Puls Y User Manual

Page 1
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
MOSFET REDUNDANCY MODULE
Except QT40 Series
Only 150mV Voltage Drop at 40A Only 6.2W at 40A 160% (65A) Peak Load Capability Reverse Input Polarity Protection Full Power Between -40°C and +60°C Width only 46mm Rugged Metal Housing Easy Wiring:
Distribution Terminal for Negative Pole Included
3 Year Warranty
1/18
GENERAL DESCRIPTION
The YR40.245 is a redundancy module, which can be used to build redundant systems. The module has one input and one output and can carry nominal currents up to 40A. The output is equipped with a plug-connector, which allows replacing the power supply or the redundancy module while the system is running (hot­swapping)
The novelty of this redundancy module is the utilization of mosfets instead of diodes for the decoupling of the two input channels. This reduces the heat generation and the voltage drop between input and output. The redundancy module does not require an additional auxiliary voltage.
Due to the low power losses, the unit is very slender and only requires 46mm width on the DIN-rail. Large connection terminals allow for a safe and fast installation. The large international approval package makes this unit suitable for nearly every application.
SHORT-FORM DATA
Input voltage DC 12-28V ±30% Input voltage range
8.4-36.4Vdc
Input current 0-40A continuous 40-65A for 5 seconds Output current 0-40A continuous 40-65A for 5 seconds
max. 22A
in overload
*)
or
short circuit mode
Input to output voltage drop
typ. 80mV typ. 150mV
at 20A
at 40A Power losses typ. 120mW at no load typ. 1.8W at 24V, 20A typ. 6.2W at 24V, 40A Temperature range -40°C to +70°C operational Derating 1A/°C +60 to +70°C Dimensions *)
46x124x127mm WxHxD
Weight 340g, 0.75lb
*) Currents at voltages below 6V **) Plus height for plug connector
ORDER NUMBERS
Redundancy YR40.245 12-28V Standard unit Module
Accessory ZM2.WALL Wall/ panel mount bracket ZM12.SIDE Side mount bracket
MARKINGS
IND. CONT. E
Q.
UL 508, pending
UL 60950-1,
pending
Class I Div 2,
pending
IECEx ATEX
II 3G Ex nA IIC T4 Gc
pending
Marine, pending
EMC, LVD
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
Page 2
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
INDEX
Page Page
1.
Intended Use .......................................................3
2. Installation Requirements...................................3
3. Input and Output Characteristics .......................4
4. Power Losses........................................................5
5. Lifetime Expectancy and MTBF...........................6
6. Terminals and Wiring..........................................7
7. Replacing Units while the System is Running....8
8. Functional Diagram.............................................9
9. Front Side and User Elements.............................9
10. EMC....................................................................10
11. Environment ......................................................11
12. Protection Features ...........................................12
13. Safety Features ..................................................12
14. Dielectric Strength............................................ 12
15. Approvals.......................................................... 13
16. Fulfilled Standards............................................ 13
17. Physical Dimensions and Weight ..................... 14
18. Accessories ........................................................ 15
19. Application Notes............................................. 16
19.1. Recommendations for Redundancy.........16
19.2. Inductive and Capacitive Loads................16
19.3. Sidewards Installation Clearances............16
19.4. 1+1 Redundancy up to 40A...................... 17
19.5. N+1 Redundancy, Example with 120A ....17
19.6. Mounting Orientations ............................18
The information presented in this document is believed to be accurate and reliable and may change without notice. No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
TERMINOLOGY AND ABREVIATIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d. To be defined, value or description will follow later.
DC 24V A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
24Vdc A figure with the unit (Vdc) at the end is a momentary figure without any additional
tolerances included.
may A key word indicating flexibility of choice with no implied preference
shall A key word indicating a mandatory requirement
should A key word indicating flexibility of choice with a strongly preferred implementation
1+1 Redundancy Use of two identical power supplies in parallel to provide continued operation following most
failures in a single power supply. The two power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements. E.g. two 10A power supplies are needed to achieve a 10A redundant system.
N+1 Redundancy Use of three or more identical power
supplies in parallel to provide continued operation following most failures in a single power supply. All power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements. E.g.: To achieve a 30A redundant system, four 10A power supplies are needed in a N+1 redundant system.
N+1
Redundancy
1+1
Redundancy
ACDCAC
DC
Load
+
-
IN
OUTINOUT
AC
DC
IN
OUTINOUT
AC
DC
ACDCAC
DC
Load
+
-
IN
OUTINOUT
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
2/18
Page 3
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
1. INTENDED USE
This redundancy module is designed for installation in an enclosure and is intended for the general use such as in industrial control, office, communication, and instrumentation equipment.
This redundancy module can be used with any DIMENSION power supplies except the QT40 series. Do not use this redundancy module in equipment, where malfunction may cause severe personal injury or threaten
human life. This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations.
2. INSTALLATION REQUIREMENTS
This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable parts. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection. Mount the unit on a DIN-rail so that the input terminals are located on the bottom and the output terminals on the
top of the unit. For other mounting orientations see de-rating requirements of chapter 19.6 in this document. This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do
not cover the ventilation grid (e.g. cable conduits) by more than 30%! Keep the following installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated output current. Increase the side clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply). See chapter 19.3 for other allowed clearances when used with the PULS DIMENSION series in a 1+1 redundant configuration.
WARNING
Risk of electrical shock, fire, personal injury or death.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Make sure that the wiring is correct by following all local and national codes.
- Do not open, modify or repair the unit.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
Notes for use in hazardous location areas:
The redundancy module is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2) environments and is evaluated according to EN 60079-0:2009 and EN 60079-15:2010.
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit unless power has been switched off or the area is known to be non-hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the requirements of the EN 60079-15:2010.
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
3/18
Page 4
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
3. INPUT AND OUTPUT CHARACTERISTICS
Number of inputs - 1 Number of outputs - 1 Input voltage nom. DC 12-28V ±30% The input circuitry must meet the SELV requirements
stipulated by IEC/EN/UL 60950-1. Input voltage range - 8.4-36.4Vdc Voltage drop, input to output typ. 80mV at 20A, see Fig. 3-1 typ. 150mV at 40A, see Fig. 3-1 Input current nom. 0-40A continuous nom. 40-65A for 5 seconds max
22A
in overload (voltage < 6V) or short circuit mode Peak input current max. 1500A for max. 1ms per input Output current nom. 40A continuous nom. 40-65A for 5 seconds max.
22A
in overload (voltage < 6V) or short circuit mode Reverse current max. 1mA at 24V, per input, -40°C to +70°C Reverse voltage max. 40Vdc voltage applied to the output, continuously allowed Output capacitance typ. 320μF
Fig. 3-1 Input to output voltage drop when both inputs draw current
(typical 1+1 redundant case, when the output voltages of the two units are equal)
Voltage Drop, typ
0mV
10A 30A
25mV
50mV
75mV
100mV
125mV
150mV
40A20A
A
.
.
.
2
5
°
C
B
.
.
.
6
0
°
C
Output Current
0
175mV
200mV
A
B
V
A
QS40
24V,40A
+
-
I
IN
U
IN
Voltage Drop
UIN=
U
OUT
-
Output
A
V
I
OUT
U
OUT
Variable
Load, 0-40A
YR40.245
Input Output
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
4/18
Page 5
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
4. POWER LOSSES
DC 12V DC 24V
Power losses typ.
1.7W 1.8W at 20A
typ.
6.1W 6.2W
at 40A
Standby power losses typ. 0.06W 0.12W at no output current
Fig. 4-1 Power losses when both inputs draw equal current
Power Losses, typ.
0
0510 30
1
4
5
8W
40
A
2515 20 35
Output Current
A
2
6
B
7
A
.
.
.
2
4
V
,
2
5
°
C
B
.
.
.
2
4
V
,
6
0
°
C
3
V
A
QS40
set to 24V
+
-
I
IN
U
IN
Output
A
V
I
OUT
U
OUT
Variable
Load,
0-40A
YR40.245
Input Output
Losses
UIN=
U
OUT
-*IIN)(
*
I
OUT
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
5/18
Page 6
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
5. LIFETIME EXPECTANCY AND MTBF
Load conditions
Output: 20A Output: 40A
Lifetime expectancy
*)
557 000h
*)
134 000h
*)
at 24V and 40°C
1 576 000h
*)
378 000h
*)
at 24V and 25°C
MTBF
**)
SN 29500, IEC 61709 13 290 000h 6 357 000h at 24V 40°C 22 628 000h 12 238 000h at 24V 25°C MTBF
**)
MIL HDBK 217F 381 000h 278 000h Ground Fixed GF40 (24V and 40°C) 518 000h 366 000h Ground Fixed GF25 (24V and 25°C) 1 816 000h 1 401 000h Ground Benign GB40 (24V and 40°C) 2 486 000h 1 861 000h Ground Benign GB25 (24V and 25°C)
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit has been running for 50 000h or only for 100h.
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
6/18
Page 7
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
6. TERMINALS AND WIRING
Input Output
Type Screw termination
IP20 Finger safe construction. Suitable for field installation.
Pluggable screw termination IP20 Finger safe construction.
Suitable for field installation. Solid wire 0.5-16mm2 0.2-16mm2 Stranded wire 0.5-10mm
2
0.5-10mm2 American Wire Gauge 22-8 AWG 22-6 AWG Max. wire diameter 5.2mm (including ferrule) 5.4mm (including ferrule) Wire stripping length 12mm / 0.5inch 12mm / 0.5inch Screwdriver 3.5x1mm slotted or Pozidrive No 2 5.5x1mm slotted or Pozidrive No 2 Recommended tightening torque 1.2Nm, 10.6lb-in 1.4Nm, 12lb-in
To connect the chassis to ground, use a ring-type terminal (ring cable lug) which is suitable for a M4 screw and connect it to the chassis ground terminal on top of the unit.
Instructions:
a) The external circuitry of all terminals must meet the safety requirements stipulated by IEC/EN/UL 60950-1: SELV. b) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum. c) Follow national installation codes and installation regulations! d) Ensure that all strands of a stranded wire enter the terminal connection! e) Screws of unused terminal compartments should be securely tightened. f) Ferrules are allowed. g) Do not connect or disconnect the wires from the terminals below -25°C (-13°F).
Instructions for inserting and removing the pluggable output terminal
To avoid an accidental disconnection of the output, the plug connector is equipped with a locking system.
Fig. 6-1 Removing the latch mechanism
A
Unlock the red sliders by pushing the tabs down
B
At the same time slide the tabs back
C Pull-out to unplug the connector
To insert the plug connector, reverse the procedure
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
7/18
Page 8
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
7. REPLACING UNITS WHILE THE SYSTEM IS RUNNING
Fig. 7-1 Replacing the power supply or redundancy module while the system is running
L N PE
Power Supply
+ +
- -
DC 24V
Load
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
I I
L N
PE
L N PE
Power Supply
+ +
- -
DC 24V
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
1
2
3a
3b
4
Instructions:
- Switch-off circuit breaker (3a).
- Remove plug (4). The plug prevents the cables from shorting.
- Change power supply (1) or/ and redundancy module (2).
- Put the plug (4) back in.
- Turn-on the circuit breaker (3a).
- The circuit is redundant again.
To replace the right power supply or redundancy module, use the same procedure but turn off circuit breaker (3b).
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
8/18
Page 9
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
8. FUNCTIONAL DIAGRAM
Fig. 8-1 Functional diagram
+
-
+
-
Input
control
Chassis Ground
Output
9. FRONT SIDE AND USER ELEMENTS
Fig. 9-1 Front side
A
Output Terminals (pluggable screw terminals)
B Chassis Ground Terminals
To be connected on the top side of the housing with a ring-type terminal (ring cable lug) which is suitable for a M4 screw. Connection of the chassis is optional and not required since the unit fulfils the requirements according to protection class III.
C
Input Terminals (screw terminals)
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
9/18
Page 10
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
10. EMC
The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any restrictions. A detailed EMC report is available on request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV 15kV
Criterion A
Criterion A Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
2kV 2kV
Criterion A
Criterion A Surge voltage on input
lines
EN 61000-4-5 + Æ -
+/- Æ Chassis ground
500V 1kV
Criterion A
Criterion A
Surge voltage on output lines
EN 61000-4-5 + Æ -
+/- Æ Chassis ground
500V 1kV
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 20V Criterion A Power-frequency magnetic
field *)
EN 61000-4-8 50Hz 30A/m Criterion A
Criterions: A: Redundancy module shows normal operation behavior within the defined limits. Notes: *) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall
elements, electrodynamic microphones, etc.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 limits for DC power ports according
EN 61000-6-3 fulfilled *) Radiated emission EN 55011, EN 55022 Class B This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
*) For information only, not mandatory for EN 61000-6-3. Provided, that power sources connected on the inputs fulfill the requirements too.
Switching frequency
The internal auxiliary supply is generated with a boost converter. The switching frequency varies from 140kHz to 500kHz depending on the input voltage.
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
10/18
Page 11
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
11. ENVIRONMENT
Operational temperature
*)
-40°C to +70°C (-40°F to 158°F) Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation Output de-rating 1A / °C 60-70°C (140°F to 158°F) Humidity
**)
5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock 30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions 2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
see Fig. 11-2 Altitude de-rating 2.5A/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 11-2 Over-voltage category not applicable The concept of the overvoltage category is
used for equipment energized directly from
the low voltage mains (IEC 60664-1 §4.3.3.2.1). Degree of pollution 2 IEC 62103, EN 50178, not conductive LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. **) Do not energize while condensation is present
Fig. 11-1 Output current vs. ambient temp. Fig. 11-2 Output current vs. altitude
Allowed Output Current
0
0 2000 4000
6000m
10
20
30
40
50
65A
n
o
r
m
a
l
m
o
d
e
Altitude
s
h
o
r
t
t
e
r
m
(
<
5
s
)
A
.
.
.
T
a
m
b
<
7
0
°
C
B
.
.
.
T
a
m
b
<
6
0
°
C
C
.
.
.
T
a
m
b
<
5
0
°
C
A
B
C
Allowed Output Current
0
-40 0 20 40
70°C
10
20
30
40
50
65A
60-25
n
o
r
m
a
l
m
o
d
e
s
h
o
r
t
t
e
r
m
(
<
5
s
)
Ambient Temperature
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
11/18
Page 12
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
12. PROTECTION FEATURES
Output over-current protection not included Reverse input polarity
protection
included unit does not start when input voltage is reversed
Degree of protection IP 20 EN/IEC 60529 Penetration protection > 3.6mm e.g. screws, small parts Over-temperature protection not included Input transient protection not included Output transient protection included see EMC section Internal input fuse not included
13. SAFETY FEATURES
Input / output separation no galvanic separation Mosfet between input and output Class of protection III PE (Protective Earth) or chassis connection not required PE resistance < 0.1Ohm between housing and chassis-ground terminal
14. DIELECTRIC STRENGTH
The input and output voltages have the same reference, are floating and have no ohmic connection to ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect input/output terminals together before conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 14-1 Dielectric strength
A
Type test 60s 500Vac
Factory test 5s 500Vac
12/18
Field test 5s 500Vac
Cut-off current setting > 2mA
A
Chassis
In- / Output
-
+
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
Page 13
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
15. APPROVALS
EC Declaration of Conformity
The CE mark indicates conformance with the
- EMC directive 2004/108/EC,
- Low-voltage directive (LVD) 2006/95/EC and
- RoHS directive 2011/65/EU. The CE mark indicates conformance with the
- ATEX directive 94/9/EC (Equipment and protection systems intended for use in potentially explosive atmospheres)
CB Scheme, Information Technology Equipment
IEC 60950-1, pending
UL 508, pending
IND. CONT. EQ.
Listed for use as Industrial Control Equipment; U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01); E-File: E198865
UL 60950-1, pending
Recognized for use as Information Technology Equipment, Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950); E-File: E137006
ANSI / ISA 12.12.01-2007 (Class I Div 2) , pending
LISTED for use in Hazardous Location Class I Div 2 T4 Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01-2007) and Canada (C22.2 No. 213-M1987)
Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc locations. Number of ATEX certificate: EPS 13 ATEX y yyy X The redundancy module must be built-in in an IP54 enclosure.
EN 60079-0, EN 60079-15 ATEX, pending
II 3G Ex nA IIC T4 Gc
Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc locations. Number of IECEx certificate: IECEx EPS 13.yyyyX
IEC 60079-0, IEC 60079-15, pending
IECEx
Marine, pending
GL (Germanischer Lloyd) classified Environmental category: C, EMC1 Marine and offshore applications
16. FULFILLED STANDARDS
EN/IEC 60204-1
Safety of Electrical Equipment of Machines EN/IEC 61131-2 Programmable Controllers EN 50178, IEC 62103 Electronic Equipment in Power Installations
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
13/18
Page 14
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
17. PHYSICAL DIMENSIONS AND WEIGHT
Weight 340g / 0.75lb DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the unit depth (127mm) to calculate the total required installation depth.
Installation clearances See chapter 2
Fig. 17-1 Front view Fig. 17-2 Side view
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
14/18
Page 15
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
18. ACCESSORIES
ZM2.WALL Wall mounting bracket This standard bracket is used to mount the YR40.245 redundancy module onto a flat surface without utilizing a DIN-
Rail.
Fig. 18-1 ZM2.WALL Wall mounting bracket Fig. 18-2 Assembled wall mounting bracket
ZM12.SIDE Side mounting bracket
This bracket is used to mount the YR40.245 redundancy module sideways with or without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the unit have to be detached, so that the steel brackets can
be mounted. For sideway DIN-rail mounting, the removed aluminum brackets and the black plastic slider need to be mounted on
the steel bracket.
Fig. 18-3
ZM12.SIDE Side mounting bracket
Fig. 18-4
Side mounting with DIN-rail brackets
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
15/18
Page 16
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
19. APPLICATION NOTES
19.1. RECOMMENDATIONS FOR REDUNDANCY
Recommendations for the configuration of redundant power systems:
- Use separate input fuses for each power supply.
- Use three-phase power supplies to gain functional safety if one phase fails.
- When single-phase power supplies are utilized connect them to different phases or mains circuits if possible.
- Set the power supply in “Parallel-Use” mode if this feature is available
- It is desirable to set the output voltages of all power supplies to the same value.
19.2. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads.
19.3. SIDEWARDS INSTALLATION CLEARANCES
The minimum clearance recommendations are defined in chapter 2. Normally, the following installation clearance are recommended: 40mm on top, 20mm on the bottom, 5mm on the
left and right sides when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
The clearance between the power supplies and the redundancy module can be reduced to zero under the following conditions:
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
max.
40A
Load
0mm 0mm 0mm
- 1+1 redundancy application with maximum
40A output current.
- The power supplies are from the PULS
DIMENSION series.
- The redundancy module is placed between
the two power supplies or at least on one side of the power supply.
- The output voltage is set to the same level
on both power supplies.
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
16/18
Page 17
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
19.4. 1+1 REDUNDANCY UP TO 40A
1+1 Redundancy up to 40A requires two 40A power supplies and two YR40.245 redundancy modules.
Fig. 19-1 Wiring diagram, 1+1 Redundancy, 40A output current
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
L
N
PE
I
I
24V 40A
Load
Failure
Monitor
Note: Use separate mains systems for each power supply whenever it is possible
19.5. N+1 REDUNDANCY, EXAMPLE WITH 120A
N+1 Redundancy up to 120A requires four 40A power supplies and four YR40.245 redundancy modules.
Fig. 19-2 Wiring diagram, n+1 Redundancy, 120A output current
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
L N
PE
I
I
Failure
Monitor
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
L N PE
+ +
- -
24V, 40A
Parallel Use
Single Use
DC­OK
Power Supply
AC Input
YR40.245
Redundancy
Module
+
-
Input
Output
+
-
24V 120A Load
I I
+
-
Note: Use separate mains systems for each power supply whenever it is possible
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
17/18
Page 18
YR40.245
Y-Series
12-28V, 40A, SINGLE REDUNDANCY MODULE
Oct. 2013 / Rev. 1.0 DS-YR40.245-EN All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
19.6. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current. Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 19-3 Mounting Orientation A
(Standard orientation)
YR40.245
Redundancy
Module
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
10
20
30
40A
50
A
1
Ambient Temperature
Fig. 19-4 Mounting Orientation B
(Upside down)
YR40.245
Redundancy
Module
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
10
20
30
40A
50
A
1
Ambient Temperature
Fig. 19-5 Mounting Orientation C
(Table-top mounting)
Output Current
0
10 20 30 40
60°C
10
30
40A
50
20
A
1
A
2
Ambient Temperature
Fig. 19-6 Mounting Orientation D
(Horizontal cw)
YR40.245
Redundancy
Module
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
10
30
40A
50
20
A
1
A
2
Ambient Temperature
Fig. 19-7 Mounting Orientation E
(Horizontal ccw)
YR40.245
Redundancy
Module
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
10
30
40A
50
20
A
1
A
2
Ambient Temperature
18/18