UZK12.071/ UZB12.071/ UZO12.07
–
U-Series
BATTERY MODULES
A modular concept allows the user to meet individual
application demands and is available with two different
options:
You can order the module with an assembled battery or
you can choose only the bracket allowing the mounting
of individual batteries such as long life or higher current
which achieves a longer buffer-time. The mounting
bracket allows the battery to be assembled just in time
avoiding outdated batteries due to limited shelf life.
■ Two mounting options:
DATA
Battery
Maintenance free valve regulated lead acid battery
Battery voltage nom 12Vdc
Battery capacity nom 7Ah
Self-discharge typ 3%/ month at 20°C
Design life (EUROBAT) 3 to 5 years
Fuse
Blade terminal fuse nom
(257 030 Littelfuse)
Terminals and Wiring
Type Screw terminals
Solid wire nom 2.5-4mm
Stranded wire nom 2.5-4mm
American wire gauge max 12 AWG
Wire stripping length nom 7mm / 0.275”
Tightening torque nom 0.8Nm / 7lb.in
Ambient Temperature
Operation min +0°C to +40°C
Storage and transport min -20°C to +50°C
Dimensions and Weight (UZK12.071)
Width nom 155mm / 6.1“
Height nom 124mm / 4.88“
Depth nom 112mm / 4.41“
Weight max 3200g / 7.06lb
The DIN-rail height when used must be added to the depth
to calculate the total required installation unit depth.
30A ATO
®
2
2
ORDER NUMBERS
UZK12.071
UZO12.07
UZB12.071
Battery module with battery
Mounting kit without battery
Battery replacement
■ Easy access to the terminals and the fuse
■ Heavy duty fuse holder and spare fuse included
DATA
Instructions for Use and Disposal of the Battery
Warranty
3 Year limited warranty except battery as battery is
considered as a service part. Special conditions are part of
our general terms and conditions. Do not store the battery
longer than 9 month without supplementary charge or
performance might change.
MARKINGS
Battery Module 12V, 7Ah
DIN-Rail or panel/wall mounting
Place the battery module outside the cabinet or in the
coolest area when used inside the cabinet.
Use wires no smaller than 2.5mm2 (or 12 AWG) and not
longer than 2x1.5m (cord length 1.5m).
Disconnect battery fuse before working on the battery
or on the DC-UPS.
To replace battery, loosen screw with only one turn and
slide the mounting bracket up.
For storage, installation and operation, the
requirements of the EN 50272-2 as well as other
national regulations must be observed.
Ensure sufficient ventilation for the battery.
Always dispose the batteries through a recycling
organisation. Batteries must be completely discharged
before recycling.
Battery, terminal block,
cables, fuse and fuse
holder are UL-approved
components.
GL
Marine, pending
September 2006 / Rev. 1.0 / DS-UZK12.071-EN / All parameters are specified at 25°C ambient unless otherwise noted.
The information presented in this datasheet is believed to be accurate and reliable and may change without notice.
www.pulspower.com Phone +49 89 9278 0 Germany
1/1
UZK12.071/ UZB12.071/ UZO12.07
–
U-Series
PHYSICAL DIMENSIONS
Fig. 1 Front view Fig. 2 Side view
PANEL/WALL MOUNTING
Fig. 3 Detaching DIN-Rail brackets Fig. 4 Detach slide
Battery Module 12V, 7Ah
Fig. 5 Panel/wall mount
Detach the two aluminium brackets by
removing the two screws with a Torx
screwdriver (Torx 10).
Fig. 6 Rear hole pattern Fig. 7 Bottom hole pattern
Remove the plastic lock mechanism by
using a flat-blade screwdriver to press
the lock downwards while pushing the
plastic slide upwards at the same time.
Detach the plastic slide.
Panel/wall mounting is possible by
using either the four holes on the
rear or the bottom of the unit.
See hole pattern below.
September 2006 / Rev. 1.0 / DS-UZK12.071-EN / All parameters are specified at 25°C ambient unless otherwise noted.
The information presented in this datasheet is believed to be accurate and reliable and may change without notice.
www.pulspower.com Phone +49 89 9278 0 Germany
2/2