic reservoirand other items which are
should be inspectedsubject to deterioration with
every 3-6 months. age. If the pump has been in
Maintain the oil level andstorage for longer than 12
assure that no water ormonths it is recommended
condensation is present,that these items be replaced
follow Procedure II, Stepprior to going into service.
A below.Material and labor to
4.It is recommended thatrecondition or replace this
the stroke length of theclass of item is the
pump be adjusted to itspurchaser's responsibility.
midpoint and that theFor a one year service
To establish a maintenancepiston be manuallywarranty after extended
record and routine procedure,cycled through 3-6storage the refurbishment and
check lubricant and drivecycles every 6 months.equipment inspection must be
mechanism at three and six5.Prior to start-up, performdone by a Pulsafeeder
month intervals. At the first sixa complete inspectionserviceman.
12
Maintenance Parts StockOrdering PartsTrouble Shooting
Pulsafeeder offers a KOPkitWhen ordering parts alwaysExperience drawn from
which uses a group ofspecify:thousands of installations has
recommended spares carriedshown that there are three
in stock for replacement due1.Pump model and serialoutstanding areas which
to normal wear. The Kitnumber (stamped oncontribute to the bulk of
covers such items asnameplate).operating problems. First and
diaphragm, diaphragm2.Part number (from partsforemost is installation
gaskets if used, inlet andlist), or KOPkit number.conditions - improper location
discharge valve parts, a3.Material of reagent headand supply, inadequate or
complete set of valve gasketsconstruction (liquid endrestrictive piping to and from
and hydraulic pump headparts).pump; unsupported piping;
gasket. The KOPkit partlack of strainer in suction
number for your pump isAdditional Pulsafeederpiping.
indicated on the nameplate. Services
A sufficient quantity ofThe second major area is
PULSAlube oil should be onFIELD SERVICE - Includingcheck valves. The check
hand for periodic oil changes.pump repair or conversion tovalve is the heart of any pump
different services is availableand sees more severe service
at nominal cost.than any other part of the
pump. Opening and closing
FACTORY REPAIR -40 to 140 times per minute,
Complete pumpthe valve not only receives a
reconditioning.mechanical hammering but
receives it under high velocity
OPERATOR TRAININGcorrosive, erosive and
SEMINARS - Conducted bysometimes extreme
experienced factory trainedtemperature conditions.
service personnel at theForeign particles, unlevel
factory in Rochester, NY or inmounting, defective seals and
the field. Field trips areimproper torquing all too often
available at nominal cost.aggravate even the simplest
application.
The third area is a simple lack
of a routine service policy.
Routine service will catch or
avoid simple operating
problems which can develop
into a crisis if left unattended.
The following is a brief trouble
shooting guide to help identify
and cure any operating
problems you might
experience.
13
Trouble Shooting Chart
DifficultyProbable CauseRemedy
Pump Does Not Start1. Coupling disconnectedConnect and align
4. Fouled bypass or make-up valveRefer to "Operation and Maintenance"
5. Strainer fouledClean or replace screen
6. Product changeCheck viscosity
7. Bypass leakageCorrect for bypass valve leakage
Delivery Erratic1. Leak in suction lineLocate and correct
2. Product cavitatingIncrease suction pressure
3. Entrained air or gas in productConsult factory for suggested venting
4. Motor speed erraticCheck voltage, hertz
5. Fouled check valvesClean, replace if necessary
14
DifficultyProbable CauseRemedy
Delivery Higher
Than Rated1. Suction pressure higher thanInstall back pressure valve or consult factory
discharge pressurefor piping recommendations
2. Suction piping too smallIncrease pipe size -- Install PULSAtrol pulsation
dampener at pump in suction line
3. Back pressure valvae set too lowIncrease setting
4. Back pressure valve leaksRepair, clean, or replace
Pump Loses Oil1. Diaphragm rupturedReplace
2. Leaky oil sealReplace
3. Cover gasket leaksReplace or tighten
4. Pump head gasket leaksReplace -- tighten pump head bolts. Seal with
permatex.
5. Gear box overfilledRemove excess oil
Air Continuously 1. Oil in reservoir lowRefill to correct level
Bleeds From 2. Hydraulic Bypass valve opening Refer to "Hydraulic Bypass Valve"
Automated Air Bleed continuously
Valve3. Suction pressure too lowIncrease pressure
4. Breakdown of oil, temperature highChange oil type, consult factory
Noisy Gearing,
Knocking1. Discharge pressure too highReduce pressure or discharge pipe size
6. Eccentric or worm gearTighten or replace assembly
7. Bypass valve set too highReadjust (see "Hydraulic Bypass Valve")
Piping Noisy
1. Pipe size too smallIncrease size of piping, install PULSAtrol
2. Pipe runs too longInstall PULSAtrol in line
3. Surge chambers full of liquidRecharge with air or inert gas, replace diaphragm
and recharge
4. No surge chambers usedInstall PULSAtrols -- pulsation dampeners
Motor Overheats
1. Pump overloadedCheck operating conditions against pump design
2. Oil too viscousConsult factory
3. Low voltageCheck power supply
4. Loose wireTrace and correct. Check no load amps
15
APPENDIX PULSAFEEDER ACCESSORIES
I.PULSATROL INSTALLATION, OPERATION AND REMOVAL INSTRUCTIONS
The PULSAtrol is a pneumatically charged diaphragm type chamber that continuously stores energy. Used on
the inlet it will improve NPSH (Net Positive Suction Head available) characteristics of the suction piping
a
system. On the discharge line it will reduce dangerous peak pressures, eliminate shock waves and if of
sufficient volume will reduce pulsating flow to almost linear.
INSTALLATION
Figures 13 a and b
On both discharge and suction lines it is desirable to mount the PULSAtrol as close to the pump connection as
possible. It can be mounted in any position, but vertical is preferred for ease of charging, draining and
servicing. The air chamber is sealed and will not require replenishing regardless of position. A shut off valve
should always be used between the piping system and PULSAtrol, also a drain valve should always be
installed directly below the PULSAtrol. If the discharge line is open to atmospheric pressure then a back
pressure valve should also be incorporated in the system near the PULSAtrol to assure proper operation.
16
OPERATION (Charging the PULSAtrol)
A. Discharge Installation
The air side of the PULSAtrol must be precharged to approximately 50 percent of anticipated mean line
pressure before placing on stream. This will permit the diaphragm to move to a neutral position between the
chambers when operating.
PROCEDURE
Pre Charge Procedure for Discharge Installation
1. Calculate the precharge pressure
Mean Line Pressure (PSIG)
3. Carefully drain off process fluid by opening a drain valve (see recommend piping arrangement).
4. Apply precharge pressure (additional liquid may drain as diaphragm moves).
5. Close drain valve.
6. Place PULSAtrol in stream.
B. Suction Installation (Flooded Suction)
Charge the PULSAtrol with adequate pressure to overcome the static suction head. Start up the pump.
Depress the stem on the charge valve, but only during discharge strokes of the pump, until the gauge indicates
pressure pulses. The diaphragm has not centered allowing the PULSAtrol to accumulate liquid while the
pump is discharging. If too much air becomes released and the gauge will not indicate pressure pulses then
recharge the PULSAtrol and repeat the procedure.
PROCEDURE
Pre Charge Procedure for Suction Installation
1. Isolate accumulator from line.
2.Carefully drain off process fluid by opening a drain valve (see recommended piping arrangement,
attached).
3.Apply 5-10 psi precharge pressure (additional liquid may drain as diaphragm moves).
4.Close drain valve.
5.Bleed off all pressure on the PULSAtrol.
6.Open the valve to put PULSAtrol in stream.
7.Push in on the stem of the charging valve during the discharge stroke of the pump and release
during the suction stroke.
8.Continue this for about 10 times and observe the compound gauge. As accumulator functions, the
needle will go from pressure to vacuum.
C. Suction Installation (Suction Lift)
Consult your PULSA Series representative or the factory for details.
17
II. DIAPHRAGM BACK PRESSURE VALVES
Figure 14
Pulsafeeder diaphragm back pressure valves create a constant back pressure without chatter or cycling. A
TFE diaphragm, offering maximum chemical protection and service life, seals spring and bonnet from product.
This diaphragm seals directly on a replaceable seat.
Be sure to install with fluid flow in direction of arrow on valve body. If arrow is missing from plastic valve body,
install with flow exiting out center hole of valve body.
Figure 14
18
MAINTENANCE LOG
Pump ModelSerial #
Gear RatioMaximum Flow
Piston DiameterMaximum Pressure
KOPKit
All the above information can be obtained from the pump nameplate. Refer to the Pump Specification Data Sheet
for additional information.
DateServiced ByMaintenance Performed
19
CP 9/97 PRINTED IN USA
20
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.