U–Series
1. GENERAL DESCRIPTION
This uninterruptible power supply (UPS) controller
UBC10.241 with integrated battery is a compact
addition to standard 24V power supplies to bridge
power failures or voltage fluctuations. Expensive
downtimes, long restart cycles and loss of data can
be avoided.
The DC-UPS includes a professional battery
management system which charges and monitors
the battery to achieve the longest battery service life
as well as many diagnostic functions that ensure a
reliable operation of the entire system.
A unique feature of the UBC10.241 is that only one
12V battery is required to buffer the 24V output.
This makes matching batteries unnecessary and
allows a precise battery charging and testing.
The UBC10.241 has one integrated 12V 5Ah high
current VRLA battery, which is easy to change.
In addition to the UBC10.241, a separate UPS
controller (UB10.241) which requires an external 12V
battery is available when a longer buffer time is
required.
UBC10.241, UBC10.241-N1
24V, 10A, DC-UPS
DC-UPS WITH INTEGRATED BATTERY
■ Compact and Easy to Install
■ Longest Buffer Time in Class
■ Easy Battery Access
■ Stable Output Voltage in Buffer Mode
■ Superior Battery Management for Longest Battery Life
■ Temperature Compensated Battery Charging
■ Comprehensive Diagnostics and Monitoring Functions
■ Replace Battery Signal Included
■ Electronically Overload and Short Circuit Protected
■ 50% Power Reserves
■ Selectable Buffer Time Limiter
2. SHORT-FORM DATA
Input voltage nom. 24Vdc
range 22.5-30Vdc
Output current min. 15A Normal mode
min. 10A Buffer mode
Output voltage typ. 0.23V lower
as input voltage
22.25V Buffer mode, 10A
Integrated battery 12V 5Ah VRLA lead acid
Temperature range 0 to 40°C Operational
Dimensions 123x124x119mm WxHxD
Buffer time typ. 16’15” At 5A load
typ. 6’15” At 10A load
Typical setup of a DC-UPS system with the UBC10.241:
AC
24V
Power
Supply
e.g.:
Dimension
24V
DC-UPS
UBC10.241
Normal mode
DC
24V
Load
e.g.: PLC
3. ORDER NUMBERS
DC-UPS
UBC10.241-N1
Accessories UZB12.051
May. 2008 / Rev. 1.1 DS-UBC10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
UBC10.241
Standard unit
Battery not assembled
Battery 12V 5Ah
www.pulspower.com Phone +49 89 9278 0 Germany
4. MARKINGS
IND. CONT. E
UL 508
CUS
182790
GL
Class I Div 2
EMC, LVD
UL 60950-1
R
Marine
1/23