A modular concept allows the user to meet individual application demands and is available with two different options: You can order the module with an assembled battery or you can choose only the bracket allowing the mounting of individual batteries such as long life or higher current which achieves a longer buffer-time. The mounting bracket allows the battery to be assembled just in time avoiding outdated batteries due to limited shelf life.
Two mounting options:
DATA
Battery Maintenance free valve regulated lead acid battery Battery voltage nom 12Vdc Battery capacity nom 7Ah Self-discharge typ 3%/ month at 20°C Design life (EUROBAT) 3 to 5 years
Fuse
Blade terminal fuse nom (257 030 Littelfuse)
Terminals and Wiring
Type Screw terminals Solid wire nom 2.5-4mm Stranded wire nom 2.5-4mm American wire gauge max 12 AWG Wire stripping length nom 7mm / 0.275” Tightening torque nom 0.8Nm / 7lb.in
Ambient Temperature Operation min +0°C to +40°C Storage and transport min -20°C to +50°C
Dimensions and Weight (UZK12.071) Width nom 155mm / 6.1“ Height nom 124mm / 4.88“ Depth nom 112mm / 4.41“ Weight max 3200g / 7.06lb
The DIN-rail height when used must be added to the depth to calculate the total required installation unit depth.
30A ATO
®
2
2
ORDER NUMBERS
UZK12.071 UZO12.07 UZB12.071
Battery module with battery Mounting kit without battery Battery replacement
Easy access to the terminals and the fuse
Heavy duty fuse holder and spare fuse included
DATA
Instructions for Use and Disposal of the Battery
Warranty
3 Year limited warranty except battery as battery is considered as a service part. Special conditions are part of our general terms and conditions. Do not store the battery longer than 9 month without supplementary charge or performance might change.
MARKINGS
Battery Module 12V, 7Ah
DIN-Rail or panel/wall mounting
Place the battery module outside the cabinet or in the
coolest area when used inside the cabinet.
Use wires no smaller than 2.5mm2 (or 12 AWG) and not
longer than 2x1.5m (cord length 1.5m).
Disconnect battery fuse before working on the battery
or on the DC-UPS.
To replace battery, loosen screw with only one turn and
slide the mounting bracket up.
For storage, installation and operation, the
requirements of the EN 50272-2 as well as other national regulations must be observed.
Ensure sufficient ventilation for the battery. Always dispose the batteries through a recycling
organisation. Batteries must be completely discharged before recycling.
Battery, terminal block,
cables, fuse and fuse
holder are UL-approved
components.
GL
Marine, pending
September 2006 / Rev. 1.0 / DS-UZK12.071-EN / All parameters are specified at 25°C ambient unless otherwise noted. The information presented in this datasheet is believed to be accurate and reliable and may change without notice.
www.pulspower.com Phone +49 89 9278 0 Germany
1/1
UZK12.071/ UZB12.071/ UZO12.07
U-Series
PHYSICAL DIMENSIONS
Fig. 1 Front view Fig. 2 Side view
PANEL/WALL MOUNTING
Fig. 3 Detaching DIN-Rail brackets Fig. 4 Detach slide
Battery Module 12V, 7Ah
Fig. 5 Panel/wall mount
Detach the two aluminium brackets by removing the two screws with a Torx screwdriver (Torx 10).
Fig. 6 Rear hole pattern Fig. 7 Bottom hole pattern
Remove the plastic lock mechanism by
using a flat-blade screwdriver to press the lock downwards while pushing the plastic slide upwards at the same time. Detach the plastic slide.
Panel/wall mounting is possible by
using either the four holes on the rear or the bottom of the unit.
See hole pattern below.
September 2006 / Rev. 1.0 / DS-UZK12.071-EN / All parameters are specified at 25°C ambient unless otherwise noted. The information presented in this datasheet is believed to be accurate and reliable and may change without notice.
www.pulspower.com Phone +49 89 9278 0 Germany
2/2
Loading...